air-diffusion flowbar - swegon

36
KEY FEATURES High capacity single slot diffuser available in five slot widths of 25mm, 38mm, 51mm, 63mm and 76mm Surface mounted and plaster frame border frames available Choice of HT (High Throw) series horizontal or JT (Jet Throw) series vertical air patterns Curved Sections Ceiling or Sidewall Applications Modular or Continuous Lengths Mitred Corner Pieces Angled End Sections Adjustable Discharge Pattern Concealed Fixing Matching Plenum Boxes AIR-DIFFUSION FLOWBAR Architectural High-Capacity Linear Slot Diffuser

Upload: others

Post on 24-Feb-2022

11 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: AIR-DIFFUSION FLOWBAR - Swegon

KEY FEATURES ○ High capacity single slot diffuser available in five slot widths of 25mm, 38mm, 51mm, 63mm and 76mm

○ Surface mounted and plaster frame border frames available

○ Choice of HT (High Throw) series horizontal or JT (Jet Throw) series vertical air patterns

○ Curved Sections

○ Ceiling or Sidewall Applications

○ Modular or Continuous Lengths

○ Mitred Corner Pieces

○ Angled End Sections

○ Adjustable Discharge Pattern

○ Concealed Fixing

○ Matching Plenum Boxes

AIR-DIFFUSION FLOWBARArchitectural High-Capacity Linear Slot Diffuser

Page 2: AIR-DIFFUSION FLOWBAR - Swegon

FLOWBAR

2Swegon reserves the right to alter specifications. 200930 - LNNN00394 (1.5)

Introduction FlowBar is an architecturally designed high capacity linear slot diffuser. It is designed to combine a high air handling capacity with maximum flexibility and is suitable for either ceiling or sidewall applications. The flexibility of the system can blend into a design or provide contrast with its striking but simple design.

FlowBar is a flexible system that can provide straight lines or curves to blend with other architectural elements and enhance the overall concept of the project.

ContentsIntroduction ��������������������������������������������������������2

Specification ���������������������������������������������������������3High Throw Series (HT) ............................................... 3

Jet Throw Series (JT) ................................................... 3

Air Patterns�����������������������������������������������������������4

Flange Styles ��������������������������������������������������������5

Curved Sections ���������������������������������������������������6

Corner Sections ����������������������������������������������������7

Application Photos ����������������������������������������������8

Performance Data ���������������������������������������������14Continuous Slot Plenum High Throw (HT) ................ 14

FlowBar with Swegon Plenum - High Throw (HT) ...... 15

Continuous Slot Plenum Jet Throw (JT) ..................... 19

FlowBar with Swegon Plenum - Jet Throw (JT) .......... 20

Standard Fixing Details �������������������������������������24

Dimensions ��������������������������������������������������������26High Throw (HT) Dimensions ..................................... 26

Jet Throw (JT) Dimensions ......................................... 27

Slot Run Dimensions ................................................. 27

End Border Configurations ........................................ 28

Standard Installation Details ����������������������������29Installation Details - HT and JT ................................. 29

Installation Details - JT only ....................................... 31

Diffuser Ordering Key ���������������������������������������32

Plenum Boxes �����������������������������������������������������33Specifications ............................................................ 33

Pressure Drops & Sound Rating ................................. 34

Plenum Box Dimensions ............................................ 35

Plenum Accessories ................................................... 36

Plenum Ordering Key ����������������������������������������32

Page 3: AIR-DIFFUSION FLOWBAR - Swegon

3200930 - LNNN00394 (1.5) Swegon reserves the right to alter specifications.

FLOWBAR

SpecificationHigh Throw Series (HT)

• The High Throw series is primarily designed for ceiling applications and allows the air diffuser to become inconspicuous, whilst fully integrating into the ceiling system.

• The FlowBar systems satisfy both architectural and engineering requirements for designing an air distribu-tion system that will maintain optimum room air conditions whilst being efficient yet inconspicuous.

• Integral pattern controllers are 600mm in length allowing the airstream to be directed left and right for horizontal and vertical airflow.

• Standard slot sizes are 25mm, 38mm, 51mm, 63mm and 76mm with single section lengths available up to 2400mm.

• Frame styles 66 (surface mounted), 22 and 55 (plaster frame border) and 11 flangeless are available as standard.

• Factory engineered plenum boxes are supplied to ensure a trouble free installation and to ensure published performance data is met.

HT Configurations• FL-10-HT / 25mm Slot

• FL-15-HT / 38mm Slot

• FL-20-HT / 51mm Slot

• FL-25-HT / 63mm Slot

• FL-30-HT / 76mm Slot

Jet Throw Series (JT)

• The Jet Throw series has pattern flow controllers to allow the airstream to be jetted in a horizontal direction (sidewall mounted) whilst fully integrating into the wall system.

• The FlowBar systems satisfy both architectural and engineering requirements for designing an air distribu-tion system that will maintain optimum room air conditions whilst being an integral component of the architectural concept of the project.

• Integral pattern controllers 600mm in length allow the airstream to be directed vertically left and right (ceiling application) and up and down (sidewall application) at a 45˚ angle.

• Jet Throw pattern controllers allow extended throws in typical high bay applications for heated and/or cooled air.

• Jet Throw pattern controllers are useful along perim-eter walls where heated air can be directed downward.

• Standard slot sizes are 25mm, 38mm, 51mm, 63mm and 76mm with single section lengths available up to 2400mm.

• Frame styles 66 (surface mounted), 22 and 55 (plaster frames) and 11, flangeless are available as standard.

• Factory engineered plenum boxes are supplied to ensure a trouble free installation and to ensure published performance data is met.

JT Configurations• FL-10-JT / 25mm Slot

• FL-15-JT / 38mm Slot

• FL-20-JT / 51mm Slot

• FL-25-JT / 63mm Slot

• FL-30-JT / 76mm Slot

Page 4: AIR-DIFFUSION FLOWBAR - Swegon

FLOWBAR

4Swegon reserves the right to alter specifications. 200930 - LNNN00394 (1.5)

Air Patterns

High Throw (HT)

Horizontal Left Horizontal Right Vertical

Jet Throw (JT)

Horizontal Upward Downward

Page 5: AIR-DIFFUSION FLOWBAR - Swegon

5200930 - LNNN00394 (1.5) Swegon reserves the right to alter specifications.

FLOWBAR

Flange Styles

Type 66 Type 55

Type 22 Type 11

Page 6: AIR-DIFFUSION FLOWBAR - Swegon

FLOWBAR

6Swegon reserves the right to alter specifications. 200930 - LNNN00394 (1.5)

Key

Curved Supply

• Curving is only possible with the HT model using border types 11/22/66.

• Please contact our technical team to discuss curved FlowBar in more detail including any special applica-tions not covered in this product sheet.

B = Overall Width T = Overall Length C = Overall Arc Length L = Slot Width

Curved Sections

Minimum Curve Radius

HT High Throw - Border 22

Slot Width Min Radius (mm)

FL10 25 1700

FL15 38 1700

FL20 51 45000

HT High Throw - Border 11

Slot Width Min Radius (mm)

FL10 25 800

FL15 38 1200

FL20 51 2100

HT High Throw - Border 66

Slot Width Min Radius (mm)

FL10 25 800

FL15 38 1200

FL20 51 2100

Page 7: AIR-DIFFUSION FLOWBAR - Swegon

7200930 - LNNN00394 (1.5) Swegon reserves the right to alter specifications.

FLOWBAR

Slot/Style Width T B

Border 66 25 200 95

Border 22 25 200 107

Border 55 25 200 70

Border 11 25 200 70

Border 66 38 200 121

Border 22 38 200 133

Border 55 38 200 95

Border 11 38 200 95

Border 66 51 200 146

Border 22 51 200 158

Border 55 51 200 121

Border 11 51 200 121

Border 66 63 300 172

Border 22 63 300 172

Border 55 63 300 146

Border 11 63 300 146

Border 66 76 300 197

Border 22 76 300 197

Border 55 76 300 172

Border 11 76 300 172

Corner Sections90˚ Flat Corner Multidirection Supply

* Specify Angle

1

1

2

2

3

3

4

4

5

5

6

6

A A

B B

C C

D D

Comments:Rev:

Drawn By: M.Bishop

Approved By:

.Client:

Flow Bar Diffuser

.

Drawing No:

Date:

Date:

By: Date:

15/05/18Date:

Created using drawing template RAM-F-027 Issue E 12/16

Checked By:

Sheet

RevDrawing No: All dimensions in mm. Do NOT scale from drawing. If in doubt ASK!

The information disclosed herein was originated by and is the property of Swegon Air Management Limited (SAML). SAML reserves all patent, proprietary,design, use, sale, manufacturing and reproduction rights thereto. This does not apply to any vendor parts.

Sheet Rev

Internal & External Flow Bar Sections

Product:

Project:

Description:

A3Third AngleProjection

© Swegon Air Management LimitedStourbridge Road, Bridgnorth, Shropshire

WV15 5BB

Tel: +44 (0)1746 761921Fax: +44 (0)1746 766450

www.swegonair.co.uk

Notes:-

All SIZES ARE TAKEN FROMFACE OF DIFFUSER

W Clarke 15/05/18

6

27

3

G Mansell 15/05/18

T

T

T

T

FACE OF FLOWBAR

FACE OF FLOWBAR

INTERNAL

EXTERNAL

1

1

2

2

3

3

4

4

5

5

6

6

A A

B B

C C

D D

Comments:Rev:

Drawn By: M.Bishop

Approved By:

.Client:

Flow Bar Diffuser

.

Drawing No:

Date:

Date:

By: Date:

15/05/18Date:

Created using drawing template RAM-F-027 Issue E 12/16

Checked By:

Sheet

RevDrawing No: All dimensions in mm. Do NOT scale from drawing. If in doubt ASK!

The information disclosed herein was originated by and is the property of Swegon Air Management Limited (SAML). SAML reserves all patent, proprietary,design, use, sale, manufacturing and reproduction rights thereto. This does not apply to any vendor parts.

Sheet Rev

Internal & External Flow Bar Sections

Product:

Project:

Description:

A3Third AngleProjection

© Swegon Air Management LimitedStourbridge Road, Bridgnorth, Shropshire

WV15 5BB

Tel: +44 (0)1746 761921Fax: +44 (0)1746 766450

www.swegonair.co.uk

Notes:-

All SIZES ARE TAKEN FROMFACE OF DIFFUSER

W Clarke 15/05/18

6

27

3

G Mansell 15/05/18

T

T

T

T

FACE OF FLOWBAR

FACE OF FLOWBAR

INTERNAL

EXTERNAL

Internal Corner

External Corner

Page 8: AIR-DIFFUSION FLOWBAR - Swegon

FLOWBAR

8Swegon reserves the right to alter specifications. 200930 - LNNN00394 (1.5)

Application Photos

Page 9: AIR-DIFFUSION FLOWBAR - Swegon

9200930 - LNNN00394 (1.5) Swegon reserves the right to alter specifications.

FLOWBAR

Page 10: AIR-DIFFUSION FLOWBAR - Swegon

FLOWBAR

10Swegon reserves the right to alter specifications. 200930 - LNNN00394 (1.5)

Page 11: AIR-DIFFUSION FLOWBAR - Swegon

11200930 - LNNN00394 (1.5) Swegon reserves the right to alter specifications.

FLOWBAR

Page 12: AIR-DIFFUSION FLOWBAR - Swegon

FLOWBAR

12Swegon reserves the right to alter specifications. 200930 - LNNN00394 (1.5)

Performance Data Continuous Slot Plenum High Throw (HT) Data based on active section 1200 long

25mm Slot Width

Air Flow, l/s-m 36 58 79 101 122 144 165

Static Pressure, Pa 7 18 34 55 81 112 148

NC (Noise Criteria) <10 16 26 33 39 44 49

Throw, m 1.5 - 2.5 - 4.3 2.8 - 4 - 5.5 3.8 - 4.5 - 6.5 4.3 - 5.3 - 7.3 4.5 - 5.8 - 8.3 5.3 - 6 - 8.8 5.5 - 6.8 - 9.5

FL-10

38mm Slot Width

Air Flow, l/s-m 43 65 86 108 129 151 173

Static Pressure, Pa 8 18 32 51 73 99 129

NC (Noise Criteria) <10 14 24 31 37 42 48

Throw, m 1.8 - 3 - 5 3 - 4.3 - 5.8 4 - 5 - 6.8 4.3 - 5.5 - 7.5 5 - 5.8 - 8.3 5.3 - 6.5 - 8.8 5.5 - 6.8 - 9.8

FL-15

51mm Slot Width

Air Flow, l/s-m 43 72 101 129 158 187 216

Static Pressure, Pa 5 14 28 46 68 95 127

NC (Noise Criteria) <10 11 22 30 36 41 46

Throw, m 1.5 - 2.8 - 5 2.8 - 4.3 - 6 4 - 5.3 - 7.3 5 - 5.8 - 8.3 5.3 - 6.5 - 9.3 5.8 - 7 - 10 6 - 7.5 - 10.8

FL-20

63mm Slot Width

Air Flow, l/s-m 43 79 115 151 187 223 259

Static Pressure, Pa 3 10 22 38 58 82 110

NC (Noise Criteria) <10 11 23 31 38 43 48

Throw, m 1.3 - 2.5 - 5 3 - 4.5 - 6.5 4.3 - 5.5 - 8 5.3 - 6.5 - 8.8 5.8 - 7 - 10 6.5 - 7.5 - 11 6.8 - 8.3 - 12.8

FL-25

76mm Slot Width

Air Flow, l/s-m 43 86 129 173 216 259 302

Static Pressure, Pa 3 11 25 44 69 99 135

NC (Noise Criteria) <10 <10 18 27 34 40 45

Throw, m 1 - 2.3 - 4.5 3 - 4.5 - 6.8 4.5 - 5.8 - 8.3 5.5 - 6.8 - 9.8 6 - 7.5 - 10.8 6.8 - 8.3 - 12 7.3 - 8.8 - 12.8

FL-30

Length, mm 600 1200 1800 2400 3000

Supply -3 0 +2 +3 +5

Return 0 +3 +5 +6 +8

Table A� NC Correction for Length

Length, mm 600 1200 2400 3000 3600

Throw Correction 0.72 1 1.5 1.7 1.8

Table B� Correction Multiplier for Length

• Pressures are given in Pascal (Pa).

• Pressure loss data assumes a duct velocity is less than 4m/sec in the inlet duct.

• Isothermal throw values are given for terminal velocities of 0.8, 0.5 and 0.3m/sec respectively.

• Throw data is based on 1200mm active section. For a 600mm section the throw values are 0.72 times those shown. For a 3000mm continuous length, the throw values are 1.7 times those shown and 1.8 for 3600mm units

• Each NC value represents the noise criteria curve which will not be exceeded by the sound pressure in any of the octave bands, 2nd through 7th, with a

room absorption of 10dB, re 10-12 watts, for a 1200mm section. (See Table A for other lengths).

• For supply units used as a return, add 3 NC

• The tests were conducted with no Plenum effect for pressure or sound

• Throw values for High Throw units are based on a 1-way discharge from the slot

• Throws listed are for the 1-way air pattern. For divided airflow, select the airflow in each direction according to the number of slots aimed in that direction, with the total airflow apportioned between slot

Page 13: AIR-DIFFUSION FLOWBAR - Swegon

13200930 - LNNN00394 (1.5) Swegon reserves the right to alter specifications.

FLOWBAR

25mm Slot Width

Length 600mm

Air Flow, l/s 12 24 35 47 59 71 83

Total Pressure, Pa 2 8 18 32 50 72 98

Static Pressure, Pa 2 7 16 28 44 63 86

NC (Noise Criteria) <10 <10 <10 20 28 35 40

Throw, m 0.3 - 0.5 - 1.8 1 - 1.8 - 3 1.8 - 2.8 - 3.8 2.5 - 3 - 4.3 2.8 - 3.3 - 5 3 - 3.8 - 5.5 3.3 - 4 - 5.8

Length 1200mm

Air Flow, l/s 19 38 57 76 94 113 132

Total Pressure, Pa 2 7 16 28 44 64 87

Static Pressure, Pa 1 4 10 18 28 40 55

NC (Noise Criteria) <10 <10 <10 16 24 31 37

Throw, m 0.3 - 0.5 - 1.8 1 - 1.8 - 4 1.8 - 3 - 5 2.8 - 4 - 5.5 3.3 - 4.3 - 6 4 - 5 - 6.8 4.3 - 5.3 - 7.3

Length 1500mm

Air Flow, l/s 24 47 71 94 118 142 165

Total Pressure, Pa 2 9 19 34 53 77 104

Static Pressure, Pa 1 4 10 18 28 40 55

NC (Noise Criteria) <10 <10 <10 18 26 33 38

Throw, m 0.3 - 0.5 - 2.3 1 - 2.3 - 4.3 2.3 - 3.3 - 5.5 3 - 4.3 - 6 3.8 - 5 - 7 4.3 - 5.5 - 7.5 5 - 5.8 - 8.3

FL-10 with 150mm inlet

38mm Slot Width

Length 600mm

Air Flow, l/s 19 33 47 61 76 90 104

Total Pressure, Pa 4 13 26 45 68 96 128

Static Pressure, Pa 4 11 22 38 57 81 109

NC (Noise Criteria) <10 <10 16 25 33 40 46

Throw, m 0.5 - 1.5 -2.8 1.5 - 2.5 - 3.8 2.5 - 3 - 4.3 2.8 - 3.8 - 5 3.3 - 4 - 5.5 3.3 - 4.3 - 6 3.8 - 4.5 - 6.5

Length 1200mm

Air Flow, l/s 38 57 76 94 113 132 151

Total Pressure, Pa 6 14 25 39 56 76 99

Static Pressure, Pa 4 8 14 22 32 44 57

NC (Noise Criteria) <10 <10 12 20 27 33 38

Throw, m 1 - 1.8 - 4 1.8 - 3 - 5 2.8 - 4 - 5.5 3.3 - 4.3 - 6 4 - 5 - 6.8 4.3 - 5.3 - 7.3 4.5 - 5.5 - 8

Length 1500mm

Air Flow, l/s 42 66 90 113 137 160 184

Total Pressure, Pa 6 15 28 44 64 88 116

Static Pressure, Pa 3 7 13 21 30 42 55

NC (Noise Criteria) <10 <10 12 20 27 33 39

Throw, m 1 - 1.8 - 4 1.8 - 3 - 5.3 2.8 - 4.3 - 6 3.3 - 5 - 6.8 4.3 - 5.3 - 7.3 4.5 - 5.8 - 8.3 5 - 6 - 8.5

FL-15 with 150mm inlet

51mm Slot Width

Length 600mm

Air Flow, l/s 24 40 57 73 90 106 123

Total Pressure, Pa 4 11 22 37 56 78 104

Static Pressure, Pa 4 10 20 34 51 71 95

NC (Noise Criteria) <10 <10 12 21 28 35 40

Throw, m 0.5 - 1.5 - 3 1.8 - 2.8 - 4 2.5 - 3.3 - 5 3 - 4 - 5.5 3.3 - 4.3 - 6 3.8 - 4.5 - 6.8 4 - 5 - 7

Length 1200mm

Air Flow, l/s 42 71 99 127 156 184 212

Total Pressure, Pa 4 11 21 35 52 73 97

Static Pressure, Pa 3 8 16 26 38 54 71

NC (Noise Criteria) <10 <10 20 29 36 42 48

Throw, m 1 - 1.8 - 4 2.3 - 3.3 - 5.5 3 - 4.5 - 6.5 4 - 5.3 - 7.3 4.5 - 5.5 - 8 5 - 6 - 8.5 5.5 - 6.8 - 9.5

Length 1500mm

Air Flow, l/s 47 78 109 139 170 201 231

Total Pressure, Pa 4 10 19 31 46 64 85

Static Pressure, Pa 2 6 12 20 29 41 54

NC (Noise Criteria) <10 <10 19 28 36 42 47

Throw, m 0.5 - 1.5 - 4 1.8 - 3 - 5.5 3 - 4.5 - 6.8 4 - 5.3 - 7.5 4.5 - 5.8 - 8.3 5.3 - 6.5 - 9.3 5.5 - 7 - 9.8

FL-20 with 200mm inlet

FlowBar with Swegon Plenum - High Throw (HT)

Page 14: AIR-DIFFUSION FLOWBAR - Swegon

FLOWBAR

14Swegon reserves the right to alter specifications. 200930 - LNNN00394 (1.5)

25mm Slot Width

Length 600mm

Air Flow, l/s 24 35 47 59 71 83 94

Total Pressure, Pa 7 16 29 46 66 90 117

Static Pressure, Pa 7 16 28 44 63 86 112

NC (Noise Criteria) <10 <10 19 27 34 40 44

Throw, m 1 - 1.8 - 3 1.8 - 2.8 - 3.8 2.5 - 3 - 4.3 2.8 - 3.3 - 5 3 - 3.8 - 5.5 3.3 - 4 - 5.8 3.8 - 4.3 - 6

Length 1200mm

Air Flow, l/s 33 52 71 90 109 127 146

Total Pressure, Pa 4 10 19 30 44 60 80

Static Pressure, Pa 3 8 16 25 37 51 67

NC (Noise Criteria) <10 <10 13 22 29 35 40

Throw, m 0.5 - 1.5 - 3.3 1.8 - 2.8 - 4.5 2.5 - 3.8 - 5.5 3 - 4.3 - 6 3.8 - 4.5 - 6.8 4.3 - 5.3 - 7.3 4.5 - 5.5 - 7.5

Length 1500mm

Air Flow, l/s 38 61 85 109 132 156 179

Total Pressure, Pa 4 10 19 30 45 63 83

Static Pressure, Pa 3 8 15 24 35 49 65

NC (Noise Criteria) <10 <10 13 22 29 35 40

Throw, m 0.5 - 1.5 - 3.8 1.8 - 2.8 - 5 2.8 - 4 - 5.8 3.3 - 4.5 - 6.8 4.3 - 5.3 - 7.3 4.5 - 5.5 - 8 5 - 6 - 8.5

FL-10 with 200mm inlet

38mm Slot Width

Length 600mm

Air Flow, l/s 19 33 47 61 76 90 104

Total Pressure, Pa 4 12 24 40 61 86 115

Static Pressure, Pa 4 11 22 38 57 81 109

NC (Noise Criteria) <10 <10 14 24 32 38 45

Throw, m 0.5 - 1.5 -2.8 1.5 - 2.5 - 3.8 2.5 - 3 - 4.3 2.8 - 3.8 - 5 3.3 - 4 - 5.5 3.3 - 4.3 - 6 3.8 - 4.5 - 6.5

Length 1200mm

Air Flow, l/s 38 61 85 109 132 156 179

Total Pressure, Pa 4 12 22 36 54 75 99

Static Pressure, Pa 4 9 18 30 44 61 81

NC (Noise Criteria) <10 <10 15 24 32 38 43

Throw, m 1 - 1.8 - 4 2.3 - 3 - 5 3 - 4.3 - 5.8 3.8 - 4.5 - 6.8 4.3 - 5.5 - 7.3 4.5 - 5.5 - 8 5 - 6 - 8.5

Length 1500mm

Air Flow, l/s 42 71 99 127 156 184 212

Total Pressure, Pa 4 11 21 35 53 74 99

Static Pressure, Pa 3 8 16 26 39 55 73

NC (Noise Criteria) <10 <10 14 24 31 37 43

Throw, m 1 - 1.8 - 4 2.3 - 3.3 - 5.5 3 - 4.5 - 6.5 4 - 5.3 - 7.3 4.5 - 5.5 - 8 5 - 6 - 8.5 5.5 - 6.8 - 9.5

FL-15 with 200mm inlet

51mm Slot Width

Length 600mm

Air Flow, l/s 24 42 61 80 99 118 137

Total Pressure, Pa 4 12 24 41 63 90 121

Static Pressure, Pa 4 11 24 41 62 88 119

NC (Noise Criteria) <10 <10 <10 13 20 27 32

Throw, m 0.5 - 1.5 - 3 1.8 - 2.8 - 4.3 2.8 - 3.8 - 5 3.3 - 4 - 5.8 3.8 - 4.5 - 6.5 4 - 5 - 7 4.3 - 5.3 - 7.3

Length 1200mm

Air Flow, l/s 42 78 113 149 184 219 255

Total Pressure, Pa 3 10 22 37 57 82 110

Static Pressure, Pa 3 10 20 35 54 76 103

NC (Noise Criteria) <10 <10 13 23 31 37 43

Throw, m 1 - 1.8 - 4 2.5 - 3.8 - 5.5 3.3 - 5 - 6.8 4.5 - 5.5 - 8 5 - 6 - 8.5 5.5 - 6.8 - 9.5 5.8 - 7.3 - 10

Length 1500mm

Air Flow, l/s 47 90 132 175 217 260 302

Total Pressure, Pa 3 9 20 34 53 76 103

Static Pressure, Pa 2 8 18 31 48 68 92

NC (Noise Criteria) <10 <10 15 25 33 39 45

Throw, m 0.5 - 1.5 - 4 2.5 - 3.8 - 6 3.8 -.5.3 - 7.3 5 - 6 - 8.5 5.5 - 6.8 - 9.5 5.8 - 7.3 - 10.3 6.5 - 8 - 11

FL-20 with 300mm inlet

FlowBar with Swegon Plenum - High Throw (HT)

Page 15: AIR-DIFFUSION FLOWBAR - Swegon

15200930 - LNNN00394 (1.5) Swegon reserves the right to alter specifications.

FLOWBAR

63mm Slot Width

Length 600mm

Air Flow, l/s 47 68 90 111 132 153 175

Total Pressure, Pa 9 19 33 50 71 96 124

Static Pressure, Pa 9 18 31 47 67 90 117

NC (Noise Criteria) <10 <10 17 26 33 39 44

Throw, m 1.8 - 3 -4.3 2.8 - 3.8 - 5.3 3.3 - 4.3 - 6 4 - 5 - 6.8 4.3 - 5.3 - 7.3 4.5 - 5.5 - 8 5 - 6 - 8.5

Length 1200mm

Air Flow, l/s 66 104 142 179 217 255 293

Total Pressure, Pa 5 13 24 38 56 77 102

Static Pressure, Pa 4 10 19 31 45 62 82

NC (Noise Criteria) <10 <10 20 29 37 44 49

Throw, m 1.5 - 2.8 - 5.3 3 - 4.5 - 6.5 4.3 - 5.5 - 7.5 5 - 6 - 8.5 5.5 - 6.8 - 9.5 5.8 - 7.3 - 10 6.5 - 7.5 - 11

Length 1500mm

Air Flow, l/s 71 113 156 198 241 283 326

Total Pressure, Pa 4 11 21 33 49 68 90

Static Pressure, Pa 3 8 15 24 35 49 65

NC (Noise Criteria) <10 <10 18 28 36 43 49

Throw, m 1.3 - 2.8 - 5.5 3 - 4.5 - 6.8 4 - 5.5 - 8 5.3 - 6.5 - 8.8 5.8 - 7 - 9.8 6 - 7.5 - 10.8 6.8 - 8.3 - 11.5

76mm Slot Width

Length 600mm

Air Flow, l/s 59 80 101 123 144 165 186

Total Pressure, Pa 13 24 38 55 76 100 128

Static Pressure, Pa 12 22 35 52 71 94 119

NC (Noise Criteria) <10 <10 15 23 30 36 41

Throw, m 2.3 - 3.3 - 5 3 - 4 - 5.8 3.8 - 4.5 - 6.5 4 - 5 - 7 4.5 - 5.5 - 7.5 5 - 5.8 - 8.3 5.3 - 6 - 8.8

Length 1200mm

Air Flow, l/s 94 130 165 201 236 271 307

Total Pressure, Pa 10 18 30 44 61 81 103

Static Pressure, Pa 8 14 23 35 48 63 81

NC (Noise Criteria) <10 <10 17 25 32 39 44

Throw, m 2.5 - 4 - 6 3.8 - 5.3 - 7.3 4.5 - 5.8 - 8.3 5.3 - 6.5 - 9.3 5.8 - 7 - 9.8 6 - 7.3 - 10.3 6.5 - 8 - 11.3

Length 1500mm

Air Flow, l/s 104 146 189 231 274 316 359

Total Pressure, Pa 8 17 28 42 59 78 101

Static Pressure, Pa 6 12 20 29 41 55 71

NC (Noise Criteria) <10 <10 17 25 33 40 46

Throw, m 2.5 - 3.8 - 6.5 3.8 - 5.3 - 7.5 4.5 - 6 - 8.8 5.5 - 7 - 9.8 6 - 7.3 - 10.8 6.5 - 8 - 11.3 7 - 8.5 - 12.3

FL-25 with 250mm inlet

FL-30 with 250mm inlet

FlowBar with Swegon Plenum - High Throw (HT)

• Pressures are given in Pascal (Pa)

• Isothermal throw values are given for terminal velocities of 0.8, 0.5 and 0.3m/sec respectively

• Each NC value represents the noise criteria curve which will not be exceeded by the sound pressure in any of the octave bands, 2nd through 7th, with a room absorption of 10dB, re 10-12 watts

• The tests were conducted with the FlowBar and plenums as a composite assembly

• Throw values for High Throw units are based on a 1-way discharge from the slot

• Throws listed are for the 1-way air pattern. For divided air flow, select the airflow in each direction according to the number of slots aimed in that direction, with the total airflow apportioned between slot

• Plenums not provided by Swegon may demonstrate performance variations from the published data and therefore Swegon would not be able to subsequently guarantee that performance matches our data

Page 16: AIR-DIFFUSION FLOWBAR - Swegon

FLOWBAR

16Swegon reserves the right to alter specifications. 200930 - LNNN00394 (1.5)

63mm Slot Width

Length 600mm

Air Flow, l/s 47 68 90 111 132 153 175

Total Pressure, Pa 9 18 32 48 69 93 120

Static Pressure, Pa 9 18 31 47 67 90 117

NC (Noise Criteria) <10 <10 12 21 28 34 40

Throw, m 1.8 - 3 -4.3 2.8 - 3.8 - 5.3 3.3 - 4.3 - 6 4 - 5 - 6.8 4.3 - 5.3 - 7.3 4.5 - 5.5 - 8 5 - 6 - 8.5

Length 1200mm

Air Flow, l/s 66 106 146 186 227 267 307

Total Pressure, Pa 5 12 23 37 55 76 101

Static Pressure, Pa 4 11 20 33 49 68 90

NC (Noise Criteria) <10 <10 16 26 34 41 46

Throw, m 1.5 - 2.8 - 5.3 3 - 4.5 - 6.8 4.3 - 5.5 - 7.5 5.3 - 6 - 8.8 5.5 - 6.8 - 9.8 6 - 7.3 - 10.3 6.5 - 8 - 11.3

Length 1500mm

Air Flow, l/s 71 118 165 212 260 307 354

Total Pressure, Pa 4 10 20 33 49 68 91

Static Pressure, Pa 3 9 17 28 41 58 77

NC (Noise Criteria) <10 <10 16 26 34 41 47

Throw, m 1.3 - 2.8 - 5.5 3 - 4.5 - 7 4.3 - 5.8 - 8.3 5.5 - 6.8 - 9.5 5.8 - 7.3 - 10.3 6.5 - 8 - 11.3 7 - 8.5 - 12

76mm Slot Width

Length 600mm

Air Flow, l/s 59 80 101 123 144 165 186

Total Pressure, Pa 12 23 37 53 74 97 123

Static Pressure, Pa 12 22 35 52 71 94 119

NC (Noise Criteria) <10 <10 11 19 26 32 37

Throw, m 2.3 - 3.3 - 5 3 - 4 - 5.8 3.8 - 4.5 - 6.5 4 - 5 - 7 4.5 - 5.5 - 7.5 5 - 5.8 - 8.3 5.3 - 6 - 8.8

Length 1200mm

Air Flow, l/s 94 137 179 222 264 307 349

Total Pressure, Pa 9 18 31 48 68 92 119

Static Pressure, Pa 8 16 28 42 60 81 105

NC (Noise Criteria) <10 <10 16 26 33 40 45

Throw, m 2.5 - 4 - 6 3.8 - 5.3 - 7.3 5 - 6 - 8.5 5.5 - 6.8 - 9.5 6 - 7.3 - 10.3 6.5 - 8 - 11.3 7 - 8.5 - 12

Length 1500mm

Air Flow, l/s 104 156 208 260 311 363 415

Total Pressure, Pa 7 16 29 45 64 88 114

Static Pressure, Pa 6 13 24 37 53 73 95

NC (Noise Criteria) <10 <10 17 26 34 41 47

Throw, m 2.5 - 3.8 - 6.5 3.8 - 5.5 - 8 5 - 6.5 - 9.3 5.8 - 7.3 - 10.3 6.5 - 8 - 11.3 7 - 8.5 - 12.3 7.5 - 9.3 - 13

FL-25 with 300mm inlet

FL-30 with 300mm inlet

FlowBar with Swegon Plenum - High Throw (HT)

• Pressures are given in Pascal (Pa)

• Isothermal throw values are given for terminal velocities of 0.8, 0.5 and 0.3m/sec respectively

• Each NC value represents the noise criteria curve which will not be exceeded by the sound pressure in any of the octave bands, 2nd through 7th, with a room absorption of 10dB, re 10-12 watts

• The tests were conducted with the FlowBar and plenums as a composite assembly

• Throw values for High Throw units are based on a 1-way discharge from the slot

• Throws listed are for the 1-way air pattern. For divided air flow, select the airflow in each direction according to the number of slots aimed in that direction, with the total airflow apportioned between slot

• Plenums not provided by Swegon may demonstrate performance variations from the published data and therefore Swegon would not be able to subsequently guarantee that performance matches our data

Page 17: AIR-DIFFUSION FLOWBAR - Swegon

17200930 - LNNN00394 (1.5) Swegon reserves the right to alter specifications.

FLOWBAR

Continuous Slot Plenum Jet Throw (JT) Data based on active section 1200 long

25mm Slot Width

Air Flow, l/s-m 31 62 93 124 155 186 217

Static Pressure, Pa 2 7 15 27 42 61 83

NC (Noise Criteria) <10 <10 17 24 28 32 36

Throw, m 0.5 - 1 - 2.3 1.3 - 2.3 - 4 2.3 - 3 - 5.8 2.8 - 4 - 6.8 3.3 - 5.3 - 7.3 4 - 5.8 - 8 4.5 - 6 - 8.8

FL-10

38mm Slot Width

Air Flow, l/s-m 46 93 139 186 232 279 325

Static Pressure, Pa 2 8 18 31 49 70 95

NC (Noise Criteria) <10 <10 17 22 28 34 40

Throw, m 0.5 - 1.3 - 2.3 1.5 - 2.3 - 4.5 2.3 - 3.3 - 6.8 3 - 4.5 - 8 3.8 - 5.5 - 9.3 4.5 - 6.8 - 9.8 5.3 - 7.5 - 10.8

FL-15

51mm Slot Width

Air Flow, l/s-m 54 116 178 240 302 364 426

Static Pressure, Pa 1 7 15 28 44 64 88

NC (Noise Criteria) <10 <10 18 24 29 33 37

Throw, m 0.3 - 1 - 2.3 1.5 - 2.5 - 4.5 2.5 - 3.8 - 7 3 - 5.- 9.3 4 - 6 - 10.3 5 - 7.3 - 11.3 5.5 - 8.5 - 12.3

FL-20

63mm Slot Width

Air Flow, l/s-m 62 147 232 317 402 488 573

Static Pressure, Pa 1 7 17 31 51 74 102

NC (Noise Criteria) <10 <10 18 25 30 35 39

Throw, m 0.3 - 1 - 2.3 1.8 - 2.5 - 5.3 2.8 - 4 - 8 3.8 - 5.5 - 10.8 4.5 - 7 - 12 5.5 - 8.5 - 13 6.8 - 10 - 14

FL-25

76mm Slot Width

Air Flow, l/s-m 77 178 279 379 480 580 681

Static Pressure, Pa 1 7 17 31 50 73 100

NC (Noise Criteria) <10 <10 15 24 30 35 40

Throw, m 0.3 - 1 - 2.5 1.8 - 2.8 - 5.5 2.8 - 4.3 - 8.5 4 - 5.8 - 11.5 5 - 7.3 - 12.8 6 - 8.8 - 14.3 7 - 10.3 - 15.5

FL-30

Table B� Correction Multiplier for Length

Length, mm 600 1200 2400 3000 3600

Throw Correction 0.72 1 1.5 1.7 1.8

Table A� NC Correction for Length

Length, mm 600 1200 1800 2400 3000

Supply -3 0 +2 +3 +5

Return 0 +3 +5 +6 +8

• Pressures are given in Pascal (Pa)

• Pressure loss data assumes a duct velocity is less than 4m/sec in the inlet duct

• Isothermal throw values are given for terminal velocities of 0.8, 0.5 and 0.3m/sec respectively

• Throw data is based on 1200mm active section. For a 600mm section the throw values are 0.72 times those shown. For a 3000mm continuous length, the throw values are 1.7 times those shown and 1.8 for 3600mm units

• Each NC value represents the noise criteria curve which will not be exceeded by the sound pressure in any of the octave bands, 2nd through 7th, with a room absorption of 10dB, re 10-12 watts, for a 1200mm section. See Table A for other lengths

• For supply units used as a return, add 3 NC

• The tests were conducted with no Plenum effect for pressure or sound

• Throw values for Jet Throw units are based on the pattern controller set at 0° discharge vertical flow

Page 18: AIR-DIFFUSION FLOWBAR - Swegon

FLOWBAR

18Swegon reserves the right to alter specifications. 200930 - LNNN00394 (1.5)

25mm Slot Width

Length 600mm

Air Flow, l/s 24 45 66 87 109 130 151

Total Pressure, Pa 3 11 23 41 63 90 121

Static Pressure, Pa 3 10 21 36 56 80 108

NC (Noise Criteria) <10 <10 16 23 29 34 39

Throw, m 0.5 - 1 - 1.8 1.3 - 1.8 - 3.3 1.5 - 2.5 - 4.3 2.3 - 3.3 - 5 2.8 - 4 - 5.5 3.3 - 4.3 - 6 3.8 - 4.5 - 6.8

Length 1200mm

Air Flow, l/s 47 83 118 153 189 224 260

Total Pressure, Pa 4 12 25 41 63 88 119

Static Pressure, Pa 3 8 17 28 42 60 80

NC (Noise Criteria) <10 <10 18 25 30 34 38

Throw, m 1 - 1.3 - 2.5 1.5 - 2.3 - 4.3 2.3 - 3 - 5.8 2.8 - 4 - 6.8 3.3 - 5.3 - 7.3 4 - 5.8 - 8 4.5 - 6 - 8.5

Length 1500mm

Air Flow, l/s 52 92 132 172 212 252 293

Total Pressure, Pa 4 11 23 40 60 85 114

Static Pressure, Pa 2 6 13 23 34 48 65

NC (Noise Criteria) <10 <10 17 24 29 33 37

Throw, m 1 - 1.3 - 2.5 1.5 - 2.3 - 4.3 2.3 - 3 - 6 2.8 - 4 - 7 3.3 - 5.3 - 8 4 - 6 - 8.5 4.5 - 6.5 - 9.3

38mm Slot Width

Length 600mm

Air Flow, l/s 28 52 76 99 123 146 170

Total Pressure, Pa 3 11 24 42 64 91 122

Static Pressure, Pa 2 7 14 24 37 52 70

NC (Noise Criteria) <10 <10 <10 16 24 31 37

Throw, m 0.3 - 1 -1.5 1 - 1.5 - 2.8 1.5 - 2.3 - 4.3 1.8 - 2.8 - 5.3 2.3 - 3.3 - 5.8 2.8 - 4 - 6.5 3 - 4.5 - 7

Length 1200mm

Air Flow, l/s 57 85 113 142 170 198 227

Total Pressure, Pa 8 17 31 48 70 95 124

Static Pressure, Pa 2 4 8 12 18 24 31

NC (Noise Criteria) <10 <10 <10 <10 16 22 27

Throw, m 0.5 - 1.3 - 2.3 1.3 - 1.5 - 3.3 1.5 - 2.3 - 4.5 1.8 - 2.8 - 5.5 2.3 - 3.3 - 6.8 2.5 - 4 - 7.5 3 - 4.5 - 8

Length 1500mm

Air Flow, l/s 66 94 123 151 179 208 236

Total Pressure, Pa 10 20 33 50 71 95 122

Static Pressure, Pa 2 3 6 9 13 17 22

NC (Noise Criteria) <10 <10 <10 <10 12 17 22

Throw, m 0.5 - 1.3 - 2.5 1.3 - 1.5 - 3.3 1.5 - 2.3 - 4.3 1.8 - 2.8 - 5.3 2.3 - 3 - 6.5 2.5 - 3.8 - 7.3 2.8 - 4.3 - 8.3

51mm Slot Width

Length 600mm

Air Flow, l/s 33 66 99 132 165 198 231

Total Pressure, Pa 2 8 18 33 51 74 100

Static Pressure, Pa 1 6 13 23 36 51 70

NC (Noise Criteria) <10 <10 14 21 27 33 38

Throw, m 0.3 - 0.5 - 1.5 1 - 1.5 - 3 1.5 - 2.3 - 4.5 2.3 - 3 - 6 2.5 - 3.8 - 7 3 - 4.5 - 7.5 3.8 - 5.3 - 8.3

Length 1200mm

Air Flow, l/s 66 113 160 208 255 302 349

Total Pressure, Pa 4 12 23 39 58 82 110

Static Pressure, Pa 1 4 8 14 21 30 40

NC (Noise Criteria) <10 12 21 27 32 36 40

Throw, m 0.3 - 1 - 2.3 1.3 - 1.8 - 3.8 1.8 - 2.8 - 5.3 2.3 - 3.3 - 6.8 2.8 - 4.3 - 8.3 3.3 - 5 - 9.3 3.8 - 5.8 - 10

Length 1500mm

Air Flow, l/s 71 123 175 227 278 330 382

Total Pressure, Pa 4 12 24 40 61 85 114

Static Pressure, Pa 1 3 6 11 16 23 30

NC (Noise Criteria) <10 13 21 27 32 36 40

Throw, m 0.3 - 1 - 2.3 1 - 1.8 - 3.8 1.8 - 2.5 - 5.3 2.3 - 3.3 - 6.8 2.8 - 4 - 8.3 3 - 5 - 9.5 3.8 - 5.5 - 10.3

FL-10 with 200mm inlet

FL-15 with 200mm inlet

FL-20 with 200mm inlet

FlowBar with Swegon Plenum - Jet Throw (JT)

Page 19: AIR-DIFFUSION FLOWBAR - Swegon

19200930 - LNNN00394 (1.5) Swegon reserves the right to alter specifications.

FLOWBAR

25mm Slot Width

Length 600mm

Air Flow, l/s 24 45 66 87 109 130 151

Total Pressure, Pa 3 10 22 38 59 84 114

Static Pressure, Pa 3 10 21 36 56 80 108

NC (Noise Criteria) <10 <10 16 22 28 33 38

Throw, m 0.5 - 1 - 1.8 1.3 - 1.8 - 3.3 1.5 - 2.5 - 4.3 2.3 - 3.3 - 5 2.8 - 4 - 5.5 3.3 - 4.3 - 6 3.8 - 4.5 - 6.8

Length 1200mm

Air Flow, l/s 47 85 123 160 198 236 274

Total Pressure, Pa 3 10 21 37 56 79 107

Static Pressure, Pa 3 9 18 31 47 66 89

NC (Noise Criteria) <10 <10 18 25 30 35 39

Throw, m 1 - 1.3 - 2.5 1.5 - 2.3 - 4.5 2.3 - 3.3 - 5.8 2.8 - 4.3 - 6.8 3.8 - 5.3 - 7.5 4.3 - 5.8 - 8.3 5 - 6.5 - 8.8

Length 1500mm

Air Flow, l/s 52 99 146 193 241 288 335

Total Pressure, Pa 3 10 21 37 58 82 112

Static Pressure, Pa 2 7 16 28 44 63 85

NC (Noise Criteria) <10 <10 19 26 31 35 40

Throw, m 1 - 1.3 - 2.5 1.5 - 2.5 - 5 2.5 - 3.3 - 6.5 3 - 4.5 - 7.3 4 - 5.8 - 8.3 4.5 - 6.5 - 9.3 5.5 - 7 - 9.8

38mm Slot Width

Length 600mm

Air Flow, l/s 28 59 90 120 151 182 212

Total Pressure, Pa 2 9 20 37 58 84 115

Static Pressure, Pa 2 8 20 35 55 80 110

NC (Noise Criteria) <10 <10 <10 18 27 35 43

Throw, m 0.3 - 1 -1.5 1.3 - 1.5 - 3.3 1.5 - 2.5 - 5 2.3 - 3.3 - 5.8 2.8 - 4.3 - 6.8 3.3 - 5.3 - 7.3 4 - 5.5 - 8

Length 1200mm

Air Flow, l/s 57 113 170 227 283 340 396

Total Pressure, Pa 2 9 21 37 58 83 113

Static Pressure, Pa 2 8 18 31 49 70 95

NC (Noise Criteria) <10 <10 10 21 30 37 45

Throw, m 0.5 - 1.3 - 2.3 1.5 - 2.3 - 4.5 2.3 - 3.3 - 6.8 3 - 4.5 - 8 3.8 - 5.5 - 9.3 4.8 - 6.8 - 9.8 5.3 - 7.5 - 10.8

Length 1500mm

Air Flow, l/s 66 132 198 264 330 396 463

Total Pressure, Pa 2 9 20 35 55 79 107

Static Pressure, Pa 2 7 15 27 42 61 83

NC (Noise Criteria) <10 <10 10 21 29 36 43

Throw, m 0.5 - 1.3 - 2.5 1.5 - 2.5 - 4.5 2.5 - 3.3 - 7 3 - 4.5 - 8.8 4 - 5.8 - 9.8 4.5 - 7 - 10.8 5.5 - 8.3 - 11.5

51mm Slot Width

Length 600mm

Air Flow, l/s 33 76 118 160 203 245 288

Total Pressure, Pa 2 8 20 36 58 85 117

Static Pressure, Pa 1 7 8 34 54 79 108

NC (Noise Criteria) <10 <10 <10 17 25 31 36

Throw, m 0.3 - 0.5 - 1.5 1.3 - 1.8 - 3.3 1.8 - 2.8 - 5.5 2.5 - 3.8 - 6.8 3 - 4.5 - 7.5 3.8 - 5.5 - 8.3 4.3 - 6.5 - 9.3

Length 1200mm

Air Flow, l/s 66 137 208 278 349 420 491

Total Pressure, Pa 2 8 19 34 54 77 106

Static Pressure, Pa 1 6 14 25 40 58 79

NC (Noise Criteria) <10 <10 17 24 31 37 41

Throw, m 0.3 - 1 - 2.3 1.5 - 2.3 - 4.5 2.3 - 3.3 - 6.8 3 - 4.5 - 8.8 3.8 - 5.8 - 10 4.5 - 6.8 - 11 5.3 - 8 - 12

Length 1500mm

Air Flow, l/s 71 156 241 326 411 496 580

Total Pressure, Pa 2 8 19 34 54 79 108

Static Pressure, Pa 1 5 12 22 35 51 70

NC (Noise Criteria) <10 <10 19 26 32 38 43

Throw, m 0.3 - 1 - 2.3 1.5 - 2.3 - 4.5 2.5 -3.3 - 7 3 - 5 - 9.5 4 - 6 - 11 5 - 7.3 - 12 5.5 - 8.5 - 12.8

FL-10 with 250mm inlet

FL-15 with 300mm inlet

FL-20 with 300mm inlet

FlowBar with Swegon Plenum - Jet Throw (JT)

Page 20: AIR-DIFFUSION FLOWBAR - Swegon

FLOWBAR

20Swegon reserves the right to alter specifications. 200930 - LNNN00394 (1.5)

63mm Slot Width

Length 600mm

Air Flow, l/s 38 85 132 179 227 274 321

Total Pressure, Pa 2 8 19 35 55 81 111

Static Pressure, Pa 1 6 15 27 43 63 87

NC (Noise Criteria) <10 <10 <10 13 21 28 34

Throw, m 0.3 - 0.5 -1.5 1.3 - 1.8 - 3.3 1.8 - 2.8 - 5.3 2.5 - 3.8 - 7 3 - 4.5 - 8 3.8 - 5.5 - 8.8 4.3 - 6.5 - 9.5

Length 1200mm

Air Flow, l/s 71 142 212 283 354 425 496

Total Pressure, Pa 2 9 20 36 56 80 109

Static Pressure, Pa 1 4 9 17 26 38 52

NC (Noise Criteria) <10 <10 <10 17 24 30 36

Throw, m 0.3 - 0.5 - 2.3 1.3 - 2.3 - 4 2.3 - 3 - 6 2.8 - 4 - 8 3.3 - 5 - 10 4 - 6 - 11 4.5 - 7 - 12

Length 1500mm

Air Flow, l/s 76 156 236 316 396 477 557

Total Pressure, Pa 2 9 21 37 58 84 114

Static Pressure, Pa 1 3 7 13 21 31 42

NC (Noise Criteria) <10 <10 <10 16 24 30 36

Throw, m 0.3 - 0.5 - 1.8 1.3 - 1.8 - 4 2.3 - 3 - 6 2.8 - 4 - 8 3.3 - 5.3 - 10 4 - 6 - 11.5 4.5 - 7 - 12.5

76mm Slot Width

Length 600mm

Air Flow, l/s 47 101 156 210 264 319 373

Total Pressure, Pa 2 8 20 36 57 83 113

Static Pressure, Pa 1 6 14 26 41 59 81

NC (Noise Criteria) <10 <10 <10 <10 15 24 31

Throw, m 0.3 - 0.5 - 1.8 1.3 - 1.8 - 3.8 1.8 - 2.8 - 5.5 2.5 - 3.8 - 7.5 3 - 5 - 8.8 3.8 - 5.8 - 9.5 4.5 - 6.8 - 10.3

Length 1200mm

Air Flow, l/s 94 170 245 321 396 472 547

Total Pressure, Pa 3 11 23 39 60 85 114

Static Pressure, Pa 1 4 9 15 23 32 44

NC (Noise Criteria) <10 <10 <10 <10 13 21 27

Throw, m 0.3 - 1 - 2.5 1.3 - 2.3 - 4.3 2.3 - 3 - 6 2.8 - 4 - 8.3 3.3 - 5 - 10 4 - 6 - 11.5 4.5 - 7 - 12.5

Length 1500mm

Air Flow, l/s 113 193 274 354 434 514 595

Total Pressure, Pa 4 12 25 41 62 87 116

Static Pressure, Pa 1 3 7 12 18 25 33

NC (Noise Criteria) <10 <10 <10 <10 10 18 24

Throw, m 0.3 - 1 - 2.5 1.3 - 2.3 - 4.3 2.3 - 3 - 6 2.8 - 4 - 8 3.3 - 5 - 9.8 4 - 5.8 - 11.5 4.5 - 6.8 - 13

FL-25 with 250mm inlet

FL-30 with 250mm inlet

FlowBar with Swegon Plenum - Jet Throw (JT)

• Pressures are given in Pascal (Pa)

• Isothermal throw values are given for terminal velocities of 0.8, 0.5 and 0.3m/sec respectively

• Each NC value represents the noise criteria curve which will not be exceeded by the sound pressure in any of the octave bands, 2nd through 7th, with a room absorption of 10dB, re 10-12 watts

• The tests were conducted with the FlowBar and plenums as a composite assembly

• Plenums not provided by Swegon may demonstrate performance variations from the published data and therefore Swegon would not be able to subsequently guarantee that performance matches our data

Page 21: AIR-DIFFUSION FLOWBAR - Swegon

21200930 - LNNN00394 (1.5) Swegon reserves the right to alter specifications.

FLOWBAR

63mm Slot Width

Length 600mm

Air Flow, l/s 38 90 142 193 245 297 349

Total Pressure, Pa 1 8 19 36 57 84 116

Static Pressure, Pa 1 7 17 31 51 74 102

NC (Noise Criteria) <10 <10 <10 12 20 26 33

Throw, m 0.3 - 0.5 -1.5 1.3 - 1.8 - 3.8 1.8 - 2.8 - 5.8 2.8 - 4 - 7.3 3.3 - 5 - 8.3 4 - 6 - 9.3 4.5 - 7 - 10

Length 1200mm

Air Flow, l/s 71 158 245 333 420 507 595

Total Pressure, Pa 2 8 19 36 57 83 114

Static Pressure, Pa 1 5 13 23 37 54 74

NC (Noise Criteria) <10 <10 <10 18 26 32 38

Throw, m 0.3 - 0.5 - 2.3 1.5 - 2.3 - 4.5 2.5 - 3.3 - 7 3 - 5 - 9.5 4 - 6 - 11 5 - 7.3 - 12.3 5.5 - 8.5 - 13

Length 1500mm

Air Flow, l/s 76 175 274 373 472 571 670

Total Pressure, Pa 1 8 19 34 55 81 111

Static Pressure, Pa 1 4 10 19 30 44 60

NC (Noise Criteria) <10 <10 <10 18 26 32 38

Throw, m 0.3 - 0.5 - 1.8 1.5 - 2.3 - 4.5 2.5 - 3.3 - 7 3 - 5 - 9.5 4 - 6 - 11.5 5 - 7.3 - 12.8 5.8 - 8.5 - 13.8

76mm Slot Width

Length 600mm

Air Flow, l/s 47 106 165 224 283 342 401

Total Pressure, Pa 2 8 19 35 56 81 112

Static Pressure, Pa 1 7 16 29 47 68 94

NC (Noise Criteria) <10 <10 <10 <10 15 24 31

Throw, m 0.3 - 0.5 - 1.8 1.3 - 1.8 - 3.8 1.8 - 3 - 5.8 2.8 - 4 - 8 3.3 - 5.3 - 9.3 4 - 6 - 9.8 5 - 7.3 - 10.8

Length 1200mm

Air Flow, l/s 94 189 283 378 472 566 661

Total Pressure, Pa 2 9 21 37 58 83 113

Static Pressure, Pa 1 5 12 21 32 47 63

NC (Noise Criteria) <10 <10 <10 <10 17 25 32

Throw, m 0.3 - 1 - 2.5 1.5 - 2.5 - 5 2.5 - 3.8 - 7.3 3 - 5 - 9.5 4 - 6 - 11.5 5 - 7.3 - 12.8 5.5 - 8.3 - 13.8

Length 1500mm

Air Flow, l/s 113 217 321 425 529 632 736

Total Pressure, Pa 3 10 21 37 58 82 112

Static Pressure, Pa 1 4 10 17 26 37 50

NC (Noise Criteria) <10 <10 <10 <10 15 24 30

Throw, m 0.3 - 1 - 2.5 1.5 - 2.5 - 5 2.5 - 3.8 - 7.3 3.3 - 5 - 9.8 4 - 6 - 12 5 - 7 - 13.5 5.5 - 8.3 - 14.8

FL-25 with 300mm inlet

FL-30 with 300mm inlet

FlowBar with Swegon Plenum - Jet Throw (JT)

• Pressures are given in Pascal (Pa)

• Isothermal throw values are given for terminal velocities of 0.8, 0.5 and 0.3m/sec respectively

• Each NC value represents the noise criteria curve which will not be exceeded by the sound pressure in any of the octave bands, 2nd through 7th, with a room absorption of 10dB, re 10-12 watts

• The tests were conducted with the FlowBar and plenums as a composite assembly

• Plenums not provided by Swegon may demonstrate performance variations from the published data and therefore Swegon would not be able to subsequently guarantee that performance matches our data

Page 22: AIR-DIFFUSION FLOWBAR - Swegon

FLOWBAR

22Swegon reserves the right to alter specifications. 200930 - LNNN00394 (1.5)

Standard Fixing Details

Dimensions FL-10-HT (25mm)

W = 70mm

Dimensions FL-10-HT (25mm)

W = 78mm

Flowbar Border 66Installation Detail

Dimensions FL-25-HT (63.5mm)

W = 146mm

Dimensions FL-25-HT (63mm)

W = 154mm

Dimensions FL-30-HT (76mm)

W = 171mm

Dimensions FL-30-HT (76mm)

W = 179mm

Dimensions FL-15-HT (38mm)

W = 95mm

Dimensions FL-15-HT (38mm)

W = 103mm

Dimensions FL-20-HT (51mm)

W = 121mm

Dimensions FL-20-HT (51mm)

W = 129mm

High Throw (HT) Details

Optional F6 Fixing (HT) Details

M gg

� 0

Dimensions FL-10-HT (25mm) W=78mm

Dimensions FL-15-HT (38mm) W= 103mm

Dimensions FL-20-HT (51 mm) W= 129mm

E E

0 0

+ � 0

1•1 ______ N_om_i _na _l _Le _n_g _th _____ _,

1•1Plenum Length

Dimensions FL-25-HT (63.5mm) W = 154mm

Dimensions FL-30-HT (76mm) W = 179mm

Flowbar Border 66 Install ation Detail

Page 23: AIR-DIFFUSION FLOWBAR - Swegon

23200930 - LNNN00394 (1.5) Swegon reserves the right to alter specifications.

FLOWBAR

Jet Throw (JT) Details

Dimensions FL-10-JT (25mm)

W = 78mm

Dimensions FL-25-JT (63mm)

W = 154mm

Flowbar Border 66Installation Detail

Dimensions FL-30-JT (76mm)

W = 179mm

Dimensions FL-20-JT (51mm)

W = 129mm

Dimensions FL-15-JT (38mm)

W = 103mm

Dimensions FL-10-JT (25mm)

W = 78mm

Dimensions FL-25-JT (63mm)

W = 154mm

Flowbar Border 66Installation Detail

Dimensions FL-30-JT (76mm)

W = 179mm

Dimensions FL-20-JT (51mm)

W = 129mm

Dimensions FL-15-JT (38mm)

W = 103mm

Jet Throw (JT) PBL-4 Installation Details

Page 24: AIR-DIFFUSION FLOWBAR - Swegon

FLOWBAR

24Swegon reserves the right to alter specifications. 200930 - LNNN00394 (1.5)

Dimensions High Throw (HT) Dimensions

Type 66

Type 22

FL-10/15/20/25/30 - HT Border Type 66

F S W H

1 Slot (25mm) 35 25 70 43

1 Slot (38mm) 41 38 95 43

1 Slot (51mm) 48 51 121 43

1 Slot (63mm) 54 63 146 59

1 Slot (76mm) 60 76 171 59

FL-10/15/20/25/30 - HT Border Type 22

F S W H

1 Slot (25mm) 41 25 70 43

1 Slot (38mm) 48 38 95 43

1 Slot (51mm) 54 51 121 43

1 Slot (63mm) 54 63 146 61

1 Slot (76mm) 60 76 171 61

Type 11

Type 55

FL-10/15/20/25/30 - HT Border Type 11

F S W H

1 Slot (25mm) 22 25 70 43

1 Slot (38mm) 28.5 38 95 43

1 Slot (51mm) 35 51 121 43

1 Slot (63mm) 41 63 146 58.5

1 Slot (76mm) 47.5 76 171 58.5

FL-10/15/20/25/30 - HT Border Type 55

F S W H

1 Slot (25mm) 14 25 70 61.5

1 Slot (38mm) 21 38 95 61.5

1 Slot (51mm) 27 51 121 61.5

1 Slot (63mm) 31 63 146 61.5

1 Slot (76mm) 38 76 171 61.5

Page 25: AIR-DIFFUSION FLOWBAR - Swegon

25200930 - LNNN00394 (1.5) Swegon reserves the right to alter specifications.

FLOWBAR

Jet Throw (JT) Dimensions

FL-10/15/20/25/30 - JT Border Type 66

F S W H O

1 Slot (25mm) 35 25 70 43 76

1 Slot (38mm) 41 38 95 43 102

1 Slot (51mm) 48 51 121 43 127

1 Slot (63mm) 54 63 146 59 152

1 Slot (76mm) 60 76 171 59 178

FL-10/15/20/25/30 - JT Border Type 22

F S W H

1 Slot (25mm) 41 25 70 43

1 Slot (38mm) 48 38 95 43

1 Slot (51mm) 54 51 121 43

1 Slot (63mm) 54 63 146 61

1 Slot (76mm) 60 76 171 61

Border Type 66 Slot Run

H

Type 66 FL-10/15/20/25/30 Type 22 FL-10/15/20/25/30

Slot Run Dimensions

Border Type 22 Slot Run

Border Type 11/22/55 Slot Run with end plates

Page 26: AIR-DIFFUSION FLOWBAR - Swegon

FLOWBAR

26Swegon reserves the right to alter specifications. 200930 - LNNN00394 (1.5)

End Border Configurations

Border Type 66

Optional Blanking Plates - FBBO Blank-off

Optional Return Light Shield Painted Black

FBBO - 10 (25mm Slot) FBBO - 15 (38mm Slot) FBBO - 20 (51mm Slot) FBBO - 25 (63mm Slot) FBBO - 30 (76mm Slot)

FBR - 10 (25mm Slot) FBR - 15 (38mm Slot) FBR - 20 (51mm Slot) FBR - 25 (63mm Slot) FBR - 30 (76mm Slot)

Border Type 11, 22 & 55

Page 27: AIR-DIFFUSION FLOWBAR - Swegon

27200930 - LNNN00394 (1.5) Swegon reserves the right to alter specifications.

FLOWBAR

Standard Installation Details

UHC Upper Hanger ClipThe upper hanger clip is used to suspend the FlowBar assembly from the structure. The clip is designed to utilize standard ceiling hanger wire. UHC is for 1 slot only and FL-10, 15 and 20.

H2 Hard Ceiling ClipThe H2 hard ceiling clip is used to mount the FlowBar assembly with border type 55 when 25mm thick plasterboard ceiling is required.

H3 Hard Ceiling ClipThe H3 hard ceiling clip can be used to mount the FlowBar assembly with border type 22 when a standard plasterboard ceiling is required.

Spline Support ClipThe SS1 spline clip is also used to adjoin multiple sections of FlowBar when continuous lengths are desired.

Installation Details - High Throw (HT) and Jet Throw (JT)

Page 28: AIR-DIFFUSION FLOWBAR - Swegon

FLOWBAR

28Swegon reserves the right to alter specifications. 200930 - LNNN00394 (1.5)

Standard Types 22 Plaster Frame Instal-lation

Standard Installation for Suspended Ceiling Systems

Standard Installation for Solid (Plaster-board) Type Ceiling Systems

Standard Plenum Box Installation System (HT Only)

Page 29: AIR-DIFFUSION FLOWBAR - Swegon

29200930 - LNNN00394 (1.5) Swegon reserves the right to alter specifications.

FLOWBAR

Diffuser Installation with plenum

FlowBar Model Ceiling Opening dimensions for border type 66

1-Slot

FL - 10 76

FL - 15 102

FL - 20 127

FL - 25 152

FL - 30 178

Ceiling

Di�user Flange

Mounting Bracket

Attach Hanger Wire/Rods to Plenum Support Brackets Ceiling

Hemmed Edge of Plenum

Mounting bracket catches in HemmedEdge of Plenum

Di�user �ange overlaps ceiling opening

Opening

Plenum

Concealed Fastening Plenum Installation Diffuser Installation with PlenumAttach Hanger Wire/Rods to Plenum Support Brackets Ceiling

Hemmed Edge of Plenum

Mounting bracket catches in HemmedEdge of Plenum

Di�user �ange overlaps ceiling opening

Opening

Plenum

Concealed Fastening Plenum Installation Diffuser Installation with Plenum

Diffuser Installation without plenum

Concealed Fastening Plenum Instal-lation

Installation Details - Jet Throw (JT) only

Bracket Diffuser Assembly

Page 30: AIR-DIFFUSION FLOWBAR - Swegon

FLOWBAR

30Swegon reserves the right to alter specifications. 200930 - LNNN00394 (1.5)

Ordering KeyDiffuser ordering keyFlowBar

FlowBar a b c d e f g h i

Frame:

- 11 Flangeless

- 22 Plaster frame

- 55 Plaster frame (deep)

- 66 Surface Mounting

Diffuser Model

- HT High Throw

- JT Jet Throw

Number of slots: - 1

Slot Width (mm)

- 10

- 15

- 20

- 25

- 30

End Flanges

- ME0 Open End

- ME1 End border one end

- ME2 End border two ends

- EP1 End plate one end

- EP2 End Plate two ends

Plenum Fix

- F6 ‘U’ Bracket fixing

- F9 Toggle Fix

Diffuser Fix

- SP Special Fixing

- H2 Hard Ceiling clip (25mm)

- H3 Hard Ceiling clip (12.5mm)

- UHC Upper hanger clip (Border Type 66)

Frame Finish

- 3 Standard White matt. Type 66 border

- 4 Standard Black Type 22, 55 & 11 Border

- 6 Other colours available to special order

Blade Finish

- 4 Standard Black

- 6 Other colours available to special order

Example: FlowBar - 66 - HT -1 - 15 - E1 - F6 - 3 - 4

Page 31: AIR-DIFFUSION FLOWBAR - Swegon

31200930 - LNNN00394 (1.5) Swegon reserves the right to alter specifications.

FLOWBAR

Plenum BoxesSupplied with 6mm lining as standard with side entry spigot. Plenum boxes can be supplied without lining or with 12mm lining as an option. Apply to sales office for price.

SpecificationsMaterial/FinishStandard is a minimum of 0.7mm thick galvanised steel.

ConstructionPlenum boxes are generally fabricated in 3 sections, which are either mechanically joined or spot welded to form an airtight seal. As standard, spigots are side entry and located centrally. All boxes are supplied with stepped edges. F9 (HT) or hemmed edges F6 (JT) as standard.

Installation OptionsFixing lugs can be factory fitted if preferred or special fixing methods (by others) may be used. For plenum boxes having flush ends separate hanging brackets/fixing lugs need to be fitted to allow independent support of diffuser and plenum box.

Accessories• Joggled style plenum boxes or pan adapters

• Spigot dampers include manual quadrant or cord operated

• Options for: Unlined; 6mm or 12mm thick Class ‘O’ internal lining

• Equalising grids (50% free area perforated mesh)

• Fixing lugs or special fixings (by others)

High Throw (HT) Plenum

Jet Throw (JT) Plenum

Page 32: AIR-DIFFUSION FLOWBAR - Swegon

FLOWBAR

32Swegon reserves the right to alter specifications. 200930 - LNNN00394 (1.5)

Pressure Drops & Sound RatingThe pressure drop given is for supply diffuser with damper fully open. When the diffuser is installed with plenum box, the pressure loss of the box has to be added to the diffuser.

Plenum Box Spigot Volumes (l/s)

Spigot Velocity m/s

1.5 2.0 2.5 3.0 3.5 4.0

Pressure Drop Pa* 2 4 6 8 12 16

Sound Power Level NR* - - 25 30 35 40

*The figures given are approximate - dependent upon spigot entry conditions.

Spigot Velocity m/s

Diameter (mm) 1.5 2.0 2.5 3.0 3.5 4.0

100 10 15 19 22 26 30

125 18 24 30 35 41 47

150 25 34 42 51 60 68

175 35 46 58 70 82 94

200 45 60 75 91 109 121

225 58 77 96 117 137 151

250 71 95 120 142 170 191

275 86 115 145 172 205 230

300 103 139 172 208 240 275

325 120 160 200 240 280 320

350 140 188 235 280 328 375

400 185 245 310 370 430 495

Page 33: AIR-DIFFUSION FLOWBAR - Swegon

33200930 - LNNN00394 (1.5) Swegon reserves the right to alter specifications.

FLOWBAR

Type PBL-1

Angle Bracket fixing available if required.Optional rectangular or flat oval spigots* available (minimum height 100mm).

Type PBL-1 for F6 fixing

Plenum Box Dimensions

:,:

I I I

65

---� / )

Cord operated spigot damper

65 � I I

:,:

. '-'I w

*

0 N

IS> 0

0 N

IS> 0

X

L + 18mm

X

L + 18mm

:,:

I I I

65

---� / )

Cord operated spigot damper

65 � I I

:,:

. '-'I w

*

0 N

IS> 0

0 N

IS> 0

X

L + 18mm

X

L + 18mm

Order Details

C

H L W D LH RH X

- - - - - - -

Order Details

C

H L W D LH RH X

- - - - - - -

L+18

Page 34: AIR-DIFFUSION FLOWBAR - Swegon

FLOWBAR

34Swegon reserves the right to alter specifications. 200930 - LNNN00394 (1.5)

Plenum AccessoriesManual Quadrant Control Damper

Model Ref Nominal Duct Diameter* Open Blade Protrusion (mm) DW144 Casing Leakage Class Weight (Kg)

CB 100 – C 0.56

CB 125 – C 0.71

CB 150 – C 0.85

CB 160 C 0.91

CB 200 C 1.17

CB 250 20.5 C 1.53

CB 300 45.5 C 1.92

CB 315 53 C 2.05

CB 350 70.5 C 2.35

CB 355 73 C 2.40

* NDD: Nominal duct diameter. Actual sizes are in accordance with BS EN 1506.

200

5050

75

50

50

60

ND

D

Type PBL-4 for F6 fixing

Order Details

H L W Wo D (spigot) Ko Q

- - - - - - -

Page 35: AIR-DIFFUSION FLOWBAR - Swegon

35200930 - LNNN00394 (1.5) Swegon reserves the right to alter specifications.

FLOWBAR

Type PBL-1

Plenum Box Detail Lever Operated Damper Option

6565

Page 36: AIR-DIFFUSION FLOWBAR - Swegon

FLOWBAR

36Swegon reserves the right to alter specifications. 200930 - LNNN00394 (1.5)

Plenum ordering keyPlenum

Plenum a b c d e

Model:

- PBL-1 Linear Plenum Box with either a circular or square side entry spigot

- PBL-2 Linear Plenum Box having either a circular or square top entry spigot

- PBL-3 Linear Plenum Box with joggle section having ei ther a circular or square side entry spigot

- PBL-4 Linear Plenum Box with joggle section having either a circular or square top entry spigot

Internal Lining:

- U Unlined

- L 6mm class 'O' lining

Spigot Damper: - N Plain spigot no damper

- Q Quadrant damper

- Z Lever operated opposed blade damper

- C Cord operated damper fitted to spigot

Options (mm)

- 0 No options

- 2 Equalising grid

- 3 Fixing lugs fitted to side of plenum

- 4 Profile ends on each end of plenum

- 5 Hemmed Edge for concealed strap fixing

- 6 Plenum retaining clips (HT Only

Dimensions:

- See dimension guide below

Plenum (PBL-1, PBL-2 dimension key)See page 33 for plenum dimensioning drawings

Circular Spigot

Plenum (all dimensions in mm) a b c

Neck Size (L x W)

Plenum Height (H)

Circular Spigot Diameter

Square Spigot

Plenum (all dimensions in mm) a b c d

Neck Size (L x W)

Plenum Height

Sq/Rect Spigot Width x Height (A x B)

Centre line of spigot (X)