AIR-HANDLING-UNITAT4 COMPLIANT WITH EUGUIDELINE ATEX 95
SAFETY CERTIFIED QUALITY
AIR-HANDLING-UNITS
8/9/2019 Al-ko Prospekt At4-Atex Engl
http://slidepdf.com/reader/full/al-ko-prospekt-at4-atex-engl 2/4
ATEX 95 unit categories
According to the ATEX guideline (94 / 9 /
EG), units are grouped into categories
for use in the corresponding zones.
There are three different unit categories
for the unit group II, which correspond
to the different zones. This makes it
possible to associate explosion-proof
products with operational Ex zones.
Category 1 includes units for zones 0
and 20 (very high degree of safety).
AT4-classification
Category 2 includes units that are struc-
turally designed so that they can be
operated in compliance with the para-
meters furnished by the manufacturer
and assure a high degree of safety. Units
of this category can, upon approval, be
operated in zones 1 and 21.
Category 3 includes units that are struc-
turally designed so that they can be
operated in compliance with the para-
meters furnished by the manufacturer
and assure a normal degree of safety.
Units of this category can, upon appro-
val, be operated in zones 2 and 22. DIN
EN 50281-1-2 differentiates between
conductive and nonconductive dust.
When there is conductive dust in zone
22, equipment from category 2 D must
be used.
EX-suitable unit components
I EX models of direct-driven fans for
zone 1 to T4 or 21 to T 120 °C com-
bined with a pressure-tight encapsu-
lated motor
I belt-driven EX fans for only zone 2
and temperature class T3!
I electrically conductive fan drive belt
I flexible connection made of electric-ally conductive material
I air filter cannot be statically charged
– for Explosionsgroups (IIA – IIC)
I inspection portholes made of glass
I drip eliminator cannot be statically
charged – new development
I all electrical components ATEX-
certified, all mechanical components
with manufacturer confirmation
I unit construction is completely
earthed
I earthing of louvre damper vanes
I run around coil system or plate heat
exchanger can be used for heat
recovery
CE II 2G / D c IIC T4 (x)
8/9/2019 Al-ko Prospekt At4-Atex Engl
http://slidepdf.com/reader/full/al-ko-prospekt-at4-atex-engl 3/4
Unit situated inside the EX-zone
I dischargeable flexible connection
I earthed damper vanes
I electrically conductive filter G4 – H13
I heat recovery provided by a run
around coil system or heat recovery
I electrically conductive droplet eliminatorI EX models of direct-driven fans for zone
1 to T4 or 21 to T 120 °C combined with
a pressure-tight encapsulated motor
I belt-driven EX ventilators only for zone
2 and temperature class T3
I drive motor encapsulated in pressure-
tight fashion with FC = frequency
converter operation
I sound absorber
I weatherproof grille at exhaust
Unit design 1
Exhaust air unit situated outside
EX-zone
Same components as in unit design 1
Unit design 2
Intake and exhaust air unit situated
inside the EX-zone
I intake and exhaust air units must
be EX-models
I all electrical components must be
EX- models
Unit arrangement
Intake and exhaust air unit situated
outside the EX-zone
I exhaust air unit must be an EX-model
I intake air unit (EX-model not required)
with louvre damper at air outlet to
prevent return flow
I electrical components situated
outside the EX-zone do not have to be
EX-models
for zone 1, T3 to T4,
or zone 21 to T 120 °C
for zone 2, T3