airflow characteristics and ventilation effectiveness in

10
Airflow Characteristics and Ventilation Effectiveness in the Office Room with Task and Ambient Air-Conditioning System using Personalized Selective Task Diffusers Toshio Yamanaka 1 , Kazunobu Sagara 1 , Hisashi Kotani 1 , Masashi Yamagiwa 2 , Susumu Horikawa 3 , Tatsuya Yamashita 4 , Eunsu Lim 1 1 Osaka University, Japan 2 THE KANSAI ELECTRIC POWER CO., INC, Japan 3 NIKKEN SEKKEI LTD., Japan 4 SANKI ENGINEERING CO., LTD., Japan Corresponding email: [email protected] SUMMARY “Task and ambient air conditioning system” for the large office room is a very comfortable and energy saving system with an ambient temperature maintained at a little higher than the that of the zone in the vicinity of seated occupants so long as the occupants can control the thermal environment freely as a personal zone. A new selective floor diffuser for task zone (occupancy zone) has been developed in order to improve the personal controllability. This diffuser can provide two different airflows ; one is swirling diffusive flow (“swirl flow”) and the other is directional jet (“directional flow”). One can change the flow type easily by turning the switch on the floor diffuser. This selection can give the comfortable environment for any occupants with different thermal tastes. In this study, the temperature distributions, airflow characteristics and ventilation effectiveness were measured in a large office room with this floor diffusers and grille type ceiling outlets for ambient zone. The tracer gas pulse method was adopted to measure the local mean age of air and SVE4 (scale for ventilation efficiency No.4) which presents the contribution ratio of each supply outlet. In addition to the measurements, the CFD analysis was conducted to investigate the detail of the air distributions in the room. As a result of these investigations, the attainment of “task zone” around the occupants and negligible effect of the task diffusers other than the closest task diffuser were confirmed. INTRODUCTION The measurement of the temperature, air velocity and ventilation indices were conducted in an large office room with task and ambient air-conditioning system using personalized selective task diffusers. This office room is located in the 30 th floor of a high-rise office building in Osaka, Japan. As presented in previous papers [1][2], this building was designed to utilize wind-forced ventilation for the environment control of ambient zone of he room in intermediate seasons. In summer and winter seasons, the openings for wind-forced ventilation are all closed, and so-called “task and ambient air conditioning system” control the indoor environment. The purpose of this measurement is to examine the effect of the change of the flow type of floor diffuser on the flow characteristics and thermal environment around a

Upload: others

Post on 16-Jun-2022

7 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Airflow Characteristics and Ventilation Effectiveness in

Airflow Characteristics and Ventilation Effectiveness in the Office Room

with Task and Ambient Air-Conditioning System using Personalized

Selective Task Diffusers

Toshio Yamanaka1, Kazunobu Sagara

1, Hisashi Kotani

1, Masashi Yamagiwa

2,

Susumu Horikawa3, Tatsuya Yamashita

4, Eunsu Lim

1

1 Osaka University, Japan

2 THE KANSAI ELECTRIC POWER CO., INC, Japan

3 NIKKEN SEKKEI LTD., Japan

4 SANKI ENGINEERING CO., LTD., Japan

Corresponding email: [email protected]

SUMMARY

“Task and ambient air conditioning system” for the large office room is a very comfortable

and energy saving system with an ambient temperature maintained at a little higher than the

that of the zone in the vicinity of seated occupants so long as the occupants can control the

thermal environment freely as a personal zone. A new selective floor diffuser for task zone

(occupancy zone) has been developed in order to improve the personal controllability. This

diffuser can provide two different airflows ; one is swirling diffusive flow (“swirl flow”) and

the other is directional jet (“directional flow”). One can change the flow type easily by turning

the switch on the floor diffuser. This selection can give the comfortable environment for any

occupants with different thermal tastes.

In this study, the temperature distributions, airflow characteristics and ventilation

effectiveness were measured in a large office room with this floor diffusers and grille type

ceiling outlets for ambient zone. The tracer gas pulse method was adopted to measure the

local mean age of air and SVE4 (scale for ventilation efficiency No.4) which presents the

contribution ratio of each supply outlet. In addition to the measurements, the CFD analysis

was conducted to investigate the detail of the air distributions in the room.

As a result of these investigations, the attainment of “task zone” around the occupants and

negligible effect of the task diffusers other than the closest task diffuser were confirmed.

INTRODUCTION

The measurement of the temperature, air velocity and ventilation indices were conducted in

an large office room with task and ambient air-conditioning system using personalized

selective task diffusers. This office room is located in the 30th

floor of a high-rise office

building in Osaka, Japan. As presented in previous papers [1][2], this building was designed

to utilize wind-forced ventilation for the environment control of ambient zone of he room in

intermediate seasons. In summer and winter seasons, the openings for wind-forced ventilation

are all closed, and so-called “task and ambient air conditioning system” control the indoor

environment. The purpose of this measurement is to examine the effect of the change of the

flow type of floor diffuser on the flow characteristics and thermal environment around a

Page 2: Airflow Characteristics and Ventilation Effectiveness in

sitting occupant. In fact, a simple thermal mannequin and black lamps were used instead of

real persons. Two indices, local mean age of air [3][4] for specific supply opening and SVE4

[5] (scale for ventilation efficiency No.4) were used, and tracer gas pulse method was applied

to measure these indices. In addition to the measurement, CFD analysis by standard k- model

was conducted to clarify the effect of the flow rate ratio of floor diffuser and ceiling grille on

the temperature distribution in the room.

The results of the measurement and CFD analysis under the hybrid air conditioning system of

floor supply and natural ventilation will be presented in another paper [6] printed in

proceedings of ROOMVENT 2007.

MEASUREMENT

Outline of measured building and air conditioning system

The measurement was conducted in an office room on

the 30th

floor of the high rise office building shown in

Fig.1. The outline of the building is shown in Table 1.

Table 1. Outline of the measured building. Location Osaka city, Japan

Building use Office, Substation, District heating

and cooling, Parking

Total floor area 5 stories in underground and 41

stories on the ground (GL+195m)

As many openings for wind-forced ventilation were

closed, and conditioned air is supplied from ceiling

grille for ambient zone and floor diffusers for the task

zone around occupants. Fig.2 shows the duct system,

and the supply flow rates are shown in Table 2, flow

rate of return air in Table 3. As is shown in Fig. 2, the

ambient zone temperature is set to 28 ºC and task zone

26ºC. Outside fresh air is introduced into AHU for

ambient zone and supplied from the ceiling sully grille.

As for AHU for task zone, only the return air is

circulated. The flow rate of outside air is 6,600 m3/h. The supply flow rate is 21,000 m

3/h for

floor diffuser, 18,000 m3/h for ceiling grille.

VAV

MD

Outside air

ceiling slit for return air

Ambient zone (28 degC) Ceiling supply grille

Floor diffuser

AHU for ambient zone

AHU for tast zone

Task zone (26 degC)

Opening for wind-forved ventilation

MD

MD

Relief air toEV hallCeiling plenum chamber

Figure 2. Duct and AHU system in section.

Measured floor

27-34F : floors with openings for wind-forced ventilation

14-17F : floors with openings for wind-forced ventilation

Office

Office

Entrance hall

GL+195m

GL

Figure 1. Section of

measured building.

Page 3: Airflow Characteristics and Ventilation Effectiveness in

Table 2. Supply air conditions.

Supply

opening Control

Supply air

temperature

Maximum airflow

rate of each

supply

Number

of supply

unit

Floor

diffuser (for

task zone)

Person sensor or manual

switch

Flow rate : (Large, Small,

Close)

Flow direction :

(Directional, Swirl flow)

21~22 degC

(during

measurement)

110 m3/h 254

Ceiling grille

(for ambient

zone)

VAV

21.5~22 degC

(during

measurement)

Perimeter zone:

110 m3/h

Interior zone: 100

m3/h

143

Table 3 Airflow rate of return, relief and exhaust air

Airflow rate

Return through ceiling chamber 39,000 m3/h

Relief air 6,600 m3/h

Exhaust from the smoking room 800 m3/h

57,600

36,0

00

NArea showed in Fig.7

Measured occupant area with a mannequin generating 60W

Measured room

Outside of measurement area

Floor difuser Ceiling grille

Open ceiling(30-32F)

Smoking room

Figure 3. Plan of measured 30th floor.

The plan of the measured floor is shown in Fig. 3.

Fig. 4 shows the picture of floor diffuser. The flow type of

this diffuser can be changed by shutting the directional

outlet at the center of this diffuser. One is called

“directional flow”, and the other “swirl flow”. Fig.5 shows

the schematic airflow from the floor diffuser to an

occupant for each flow setting of the diffuser. One floor

diffuser is prepared for one sitting occupant in principle.

Fig.6 shows the picture of ceiling grille.

φ200mm φ200mm

φ100mm φ100mm

Swirl diffuserSwitch of flowrate

Directional diffuser Shutter switch

Figure 4. Face of floor diffuser.

Page 4: Airflow Characteristics and Ventilation Effectiveness in

Method of measurement

The measurement was carried out from 16 July,

2005 to 18 July, 2005. A mannequin wrapped with

heating tape was seated in the area of dotted line

in Fig.3. Air velocity, temperature and tracer gas

concentration were measured around the

mannequin. SF6 was used as tracer gas, and the

balloons filled with SF6 set in the ten floor diffuser and three ceiling grille were divided by a

needle one by one, and the concentration response of SF6 was measured at many points. The

positions of the diffusers and grilles where a balloon was divided are shown in Fig. 7.

Measurement points of tracer gas concentration are shown in Fig.8. As the flow from ceiling

grilles is directed to the left (west) direction in Fig.7, three ceiling grilles in the right (east)

side of the mannequin were selected as a pulse source of tracer gas. The floor diffuser “T-3”

is the closest one to the heated mannequin.

T-1

T-3

T-4

T-5

T-7

T-6

T-8

T-9

T-10

T-2A-1

A-3A-A-2

Area of dotted line in Fig.3

Measured occupant zone

Floor diffuserFloor diffuser with tracer gas injection (T-1~10)Ceiling grille with tracer gas injection (A-1~3)

L L'

C C'

C10

C11

C12

1600

1100

100

500

500

500

500 500

C1

C2

C4

C5

C7

C8

C9

C-C' section

R R'T-4

T-3

Directional airflow

Directional airflow

Mouse of mannequin

M

C3 C6

plan

Measurement point of tracer gas concentration (36 points)

Measured occupant area

Figure 7. Plan of measured area. Figure 8. Measurement points of SF6 concentration

Because measurement period was holidays, there were no working occupants in the office. A

hundred and ten black lamps of 60 W were set at all chairs to simulate the heat emission from

persons. As other heat source, all the illuminators on the ceiling were lit and all notebook

computers on the desk were set to standby mode.

Measurement was carried out under two conditions of the floor diffuser ; diffusive flow

setting and swirl flow setting. The flow rate of floor diffusers was set to the maximum (110

m3/h). Under the directional flow setting, only the ten diffusers were directed to the each

occupant seat closest to each diffuser. The flow the directional diffuser was set to the

direction with 45 degrees to each occupant horizontally because flow from the diffuser will

change its direction due to the swirling flow around the directional diffuser.

Section Plan

Section Plan

(1) Directional flow setting

(2) Swirl flow setting

Direction change due to swirl flow

Swirl flow

Figure 5. Schematic flow from floor

diffuser.

200mm

200mm

Figure 6. Face of ceiling grille.

Page 5: Airflow Characteristics and Ventilation Effectiveness in

Time mean values of air velocity and temperature were calculated, and the local mean age of

air for specific supply opening ip and SVE4 (Scale for Ventilation Efficiency No.4) were

calculated from the measured concentration response of SF6 according to the method

presented by Lim et al. [6]. Here, it is important to note “local mean age of air for specific

opening” is different from the normal local mean age in the respect that only the air supplied

to the specific supply opening is accounted for.

MEASUREMENT RESULTS

Temperature distribution in task zone around mannequin

The temperature distributions in the case of two flow settings of floor diffusers are shown in

Figure 9. It can be seen that the positions of area with the lowest temperature is different. In

both cases, ambient zone with rather uniform temperature is maintained in the upper zone of

the room.

2525

24

24

24

24

24.5

24.5

24.75

23.75 23.7524.25

25.25

25

25

24.5

24.5

24.75

24.25

25.25

00

500500

10001000

15001500

20002000

25002500

28002800

2500250020002000150015001000100050050000 2500250020002000150015001000100050050000

T-3 T-3

Unit : [degC] Unit : [degC]

[mm] [mm]

[mm] Ceiling grille Ceiling grille

MannequinMannequin

Desk Desk

Directional flow setting Swirl flow setting Figure 9. Temperature distribution in task zone around mannequin.

Vertical distribution of air velocity at the back of mannequin

Fig.10 shows vertical distribution of air velocity at the back

of mannequin (point : C7, C8, C9) under the condition of

directional flow, swirl flow and closed case (no supply air).

From this figure, the maximum velocity is seen at the height

of 60 cm above floor on both flow settings, but the velocity of

directional flow is much higher than the swirl flow. This

indicates the supplied air from floor diffuser reaches the

occupant under directional flow setting.

Distribution of “local mean age of air for specific

opening” ip

Based on the integration of Sf6 concentration response on

time series, local mean age of air for specific opening ip was

calculated. Fig. 13 shows the horizontal distributions of

ip around mannequin at the height of FL+1600, FL+1100

and FL+100. The left row is the cases of directional flow and the right row is the cases of

swirl flow. Mean age ranges from 60 to 90 seconds around the mannequin in the case of swirl

0

200

400

600

800

1000

1200

1400

1600

1800

0 0.1 0.2 0.3air velocity [m/s]

Hei

ght a

bove

flo

or [

mm

]

Directionalflow setting

Closed

Swirl flowsetting

Figure 10. Vertical

temperature distribution

at the back of mannequin.

Page 6: Airflow Characteristics and Ventilation Effectiveness in

flow supply, but mean age of directional

flow is shorter than that of swirl flow

supply, which ranges from 40 to 60

seconds. ip at higher level is larger than

ip at lower level.

The vertical distributions of ip in the

section passing the centerline of the

mannequin are shown in Figure 12. The

shape of these distributions resemble the

temperature distribution shown in Fig.9.

This tendency suggest that the convection

and diffusive transfer of heat is similar to

the convection and diffusive transfer of

supplied air.

Figure 13 shows the local mean age of air

for 10 floor diffusers (T-1~10) and three

ceiling grilles (A-1~3) at the front of the

occupant (C4, C5, C6). In the case of

directional flow setting, mean age of T-3

(nearest diffuser) is the smallest at

FL+100 and FL+1100, but the effect of

the floor diffusers in the opposite row

across the desks (T-6~10) is rather strong

at FL+1600. This shows the arrival of the

air supplied over the desks from the

opposite row of floor diffusers. The mean

age from the ceiling grilles is

comparatively small.

In the case of swirl flow settings of floor

diffusers, mean age of T-6~10 is not so

small as mean age of the diffusers on the

same row as the mannequin.

The mean age of ceiling grilles

is lager than most of mean age

of floor diffusers. From the

above, it is said that the

diffusers on the other side of

desks have less effect than the

diffusers on the same side as

the mannequin if the floor

diffusers are set to swirl flow.

The index of mean age,

however, indicates only the

time of arrival and does not

evaluate the amount of air

which arrived there.

0

200

400

600

800

1000

1200

1400

1600

0

200

400

600

800

1000

1200

1400

1600

0

200

400

600

800

1000

1200

1400

1600

0 200 400 600 800 100012000

0 200 400 600 80010001200

FL+1600

FL+1100

FL+100

FL+1600

FL+1100

FL+100

50

60

60

60

5040

5060

60

60

60

7070

70

70

70

80

8080 90

60 70

70 8080

90

8090

90

90

100

100

100

110

120

80

20

30

4050

50

6060

70 80

40

60

80

100 100

Swirl flowDirectional flow

Swirl flowDirectional flow

Swirl flowDirectional flow

[mm]

[mm]

[mm]

[mm] [mm]

T-3 T-3

T-3 T-3

T-3T-3

Unit : [s] Unit : [s]

Unit : [s] Unit : [s]

unit : [s] unit : [s]

GasEmission

GasEmission

GasEmission

Gasemission

Gasemission

Gasemission

Desk Desk

Desk Desk

Figure 11. Horizontal distribution of local

mean age of air for specific opening.

Directional flow setting Swirl flow setting

Gas emission Gas emission20

30

40

40

5050

5050

50

60

60

70

40

60

60

8080

80

100

100120

Unit : [s] Unit : [s]

30T-3 T-3

Figure 12. Vertical distribution of local mean age of air

for specific opening.

Page 7: Airflow Characteristics and Ventilation Effectiveness in

SVE4 of each supply openings at the front of

Figure 14 shows the ratio of SVE4 at three points in front of the mannequin (C4, C5, C6) for

both cases of directional flow setting and swirl flow setting. SVE4 is an index to evaluate the

relative strength of each supply opening at a certain point in the room. From this figure, the

floor diffuser T-3 has the largest ratio at FL+100 and FL+1100 when the floor diffuser is set

to directional flow. This corresponds to the result of local mean age of air seen in Fig.15. On

the other hand, SVE4 of ceiling grilles are quite small in the lower level. At FL+1600, the

values of the diffusers on the other side of desks T-6~10 are several times as large as the

diffusers on the mannequin side (T-1~5). Therefore, it is said that task zone will be formed

around sitting occupant by supplied air from the nearest diffuser (T-3) of directional flow

setting.

In the case of swirl flow setting, SVE4 of T-3 have larger values at any height, which means

the volume of task zone is a little larger than that of directional flow case. Anyway, in both

cases of directional flow case and swirl flow case, task zone is formed clearly around the

sitting occupants. In other word, task and ambient air conditioning system is maintained

regardless of occupant’s selection of flow type of floor diffusers.

0

20

40

60

80

100

120

140

160

Loc

al m

ean

age

for

spec

ific

ope

ning

[s]

Loc

al m

ean

age

for

spec

ific

ope

ning

[s]

Loc

al m

ean

age

for

spec

ific

ope

ning

[s]

0

20

40

60

80

100

120

140

160

0

20

40

60

80

100

120

140

160

T-1 T-2 T-3 T-4 T-5 T-6 T-7 T-8 T-9 T-10 A-1 A-2

Floor diffuser (T)Ceilinggrille(A)

Mannequin row Opposite rowFloor diffuser (T)

Ceilinggrille(A)

Mannequin row Opposite row

Floor diffuser (T)Ceilinggrille(A)

Mannequin row Opposite rowFloor diffuser (T)

Ceilinggrille(A)

Mannequin row Opposite row

Floor diffuser (T)Ceilinggriller(A)

Mannequin row Opposite rowFloor diffuser (T)

Ceilinggrille(A)

Mannequin row Opposite row

T-1 T-2 T-3 T-4 T-5 T-6 T-7 T-8 T-9 T-10 A-1 A-2

T-1 T-2 T-3 T-4 T-5 T-6 T-7 T-8 T-9 T-10 A-1 A-2

C4 (FL+1600mm)

C5 (FL+1100mm)

C6 (FL+100mm)

T-1 T-2 T-3 T-4 T-5 T-6 T-7 T-8 T-9 T-10 A-1 A-2 A-3

T-1 T-2 T-3 T-4 T-5 T-6 T-7 T-8 T-9 T-10 A-1 A-2 A-3

T-1 T-2 T-3 T-4 T-5 T-6 T-7 T-8 T-9 T-10 A-1 A-2 A-3

C4 (FL+1600mm)

C5 (FL+1100mm)

C6 (FL+100mm)

Directional flow

FL+1.6m

FL+1.1m

FL+0.1m

Swirl flow

Figure 13. Comparison of local mean age of air for different supply openings.

Page 8: Airflow Characteristics and Ventilation Effectiveness in

CFD ANALYSIS

CFD simulation was carried out with

standard k- model. Fluent ver.6.2 was

used for CFD code. Analyzed volume is

14,400 2,800 7,200mm3 as shown

in Fig.15. This space consists of eight

modules. The area of one module is

3,600 14,400 m2, and one module contains 4 desks, 2 illuminators and return slits, 4 person

simulators and 3.5 floor diffusers on average. As it is quite difficult to make the complex

shape of floor diffusers in CFD field, the boundary model of the velocity vector, k and were

input at the height of 350 mm above the floor (see Fig.16) based on the velocity measurement

using a hot-wire anemometer [7]. Instead of the floor diffusers, simple square openings were

installed on the floor. Velocity vector of ceiling grille is inclined to the left side by 45 degrees.

Three conditions were assumed. These are ambient (ceiling grilles) only, task and ambient

(the same as measurement), task (floor diffuser with diffusive flow) only. The flow rate of

each opening was decided so as to keep the room temperature 23.3 ºC if the room air is

T-1T-2

T-3T-4

T-5

A-1A-2

T-10

T-6

T-7

T-8

T-9

Opposite row (T6~10)

Mannequin row (T-1~5)

Ceiling grille

(A)

C4 (FL+1600)

FL+1.6m

T3

T-1

T-4T-5

T-6

T-7

T-8

T-9

T-10A-1 A-2

T-2Ceiling grille (A)

M

annequin nrow (T-1~5)

Opposite row (T6~10)

C5 (FL+1100)

FL+1.1m

Mannequin row (T-1~5)

Ceiling grille

(A)

C4 (FL+1600)

FL+1.6m

T-1T-2

T-3

T-4T-5T-6

T-7

T-8

T-9

T-10

A-1A-2

A-3

Opposite row (T6~10)

T-4

C5 (FL+1100)

Mannequin row (T-1~5)

Ceiling grille (A)

T-6~10

FL+1.1m

T-2

T-3

A-1~3T-1

T-5

C6 (FL+100)

Mannequin row (T1~5)

Floor diffuser (A)T-6~10

Ceil

ing grill

e (T-6~10)

T-1

T-2

T-3

T-4

T-5

A-1 A-2

FL+0.1m

Directional flow

C6 (FL+100)

Oppo

site row

(T) A-1~3

T-6~

10

FL+0.1m

T-2

T-3

T-1

T-5T-4

Mannequin row (T1~5)

Ceiling grille (A)

Swirl flow

Figure 14. Ratio of SVE4 in front of

the mannequin.

100

600

600

400

400

Square suppy opening

300

Blocks for virtual boundary

Figure 16. Boundary model for floor diffuser.

Swirl flow model Square supply opening

Illuminator Ceiling slit for return air

Notebook computer

Person simulator

Figure 15. Analyzed space by CFD.

Figure 17. Temperature distributions in the case

of ambient only, task and ambient, task only.

(1) Only ceiling grilles (260m3/h per one grille)

(3) Only floor diffusers (170m3/h per one diffuser)

(2) Task and ambient (110m3/h per one floor diffuser and 90 m3/h per one ceiling grille)

15

25

161718192021222324

[ºC]

Page 9: Airflow Characteristics and Ventilation Effectiveness in

perfectly mixed. Here, supply

temperature of floor diffuses is 21 ºC,

and the supply temperature of ceiling

grilles is 18 ºC.

Figure 17 shows the temperature

distributions in section under three

conditions. In the case of ceiling

diffusers only, there can be seen rather

large temperature decline from the right

to the left. This horizontal distribution is

caused by the inclined flow direction of

ceiling grilles. The temperature

distribution of task and ambient is so

similar to the case of floor diffusers

only, and there is a clear task zone

around each occupant. From Figure 18, there is large velocity at the back of all occupants,

which may cause draught to occupants and bring thermal discomfort. Therefore, it is said that

the task and ambient air conditioning system is the most comfortable and energy saving

system among three in respect of the environment around occupants.

DISCUSSION

As a result of the measurement in a real office room with task and ambient air conditioning

system, the existence of task zone around the occupants were confirmed by the distribution of

temperature, local mean age of air for specific opening and SVE4. The flow selection of floor

diffusers turned out to be effective in order to control the personal thermal sensation of each

occupant. From the CFD analysis, the priority of this system to ceiling supply and floor

supply system was made clear.

The assessment from the view point of energy consumption will be needed, and the boundary

model for the floor diffuser used for CFD should be verified and improved for wider

application of this method to the design process of this kind of air conditioning system.

ACKNOWLEDGEMENT

The authors would like to thank Ms. Machiko Kuise and Mr. Shogo Takeda for helping us

with the experiment and analyzing the data.

REFERENCES

1. Ushio, T, Sagara, K, Yamanaka, T, Kotani, H, et al. 2006. Task Ambient Air Conditioning

System with Natural Ventilation for High Rise Office Building (Part 1: Outline of System and

Thermal Environment in Working Zone). 2006. Proceedings of Healthy Buildings 2006, Vol.4,

pp.269-274.

2. Kotani, H, Sagara, K, Yamanaka, T, Kuise, M, et al. 2006. Task Ambient Air Conditioning

System with Natural Ventilation for High Rise Office Building (Part 2: Measurement of Natural

Ventilation Rate and CFD Analysis using Measured Data). Proceedings of Healthy Buildings

2006, Vol.5, pp.135-140.

3. Sandberg, M. 1983. Ventilation Efficiency as a Guide to Design, ASHRAE Transactions, Part

2B, pp.455-477.

(1) Only ceiling grilles (260m3/h per one grille)

(3) Only floor diffusers (170m3/h per one diffuser)

(2) Task and ambient (110m3/h per one floor diffuser and 90 m3/h per one ceiling grille)

0

1.0

0.10.20.30.40.50.60.70.80.9

[m/s]

Figure 18. Velocity distributions in the case of

ambient only, task and ambient, task only.

Page 10: Airflow Characteristics and Ventilation Effectiveness in

4. Etheridge, D, Sandberg, M. 1996. BUILDING VENTILATION Theory and Measurement :

John Wiley & Sons.

5. Kato, S, Murakami, S, Kobayashi H. 1992. Preprints of International Symposium on Room Air

Convection and Ventilation Effectiveness (ISRACVE), pp.321-322

6. Lim, E, Sagara, K, Yamanaka, T, Kotani, H, et al. 2007. Airflow Characteristics in Room with

Hybrid Air-conditioning System of Task Air Supply and Natural Ventilation, ROOMVENT

2007

7. Kuise, M, Sagara, K, Yamanaka, T, Kotani, H, et al.2005. Indoor Air Quality and Thermal

Environment in Room with Task Ambient Air Conditioning System with Natural Ventilation

(Part 3. Airflow Modeling of Under-floor Air Supply Opening for CFD Simulation). Technical

Papers of Annual Meeting, The Society of Heating , Air-Conditioning and Sanitary Engineers of

Japan, pp.1029-1032. (in Japanese)