AMENDMENT NO. 1 Project No.: UHM 1168-004-17 IFB NO. UHM116800417 Page 1 of 55 AMENDMENT NO. 1 IFB NO. UHM116800417 TO THE PLANS AND SPECIFICATIONS FOR SPALDING HALL SECOND FLOOR RENOVATIONS PROJECT NO. UHM 1168-004-17 UNIVERSITY OF HAWAI‘I AT MĀNOA HONOLULU, HAWAII DECEMBER 28, 2018 This amendment modifies the original Solicitation Documents for the Project. The items listed within are hereby made a part of the contract for the above project and shall govern the work, taking precedence over previously issued plans and specifications governing the items mentioned. A. CHANGE TO DRAWINGS DISCIPLINE SHEET NUMBER DESCRIPTION None -- -- B. CHANGES TO TECHNICAL SPECIFICATIONS: The following pages of the Solicitation Documents are revised: None C. SUBSTITUTION OF MATERIALS AND EQUIPMENT SECTION / ITEMS SPECIFIED BRAND SUBSTITUTE BRAND VARIANCE STATUS FCU-1 through FCU-6 Carrier Daikin - Minor CFM variance. - Minor BTUH variance. - No valve package. No exceptions taken, subject to notes on submittal. 2.02 – FAN COIL UNIT Carrier Williams - 6 row coils required to meet sensible capacities. - Williams FCU is slight longer and slightly wider than Carrier FCU. - Williams FCU height is slightly shorter than Carrier FCU. Rejected, due to add’l rows of coil req’d as well as its larger dimensions.

Upload: others

Post on 17-Jun-2020

0 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: AMENDMENT NO. 1 TO THE PLANS AND SPECIFICATIONS FOR … No... · AMENDMENT NO. 1 Project No.: UHM 1168-004-17 IFB NO.UHM116800417 Page 2 of 55 D. REQUEST FOR INFORMATION / CLARIFICATION

AMENDMENT NO. 1 Project No.: UHM 1168-004-17 IFB NO. UHM116800417

Page 1 of 55

AMENDMENT NO. 1

IFB NO. UHM116800417

TO THE PLANS AND SPECIFICATIONS FOR

SPALDING HALL

SECOND FLOOR RENOVATIONS

PROJECT NO. UHM 1168-004-17

UNIVERSITY OF HAWAI‘I AT MĀNOA HONOLULU, HAWAII

DECEMBER 28, 2018

This amendment modifies the original Solicitation Documents for the Project. The items listed within are hereby made a part of the contract for the above project and shall govern the work, taking precedence over previously issued plans and specifications governing the items mentioned. A. CHANGE TO DRAWINGS DISCIPLINE SHEET NUMBER DESCRIPTION None -- -- B. CHANGES TO TECHNICAL SPECIFICATIONS: The following pages of the

Solicitation Documents are revised: None

C. SUBSTITUTION OF MATERIALS AND EQUIPMENT SECTION / ITEMS

SPECIFIED BRAND

SUBSTITUTE BRAND

VARIANCE STATUS

FCU-1 through FCU-6

Carrier Daikin - Minor CFM variance. - Minor BTUH variance. - No valve package.

No exceptions taken, subject to notes on submittal.

2.02 – FAN COIL UNIT

Carrier Williams

- 6 row coils required to meet sensible capacities.

- Williams FCU is slight longer and slightly wider than Carrier FCU.

- Williams FCU height is slightly shorter than Carrier FCU.

Rejected, due to add’l rows of coil req’d as well as its larger dimensions.

Page 2: AMENDMENT NO. 1 TO THE PLANS AND SPECIFICATIONS FOR … No... · AMENDMENT NO. 1 Project No.: UHM 1168-004-17 IFB NO.UHM116800417 Page 2 of 55 D. REQUEST FOR INFORMATION / CLARIFICATION

AMENDMENT NO. 1 Project No.: UHM 1168-004-17 IFB NO. UHM116800417

Page 2 of 55

D. REQUEST FOR INFORMATION / CLARIFICATION

1. In regards to Section 11080 – Audio Video Systems, please confirm the following: a. Is there a one line drawing available for reference?

Response: The AV infrastructure shown is just “point to point”, so there isn’t a need for a one-line diagram. b. Will a full set of AV Drawings be made available for reference? In the

Drawing Set, drawings AV-3, AV-4 and AV-5 are missing.

Response: Drawings are not available.

2. Which doors require STC rating and what is the STC required? Response: The Control Room and Recording Rooms have STC 51 doors. The outer vestibule door only needs to be STC 30. See AC-1 Acoustical Details Layout for reference.

E. PRE-BID CONFERENCE AND JOB SITE WALK-THROUGH

1. Pre-bid conference and site walk through was held on December 19, 2018

at 9:00am at University of Hawaii, Manoa at Spalding Hall, Second Floor.

END OF AMENDMENT NO. 1

Page 3: AMENDMENT NO. 1 TO THE PLANS AND SPECIFICATIONS FOR … No... · AMENDMENT NO. 1 Project No.: UHM 1168-004-17 IFB NO.UHM116800417 Page 2 of 55 D. REQUEST FOR INFORMATION / CLARIFICATION
Page 4: AMENDMENT NO. 1 TO THE PLANS AND SPECIFICATIONS FOR … No... · AMENDMENT NO. 1 Project No.: UHM 1168-004-17 IFB NO.UHM116800417 Page 2 of 55 D. REQUEST FOR INFORMATION / CLARIFICATION

Job Number: E21UYZ Page Prepared Date: 12/21/2018 Job Name: Spalding Hall 2nd Floor

Renovation

1 of 37 www.DaikinApplied.com

SUBMITTAL DATA

for

Spalding Hall 2nd Floor Renovation

Page 5: AMENDMENT NO. 1 TO THE PLANS AND SPECIFICATIONS FOR … No... · AMENDMENT NO. 1 Project No.: UHM 1168-004-17 IFB NO.UHM116800417 Page 2 of 55 D. REQUEST FOR INFORMATION / CLARIFICATION

Job Number: E21UYZ Page Prepared Date: 12/21/2018 Job Name: Spalding Hall 2nd Floor

Renovation

2 of 37 www.DaikinApplied.com

Table of Contents

Drawings(1) for FCU-1 ................................................................................................................................................................ 3

Item Summary for FCU-1............................................................................................................................................................ 4

Technical Data Sheet for FCU-1 .................................................................................................................................................. 6

Drawings(1) for FCU-2 ................................................................................................................................................................ 8

Item Summary for FCU-2............................................................................................................................................................ 9

Technical Data Sheet for FCU-2 ................................................................................................................................................ 11

Drawings(1) for FCU-3 .............................................................................................................................................................. 13

Item Summary for FCU-3.......................................................................................................................................................... 14

Technical Data Sheet for FCU-3 ................................................................................................................................................ 16

Drawings(1) for FCU-4 .............................................................................................................................................................. 18

Item Summary for FCU-4.......................................................................................................................................................... 19

Technical Data Sheet for FCU-4 ................................................................................................................................................ 21

Drawings(1) for FCU-5 .............................................................................................................................................................. 23

Item Summary for FCU-5.......................................................................................................................................................... 24

Technical Data Sheet for FCU-5 ................................................................................................................................................ 26

Drawings(1) for FCU-6 .............................................................................................................................................................. 28

Item Summary for FCU-6.......................................................................................................................................................... 29

Technical Data Sheet for FCU-6 ................................................................................................................................................ 31

Specification for DST Vertical Fancoil ALL ................................................................................................................................ 33

Page 6: AMENDMENT NO. 1 TO THE PLANS AND SPECIFICATIONS FOR … No... · AMENDMENT NO. 1 Project No.: UHM 1168-004-17 IFB NO.UHM116800417 Page 2 of 55 D. REQUEST FOR INFORMATION / CLARIFICATION

Job

Nam

e:

Job

Nu

mb

er:

Draw

ings(1

) for FC

U-1

Spald

ing H

all 2n

d Flo

or

Ren

ovatio

n

E21

UYZ

3 o

f 37

Page

Pre

pare

d D

ate:

ww

w.D

aikinA

pp

lied.co

m

12

/21

/20

18

Drawings(1) for FCU-1

Product Drawing Unit Tag: FCU-1 Sales Office: Norman Wright Mech. Equip. Corp.

13600 Industrial Park Blvd. Minneapolis, MN 55441

www.DaikinApplied.com Software Version: 06.70

Product: Project Name: Spalding Hall 2nd Floor Renovation

Sales Engineer:

Model: FCHH210 Dec. 21, 2018 Ver/Rev: Sheet: 1 of 1 Scale: NTS Tolerance: +/- 0.25” Dwg Units: in

No change to this drawing may be made unless approved in writing by Daikin Applied. Purchaser must determine that the equipment is fit and sufficient for the job specifications.

Page 7: AMENDMENT NO. 1 TO THE PLANS AND SPECIFICATIONS FOR … No... · AMENDMENT NO. 1 Project No.: UHM 1168-004-17 IFB NO.UHM116800417 Page 2 of 55 D. REQUEST FOR INFORMATION / CLARIFICATION

Item Summary for FCU-1

Job Number: E21UYZ Page Prepared Date: 12/21/2018 Job Name: Spalding Hall 2nd Floor

Renovation 4 of 37 www.DaikinApplied.com

Item Summary for FCU-1

Job Information Item Summary

Job Name Spalding Hall 2nd Floor Renovation Date 11/14/2018

Model FCHH210 Software Version 06.70

Unit Tag FCU-1

Unit Options

Code Item

Code Value

Description

1 FC Unit Type; Fan Coil

2 HH Product Identifier; Horizontal Hideaway

3 2 Design Series; Design 2

4 10 Unit Size; 1000 CFM

5 A Voltage - Primary and Secondary; 115/60/1

6 A Coils - Fin Type; Aluminum

7 G Coils - Casing Material; Galvanized

8 M Coils - Air Vent; Manual

9 Y Coils - Coating; None

10 06 Coil Circuiting - Primary Coil; 6 Circuits

11 C Primary Coil Type; Chilled Water Only

12 4 Rows Primary Coil; 4-Row

13 12 Fins Per Inch - Primary Coil; 12 FPI

14 L Connection Location - Primary Coil; Left Hand

15 Y Piping Package - Primary Coil; None

16 S Connection Type - Primary Coil; Sweat

17 YY Preheat Coil Type; None

18 00 Fins Per Inch - Preheat Coil; None

19 Y Connection Location - Preheat Coil; None

20 Y Piping Package - Preheat Coil; None

21 Y Connection Type - Preheat Coil; None

22 YY Coil Circuiting - Secondary Coil; None

23 YY Reheat Coil Type; None

24 00 Fins Per Inch - Reheat Coil; None

25 Y Connection Location - Reheat Coil; None

26 Y Piping Package - Reheat Coil; None

27 Y Connection Type - Reheat Coil; None

28 Y Electric Heat Power Supply; None

29 000 Electric Heat Wattage; None

30 YY Future Use - Secondary Heating; None

31 S Drain Pan Material; Stainless Steel

32 VSP Blower Motor Type; Field Adjustable ECM

33 H Discharge Conditions; High Static

34 3 Motor Speed; 3 Speed

35 Q Motor Connections; Quick Connect

36 CC ECM Blower Motor Type; Constant CFM

37 YY Fresh Air Damper; None

38 YYY Cabinet Length; Standard Cabinet

39 D Unit Disconnect Switch; Disconnect Switch, Toggle

40 L Control Voltage; 24V control voltage

41 L Control Type; LV interface board, 3 sp switch

42 Y Network Communication Card; None

43 Y Changeover Type; None

44 Y Programmability; None

45 YY Setpoint Adjustment; None

Page 8: AMENDMENT NO. 1 TO THE PLANS AND SPECIFICATIONS FOR … No... · AMENDMENT NO. 1 Project No.: UHM 1168-004-17 IFB NO.UHM116800417 Page 2 of 55 D. REQUEST FOR INFORMATION / CLARIFICATION

Item Summary for FCU-1

Job Number: E21UYZ Page Prepared Date: 12/21/2018 Job Name: Spalding Hall 2nd Floor

Renovation 5 of 37 www.DaikinApplied.com

Code Item

Code Value

Description

46 YBY Fan Speed Control; Off/Low/Med/High

47 Y Timed Override; None

48 YYYY Primary Coil Valve; None

49 YYYY Preheat Coil Valve; None

50 YYYY Reheat Coil Valve; None

51 Y Future Use - Controls; None

52 Y Low Temperature Protection; None

53 Y Condensate Overflow Protection; None

54 Y Discharge Air Thermistor; None

55 Y Smoke Input; None

56 Y Occ / Vacant Control Input; None

57 Y Filter Status; None

58 Y Fan Status; None

59 Y Entering Water Thermistor; None

60 Y Control Panel Revision; None

61 Y Cabinet Style; None

62 18 Cabinet Gauge; 18 Gauge

63 Y Cabinet Coating Type; None

64 Y Cabinet Color; None

65 00 Cabinet Depth Extension; None

66 S Unit Lineup Position; Standalone

67 00 Left Hand End Pocket Extension; None

68 00 Right Hand End Pocket Extension; None

69 YYY Subbase; None

70 FD Discharge Air - Outlet; Front Discharge, Duct Collar

71 RD Return Air - Inlet; Rear Return Air, Duct Collar

72 1 Filter; 1" Throwaway MERV 4 Filter

73 YYY Special Options; None

74 F Cabinet/Plenum; 1/2 inch Fiberglass

75 A Agency Listing; ETL, CETL, ARI

76 S Packaging; Standard

77 L Extended Warranty; 1st Year Labor Allowance

78 C Shipping Options; Standard

Page 9: AMENDMENT NO. 1 TO THE PLANS AND SPECIFICATIONS FOR … No... · AMENDMENT NO. 1 Project No.: UHM 1168-004-17 IFB NO.UHM116800417 Page 2 of 55 D. REQUEST FOR INFORMATION / CLARIFICATION

Technical Data Sheet for FCU-1

Job Number: E21UYZ Page Prepared Date: 12/21/2018 Job Name: Spalding Hall 2nd Floor

Renovation 6 of 37 www.DaikinApplied.com

Technical Data Sheet for FCU-1

Job Information Technical Data Sheet

Job Name Spalding Hall 2nd Floor Renovation

Date 12/21/2018

Submitted By Thomas Miske

Software Version 06.70

Unit Tag FCU-1

Unit Overview

Model Number Unit Size Voltage V/Hz/Phase

Air Flow CFM

External Static Pressure

inH₂O

Unit Configuration

FCHH210 10 115/60/1 509.0 0.20 Horizontal

Unit

Model Number: FCHH210 Type: Fan Coil

Orientation: Horizontal

Size: 10

Cabinet: Hideaway

Approval ETL, CETL, AHRI

Physical

Unit

Depth Width Height Shipping Weight

20.2 in 63.5 in 9.9 in 134 lb

Filters

Type (Quantity) Height x Width x Depth

1" Throwaway MERV 4 Filter (2) 9.38 in x 26.00 in x 1 in

Electrical

Unit

Voltage Fan Motor Amps Unit MCA Unit MROPD

115/60/1 V/Hz/Phase 8.5 A 10.6 A 15 A

Chilled Water Coil

Physical

Fins per Inch Number of Rows Coil Circuits Face Area Face Velocity

12 4 6 3.1 ft² 162.1 ft/min

Performance

Capacity Air Temperature

Total Btu/hr

Sensible Btu/hr

Entering Leaving

Dry Bulb °F

Wet Bulb °F

Dry Bulb °F

Wet Bulb °F

22369 15175 80.0 67.0 52.7 52.5

Fluid

Temperature Type Flow rate gpm

Pressure Drop ft H₂O Entering

°F Leaving

°F

45.0 55.0 Water 4.5 3.65

Page 10: AMENDMENT NO. 1 TO THE PLANS AND SPECIFICATIONS FOR … No... · AMENDMENT NO. 1 Project No.: UHM 1168-004-17 IFB NO.UHM116800417 Page 2 of 55 D. REQUEST FOR INFORMATION / CLARIFICATION

Technical Data Sheet for FCU-1

Job Number: E21UYZ Page Prepared Date: 12/21/2018 Job Name: Spalding Hall 2nd Floor

Renovation 7 of 37 www.DaikinApplied.com

Supply Fan

Fan

Fan Height Fan Width Quantity

8.00 in 6.00 in 4

Motor

Type Horsepower Quantity

Field Adjustable ECM (2) 1/4 hp 2

Sound

Casing Radiated Sound Power (db)

125 Hz 250 Hz 500 Hz 1 kHz 2 kHz 4 kHz 8 kHz

56 56 58 57 53 46 47

Options

General

Cabinet Plenum Insulation: 1/2 inch Fiberglass

Cabinet Gauge: 18 Gauge

Return Air Plenum: Plenum

Return Air Location: Rear

Disconnect Switch: Disconnect Switch

Warranty

Warranty: Standard

AHRI Certification

All equipment is rated and certified in accordance with AHRI 440.

Notes

Sound Power (dB) measured in accordance with ANSI/AHRI Standard 260-2008.

Page 11: AMENDMENT NO. 1 TO THE PLANS AND SPECIFICATIONS FOR … No... · AMENDMENT NO. 1 Project No.: UHM 1168-004-17 IFB NO.UHM116800417 Page 2 of 55 D. REQUEST FOR INFORMATION / CLARIFICATION

Job

Nam

e:

Job

Nu

mb

er:

Draw

ings(1

) for FC

U-2

Spald

ing H

all 2n

d Flo

or

Ren

ovatio

n

E21

UYZ

8 o

f 37

Page

Pre

pare

d D

ate:

ww

w.D

aikinA

pp

lied.co

m

12

/21

/20

18

Drawings(1) for FCU-2

Product Drawing Unit Tag: FCU-2 Sales Office: Norman Wright Mech. Equip. Corp.

13600 Industrial Park Blvd. Minneapolis, MN 55441

www.DaikinApplied.com Software Version: 06.70

Product: Project Name: Spalding Hall 2nd Floor Renovation

Sales Engineer:

Model: FCHH212 Dec. 21, 2018 Ver/Rev: Sheet: 1 of 1 Scale: NTS Tolerance: +/- 0.25” Dwg Units: in

No change to this drawing may be made unless approved in writing by Daikin Applied. Purchaser must determine that the equipment is fit and sufficient for the job specifications.

Page 12: AMENDMENT NO. 1 TO THE PLANS AND SPECIFICATIONS FOR … No... · AMENDMENT NO. 1 Project No.: UHM 1168-004-17 IFB NO.UHM116800417 Page 2 of 55 D. REQUEST FOR INFORMATION / CLARIFICATION

Item Summary for FCU-2

Job Number: E21UYZ Page Prepared Date: 12/21/2018 Job Name: Spalding Hall 2nd Floor

Renovation 9 of 37 www.DaikinApplied.com

Item Summary for FCU-2

Job Information Item Summary

Job Name Spalding Hall 2nd Floor Renovation Date 11/14/2018

Model FCHH212 Software Version 06.70

Unit Tag FCU-2

Unit Options

Code Item

Code Value

Description

1 FC Unit Type; Fan Coil

2 HH Product Identifier; Horizontal Hideaway

3 2 Design Series; Design 2

4 12 Unit Size; 1200 CFM

5 A Voltage - Primary and Secondary; 115/60/1

6 A Coils - Fin Type; Aluminum

7 G Coils - Casing Material; Galvanized

8 M Coils - Air Vent; Manual

9 Y Coils - Coating; None

10 06 Coil Circuiting - Primary Coil; 6 Circuits

11 C Primary Coil Type; Chilled Water Only

12 4 Rows Primary Coil; 4-Row

13 12 Fins Per Inch - Primary Coil; 12 FPI

14 L Connection Location - Primary Coil; Left Hand

15 Y Piping Package - Primary Coil; None

16 S Connection Type - Primary Coil; Sweat

17 YY Preheat Coil Type; None

18 00 Fins Per Inch - Preheat Coil; None

19 Y Connection Location - Preheat Coil; None

20 Y Piping Package - Preheat Coil; None

21 Y Connection Type - Preheat Coil; None

22 YY Coil Circuiting - Secondary Coil; None

23 YY Reheat Coil Type; None

24 00 Fins Per Inch - Reheat Coil; None

25 Y Connection Location - Reheat Coil; None

26 Y Piping Package - Reheat Coil; None

27 Y Connection Type - Reheat Coil; None

28 Y Electric Heat Power Supply; None

29 000 Electric Heat Wattage; None

30 YY Future Use - Secondary Heating; None

31 S Drain Pan Material; Stainless Steel

32 VSP Blower Motor Type; Field Adjustable ECM

33 H Discharge Conditions; High Static

34 3 Motor Speed; 3 Speed

35 Q Motor Connections; Quick Connect

36 CC ECM Blower Motor Type; Constant CFM

37 YY Fresh Air Damper; None

38 YYY Cabinet Length; Standard Cabinet

39 D Unit Disconnect Switch; Disconnect Switch, Toggle

40 L Control Voltage; 24V control voltage

41 L Control Type; LV interface board, 3 sp switch

42 Y Network Communication Card; None

43 Y Changeover Type; None

44 Y Programmability; None

45 YY Setpoint Adjustment; None

Page 13: AMENDMENT NO. 1 TO THE PLANS AND SPECIFICATIONS FOR … No... · AMENDMENT NO. 1 Project No.: UHM 1168-004-17 IFB NO.UHM116800417 Page 2 of 55 D. REQUEST FOR INFORMATION / CLARIFICATION

Item Summary for FCU-2

Job Number: E21UYZ Page Prepared Date: 12/21/2018 Job Name: Spalding Hall 2nd Floor

Renovation 10 of 37 www.DaikinApplied.com

Code Item

Code Value

Description

46 YBY Fan Speed Control; Off/Low/Med/High

47 Y Timed Override; None

48 YYYY Primary Coil Valve; None

49 YYYY Preheat Coil Valve; None

50 YYYY Reheat Coil Valve; None

51 Y Future Use - Controls; None

52 Y Low Temperature Protection; None

53 Y Condensate Overflow Protection; None

54 Y Discharge Air Thermistor; None

55 Y Smoke Input; None

56 Y Occ / Vacant Control Input; None

57 Y Filter Status; None

58 Y Fan Status; None

59 Y Entering Water Thermistor; None

60 Y Control Panel Revision; None

61 Y Cabinet Style; None

62 18 Cabinet Gauge; 18 Gauge

63 Y Cabinet Coating Type; None

64 Y Cabinet Color; None

65 00 Cabinet Depth Extension; None

66 S Unit Lineup Position; Standalone

67 00 Left Hand End Pocket Extension; None

68 00 Right Hand End Pocket Extension; None

69 YYY Subbase; None

70 FD Discharge Air - Outlet; Front Discharge, Duct Collar

71 RD Return Air - Inlet; Rear Return Air, Duct Collar

72 1 Filter; 1" Throwaway MERV 4 Filter

73 YYY Special Options; None

74 F Cabinet/Plenum; 1/2 inch Fiberglass

75 A Agency Listing; ETL, CETL, ARI

76 S Packaging; Standard

77 L Extended Warranty; 1st Year Labor Allowance

78 C Shipping Options; Standard

Page 14: AMENDMENT NO. 1 TO THE PLANS AND SPECIFICATIONS FOR … No... · AMENDMENT NO. 1 Project No.: UHM 1168-004-17 IFB NO.UHM116800417 Page 2 of 55 D. REQUEST FOR INFORMATION / CLARIFICATION

Technical Data Sheet for FCU-2

Job Number: E21UYZ Page Prepared Date: 12/21/2018 Job Name: Spalding Hall 2nd Floor

Renovation 11 of 37 www.DaikinApplied.com

Technical Data Sheet for FCU-2

Job Information Technical Data Sheet

Job Name Spalding Hall 2nd Floor Renovation

Date 12/21/2018

Submitted By Thomas Miske

Software Version 06.70

Unit Tag FCU-2

Unit Overview

Model Number Unit Size Voltage V/Hz/Phase

Air Flow CFM

External Static Pressure

inH₂O

Unit Configuration

FCHH212 12 115/60/1 800.0 0.20 Horizontal

Unit

Model Number: FCHH212 Type: Fan Coil

Orientation: Horizontal

Size: 12

Cabinet: Hideaway

Approval ETL, CETL, AHRI

Physical

Unit

Depth Width Height Shipping Weight

20.2 in 72.5 in 9.9 in 155 lb

Filters

Type (Quantity) Height x Width x Depth

1" Throwaway MERV 4 Filter (2) 9.38 in x 31.50 in x 1 in

Electrical

Unit

Voltage Fan Motor Amps Unit MCA Unit MROPD

115/60/1 V/Hz/Phase 8.5 A 10.6 A 15 A

Chilled Water Coil

Physical

Fins per Inch Number of Rows Coil Circuits Face Area Face Velocity

12 4 6 3.8 ft² 208.9 ft/min

Performance

Capacity Air Temperature

Total Btu/hr

Sensible Btu/hr

Entering Leaving

Dry Bulb °F

Wet Bulb °F

Dry Bulb °F

Wet Bulb °F

36121 23842 80.0 67.0 52.7 52.1

Fluid

Temperature Type Flow rate gpm

Pressure Drop ft H₂O Entering

°F Leaving

°F

45.0 55.0 Water 7.2 16.24

Page 15: AMENDMENT NO. 1 TO THE PLANS AND SPECIFICATIONS FOR … No... · AMENDMENT NO. 1 Project No.: UHM 1168-004-17 IFB NO.UHM116800417 Page 2 of 55 D. REQUEST FOR INFORMATION / CLARIFICATION

Technical Data Sheet for FCU-2

Job Number: E21UYZ Page Prepared Date: 12/21/2018 Job Name: Spalding Hall 2nd Floor

Renovation 12 of 37 www.DaikinApplied.com

Supply Fan

Fan

Fan Height Fan Width Quantity

8.00 in 6.00 in 4

Motor

Type Horsepower Quantity

Field Adjustable ECM (2) 1/4 hp 2

Sound

Casing Radiated Sound Power (db)

125 Hz 250 Hz 500 Hz 1 kHz 2 kHz 4 kHz 8 kHz

63 62 62 61 58 52 47

Options

General

Cabinet Plenum Insulation: 1/2 inch Fiberglass

Cabinet Gauge: 18 Gauge

Return Air Plenum: Plenum

Return Air Location: Rear

Disconnect Switch: Disconnect Switch

Warranty

Warranty: Standard

AHRI Certification

All equipment is rated and certified in accordance with AHRI 440.

Notes

Sound Power (dB) measured in accordance with ANSI/AHRI Standard 260-2008.

Page 16: AMENDMENT NO. 1 TO THE PLANS AND SPECIFICATIONS FOR … No... · AMENDMENT NO. 1 Project No.: UHM 1168-004-17 IFB NO.UHM116800417 Page 2 of 55 D. REQUEST FOR INFORMATION / CLARIFICATION

Job

Nam

e:

Job

Nu

mb

er:

Draw

ings(1

) for FC

U-3

Spald

ing H

all 2n

d Flo

or

Ren

ovatio

n

E21

UYZ

13

of 3

7

Page

Pre

pare

d D

ate:

ww

w.D

aikinA

pp

lied.co

m

12

/21

/20

18

Drawings(1) for FCU-3

Product Drawing Unit Tag: FCU-3 Sales Office: Norman Wright Mech. Equip. Corp.

13600 Industrial Park Blvd. Minneapolis, MN 55441

www.DaikinApplied.com Software Version: 06.70

Product: Project Name: Spalding Hall 2nd Floor Renovation

Sales Engineer:

Model: FCHH206 Dec. 21, 2018 Ver/Rev: Sheet: 1 of 1 Scale: NTS Tolerance: +/- 0.25” Dwg Units: in

No change to this drawing may be made unless approved in writing by Daikin Applied. Purchaser must determine that the equipment is fit and sufficient for the job specifications.

Page 17: AMENDMENT NO. 1 TO THE PLANS AND SPECIFICATIONS FOR … No... · AMENDMENT NO. 1 Project No.: UHM 1168-004-17 IFB NO.UHM116800417 Page 2 of 55 D. REQUEST FOR INFORMATION / CLARIFICATION

Item Summary for FCU-3

Job Number: E21UYZ Page Prepared Date: 12/21/2018 Job Name: Spalding Hall 2nd Floor

Renovation 14 of 37 www.DaikinApplied.com

Item Summary for FCU-3

Job Information Item Summary

Job Name Spalding Hall 2nd Floor Renovation Date 11/14/2018

Model FCHH206 Software Version 06.70

Unit Tag FCU-3

Unit Options

Code Item

Code Value

Description

1 FC Unit Type; Fan Coil

2 HH Product Identifier; Horizontal Hideaway

3 2 Design Series; Design 2

4 06 Unit Size; 600 CFM

5 A Voltage - Primary and Secondary; 115/60/1

6 A Coils - Fin Type; Aluminum

7 G Coils - Casing Material; Galvanized

8 M Coils - Air Vent; Manual

9 Y Coils - Coating; None

10 04 Coil Circuiting - Primary Coil; 4 Circuits

11 C Primary Coil Type; Chilled Water Only

12 4 Rows Primary Coil; 4-Row

13 12 Fins Per Inch - Primary Coil; 12 FPI

14 L Connection Location - Primary Coil; Left Hand

15 Y Piping Package - Primary Coil; None

16 S Connection Type - Primary Coil; Sweat

17 YY Preheat Coil Type; None

18 00 Fins Per Inch - Preheat Coil; None

19 Y Connection Location - Preheat Coil; None

20 Y Piping Package - Preheat Coil; None

21 Y Connection Type - Preheat Coil; None

22 YY Coil Circuiting - Secondary Coil; None

23 YY Reheat Coil Type; None

24 00 Fins Per Inch - Reheat Coil; None

25 Y Connection Location - Reheat Coil; None

26 Y Piping Package - Reheat Coil; None

27 Y Connection Type - Reheat Coil; None

28 Y Electric Heat Power Supply; None

29 000 Electric Heat Wattage; None

30 YY Future Use - Secondary Heating; None

31 S Drain Pan Material; Stainless Steel

32 VSP Blower Motor Type; Field Adjustable ECM

33 H Discharge Conditions; High Static

34 3 Motor Speed; 3 Speed

35 Q Motor Connections; Quick Connect

36 CC ECM Blower Motor Type; Constant CFM

37 YY Fresh Air Damper; None

38 YYY Cabinet Length; Standard Cabinet

39 D Unit Disconnect Switch; Disconnect Switch, Toggle

40 L Control Voltage; 24V control voltage

41 L Control Type; LV interface board, 3 sp switch

42 Y Network Communication Card; None

43 Y Changeover Type; None

44 Y Programmability; None

45 YY Setpoint Adjustment; None

Page 18: AMENDMENT NO. 1 TO THE PLANS AND SPECIFICATIONS FOR … No... · AMENDMENT NO. 1 Project No.: UHM 1168-004-17 IFB NO.UHM116800417 Page 2 of 55 D. REQUEST FOR INFORMATION / CLARIFICATION

Item Summary for FCU-3

Job Number: E21UYZ Page Prepared Date: 12/21/2018 Job Name: Spalding Hall 2nd Floor

Renovation 15 of 37 www.DaikinApplied.com

Code Item

Code Value

Description

46 YBY Fan Speed Control; Off/Low/Med/High

47 Y Timed Override; None

48 YYYY Primary Coil Valve; None

49 YYYY Preheat Coil Valve; None

50 YYYY Reheat Coil Valve; None

51 Y Future Use - Controls; None

52 Y Low Temperature Protection; None

53 Y Condensate Overflow Protection; None

54 Y Discharge Air Thermistor; None

55 Y Smoke Input; None

56 Y Occ / Vacant Control Input; None

57 Y Filter Status; None

58 Y Fan Status; None

59 Y Entering Water Thermistor; None

60 Y Control Panel Revision; None

61 Y Cabinet Style; None

62 18 Cabinet Gauge; 18 Gauge

63 Y Cabinet Coating Type; None

64 Y Cabinet Color; None

65 00 Cabinet Depth Extension; None

66 S Unit Lineup Position; Standalone

67 00 Left Hand End Pocket Extension; None

68 00 Right Hand End Pocket Extension; None

69 YYY Subbase; None

70 FD Discharge Air - Outlet; Front Discharge, Duct Collar

71 RD Return Air - Inlet; Rear Return Air, Duct Collar

72 1 Filter; 1" Throwaway MERV 4 Filter

73 YYY Special Options; None

74 F Cabinet/Plenum; 1/2 inch Fiberglass

75 A Agency Listing; ETL, CETL, ARI

76 S Packaging; Standard

77 L Extended Warranty; 1st Year Labor Allowance

78 C Shipping Options; Standard

Page 19: AMENDMENT NO. 1 TO THE PLANS AND SPECIFICATIONS FOR … No... · AMENDMENT NO. 1 Project No.: UHM 1168-004-17 IFB NO.UHM116800417 Page 2 of 55 D. REQUEST FOR INFORMATION / CLARIFICATION

Technical Data Sheet for FCU-3

Job Number: E21UYZ Page Prepared Date: 12/21/2018 Job Name: Spalding Hall 2nd Floor

Renovation 16 of 37 www.DaikinApplied.com

Technical Data Sheet for FCU-3

Job Information Technical Data Sheet

Job Name Spalding Hall 2nd Floor Renovation

Date 12/21/2018

Submitted By Thomas Miske

Software Version 06.70

Unit Tag FCU-3

Unit Overview

Model Number Unit Size Voltage V/Hz/Phase

Air Flow CFM

External Static Pressure

inH₂O

Unit Configuration

FCHH206 06 115/60/1 308.0 0.20 Horizontal

Unit

Model Number: FCHH206 Type: Fan Coil

Orientation: Horizontal

Size: 06

Cabinet: Hideaway

Approval ETL, CETL, AHRI

Physical

Unit

Depth Width Height Shipping Weight

20.2 in 47.0 in 9.9 in 94 lb

Filters

Type (Quantity) Height x Width x Depth

1" Throwaway MERV 4 Filter (1) 9.38 in x 35.75 in x 1 in

Electrical

Unit

Voltage Fan Motor Amps Unit MCA Unit MROPD

115/60/1 V/Hz/Phase 4.2 A 5.3 A 15 A

Chilled Water Coil

Physical

Fins per Inch Number of Rows Coil Circuits Face Area Face Velocity

12 4 4 2.1 ft² 146.0 ft/min

Performance

Capacity Air Temperature

Total Btu/hr

Sensible Btu/hr

Entering Leaving

Dry Bulb °F

Wet Bulb °F

Dry Bulb °F

Wet Bulb °F

13103 9003 80.0 67.0 53.3 53.1

Fluid

Temperature Type Flow rate gpm

Pressure Drop ft H₂O Entering

°F Leaving

°F

45.0 55.0 Water 2.6 3.63

Page 20: AMENDMENT NO. 1 TO THE PLANS AND SPECIFICATIONS FOR … No... · AMENDMENT NO. 1 Project No.: UHM 1168-004-17 IFB NO.UHM116800417 Page 2 of 55 D. REQUEST FOR INFORMATION / CLARIFICATION

Technical Data Sheet for FCU-3

Job Number: E21UYZ Page Prepared Date: 12/21/2018 Job Name: Spalding Hall 2nd Floor

Renovation 17 of 37 www.DaikinApplied.com

Supply Fan

Fan

Fan Height Fan Width Quantity

8.00 in 6.00 in 2

Motor

Type Horsepower Quantity

Field Adjustable ECM 1/4 hp 1

Sound

Casing Radiated Sound Power (db)

125 Hz 250 Hz 500 Hz 1 kHz 2 kHz 4 kHz 8 kHz

54 56 57 56 52 45 39

Options

General

Cabinet Plenum Insulation: 1/2 inch Fiberglass

Cabinet Gauge: 18 Gauge

Return Air Plenum: Plenum

Return Air Location: Rear

Disconnect Switch: Disconnect Switch

Warranty

Warranty: Standard

AHRI Certification

All equipment is rated and certified in accordance with AHRI 440.

Notes

Sound Power (dB) measured in accordance with ANSI/AHRI Standard 260-2008.

Page 21: AMENDMENT NO. 1 TO THE PLANS AND SPECIFICATIONS FOR … No... · AMENDMENT NO. 1 Project No.: UHM 1168-004-17 IFB NO.UHM116800417 Page 2 of 55 D. REQUEST FOR INFORMATION / CLARIFICATION

Job

Nam

e:

Job

Nu

mb

er:

Draw

ings(1

) for FC

U-4

Spald

ing H

all 2n

d Flo

or

Ren

ovatio

n

E21

UYZ

18

of 3

7

Page

Pre

pare

d D

ate:

ww

w.D

aikinA

pp

lied.co

m

12

/21

/20

18

Drawings(1) for FCU-4

Product Drawing Unit Tag: FCU-4 Sales Office: Norman Wright Mech. Equip. Corp.

13600 Industrial Park Blvd. Minneapolis, MN 55441

www.DaikinApplied.com Software Version: 06.70

Product: Project Name: Spalding Hall 2nd Floor Renovation

Sales Engineer:

Model: FCHH210 Dec. 21, 2018 Ver/Rev: Sheet: 1 of 1 Scale: NTS Tolerance: +/- 0.25” Dwg Units: in

No change to this drawing may be made unless approved in writing by Daikin Applied. Purchaser must determine that the equipment is fit and sufficient for the job specifications.

Page 22: AMENDMENT NO. 1 TO THE PLANS AND SPECIFICATIONS FOR … No... · AMENDMENT NO. 1 Project No.: UHM 1168-004-17 IFB NO.UHM116800417 Page 2 of 55 D. REQUEST FOR INFORMATION / CLARIFICATION

Item Summary for FCU-4

Job Number: E21UYZ Page Prepared Date: 12/21/2018 Job Name: Spalding Hall 2nd Floor

Renovation 19 of 37 www.DaikinApplied.com

Item Summary for FCU-4

Job Information Item Summary

Job Name Spalding Hall 2nd Floor Renovation Date 11/14/2018

Model FCHH210 Software Version 06.70

Unit Tag FCU-4

Unit Options

Code Item

Code Value

Description

1 FC Unit Type; Fan Coil

2 HH Product Identifier; Horizontal Hideaway

3 2 Design Series; Design 2

4 10 Unit Size; 1000 CFM

5 A Voltage - Primary and Secondary; 115/60/1

6 A Coils - Fin Type; Aluminum

7 G Coils - Casing Material; Galvanized

8 M Coils - Air Vent; Manual

9 Y Coils - Coating; None

10 06 Coil Circuiting - Primary Coil; 6 Circuits

11 C Primary Coil Type; Chilled Water Only

12 4 Rows Primary Coil; 4-Row

13 12 Fins Per Inch - Primary Coil; 12 FPI

14 L Connection Location - Primary Coil; Left Hand

15 Y Piping Package - Primary Coil; None

16 S Connection Type - Primary Coil; Sweat

17 YY Preheat Coil Type; None

18 00 Fins Per Inch - Preheat Coil; None

19 Y Connection Location - Preheat Coil; None

20 Y Piping Package - Preheat Coil; None

21 Y Connection Type - Preheat Coil; None

22 YY Coil Circuiting - Secondary Coil; None

23 YY Reheat Coil Type; None

24 00 Fins Per Inch - Reheat Coil; None

25 Y Connection Location - Reheat Coil; None

26 Y Piping Package - Reheat Coil; None

27 Y Connection Type - Reheat Coil; None

28 Y Electric Heat Power Supply; None

29 000 Electric Heat Wattage; None

30 YY Future Use - Secondary Heating; None

31 S Drain Pan Material; Stainless Steel

32 VSP Blower Motor Type; Field Adjustable ECM

33 H Discharge Conditions; High Static

34 3 Motor Speed; 3 Speed

35 Q Motor Connections; Quick Connect

36 CC ECM Blower Motor Type; Constant CFM

37 YY Fresh Air Damper; None

38 YYY Cabinet Length; Standard Cabinet

39 D Unit Disconnect Switch; Disconnect Switch, Toggle

40 L Control Voltage; 24V control voltage

41 L Control Type; LV interface board, 3 sp switch

42 Y Network Communication Card; None

43 Y Changeover Type; None

44 Y Programmability; None

45 YY Setpoint Adjustment; None

Page 23: AMENDMENT NO. 1 TO THE PLANS AND SPECIFICATIONS FOR … No... · AMENDMENT NO. 1 Project No.: UHM 1168-004-17 IFB NO.UHM116800417 Page 2 of 55 D. REQUEST FOR INFORMATION / CLARIFICATION

Item Summary for FCU-4

Job Number: E21UYZ Page Prepared Date: 12/21/2018 Job Name: Spalding Hall 2nd Floor

Renovation 20 of 37 www.DaikinApplied.com

Code Item

Code Value

Description

46 YBY Fan Speed Control; Off/Low/Med/High

47 Y Timed Override; None

48 YYYY Primary Coil Valve; None

49 YYYY Preheat Coil Valve; None

50 YYYY Reheat Coil Valve; None

51 Y Future Use - Controls; None

52 Y Low Temperature Protection; None

53 Y Condensate Overflow Protection; None

54 Y Discharge Air Thermistor; None

55 Y Smoke Input; None

56 Y Occ / Vacant Control Input; None

57 Y Filter Status; None

58 Y Fan Status; None

59 Y Entering Water Thermistor; None

60 Y Control Panel Revision; None

61 Y Cabinet Style; None

62 18 Cabinet Gauge; 18 Gauge

63 Y Cabinet Coating Type; None

64 Y Cabinet Color; None

65 00 Cabinet Depth Extension; None

66 S Unit Lineup Position; Standalone

67 00 Left Hand End Pocket Extension; None

68 00 Right Hand End Pocket Extension; None

69 YYY Subbase; None

70 FD Discharge Air - Outlet; Front Discharge, Duct Collar

71 RD Return Air - Inlet; Rear Return Air, Duct Collar

72 1 Filter; 1" Throwaway MERV 4 Filter

73 YYY Special Options; None

74 F Cabinet/Plenum; 1/2 inch Fiberglass

75 A Agency Listing; ETL, CETL, ARI

76 S Packaging; Standard

77 L Extended Warranty; 1st Year Labor Allowance

78 C Shipping Options; Standard

Page 24: AMENDMENT NO. 1 TO THE PLANS AND SPECIFICATIONS FOR … No... · AMENDMENT NO. 1 Project No.: UHM 1168-004-17 IFB NO.UHM116800417 Page 2 of 55 D. REQUEST FOR INFORMATION / CLARIFICATION

Technical Data Sheet for FCU-4

Job Number: E21UYZ Page Prepared Date: 12/21/2018 Job Name: Spalding Hall 2nd Floor

Renovation 21 of 37 www.DaikinApplied.com

Technical Data Sheet for FCU-4

Job Information Technical Data Sheet

Job Name Spalding Hall 2nd Floor Renovation

Date 12/21/2018

Submitted By Thomas Miske

Software Version 06.70

Unit Tag FCU-4

Unit Overview

Model Number Unit Size Voltage V/Hz/Phase

Air Flow CFM

External Static Pressure

inH₂O

Unit Configuration

FCHH210 10 115/60/1 509.0 0.20 Horizontal

Unit

Model Number: FCHH210 Type: Fan Coil

Orientation: Horizontal

Size: 10

Cabinet: Hideaway

Approval ETL, CETL, AHRI

Physical

Unit

Depth Width Height Shipping Weight

20.2 in 63.5 in 9.9 in 134 lb

Filters

Type (Quantity) Height x Width x Depth

1" Throwaway MERV 4 Filter (2) 9.38 in x 26.00 in x 1 in

Electrical

Unit

Voltage Fan Motor Amps Unit MCA Unit MROPD

115/60/1 V/Hz/Phase 8.5 A 10.6 A 15 A

Chilled Water Coil

Physical

Fins per Inch Number of Rows Coil Circuits Face Area Face Velocity

12 4 6 3.1 ft² 162.1 ft/min

Performance

Capacity Air Temperature

Total Btu/hr

Sensible Btu/hr

Entering Leaving

Dry Bulb °F

Wet Bulb °F

Dry Bulb °F

Wet Bulb °F

22369 15175 80.0 67.0 52.7 52.5

Fluid

Temperature Type Flow rate gpm

Pressure Drop ft H₂O Entering

°F Leaving

°F

45.0 55.0 Water 4.5 3.65

Page 25: AMENDMENT NO. 1 TO THE PLANS AND SPECIFICATIONS FOR … No... · AMENDMENT NO. 1 Project No.: UHM 1168-004-17 IFB NO.UHM116800417 Page 2 of 55 D. REQUEST FOR INFORMATION / CLARIFICATION

Technical Data Sheet for FCU-4

Job Number: E21UYZ Page Prepared Date: 12/21/2018 Job Name: Spalding Hall 2nd Floor

Renovation 22 of 37 www.DaikinApplied.com

Supply Fan

Fan

Fan Height Fan Width Quantity

8.00 in 6.00 in 4

Motor

Type Horsepower Quantity

Field Adjustable ECM (2) 1/4 hp 2

Sound

Casing Radiated Sound Power (db)

125 Hz 250 Hz 500 Hz 1 kHz 2 kHz 4 kHz 8 kHz

56 56 58 57 53 46 47

Options

General

Cabinet Plenum Insulation: 1/2 inch Fiberglass

Cabinet Gauge: 18 Gauge

Return Air Plenum: Plenum

Return Air Location: Rear

Disconnect Switch: Disconnect Switch

Warranty

Warranty: Standard

AHRI Certification

All equipment is rated and certified in accordance with AHRI 440.

Notes

Sound Power (dB) measured in accordance with ANSI/AHRI Standard 260-2008.

Page 26: AMENDMENT NO. 1 TO THE PLANS AND SPECIFICATIONS FOR … No... · AMENDMENT NO. 1 Project No.: UHM 1168-004-17 IFB NO.UHM116800417 Page 2 of 55 D. REQUEST FOR INFORMATION / CLARIFICATION

Job

Nam

e:

Job

Nu

mb

er:

Draw

ings(1

) for FC

U-5

Spald

ing H

all 2n

d Flo

or

Ren

ovatio

n

E21

UYZ

23

of 3

7

Page

Pre

pare

d D

ate:

ww

w.D

aikinA

pp

lied.co

m

12

/21

/20

18

Drawings(1) for FCU-5

Product Drawing Unit Tag: FCU-5 Sales Office: Norman Wright Mech. Equip. Corp.

13600 Industrial Park Blvd. Minneapolis, MN 55441

www.DaikinApplied.com Software Version: 06.70

Product: Project Name: Spalding Hall 2nd Floor Renovation

Sales Engineer:

Model: FCHH204 Dec. 21, 2018 Ver/Rev: Sheet: 1 of 1 Scale: NTS Tolerance: +/- 0.25” Dwg Units: in

No change to this drawing may be made unless approved in writing by Daikin Applied. Purchaser must determine that the equipment is fit and sufficient for the job specifications.

Page 27: AMENDMENT NO. 1 TO THE PLANS AND SPECIFICATIONS FOR … No... · AMENDMENT NO. 1 Project No.: UHM 1168-004-17 IFB NO.UHM116800417 Page 2 of 55 D. REQUEST FOR INFORMATION / CLARIFICATION

Item Summary for FCU-5

Job Number: E21UYZ Page Prepared Date: 12/21/2018 Job Name: Spalding Hall 2nd Floor

Renovation 24 of 37 www.DaikinApplied.com

Item Summary for FCU-5

Job Information Item Summary

Job Name Spalding Hall 2nd Floor Renovation Date 11/14/2018

Model FCHH204 Software Version 06.70

Unit Tag FCU-5

Unit Options

Code Item

Code Value

Description

1 FC Unit Type; Fan Coil

2 HH Product Identifier; Horizontal Hideaway

3 2 Design Series; Design 2

4 04 Unit Size; 400 CFM

5 A Voltage - Primary and Secondary; 115/60/1

6 A Coils - Fin Type; Aluminum

7 G Coils - Casing Material; Galvanized

8 M Coils - Air Vent; Manual

9 Y Coils - Coating; None

10 04 Coil Circuiting - Primary Coil; 4 Circuits

11 C Primary Coil Type; Chilled Water Only

12 4 Rows Primary Coil; 4-Row

13 12 Fins Per Inch - Primary Coil; 12 FPI

14 L Connection Location - Primary Coil; Left Hand

15 Y Piping Package - Primary Coil; None

16 S Connection Type - Primary Coil; Sweat

17 YY Preheat Coil Type; None

18 00 Fins Per Inch - Preheat Coil; None

19 Y Connection Location - Preheat Coil; None

20 Y Piping Package - Preheat Coil; None

21 Y Connection Type - Preheat Coil; None

22 YY Coil Circuiting - Secondary Coil; None

23 YY Reheat Coil Type; None

24 00 Fins Per Inch - Reheat Coil; None

25 Y Connection Location - Reheat Coil; None

26 Y Piping Package - Reheat Coil; None

27 Y Connection Type - Reheat Coil; None

28 Y Electric Heat Power Supply; None

29 000 Electric Heat Wattage; None

30 YY Future Use - Secondary Heating; None

31 S Drain Pan Material; Stainless Steel

32 VSP Blower Motor Type; Field Adjustable ECM

33 H Discharge Conditions; High Static

34 3 Motor Speed; 3 Speed

35 Q Motor Connections; Quick Connect

36 CC ECM Blower Motor Type; Constant CFM

37 YY Fresh Air Damper; None

38 YYY Cabinet Length; Standard Cabinet

39 D Unit Disconnect Switch; Disconnect Switch, Toggle

40 L Control Voltage; 24V control voltage

41 L Control Type; LV interface board, 3 sp switch

42 Y Network Communication Card; None

43 Y Changeover Type; None

44 Y Programmability; None

45 YY Setpoint Adjustment; None

Page 28: AMENDMENT NO. 1 TO THE PLANS AND SPECIFICATIONS FOR … No... · AMENDMENT NO. 1 Project No.: UHM 1168-004-17 IFB NO.UHM116800417 Page 2 of 55 D. REQUEST FOR INFORMATION / CLARIFICATION

Item Summary for FCU-5

Job Number: E21UYZ Page Prepared Date: 12/21/2018 Job Name: Spalding Hall 2nd Floor

Renovation 25 of 37 www.DaikinApplied.com

Code Item

Code Value

Description

46 YBY Fan Speed Control; Off/Low/Med/High

47 Y Timed Override; None

48 YYYY Primary Coil Valve; None

49 YYYY Preheat Coil Valve; None

50 YYYY Reheat Coil Valve; None

51 Y Future Use - Controls; None

52 Y Low Temperature Protection; None

53 Y Condensate Overflow Protection; None

54 Y Discharge Air Thermistor; None

55 Y Smoke Input; None

56 Y Occ / Vacant Control Input; None

57 Y Filter Status; None

58 Y Fan Status; None

59 Y Entering Water Thermistor; None

60 Y Control Panel Revision; None

61 Y Cabinet Style; None

62 18 Cabinet Gauge; 18 Gauge

63 Y Cabinet Coating Type; None

64 Y Cabinet Color; None

65 00 Cabinet Depth Extension; None

66 S Unit Lineup Position; Standalone

67 00 Left Hand End Pocket Extension; None

68 00 Right Hand End Pocket Extension; None

69 YYY Subbase; None

70 FD Discharge Air - Outlet; Front Discharge, Duct Collar

71 RD Return Air - Inlet; Rear Return Air, Duct Collar

72 1 Filter; 1" Throwaway MERV 4 Filter

73 YYY Special Options; None

74 F Cabinet/Plenum; 1/2 inch Fiberglass

75 A Agency Listing; ETL, CETL, ARI

76 S Packaging; Standard

77 L Extended Warranty; 1st Year Labor Allowance

78 C Shipping Options; Standard

Page 29: AMENDMENT NO. 1 TO THE PLANS AND SPECIFICATIONS FOR … No... · AMENDMENT NO. 1 Project No.: UHM 1168-004-17 IFB NO.UHM116800417 Page 2 of 55 D. REQUEST FOR INFORMATION / CLARIFICATION

Technical Data Sheet for FCU-5

Job Number: E21UYZ Page Prepared Date: 12/21/2018 Job Name: Spalding Hall 2nd Floor

Renovation 26 of 37 www.DaikinApplied.com

Technical Data Sheet for FCU-5

Job Information Technical Data Sheet

Job Name Spalding Hall 2nd Floor Renovation

Date 12/21/2018

Submitted By Thomas Miske

Software Version 06.70

Unit Tag FCU-5

Unit Overview

Model Number Unit Size Voltage V/Hz/Phase

Air Flow CFM

External Static Pressure

inH₂O

Unit Configuration

FCHH204 04 115/60/1 225.0 0.20 Horizontal

Unit

Model Number: FCHH204 Type: Fan Coil

Orientation: Horizontal

Size: 04

Cabinet: Hideaway

Approval ETL, CETL, AHRI

Physical

Unit

Depth Width Height Shipping Weight

20.2 in 36.0 in 9.9 in 76 lb

Filters

Type (Quantity) Height x Width x Depth

1" Throwaway MERV 4 Filter (1) 9.38 in x 24.75 in x 1 in

Electrical

Unit

Voltage Fan Motor Amps Unit MCA Unit MROPD

115/60/1 V/Hz/Phase 4.2 A 5.3 A 15 A

Chilled Water Coil

Physical

Fins per Inch Number of Rows Coil Circuits Face Area Face Velocity

12 4 4 1.4 ft² 157.3 ft/min

Performance

Capacity Air Temperature

Total Btu/hr

Sensible Btu/hr

Entering Leaving

Dry Bulb °F

Wet Bulb °F

Dry Bulb °F

Wet Bulb °F

9995 6753 80.0 67.0 52.6 52.4

Fluid

Temperature Type Flow rate gpm

Pressure Drop ft H₂O Entering

°F Leaving

°F

45.0 55.0 Water 2.0 1.80

Page 30: AMENDMENT NO. 1 TO THE PLANS AND SPECIFICATIONS FOR … No... · AMENDMENT NO. 1 Project No.: UHM 1168-004-17 IFB NO.UHM116800417 Page 2 of 55 D. REQUEST FOR INFORMATION / CLARIFICATION

Technical Data Sheet for FCU-5

Job Number: E21UYZ Page Prepared Date: 12/21/2018 Job Name: Spalding Hall 2nd Floor

Renovation 27 of 37 www.DaikinApplied.com

Supply Fan

Fan

Fan Height Fan Width Quantity

8.00 in 6.00 in 2

Motor

Type Horsepower Quantity

Field Adjustable ECM 1/8 hp 1

Sound

Casing Radiated Sound Power (db)

125 Hz 250 Hz 500 Hz 1 kHz 2 kHz 4 kHz 8 kHz

53 54 51 49 44 35 33

Options

General

Cabinet Plenum Insulation: 1/2 inch Fiberglass

Cabinet Gauge: 18 Gauge

Return Air Plenum: Plenum

Return Air Location: Rear

Disconnect Switch: Disconnect Switch

Warranty

Warranty: Standard

AHRI Certification

All equipment is rated and certified in accordance with AHRI 440.

Notes

Sound Power (dB) measured in accordance with ANSI/AHRI Standard 260-2008.

Page 31: AMENDMENT NO. 1 TO THE PLANS AND SPECIFICATIONS FOR … No... · AMENDMENT NO. 1 Project No.: UHM 1168-004-17 IFB NO.UHM116800417 Page 2 of 55 D. REQUEST FOR INFORMATION / CLARIFICATION

Job

Nam

e:

Job

Nu

mb

er:

Draw

ings(1

) for FC

U-6

Spald

ing H

all 2n

d Flo

or

Ren

ovatio

n

E21

UYZ

28

of 3

7

Page

Pre

pare

d D

ate:

ww

w.D

aikinA

pp

lied.co

m

12

/21

/20

18

Drawings(1) for FCU-6

Product Drawing Unit Tag: FCU-6 Sales Office: Norman Wright Mech. Equip. Corp.

13600 Industrial Park Blvd. Minneapolis, MN 55441

www.DaikinApplied.com Software Version: 06.70

Product: Project Name: Spalding Hall 2nd Floor Renovation

Sales Engineer:

Model: FCHH204 Dec. 21, 2018 Ver/Rev: Sheet: 1 of 1 Scale: NTS Tolerance: +/- 0.25” Dwg Units: in

No change to this drawing may be made unless approved in writing by Daikin Applied. Purchaser must determine that the equipment is fit and sufficient for the job specifications.

Page 32: AMENDMENT NO. 1 TO THE PLANS AND SPECIFICATIONS FOR … No... · AMENDMENT NO. 1 Project No.: UHM 1168-004-17 IFB NO.UHM116800417 Page 2 of 55 D. REQUEST FOR INFORMATION / CLARIFICATION

Item Summary for FCU-6

Job Number: E21UYZ Page Prepared Date: 12/21/2018 Job Name: Spalding Hall 2nd Floor

Renovation 29 of 37 www.DaikinApplied.com

Item Summary for FCU-6

Job Information Item Summary

Job Name Spalding Hall 2nd Floor Renovation Date 11/14/2018

Model FCHH204 Software Version 06.70

Unit Tag FCU-6

Unit Options

Code Item

Code Value

Description

1 FC Unit Type; Fan Coil

2 HH Product Identifier; Horizontal Hideaway

3 2 Design Series; Design 2

4 04 Unit Size; 400 CFM

5 A Voltage - Primary and Secondary; 115/60/1

6 A Coils - Fin Type; Aluminum

7 G Coils - Casing Material; Galvanized

8 M Coils - Air Vent; Manual

9 Y Coils - Coating; None

10 04 Coil Circuiting - Primary Coil; 4 Circuits

11 C Primary Coil Type; Chilled Water Only

12 4 Rows Primary Coil; 4-Row

13 12 Fins Per Inch - Primary Coil; 12 FPI

14 L Connection Location - Primary Coil; Left Hand

15 Y Piping Package - Primary Coil; None

16 S Connection Type - Primary Coil; Sweat

17 YY Preheat Coil Type; None

18 00 Fins Per Inch - Preheat Coil; None

19 Y Connection Location - Preheat Coil; None

20 Y Piping Package - Preheat Coil; None

21 Y Connection Type - Preheat Coil; None

22 YY Coil Circuiting - Secondary Coil; None

23 YY Reheat Coil Type; None

24 00 Fins Per Inch - Reheat Coil; None

25 Y Connection Location - Reheat Coil; None

26 Y Piping Package - Reheat Coil; None

27 Y Connection Type - Reheat Coil; None

28 Y Electric Heat Power Supply; None

29 000 Electric Heat Wattage; None

30 YY Future Use - Secondary Heating; None

31 S Drain Pan Material; Stainless Steel

32 VSP Blower Motor Type; Field Adjustable ECM

33 H Discharge Conditions; High Static

34 3 Motor Speed; 3 Speed

35 Q Motor Connections; Quick Connect

36 CC ECM Blower Motor Type; Constant CFM

37 YY Fresh Air Damper; None

38 YYY Cabinet Length; Standard Cabinet

39 D Unit Disconnect Switch; Disconnect Switch, Toggle

40 L Control Voltage; 24V control voltage

41 L Control Type; LV interface board, 3 sp switch

42 Y Network Communication Card; None

43 Y Changeover Type; None

44 Y Programmability; None

45 YY Setpoint Adjustment; None

Page 33: AMENDMENT NO. 1 TO THE PLANS AND SPECIFICATIONS FOR … No... · AMENDMENT NO. 1 Project No.: UHM 1168-004-17 IFB NO.UHM116800417 Page 2 of 55 D. REQUEST FOR INFORMATION / CLARIFICATION

Item Summary for FCU-6

Job Number: E21UYZ Page Prepared Date: 12/21/2018 Job Name: Spalding Hall 2nd Floor

Renovation 30 of 37 www.DaikinApplied.com

Code Item

Code Value

Description

46 YBY Fan Speed Control; Off/Low/Med/High

47 Y Timed Override; None

48 YYYY Primary Coil Valve; None

49 YYYY Preheat Coil Valve; None

50 YYYY Reheat Coil Valve; None

51 Y Future Use - Controls; None

52 Y Low Temperature Protection; None

53 Y Condensate Overflow Protection; None

54 Y Discharge Air Thermistor; None

55 Y Smoke Input; None

56 Y Occ / Vacant Control Input; None

57 Y Filter Status; None

58 Y Fan Status; None

59 Y Entering Water Thermistor; None

60 Y Control Panel Revision; None

61 Y Cabinet Style; None

62 18 Cabinet Gauge; 18 Gauge

63 Y Cabinet Coating Type; None

64 Y Cabinet Color; None

65 00 Cabinet Depth Extension; None

66 S Unit Lineup Position; Standalone

67 00 Left Hand End Pocket Extension; None

68 00 Right Hand End Pocket Extension; None

69 YYY Subbase; None

70 FD Discharge Air - Outlet; Front Discharge, Duct Collar

71 RD Return Air - Inlet; Rear Return Air, Duct Collar

72 1 Filter; 1" Throwaway MERV 4 Filter

73 YYY Special Options; None

74 F Cabinet/Plenum; 1/2 inch Fiberglass

75 A Agency Listing; ETL, CETL, ARI

76 S Packaging; Standard

77 L Extended Warranty; 1st Year Labor Allowance

78 C Shipping Options; Standard

Page 34: AMENDMENT NO. 1 TO THE PLANS AND SPECIFICATIONS FOR … No... · AMENDMENT NO. 1 Project No.: UHM 1168-004-17 IFB NO.UHM116800417 Page 2 of 55 D. REQUEST FOR INFORMATION / CLARIFICATION

Technical Data Sheet for FCU-6

Job Number: E21UYZ Page Prepared Date: 12/21/2018 Job Name: Spalding Hall 2nd Floor

Renovation 31 of 37 www.DaikinApplied.com

Technical Data Sheet for FCU-6

Job Information Technical Data Sheet

Job Name Spalding Hall 2nd Floor Renovation

Date 12/21/2018

Submitted By Thomas Miske

Software Version 06.70

Unit Tag FCU-6

Unit Overview

Model Number Unit Size Voltage V/Hz/Phase

Air Flow CFM

External Static Pressure

inH₂O

Unit Configuration

FCHH204 04 115/60/1 225.0 0.20 Horizontal

Unit

Model Number: FCHH204 Type: Fan Coil

Orientation: Horizontal

Size: 04

Cabinet: Hideaway

Approval ETL, CETL, AHRI

Physical

Unit

Depth Width Height Shipping Weight

20.2 in 36.0 in 9.9 in 76 lb

Filters

Type (Quantity) Height x Width x Depth

1" Throwaway MERV 4 Filter (1) 9.38 in x 24.75 in x 1 in

Electrical

Unit

Voltage Fan Motor Amps Unit MCA Unit MROPD

115/60/1 V/Hz/Phase 4.2 A 5.3 A 15 A

Chilled Water Coil

Physical

Fins per Inch Number of Rows Coil Circuits Face Area Face Velocity

12 4 4 1.4 ft² 157.3 ft/min

Performance

Capacity Air Temperature

Total Btu/hr

Sensible Btu/hr

Entering Leaving

Dry Bulb °F

Wet Bulb °F

Dry Bulb °F

Wet Bulb °F

9995 6753 80.0 67.0 52.6 52.4

Fluid

Temperature Type Flow rate gpm

Pressure Drop ft H₂O Entering

°F Leaving

°F

45.0 55.0 Water 2.0 1.80

Page 35: AMENDMENT NO. 1 TO THE PLANS AND SPECIFICATIONS FOR … No... · AMENDMENT NO. 1 Project No.: UHM 1168-004-17 IFB NO.UHM116800417 Page 2 of 55 D. REQUEST FOR INFORMATION / CLARIFICATION

Technical Data Sheet for FCU-6

Job Number: E21UYZ Page Prepared Date: 12/21/2018 Job Name: Spalding Hall 2nd Floor

Renovation 32 of 37 www.DaikinApplied.com

Supply Fan

Fan

Fan Height Fan Width Quantity

8.00 in 6.00 in 2

Motor

Type Horsepower Quantity

Field Adjustable ECM 1/8 hp 1

Sound

Casing Radiated Sound Power (db)

125 Hz 250 Hz 500 Hz 1 kHz 2 kHz 4 kHz 8 kHz

53 54 51 49 44 35 33

Options

General

Cabinet Plenum Insulation: 1/2 inch Fiberglass

Cabinet Gauge: 18 Gauge

Return Air Plenum: Plenum

Return Air Location: Rear

Disconnect Switch: Disconnect Switch

Warranty

Warranty: Standard

AHRI Certification

All equipment is rated and certified in accordance with AHRI 440.

Notes

Sound Power (dB) measured in accordance with ANSI/AHRI Standard 260-2008.

Page 36: AMENDMENT NO. 1 TO THE PLANS AND SPECIFICATIONS FOR … No... · AMENDMENT NO. 1 Project No.: UHM 1168-004-17 IFB NO.UHM116800417 Page 2 of 55 D. REQUEST FOR INFORMATION / CLARIFICATION

Specification for DST Vertical Fancoil ALL

Job Number: E21UYZ Page Prepared Date: 12/21/2018 Job Name: Spalding Hall 2nd Floor

Renovation 33 of 37 www.DaikinApplied.com

Specificati on for DST Verti cal Fancoil A LL

PART 1: GENERAL

1.01 SECTION INCLUDES

A. Horizontal Fan Coil

1.02 REFERENCES

A. Load Ratings and Fatigue Life for Ball Bearings.

B. Standards Handbook.

C. Laboratory Methods of Testing Fans for Rating Purposes.

D. Test Code for Sound Rating Air Moving Devices.

E. Test Methods for Louver, Dampers, and Shutters.

F. Room Fan Coil Unit.

G. Standard Practice for Operating Salt Spray Apparatus.

H. Motors and Generators.

I. National Electrical Code.

J. HVAC Duct Construction Standards - Metal and Flexible

K. Test for Surface Burning Characteristics of Building Materials.

L. Test Performance of Air Filter Units.

M. Standard for Heating and Cooling Equipment.

N. Test for Flammability of Plastic Materials for Parts in Devices and Appliances.

1.03 SUBMITTALS

A. Shop Drawings: Indicate assembly, unit dimensions, weight loading, required clearances, construction details, field

connection details, and electrical characteristics and connection requirements.

B. Product Data

1. Provide literature that indicates dimensions, weights, capacities, ratings, fan performance, gauges and finishes

of materials, and electrical characteristics and connection requirements.

1.04 OPERATION AND MAINTENANCE DATA

A. Maintenance Data: Include instructions for lubrication and filter replacement.

1.05 QUALIFICATIONS

A. Manufacturer: Company specializing in manufacturing Air Handler products specified in this section must show a

minimum five years documented experience and complete catalog data on total product.

1.06 DELIVERY, STORAGE, AND HANDLING

A. Deliver, store, protect and handle products to site.

B. Accept products on site wrapped in protective cardboard wrap. Inspect for damage.

C. Store in a clean dry place and protect from weather and construction traffic. Handle carefully to avoid damage.

1.07 ENVIORMENTAL REQUIREMENTS

A. Do not operate units for any purpose, temporary or permanent, until ductwork is clean, filters are in place,

bearings lubricated, and fan has been test run under observation.

PART 2: PRODUCTS

2.01 ACCEPTABLE MANUFACTURERS

A. The following manufacturers are approved for use. No substitutions.

1. Daikin Applied - 'ThinLine 3G' Fan Coil is the basis of design, including standard product features and all special

features required per plans and specifications.

Page 37: AMENDMENT NO. 1 TO THE PLANS AND SPECIFICATIONS FOR … No... · AMENDMENT NO. 1 Project No.: UHM 1168-004-17 IFB NO.UHM116800417 Page 2 of 55 D. REQUEST FOR INFORMATION / CLARIFICATION

Specification for DST Vertical Fancoil ALL

Job Number: E21UYZ Page Prepared Date: 12/21/2018 Job Name: Spalding Hall 2nd Floor

Renovation 34 of 37 www.DaikinApplied.com

2. ETI

3. Greenheck

2.02 FAN COIL TYPE AND ARRANGEMENT

A. The fan coil shall be furnished as a draw-through cooling coil with a heating coil in preheat/reheat position.

2.03 GENERAL CONSTRUCTION

A. The units shall include a chassis, coil(s), fan deck with blower(s)/blower housing and motor(s). Steel parts exposed

to moisture shall be galvanized and insulated to prevent condensation. The complete fan assembly shall be easily

removable for service and maintenance. A quick-connect motor electric plug shall be provided.

B. Hideaway

1. Unit shall be supplied with return plenum complete with filter frame and filter. The plenum shall be fabricated

of 18 gauge galvanized steel. The inside plenum surface shall be insulated with 1/2" matt-faced fibergalss

insulation. Plenum insulation shall meet minimum K value of 0.24 (BTU-in)/(hr-ft2-F) and rated for maximum air

velocity of 5000 fpm. Fiberglass insulation conforms to:

a. a. ASTM C1071 (including C665)

b. b. UL 181 for erosion

c. c. 25/50 rating for flame spread/smoke developed per ASTM E-84, UL 723 and NFPA 90A

2.04 SUPPLY FAN

A. Supply fans shall be a DWDI forward-curved type. Fan assemblies including fan, motor and sheaves shall be

dynamically balanced by the manufacturer on all three planes at all bearing supports. Manufacturer must ensure

maximum fan RPM is below the first critical speed.

B. The complete fan assembly, including motor and main drain pan shall be easily removable.

C. Units shall be certified in accordance with the Room Fan Coil Unit certification program that is based on ARI

Standard 440.

D. An ECM blower motor shall be provided on all units. Factory motor wiring shall be set for optimum fan

performance. The unit shall be shipped at one fixed setting. The ECM motor shall utilize a permanent magnet rotor,

which is connected to the shaft through resilient rings to absorb high frequency torque ripple. ECM motor shall be

programmed for constant CFM or constant torque.

E. ECM blower motor shall be 3 speeds, single phase with means for proportional field adjustment of each speed.

2.05 ELECTRICAL

A. Supply fans shall be driven by permanent split-capacitor motors that are run-tested in the assembled unit and

permanently lubricated. All motors shall have integral thermal overload protection with a maximum ambient

operating temperature of 104°F. Motors shall be capable of starting at 78 percent of rated voltage and operating at

90 percent of rated voltage on all speed settings. Motors can operate up to 10 percent overvoltage.

B. Motor wires shall include a quick-disconnect motor plug.

2.06 COOLING AND HEATING

A. Cooling Coils

1. Cooling performance shall be as specified on the unit schedule.

2. Water coil fins shall have full drawn collars to provide a continuous surface cover over the entire tube for

maximum heat transfer. Seamless copper tubes shall be mechanically expanded into the fins to provide a

continuous primary-to-secondary compression bond over the entire finned length for maximum heat transfer

rates. Bare copper tubes shall not be visible between fins. Coil casing shall be constructed of galvanized steel.

3. Water coils shall be provided with headers of seamless copper tubing with intruded tube holes to permit

expansion and contraction without creating undue stress or strain. Coil connections shall be copper sweat

connections with connection size to be determined by manufacturer based upon the most efficient coil circuiting.

Page 38: AMENDMENT NO. 1 TO THE PLANS AND SPECIFICATIONS FOR … No... · AMENDMENT NO. 1 Project No.: UHM 1168-004-17 IFB NO.UHM116800417 Page 2 of 55 D. REQUEST FOR INFORMATION / CLARIFICATION

Specification for DST Vertical Fancoil ALL

Job Number: E21UYZ Page Prepared Date: 12/21/2018 Job Name: Spalding Hall 2nd Floor

Renovation 35 of 37 www.DaikinApplied.com

Vent and drain connections shall be furnished on the coil connection, external to the cabinet. Vent connections

provided at the highest point to assure proper venting. Drain connections shall be provided at the lowest point.

4. All steel parts exposed to moisture shall be galvanized.

5. Unit shall include a noncorrosive, ABS main drain pan, positively sloped in every plane and insulated with

closed-cell insulation. The drain pan shall be designed to ensure no pooling of condensate water per ASHRAE 62.2.

2.07 VALVE PACKAGES

A. Fan coil units shall be provided with factory-installed valve / piping package(s)available for the primary and

secondary coils. All piping packages shall be factory assembled and tested at 400 psig (2760 kPa) and re-tested for

leak when factory soldered to the coil(s) at 300 psig (2069 kPa) Maximum Working Pressure of the piping package

shall be 300 psig (2069 kPa).

B. The valve package shall be designed so that any condensation is directed into the secondary drain pan. With the

secondary drain pan provided, insulation of the piping package is not required.

C. The valve package shall be provided with:

1. Interconnecting copper piping and shut-off ball valves.

2. Connecting supply and return lines to the unit. Four-pipe packages shall include a venting valve for the preheat

or reheat coil.

3. A manual circuit setter in the supply water pipe. The circuit setter acts as both a flow-setting device and a shut-

off valve. It allows water flow through the fan coil to be set quickly and accurately. The valve shall have a memory

stop so that the correct setting can be found quickly.

4. An automatic circuit setter. The circuit setter includes a cartridge within the valve body that is sized to allow a

specific flow rate through the coil. This valve sets flow through the coil without any action required by a system

piping balancer.

5. P/T ports to measure the temperature or pressure drop across the valve. This pressure drop can be compared

to factory-supplied curves that relate the pressure drop to a specific flow rate.

6. Unions at the coil connections.

7. A 20 mesh strainer on the supply side that is easily removed for cleaning, with a blow-off valve. The strainer

shall have a pressure rating of up to 400 psig (2,758 kPa).

8. Isolating ball valve on the supply side.

9. Balancing flow valve ( auto-fixed or manual) with isolating ball valve on the return.

10. Control valves in the supply water pipe.

11. Two-Way/Two-Position Valves that are fully open or fully closed in response to a line voltage (115 or 265-277

VAC) or a 24 VAC signal from the Daikin Applied thermostat or controller. Some means of relieving pump head

pressure should be accounted for when two-way valves are selected. Normally open or normally closed valves are

available. Both are spring-return.

12. Three-Way, Two-Position Valves that either allow full water flow through the coil or divert the flow through a

bypass line. The valves respond to a line voltage (115 or 265-277 VAC) or to a 24 VAC signal from the Daikin

Applied thermostat or controller. All standard three-way valves come with a fixed-balance orifice in the bypass line

to compensate for flow balancing in the bypass position, eliminating the need for an additional balancing valve.

Normally open or normally closed valves are available.

13. Two-Way Modulating Valves that modulate the water flow through the coil in response to a signal from the

Daikin Applied thermostat or controller. All standard Daikin Applied modulating valves are three-wire floating

point equal percentage valves. The modulating valves are factory mounted in the supply water pipe upstream of

the coil.

14. Three-Way Modulating Valves that modulate the water flow through the coil in response to a signal from the

Daikin Applied thermostat or controller. Three-way valves allow water that is directed through the coil to mix with

water that is directed through the bypass line. This mixture exits through the leaving water pipe. All modulating

valves are three-wire, floating-point equal percentage valves.

Page 39: AMENDMENT NO. 1 TO THE PLANS AND SPECIFICATIONS FOR … No... · AMENDMENT NO. 1 Project No.: UHM 1168-004-17 IFB NO.UHM116800417 Page 2 of 55 D. REQUEST FOR INFORMATION / CLARIFICATION

Specification for DST Vertical Fancoil ALL

Job Number: E21UYZ Page Prepared Date: 12/21/2018 Job Name: Spalding Hall 2nd Floor

Renovation 36 of 37 www.DaikinApplied.com

2.08 FILTERS

A. Filters shall be 1” (25 mm) throwaway. They shall be concealed from sight and easily removable.

2.09 CONTROLS

A. Unit shall be supplied with a DDC interface board.

B. DDC Interface board shall have three 24-volt relays with line-voltage contactors to operate the fan motor speeds.

C. DDC interface board shall have terminal connections for interfacing to:

1. Wall-Mounted Thermostat

2. Low-voltage, on-off valve actuators.

3. A return air sensor.

4. A pipe temperature sensor for changeover from heating to cooling on two-pipe systems.

5. Condensate overflow switch.

6. Room occupancy sensor.

PART 3: EXECUTION

3.01 INSTALLATION

A. The Thinline Fan Coil unit shall be installed per manufacturer's Installation & Maintenance Bulletin.

1. Selected field mounted kits shall be specified on the unit schedule and installed per manufacturer's instruction.

Page 40: AMENDMENT NO. 1 TO THE PLANS AND SPECIFICATIONS FOR … No... · AMENDMENT NO. 1 Project No.: UHM 1168-004-17 IFB NO.UHM116800417 Page 2 of 55 D. REQUEST FOR INFORMATION / CLARIFICATION

Document Summary Page

Page 41: AMENDMENT NO. 1 TO THE PLANS AND SPECIFICATIONS FOR … No... · AMENDMENT NO. 1 Project No.: UHM 1168-004-17 IFB NO.UHM116800417 Page 2 of 55 D. REQUEST FOR INFORMATION / CLARIFICATION
Page 42: AMENDMENT NO. 1 TO THE PLANS AND SPECIFICATIONS FOR … No... · AMENDMENT NO. 1 Project No.: UHM 1168-004-17 IFB NO.UHM116800417 Page 2 of 55 D. REQUEST FOR INFORMATION / CLARIFICATION

Fan Coils ScheduleLine

#

Tag Family Cab Size CFM ESP Motor Type HP Spec TotalFLA

C-Rws

Cool-EDB

Cool-EWB

Cool-Fluid

Cool-Temp

TotalBTU

SensibleBTU

Cool-LDB

Cool-LWB

Cool-LWT

Cool-GPM

Cool-Water

PD

KW H-Rws

Heat-EDB

Heat-Fluid

Heat-Temp

Total BTU Heat-LDB

Heat-LWT

Heat-GPM

Heat-Water

PD

1 FCU-1,4

Horizontal LH-R 006 475 0.20 ECM -Constant

Volume withUser Input

Speed Splits

1/3 120/1/60 5.0 6 80.00 67.00 Water 45.00 23,977 15,620 49.9 49.9 55.0 4.8 5.6 None 0 0.0 None 0.0 na na na na na

2 FCU-2 Horizontal LH-R 008 800 0.20 ECM -Constant

Volume withUser Input

Speed Splits

1/2 120/1/60 7.7 6 80.00 67.00 Water 45.00 33,893 23,556 53.1 53.1 55.0 6.8 2.0 None 0 0.0 None 0.0 na na na na na

3 FCU-3 Horizontal LH-R 004 300 0.20 ECM -Constant

Volume withUser Input

Speed Splits

1/3 120/1/60 5.0 6 80.00 67.00 Water 45.00 15,630 10,079 49.3 49.3 55.0 3.1 6.3 None 0 0.0 None 0.0 na na na na na

4 FCU-5,6

Horizontal LH-R 003 225 0.20 ECM -Constant

Volume withUser Input

Speed Splits

1/3 120/1/60 5.0 6 80.00 67.00 Water 45.00 9,987 6,813 52.3 52.3 55.0 2.0 0.9 None 0 0.0 None 0.0 na na na na na

Company: normanwrightwaipahu Project Name: Spalding Hall 2nd floor renovations ,Honolulu ,Hawaii

Proposal: 84571 Date: 12-21-2018

Information contained herein are not express warranties nor do they constitute an agreement between the parties. Williams ® may change the design and product specifications at anytime. Contact the factory for current information. AHU OM-January 2012: Certified inaccordance with the AHRI Central Station Air-Handling Unit Certification Program, which is based on the AHRI standard430. Certified units may be found in the AHRI Directory at www.ahridirectory.org. Rating version number: 2.01

Page 1 of 16

Page 43: AMENDMENT NO. 1 TO THE PLANS AND SPECIFICATIONS FOR … No... · AMENDMENT NO. 1 Project No.: UHM 1168-004-17 IFB NO.UHM116800417 Page 2 of 55 D. REQUEST FOR INFORMATION / CLARIFICATION

Fan Coils ScheduleSupplemental DataLine

#

Tag UOM MotCnt

BHP MinHP

RPM FLA MCA MOP MotorSpeed

MotorWatts

Velo-city

Altitude FinsPer In

TotalMCA

TotalMOP

C-CKT

EDP Cool-Delta T

Cool-%

Glycol

Refrig-erant

SST H-CKT

Heat-Delta T

Heat-%

Glycol

Heat-Flow

Heat-Conden-

sate

Elec.HeatBTU

Elec.HeatFLA

Elec.HeatMCA

Elec.HeatMOP

ShpngWt

OprWt

UserAppvl

1 FCU-1, 4 Standard 1 0.0 na 0.0 5.0 6.25 15.0 High Speed 600 284 0.0 12 6.25 15.0 3 60.4 10.0 0 None 0.0 0 0.0 0 na na na 0.0 0.0 15.0 186 154 LowLeaving

AirTemperature

Approved

2 FCU-2 Standard 1 0.0 na 0.0 7.7 9.625 15.0 High Speed 924 411 0.0 12 9.625 15.0 6 60.4 10.0 0 None 0.0 0 0.0 0 na na na 0.0 0.0 15.0 206 170 LowLeaving

AirTemperature

Approved

3 FCU-3 Standard 1 0.0 na 0.0 5.0 6.25 15.0 High Speed 600 240 0.0 12 6.25 15.0 2 60.4 10.0 0 None 0.0 0 0.0 0 na na na 0.0 0.0 15.0 167 133 LowLeaving

AirTemperature

Approved

4 FCU-5, 6 Standard 1 0.0 na 0.0 5.0 6.25 15.0 High Speed 600 240 0.0 12 6.25 15.0 3 60.4 10.0 0 None 0.0 0 0.0 0 na na na 0.0 0.0 15.0 140 105 LowLeaving

AirTemperature

Approved

Company: normanwrightwaipahu Project Name: Spalding Hall 2nd floor renovations ,Honolulu ,Hawaii

Proposal: 84571 Date: 12-21-2018

Information contained herein are not express warranties nor do they constitute an agreement between the parties. Williams ® may change the design and product specifications at anytime. Contact the factory for current information. AHU OM-January 2012: Certified inaccordance with the AHRI Central Station Air-Handling Unit Certification Program, which is based on the AHRI standard430. Certified units may be found in the AHRI Directory at www.ahridirectory.org. Rating version number: 2.01

Page 2 of 16

Page 44: AMENDMENT NO. 1 TO THE PLANS AND SPECIFICATIONS FOR … No... · AMENDMENT NO. 1 Project No.: UHM 1168-004-17 IFB NO.UHM116800417 Page 2 of 55 D. REQUEST FOR INFORMATION / CLARIFICATION

Performance Summary - Unit 1 , FCU-1, 4

84571-1 Horizontal Ceiling Concealed with Plenum (LH-R) - 006, 120/1/60, 6/0 Coil, RightHand, 6R3C Cool (LH-R006W2R601R000) The Horizontal with Return-Air Plenum fan coil is ideal for mounting above ceilings inclosets hallways and bathroom areas. The plenum conceals the unit's blower motor which iseasily accessible for service by removing the bottom panel.

Performance Calculations are at an altitude of 0.0 feet Unit Application User Approvals: Low Leaving Air Temperature Approved

Fan Performance

Motor Voltage:

120/1/60

Motor Type:

ECM - Constant Volume with User InputSpeed Splits

External Static:

0.20 InWC

Airflow at High Speed: 475 cfm

Cooling Coil Performance - 6 rows, 3 circuit, 12 fins/inch Entering Dry Bulb:Entering Wet Bulb:Fluid Type:

80.00 oF67.00 oFWater

Leaving Dry Bulb:Leaving Wet Bulb:Flow Rate:

49.9 oF49.9 oF4.8 GPM

Entering Fluid Temp:EAT Dew Point:

45.00 oF60.4 oF

Leaving Fluid Temp:Fluid Pressure Drop:

55.0 oF5.6 FtWC

Total Cooling Capacity:

23,977 BTUH

Sensible Cooling Capacity:

15,620 BTUH

Company: normanwrightwaipahu Project Name: Spalding Hall 2nd floor renovations ,Honolulu ,Hawaii

Proposal: 84571 Date: 12-21-2018

Information contained herein are not express warranties nor do they constitute an agreement between the parties. Williams ® may change the design and product specifications at anytime. Contact the factoryfor current information. AHU OM-January 2012: Certified in accordance with the AHRI Central Station Air-Handling Unit Certification Program, which is based on the AHRI standard430. Certified units may befound in the AHRI Directory at www.ahridirectory.org. Rating version number: 2.01

Page 3 of 16

Page 45: AMENDMENT NO. 1 TO THE PLANS AND SPECIFICATIONS FOR … No... · AMENDMENT NO. 1 Project No.: UHM 1168-004-17 IFB NO.UHM116800417 Page 2 of 55 D. REQUEST FOR INFORMATION / CLARIFICATION

Base Unit Summary - Unit 1 , FCU-1, 484571-1 Horizontal Ceiling Concealed with Plenum (LH-R) - 006, 120/1/60, 6/0 Coil, Right Hand, 6R3C Cool (LH-R006W2R601R000)

The Horizontal with Return-Air Plenum fan coil is ideal for mounting above ceilings inclosets hallways and bathroom areas. The plenum conceals the unit's blower motor which iseasily accessible for service by removing the bottom panel.

Unit Application - Fan CoilCabinet Style (Model) - Horizontal Ceiling Concealed with Plenum(LH-R) Unit Size - 006 Sales Program - Standard System Type - Cool Only System Configuration - 2-pipe Hydronic Motor Type - ECM - Constant Volume with User Input Speed Splits Motor Voltage/Freq/Phase - 120/1/60 Motor Count - 1

Supply - Front Ducted Return - Rear Ducted Wall Type - Single Wall Insulation - 1/2" Fiberglass Finish - GalvanizedMotor Watts - 600

Filter Type - Pleated - 2 inch - MERV 8 Rated Hand - Right Electrical Hand - LeftCooling Rows Deep - 6 Cooling Circuiting - 3 Cooling Air Vent - Manual Fins Per Inch - 12 Fin/Casing Material - Aluminum/Galvanized

Drain Pan - Stainless Shipping Weight - 186 lbsOperating Weight - 154 lbs

Cooling Coil Connection Size: 1/2 Heating Coil Connection Size: na

Unit Revision Level - B

Filter Access - Bottom Circuit Wiring - Single Power Source

Company: normanwrightwaipahu Project Name: Spalding Hall 2nd floor renovations ,Honolulu ,Hawaii

Proposal: 84571 Date: 12-21-2018

Information contained herein are not express warranties nor do they constitute an agreement between the parties. Williams ® may change the design and product specifications at anytime. Contact the factoryfor current information. AHU OM-January 2012: Certified in accordance with the AHRI Central Station Air-Handling Unit Certification Program, which is based on the AHRI standard430. Certified units may befound in the AHRI Directory at www.ahridirectory.org. Rating version number: 2.01

Page 4 of 16

Page 46: AMENDMENT NO. 1 TO THE PLANS AND SPECIFICATIONS FOR … No... · AMENDMENT NO. 1 Project No.: UHM 1168-004-17 IFB NO.UHM116800417 Page 2 of 55 D. REQUEST FOR INFORMATION / CLARIFICATION

Standard Drawing - Unit 1 , FCU-1, 4 84571-1 Horizontal Ceiling Concealed with Plenum (LH-R) - 006, 120/1/60, 6/0 Coil, Right Hand, 6R3C Cool (LH-R006W2R601R000)

Company: normanwrightwaipahu Project Name: Spalding Hall 2nd floor renovations ,Honolulu ,Hawaii

Proposal: 84571 Date: 12-21-2018

Information contained herein are not express warranties nor do they constitute an agreement between the parties. Williams ® may change the design and product specifications at anytime. Contact the factoryfor current information. AHU OM-January 2012: Certified in accordance with the AHRI Central Station Air-Handling Unit Certification Program, which is based on the AHRI standard430. Certified units may befound in the AHRI Directory at www.ahridirectory.org. Rating version number: 2.01

Page 5 of 16

kgogue
Line
Page 47: AMENDMENT NO. 1 TO THE PLANS AND SPECIFICATIONS FOR … No... · AMENDMENT NO. 1 Project No.: UHM 1168-004-17 IFB NO.UHM116800417 Page 2 of 55 D. REQUEST FOR INFORMATION / CLARIFICATION

Performance Summary - Unit 2 , FCU-2

84571-2 Horizontal Ceiling Concealed with Plenum (LH-R) - 008, 120/1/60, 6/0 Coil, RightHand, 6R6C Cool (LH-R008W2R601R000) The Horizontal with Return-Air Plenum fan coil is ideal for mounting above ceilings inclosets hallways and bathroom areas. The plenum conceals the unit's blower motor which iseasily accessible for service by removing the bottom panel.

Performance Calculations are at an altitude of 0.0 feet Unit Application User Approvals: Low Leaving Air Temperature Approved

Fan Performance

Motor Voltage:

120/1/60

Motor Type:

ECM - Constant Volume with User InputSpeed Splits

External Static:

0.20 InWC

Airflow at High Speed: 800 cfm

Cooling Coil Performance - 6 rows, 6 circuit, 12 fins/inch Entering Dry Bulb:Entering Wet Bulb:Fluid Type:

80.00 oF67.00 oFWater

Leaving Dry Bulb:Leaving Wet Bulb:Flow Rate:

53.1 oF53.1 oF6.8 GPM

Entering Fluid Temp:EAT Dew Point:

45.00 oF60.4 oF

Leaving Fluid Temp:Fluid Pressure Drop:

55.0 oF2.0 FtWC

Total Cooling Capacity:

33,893 BTUH

Sensible Cooling Capacity:

23,556 BTUH

Company: normanwrightwaipahu Project Name: Spalding Hall 2nd floor renovations ,Honolulu ,Hawaii

Proposal: 84571 Date: 12-21-2018

Information contained herein are not express warranties nor do they constitute an agreement between the parties. Williams ® may change the design and product specifications at anytime. Contact the factoryfor current information. AHU OM-January 2012: Certified in accordance with the AHRI Central Station Air-Handling Unit Certification Program, which is based on the AHRI standard430. Certified units may befound in the AHRI Directory at www.ahridirectory.org. Rating version number: 2.01

Page 6 of 16

Page 48: AMENDMENT NO. 1 TO THE PLANS AND SPECIFICATIONS FOR … No... · AMENDMENT NO. 1 Project No.: UHM 1168-004-17 IFB NO.UHM116800417 Page 2 of 55 D. REQUEST FOR INFORMATION / CLARIFICATION

Base Unit Summary - Unit 2 , FCU-284571-2 Horizontal Ceiling Concealed with Plenum (LH-R) - 008, 120/1/60, 6/0 Coil, Right Hand, 6R6C Cool (LH-R008W2R601R000)

The Horizontal with Return-Air Plenum fan coil is ideal for mounting above ceilings inclosets hallways and bathroom areas. The plenum conceals the unit's blower motor which iseasily accessible for service by removing the bottom panel.

Unit Application - Fan CoilCabinet Style (Model) - Horizontal Ceiling Concealed with Plenum(LH-R) Unit Size - 008 Sales Program - Standard System Type - Cool Only System Configuration - 2-pipe Hydronic Motor Type - ECM - Constant Volume with User Input Speed Splits Motor Voltage/Freq/Phase - 120/1/60 Motor Count - 1

Supply - Front Ducted Return - Rear Ducted Wall Type - Single Wall Insulation - 1/2" Fiberglass Finish - GalvanizedMotor Watts - 924

Filter Type - Pleated - 2 inch - MERV 8 Rated Hand - Right Electrical Hand - LeftCooling Rows Deep - 6 Cooling Circuiting - 6 Cooling Air Vent - Manual Fins Per Inch - 12 Fin/Casing Material - Aluminum/Galvanized

Drain Pan - Stainless Shipping Weight - 206 lbsOperating Weight - 170 lbs

Cooling Coil Connection Size: 1/2 Heating Coil Connection Size: na

Unit Revision Level - B

Filter Access - Bottom Circuit Wiring - Single Power Source

Company: normanwrightwaipahu Project Name: Spalding Hall 2nd floor renovations ,Honolulu ,Hawaii

Proposal: 84571 Date: 12-21-2018

Information contained herein are not express warranties nor do they constitute an agreement between the parties. Williams ® may change the design and product specifications at anytime. Contact the factoryfor current information. AHU OM-January 2012: Certified in accordance with the AHRI Central Station Air-Handling Unit Certification Program, which is based on the AHRI standard430. Certified units may befound in the AHRI Directory at www.ahridirectory.org. Rating version number: 2.01

Page 7 of 16

Page 49: AMENDMENT NO. 1 TO THE PLANS AND SPECIFICATIONS FOR … No... · AMENDMENT NO. 1 Project No.: UHM 1168-004-17 IFB NO.UHM116800417 Page 2 of 55 D. REQUEST FOR INFORMATION / CLARIFICATION

Standard Drawing - Unit 2 , FCU-2 84571-2 Horizontal Ceiling Concealed with Plenum (LH-R) - 008, 120/1/60, 6/0 Coil, Right Hand, 6R6C Cool (LH-R008W2R601R000)

Company: normanwrightwaipahu Project Name: Spalding Hall 2nd floor renovations ,Honolulu ,Hawaii

Proposal: 84571 Date: 12-21-2018

Information contained herein are not express warranties nor do they constitute an agreement between the parties. Williams ® may change the design and product specifications at anytime. Contact the factoryfor current information. AHU OM-January 2012: Certified in accordance with the AHRI Central Station Air-Handling Unit Certification Program, which is based on the AHRI standard430. Certified units may befound in the AHRI Directory at www.ahridirectory.org. Rating version number: 2.01

Page 8 of 16

kgogue
Line
Page 50: AMENDMENT NO. 1 TO THE PLANS AND SPECIFICATIONS FOR … No... · AMENDMENT NO. 1 Project No.: UHM 1168-004-17 IFB NO.UHM116800417 Page 2 of 55 D. REQUEST FOR INFORMATION / CLARIFICATION

Performance Summary - Unit 3 , FCU-3

84571-3 Horizontal Ceiling Concealed with Plenum (LH-R) - 004, 120/1/60, 6/0 Coil, RightHand, 6R2C Cool (LH-R004W2R601R000) The Horizontal with Return-Air Plenum fan coil is ideal for mounting above ceilings inclosets hallways and bathroom areas. The plenum conceals the unit's blower motor which iseasily accessible for service by removing the bottom panel.

Performance Calculations are at an altitude of 0.0 feet Unit Application User Approvals: Low Leaving Air Temperature Approved

Fan Performance

Motor Voltage:

120/1/60

Motor Type:

ECM - Constant Volume with User InputSpeed Splits

External Static:

0.20 InWC

Airflow at High Speed: 300 cfm

Cooling Coil Performance - 6 rows, 2 circuit, 12 fins/inch Entering Dry Bulb:Entering Wet Bulb:Fluid Type:

80.00 oF67.00 oFWater

Leaving Dry Bulb:Leaving Wet Bulb:Flow Rate:

49.3 oF49.3 oF3.1 GPM

Entering Fluid Temp:EAT Dew Point:

45.00 oF60.4 oF

Leaving Fluid Temp:Fluid Pressure Drop:

55.0 oF6.3 FtWC

Total Cooling Capacity:

15,630 BTUH

Sensible Cooling Capacity:

10,079 BTUH

Company: normanwrightwaipahu Project Name: Spalding Hall 2nd floor renovations ,Honolulu ,Hawaii

Proposal: 84571 Date: 12-21-2018

Information contained herein are not express warranties nor do they constitute an agreement between the parties. Williams ® may change the design and product specifications at anytime. Contact the factoryfor current information. AHU OM-January 2012: Certified in accordance with the AHRI Central Station Air-Handling Unit Certification Program, which is based on the AHRI standard430. Certified units may befound in the AHRI Directory at www.ahridirectory.org. Rating version number: 2.01

Page 9 of 16

Page 51: AMENDMENT NO. 1 TO THE PLANS AND SPECIFICATIONS FOR … No... · AMENDMENT NO. 1 Project No.: UHM 1168-004-17 IFB NO.UHM116800417 Page 2 of 55 D. REQUEST FOR INFORMATION / CLARIFICATION

Base Unit Summary - Unit 3 , FCU-384571-3 Horizontal Ceiling Concealed with Plenum (LH-R) - 004, 120/1/60, 6/0 Coil, Right Hand, 6R2C Cool (LH-R004W2R601R000)

The Horizontal with Return-Air Plenum fan coil is ideal for mounting above ceilings inclosets hallways and bathroom areas. The plenum conceals the unit's blower motor which iseasily accessible for service by removing the bottom panel.

Unit Application - Fan CoilCabinet Style (Model) - Horizontal Ceiling Concealed with Plenum(LH-R) Unit Size - 004 Sales Program - Standard System Type - Cool Only System Configuration - 2-pipe Hydronic Motor Type - ECM - Constant Volume with User Input Speed Splits Motor Voltage/Freq/Phase - 120/1/60 Motor Count - 1

Supply - Front Ducted Return - Rear Ducted Wall Type - Single Wall Insulation - 1/2" Fiberglass Finish - GalvanizedMotor Watts - 600

Filter Type - Pleated - 2 inch - MERV 8 Rated Hand - Right Electrical Hand - LeftCooling Rows Deep - 6 Cooling Circuiting - 2 Cooling Air Vent - Manual Fins Per Inch - 12 Fin/Casing Material - Aluminum/Galvanized

Drain Pan - Stainless Shipping Weight - 167 lbsOperating Weight - 133 lbs

Cooling Coil Connection Size: 1/2 Heating Coil Connection Size: na

Unit Revision Level - B

Filter Access - Bottom Circuit Wiring - Single Power Source

Company: normanwrightwaipahu Project Name: Spalding Hall 2nd floor renovations ,Honolulu ,Hawaii

Proposal: 84571 Date: 12-21-2018

Information contained herein are not express warranties nor do they constitute an agreement between the parties. Williams ® may change the design and product specifications at anytime. Contact the factoryfor current information. AHU OM-January 2012: Certified in accordance with the AHRI Central Station Air-Handling Unit Certification Program, which is based on the AHRI standard430. Certified units may befound in the AHRI Directory at www.ahridirectory.org. Rating version number: 2.01

Page 10 of 16

Page 52: AMENDMENT NO. 1 TO THE PLANS AND SPECIFICATIONS FOR … No... · AMENDMENT NO. 1 Project No.: UHM 1168-004-17 IFB NO.UHM116800417 Page 2 of 55 D. REQUEST FOR INFORMATION / CLARIFICATION

Standard Drawing - Unit 3 , FCU-3 84571-3 Horizontal Ceiling Concealed with Plenum (LH-R) - 004, 120/1/60, 6/0 Coil, Right Hand, 6R2C Cool (LH-R004W2R601R000)

Company: normanwrightwaipahu Project Name: Spalding Hall 2nd floor renovations ,Honolulu ,Hawaii

Proposal: 84571 Date: 12-21-2018

Information contained herein are not express warranties nor do they constitute an agreement between the parties. Williams ® may change the design and product specifications at anytime. Contact the factoryfor current information. AHU OM-January 2012: Certified in accordance with the AHRI Central Station Air-Handling Unit Certification Program, which is based on the AHRI standard430. Certified units may befound in the AHRI Directory at www.ahridirectory.org. Rating version number: 2.01

Page 11 of 16

kgogue
Line
Page 53: AMENDMENT NO. 1 TO THE PLANS AND SPECIFICATIONS FOR … No... · AMENDMENT NO. 1 Project No.: UHM 1168-004-17 IFB NO.UHM116800417 Page 2 of 55 D. REQUEST FOR INFORMATION / CLARIFICATION

Performance Summary - Unit 4 , FCU-5, 6

84571-5 Horizontal Ceiling Concealed with Plenum (LH-R) - 006, 120/1/60, 6/0 Coil, RightHand, 6R3C Cool (LH-R006W2R601R000) The Horizontal with Return-Air Plenum fan coil is ideal for mounting above ceilings inclosets hallways and bathroom areas. The plenum conceals the unit's blower motor which iseasily accessible for service by removing the bottom panel.

Performance Calculations are at an altitude of 0.0 feet Unit Application User Approvals: Low Leaving Air Temperature Approved

Fan Performance

Motor Voltage:

120/1/60

Motor Type:

ECM - Constant Volume with User InputSpeed Splits

External Static:

0.20 InWC

Airflow at High Speed: 225 cfm

Cooling Coil Performance - 6 rows, 3 circuit, 12 fins/inch Entering Dry Bulb:Entering Wet Bulb:Fluid Type:

80.00 oF67.00 oFWater

Leaving Dry Bulb:Leaving Wet Bulb:Flow Rate:

52.3 oF52.3 oF2.0 GPM

Entering Fluid Temp:EAT Dew Point:

45.00 oF60.4 oF

Leaving Fluid Temp:Fluid Pressure Drop:

55.0 oF0.9 FtWC

Total Cooling Capacity:

9,987 BTUH

Sensible Cooling Capacity:

6,813 BTUH

Company: normanwrightwaipahu Project Name: Spalding Hall 2nd floor renovations ,Honolulu ,Hawaii

Proposal: 84571 Date: 12-21-2018

Information contained herein are not express warranties nor do they constitute an agreement between the parties. Williams ® may change the design and product specifications at anytime. Contact the factoryfor current information. AHU OM-January 2012: Certified in accordance with the AHRI Central Station Air-Handling Unit Certification Program, which is based on the AHRI standard430. Certified units may befound in the AHRI Directory at www.ahridirectory.org. Rating version number: 2.01

Page 12 of 16

Page 54: AMENDMENT NO. 1 TO THE PLANS AND SPECIFICATIONS FOR … No... · AMENDMENT NO. 1 Project No.: UHM 1168-004-17 IFB NO.UHM116800417 Page 2 of 55 D. REQUEST FOR INFORMATION / CLARIFICATION

Base Unit Summary - Unit 4 , FCU-5, 684571-5 Horizontal Ceiling Concealed with Plenum (LH-R) - 006, 120/1/60, 6/0 Coil, Right Hand, 6R3C Cool (LH-R006W2R601R000)

The Horizontal with Return-Air Plenum fan coil is ideal for mounting above ceilings inclosets hallways and bathroom areas. The plenum conceals the unit's blower motor which iseasily accessible for service by removing the bottom panel.

Unit Application - Fan CoilCabinet Style (Model) - Horizontal Ceiling Concealed with Plenum(LH-R) Unit Size - 003 Sales Program - Standard System Type - Cool Only System Configuration - 2-pipe Hydronic Motor Type - ECM - Constant Volume with User Input Speed Splits Motor Voltage/Freq/Phase - 120/1/60 Motor Count - 1

Supply - Front Ducted Return - Rear Ducted Wall Type - Single Wall Insulation - 1/2" Fiberglass Finish - GalvanizedMotor Watts - 600

Filter Type - Pleated - 2 inch - MERV 8 Rated Hand - Right Electrical Hand - LeftCooling Rows Deep - 6 Cooling Circuiting - 3 Cooling Air Vent - Manual Fins Per Inch - 12 Fin/Casing Material - Aluminum/Galvanized

Drain Pan - Stainless Shipping Weight - 140 lbsOperating Weight - 105 lbs

Cooling Coil Connection Size: 1/2 Heating Coil Connection Size: na

Unit Revision Level - B

Filter Access - Bottom Circuit Wiring - Single Power Source

Company: normanwrightwaipahu Project Name: Spalding Hall 2nd floor renovations ,Honolulu ,Hawaii

Proposal: 84571 Date: 12-21-2018

Information contained herein are not express warranties nor do they constitute an agreement between the parties. Williams ® may change the design and product specifications at anytime. Contact the factoryfor current information. AHU OM-January 2012: Certified in accordance with the AHRI Central Station Air-Handling Unit Certification Program, which is based on the AHRI standard430. Certified units may befound in the AHRI Directory at www.ahridirectory.org. Rating version number: 2.01

Page 13 of 16

Page 55: AMENDMENT NO. 1 TO THE PLANS AND SPECIFICATIONS FOR … No... · AMENDMENT NO. 1 Project No.: UHM 1168-004-17 IFB NO.UHM116800417 Page 2 of 55 D. REQUEST FOR INFORMATION / CLARIFICATION

Standard Drawing - Unit 4 , FCU-5, 6 84571-5 Horizontal Ceiling Concealed with Plenum (LH-R) - 006, 120/1/60, 6/0 Coil, Right Hand, 6R3C Cool (LH-R006W2R601R000)

Company: normanwrightwaipahu Project Name: Spalding Hall 2nd floor renovations ,Honolulu ,Hawaii

Proposal: 84571 Date: 12-21-2018

Information contained herein are not express warranties nor do they constitute an agreement between the parties. Williams ® may change the design and product specifications at anytime. Contact the factoryfor current information. AHU OM-January 2012: Certified in accordance with the AHRI Central Station Air-Handling Unit Certification Program, which is based on the AHRI standard430. Certified units may befound in the AHRI Directory at www.ahridirectory.org. Rating version number: 2.01

Page 14 of 16

kgogue
Line