Bulletin 160C
8/00
Air Make-Up Burners
ECLIPSE AH-MABURNERS
E C L I P S E
Designed for trouble-freemake-up or process air heating.
Eclipse AH-MA burners produce a uniform, odorless, and smokelessflame ideal for heating fresh air inmake-up and process air heating applications. The AH-MA design provides stable operation over a widerange of velocities, inputs and fuels.
AH-MA easily passes all global standards for indoor air quality through a wide operational range. It is ETL listed,complying with ANSI Z21.20 designstandards, and is used in systemswhich meet ANSI Z83.4 / CGA 3.7emissions standards for NOx and CO.
The new aluminum burner body creates a lightweight, corrosion resistant burner. Cast iron and corrosionresistant cast iron bodies are also available. Divergent air wings are madeof stainless steel. The burner bodiessupply fuel to the center of the airwings to control the air and fuel mixtureinside the burner and to optimize emissions and efficiency.
Low pressure models require only a6.0" w.c. ΔP natural gas at 800,000Btu/hr/LF, making them ideal for usewith the Maxitrol Selectra control valve.
Ready for the world
AH-MA burners combine advancedengineering with installation and operational features that are truly world class.
• Assembled from straight sections,tees and crosses to produce nearly any configuration required.
• Inputs up to 1,200,000 Btu/hr/LF
• Up to 30:1 turndown
• Up to 450°F upstream air temperature.
• Up to 850°F downstream air temperature.
• Multi-fuel capability (natural gas, propane and butane)
In addition to the many user-preferredfeatures of AH-MA, Eclipse offers you acomprehensive, global network of servicewith more years of air-heating experiencethan any other burner manufacturer.
AH-MA BurnersIdeal for make-up air heating applications
Bulletin 160C 8/00 Litho in USA
AdjustableProfile Plate
UniformAir Flow
UniformAir Flow
AdjustableProfile Plate
Burner Body
Gas Feed Pipe
Air WIng
HeatedAir
FlameLength
AH-MA SeriesVersion 2.20
AirHeatBurners
11/7/04Data 160
** Burners over 5 lineal feet include flame supervision at the far end. If pilot ignition is being used,two flame supervision units are required; one for the pilot and one for the far end. If using directspark on the main flame, only flame supervision at the far end is required providing ignition canbe accomplished within 15 seconds. (Reference NFPA Requirement 5-9.2.2)
• Eclipse reserves the right to change the construction and/or configurations of our products atany time without being obliged to adjust earlier supplies accordingly.
• All information is based on laboratory testing. Different chamber size and air flow conditionsmay affect the data.
• All information is based on standard conditions (70°F at sea level). Contact Eclipse forperformance data above ambient temperature.
• All inputs based on gross caloric values.
Main Specifications
Parameter Description
Input (Btu/hr./ft.) 1,200,000 maximumCombustion Airstream 0.2" to 1.4"w.c.Pressure Drop/Velocity Ignition Direct spark ignition (6000VAC).Pilot Interruptible pilot for natural gas, propane or butane.Integral Pilot Capacities 20,000 Btu/hr. Burner Bodies Standard Aluminum Low Pressure Aluminum* Standard Cast Iron Corrosion Resistant, EN Plated Cast Iron Low Pressure Cast Iron*Burner Section Sizes • 150mm (6") straight section • 300mm (12") straight section • 300mm (12") straight section with back inlet • 300mm (12") straight section with pilot • 150mm (6") by 300mm (12") tee section • 150mm (6") by 300mm (12") tee section with pilot • 300mm (12") by 300mm (12") cross sectionPipe Threads N.P.T. or B.S.P.Maximum Upstream Air Temp. 450˚F (232˚C)Maximum Downstream Air Temp. 850˚F (454˚C)Maximum Temperature Rise 750˚F (400˚C)Minimum Inlet Air Oxygen (O2) 18%Flame Detection** Flame rod or scanner.Fuels Natural gas, propane or butane.
* For use with Natural Gas only.
Eclipse AH-MA AirHeat Burners v2.20, Data Sheet 160, 11/7/042
Operating Range & Duct Pressure Measurement
Inlet Air Temperature Correction
1,000,000
900,000
800,000
700,000
600,000
500,000
400,000
300,000
30,000
25,000
20,000
15,000
10,000
5,000
0
1,100,000
1,200,000
1,300,000
Natural GasPropane/Butane
Hea
t In
put
(Btu
/hr.
/ft.)
0.2 0.4 0.6 0.8 1.0 1.2 1.4
Air Pressure Drop ("w.c.) @ 70˚ F Air Inlet
Maxim
um H
eat In
put
Minimum Heat Input
Air Press. Drop @ Air Temp. = Air Press. Drop from “Oper. Range” Chart x Correction Factor
Air Inlet Temp. (°F) 0 30 70 150 200 250 300 350 400 450
Correction Factor 0.87 0.92 1.00 1.15 1.25 1.34 1.43 1.53 1.62 1.72
Air Velocity Calculation
Air Velocity (fpm) = 1096.2 Air Pressure Drop ("w.c.)
Air Density (lbs./cubic ft.)
Eclipse AH-MA AirHeat Burners v2.20, Data Sheet 160, 11/7/04 3
Differential Pressure Measurement & Burner Gas Pressure Drops
Flame Lengths
Emissions Data
60
70
50
40
30
20
10
0100 200 300 400 500 600 700 800 900 1,000 1,100 1,200
Fla
me
Len
gth
(Inc
hes)
Heat Input (1000’s Btu/hr./ft.)
0.4"w.c. 0.7"w.c.1.0"w.c.
Air Pressure DropFlameLength
Note:Flame length may vary slightly from these values depending on actual fuel, air handling system, duct configuratons and profile plates uses.
100
80
90
70
60
50
40
30
0 200 400 600 800 1,000 1,200
NO
x (p
pmvd
@ 3
% O
2)
Input (1000’s Btu/hr./ft.)
20
10
0
0.4"w.c. 0.7"w.c.1.0"w.c.
Air Pressure Drop
1400
1000
1200
800
600
400
200
00 200 400 600 800 1,000 1,200
CO
(pp
mvd
@ 3
% O
2)
Input (1000’s Btu/hr./ft.)
1600
1800
0.4"w.c. 0.7"w.c.1.0"w.c.
Air Pressure Drop
“D”10-20"(254-508mm)
30
25
20
15
10
5
00 200 400 600 800 1,000 1,200
Gas
Pre
ssur
e D
rop
("w
.c.)
, B
urne
r In
let
to D
uct
Heat Input (1000’s Btu/hr./ft.)
Main gas differential pressure measured between “A” and “D”
Natural Gas*Propane*Butane*Natural Gas (Low Press.)* *
* 2.0mm gas ports.* * 2.4mm gas ports
"A"Tap On
Inlet GasPiping
•