1 Exam Prep
Air Conditioning "A", "B" and Mechanical Practice Exam 16
1 Solar systems shall be controlled so that the temperature in the supply system shall not exceed?
A 250 degrees Centigrade B 250 degrees Fahrenheit C 212 degrees Fahrenheit D 121 degrees Fahrenheit
2 The Pittsburgh lock is good to water gage.
A Plus 10 B Minus 10 C Plus or minus 8 D Plus or minus 10
3 Ducts with interior widths of inches or less do not require mechanical fasteners in addition to adhesives.
A6 B 8 C10 D 12
4 Refrigerants shall be classified according to?
A ARI 700 B ASHLRAE 34 C UL 1995 D Table 1103.1
5 According to the Florida Building Code, Plumbing, exhaust outlets that terminate above the roof, shall have the discharge opening located not less than inches above the roof surface.
A18 B 36 C 40 D 48
1
6 A 28 inch 20 gage round spiral seam duct 100 feet long weighs pounds.
A 12.9 B 129 C 1,290 D 680
7 When needing to install a 15 ton unit using R-22, at 100 feet developed length with a 3 psi drop from the receiver to the evaporator, the size Type "U copper line to use with a suction of 40F and 105 F condensing is inches.
A 7/8 B 1 C 1 1/8 D 13/8
8 Replacement air shall always be adequate to prevent pressures in commercial cooking.
A Negative B Positive C Neutral D Active
9 Dew point is?
A Condensation droplets occurring on the inside of the unit B Wet bulb as a reverse of dry bulb C The temperature at which moisture will start to condense from the air D Evaporation of the water droplets
10 The thermostat should be replaced when a calibration of more than degrees Fahrenheit is needed.
A10 B 5 C3 D 2
1 1 The hardness of the makeup water is 6. The hardness of the sump water is 10. Evaporation is .3 gallons per minute. The blowdown is?
A .3 B .12 C .2 D .45
2
12 The oil in the sight level glass should be at?
A Or slightly above the center of the sight glass B Or slightly below the center of the sight glass C The center of the sight glass D The upper top section of the sight glass
13 A large deterrent to using the earth as a heat sink is?
A Environmental concern B Cost C Location D Productivity
14 The proper wire connection for the reversing valve in a heat pump thermostat is the?
AB B G C 0 DX
15 When experiencing an unstable gas supply the contractor should use a?
A Larger regulator B Two stage regulator C Smaller regulator D High compression regulator
16 A clockwise top angular down blast discharge is identified as?
A CWTADD B CCWTAUD C CCWTADD D CWTADD
17 Archimedes Inc. sold a rope with a 4,000 pound capacity to AAA. The rope factor was 4:1. The maximum safe load AAA may lift with the rope is?
A 2 tons B 16 tons C 2,000 pounds D 1,000 pounds
3
18 An improperly located feeler bulb will result in a?
A High suction pressure B Low suction pressure C Broken fan belt D Icing situation
19 A proportional controller produces a?
A Modulated signal B Calibrated signal C Pneumatic action D Piston drive
20 For accurate readings, whirling of the psychrometer should continue until?
A The wick is dry B The clicking sounds stops C All readings are confirmed D Two sets of successive readings agree
21 Heat pump defrost controls are used to detect on the outdoor coil during the heating cycle.
A Ice and frost B Heat C Air flow D THX operation
22 All pneumatic nailers shall have a safety device on the muzzle when operated at psi or greater.
A 30 B 80 C 100 D 120
23 The TWA for R 134a is?
A 1,000 B 2,500 C 300 D 50
4
24 Which gas when combined with oil will cause an explosion?
A Nitrogen B Argon C Xenon D Oxygen
25 A central warm air system through which air is circulated by gravity is a/an system.
A Forced air B Gravity C Flow-through D Metered
26 Safety nets are required when no other means of catch platforms are used and the height is more than feet above the ground or water surface.
A6 B10 C 25 D 32
27 Sheet metal sleeves used inside ductboard for heater applications shall extend how many inches beyond each side of the heater?
Al2 B 6 C4 D 18
28 When the humidity is percent or higher there is a greater opportunity for mold growth.
A 25 45
C 60 D 80
29 When acting as a signaler, which of the following is not allowed?
A Swing the load over materials B Being aware of overhead lines C Placing a signaler on each side of the crane D Warning people to stay away
5
30 Amperage relays must be for satisfactory operation.
A Properly mounted B Electromagnetic C High voltage D Low voltage
31 Hearing protection is required where sound levels are greater than how many decibels?
A 80 B 90 C 100 D 105
32 Many large compressors are provided with controls to provide capacity.
A Controlled B Variable C Constant D Unlimited
33 The most probable cause for the suction line to be frosted or sweating in refrigeration is?
A The expansion valve is stuck open B An overcharge of refrigerant C The evaporator is overloaded D The cooling water is shutoff
34 Auxiliary drain pans shall not be less than inches larger than the unit.
A 1.5 B 3 C6 D 12
35 An 18 inch diameter connector requires a minimum nominal galvanized thickness of?
A 16 gage B .043 C 24 gage D 26 gage
36 During the winter months a desired relative humidity should be between percent.
A 30 and 50 B 40 and 60 C 50 and 70 D 60 and 80
37 The auxiliary drain pan shall have a minimum depth of inches.
A 1.5 B 3 C6 D 8
38 For exposed rectangular ducts over 14 inches the minimum galvanized sheet metal thickness is?
A 26 gage B .019 inches C .024 inches D .013 inches
39 The difference between actual cold water temperature and existing wet bulb temperature is termed?
A Approach B Range C Dew point D Condensation
40 Public toilet rooms require a minimum air flow of?
A 50 sfm's per unit B 100 sfm's C 50 cfm's per unit D 100 cfm's
QUESTION 41 IS FOR MECHANICAL. CONTRACTORS ONLY
41 The minimum square feet of opening required for a unit consuming L000,000 BTU's and using all air from outdoors is square feet.
A 250 B 1.73 C 3.47 D 6.94
7
42 The amount of friction loss within a pipe is dependent upon?
A The condition of the pipe and the velocity of the water B The type of pipe and the velocity of the water C The size of the pump and the distance of the flow D Rate of flow and the condition of the pump
43 The most probable cause for high head pressure in a heat pump is?
A An overcharge of refrigerant B High air temperature C Defective reversing valve D Shortage of refrigerant
44 A plugged capillary tube is caused by?
A Excessive airflow B Trapped foreign particles C Untrappped foreign particles D Low head pressure
45 An 18 inch by 18 inch rectangular elbow should have a centerline radius of inches.
A18 B 27 C 36 D 45
46 Inspection windows shall be permitted in air ducts provided they are?
A Glazed B Tempered C Wired glass D Glazed with wire glass
47 Liquid adhesive coating used on air filters shall have a minimum flash point of degrees Fahrenheit.
A 212 B 250 C 300 D 325
8
48 The ten-inch impeller is delivering 550 gallons per minute. Billy needs to deliver 685 gallons per minute. Billy should upgrade to a inch impeller.
A 11 12
C13 D 14
49 The excavation is to be 960 feet long. There will be 1 cubic yard per lineal foot. The contractor is able to excavate 6 cubic yards per hour. The total number of 8-hour days to complete the excavation is?
A Less than 40 B Between 40 and 80 C Between 80 and 160 D More than 160
50 Which should not be used to pressurize a system?
A Air B Nitrogen C Argon D Oxygen
51 According to Trane Reciprocating Refrigeration, which of the following should never be used as a test gas?
A Dry nitrogen B Oxygen C Krypton D Argon
52 Jesse is using a braided sling with a hook. The maximum percent from plane twist allowed from the throat is?
A 10 15
C 20 D 25
53 The type vent required for oil burning appliances is?
A Type A B Type BW C Pellet D Type L
9
54 The fan belt should be flexible for not more than?
A 1/2 inch B 3/4 inch C 1 inch D 2 inches
55 Suspended equipment must have a minimum clearance from grade of?
A 6 inches B 1 foot C 18 inches D 2 feet
56 Each scaffold must be capable of supporting at least how many times its own weight?
A4 B 3 C2 D 1
57 Fusible links shall have a temperature rating of approximately degrees Fahrenheit.
A 250 B 200 C 150 D 50
58 A Class "E" round duct angle ring has a size of?
A1.5 X1.5 X.25 B 2 X2 X.1875 C2 X2 X.25 D 1 X1 X1
59 The looping of hot gas from the compressor is usually done by a degree loop.
A 45 B 90 C 180 D 360
10
60 Within a dwelling unit, appliances installed in a compartment space shall be accessed by an opening or door and an unobstructed passageway of not less than inches.
A 24 B 30 C 32 D 36
61 Reinforcement for flat sides of oval duct shall be provided to limit wall deflection to inches.
A 1/2 B 3/4 C .25 D 3/16
62 Using R-22 with 25 tons and a 1 5/8 inch line, the gas velocity in feet per minute is?
A 4,000 B 6,000 C 1,000 D 2,000
63 Pitot tubes when used with manometers cannot be used to accurately measure air velocities of less than how many feet per minute?
A 700 B 1,000 C 1,200 D 1,500
64 The minimum clearance for a Type 1 hood to combustibles is inches.
A6 B 12 C18 D 24
65 Starting capacitors found to be out of the range of percent of the mfd rating of the capacitor must be replaced.
A Oto+ 20 B 5 to + 20 C5 to+ 25 D 10 to+ 30
11
66 Clearance from the duct to the interior surface of a limited-combustible shall be not less than how many inches?
A6 B8 C12 D 18
67 A device use to measure watts is the?
A Ammeter B Resistor C Conductor D Capacitor
68 Which is not a common cause of high discharge pressure?
A Compressor discharge service valve is front-seated B Excessive cooling air C Lack of cooling water D Non-condensable gases
69 Refrigerant 134A boils at?
A -41.1 F B -14.92F C -28 F D 82.11F
70 The equivalent length in feet is 50. R-22 is being used from the evaporator to the compressor. The suction is 35 degrees Fahrenheit and 115 degrees Fahrenheit condensing. The pressure drop is 2.0 psi. The minimum tonnage using a 7/8 inch Type "L" copper line is?
A 3.4 B 3.8 C 3.52 D 38.08
71 The terminal that is the most likely to short is the one with the?
A Red dot B Double clip C Plus sign D Minus sign
12
72 The latent heat generated by an adult male doing moderate dancing is BTU's.
A 900 B 850 C 305 D 545
73 When pressurizing a system with nitrogen, the technician should use a/an?
A Two stage regulator B Gauge-equipped regulator C Air pack D Strip and peel swab
74 Where equipment requiring access is installed on a roof at a height exceeding feet, such access shall be provided by a permanent means of access.
A6 B 10 C16 D 20
75 When using a psychrometer, the lowest reading is the?
A Wet bulb B Dry bulb C Correct reading D Useable reading
76 Once the compressor is fully unloaded, any further system load reduction causes the?
A System to overheat and shut down B Compressor suction pressure and temperature to fall accordingly C THX valve to automatically close and open D Oil pressure to decrease and the system to chug
77 Phos-copper filler metals should not be used on ferrous metals containing more than percent nickel.
A10 15
C 20 D 25
13
78 If tubing is flattened there may be condensation or frost on the side of the kink.
A Inlet B Outlet C Front D Back
79 When a flux becomes saturated with oxides its?
A Viscosity increases B Viscosity decreases C Viscosity remains constant D Saturation index is nullified
80 The amount of makeup air shall always be equal to?
A The amount of air required for the cooking operation B The amount of air required for the cooking operation plus 5 percent C The amount of air so as to not require a negative air flow D The amount of exhaust air to prevent a negative air flow
81 A 1/4 inch single hanger rod for rectangular duct should have a maximum allowable load of how many pounds?
A 80 B 120 C 160 D 270
82 Rooms containing appliances requiring access shall be provided with a door and an unobstructed passageway measuring not less than inches wide.
A 24 B 30 C 32 D 36
83 Running capacitors that are found to be out of range percent of the mfd rating must be replaced.
A Plus or minus 5 B Plus or minus 10 C Plus or minus 15 D Plus or minus 20
14
84 Given .075 friction and an air volume of 4,000 cfm's, the opposite side of a 30 inch rectangular duct would be inches?
A 15 B 16 C17 D 18
85 The suction line is from the?
A Evaporator to the compressor B Condenser to the evaporator C Compressor to the condenser D Compressor to the evaporator
86 An open winding is indicated by a resistance reading on the ohmmeter of?
A Low B High C Infinity D Normal
87 Fans shall discharge a minimum of how many inches away from any roof surface?
A18 B 36 C 40 D 42
88 The number of mitered pieces required for a mitered elbow when the velocity is less than 1,000 feet per minute is?
A 1 B 2 C3 D4
89 Each extra-heavy-duty type lA plastic ladder shall sustain at least times the maximum intended load.
A 2.5 B 3.3 C4 D 5
15
90 All screws penetrating ductboard shall be no more than inches longer than the ductboard.
A2 B 1 C.5 D .25
91 The fire damper rating required for a 2 hour fire-resistance-rated assembly is hours.
A 1 B 1.5 C2 D 3
92 All deep-fat fryers shall be installed with at least a inch space between the fryer and surface flames.
A6 B 12 C16 D 18
93 When torch brazing, the contractor should use a lens shade of?
A 14 B 11 C5 D4
94 According to the Florida Mechanical Code, the only time oxygen is allowed to be used as a test gas is?
A In the event of a medical evacuation B As directed in the NFPA C Never D When diluted with oil free dry nitrogen
95 The service technician notices the gage pressure for Refrigerant 22 is 243 degrees. The temperature should be how many degrees Fahrenheit?
A 114 B 115 C 116 D 117
16
96 Water has a specific heat of?
Al B .5 C .25 D .940
97 Do not allow liquid refrigerant to come into contact with the?
A Hoses B Skin or eyes C Regulators D Gauges
98 To stabilize the suction pressure and temperature throughout, compressors used in large systems are generally equipped with cylinder?
A Sequence monitoring B Unloading control C Timing mechanisms D Withdrawal blocks
99 When replacing a heating relay, the service technician should always use?
A Capillary tongs B An ohmmeter C An exact replacement D A replacement either the same or of higher value
100 On scaffolds where platforms are overlapped to form a long platform, the overlap shall be not less than inches.
A 24 B 18 C12 D 6
101 A burned-out defrost valve solenoid coil will prevent operation of the?
A Defrost circuit B THX valve C Solenoid coil D Hot gas bypass line
17
102 One of the nice things about a trap is?
A The filter effect on the fluid B The aid in allowing the oil to start its climb up the suction and hot gas risers C The minimum horizontal dimension required for cutting down the elbows D The accumulation of oil drained from the hot gas riser
103 Chlorotrifluoromethane is designated as refrigerant?
A R13 B R12 C R 134a DR 218
104 When joining copper-to-steel the best solder to use is?
A Hard B Soft C Silver D Lead
105 Most air conditioning systems use a superheat setting of approximately degrees Fahrenheit. A 12 to 15 B 15 to 18 C 18 to 21 D 21 to 24
106 No solid fuel cooking device of any type shall be used for deep-fat frying involving more than quart(s) of liquid shortening.
Al B2 C3 D 4
107 Minimum insertion distance should be equal to the?
A Amount of the filler metal B Diameter of the outer tube C Diameter of the inner tube D Clearance of the inner and outer walls
108 The drawing below is representative of a/an?
A Volume damper B Wye junction C Smoke damper D Standard junction
109 Discharge fan Number 2 is a/an?
A CWUBD B CCWDBD C CCWTADD D CCWUBD
19
ANSWER KEY — EXAM 16
1
2
3
B
D
B
NFPA 90B
SMACNA HVAC Duct Construction Standards, Metal/Flexible
SMACNA HVAC Duct Construction Standards, Metal/Flexible
6.1.8.1
2.10
1.6, S 2.6
4 B Florida Building Code, Mechanical, 2010 1103.1
5 C Florida Building Code, Mechanical, 2010 506.3.12.1
6 C SMACNA HVAC Duct Construction Standards, Metal/Flexible A.9
7 A Trane Reciprocating Refrigeration 91
8 A NFPA 96 8.3.1
9 C Trane Air Conditioning Manual 64
10 A Air Conditioning and Refrigeration Troubleshooting Handbook 25
11 D Trane Air Conditioning Manual 252
10 - 6 = 4 6 ÷ 4 X .3 = .45
12 A Air Conditioning and Refrigeration Troubleshooting Handbook 15
13 B Trane Air Conditioning Manual 204
14 C Air Conditioning and Refrigeration Troubleshooting Handbook 183
15 B Air Conditioning and Refrigeration Troubleshooting Handbook 114
16 D SMACNA HVAC Duct Construction Standards, Metal/Flexible A.18
17 D Contractors Manual 7-53
18 B Air Conditioning and Refrigeration Troubleshooting Handbook 49
19 A Trane Reciprocating Refrigeration 50
20 D Trane Air Conditioning Manual 62
21 A Air Conditioning and Refrigeration Troubleshooting Handbook 131
22 C OSHA 29 CFR Part 1926 .302(b)(3)
23 A Florida Building Code, Mechanical, 2010 Table 1103.1
24 D Air Conditioning and Refrigeration Troubleshooting Handbook 430
25 B NFPA 90B 5
26 C OSHA 29 CFR Part 1926 .105
27 B SMACNA Fibrous Glass Duct Construction Standards 6.7
28 C SMACNA Energy Systems Analysis and Management 9.2
29 C Contractors Manual 7-91
20
30 A Air Conditioning and Refrigeration Troubleshooting Handbook 35
31 B Air Conditioning and Refrigeration Troubleshooting Handbook 428
32 B Trane Air Conditioning Manual 142
33 A Air Conditioning and Refrigeration Troubleshooting Handbook 462
34 B Florida Building Code, Mechanical, 2010 307.2.3
35 A Florida Building Code, Mechanical, 2010 Table 803.9(1)
36 B Air Conditioning and Refrigeration Troubleshooting Handbook 104
37 A Florida Building Code, Mechanical, 2010 307.2.3
38 B NFPA 90B Table 4.1.1.1
39 A Trane Air Conditioning Manual 247
40 C Florida Building Code, Mechanical, 2010 Table 403.3
4 1 C Florida Building Code, Fuel Gas, 2010 304.6.1
1,000,000 + 4,000 = 250 + 144 X 2 = 3.47
4 2 A Trane Reciprocating Refrigeration 108
43 A Air Conditioning and Refrigeration Troubleshooting Handbook 456
44 C Air Conditioning and Refrigeration Troubleshooting Handbook 56
45 B Solar Domestic Hot Water Systems Repair/ Maintenance Manual 4.3
18 X 1.5 = 27
46 D NFPA 90A 4.3.5.4
47 D NFPA 90A 4.2.2.3
48 C SMACNA Energy Systems Analysis and Management 4.10
10 + 550 X 685 = 12.45 = 13
49 A 960+6+8=20
50 D Air Conditioning and Refrigeration Troubleshooting Handbook 432
51 B Trane Reciprocating Refrigeration 118
52 A Contractors Manual 7-87
53 D Florida Building Code, Mechanical, 2010 Table 802.2
54 C Air Conditioning and Refrigeration Troubleshooting Handbook 48
55 A Florida Building Code, Mechanical, 2010 304.10
56 A OSHA 29 CFR Part 1926 .451(a)
57 D NFPA 90A 5.4.5.2.1
58 B SMACNA HVAC Duct Construction Standards, Metal/Flexible 3.6
21
59 A Trane Reciprocating Refrigeration 77
60 A Florida Building Code, Mechanical, 2010 306.2
61 B SMACNA HVAC Duct Construction Standards, Metal/Flexible 3.27
62 A Trane Reciprocating Refrigeration 95
63 A Trane Air Conditioning Manual 258
64 C Florida Building Code, Mechanical, 2010 507.9
65 A Air Conditioning and Refrigeration Troubleshooting Handbook 32
66 A NFPA 96 7.7.2.2.2
67 A Air Conditioning and Refrigeration Troubleshooting Handbook 15
68 B Air Conditioning and Refrigeration Troubleshooting Handbook 40
69 B Trane Air Conditioning Manual 121
70 B Trane Reciprocating Refrigeration 92/93
71 A Air Conditioning and Refrigeration Troubleshooting Handbook 34
72 D Trane Air Conditioning Manual 376
73 B Air Conditioning and Refrigeration Troubleshooting Handbook 430
74 C Florida Building Code, Mechanical, 2010 306.5
75 A Trane Air Conditioning Manual 62
76 B Trane Reciprocating Refrigeration 17
77 A Air Conditioning and Refrigeration Troubleshooting Handbook 307
78 B Air Conditioning and Refrigeration Troubleshooting Handbook 55
79 A Air Conditioning and Refrigeration Troubleshooting Handbook 311
80 D Florida Building Code, Mechanical, 2010 508.1
81 D SMACNA HVAC Duct Construction Standards, Metal/Flexible 5.7
82 D Florida Building Code, Mechanical, 2010 306.2
83 B Air Conditioning and Refrigeration Troubleshooting Handbook 34
84 D Trane Ductulator
85 A Trane Reciprocating Refrigeration 76
86 C Air Conditioning and Refrigeration Troubleshooting Handbook 84
87 C NFPA 96 7.8.2.1(8)(b)
88 C SMACNA HVAC Duct Construction Standards, Metal/Flexible 3.1
89 B OSHA 29 CFR Part 1926 .1053(a)(1)(i)
90 C SMACNA Fibrous Glass Duct Construction Standards 3.1
22
91 B Florida Building Code, Mechanical, 2010 Table 607.3.2.1
92 C NFPA 96 12.1.2.4
94 C Florida Building Code, Mechanical, 2010 1108.2
95 B Trane Reciprocating Refrigeration 4
96 A Trane Air Conditioning Manual 362
97 B Air Conditioning and Refrigeration Troubleshooting Handbook 430
98 B Trane Reciprocating Refrigeration 17
99 C Air Conditioning and Refrigeration Troubleshooting Handbook 94
100 C OSHA 29 CFR Part 1926 .451(b)(7)
101 A Air Conditioning and Refrigeration Troubleshooting Handbook 74
102 B Trane Reciprocating Refrigeration 76
103 A Florida Building Code, Mechanical, 2010 Table 1103.1
104 C Trane Reciprocating Refrigeration 106
105 A Trane Reciprocating Refrigeration 123
106 A NFPA 96 14.9.4.5
107 C Air Conditioning and Refrigeration Troubleshooting Handbook 308
108 B SMACNA HVAC Duct Construction Standards, Metal/Flexible 1.21
109 D SMACNA HVAC Duct Construction Standards, Metal/Flexible A.18