airconditioningforlargemultistorybuildings-110522204801-phpapp02

Upload: fazal-husain

Post on 02-Jun-2018

219 views

Category:

Documents


0 download

TRANSCRIPT

  • 8/10/2019 airconditioningforlargemultistorybuildings-110522204801-phpapp02

    1/24

  • 8/10/2019 airconditioningforlargemultistorybuildings-110522204801-phpapp02

    2/24

    Most large multistory buildings use highlycentralized air conditioning equipment. Theroof and basement are the usual choice forthese central station systems.

    The basement has the advantage of easyutility connections, noise isolation, not beingvaluable rental area and the fact that

    structural loads are not a problem.

  • 8/10/2019 airconditioningforlargemultistorybuildings-110522204801-phpapp02

    3/24

    The roof is the ideallocation for fresh air

    intakes and heat rejectionto the atmosphere.

    Cooling tower are noisy,produce very hot andhumid exhaust air, so thebest location for coolingrower is placed on the roof.

    SECTION OF A TYPICALMULTISTORY BUILDING WITH

    A ROOFTOP CENTRALSTATION MECHANICALSYSTEM

  • 8/10/2019 airconditioningforlargemultistorybuildings-110522204801-phpapp02

    4/24

    In most buildings, themechanical equipment isshown to be on the roof. Thissection shows an all-airsystem served by a singlecentral air handling unit onthe roof.

    To avoid the large verticalducts, separate air handlingunits can be placed on eachfloor and only water circulatesvertically. This saves much

    energy because moving airgreat distances requires muchpower.

    MECHANICAL EQUIPMENT ISSTILL ON THE ROOF, EACHFLOOR HAS A SEPARATE AHU

  • 8/10/2019 airconditioningforlargemultistorybuildings-110522204801-phpapp02

    5/24

    The advantage of all-air system is completecontrol over air quality is possible. Thedisadvantage is that all-air systems are verybulky and a significant part of the buildingvolume must be devoted to them.

    There are 5 system in all-air system categories.i. Central Plants

    ii. Variable Air Volume (V.A.V)

    iii. Terminal Reheat System

    iv. Multizone Systemv. Double Duct System

  • 8/10/2019 airconditioningforlargemultistorybuildings-110522204801-phpapp02

    6/24

    The central air conditioning system has thelimitation of the same air quality being deliveredthroughout the building.

    If the structure is zoned or divided and

    compartmented into several different functionssuch as offices, workshops, canteen.

    The temperature of each element can becontrolled with zoned thermostats.

    The fan precedes the chiller and reheater coils

    and blow air through the air-handling unit. Several ducts radiate from the unit to designated

    zones within the building.

  • 8/10/2019 airconditioningforlargemultistorybuildings-110522204801-phpapp02

    7/24

  • 8/10/2019 airconditioningforlargemultistorybuildings-110522204801-phpapp02

    8/24

    This is a single duct system that can easilyhave many zones. A variable air volumecontrol box is located wherever a duct entersa separate zone.

    A thermostat in each zone controls the airflow by operating a damper in the V.A.Vcontrol box. More cooling is required, morecool air is allowed to enter the zone.

  • 8/10/2019 airconditioningforlargemultistorybuildings-110522204801-phpapp02

    9/24

    Floor plan of a VAV system.

    VAV system.

    VAV control box.

  • 8/10/2019 airconditioningforlargemultistorybuildings-110522204801-phpapp02

    10/24

    VARIABLE AIR VOLUME SYSTEM

  • 8/10/2019 airconditioningforlargemultistorybuildings-110522204801-phpapp02

    11/24

  • 8/10/2019 airconditioningforlargemultistorybuildings-110522204801-phpapp02

    12/24

    In this system, every zone receives air at therequired temperature through a separateduct.

    These ducts are supplied by a special

    multizone air handling unit that custommixes hot and cold air for each zone.

    This is accomplished by motorized damperslocated in the air handling unit but controlled

    by thermostats in each zone. Depending onthe temperature, the ratio of hot and cold airvaries but the total amount of air is constant.

  • 8/10/2019 airconditioningforlargemultistorybuildings-110522204801-phpapp02

    13/24

    The multizone unit is supplied with hot water,chilled water and a small amount of fresh air.

    Each multizone unit can handle about 8zones.

    Because moderate air temperatures arecreated by mixing hot and cold air, this

    system also wasteful of energy. Disadvantage this system are costs relatively

    high while the thermal control is relativelypoor.

  • 8/10/2019 airconditioningforlargemultistorybuildings-110522204801-phpapp02

    14/24

    Like the multizone system, the double duct system mixeshot and cold air to achieve the required air temperature.

    Instead of mixing the air at a central air handling unit,mixing boxes are dispersed throughout the building.

    The double duct system creates a high level of thermalcomfort and allows for great zoning flexibility, it is veryexpensive, requires much building space and its wastefulof energy.

    Double duct system.

  • 8/10/2019 airconditioningforlargemultistorybuildings-110522204801-phpapp02

    15/24

    To reduce the size of the ducts, a high-velocity version of this system

    High-velocity air systems (6000 feet/minute)consume more fan power than normalvelocity systems(2000 feet/minute).

    Because of these problem and because V.A.Vsystem are a good alternative, dual ductsystems are not used much anymore.

  • 8/10/2019 airconditioningforlargemultistorybuildings-110522204801-phpapp02

    16/24

    These system supply both airand water to eachzone of a building.

    It greatly decreases the size of the equipmentbecause of the immense heart-carrying capacity

    of water as opposed to air. Air is supplied mainly because of the need for

    ventilation.

    There are 2 system in air-water systemcategories.

    i. Induction Systemii. Fan- coil with supplementary air

    But in this topic is cover induction system only

  • 8/10/2019 airconditioningforlargemultistorybuildings-110522204801-phpapp02

    17/24

    A small quantity of high-velocity air issupplied to each zone to supply the requiredfresh air and to induce room air to circulate.

    Most induction terminal units are found

    under windows where they can effectivelyneutralize the heat gain.

    As the high-velocity air shoots into the roomit induces a large amount of room air to

    circulates. This combination of room air and fresh air,

    then passes over heating or cooling coils.

  • 8/10/2019 airconditioningforlargemultistorybuildings-110522204801-phpapp02

    18/24

    Local thermostats regulate the temperature bycontrolling the flow of either hot or cold waterthrough the coils.

    It takes a lot of fan power to circulate air at highvelocity throughout a building.

    Because of the high cost of energy and theexpense of high-velocity ductwork, the use ofinduction systems is limited.

    Induction system.

  • 8/10/2019 airconditioningforlargemultistorybuildings-110522204801-phpapp02

    19/24

    Induction system.

    Induction unit with coolingor heating coils

  • 8/10/2019 airconditioningforlargemultistorybuildings-110522204801-phpapp02

    20/24

    These systems supply no air. There are 2 system in all-water system

    categories.

    i. Fan-coil System

    ii. Water Loop Heat Pump System

    But in this topic is cover Fan-coil system only.

  • 8/10/2019 airconditioningforlargemultistorybuildings-110522204801-phpapp02

    21/24

    The fan-coil unit basically consists of a fanand a coil within water circulates.

    The units are in the form of cabinets forplacement under windows.

    The fan blows room air across coilscontaining either hot or cold water.

    Thermostatically controlled valves regulatethe flow of water through the coils.

    A 4 pipe system, which is has 2 pipes for hotwater supply and return and another 2 pipesfor cold water supply and return.

  • 8/10/2019 airconditioningforlargemultistorybuildings-110522204801-phpapp02

    22/24

    Condensation on the cooling coils must becollected in a pan and drained away.

    When the fan-coil unit is on an outside

    wall, it is possible to have an outdoor airintake connected to the unit.

    A three-speed fan switch allows occupantsof the zone to have some control over the

    temperature. Fan-coil units are most appropriate for air

    conditioning buildings with small zones(eg. Apartments, condominiums, motels,hotels, hospitals and schools).

    Fan coil units also located above windows,in small closets or in the dropped ceilingabove a bathroom.

  • 8/10/2019 airconditioningforlargemultistorybuildings-110522204801-phpapp02

    23/24

    Fan Coil System.

    Schematic diagram of an under window FCU ( 4

    pipe system).

  • 8/10/2019 airconditioningforlargemultistorybuildings-110522204801-phpapp02

    24/24

    FCU placed in a small closet.

    FCU placed above a dropped ceiling.