Bay Protection Solutions
from Distribution to EHV application
The artofProtection
Bay
2 ABB
Everything you need
The Highlights of ABB’s BPS 600 Series
■ Optimized, pre-designed protection solutions
from Distribution to EHV
■ Flexible realization of your protection philosophy and schemes
■ Scalable hardware and functionality
■ Fully modeled schemes according IEC 61850 and
efficient integration into IEC 61850-compliant systems
■ Convenient selection, simple
ordering and fast delivery
is already prepared
ordering and fast delivery
3
The BPS600 Series of modular bay protection
solutions offers you a smart way of easily
realizing reliable protection schemes for all applications in new and retrofit substations.
ABB’s long experience and deep know-how as global protection systems supplier, field-proven
functionality and hardware as well as innovative technologies are all part of the package.
Short project implementation times, reduced risks and life-cycle cost as well as easy intro-
duction of IEC 61850 into your substations are additional benefits.
The BPS 600 Series together with BCS 600 Series Bay Control
Solutions and SAS 600 Series Substation Automation Solutions is
the perfect strategy to build Substation Automation Systems.
Main 1 / Group1
BPS 673BPS 671 BPS 671 BPS 671 BPS 673BPS 670BPS 674
Main 2 / Group 2
Busbar
QB1 QB2
QA1
BI1BI2BI3BI4
QB1 QB2
QA1
BI1BI2BI3BI4
LongLine
BI1
QB1 QB2
QA1
BI1BI2BI3BI4
BI1
MediumLine
QB1 QB2
QA1
BI1BI2BI3BI4
ShortLine
BI1
QB1 QB2
QA1
BI1BI2BI3BI4
BI6
BI5
BI7
QB1 QB2
QA1
BI1BI2BI3BI4
BI6
BI7
Bay Protection Solutions
Cable feeder
Line Feeder
Busbar / Breaker-failure
TransformerCoupler / Section / DiameterShunt
MotorT-Zone
Distribution
Sub-transmission Main Backup
Main 1Main 2
Main
Main 1Main 2
Transmission
Protection
concept
BPS504
BPS503
BPS502
BPS501
BPS634
BPS533
BPS532
BPS531
BPS630
BPS654
BPS653
BPS552
BPS651
BPS650
BPS674
BPS
BPS
BPS671
BPS684
BPS
BPS682
BPS506
BPS685
BPS687
BPS681
BPS
BPS
673
670
672
683
680
BPS modular scalable
protection solutions
protects your entire
substation
4
built-inABB expertise
With
Main 1 / Group1
BPS 673BPS 671 BPS 671 BPS 671 BPS 673BPS 670BPS 674
Main 2 / Group 2
Busbar
QB1 QB2
QA1
BI1BI2BI3BI4
QB1 QB2
QA1
BI1BI2BI3BI4
LongLine
BI1
QB1 QB2
QA1
BI1BI2BI3BI4
BI1
MediumLine
QB1 QB2
QA1
BI1BI2BI3BI4
ShortLine
BI1
QB1 QB2
QA1
BI1BI2BI3BI4
BI6
BI5
BI7
QB1 QB2
QA1
BI1BI2BI3BI4
BI6
BI7
Bay Protection Solutions
Cable feeder
Line Feeder
Busbar / Breaker-failure
TransformerCoupler / Section / DiameterShunt
MotorT-Zone
Distribution
Sub-transmission Main Backup
Main 1Main 2
Main
Main 1Main 2
Transmission
Protection
concept
BPS504
BPS503
BPS502
BPS501
BPS634
BPS533
BPS532
BPS531
BPS630
BPS654
BPS653
BPS552
BPS651
BPS650
BPS674
BPS
BPS
BPS671
BPS684
BPS
BPS682
BPS506
BPS685
BPS687
BPS681
BPS
BPS
673
670
672
683
680
5
Reliable solutions for efficient system integration
beyondprotection
Far
Busbar Protection
BPS 6x0
■ For single to quadruple busbars incl. transfer bus■ For one and a half breaker systems■ Decentralized and centralized installation for up to 60 bays■ Breaker-failure protection■ Event- and disturbance recording
Busbar Protection Add-ons■ IEC 61850-8-1 interface■ Endfault protection■ Test switches
Line and Cable Protection
BPS 6x1 / 6x2
Line Differential protection■ Phase-segregated differential protection■ Direct fiber-optic link between relays (3 to 100 km)■ With / without transformers in the protected zone■ Redundant communi- cation possibility ■ GPS time synchroni- zation in route switched networks■ Associated functions ■ Long lines with charging current com- pensation ■ Non-directional E/F over-current protection ■ Disturbance recorder
Line Distance Protection■ Full scheme distance protection■ Up to 5 Zones, phase- selective, quadrilateral characteristics■ Wide range of commu- nication schemes■ Line distance protection can be an integrated part of the station pro- tection bay unit■ Associated functions ■ Non-directional E/F over-current protection ■ Directional E/F protection ■ Power-swing blocking ■ Fuse-failure super- vision ■ Switch-onto-fault ■ Disturbance recorder
Line and cable protection Add-ons ■ IEC 61850-8-1 Interface■ 1 and/or 3-phase auto- reclosure ■ Synchrocheck / voltage check ■ Bay unit with busbar / breaker- failure and endfault protection■ Trip circuit supervision ■ DTT Lockout relays■ Test switches
Transformer Protection
BPS 6x3
Transformer Differential Protection■ Biased differential protection for transfor- mers /autotransformers■ Phase-segregated high- impedance protection■ High-impedance/low- impedance restricted earth fault (REF) protect- ions on the primary and/or secondary side■ Tertiary earth fault protection■ Transformer differential protection can be an integrated part of the station protection bay unit
■ Associated functions ■ Non-directional E/F over-current protection ■ Phase over-current protection ■ Thermal overload ■ Overfluxing protection ■ Over-voltage protection ■ Logic for Buchholz, winding, oil tempera- ture etc. ■ Transformer guard units for eight mecha- nical protection signals like Buchholz ■ Disturbance recorder
Transformer Protection Add-ons ■ IEC 61850-8-1 interface■ Transformer guard unit for eight mechanical protections like Buch- holz, temperature and overpressure devices including necessary auxiliary relays for signaling / tripping■ Bay unit with busbar / breaker-failure and endfault protection■ Trip-circuit supervision ■ DTT Lockout relays■ Test switches
BPS 6x0 Busbar & Breakerfailure
BPS 6x Distance protection
BPS 6x Transformer protection
BPS 6x1 Line protection & BPS 6x2 Cable protection BPS 6x Shunt protection
BPS 6x3 Transformer protection
BPS
BPS Motor protection
M
BPS 6x0 Busbar & Breakerfailure
BPS 6x Distance protection
BPS 6x Transformer protection
BPS 6x1 Line protection & BPS 6x2 Cable protection BPS 6x Shunt protection
BPS 6x3 Transformer protection
BPS
BPS Motor protection
M
BPS 6x0 Busbar & Breakerfailure
BPS 6x Distance protection
BPS 6x Transformer protection
BPS 6x1 Line protection & BPS 6x2 Cable protection BPS 6x Shunt protection
BPS 6x3 Transformer protection
BPS
BPS Motor protection
M
6
Coupler / Section / Diameter Protection
BPS 6x4
■ Busbar protection bay unit■ Definite time overcurrent protection for the coupler / sectionalizer ■ Breaker-failure protection ■ Disturbance recorder ■ This solution is mostly combined with the central unit of a BPS6x0 in a decentralized arrangement
Coupler / Section / Diameter Protection Add-ons ■ IEC 61850-8-1 interface■ Trip circuit supervision ■ Test switches
Line Shunt Reactor Protection
BPS 6x5
■ Biased low-impedance or high-impedance differential protection■ Restricted earth fault, low or high- impedance ■ Non-directional over- current protection ■ Thermal overload ■ Overfluxing ■ Disturbance recorder
Line Shunt Reactor Protection Add-ons ■ IEC 61850-8-1 Interface■ Bay unit with busbar / breaker- failure and endfault protection■ Trip-circuit supervision■ DTT Lockout relays■ Test switches
BPS 6x0 Busbar & Breakerfailure
BPS 6x Distance protection
BPS 6x Transformer protection
BPS 6x1 Line protection & BPS 6x2 Cable protection BPS 6x Shunt protection
BPS 6x3 Transformer protection
BPS
BPS Motor protection
M
BPS 6x0 Busbar & Breakerfailure
BPS 6x Distance protection
BPS 6x Transformer protection
BPS 6x1 Line protection & BPS 6x2 Cable protection BPS 6x Shunt protection
BPS 6x3 Transformer protection
BPS
BPS Motor protection
M
T-Zone Protection
BPS 6x7
■ Biased differential protection or per-phase high-impedance protection■ Non-directional over- current protection■ Disturbance recorder
T-Zone Protection Add-ons ■ IEC 61850-8-1 Interface■ Lockout relays■ Test switches
BPS 6x0 Busbar & Breakerfailure
BPS 6x Distance protection
BPS 6x Transformer protection
BPS 6x1 Line protection & BPS 6x2 Cable protection BPS 6x Shunt protection
BPS 6x3 Transformer protection
BPS
BPS Motor protection
M
Sequence of events
■ Event list■ Historical events■ Filtering function■ Export facilities
Disturbance record upload
■ Manual upload■ Cyclic upload■ Event-driven upload
Disturbance record analysis
■ Waveform visualiza- tions, signal vectors■ Fault location, advan- ced calculation■ Frequency deviation, apparent and reactive power calculation■ Automatic analysis
Trip counter tableIED parameterization
Automatic sequences
Trends
Dynamic busbarcoloring
Measurements reports
External alarming
Advanced functionalities
Disturbance record upload
Disturbance record analysis
Public PagingSystems Faxe-mail
TelephoneFixed
AlarmBelx,eoidihjkjklkdlkjdlkul lkj never againQuare sibi habeant.Belx,eoidihjkjk
lkdlkjdlkul lkj never againQuare sibi habeant.Belx,eoidihjkjk
lkdlkjdlkul lkj never againQuare sibi habeant.Belx,eoidihjkjk
lkdlkjdlkul lkj never again
Alarm Belx,eoidihjkjk
lkdlkjdlkul lkj never again
Station Computer
TelephoneMobile ShortMessages(SMS)
AlarmBelx,eoidihjkjklkdlkjdlkul lkj never Quare sibi habeant.Belx,eoidihjkjklkdlkjdlkul lkj never again. Quare sibi habeant. Belx
Trip counter tableIED parameterization
Automatic sequences
Trends
Dynamic busbarcoloring
Measurements reports
External alarming
Advanced functionalities
Disturbance record upload
Disturbance record analysis
Public PagingSystems Faxe-mail
TelephoneFixed
AlarmBelx,eoidihjkjklkdlkjdlkul lkj never againQuare sibi habeant.Belx,eoidihjkjk
lkdlkjdlkul lkj never againQuare sibi habeant.Belx,eoidihjkjk
lkdlkjdlkul lkj never againQuare sibi habeant.Belx,eoidihjkjk
lkdlkjdlkul lkj never again
Alarm Belx,eoidihjkjk
lkdlkjdlkul lkj never again
Station Computer
TelephoneMobile ShortMessages(SMS)
AlarmBelx,eoidihjkjklkdlkjdlkul lkj never Quare sibi habeant.Belx,eoidihjkjklkdlkjdlkul lkj never again. Quare sibi habeant. Belx
IED parameterization
■ Configuration/para- meter upload from IED■ Change of individual parameters or para- meter sets■ Access to all IED para- meters
Trip counter tableIED parameterization
Automatic sequences
Trends
Dynamic busbarcoloring
Measurements reports
External alarming
Advanced functionalities
Disturbance record upload
Disturbance record analysis
Public PagingSystems Faxe-mail
TelephoneFixed
AlarmBelx,eoidihjkjklkdlkjdlkul lkj never againQuare sibi habeant.Belx,eoidihjkjk
lkdlkjdlkul lkj never againQuare sibi habeant.Belx,eoidihjkjk
lkdlkjdlkul lkj never againQuare sibi habeant.Belx,eoidihjkjk
lkdlkjdlkul lkj never again
Alarm Belx,eoidihjkjk
lkdlkjdlkul lkj never again
Station Computer
TelephoneMobile ShortMessages(SMS)
AlarmBelx,eoidihjkjklkdlkjdlkul lkj never Quare sibi habeant.Belx,eoidihjkjklkdlkjdlkul lkj never again. Quare sibi habeant. Belx
Various back-up protection functions are available in the used devices and can be applied as a customization■ Definite time over- and undercurrent protection
■ Three- phase current plausibility check■ Three- phase voltage plausibility check■ Direct. sensitive EF prot. for grounded systems■ Directional over-current inverse time protection
Back-up Protection
■ Inverse time over- current protection■ Definite time over- and undervoltage protection■ Inverse time earth fault over-current protection■ Directional overcurrent definite time protection
7
BPS 6x1 / BPS 6x2 Line and cable protectionThe modular basic packages are
designed for cables, overhead lines
and multi-terminal lines of various
lengths. These can be complemen-
ted by a choice of options to meet
your specific requirements and
philosophy
Typical applications for BPS6x1
■ Short lines ■ Medium lines■ Long lines■ Multi-terminal lines with / without transformers■ Tapped lines with / without transformers
Typical applications for BPS6x2
■ Cables
Available line and cable protection solutions
Short lines
Medium lines
Long lines
Multi-terminal lines
V15
V25
V35
V11V14
V21V24
V11 V11 V11
IED 1Main 1
IED 2 Main 2 / Back-up BPS 651 BPS 671 BPS 681
IED 1 IED 2 BPS 652 BPS 672 BPS 682
Cables
V31
V41
V31
V21
V11
Mainprotection functions
Sub-transmission
Transmissionone and a
half breaker
Transmissionsingle /
double bus
PDIF PDIF
PDIF PDIS
PDIF PDIF
PDIF PDIS* PDIS
PDIF PDIS*
PDIF PDIS*
* used as a back-up in the same device
8 ABB
BB – I
Line Bay Single / Double Bus
BB – II
QB1
QA1
BI1
BI2
BI3
BU1
IEC 61850-8-1
General options
2769
TCSLatch
Busbar &Breaker Failure
Protection
PDIFRBRFPTOCRDREPTRC
87B50/62BF51EFP95DR
94
Main 1Protection
IEC ANSI
PDISPTOCPTOCPIOCPTOVRPSBPSOFPTTRPTRCRDREGGIO
21,8551/67N51/67
50/50N59/59N
78SOTF
4994
95DRDTT
Main 2Protection
IEC ANSI
Add-onPackage
IEC ANSI
RSYNRREC
2579
Add-onPackage
IEC ANSI
PDIFPDISPTOCPTOCPIOCPTOVRPSBPSOFPTRCRDREGGIO
87L21
51/67N51/67
50/50N59/59N
78SOTF
9495DRDTT
RSYNRREC
2579
IEC ANSI
IEC ANSI
BPS 6x1 / BPS 6x2 Line and cable protection
9ABB
BB – I
Line Bay Single / Double Bus
BB – II
QB1
QA1
BI1
BI2
BI3
BU1
IEC 61850-8-1
General options
2769
TCSLatch
Busbar &Breaker Failure
Protection
PDIFRBRFPTOCRDREPTRC
87B50/62BF51EFP95DR
94
Main 1Protection
IEC ANSI
PDISPTOCPTOCPIOCPTOVRPSBPSOFPTTRPTRCRDREGGIO
21,8551/67N51/67
50/50N59/59N
78SOTF
4994
95DRDTT
Main 2Protection
IEC ANSI
Add-onPackage
IEC ANSI
RSYNRREC
2579
Add-onPackage
IEC ANSI
PDIFPDISPTOCPTOCPIOCPTOVRPSBPSOFPTRCRDREGGIO
87L21
51/67N51/67
50/50N59/59N
78SOTF
9495DRDTT
RSYNRREC
2579
IEC ANSI
IEC ANSI
Features■ Comprehensive functionality
for Main1 + Main 2 / Back-up■ LAN connectivity to IEDs for
configuration and monitoring
Options■ IEC 61850-8-1 communication
interface■ Autoreclosure and synchrocheck■ Busbar and breaker failure
protection■ Trip circuit supervision■ DTT Lock-out relays■ Test switches
BPS 6x3 Transformer protectionThe scaleable solutions provide
reliable protection for all types and
sizes of transformers. Their field-
proven protection and monitoring
functionality helps to prolong the
service-life of the most expensive
pieces of equipment in your sub-
station.
Typical applications for BPS6x3
■ Two and three Winding-transformers■ Autotransformers
Available versions
IED 1Main 1
IED 2 Group 2 / Back-up
BPS 653 BPS 673 BPS 683
V12V12V15Two or three Winding-transformer
V22Autotransformer
Mainprotection functions
Sub-transmission
Transmissionone and a
half breaker
Transmissionsingle /
double bus
PDIF PTOCPDIF
PTOCPTTR
PTOVPVPH
PDIF PTOCPDIF
PTOCPTTR
PTOVPVPH
BB – I
Transformer Bay Single / Double Bus
BB – II
QB1 QB2
QA1
BI1
BI2
BI3
BI4
BI7
BI5
BI6
IEC 61850-8-1
Group 1Protection
PDIFPTOC PIOCPTTRPTRCRDREGGIO
87T51/67
50/50N4994
95DRDTT
IEC ANSI
PTOCPTOCPIOCPVPHPTOVPTRCRDREGGIO
51/67N51/67
50245994
95DRDTT
Group 2Protection
IEC ANSI
Add-onPackage
GGIO GuardIEC ANSI
PDIF HVPDIF MV
GGIO
87N87N
Guard
IEC ANSI
Add-onPackage
27 TCS
Busbar &Breaker Failure
Protection
PDIFRBRFPTOCRDREPTRC
87B50/62BF51EFP95DR
94
General optionsIEC ANSI
IEC ANSI
10
BB – I
Transformer Bay Single / Double Bus
BB – II
QB1 QB2
QA1
BI1
BI2
BI3
BI4
BI7
BI5
BI6
IEC 61850-8-1
Group 1Protection
PDIFPTOC PIOCPTTRPTRCRDREGGIO
87T51/67
50/50N4994
95DRDTT
IEC ANSI
PTOCPTOCPIOCPVPHPTOVPTRCRDREGGIO
51/67N51/67
50245994
95DRDTT
Group 2Protection
IEC ANSI
Add-onPackage
GGIO GuardIEC ANSI
PDIF HVPDIF MV
GGIO
87N87N
Guard
IEC ANSI
Add-onPackage
27 TCS
Busbar &Breaker Failure
Protection
PDIFRBRFPTOCRDREPTRC
87B50/62BF51EFP95DR
94
General optionsIEC ANSI
IEC ANSI
IEC 61850-8-1
11ABB
Features■ Comprehensive functionality
for Group 1 + Group 2 / Back-up■ LAN connectivity to IED’s
for configuration and monitoring
Options■ IEC 61850-8-1 communication
interface■ Busbar and breaker-failure
protection■ Trip circuit supervision■ DTT Lock-out relays■ Test switches
BPS6x0 / BPS 6x4 Busbar and Breakerfailure protectionThe solutions ensure highest
availability of busbars of any type,
configuration and size. Centralized
and cable-saving decentralized
solutions cater for new and retro-
fit substations and offer additional
backup protection in the bays.
For a more integrated, space and
cost-efficient solution, a station
protection system covering busbars,
line and transformers feeders is
available as well.
Typical applications for BPS6x0
■ Single to quadruple busbars incl. transfer bus
■ One and a half breaker systems
■ AIS / GIS installations with up to 60 bays
Typical applications for BPS6x4
■ Buscoupler■ Sections■ Diameters
Available versions
IEC 61850-8-1
Bay level
Bayunit
FOlink
Central unit
Bayunit
Station level
IEC ANSIBuscoupler
RBRFPTOCPTOCPDREPTRC
50/62BF51EFP
5195DR
94
27 TCS
Add-onIEC ANSI
PDIF 87B
Central unitBPS 670
IEC ANSIQ
B1
QB
2
QA
1
BI1
BI2
BI3
BI4
QB
1Q
B2
QA
1
BI1
BI2
BI3
BI4
BI1
QB
1Q
B2
QA
1
BI1
BI2
BI3
BI4
BI1
QB
1Q
B2
QA
1
BI1
BI2
BI3
BI4
BI1
QB
1Q
B2
QA
1
BI1
BI2
BI3
BI4
BI6
QB
1Q
B2
QA
1
BI1
BI2
BI3
BI4
BI6
V11V12V13V14V15V16
V11V12V13V14V15V16
V11V12V13V14V15V16
Decentral
V21V34
V21V33V21
Central
BPS 650 BPS 670 BPS 680
V11V21
V11V12
V11Coupler /Section /Diameter
PDIF RBRF
PDIF RBRF
RBRFPTOC
Mainprotection functions
Sub-transmission
Transmissionone and a
half breaker
Transmissionsingle /
double bus
12
BPS6x0 / BPS 6x4 Busbar and Breakerfailure protection
Features■ Highly selective and fast
busbar protection■ Breaker failure protection■ LAN connectivity to IED’s
for configuration and monitoring
Options■ IEC61850-8-1 communication
interface■ Back-up protection functions
in bay units■ Trip circuit supervision■ End fault protection■ Test switches
IEC 61850-8-1
Bay level
Bayunit
FOlink
Central unit
Bayunit
Station level
IEC ANSIBuscoupler
RBRFPTOCPTOCPDREPTRC
50/62BF51EFP
5195DR
94
27 TCS
Add-onIEC ANSI
PDIF 87B
Central unitBPS 670
IEC ANSI
QB
1Q
B2
QA
1
BI1
BI2
BI3
BI4
QB
1Q
B2
QA
1
BI1
BI2
BI3
BI4
BI1
QB
1Q
B2
QA
1
BI1
BI2
BI3
BI4
BI1
QB
1Q
B2
QA
1
BI1
BI2
BI3
BI4
BI1
QB
1Q
B2
QA
1
BI1
BI2
BI3
BI4
BI6
QB
1Q
B2
QA
1
BI1
BI2
BI3
BI4
BI6
Protection solutionsIEC 61850
Trans-mission
level
Sub-trans-
missionlevel
Hardcopyprinter
SAS 650
Eventprinter
Additionalworkstation
GPSRedundant station HMI
Stationalarmdevice
Remoteaccessrouter
Telecommuni-cation link
Masterclock
Bay Protection and Bay Control Solutions
Bay Protection and Bay Control Solutions
Substation Automation System
Typical ABB Substation Automation Solution
Stationlevel
BPS 670BPS 674
BPS 673 BPS 671
BPS 650BPS 654
BPS 653 BPS 651 BCS 680
BCS 670 BCS 670 BCS 670
Station server
Gateway
14 ABB
based on
Protection solutionsIEC 61850
LD “Distance Protection”
“Circuit Breaker”
LD “Recloser”
PDIS 1 PTRC
XCBR
STR
TR
“Retrip” “Close”
Pos
Op
Op
STR STR TrMod
MaxCycl
MaxTmms
Rec i Tmms
TrBeh
RecCyc
OP
Op
Status Settings
Status
ProgrammableCombination
of Inputs
Op
STR
RREC
PDIS 2
PDIS n
15ABB
in a substation automation environmentin a substation in a substation
environment
How to use IEC 61850 for time-critical
information exchange
There are several automated functions in the substa-
tion automation system, which require a time-critical
exchange of binary information between functions
located within the same bay or in different bays.
Examples:■ Exchange between line protection and auto-recloser
■ Exchange between bays for breaker-failure protection
■ Exchange between bays for station interlocking
■ DR triggering by protection functions
Generic Object Oriented Substation Event
For the exchange of this type of (binary) information
over serial communication, IEC 61850 introduces a
specific information exchange service called GOOSE
(Generic Object Oriented Substation Event) based on
the publisher-subscriber concept. The content of a
GOOSE message is defined with a dataset (similar
as for the report model described above). The
GOOSE message is sent as a multicast message
over the communication network. This means that
various devices can receive the message and retrieve
the information required from the message. The
communication service is not confirmed; instead,
the message is repeated several times.
Exchange of information within the bay
A typical example is the exchange of information be-
tween Logical Device “Distance Protection” containing
instances of LN PDIS per zone and the LN PTRC
and the Logical Device “Recloser” containing the LN
RREC in case these both functions are installed in
separate devices.
Bay Protection Solutions
Cable feeder
Line Feeder
Busbar / Breaker-failure
TransformerCoupler / Section / DiameterShunt
MotorT-Zone
Distribution
Sub-transmission Main Backup
Main 1Main 2
Main
Main 1Main 2
Transmission
Protection
concept
BPS504
BPS503
BPS502
BPS501
BPS634
BPS533
BPS532
BPS531
BPS630
BPS654
BPS653
BPS552
BPS651
BPS650
BPS674
BPS
BPS
BPS671
BPS684
BPS
BPS682
BPS506
BPS685
BPS687
BPS681
BPS
BPS
673
670
672
683
680
Perfect packages with the
Right functionality
Optimal hardware
Open communication
BPS 600 Series overview
Designed for your convenience
BPS 600—the smart choice
The BPS 600 Series together with BCS 600 Series Bay Control Solutions
and SAS 600 Series Substation Automation Solutions is the ultimate and
efficient strategy to build Substation Automation Systems.
© C
opyr
ight
200
6 A
BB
. A
ll rig
hts
rese
rved
.
1KH
A -
001
079
- S
EN
- P
DF
- 9.
06 -
Prin
ted
in S
witz
erla
nd.
ABB Schweiz LtdPower SystemsBruggerstrasse 72CH-5400 Baden/SwitzerlandPhone +41- 58 585 77 44Fax +41- 58 585 55 77E-mail substation.automation@ch.abb.com
www.abb.com/substationautomation