amana hvac ac manual

189
RS6200002 Revision 1 March 1997 Model and Manufacturing numbers listed on page 5 This manual is to be used by qualified HVAC technicians only. Amana does not assume any responsibility for property damage or personal injury for improper service proce- dures done by an unqualified person. Service Instructions RHA, RHD & RHE Model Remote Heat Pumps Blowers, Coils & Accessories

Upload: eden-abdula

Post on 27-Oct-2015

2.388 views

Category:

Documents


115 download

DESCRIPTION

Manual for the Amana HVAC AC Unit

TRANSCRIPT

  • RS6200002Revision 1

    March 1997

    Model and Manufacturingnumbers listed on page 5

    This manual is to be used by qualified HVACtechnicians only. Amana does not assumeany responsibility for property damage orpersonal injury for improper service proce-dures done by an unqualified person.

    ServiceInstructionsRHA, RHD & RHE ModelRemote Heat PumpsBlowers, Coils & Accessories

  • INDEX

    PRODUCT IDENTIFICATION ............................................................................... 5 - 7

    SPECIFICATIONSRHA Models ................................................................................................. 8 - 9RHD Models ................................................................................................ 10Air Handlers ................................................................................................. 11 - 15Evaporator Coils .......................................................................................... 16 - 22

    PRODUCT DESIGN .............................................................................................. 23 - 25

    SYSTEM OPERATIONRefrigeration Cycle ...................................................................................... 26 - 28Sequence of Operation ................................................................................ 28 - 30Electric Heaters ........................................................................................... 31

    BLOWER PERFORMANCE DATA ........................................................................ 32 - 33

    COIL PRESSURE DROP DATA............................................................................ 34 - 35

    EXPANDED PERFORMANCE DATARHA Models ................................................................................................. 36 - 84RHD/RHE Models ........................................................................................ 85 - 105Performance Test ........................................................................................ 106

    SCHEDULED MAINTENANCE ............................................................................. 107

    SERVICING ........................................................................................................... 107 - 132

    WIRING DIAGRAMSFossil Fuel Kits ............................................................................................ 133Condensing Units......................................................................................... 134 - 144BHA Blower Coils & Cabinets ...................................................................... 145 - 146BHA Electric Heater Kits .............................................................................. 147 - 158BBA/BBC Blower Cabinets .......................................................................... 159 - 160BBA/BBC Electric Heater Kits ...................................................................... 161 - 189

    WIRING SCHEMATICS......................................................................................... 186 - 189

    2

  • 3IMPORTANT INFORMATIONPride and workmanship go into every product to provide our customers with quality products. It is possible, however,that during its lifetime a product may require service. Products should be serviced only by a qualified servicetechnician who is familiar with the safety procedures required in the repair and who is equipped with the proper tools,parts, testing instruments and the appropriate service manual. REVIEW ALL SERVICE INFORMATION IN THEAPPROPRIATE SERVICE MANUAL BEFORE BEGINNING REPAIRS.

    IMPORTANT NOTICES FOR CONSUMERS AND SERVICERS

    IF REPAIRS ARE ATTEMPTED BY UNQUALIFIED PERSONS, DANGER-OUS CONDITIONS (SUCH AS EXPOSURE TO ELECTRICAL SHOCK) MAYRESULT. THIS MAY CAUSE SERIOUS INJURY OR DEATH.

    AMANA WILL NOT BE RESPONSIBLE FOR ANY INJURY OR PROPERTYDAMAGE ARISING FROM IMPROPER SERVICE OR SERVICE PROCE-

    DURES. IF YOU PERFORM SERVICE ON YOUR OWN PRODUCT, YOU ASSUME RESPONSIBILITY FORANY PERSONAL INJURY OR PROPERTY DAMAGE WHICH MAY RESULT.

    To locate an authorized servicer, please consult your telephone book or the dealer from whom you purchased thisproduct. For further assistance, please contact:

    CONSUMER AFFAIRS DEPT. OR 1-319-622-5511AMANA REFRIGERATION, INC. CALL and ask forAMANA, IOWA 52204 Consumer Affairs

    If outside the United States contact:AMANA REFRIGERATION, INC.ATTN: INTERNATIONAL DIVISIONAMANA, IOWA 52204, USATELEX: 4330076 AMANACABLE: "AMANA", AMANA, IOWA, USA

    RECOGNIZE SAFETY SYMBOLS, WORDS AND LABELS

    DANGER - Immediate hazards which WILL result insevere personal injury or death.

    WARNING - Hazards or unsafe practices which COULDresult in severe personal injury or death.

    CAUTION - Hazards or unsafe practices which COULDresult in minor personal injury or product or property damage.

    WARNINGWARNING

    DANGER

    CAUTION

    WARNINGWARNING

    CAUTION

  • IMPORTANT INFORMATION

    WARNINGWARNINGSYSTEM CONTAMINANTS, IMPROPER SERVICE PROCEDURE AND/OR PHYSICAL ABUSE AFFECTINGHERMETIC COMPRESSOR ELECTRICAL TERMINALS MAY CAUSE DANGEROUS SYSTEM VENTING.

    System contaminants, improper Service Procedure and/or physical abuse affecting hermetic compressor electricalterminals may cause dangerous system venting.

    The successful development of hermetically sealed refrigeration compressors has completely sealed the compressor'smoving parts and electric motor inside a common housing, minimizing refrigerant leaks and the hazards sometimesassociated with moving belts, pulleys, or couplings.

    Fundamental to the design of hermetic compressors is a method whereby electrical current is transmitted to thecompressor motor through terminal conductors which pass through the compressor housing wall. These terminals aresealed in a dielectric material which insulates them from the housing and maintains the pressure tight integrity of thehermetic compressor. The terminals and their dielectric embedment are strongly constructed, but are vulnerable tocareless compressor installation or maintenance procedures and equally vulnerable to internal electrical short circuitscaused by excessive system contaminants.

    In either of these instances, an electrical short between the terminal and the compressor housing may result in the lossof integrity between the terminal and its dielectric embedment. This loss may cause the terminals to be expelled, therebyventing the vaporous and liquid contents of the compressor housing and system.

    A venting compressor terminal normally presents no danger to anyone providing the terminal protective cover is properlyin place.

    If, however, the terminal protective cover is not properly in place, a venting terminal may discharge a combination of

    (a) hot lubricating oil and refrigerant

    (b) flammable mixture (if system is contaminated with air)

    in a stream of spray which may be dangerous to anyone in the vicinity. Death or serious bodily injury could occur.

    Under no circumstances is a hermetic compressor to be electrically energized and/or operated without having the terminalprotective cover properly in place.

    See Service Section S-17 for proper servicing.

    4

  • PRODUCT IDENTIFICATION

    5 Rev. 1

    The model and manufacturing number are used for positive identification of component parts used in manufacturing. Atwhich time engineering and manufacturing changes take place where interchangeability of components are affected, themanufacturing number will change.It is very important to use the model and manufacturing numbers at all times when requesting service or parts information.

    RHA18A2A P1180201CRHA24A2A P1180202CRHA30A2A P1180203CRHA36A2A P1180204CRHA36A3A P1180205CRHA36A4A P1180211CRHA42A2A P1180206CRHA48A2A P1180207CRHA48A3A P1180208CRHA48A4A P1180212CRHA60A2A P1180209CRHA60A3A P1180210CRHA60A4A P1180213C

    RHA18A2B P1180217CRHA24A2B P1180218CRHA30A2B P1180219CRHA36A2B P1180220CRHA36A3B P1180221CRHA36A4B P1180222CRHA42A2B P1180223CRHA48A2B P1180214CRHA48A3B P1180215CRHA48A4B P1180216CRHA60A2B P1180224CRHA60A3B P1180225CRHA60A4B P1180226C

    MODEL M/NRHA18A2B P1218801CRHA24A2B P1218802CRHA30A2B P1218803CRHA36A2B P1218804CRHA36A3B P1218805CRHA36A4B P1218806CRHA42A2B P1218807CRHA48A2B P1218808CRHA48A3B P1218809CRHA48A4B P1218810CRHA60A2B P1218811CRHA60A3B P1218812CRHA60A4B P1218813C

    RHD18A2A P1188001CRHD24A2A P1188002CRHD30A2A P1188003CRHD36A2A P1188004CRHD42A2A P1188005CRHD48A2A P1188006CRHD60A2A P1188007C

    RHE18A2A P1217401CRHE24A2A P1217402CRHE30A2A P1217403CRHE36A2A P1217404CRHE42A2A P1217405CRHE48A2A P1217406CRHE60A2A P1217407C

    RHE18A2A P1219101CRHE24A2A P1219102CRHE30A2A P1219103CRHE36A2A P1219104CRHE42A2A P1219105CRHE48A2A P1219106CRHE60A2A P1219107C

    BHA18FA002A P1180301CBHA24FA002A P1180302CBHA30FA002A P1180303CBHA36FA002A P1180304CBHA42FA002A P1180305CBHA48TA002A P1180306CBHA60TA002A P1180307CBHA24TB002A P1188102CBHA30TB002A P1188103CBHA36TB002A P1188104CBHA42TB002A P1188105CBHA48TB002A P1188106CBHA60TB002A P1188107CBBA24A2A P1206401CBBA36A2A P1206402CBBA48A2A P1206403CBBA60A2A P1206404CBBC36A2A P1206405CBBC60A2A P1206406C

    CCA18FUA P1111004CCCA30FUA P1111005CCCA36FUA P1111001CCCA42FUA P1111002CCCA60FUA P1111007CCCA18FCC P1203901CCCA24FCC P1203902CCCA30FCC P1203903CCCA36FCC P1203904CCCA42FCC P1203905CCCA48FCC P1203906CCCA54FCC P1203907CCCA57FCC P1203908CCCA60FCC P1203909CCCA30FDC P1203910CCCA36FDC P1203911CCCA42FDC P1203912CCCA48FDC P1203913CCCD16A22 P1203914CCCD20A22 P1203915CCCD24A26 P1203916CCCA36FKC P1203917C

    CCA18FSC P1204001CCCA24FSC P1204002CCCA30FSC P1204003CCCA36FSC P1204004CCCA42FSC P1204005CCCA48FSC P1204006CCCA54FSC P1204007CCCA57FSC P1204008CCCA60FSC P1204009CCCF24FCC P1210901CCCF30FCC P1210902CCCF36FCC P1210903CCCF42FCC P1210904CCCF48FCC P1210905CCCF60FCC P1210906CCCF61FCC P1210907CCCF24FDC P1210908CCCF36FDC P1210909CCCF48FDC P1210910CCHF18TCC P1210911CCHF24TCC P1210912CCHF30TCC P1210913CCHF36TCC P1210914CCHF42TCC P1210915CCHF48TCC P1210916C

    CHA18TUA P1124901CCHA24TUA P1124902CCHA30TUA P1124903CCHA36TUA P1124904CCHA42TUA P1124905CCHA48TUA P1124906CCHA57TUA P1124907CCHA60TUA P1124908CCHA18TCC P1203801CCHA24TCC P1203802CCHA30TCC P1203803CCHA36TCC P1203804CCHA42TCC P1203805CCHA48TCC P1203806CCHA54TCC P1203807CCHA57TCC P1203808CCHA60TCC P1203809CCHA18TSC P1204101CCHA24TSC P1204102CCHA30TSC P1204103CCHA36TSC P1204104CCHA42TSC P1204105CCHA48TSC P1204106CCHA54TSC P1204107CCHA57TSC P1204108CCHA60TSC P1204109C

    CCH24FCC P1203301CCCH30FCC P1203302CCCH36FCC P1203303CCCH48FCC P1203305CCCH60FCC P1203306CCCH24FCD P1210101CCCH30FCD P1210102CCCH36FCD P1210103CCCH48FCD P1210105CCCH60FCD P1210106CCHH24TCC P1203501CCHH30TCC P1203502CCHH36TCC P1203503CCHH48TCC P1203505CCHH60TCC P1203506CCHH24TCD P1210107CCHH30TCD P1210108CCHH36TCD P1210109CCHH48TCD P1210110C

    MODEL M/N MODEL M/N MODEL M/N

    John

    John

  • PRODUCT IDENTIFICATION

    6 Rev. 1

    Design SeriesA: First Series

    Voltage2: 230v/60Hz/1ph3: 230v/60Hz/3ph4: 460v/60Hz/3ph

    Nominal Capacity18: 18000 BTUH24: 24000 BTUH30: 30000 BTUH36: 36000 BTUH42: 42000 BTUH48: 48000 BTUH60: 60000 BTUH

    R H A 24 A 2 AProductTypeR: Remote

    System TypeC: CoolingH: Heat Pump

    Product FamilyA: 10 SEERB: 10 SEERC: 12 SEERD: 13 SEERE: 14 SEER

    Marketing DesignatorA: Standard LineB: Multi Speed

    ASC01A P1200601C Anti Short Cycle Control KitsBDK01A P1207001C Blower Delay KitFFK02A P1122302C Fossil Fuel KitHSKxxA P11800xxC Hard Start KitsLAC__A P11801__C Low Ambient Control KitLSK01A P1206901C Liquid Line Solenoid KitPCK01A P1180101C Pressure Control KitPCK02A P1180104C Pressure Control KitSPK__A P12088__C Single Point Wiring kit for use with EHK-B & ECB-B heater kitsTXV__A P12065__C Thermostatic Expansion Valve Kits Used to convert FSC coils to TSC coils

    EHK__A P11872__C Electric Heater Kits for use with BCA & BHA 1 piece blower cabinetsEHK__B P12063__C Electric Heater Kits for use with BBA & BBC 2 piece blower cabinets w/o BreakersECB__B P12063__C Electric Heater Kits for use with BBA & BBC 2 piece blower cabinets w/ Breakers

    Note : Circuit Breakers are not included in EHK-B heater kits. ECB-B heater kits include breakers and mounting hardware

  • PRODUCT IDENTIFICATION

    7 Rev. 1

    Design SeriesA: First Series

    Product TypeB: Blower Coil

    SystemTypeC: CoolingH: Heat Pump

    Coil TypeA: "A" CoilS: Slab Coil

    Nominal Capacity18: 18000 BTUH24: 24000 BTUH30: 30000 BTUH36: 36000 BTUH42: 42000 BTUH48: 48000 BTUH60: 60000 BTUH

    Expansion DeviceC: CapillaryT: Thermostatic Exp. ValveF: Flowrator (Orifice)

    Drive TypeA: StandardB: High Efficiency

    Factory Heat00: 0 KW

    Voltage1: 115v/60Hz/1ph2: 230v/60Hz/1ph

    B H A 24 T A 00 2 A

    C H A 24 T U ADesign SeriesA: First Series

    ProductTypeC: Coil

    System TypeC:CoolingH:Heat Pump or

    Hi Efficiency

    Nominal Capacity18: 18000 BTUH24: 24000 BTUH30: 30000 BTUH36: 36000 BTUH42: 42000 BTUH48: 48000 BTUH60: 60000 BTUH

    ConfigurationA: "A" CoilH:Horizontal Coil - SlabF: Horizontal Coil - "A"

    System TypeC: CasedU: UncasedS: Stand-alone (Uncased)

    Expansion DeviceC: Capillary TubeF: Flowrator (Orifice)T: TXV (Expansion Valve)

    John

    John

    John

    John

    John

    John

  • CONDENSING UNIT SPECIFICATIONS

    8 Rev. 1

    NOTE: This data is provided as a guide, it is important to electrically connect the unit and properlysize fuses/circuit breakers and wires in accordance with all national and/or local electrical codes. Usecopper wire only.

    * Unit has 7/8" connection. Use of 7/8" vapor line will decrease performance by 3-4%.

    MODEL RHA18A2A RHA24A2A RHA30A2A RHA36A2A RHA42A2A RHA48A2A RHA60A2ACOOLING CAPACITY, BTUH 18000 24000 30000 36000 42000 48000 60000COMPRESSOR R.L. AMPS 10.5 13.1 14.4 17.7 21.7 25.8 33.6 L.R. AMPS 50.0 61.0 71.0 96.0 102.0 118.0 141.0CONDENSER FAN MOTOR HORSEPOWER 1/12 1/6 1/6 1/6 1/6 1/3 1/3 R.L. AMPS 0.6 1.1 1.1 1.1 1.1 2.3 2.3 L.R. AMPS 1.2 2.1 2.1 2.1 2.1 3.6 3.6LIQUID LINE, INCHES O.D. 3/8 3/8 3/8 3/8 3/8 3/8 3/8SUCTION LINE, INCHES O.D. 5/8 3/4 3/4 3/4 7/8 7/8 1 1/8*REFRIGERANT CHARGE 81.2 oz. 108.5 oz. 159.8 oz. 187.9 oz. 216.3 oz. 247.0 oz. 253.2 oz.POWER SUPPLY 208/230-60-1 208/230-60-1 208/230-60-1 208/230-60-1 208/230-60-1 208/230-60-1 208/230-60-1 MIN.CIRCUIT AMPACITY 13.7 17.5 19.1 23.2 28.2 34.6 44.3 MAX. OVERCURRENT DEVICE 20 30 30 40 50 60 60

    ELECT. CONDUIT SIZE POWER SUPPLY 1/2" or 3/4" 1/2" or 3/4" 1/2" or 3/4" 1/2" or 3/4" 1/2" or 3/4" 1/2" or 3/4" 1/2" or 3/4" LOW VOLTAGE 1/2" 1/2" 1/2" 1/2" 1/2" 1/2" 1/2"APPROX. SHIPPING WT 152 194 221 230 246 309 322

    MODEL RHA36A3A RHA36A4A RHA48A3A RHA48A4A RHA60A3A RHA60A4ACOOLING CAPACITY, BTUH 36000 36000 48000 48000 60000 60000COMPRESSOR R.L. AMPS 10.9 5.5 14.9 7.5 20.5 10.5 L.R. AMPS 75.0 40.0 90.0 45.0 110.0 55.0CONDENSER FAN MOTOR HORSEPOWER 1/6 1/6 1/3 1/3 1/3 1/3 R.L. AMPS 1.1 0.6 2.3 1.1 2.3 1.1 L.R. AMPS 2.1 1.2 3.6 1.9 3.6 1.9LIQUID LINE, INCHES O.D. 3/8 3/8 3/8 3/8 3/8 3/8SUCTION LINE, INCHES O.D. 3/4 3/4 7/8 7/8 1 1/8* 1 1/8*REFRIGERANT CHARGE 187.9 oz. 187.9 oz. 247.0 oz. 247.0 oz. 253.2 oz. 253.2 oz.POWER SUPPLY 208/230-60-3 460-60-3 208/230-60-3 460-60-3 208/230-60-3 460-60-3 MIN.CIRCUIT AMPACITY 14.7 7.5 20.9 10.5 27.9 14.2 MAX. OVERCURRENT DEVICE 25 15 35 15 45 25

    ELECT. CONDUIT SIZE POWER SUPPLY 1/2" or 3/4" 1/2" or 3/4" 1/2" or 3/4" 1/2" or 3/4" 1/2" or 3/4" 1/2" or 3/4" LOW VOLTAGE 1/2" 1/2" 1/2" 1/2" 1/2" 1/2"APPROX. SHIPPING WT 230 230 309 309 322 322

  • CONDENSING UNIT SPECIFICATIONS

    9 Rev. 1

    NOTE: This data is provided as a guide, it is important to electrically connect the unit and properlysize fuses/circuit breakers and wires in accordance with all national and/or local electrical codes. Usecopper wire only.

    MODEL RHA18A2B RHA24A2B RHA30A2B RHA36A2B RHA42A2B RHA48A2B RHA60A2BCOOLING CAPACITY, BTUH 18000 24000 30000 36000 42000 48000 60000COMPRESSOR R.L. AMPS 9.3 11.1 13.7 16.1 19.1 23.4 28.4 L.R. AMPS 49.0 61.0 75.0 96.0 102.0 110.0 170.0CONDENSER FAN MOTOR HORSEPOWER 1/12 1/12 1/12 1/8 1/6 1/4 1/4 R.L. AMPS 0.6 0.6 0.6 1.1 1.1 1.6 1.7 L.R. AMPS 1.2 1.2 1.0 2.1 2.1 2.7 3.3LIQUID LINE, INCHES O.D. 3/8 3/8 3/8 3/8 3/8 3/8 3/8SUCTION LINE, INCHES O.D. 5/8 3/4 3/4 3/4 7/8 7/8 1 1/8*REFRIGERANT CHARGE 92.0 oz. 89.0 oz. 97.0 oz. 105.0 oz. 150.0 oz. 163.0 oz. 159.0 oz.POWER SUPPLY 208/230-60-1 208/230-60-1 208/230-60-1 208/230-60-1 208/230-60-1 208/230-60-1 208/230-60-1 MIN.CIRCUIT AMPACITY 12.3 14.5 17.7 21.5 25.0 30.9 37.2 MAX. OVERCURRENT DEVICE 25 25 30 35 40 50 60

    ELECT. CONDUIT SIZE POWER SUPPLY 1/2" or 3/4" 1/2" or 3/4" 1/2" or 3/4" 1/2" or 3/4" 1/2" or 3/4" 1/2" or 3/4" 1/2" or 3/4" LOW VOLTAGE 1/2" 1/2" 1/2" 1/2" 1/2" 1/2" 1/2"APPROX. SHIPPING WT 150 153 170 178 215 274 277

    MODEL RHA36A3B RHA36A4A RHA48A3B RHA48A4B RHA60A3B RHA60A4BCOOLING CAPACITY, BTUH 36000 36000 48000 48000 60000 60000COMPRESSOR R.L. AMPS 10.2 4.3 12.2 7.0 16.0 7.9 L.R. AMPS 75.0 40.0 90.0 46.0 124.0 59.6CONDENSER FAN MOTOR HORSEPOWER 8-Jan 1/6 1/4 1/3 1/4 1/4 R.L. AMPS 1.1 0.6 1.6 1.1 1.7 0.9 L.R. AMPS 2.1 1.2 2.7 1.9 3.3 1.5LIQUID LINE, INCHES O.D. 3/8 3/8 3/8 3/8 3/8 3/8SUCTION LINE, INCHES O.D. 3/4 3/4 7/8 7/8 1 1/8* 1 1/8*REFRIGERANT CHARGE 105.0 oz. 105.0 oz. 163.0 oz. 163.0 oz. 159.0 oz. 159.0 oz.POWER SUPPLY 208/230-60-3 460-60-3 208/230-60-3 460-60-3 208/230-60-3 460-60-3 MIN.CIRCUIT AMPACITY 13.9 6.5 16.9 9.9 21.7 11.0 MAX. OVERCURRENT DEVICE 25 15 25 15 35 15

    ELECT. CONDUIT SIZE POWER SUPPLY 1/2" or 3/4" 1/2" or 3/4" 1/2" or 3/4" 1/2" or 3/4" 1/2" or 3/4" 1/2" or 3/4" LOW VOLTAGE 1/2" 1/2" 1/2" 1/2" 1/2" 1/2"APPROX. SHIPPING WT 178 178 274 274 277 277

  • CONDENSING UNIT SPECIFICATIONS

    10 Rev. 1

    NOTE: This data is provided as a guide, it is important to electrically connect the unit and properlysize fuses/circuit breakers and wires in accordance with all national and/or local electrical codes. Usecopper wire only.

    * Unit has 7/8" connection. Use of 7/8" vapor line will decrease performance by 3-4%.

    MODEL RHD18A2A RHD24A2A RHD30A2A RHD36A2A RHD42A2A RHD48A2A RHD60A2ACOOLING CAPACITY, BTUH 18000 24000 30000 36000 42000 48000 60000COMPRESSOR R.L. AMPS 9.6 12.1 13.5 16.0 17.9 24.9 28.8 L.R. AMPS 50.0 62.5 72.5 88.0 104.0 129.0 169.0CONDENSER FAN MOTOR HORSEPOWER 1/12 1/6 1/6 1/6 1/4 1/3 1/3 R.L. AMPS 0.6 1.1 1.1 1.1 1.6 2.3 2.3 L.R. AMPS 1.2 2.1 2.1 2.1 3.0 3.6 3.6LIQUID LINE, INCHES O.D. 3/8 3/8 3/8 3/8 3/8 3/8 3/8SUCTION LINE, INCHES O.D. 5/8 3/4 3/4 3/4 7/8 7/8 1 1/8*REFRIGERANT CHARGE 118.0 oz. 127.0 oz. 189.0 oz. 191.0 oz. 199.0 oz. 242.0 oz. 288.0 oz.POWER SUPPLY 208/230-60-1 208/230-60-1 208/230-60-1 208/230-60-1 208/230-60-1 208/230-60-1 208/230-60-1 MIN.CIRCUIT AMPACITY 12.6 16.2 27.1 21.1 24.0 33.3 38.2 MAX. OVERCURRENT DEVICE 20 25 30 35 40 50 60

    ELECT. CONDUIT SIZE POWER SUPPLY 1/2" or 3/4" 1/2" or 3/4" 1/2" or 3/4" 1/2" or 3/4" 1/2" or 3/4" 1/2" or 3/4" 1/2" or 3/4" LOW VOLTAGE 1/2" 1/2" 1/2" 1/2" 1/2" 1/2" 1/2"APPROX. SHIPPING WT 184 184 211 220 236 299 312

    MODEL RHE18A2A RHE24A2A RHE30A2A RHE36A2A RHE42A2A RHE48A2A RHE60A2ACOOLING CAPACITY, BTUH 18000 24000 30000 36000 42000 48000 60000COMPRESSOR R.L. AMPS 9.6 12.1 13.5 16.0 21.9 24.9 28.8 L.R. AMPS 50.0 62.5 72.5 88.0 104.0 129.0 169.0CONDENSER FAN MOTOR HORSEPOWER 1/12 1/6 1/6 1/6 1/4 1/3 1/3 R.L. AMPS 0.6 1.1 1.1 1.1 1.6 2.3 2.3 L.R. AMPS 1.2 2.1 2.1 2.1 3.0 3.6 3.6LIQUID LINE, INCHES O.D. 3/8 3/8 3/8 3/8 3/8 3/8 3/8SUCTION LINE, INCHES O.D. 5/8 3/4 3/4 3/4 7/8 7/8 1 1/8*REFRIGERANT CHARGE 115.0 oz. 127.0 oz. 189.5 oz. 191.0 oz. 199.0 oz. 242.0 oz. 288.0 oz.POWER SUPPLY 208/230-60-1 208/230-60-1 208/230-60-1 208/230-60-1 208/230-60-1 208/230-60-1 208/230-60-1 MIN.CIRCUIT AMPACITY 12.6 16.2 18.1 21.1 29.0 33.3 38.2 MAX. OVERCURRENT DEVICE 20 25 30 35 45 50 60

    ELECT. CONDUIT SIZE POWER SUPPLY 1/2" or 3/4" 1/2" or 3/4" 1/2" or 3/4" 1/2" or 3/4" 1/2" or 3/4" 1/2" or 3/4" 1/2" or 3/4" LOW VOLTAGE 1/2" 1/2" 1/2" 1/2" 1/2" 1/2" 1/2"APPROX. SHIPPING WT 166 180 218 221 238 314 345

  • 11 Rev. 1

    * With field installed electric heater kits.

    ** CAUTIONRefer to heater kit installation manual for minimum circuit ampacity and maximum overcurrent protectiondevice size with heaters installed. Also refer to unit nameplate.While this data is presented as a guide, it is important to electrically connect the unit, properly size fuses or overcurrent devices and wiresin accordance with the National Electric Code, the Canadian Electrical Code, and/or all existing local codes.

    NOTE: The BCA, BHA-TA, & BHA-TB blowers include non-bleed TXV's: any single phase reciprocatingcompressor used with these models must include hard start components.

    NOTE: Installer must supply refrigerant lines and adaptors (if needed) based on the requirements of the outdoorunit.

    BCA/BHA BLOWER COIL SPECIFICATIONS

    MODEL BHA18FA002ABHA24FA

    002ABHA30FA

    002ABHA36FA

    002ABHA42FA

    002ABHA48TA

    002ABHA60TA

    002A

    CLG CAPACITY NOMINAL BTUH 18,000 24,000 30,000 36,000 42,000 48,000 60,000EVAPORATOR COIL FACE AREA, SQ FT 3.8 4.7 4.7 4.7 4.7 5.6 5.6 ROWS DEEP 2 2 2 3 3 3 3 FINS/INCH 14 14 14 14 14 14 14BLOWER WHEEL D x W 9 X 6 9 X 8 10 X 7 10 X 8 10 X 9 10 X 10 11 X 10BLOWER MOTOR HORSEPOWER 1/6 1/4 1/4 1/4 1/3 0 1 FULL LOAD AMPS 1.0 1.1 2.0 2.0 3.1 3.1 3.6 RATED CFM 600 850 1000 1175 1400 1650 1800 EXT.STATIC PRESS (WC), MAX* 0.3 0.3 0.4 0.3 0.4 0.45 0.35DRAIN LINE SIZE, MAIN 3/4" FPT 3/4" FPT 3/4" FPT 3/4" FPT 3/4" FPT 3/4" FPT 3/4" FPTDRAIN LINE SIZE, AUX 3/4" FPT 3/4" FPT 3/4" FPT 3/4" FPT 3/4" FPT 3/4" FPT 3/4" FPTLIQUID LINE, INCHES 3/8 3/8 3/8 3/8 3/8 3/8 3/8SUCTION LINE, INCHES 5/8 34397 3/4 3/4 34523 7/8 7/8REFRIG. EXP. DEVICE AS SHIPPED .054 RES. .061 RES. .072 RES. .076 RES. .081 RES TEV TEVPOWER SUPPLY (w/o Heater Kits)** 208/230-60-1 208/230-60-1 208/230-60-1 208/230-60-1 208/230-60-1 208/230-60-1 208/230-60-1

    MIN. CIRCUIT AMPACITY 1.3 1.4 2.5 2.5 3.9 3.9 4.5 MAX. OVERCURRENT DEVICE 15 15 15 15 15 15 15ELECT. ENTRANCE SIZE POWER SUPPLY 1 3/32" 1 3/32" 1 3/32" 1 3/32" 1 3/32" 1 3/32" 1 3/32" LOW VOLTAGE 7/8" 7/8" 7/8" 7/8" 7/8" 7/8" 7/8"APPROX. SHIPPING WT (LBS) 130 135 140 150 190 220 225

  • 12 Rev. 1

    * With field installed electric heater kits.

    ** CAUTIONRefer to heater kit installation manual for minimum circuit ampacity and maximum overcurrent protectiondevice size with heaters installed. Also refer to unit nameplate.While this data is presented as a guide, it is important to electrically connect the unit, properly size fuses or overcurrent devices and wiresin accordance with the National Electric Code, the Canadian Electrical Code, and/or all existing local codes.

    NOTE: The BCA, BHA-TA, & BHA-TB blowers include non-bleed TXV's: any single phase reciprocatingcompressor used with these models must include hard start components.

    NOTE: Installer must supply refrigerant lines and adaptors (if needed) based on the requirements of the outdoorunit.

    BCA/BHA BLOWER COIL SPECIFICATIONS

    MODEL BHA24TB002A BHA30TB002A BHA36TB002A BHA42TB002A BHA48TB002A BHA60TB002A

    CLG CAPACITY NOMINAL BTUH 18000 / 24000 30,000 36,000 42,000 48,000 60,000EVAPORATOR COIL FACE AREA, SQ FT 4.7 4.7 4.7 4.7 5.2 6.1 ROWS DEEP 2 3 3 3 3 4 FINS/INCH 14 14 14 14 14 12BLOWER WHEEL D x W 10 X 8 10 X 8 10 X 8 10 X 8 11 X 10 11 X 10BLOWER MOTOR HORSEPOWER 1/2 1/2 1/2 1/2 1 1 FULL LOAD AMPS 4.3 4.3 4.3 4.3 7.0 7.0 RATED CFM 600 / 850 1000 1200 1400 1650 1850 EXT.STATIC PRESS (WC) MAX* .70 .70 .70 .70 .70 .70DRAIN LINE SIZE, MAIN 3/4" FPT 3/4" FPT 3/4" FPT 3/4" FPT 3/4" FPT 3/4" FPTDRAIN LINE SIZE, AUX 3/4" FPT 3/4" FPT 3/4" FPT 3/4" FPT 3/4" FPT 3/4" FPTLIQUID LINE, INCHES 3/8 3/8 3/8 3/8 3/8 3/8SUCTION LINE, INCHES 3/4 3/4 3/4 7/8 7/8 7/8REFRIG. EXP. DEVICE AS SHIPPED TEV TEV TEV TEV TEV TEVPOWER SUPPLY (w/o Heater Kits)** 208/230-60-1 208/230-60-1 208/230-60-1 208/230-60-1 208/230-60-1 208/230-60-1

    MIN. CIRCUIT AMPACITY 5.4 5.4 5.4 5.4 8.8 8.8 MAX. OVERCURRENT DEVICE 15 15 15 15 15 15ELECT. ENTRANCE SIZE POWER SUPPLY 1 3/32" 1 3/32" 1 3/32" 1 3/32" 1 3/32" 1 3/32" LOW VOLTAGE 7/8" 7/8" 7/8" 7/8" 7/8" 7/8"APPROX. SHIPPING WT (LBS) 145 150 150 175 200 210

  • 13 Rev. 1

    BCA/BHA BLOWER COIL SPECIFICATIONS

    BLOWER COIL DIMENSIONSUNIT SIZE

    18 - 36 42 48 - 60A 49 7/8 49 7/8 56 3/8 B 19 23 27C 20 1/2 24 1/2 28 1/2 D 20 5/8 20 5/8 20 5/8 E 18 7/8 22 7/8 26 7/8

    FILTER SIZE (NOMINAL) 16 x 20 x 1 20 x 20 x 1 20 x 23 1/2 x 1

    DIMENSION

    3 3/8

    1 3/82 1/4

    1 5/83 1/8

    3/4

    1/2

    1/2

    3/4

    4 15/1611/16 11/161621 5/8

    EC

    A

    D

    B

  • 14 Rev. 1

    BBA/BBC BLOWER COIL SPECIFICATIONS

    11 3/8

    22 1/16

    2

    7/8 Knockout3 Knockouts1 - 3/321 - 23/641 - 23/32

    21 1/8

    19 5/8

    "W"

    "B"

    "H"

    "A"4

    Dimensions, inches (mm) Shipping Physical Information

    MODEL W H A BWeightlbs.(kg)

    Blower Wheel(D x W)

    Blower Motor(HP) MCA

    1 MOP1

    BBA24A2A16 - 1/2 15 15

    63(28.6) 9 x 7 1/4 1.9 15

    BBA36A2A(419)

    22 - 1/4(565)

    (381) (381) 68(30.8) 10 x 7 1/3 3 15

    BBA48A2A 20 - 1/2(521)19

    (483)19

    (483)78

    (35.4) 10 x 10 1/3 3.8 15

    BBA60A2A 24 - 1/2(622)26 - 1/4(667)

    23(584)

    23(584)

    90(40.8) 11 x 10 1/2 4.9 15

    BBC36A2A 16(419)22(565)

    15(381)

    15(381)

    72(32.6)

    10 x 7(254 x 177.8) 1/2 5.4 15

    BBC60A2A 24(622)26(667)

    23(584)

    23(584)

    94(42.6)

    11 x 10(279.4 x 254) 3/4 8.8 15

    1 Minimum Circuit Ampacity (MCA) and Maximum Overcurrent Protection (MOP) for blower without supplemental heat installed. Refer to unit nameplate for MCA and MOP with approved accessory heaters installed.

  • 15 Rev. 1

    BBA/BBC BLOWER COIL SPECIFICATIONSEHK/ECB ELECTRIC HEATER DATA

    CAUTIONTo avoid the risk of fire, overcurrent protection must not exceed the value listed above.

    Minimum Circuit AmpacityHeater EHK05B EHK07B EHK10B EHK15B EHK20B EHK25B EHK30B ECB15B + ECB20B + ECB25B + ECB30B +

    Model ECB05B ECB07B ECB10B ECB15B ECB20B ECB25B ECB30B SPK02A SPK02A SPK03A SPK03AL1/L2 27.8 41.3 53.8 53.8 53.8 79.8 105.7

    BBA24A2A L3/L4 26 52L1/L2 29 42.4 55 55 55 55 55 80.9 106.9 132.8 158.8

    BBA36A2A L3/L4 26 55 55 52L5/L6 26 55L1/L2 29.7 43.2 55.7 55.7 55.7 55.7 55.7 81.6 107.6 133.6 159.5

    BBA48A2A L3/L4 26 55 55 55L5/L6 26 55L1/L2 30.9 44.4 56.9 56.9 56.9 56.9 56.9 82.8 108.8 134.8 160.7

    BBA60A2A L3/L4 26 55 55 52L5/L6 26 55L1/L2 31.3 44.8 57.3 57.3 57.3 57.3 57.3 83.3 109.2 135.2 161.2

    BBC36A2A L3/L4 26 55 55 52L5/L6 26 55L1/L2 34.7 48.2 60.7 60.7 60.7 60.7 60.7 86.6 112.6 138.6 164.5

    BBC60A2A L3/L4 26 55 55 52L5/L6 26 55

    Maximum Overcurrent ProtectionHeater EHK05B EHK07B EHK10B EHK15B EHK20B EHK25B EHK30B ECB15B + ECB20B + ECB25B + ECB30B +

    Model ECB05B ECB07B ECB10B ECB15B ECB20B ECB25B ECB30B SPK02A SPK02A SPK03A SPK03AL1/L2 30 45 60 60 60 80 110

    BBA24A2A L3/L4 30 60L1/L2 30 45 60 60 60 60 60 90 110 150 175

    BBA36A2A L3/L4 30 60 60 60L5/L6 30 60L1/L2 30 45 60 60 60 60 60 90 110 150 175

    BBA48A2A L3/L4 30 60 60 60L5/L6 30 60L1/L2 35 45 60 60 60 60 60 90 110 150 175

    BBA60A2A L3/L4 30 60 60 60L5/L6 30 60L1/L2 35 45 60 60 60 60 60 90 110 150 175

    BBC36A2A L3/L4 30 60 60 60L5/L6 30 60L1/L2 35 50 70 70 70 70 70 90 125 150 175

    BBC60A2A L3/L4 30 60 60 60L5/L6 30 60

  • 16 Rev. 1

    CCA_FCC, FDC & CHA_TCCCASED COIL SPECIFICATIONS

    C C A - - F C C & C H A - - T C C C a s e d A - C o i l S p e c i f i c a t i o n s

    MODEL CCA18FCC CCA24FCCCHA18TCCCCA30FCCCHA24TCCCCA30FDC

    CCA36FCCCHA30TCCCCA36FDC

    CCA42FCCCHA36TCCCCA42FDC

    Evaporator Coil Face Area (Sq. Ft.) 2.81 2.81 3.75 3.75 4.22 Row s 2 3 2 3 3 FPI 16 14 16 14 13Drain Connections Primary 3/4 FPT 3/4 FPT 3/4 FPT 3/4 FPT 3/4 FPT Auxiliary 3/4 FPT 3/4 FPT 3/4 FPT 3/4 FPT 3/4 FPTRefrig. Line Connection Liquid* 3/8" 3/8" 3/8" 3/8" 3/8" Vapor* 5/8" 5/8" 3/4" 3/4" 7/8"

    Approx. Shipping Weight 34 39 4346 (FDC)50

    53 (FDC)54

    57 (FDC)* Refer to Outdoor Unit Specification Sheet for proper refrigeration line sizes. Installer may need to supply adapter.

    C C A - - F C C & C H A - - T C C C a s e d A - C o i l S p e c i f i c a t i o n s

    MODELCCA48FCCCHA42TCCCCA48FDC

    CCA54FCCCHA48TCC

    CCA57FCCCHA54TCC

    CCA60FCCCHA57TCC CHA60TCC

    Evaporator Coil Face Area (Sq. Ft.) 4.69 5.16 5.16 5.63 5.63 Row s 3 2 3 3 4 FPI 13 16 11 11 10Drain Connections Primary 3/4 FPT 3/4 FPT 3/4 FPT 3/4 FPT 3/4 FPT Auxiliary 3/4 FPT 3/4 FPT 3/4 FPT 3/4 FPT 3/4 FPTRefrig. Line Connection Liquid* 3/8" 3/8" 3/8" 3/8" 3/8" Vapor* 7/8" 7/8" 7/8" 7/8" 7/8"

    Approx. Shipping Weight 5862 (FDC) 64 71 73 89

    * Refer to Outdoor Unit Specification Sheet for proper refrigeration line sizes. Installer may need to supply adapter.

  • 17 Rev. 1

    CCA_FCC, FDC & CHA_TCCCASED COIL SPECIFICATIONS

    4 3/4

    W

    H

    7

    1 5/82 3/4 2 W

    1

    H2

    B (Top)

    or

    C (Botto

    m) A21 1/8

    Cabinet A-Coil Coil Cabinet Supply Air Return Air Width Model Cases Height Opening Opening( W ) ( CCA--F*C ) ( CHA--TCC ) CCD-- ( H ) (A x B) (A x C)

    CCA18FCCSmall CCA24FCC CHA18TCC 14 1/4

    ( 16 1/2 ) CCA30FCC CHA24TCC 15 x 18 3/4 15 x 20 3/16CCA36FCC CHA30TCC CCA42FCC CHA36TCC CCD16A22 22 1/4CCA30FDC

    Medium CCA36FDC CCD20A22( 20 1/2 ) CCA42FDC

    CCA48FCC CHA42TCCCCA36FKCCCA48FDC

    Large CCA54FCC CHA48TCC 26 1/4 23 x 18 3/4 23 x 20 3/16( 24 1/2 ) CCA57FCC CHA54TCC CCD24A26

    CCA60FCC CHA57TCCCHA60TCC

    18 1/4

    22 1/4 19 x 20 3/1619 x 18 3/4

    John

  • 18 Rev. 1

    CCA_FUA & CHA_TUA"A" COIL SPECIFICATIONS

    MODEL CCA18FUACHA18TUA CCA30FUACCA36FUA

    CHA24,30,36TUA

    CCA42FUACHA42TUA

    CHA48TUACHA57TUACCA60FUA

    CHA60TUA

    EVAPORATOR COIL Face Area (sq. ft.) 3.8 4.7 4.7 4.7 5.6 6.1 Rows Deep 2 2 3 3 3 4 Fins/Inch 14 14 14 14 14 12DRAIN LINE SIZE 3/4 FPT 3/4 FPT 3/4 FPT 3/4 FPT 3/4 FPT 3/4 FPTAUX. DRAIN SIZE 3/4 FPT 3/4 FPT 3/4 FPT 3/4 FPT 3/4 FPT 3/4 FPTHOLDING CHARGE NITROGEN CHARGEREFRIGERATION LINE 3/8" LIQ 3/8" LIQ 3/8" LIQ 3/8" LIQ 3/8" LIQ 3/8" LIQCONNECTIONS * 5/8" VAPOR 3/4" VAPOR 3/4" VAPOR 7/8" VAPOR 7/8" VAPOR 7/8" VAPORAPPROXIMATE SHIPPING WEIGHT 26 lbs 35 lbs 35 lbs 37 lbs 68 lbs 66 lbs

    * See OD unit spec sheet for proper line size. Ins taller may have to provide adapter.

    DIMENSIONA B C D

    CHA18TUACCA18FUA 18 1/4 15 3 7/16 8 1/8 CHA24TUACCA30FUACHA30TUACCA36FUACHA36TUA

    21 15/16 15 3 7/16 8 1/8

    CHA42TUACCA42FUA 21 15/16 19 3 7/16 12 1/8 CHA48TUACHA57TUACCA60FUA

    27 3/8 23 4 1/4 14 9/16

    CCA60TUA 27 13/16 23 4 1/4 14 9/16

    MODEL

  • 19 Rev. 1

    CCA_FSC & CHA_TSC"A" COIL SPECIFICATIONS

    C C A - - F S C & C H A - - T S C U n c a s e d A - C o i l S p e c i f i c a t i o n s

    MODEL CCA18FSC CCA24FSCCHA18TSCCCA30FSCCHA24TSC

    CCA36FSCCHA30TSC

    CCA42FSCCHA36TSC

    Evaporator Coil Face Area (Sq. Ft.) 2.81 2.81 3.75 3.75 4.22 Row s 2 3 2 3 3 FPI 16 14 16 14 13Drain Connections Primary 3/4 FPT 3/4 FPT 3/4 FPT 3/4 FPT 3/4 FPT Auxiliary 3/4 FPT 3/4 FPT 3/4 FPT 3/4 FPT 3/4 FPTRefrig. Line Connection Liquid* 3/8" 3/8" 3/8" 3/8" 3/8" Vapor* 5/8" 5/8" 3/4" 3/4" 7/8"Approx. Shipping Weight 20 21 24 31 35* Refer to Outdoor Unit Specification Sheet for proper refrigeration line sizes. Installer may need to supply adapter.

    C C A - - F S C & C H A - - T S C U n c a s e d A - C o i l S p e c i f i c a t i o n s

    MODEL CCA48FSCCHA42TSCCCA54FSCCHA48TSC

    CCA57FSCCHA54TSC

    CCA60FSCCHA57TSC CHA60TSC

    Evaporator Coil Face Area (Sq. Ft.) 4.69 5.16 5.16 5.63 5.63 Row s 3 2 3 3 4 FPI 13 16 11 11 10Drain Connections Primary 3/4 FPT 3/4 FPT 3/4 FPT 3/4 FPT 3/4 FPT Auxiliary 3/4 FPT 3/4 FPT 3/4 FPT 3/4 FPT 3/4 FPTRefrig. Line Connection Liquid* 3/8" 3/8" 3/8" 3/8" 3/8" Vapor* 7/8" 7/8" 7/8" 7/8" 7/8"Approx. Shipping Weight 36 38 45 47 56* Refer to Outdoor Unit Specification Sheet for proper refrigeration line sizes. Installer may need to supply adapter.

  • 20 Rev. 1

    CCA_FSC & CHA_TSC"A" COIL SPECIFICATIONS

    DIMENSIONS (inches)A B C D

    CCA18FSC 12 1/4CCA24FSC CHA18TSC 12 1/2CCA30FSC CHA24TSC 16 1/4 15 3 7/16 8 1/8CCA36FSC CHA30TSC 16 1/2CCA42FSC CHA36TSC 18 5/8CCA48FSC CHA42TSC 20 1/4 19 3 7/16 12 1/8CCA54FSC CHA48TSC 21 5/8CCA57FSC CHA54TSC 22 23 4 1/4 14 9/16CCA60FSC CHA57TSC 24

    CHA60TSC 24 3/8

    MODEL

    1 1/8

    1 7/83 7/8

    6

    3 3/4 11

    /16

    A 16 9/16

    2 5/16

    9/16

    DB

    C

    20

  • 21 Rev. 1

    CCH-F & CHH-THORIZONTAL COIL SPECIFICATIONS

    C D

    A

    B

    2-1/2"

    1" 7-1/8"

    1-1/2"

    1"

    3-9/16"

    DuctOpening

    CONNECTION SIZES AND WEIGHTS

    MODEL CCH24FCHH24TCCH30FCHH30T

    CCH36FCHH36T

    CCH48FCHH48T

    CCH60FCHH60T

    Drain Line Size 3/4" FPT 3/4" FPT 3/4" FPT 3/4" FPT 3/4" FPT3/8" Liq. 3/8" Liq. 3/8" Liq. 3/8" Liq. 3/8" Liq.

    5/8" Suct. 3/4" Suct. 3/4" Suct. 7/8" Suct. 7/8" Suct.*Approx. Ship Wgt. 38 44 44 60 65

    *Unit is rated with 1-1/8" suction line.

    Refrigerant Line Connections

    HORIZONTAL CASEDCOIL DIMENSIONS

    MODEL CCH(24-36)FCHH(24-36)TCCH(48-60)FCHH(48-60)T

    A 30 1/2 34 1/2B 25 29C 19 23D 21 1/2 25 1/2

  • 22 Rev. 1

    MODEL CCF24FCCCCF24FDC

    CCF30FCC

    CCF36FCC

    CCF36FDC

    CCF42FCC

    CCF48FCC

    CCF48FDC

    CCF60FCC

    Evaporator Coil Face Area (Sq. Ft.) 3.6 4.56 3.55 3.55 4.56 4.56 4.56 5.58 5.58 Row s 2 2 3 3 3 3 3 3 3 FPI 16 16 14 13 13 14 14 14 14 Orifice Size 1 0.061" 0.061" 0.063" 0.071" 0.071" 0.076" 0.081" 0.081" 0.098"Drain Connections Primary, Auxiliary 3/4" FPT 3/4" FPT 3/4" FPT 3/4" FPT 3/4" FPT 3/4" FPT 3/4" FPT 3/4" FPT 3/4" FPTRefrigeration Line Connection Liquid 2 3/8" 3/8" 3/8" 3/8" 3/8" 3/8" 3/8" 3/8" 3/8" Vapor 2 5/8" 5/8" 3/4" 3/4" 3/4" 7/8" 7/8" 7/8" 7/8"Approx. Shipping Weight (lbs) 41 44 48 48 51 56 56 59 72

    MODEL CHF18TCCCHF24TCC

    CHF30TCC

    CHF36TCC

    CHF42TCC

    CHF48TCC

    Evaporator Coil Face Area (Sq. Ft.) 3.6 3.55 3.55 4.56 4.56 5.58 Row s 2 3 3 3 3 3 FPI 16 14 13 14 14 14Drain Connections Primary, Auxiliary 3/4" FPT 3/4" FPT 3/4" FPT 3/4" FPT 3/4" FPT 3/4" FPTRefrigeration Line Connection Liquid 2 3/8" 3/8" 3/8" 3/8" 3/8" 3/8" Vapor 2 5/8" 5/8" 3/4" 7/8" 7/8" 7/8"Approx. Shipping Weight (lbs) 56 56 59 56 59 72

    CCF-F & CHF-THORIZONTAL COIL SPECIFICATIONS

    5"

    H

    1"W

    4"2" 1-1/2"

    4"

    A

    DimensionsCabinet Horizontal-Coil Cabinet Left Air Right Air Width Model Height Opening Opening( W ) ( CCA--F*C ) CHF**TCC ( H ) (A x B) (A x C)

    Small(22 1/4)

    CCF24FCCCCF30FCCCCF36FCC

    CHF18TCCCHF24TCCCHF30TCC

    16 1/2 15 X 18 3/4 15 X 20 3/16

    Medium(22 1/4)

    CCF24FDCCCF36FDCCCF42FCCCCF48FCC

    CHF36TCCCHF42TCC 20 1/2 19 X 18 3/4 19 X 20 3/16

    Large(26 1/4)

    CCF48FDCCCF60FCC CHF48TCC 24 1/2 23 X 18 3/4 23 X 20 3/16

    1 Orifice shipped with coil. When mixmatching, orifice size to be specified by outdoor unit.2 Refer to Outdoor Unit "Specification Sheet" for proper refrigeration line sizes. Installer may need to supply adapter.

  • PRODUCT DESIGN

    23 Rev. 1

    CONDENSING UNITThe RHA, RHD and RHE Remote Heat Pumps are made in1.5 through 5 ton sizes. They are designed for dual voltagesingle phase applications. The RHA 3, 4, and 5 ton modelsare also available for 230V and 460V 3 phase applications.The condenser air is pulled through the condenser coil by adirect drive propeller fan. This condenser air is then dis-charged out of the top of the cabinet.These units are designed for free air discharge, so no addi-tional resistance (like duct work) shall be attached.The suction and liquid line connections are of the sweat typefor field piping with refrigerant type copper. Non-back seat-ing valves are factory installed to accept the field run cop-per. The total refrigerant charge for a normal installation isfactory installed in the condensing unit. This charge is forthe matching evaporator coil and a 25 foot refrigerant lineset.Refrigerant line sizes listed in the Specification section arefor 50 feet or less. The maximum length of refrigerant linesis 50 feet with no more than a 20 foot vertical rise. In thiscase additional refrigerant must be added for the extra 20foot of lines.Systems should be properly sized by heat gain and losscalculations made according to methods of the Air Condi-tioning Contractors Association (ACCA) or equivalent. It isthe contractors responsibility to ensure the system has ad-equate capacity to heat or cool the conditioned space.RHD & RHE models use the Compliant Scroll compressor.There are a number of design characteristics which are dif-ferent from the traditional reciprocating compressor.- Phase 1 Scroll compressors include a discharge thermo-stat located beneath the compressor top cap.- Phase 2 Scroll compressors will not have a discharge ther-mostat.- Due to their design Scroll compressors are inherently moretolerant of liquid refrigerant.NOTE: Even though the compressor section of a Scroll com-pressor is more tolerant of liquid refrigerant, continued flood-back or flooded start conditions may wash oil from the bear-ing surfaces causing premature bearing failure.- These Scroll compressors use white oil which is compat-ible with 3GS. 3GS oil may be used if additional oil is re-quired.- The compressor may run backwards (noisy operation) for1 or 2 seconds at shutdown. This is normal and does notharm the compressor.- Operating pressures and amp draws may differ from stan-dard reciprocating compressors. This information may befound in the "Expanded Performance Data" section.

    - The 3 phase Scroll Compressors are direction of rotationsensitive. They will rotate in either direction depending onthe phasing of the power. Verification of proper rotation ismade as follows.1. Install gauges and verify that the suction pressure drops

    while the discharge pressure increases.2. Listen for normal compressor sound levels. Reverse ro-

    tation results in elevated or unusual sound levels.3. Reverse rotation will result in substantially reduced amp

    draw from tabulated values.To correct improper rotation, switch any two power supplyleads at the outdoor unit contactor.There is no negative impact on durability caused by operat-ing 3 phase compressors in reversed rotation. The com-pressors internal protector will trip, de-energizing the com-pressor.The scroll is a simple compression concept first patented in1905. A scroll is an involute spiral which, when matchedwith a mating scroll form, generates a series of crescentshaped gas pockets between the two members. See thefollowing illustration.During compression, one scroll remains stationary (fixedscroll) while the other form (orbiting scroll) is allowed to orbit(but not rotate) around the first form.As this motion occurs, the pockets between the two formsare slowly pushed to the center of the two scrolls while si-multaneously being reduced in volume. When the pocketreaches the center of the scroll form, the gas, which is nowat a high pressure, is discharged out of a port located at thecenter.During compression, several pockets are being compressedsimultaneously, resulting in a very smooth process. Boththe suction process (outer portion of the scroll members)and the discharge process (inner portion) are continuous.

  • PRODUCT DESIGN

    24 Rev. 1

    BLOWER COILSThese blower coils are designed with matching evaporatorcoils to provide an air handler for heat pump operation. Elec-tric heater kits (EHK-A) are available as sales accessoriesfor supplement electric heat.The BHA-T models are equipped with a thermostatic ex-pansion and check valve assembly for refrigerant metering.The BHA-F models are equipped with a restrictor orifice.The units are designed for upflow, counterflow, or horizon-tal application, using two speed direct drive motors on theBHA-FA & TA models, and BPM (Brushless PermanentMagnet) or ECM motor on the BHA-TB models.

    COILS AND BLOWERSAmana CCA & CHA model "A" coils are designed for upflowand counterflow operation. The CCH & CHH model slabcoils, and the CCF & CHF model cased "A" coils are de-signed for horizontal applications.These coils are designed to be installed with a furnace or airhandler and matched with Amana's heat pumps to providehigh efficiency cooling and heating. Thermal expansionvalves on the CCA_T, CHA_T, CHH and CHF coils and re-strictor orifices on the CCA_F, CCH and CCF coils provideaccurate refrigerant control and provide reliable operationover a wide range of conditions.Models CCA30FUA and CCA60FUA have restrictors fac-tory installed for 2 1/2 ton and 5 ton applications. Applica-tions with the 2 ton and 4 ton require a change in the restric-tor.All expansion valves used on indoor coils and blowers areof the non-bleed type.To avoid poor operation and/or equipment damage, anysingle-phase reciprocating compressor used with a ex-pansion valve coil must include hard start components.BBA and BBC model blower cabinets are designed as a twopiece blower coil. The BBA/BBC is the blower section whichattaches to a cased evaporator coil. This two piece arrange-ment allows for a variety of mix-matching possibilities pro-viding greater flexibility.BBC models use a variable speed motor that maintains arelatively constant airflow regardless of duct static. BBCmodels are approved for applications with cooling coils ofup to 0.8 inches w.c. external static pressure. The BBC'sinclude a feature that allows airflow to be changed by 15percent. If lower airflow is desired, place the "ADJUST" pinon the "-" setting. If higher airflow is desired, place the "AD-JUST" pin on the "+" setting.As a modular blower coil, the intended use is for applica-tions with a cased evaporator coil and a condensing unit orheat pump. The blower section may also be used as anelectric furnace. In either case, electric heating elementsare field installed. Electric heater kits (EHK-B & ECB-B) areavailable as sales accessories for supplement electric heat.

    The unit may be positioned for upflow, counterflow, horizon-tal right or horizontal left operation. All units are constructedwith R-4.2 insulation. In areas of extreme humidity (greaterthan 80% consistently), the installer should insulate the ex-terior of the blower with insulation having a vapor barrierequivalent to insulation used on ductwork, if local codespermit.

    AeroQuip Flow Control Assembly

    Chatleff Flow Control Assembly

    XXX

    Distributor Body

    RestrictorTeflon Seal

    3/8" SweatClosureFitting

    Restrictor Bullet Nose(O-Ring Seal Side)

    to face Distributor Tubes

    Orifice SizeO-Ring

    13/16" BrassHex Nut

    Distributor Tubes

  • PRODUCT DESIGN

    25 Rev. 1

    OUTDOOR UNITORIFICE SIZING CHART

    OUTDOORUNIT

    OrificeSize

    AeroQuipROK01A Kit

    OrificeSize

    ChatleffROK___A Kits

    RHA18A2A 0.054 0.055**RHA24A2A 0.061 0.061RHA30A2A 0.072 0.072RHA36A2A 0.076 0.076RHA42A2A 0.081 0.081RHA48A2A 0.088 0.088RHA60A2A 0.098 0.098RHA18A2B 0.051 0.051RHA24A2B 0.059 0.059RHA30A2B 0.065 0.065RHA36A2B 0.071 0.071RHA42A2B 0.073 0.073RHA48A2B 0.084 0.084RHA60A2B 0.098 0.098

    RHD/RHE18A2A 0.054 0.055**RHD/RHE24A2A 0.058 0.059**RHD/RHE30A2A 0.069 0.068**RHD/RHE36A2A 0.076 0.076RHD/RHE42A2A 0.079 0.080**RHD/RHE48A2A 0.092 0.092RHD/RHE60A2A 0.098 0.098 **Orifice size changed to match the new distributor flow control assembly design.

    Note: Whenever mix-matching systems, the indoor ori-fice must be matched to the condensing unit for properoperation.

    FACTORY INSTALLEDORIFICE SIZE CHARTS

    BLOWERCOIL

    ORIFICESIZE

    BHA18FA 0.054BHA24FA 0.061BHA30FA 0.072BHA36FA 0.076BHA42FA 0.081

    "A"COIL

    ORIFICESIZE

    CCA18FUA 0.051CCA30FUA 0.063CCA36FUA 0.069CCA42FUA 0.073CCA60FUA 0.092CCA18F*C 0.051CCA24F*C 0.055CCA30F*C 0.063CCA36F*C 0.068CCA42F*C 0.073CCA48F*C 0.081CCA54F*C 0.081CCA57F*C 0.092

    HORIZONTALCOIL

    ORIFICESIZE

    CCF24F*C 0.061CCF30FCC 0.063CCF36F*C 0.071CCF42FCC 0.076CCF48F*C 0.081CCF60FCC 0.098

    HORIZONTALCOIL

    CCH-FCCAeroQuip

    Orifice size

    CCH-FCDChatleff

    Orifice SizeCCH24F 0.054 0.055CCH30F 0.063 0.063CCH36F 0.069 0.068CCH48F 0.081 0.081CCH60F 0.092 0.092

    NOTE: Restrictor orifice size should always be matched tothe OD unit being used.Suction line accumulators are used on outdoor units withreciprocating compressors for additional protection for thecompressor. The object of the accumulator is to:1. Provide a liquid refrigerant storage vessel during pro-

    longed system off cycles.2. Store excess liquid refrigerant not needed by the sys-

    tem while running.3. Return oil and saturated vapor to the compressor at a

    controlled rate.4. Retain stored excess refrigerant during a sudden sys-

    tem pressure fluctuation such as seen in defrost cycles.

  • SYSTEM OPERATION

    26 Rev. 1

    COOLINGThe refrigerant used in the system is R-22. It is a clear, col-orless, non-toxic, non-irritating, and non-explosive liquid. Thechemical formula is CHCLF2. The boiling point, at atmo-spheric pressure is -41.4F.A few of the important principles that make the refrigerationcycle possible are: heat always flows from a warmer to acooler body, under lower pressure a refrigerant will absorbheat and vaporize at a low temperature, the vapors may bedrawn off and condensed at a higher pressure and tem-perature to be used again.The indoor evaporator coil functions to cool and dehumidifythe air conditioned spaces through the evaporative processtaking place within the coil tubes.NOTE: The pressures and temperatures shown in the re-frigerant cycle illustrations on the following pages are fordemonstration purposes only. Actual temperatures and pres-sures are to be obtained from the "Expanded PerformanceChart."Liquid refrigerant at condensing pressure and temperatures,(270 psig and 122F), leaves the outdoor condensing coilthrough the drier and is metered into the indoor coil throughthe metering device. As the cool, low pressure, saturatedrefrigerant enters the tubes of the indoor coil, a portion ofthe liquid immediately vaporizes. It continues to soak up heatand vaporizes as it proceeds through the coil, cooling theindoor coil down to about 48F.Heat is continually being transferred to the cool fins and tubesof the indoor evaporator coil by the warm system air. Thiswarming process causes the refrigerant to boil. The heatremoved from the air is carried off by the vapor.As the vapor passes through the last tubes of the coil, itbecomes superheated, that is, it absorbs more heat than isnecessary to vaporize it. This is assurance that only dry gaswill reach the compressor. Liquid reaching the compressorcan weaken or break compressor valves.The compressor increases the pressure of the gas, thusadding more heat, and discharges hot, high pressure su-perheated gas into the outdoor condenser coil.In the condenser coil, the hot refrigerant gas, being warmerthan the outdoor air, first loses its superheat by heat trans-ferred from the gas through the tubes and fins of the coil.The refrigerant now becomes saturated, part liquid, partvapor and then continues to give up heat until it condensesto a liquid alone. Once the vapor is fully liquefied, it contin-ues to give up heat which subcools the liquid, and it is readyto repeat the cycle.

    HEATINGThe heating portion of the refrigeration cycle is similar to thecooling cycle. By energizing the reversing valve solenoid coil,the flow of the refrigerant is reversed. The indoor coil nowbecomes the condenser coil, and the outdoor coil becomesthe evaporator coil.The check valve at the indoor coil will open by the flow ofrefrigerant letting the now condensed liquid refrigerant by-pass the indoor expansion device. The check valve at theoutdoor coil will be forced closed by the refrigerant flow,thereby utilizing the outdoor expansion device.The restrictor orifice used with the CCA-F, CCH-F and BHA-F coils will be forced onto a seat when running in the cool-ing cycle, only allowing liquid refrigerant to pass through theorifice opening. In the heating cycle it will be forced off theseat allowing liquid to flow around the restrictor. A checkvalve is not required in this circuit.

    COOLING CYCLEWhen the contacts of the room thermostat close makingterminals R to Y to G, the low voltage circuit of the trans-former is completed. Current now flows through the mag-netic holding coils of the compressor contactor (CC) andfan relay (RFC).This draws in the normally open contact CC1, starting thecompressor and condenser fan motors. At the same timecontacts RFC close starting the indoor fan motor.When the thermostat is satisfied, it opens its contacts, break-ing the low voltage circuit, causing the compressor contac-tor and indoor fan relay to open, shutting down the system.If the room thermostat fan selector switch should be set onthe "on" position, then the indoor blower would run continu-ous rather than cycling with the compressor.RHA, RHD & RHE models energize the reversing valve thor-ough the "O" circuit in the room thermostat. Therefore thereversing valve remains energized as long as the thermo-stat subbase is in the cooling position. The only exception tothis is during defrost.

    HEATING CYCLEThe RHA & RHD model heat pumps use a different controlcircuit than preceding heat pump models. These models donot use a reversing relay to energize the reversing valve.Also many previous models energized the reversing valveoff the "B" terminal on the thermostat, and all previous mod-els energized the reversing valve in the heating cycle.

  • SYSTEM OPERATION

    27 Rev. 1

    COOLING CYCLE

    IndoorCoil

    Accumulator

    Bi-FlowFilter Dryer

    OutdoorCoil

    ThermostaticExpansion

    Valve

    Check Valve

    Reversing Valve(De-Energized)

    IndoorCoil

    Accumulator

    Bi-FlowFilter Dryer

    OutdoorCoil

    ThermostaticExpansion

    Valve

    Check Valve

    Reversing Valve(Energized)

    HEATING CYCLE

  • SYSTEM OPERATION

    28 Rev. 1

    The reversing valve on the RHA, RHD & RHE models isenergized in the cooling cycle thorough the "O" terminal onthe room thermostat.These models have a 24 volt reversing valve coil. When thethermostat selector switch is set in the cooling position, the"O" terminal on the thermostat is energized all the time.Care must be taken when selecting a room thermostat. Re-fer to the installation instructions shipped with the productfor approved thermostats.If electric heaters are utilized, a two stage heating and singlestage cooling thermostat should be used.Should the second stage heating contacts in the room ther-mostat close, the first stage of electric heat would becomeenergized. If additional electric heaters are used, they wouldbe controlled by the sequencer on the proceeding heater. Ifinstalled, the electric heaters may be controlled by outdoorthermostats.

    DEFROST CYCLEThe defrosting of the outdoor coil is jointly controlled by thedefrost timer board, defrost (30/60) control, and compres-sor run time.Solid State Timer RHA-A2A ModelsThe defrost timer board can be connected for one of three(3) time intervals. Post T1 = 30 minutes, Post T2 = 60 min-utes, and Post T3 = 90 minutes (Factory connected).The timing interval can not commence until the outdoor coiltemperature reaches approximately 30F. (initiation tempera-ture) at the defrost terminator (30/60) control point of con-tact. As long as this point of contact does not reach 60F.(termination temperature), the defrost timer board will countthe number of minutes that the compressor runs.At the end of this (one of three) time interval, the defrosttimer board will call for defrost and energize the defrost (DFR)relay. This relay has four sets of contacts of which one is inthe line voltage circuit (normally closed) in series with theoutdoor fan motor. When this contact opens, the outdoorfan motor stops. The other three sets of contacts (normallyopen) are in the low voltage circuit. One set of contacts con-trol the reversing valve. When closed, the reversing valveenergizes, switching over to the cooling position sendinghot refrigerant gas to the outdoor coil, which will start to meltany frost accumulation. Another set of contacts close, lock-ing in the compressor until defrost is completed. The thirdset will energize the electric heat if available.The defrost timer board will keep the defrost (DFR) relayenergized until the outdoor coil temperature reaches approxi-mately 60F at the 30/60 control, or a maximum of 10 min-utes compressor run time.If the defrost cycle is terminated by temperature, then a newtime interval count cannot begin until the defrost (30/60) con-trol again reaches approximately 30F. If the defrost cyclewas terminated by time, then a new time interval would be-gin immediately.Integrated Defrost Control RHA-A2B ModelsThe operation of the integrated defrost control used on theRHA-A2B models is very similar to that of the solid statecontrol described above. The time interval is determined bythe position of the time select jumper which is factory set tothe specific unit design. The control will default to 90 min-utes if the jumper is missing or if the jumper is left in the testposition for more than 5 minutes.The board counts the compressor run time in the heatingmode after the 30/60 control closes. If the 30/60 controlopens, the timer will reset. The board will terminate defrostwhen the 30/60 control opens or after 14 minutes compres-sor run time which ever occurs first. If the thermostat is sat-isfied during the defrost cycle, timing is suspended, the boarddoes not reset.NOTE: RHA30 & 36 A2B units are factory set to 30 minutes.

  • SYSTEM OPERATION

    29 Rev. 1

    It is not recommended to change the defrost times on theseunits. All other models are factory set for 90 minutes andcan be adjusted to accommodate local conditions.Some additional features that are built into this controlare;Short cycle protection - The 11164401 integrated defrostcontrol includes short cycle protection. A five minute lock-out will occur when the 24 VAC power to the contactor isremoved by the thermostat demand cycling off or by theopening of a pressure switch.Pressure switch protection - When a pressure switchopens, the contactor is locked out for five minutes. After 5minutes, if the pressure switch is closed, normal operationwill resume. Note: The RHA__A2B units have a second 30/60 control which bypasses the low pressure control at thestart of the defrost mode to avoid nuisance tripping of thelow pressure switches in this phase of the defrost function.Three time Lockout Feature - After 3 pressure switch open-ings within a single heating or cooling cycle, all functions willbe locked out. Lockout is reset by cycling off the thermostator by removing 24 VAC power to the board. Note: TheRanco board requires interrupt of 24 VAC to the board toreset.Adaptive Defrost System RHD/RHE ModelsThe adaptive defrost board works in much the same way asthe standard solid state timer except that it is not set to afixed time between defrosts. Defrosts may be a minimum of30 minutes apart, to a maximum of 180 or 360 minutes (de-pendant on control model) apart depending on conditions.The optimum defrost time is programmed into the defrostcontrol (5.5 or 7 minutes). If the defrost takes less than theoptimum defrost time, the defrost board will increase thetime before the next defrost. If the next defrost also is lessthan the optimum defrost time, the board will again increasethe time before the next defrost.As conditions change increasing the frost build up on thecoil, the length of defrost will also increase above the opti-mum defrost time, causing the defrost cycles to come morefrequently.See section S-23 in the servicing portion of this manual foradditional information and servicing of the defrost control.

    BBA Standard Efficiency Blower SectionSequence of OperationBBA Cooling-Only OperationsThe cooling operation is fairly straight forward. With the ther-mostat in the FANAUTO position and a Y or G call,the blower starts within three seconds. When the Y call issatisfied, the blower will stay on until the supply tempera-ture is greater than 65F or up to a maximum of forty-fiveseconds, whichever occurs first.BBA Electric Heat-Only OperationsAs in the cooling-only operations, with the thermostat in theFANAUTO position and a W2 or E call, the blowerstarts within three seconds. The board then starts turning-on banks of electric heat, one every ten seconds, until thesupply temperature reaches 90F. If the W2 or E call hasnot been satisfied within the next five minutes, the boardturns-on additional banks of heaters and increases the mini-mum supply temperature from 90F to 105F. If an addi-tional five minutes passes and the W2 or E call has notbeen satisfied, the board will raise the minimum supply tem-perature to 120F and once again turns-on additional banksof electric heaters.Should the temperature at the thermistor go above 140F,the control logic will start turning off one bank of heatersevery ten seconds until the temperature falls below 140F.If the temperature climbs above 150F, the control logic turnsoff all electric heat. If the temperature goes above 170F,probably due to a component failure, the control logic turnsoff all power to the heaters and keeps the blower on until thetemperature falls below 90F.BBA Heat Pump Only OperationsThe control process for heat pump operations is very simi-lar to the electric heat only operations, with the thermostatin the FANAUTO position and a Y call, the blower startswithin three seconds. When the Y call is satisfied, the blowerwill stay on until the supply temperature is less than 90F orup to a maximum of forty-five seconds, whichever occursfirst.BBA Heat Pump Operations with Back-up Electric HeatThe major difference when electric heat is added is that theboard can be preset for electric heat lockout and minimumsupply air temperatures of 85F, 90F, 95F, or 100F. Thisdischarge air temperature setting will be used to lock-outthe electric heaters as long as the heat pump cycle satisfiesthe minimum supply air temperature.

  • SYSTEM OPERATION

    30 Rev. 1

    Two conditions must exist for the electric heat to be acti-vated:

    1. The thermistor is sensing temperatures below the setpoint with the heat pump heating operation, and

    2. There is a W2 call.So, if the heat pump cycle fails to satisfy the W2 call, theboard shifts to integrated heating operation which is just likethe electric heater only operation except that the initial mini-mum supply air for the heat pump cycle plus the electricheaters will be 105F instead of 90F.BBA Fan Idle OptionThe control board has a special option for the BBA models.The blower motor is wired for only one speed for heatingand cooling operations. Another tap for the motor can beuse to connect the lower or idle speed. With the thermo-stat in the FANAUTO position, the board allows the motorto operate at the lower speed during system off cycles forminimum circulation air. When the thermostat is switchedto the FANON position, the blower motor will operate atthe higher cooling speed.

    BBC High Efficiency Blower SectionSequence of OperationIt is important to note that the operational logic for thecontrol board for the BBCs is different from the BBAboard, hence, they are not interchangeable.The BBCs, like the BHA**TBs with the ECM variable speedmotor, use the variable speed to maintain constant CFM.However, there is a new twist to the BBCs with the controlboard logic that changes the CFM in response to over-tem-perature and under-temperature conditions with help fromthe discharge air temperature readings from the new dis-charge air thermistor.BBC Cooling-Only OperationsWith the thermostat in the FANAUTO position and a Yor G call, the blower ramps up to speed over a 30 secondperiod. The acceptable cooling operation temperature rangeis 45 to 65F. If the supply air temperature is above the ac-ceptable range, 65F, the control logic decreases the CFM,until the Y or G call is satisfied. Then, on the next Y orG call the CFM will return to the preset level. If the supplyair temperature is below the acceptable range, 45F, thecontrol logic increases the CFM until the Y call is satisfied.Then, on the next Y or G call the CFM will return to thepreset level. In both cases, the blower will stay on at nomi-nal CFM until the supply temperature is greater than 65For up to a maximum of forty-five seconds, whichever occursfirst. At that time the motor will ramp the CFM down over thenext 30 seconds.

    BBC Electric Heat-Only OperationsAs in the cooling-only operations, with the thermostat in theFANAUTO position and a W2 or E call, the first bankof electric heat is energized as the blower ramps up to speedover a 30 second period. The control logic continues turn-ing-on banks of electric heat, one every ten seconds, untilthe supply temperature reaches 90F. The board will thenkeep all existing banks of electric heaters on until the W2or E call has been satisfied.If the supply air temperature is above the upper limit of theacceptable range, 140F, the control turns off one bank ofheaters every 10 seconds until the temperature falls below140F. Should the temperature exceed 150F, the controllogic will shut-off all electric heat and runs the fan continu-ously until the temperature is back below 90F.BBC Heat Pump Only OperationsThe control process for heat pump operations is very simi-lar to the cooling only operations, with the thermostat in theFANAUTO position and a Y call, the blower ramps up tospeed over 30 second period. The acceptable heating op-eration temperature range is 90 to 105F. If the supply airtemperature is above the acceptable range (105F) the con-trol logic increases the CFM until the Y call is satisfied. Ifthe supply air temperature is below the acceptable range(90F) the control decreases the CFM. In either case theairflow returns to the preset level on the next call for heat-ing.BBC Heat Pump Operations with Back-up Electric HeatThe major difference when electric heat is added is that theboard can be preset for minimum supply air temperaturesof 85F, 90F, 95F, or 100F. This discharge air tempera-ture setting will be used to lock-out the electric heaters aslong as the heat pump cycle satisfies the minimum supplyair temperature. If the heat pump cycle fails to satisfy theW2 call, the control will first decrease the airflow to try toobtain the minimum supply temperature. If a lower airflow isunsuccessful, the control board then returns to the presetairflow level and shifts to integrated heating operation whichis just like the electric heater only operation except that theinitial minimum supply air for the heat pump cycle plus theelectric heaters will be 105F instead of 90F. The controllogic will then operate as for the electric heat only operation.BBC Manual Fan OperationThe control board has a special option for the BBC models.When the thermostat is switched to the FANON position,the blower motor will operate at either 50% or 100% of thecooling speed. This is accomplished with the use of the "LowSpeed Manual Fan" jumper located just below the indicatorlight on the control board. With the jumper in place (asshipped) the blower will operate at 50% of the nominal cool-ing speed selected. With the jumper removed the blowerwill operate at 100% of the nominal blower speed selected.

  • SYSTEM OPERATION

    31 Rev. 1

    ELECTRIC HEATERS

    Optional electric heaters may be added, in the quantitiesshown in the specifications section to provide electric resis-tance heating. Under no condition shall more heaters thanthe quantity shown be installed.The low voltage circuit in the air handler is factory wired andterminates at the location provided for the electric heater(s).A minimum of field wiring is required to complete the instal-lation.Other components such as a Heating/Cooling Thermostatand Outdoor Thermostats are available to complete the in-stallation.The system CFM can be determined by measuring the staticpressure external to the unit. The installation manual sup-plied with the blower coil, or the blower performance table inthe service manual shows the CFM for the static measured.Alternately, the system CFM can be determined by operat-ing the electric heaters and indoor blower WITHOUT hav-ing the compressor in operation. Measure the temperaturerise as close to the blower inlet and outlet as possible.If other than a 240V power supply is used, refer to the BTUHCAPACITY CORRECTION FACTOR chart below.EXAMPLE: Five (5) heaters provide 24.0 KW at the rated240V. Our actual measured voltage is 220V, and our mea-sured temperature rise is 42F. Find the actual CFM:Answer: 24.0KW, 42F Rise, 240 V = 1800 CFM from theTEMPERATURE RISE chart on the right.Heating output at 220 V = 24.0KW x 3.413 x .84 = 68.8MBh.Actual CFM = 1800 x .84 Corr. Factor = 1400 CFM.NOTE: The temperature rise table is for sea level installa-tions. The temperature rise at a particular KW and CFM willbe greater at high altitudes, while the external static pres-sure at a particular CFM will be less.

    FORMULAS:

    Heating Output = KW x 3413 x Corr. Factor

    Actual CFM = CFM (from table) x Corr. Factor

    BTUH = KW x 3413

    BTUH = CFM x 1.08 x Temperature Rise (T)

    CFM = KW x 34131.08 x T

    T = BTUH CFM x 1.08

    ELECTRIC HEATER CAPACITY BTUHHTRKW

    4.8KW

    7.2KW

    9.6KW

    14.4KW

    19.2KW

    24.0KW

    28.8KW

    BTUH 16380 24915 32765 49150 65530 81915 98295

    BTUH CAPACITY CORRECTION FACTORSUPPLY VOLTAGE 250 230 220 208

    MULTIPLICATION FACTOR 1.08 .92 .84 .75

    TEMPERATURE RISE (F) @ 240V

    CFM 4.8KW7.2KW

    9.6KW

    14.4KW

    19.2KW

    24.0KW

    28.8KW

    600 25 38 51 - - - -700 22 33 43 - - - -800 19 29 38 57 - - -900 17 26 34 51 - - -1000 15 23 30 46 - - -1100 14 21 27 41 55 - -1200 13 19 25 38 50 - -1300 12 18 23 35 46 - -1400 11 16 22 32 43 54 651500 10 15 20 30 40 50 601600 9 14 19 28 38 47 571700 9 14 18 27 36 44 531800 8 13 17 25 34 42 501900 8 12 16 24 32 40 482000 8 12 15 23 30 38 452100 7 11 14 22 29 36 432200 7 11 14 21 27 34 412300 7 10 13 20 26 33 39

  • BLOWER PERFORMANCE DATA

    32 Rev. 1

    BCA18TBHA18F

    BCA24TBHA24F

    BCA30TBHA30F

    BCA36TBHA36F

    BCA42TBHA42F

    BCA48TBHA48TA

    BCA60TBHA60TA

    LOW HIGH LOW HIGH LOW HIGH LOW HIGH LOW HIGH LOW HIGH LOW HIGH0.1 640 840 900 1270 1100 1270 1210 1430 1430 1660 1700 1990 1770 23200.2 620 820 860 1220 1020 1210 1160 1380 1420 1620 1690 1950 1760 22500.3 610 800 820 1150 980 1160 1100 1320 1400 1580 1660 1890 1740 22000.4 590 780 770 1070 930 1100 1040 1250 1350 1520 1620 1840 1690 21700.5 540 740 710 990 870 1040 960 1170 1300 1460 1590 1760 1650 21000.6 460 670 620 880 820 970 900 1070 1260 1390 1530 1680 1580 2020

    NOTES: 1.

    2. 3.

    4. 5.

    6. 7.

    8.

    TOTAL EXTERNAL

    STATIC

    All airflow is w ith the blow er in the upflow or horizontal left position. For counterflow or horizontal right, airflow at a given ESP w ill be about 5 to 10% low er than is show n.Data show n w ithout filters. Consult filter manufacturer for pressure drop to be added.Data show n w ithout heater kits. If adding 14.4 KW or more, use temperature rise method to estimate CFM. See heater installation manual for details.All data show n is dry coil. For w et coil, add nothing for BCA(18,24); add .05" for BCA(30, 36); add .10" for BCA(42-60).All units ship as low speed for cooling. For most jobs, 350 to 450 CFM per ton is desirable. Installer should select cooling speed to match job requirement.All units must rum at high speed w hen heating.If heater kits are installed, external static pressure is not to exceed .50" w .c. Shaded region show s excessive external static pressure w ith heater kits.Blow ers are not designed for free air delivery. See blow er nameplate or specification sheet for minimum allow able external static pressure.

    UPFLOW OR HORIZONTAL LEFTBHA24TB002A*** BHA24TB002A BHA30TB002A BHA36TB002A BHA42TB002A BHA48TB002A BHA60TB002A

    Fan Only=600CFM Fan Only=600CFM Fan Only=600CFM Fan Only=600CFM Fan Only=600CFM Fan Only=950CFM Fan Only=950CFMCooling=600 CFM** Cooling=850 CFM** Cooling=1000 CFM** Cooling=1200 CFM** Cooling=1400 CFM** Cooling=1650 CFM** Cooling=1850 CFM**

    Amps* Amps* Amps* Amps* Amps* Amps* Amps*.10 0.25 0.55 0.65 0.80 0.95 1.20 1.40.20 0.30 0.65 0.80 1.00 1.20 1.30 1.50.30 0.40 0.70 0.95 1.10 1.25 1.40 1.90.40 0.50 0.85 1.00 1.20 1.40 1.60 1.90.50 0.50 0.90 1.05 1.30 1.55 1.80 2.20.60 0.60 0.95 1.10 1.40 1.70 1.90 2.30.70 0.60 1.00 1.15 1.45 1.75 2.00 2.50

    COUNTERFLOW OR HORIZONTAL RIGHTBHA24TB002A*** BHA24TB002A BHA30TB002A BHA36TB002A BHA42TB002A BHA48TB002A BHA60TB002A

    Fan Only=600CFM Fan Only=600CFM Fan Only=600CFM Fan Only=600CFM Fan Only=600CFM Fan Only=1000CFM Fan Only=1000CFMCooling=600 CFM** Cooling=1000 CFM** Cooling=1200 CFM** Cooling=1400 CFM** Cooling=1400 CFM** Cooling=1750 CFM** Cooling=1950 CFM**

    Amps* Amps* Amps* Amps* Amps* Amps* Amps*.10 0.25 0.65 0.80 0.95 0.95 1.30 1.50.20 0.30 0.80 1.00 1.20 1.20 1.40 1.60.30 0.40 0.95 1.10 1.25 1.25 1.65 2.00.40 0.50 1.00 1.20 1.40 1.40 1.75 2.00.50 0.50 1.05 1.30 1.55 1.55 2.00 2.30.60 0.60 1.10 1.40 1.70 1.70 2.10 2.40.70 0.60 1.15 1.45 1.75 1.75 2.25 2.60

    ExternalStatic" W.C.

    Notes:1. Data shown without filters. Consult filter manufacturer for pressure drop to be added.2. Data shown without heater kits . If heater kits are installed, external s tatic pressure is not to exceed maximum value shown on blower nameplate. If heater kits are used, see installation instructions for speed tap and CFM information.3. All data shown is dry coil. See Note below marked with ** for instructions to check CFM in cooling mode.4. If unit has been in cooling mode, run unit in fan only mode for 5-10 minutes to ensure a dry coil.

    ExternalStatic" W.C.

    * Amperage of ECM motor ONLY. ** Compressor MUST NOT be running when checking cooling CFM. Switch outdoor unit breaker OFF when thermostat is calling for cooling.*** BHA24TB used with RHD18.

  • BLOWER PERFORMANCE DATA

    33 Rev. 1

    UPFLOW AND HORIZONTAL LEFT

    Blower Model Nominal CoolingCapacity (MBh)Nominal

    Cooling CFM(Y+G)

    NominalElec. Ht. CFM

    (W2)

    NominalFan Only CFM

    (G Only)

    Field ConnectedTo

    Thermostat's Y

    Field ConnectedTo

    Terms Strip's RBHA24TB002B 18000 600 850 600 YL-14BHA24TB002B 24000 850 850 600 YL-14 YL-5BHA30TB002B 30000 1000 1400 600 YL-14, YL-9BHA36TB002B 36000 1200 1400 600 YL-14, YL-9 YL-5BHA42TB002B 42000 1400 1400 600 YL-14, YL-9, YL-10 YL-5BHA48TB002B 48000 1650 1750 950 YL-14BHA60TB002B 60000 1850 1950 950 YL-14, YL-9

    COUNTERFLOW AND HORIZONTAL RIGHT

    Blower Model Nominal CoolingCapacity (MBh)Nominal

    Cooling CFM(Y+G)

    NominalElec. Ht. CFM

    (W2)

    NominalFan Only CFM

    (G Only)

    Field ConnectedTo

    Thermostat's Y

    Field ConnectedTo

    Terms Strip's RBHA24TB002B 18000 600 850 600 YL-14BHA24TB002B 24000 1000 850 600 YL-14, YL-9BHA30TB002B 30000 1200 1400 600 YL-14, YL-9 YL-5BHA36TB002B 36000 1400 1400 600 YL-14, YL-9, YL-10 YL-5BHA42TB002B 42000 1400 1400 600 YL-14, YL-9, YL-10 YL-5BHA48TB002B 48000 1750 1750 1000 YL-14 YL-5BHA60TB002B 60000 1950 1950 1000 YL-14, YL-9 YL-5

    BBC36A2AHeating or Cooling Operation1 Fan Only

    Application TonnagePin SettingAdjust Pin

    on "-" Nominal

    (All Modes)Adjust Pin

    on "+"

    "MAN FAN"Jumper

    In Place2

    "MAN FAN"Jumper

    Removed21 Ton (18) A* 550 640 720 320 6402 Ton (24) B* 700 820 950 410 820

    2 Ton (30) C* 880 1020 1140 510 10203 Ton (36) D* 1050 1230 1400 615 1230

    3 Ton (42) D3* 1230 1400

    BBC60A2AHeating or Cooling Operation1 Fan Only

    Application TonnagePin SettingAdjust Pin

    on "-" Nominal

    (All Modes)Adjust Pin

    on "+" Jumper

    In Place2Jumper

    Removed22 Ton (30) D4* 10703 Ton (36) D* 1070 1280 1460 640 1280

    3 Ton (42) C* 1250 1490 1680 745 14904 Ton (48) B* 1440 1680 1950 840 16805 Ton (60) A* 1580 1880 2050 940 1880

  • COIL PRESSURE DROP DATA

    34 Rev. 1

    ExternalStatic

    BBA24A2AAirflow (CFM)

    BBA36A2AAirflow (CFM)

    BBA48A2AAirflow (CFM)

    BBA60A2AAirflow (CFM)

    (in. w.c.) Low Med High Low Med High Low Med High Low Med High0.2 590 830 1100 1030 1280 1430 1090 1490 1720 1480 1680 21100.3 550 790 1070 1000 1250 1420 1060 1450 1670 1420 1630 20500.4 500 740 1040 960 1210 1370 1020 1400 1620 1350 1560 20200.5 680 970 920 1160 1320 970 1340 1550 1280 1490 19400.6 600 880 860 1100 1240 910 1280 1470 1210 1420 18700.7 790 800 1030 1150 750 1170 1380 1100 1340 17700.8 660 690 940 1070 650 1060 1220 1000 1240 16600.9 850 970 850 970 850 1110 1550

    230 V, no heaters, no filter, no coil

    CHA**T*A/B & CCA**F*ASTATIC PRESSURE DROP ACROSS COIL VERSUS CFM

    CHA30TCHA18T CHA24T (Rated CFM, 1050)

    (Rated CFM, 600) (Rated CFM, 800) CHA36TCCA18F CCA30F (Rated CFM, 1200)

    (Rated CFM, 600) (Rated CFM, *) CCA36F(Rated CFM, 1175)

    WET DRY WET DRY WET DRY0.050 480 500 520 535 --- ---0.075 607 650 630 690 --- ---0.100 700 744 747 798 --- ---0.125 780 820 840 890 790 8700.150 870 916 963 1002 875 9940.175 965 1015 1050 1110 945 10950.200 1050 1110 1150 1223 1020 11880.225 1130 1190 1225 1290 1100 12600.250 1190 1260 1290 1305 1160 13250.275 --- --- --- --- 1210 13950.300 --- --- --- --- 1260 1470

    CHA42T CHA48T(Rated CFM, 1400) (Rated CFM, 1650) CHA60T

    CCA42F CCA60F (Rated CFM, 1850)(Rated CFM, 1400) (Rated CFM, **)

    WET DRY WET DRY WET DRY0.125 900 1050 --- --- --- ---0.150 977 1211 --- --- --- ---0.175 1080 1320 1525 1700 1460 15250.200 1140 1438 1610 1885 1550 16900.225 1275 1590 1680 1975 1600 18000.250 1330 1700 1750 2020 1625 19000.275 1400 1760 1800 2100 1740 20050.300 1475 1840 1850 2175 1800 2100

    STATIC PRESSURE

    DROP ACROSS COIL

    STATIC PRESSURE

    DROP ACROSS COIL

  • COIL PRESSURE DROP DATA

    35 Rev. 1

    CCH24FCHH24T

    CCH30FCHH30T

    CCH36FCHH36T

    CCH48FCHH48T

    CCH60FCHH60T

    Rated CFM = 800 Rated CFM = 1000 Rated CFM = 1200 Rated CFM = 1600 Rated CFM = 1800WetCoil

    DryCoil

    WetCoil

    DryCoil

    WetCoil

    DryCoil

    WetCoil

    DryCoil

    WetCoil

    DryCoil

    0.050 427 762 --- 408 --- 508 --- 538 --- 4470.075 641 1143 --- 612 --- 732 --- 807 --- 6710.100 855 1524 506 816 444 955 669 1076 --- 8940.125 1069 1905 633 1020 555 1090 836 1345 --- 11180.150 1282 2286 759 1224 666 1224 1003 1613 865 13420.175 1496 2667 886 1429 777 1340 1171 1882 1010 15660.200 1709 3048 1012 1633 888 1455 1338 2151 1154 17890.225 --- --- 1139 1837 999 1559 1505 2420 1298 20130.250 --- --- 1265 2041 1109 1663 1672 2689 1442 22360.275 --- --- 1392 --- 1220 1758 1840 2958 1587 24600.300 --- --- 1518 --- 1331 1853 2007 3227 1731 2683

    StaticPressure

    DropAcrossCoil T

    P CCF24FCC CCF30FCCCCF36FCCCCF36FDC CCF42FCC

    CCF48FCCCCF48FDC CCF60FCC

    (in. w.c.) CHF18TCC CHF24TCC CHF30TCC CHF36TCC CHF42TCC CHF48TCCDry Wet Dry Wet Dry Wet Dry Wet Dry Wet Dry Wet

    0.050 580 440 --- --- --- --- --- --- --- --- --- ---0.075 670 520 --- --- --- --- --- --- --- --- --- ---0.100 760 600 590 560 670 610 880 750 880 750 1070 10100.125 860 680 680 650 750 690 980 850 980 850 1200 11300.150 950 770 770 730 840 760 1080 950 1080 950 1320 12500.175 1030 830 830 790 910 830 1180 1030 1180 1030 1440 13500.200 1120 900 890 850 980 890 1270 1110 1270 1110 1550 14500.225 1190 960 960 910 1040 950 1350 1190 1350 1190 1650 15400.250 1260 1030 1030 980 1100 1000 1420 1260 1420 1260 1740 16400.275 1320 1090 1080 1030 1150 1050 1490 1330 1490 1330 1830 17300.300 1390 1140 1140 1080 1210 1100 1560 1400 1560 1400 1920 1820

    NOTES: For horizontal left applications, reduce airflow 5%.

    CCH & CHH CCF & CHF

  • 36 Rev. 1

    MOD

    EL: R

    HA18

    A2A

    / BHA

    18FA

    --2A

    EXPA

    NDED

    PER

    FORM

    ANCE

    DAT

    ACO

    OLIN

    G OP

    ERAT

    ION

    Outd

    oor A

    mbien

    t Tem

    pera

    ture

    6575

    8595

    105

    115

    Enter

    ing In

    door

    Wet

    Bulb

    Temp

    eratu

    reID

    B*Ai

    rflow

    5963

    6771

    5963

    6771

    5963

    6771

    5963

    6771

    5963

    6771

    5963

    6771

    MBh

    18.4

    19.1

    20.9

    -18

    .018

    .720

    .4-

    17.6

    18.2

    19.9

    -17

    .117

    .819

    .5-

    16.3

    16.9

    18.5

    -15

    .115

    .617

    .1-

    S/T

    0.72

    0.60

    0.42

    -0.7

    50.6

    20.4

    3-

    0.77

    0.64

    0.44

    -0.7

    90.6

    60.4

    6-

    0.82

    0.68

    0.47

    -0.8

    30.6

    90.4

    8-

    Delta

    T18

    1612

    -18

    1612

    -18

    1612

    -18

    1612

    -18

    1612

    -17

    1511

    -67

    5KW

    1.41

    1.44

    1.48

    -1.5

    21.5

    51.6

    0-

    1.61

    1.65

    1.70

    -1.7

    01.7

    31.7

    9-

    1.77

    1.81

    1.87

    -1.8

    31.8

    71.9

    4-

    AMPS

    5.96.0

    6.2-

    6.36.4

    6.6-

    6.87.0

    7.2-

    7.27.4

    7.6-

    7.77.8

    8.1-

    8.18.3

    8.6-

    HI P

    R14

    215

    316

    1-

    159

    171

    181

    -18

    119

    520

    6-

    206

    222

    234

    -23

    224

    926

    3-

    256

    276

    291

    -LO

    PR

    6468

    75-

    6872

    79-

    7175

    82-

    7479

    86-

    7883

    90-

    8086

    93-

    MBh

    17.9

    18.5

    20.3

    -17

    .518

    .119

    .8-

    17.1

    17.7

    19.4

    -16

    .617

    .218

    .9-

    15.8

    16.4

    17.9

    -14

    .615

    .216

    .6-

    S/T

    0.69

    0.57

    0.40

    -0.7

    10.5

    90.4

    1-

    0.73

    0.61

    0.42

    -0.7

    50.6

    30.4

    4-

    0.78

    0.65

    0.45

    -0.7

    90.6

    60.4

    6-

    Delta

    T19

    1612

    -19

    1613

    -19

    1713

    -19

    1713

    -19

    1612

    -18

    1512

    -70

    600

    KW1.4

    01.4

    21.4

    7-

    1.50

    1.54

    1.59

    -1.6

    01.6

    31.6

    9-

    1.68

    1.72

    1.78

    -1.7

    51.7

    91.8

    5-

    1.82

    1.86

    1.92

    -AM

    PS5.8

    5.96.1

    -6.2

    6.46.6

    -6.7

    6.97.1

    -7.2

    7.37.6

    -7.6

    7.88.0

    -8.0

    8.28.5

    -HI

    PR

    140

    151

    160

    -15

    817

    017

    9-

    179

    193

    204

    -20

    422

    023

    2-

    230

    247

    261

    -25

    427

    328

    8-

    LO P

    R64

    6874

    -67

    7278

    -70

    7481

    -73

    7885

    -77

    8289

    -80

    8592

    -MB

    h16

    .517

    .118

    .7-

    16.1

    16.7

    18.3

    -15

    .716

    .317

    .9-

    15.4

    15.9

    17.4

    -14

    .615

    .116

    .6-

    13.5

    14.0

    15.3

    -S/

    T0.6

    60.5

    50.3

    8-

    0.69

    0.57

    0.40

    -0.7

    00.5

    90.4

    1-

    0.73

    0.61

    0.42

    -0.7

    50.6

    30.4

    4-

    0.76

    0.64

    0.44

    -De

    lta T

    1917

    13-

    1917

    13-

    1917

    13-

    2017

    13-

    1917

    13-

    1816

    12-

    525

    KW1.3

    61.3

    91.4

    3-

    1.47

    1.50

    1.55

    -1.5

    61.5

    91.6

    4-

    1.64

    1.68

    1.73

    -1.7

    11.7

    51.8

    1-

    1.77

    1.81

    1.87

    -AM

    PS5.7

    5.86.0

    -6.1

    6.26.4

    -6.6

    6.76.9

    -7.0

    7.17.4

    -7.4

    7.67.8

    -7.8

    8.08.3

    -HI

    PR

    136

    147

    155

    -15

    316

    417

    4-

    174

    187

    197

    -19

    821

    322

    5-

    223

    240

    253

    -24

    626

    528

    0-

    LO P

    R62

    6672

    -65

    6976

    -68

    7279

    -71

    7683

    -75

    7987

    -77

    8290

    -

    MBh

    18.7

    19.3

    20.9

    22.4

    18.3

    18.8

    20.4

    21.9

    17.9

    18.4

    19.9

    21.4

    17.4

    17.9

    19.4

    20.8

    16.6

    17.0

    18.5

    19.8

    15.3

    15.8

    17.1

    18.3

    S/T

    0.82

    0.73

    0.55

    0.36

    0.85

    0.76

    0.57

    0.37

    0.87

    0.78

    0.59

    0.38

    0.90

    0.80

    0.61

    0.39

    0.93

    0.83

    0.63

    0.41

    0.94

    0.84

    0.64

    0.41

    Delta

    T21

    1916

    1121

    1916

    1121

    1916

    1121

    2016

    1121

    1916

    1120

    1815

    1067

    5KW

    1.42

    1.45

    1.49

    1.54

    1.53

    1.56

    1.61

    1.67

    1.63

    1.66

    1.72

    1.77

    1.71

    1.75

    1.81

    1.87

    1.78

    1.82

    1.89

    1.95

    1.85

    1.89

    1.95

    2.02

    AMPS

    5.96.0

    6.26.4

    6.36.5

    6.76.9

    6.97.0

    7.27.5

    7.37.5

    7.78.0

    7.77.9

    8.28.5

    8.28.4

    8.68.9

    HI P

    R14

    315

    416

    317

    016

    117

    318

    319

    018

    319

    720

    821

    720

    822

    423

    724

    723

    425

    226

    627

    825

    927

    829

    430

    7LO

    PR

    6569

    7580

    6973

    8085

    7176

    8388

    7580

    8793

    7884

    9197

    8186

    9410

    0MB

    h18

    .218

    .720

    .321

    .817

    .818

    .319

    .821

    .217

    .317

    .919

    .320

    .716

    .917

    .418

    .920

    .216

    .116

    .517

    .919

    .214

    .915

    .316

    .617

    .8S/

    T0.7

    80.7

    00.5

    30.3

    40.8

    10.7

    20.5

    50.3

    50.8

    30.7

    40.5

    60.3

    60.8

    60.7

    70.5

    80.3

    70.8

    90.8

    00.6

    00.3

    90.9

    00.8

    00.6

    10.3

    9De

    lta T

    2220

    1611

    2220

    1711

    2220

    1711

    2220

    1712

    2220

    1711

    2019

    1511

    7560

    0KW

    1.41

    1.44

    1.48

    1.53

    1.52

    1.55

    1.60

    1.65

    1.61

    1.65

    1.70

    1.76

    1.70

    1.73

    1.79

    1.85

    1.77

    1.81

    1.87

    1.93

    1.83

    1.87

    1.94

    2.00

    AMPS

    5.96.0

    6.26.4

    6.36.4

    6.66.9

    6.87.0

    7.27.4

    7.27.4

    7.67.9

    7.77.8

    8.18.4

    8.18.3

    8.68.9

    HI P

    R14

    215

    316

    116

    815

    917

    118

    118

    918

    119

    520

    621

    520

    622

    223

    424

    423

    225

    026

    427

    525

    627

    629

    130

    4LO

    PR

    6468

    7580

    6872

    7984

    7175

    8287

    7479

    8692

    7883

    9096

    8086

    9399

    MBh

    16.8

    17.3

    18.7

    20.1

    16.4

    16.9

    18.3

    19.6

    16.0

    16.5

    17.8

    19.1

    15.6

    16.1

    17.4

    18.7

    14.8

    15.3

    16.5

    17.7

    13.7

    14.1

    15.3

    16.4

    S/T

    0.75

    0.67

    0.51

    0.33

    0.78

    0.70

    0.53

    0.34

    0.80

    0.72

    0.54

    0.35

    0.83

    0.74

    0.56

    0.36

    0.86

    0.77

    0.58

    0.37

    0.86

    0.77

    0.59

    0.38

    Delta

    T22

    2017

    1222

    2117

    1222

    2117

    1223

    2117

    1222

    2117

    1221

    1916

    1152

    5KW

    1.37

    1.40

    1.45

    1.49

    1.48

    1.51

    1.56

    1.61

    1.57

    1.61

    1.66

    1.71

    1.65

    1.69

    1.75

    1.81

    1.72

    1.76

    1.82

    1.88

    1.78

    1.83

    1.89

    1.95

    AMPS

    5.75.8

    6.06.2

    6.16.3

    6.56.7

    6.66.8

    7.07.2

    7.07.2

    7.47.7

    7.57.6

    7.98.2

    7.98.1

    8.38.6

    HI P

    R13

    814

    815

    616

    315

    416

    617

    518

    317

    618

    919

    920

    820

    021

    522

    723

    722

    524

    225

    626

    724

    926

    728

    229

    5LO

    PR

    6266

    7277

    6670

    7782

    6873

    8085

    7277

    8489

    7580

    8893

    7883

    9196

    *Ente

    ring I

    ndoo

    r Dry

    Bulb

    Temp

    eratur

    eNO

    TE: S

    hade

    d area

    is A

    CCA

    (TVA

    ) con

    dition

    s

  • 37 Rev. 1

    MOD

    EL: R

    HA18

    A2A

    / BHA

    18FA

    --2A

    EXPA

    NDED

    PER

    FORM

    ANCE

    DAT

    ACO

    OLIN

    G OP

    ERAT

    ION

    Outd

    oor A

    mbien

    t Tem

    pera

    ture

    6575

    8595

    105

    115

    Enter

    ing In

    door

    Wet

    Bulb

    Temp

    eratu

    reID

    B*Ai

    rflow

    5963

    6771

    5963

    6771

    5963

    6771

    5963

    6771

    5963

    6771

    5963

    6771

    MBh

    19.1

    19.5

    20.8

    22.3

    18.6

    19.0

    20.3

    21.7

    18.2

    18.6

    19.8

    21.2

    17.7

    18.1

    19.4

    20.7

    16.9

    17.2

    18.4

    19.7

    15.6

    15.9

    17.0

    18.2

    S/T

    0.90

    0.84

    0.69

    0.51

    0.93

    0.87

    0.71

    0.53

    0.95

    0.89

    0.73

    0.54

    1.00

    0.92

    0.75

    0.56

    1.00

    0.96

    0.78

    0.58

    1.00

    0.97

    0.79

    0.59

    Delta

    T23

    2219

    1624

    2320

    1624

    2320

    1624

    2320

    1623

    2220

    1621

    2118

    1567

    5KW

    1.43

    1.46

    1.51

    1.56

    1.54

    1.57

    1.63

    1.68

    1.64

    1.68

    1.73

    1.79

    1.73

    1.76

    1.82

    1.88

    1.80

    1.84

    1.90

    1.97

    1.86

    1.90

    1.97

    2.04

    AMPS

    6.06.1

    6.36.5

    6.46.5

    6.77.0

    6.97.1

    7.37.6

    7.47.5

    7.88.0

    7.88.0

    8.28.5

    8.28.4

    8.79.0

    HI P

    R14

    515

    616

    417

    116

    217

    518

    419

    218

    519

    921

    021

    921

    022

    623

    924

    923

    725

    526

    928

    026

    128

    129

    731

    0LO

    PR

    6670

    7681

    6974

    8086

    7277

    8489

    7680

    8894

    7984

    9298

    8287

    9510

    1MB

    h18

    .518

    .920

    .221

    .618

    .118

    .519

    .721

    .117

    .718

    .019

    .320

    .617

    .217

    .618

    .820

    .116

    .416

    .717

    .919

    .115

    .215

    .516

    .517

    .7S/

    T0.8

    60.8

    00.6

    50.4

    90.8

    90.8

    30.6

    80.5

    10.9

    10.8

    50.6

    90.5

    20.9