38ARZ/ARD Commercial Air-Cooled Split System

Product Data

The 38ARZ/ARD condensing units with scroll compressors match Carrier’s 40RM indoor-air handlers for a wide selection of dependable commercial cooling solutions.

Carrier’s air-cooled split systems:

• provide a logical solution for commercial needs • have a rugged, dependable construction

Features/Benefits These dependable split systems match Carrier’s indoor-air handlers and direct-expansion coils with outdoor condensing units for a wide selection of commercial cooling solutions. Up to 11.0 EER The high efficiency split commercial split system combining the 38ARZ/ARD outdoor condensing unit with 40RM air handling unit can save 20-27% of energy consumption. Constructed for long life The 38ARZ (single circuit, scroll compressor) and 38ARD (dual circuit, scroll compressor) models are designed and built to last. The copper tube-aluminum fin outdoor coil construction provides years of trouble-free operation. Where conditions require, a range of Enviro-Shield™ coil protection options are available. Cabinets are constructed of prepainted galvanized steel, delivering unparalleled protection from the environment. Inside and outside surfaces are protected to ensure long life, good looks, and reliable operation. Safety controls are used for enhanced system protection and reliability.

Sizes 007 – 028 With 40RM007-034 6 - 25 Nominal Tons - 60Hz

Efficient operation Building owners will appreciate the high unit EERs (Energy Efficiency Ratios) offered by the 38AR units. These units provide greater efficiency than similar units in the marketplace, which translates into year-round operating savings.

Controls for performance dependability The 38AR condensing units offer the building owner operating controls and components designed for performance dependability. The highly efficient compressors are engineered for long life and durability. The compressors include overload protection and vibration isolation for quiet operation. The high pressure switch protects the entire refrigeration system from abnormally high operating pressures. A low pressure switch protects the system from loss of charge. The 38ARD014-028 units feature 2 compressors and 2 refrigerant circuits that provide continuous air conditioning and design flexibility. All units include a crankcase heater to eliminate liquid slugging at start-up. The latest safety standards for 38AR units are UL, compliant.

Innovative Carrier 40RM packaged air handlers are custom matched to 38AR condensing units The 40RM Series has excellent fan performance, efficient direct-expansion (DX) coils, a unique combination of indoor-air quality options, and is easy to install. Its versatility and state-of-the art features help to ensure economical performance of the split system both now and in the future.

Indoor-air quality (IAQ) features — The unique combination of IAQ features in the 40RM Series air handlers help to ensure that only clean, fresh, conditioned air is delivered to the occupied space. Direct-expansion (DX) cooling coils prevent the build-up of humidity in the room, even during part-load conditions. Unit sizes of 10 tons and larger feature dual-circuit coils for improved temperature control. Standard 1-in. aluminum washable filters remove dust and airborne particles from the occupied space for cleaner air.

The pitched, non-corroding drain pan can be adjusted for a right-hand or left-hand connection to suit many applications and provide positive drainage and prevent standing condensate.

Economy — The 40RM Series packaged air handlers have low initial costs, and provide reduced installation expense and energy-efficient performance. Quick installation is ensured by the multipoise design. Units can be installed in either the horizontal or vertical configuration without modifications. Fan motors and contactors are prewired and thermostatic expansion valves (TXVs) are factory-installed on all 40RM models. High efficiency, precision-balanced fans minimize air turbulence, surging, and unbalanced operation, cutting operation expenses.

Rugged dependability — The 40RM series units are made to last. The die-formed galvanized steel panels ensure structural integrity under all operating conditions. Galvanized steel fan housings are securely mounted to a galvanized steel fan deck. Rugged pillow-block bearings (40RM014-034) are securely fastened to the solid steel fan shaft with split collets and clamp locking devices. Smaller unit sizes have spider-type bearings.

Coil flexibility — Model 40RM directexpansion coils have galvanized steel casings; inlet and outlet connections are on the same end. The coils are designed for use with R-22 refrigerant and have 3/8-in. diameter copper tubes mechanically bonded to aluminum sine-wave fins. The coils include matched, factoryinstalled thermostatic expansion valves (TXVs) with matching distributor nozzles.

Easier installation and service — The multipoise design and component layout ensures quick unit installation and operation. Units can be converted from horizontal to vertical operation by simply repositioning the unit. Drain pan connections are duplicated on both sides of the unit. The filters, motor, drive, TXVs, and coil connections are all easily accessed by removing side panels.

2

Model number nomenclature38 Z 007 -- - 5 0 1 S

Type 38AR–Commercial Air-Cooled Condenser

Z-Single Circuit D- Dual Circuit

Nominal Capacity in-Tons 007 - 6 Tons 008 - 7.5 Tons 012 - 10 Tons 014- 12 Tons 016 - 14 Tons 024 - 20 Tons

-- - Not Used

S - High Ambient

Packaging 1 - Standard

Design Series 0 - Original Design

Voltage 2 – 380–3–60 5 – 208/230–3–60 6 – 460–3–60

Fin Type -- - Standard Bare Fins C- Cu/Cu Coil P- Pre-Coated Blue Fins

Table of Contents Page.

38ARZ/ARDFeatures/Benefits………………………………………………………………………………………. 1 ModelNumber Nomenclature………………………………………………………………………….. 3 Physical Data……………………………………………………………………………………………. 4 ARI Capacity ratings 60Hz ……………………………………………………………………………. 5 Options and accessories ………………………………………………………………………………. 6 Base Unit Dimensions………………………………………………………………………………….. 7-9Performance data ……………………………………………………………………………………… 10-17Electrical Data…………………………………………………………………………………………… 18Application Data………………………………………………………………………………………… 19Typical Wiring Schematic………………………………………………………………………………. 20-26

40RM Model number nomenclature………………………………………………………………………….. 27Physical Data……………………………………………………………………………………………. 28Options and accessories 29-31Base Unit Dimensions………………………………………………………………………………….. 32-41Selection procedure……………………………………………………………………………………. 42-46Electrical Data…………………………………………………………………………………………… 47-53Typical piping and wiring ……………………………………………………………………………… 54-57Application Data………………………………………………………………………………………… 58-61

Guide SpecificationsGuide Specifications —38ARZ007-012………………………………………..…………………… 62,63 Guide specifications— 38ARD014-028 …………………………………………………………….. 64,65 Guide specifications —40RM………………………………………………………………………… 66,67

3

028 - Tons25

abdulrehman.zia
Typewritten Text
AR
abdulrehman.zia
Typewritten Text
abdulrehman.zia
Typewritten Text

4

Physical Data – English UNIT 38AR

ARZ ARD 007 008 012 014 016 024 028

NOMINAL CAPACITY (Tons) 6 7 1/2 10 12 1/2 15 20 25 OPERATING WEIGHT (lb) Aluminium Coils (Standard) Copper Coils (Optional)

300 352

383 484

430 531

676 822

740 886

764 904

1279 1532

SHIPPING DIMENSIONS (in) (W X H X D) (59.2X45.5X39) (72.6X44.25X41.7) 96.5×49×54.3 COMPRESSOR Scroll Qty Oil Charge (oz)

1 2 88 90 110 60(ea) 85(ea) 110(ea) 111 (ea)

REFRIGERANT TYPE * Operating Charge, Typical (lb) ** Shipping Charge (lb)

R22 12 20 22 23/circuit 28/circuit 17.9

2.0 3.1 3.1 FINISH Gray CONDENSER FAN Propeller Type Qty…RPM 2…850 2…1100 2…1075 2...1100 Diameter Nominal Air Flow (Total CFM)

22 in 26 in 30 5400 6500 11,000 14500

Watts (Total) 341 570 1460 1500 Motor Horsepower, 1/8 1/4 1/4 1/2 1

CONDENSER COIL (Qty) 2 Face Area (sq ft Total)) 29.2 29.2 50.4 Rows…Fins/in. 1…17 2…17 3…15 3... 16 Storage Capacity (lb)*** 17.3 34.2 48 - CONTROLS Pressurerestart Settings (psig) High Cutout Cut-in Low Cutout Cut-in

428 ± 10 320 ± 20

27 ± 3 44 ± 5

428 ± 10 320 ± 20

27 ± 4 44 ± 7

DISCHARGE GAS THERMOSTAT (0F) Cutout Cut-in ---

270 ± 9 190 ± 13

---

PRESSURE RELIEF Location Tempreature

Suction Line 200

Liquid Line 200

PIPING CONNECTION Qty…Suction 1…1 1/8 1…1 1/8 1…1 3/8 2…1 3/8 2…1 3/8 Qty…Liquid 1… 3/8 1… 3/8 1… 1/2 2… 1/2 2… 5/8 Hot Gas Stub 3/8 -

*Unit is factory-supplied with holding charge only. **Typical operating charge with 25 ft of interconnecting piping. ***Storage capacity of condenser coil with coil 80% full of liquid R-22 at 95 F.

/circuit

CONDENSING UNIT AIR HANDLER/ INDOOR COILCONDENSING UNIT ONLY

Net Cap. (Btuh) IPLV Net Cap. (Btuh) IPLV

38ARZ00740RM00740RM008

69,00071,000

11.072,000 12.4

38ARZ00840RM00740RM00840RM012

87,00090,00093,000

10.610.610.4

100,000 12.7

38ARZ01240RM01240RM014

118,000123,000

10.310.4

133,000 12.4

38ARD01440RM01240RM01440RM016

135,000145,000152,

9.710.510.8

9.910.911.0

158,00012.5

15.1

38ARD01640RM01440RM016

176,000 10.410.510.2

204,000 11.9 13.9

38ARD02440RM01640RM02440RM028

222,000232,000242,000

9.59.5

10.19.8 259,000 13.1

OCTAVE BANDS

D014

dB(A)OCTAVE BAND CENTER FREQUENCY

40RM007

40RM008

40RM012

40RM014

40RM016

40RM024

40RM028

40RM034

CONDENSING UNIT AIR HANDLER/ INDOOR COILCONDENSING UNIT ONLY

Net Cap. (Btuh) IPLV Net Cap. (Btuh) IPLV

38ARZ00740RM00740RM008

69,00071,000

11.072,000 12.4

38ARZ00840RM00740RM00840RM012

87,00090,00093,000

10.610.610.4

100,000 12.7

38ARZ01240RM01240RM014

118,000123,000

10.310.4

133,000 12.4

38ARD01440RM01240RM01440RM016

135,000145,000152,

9.710.510.8

9.910.911.0

158,00012.5

15.1

38ARD01640RM01440RM01640RM024

176,000187,000194,000

10.010.210.1

10.410.510.2

204,000 11.9 13.9

38ARD02440RM01640RM02440RM028

222,000232,000242,000

9.59.5

10.19.8 259,000 13.1

OCTAVE BANDS

D014

dB(A)OCTAVE BAND CENTER FREQUENCY

40RM007

40RM008

40RM012

40RM014

40RM016

40RM024

40RM028

40RM034

CONDENSING UNIT AIR HANDLER/ INDOOR COILCONDENSING UNIT ONLY

Net Cap. (Btuh)

38ARZ00740RM00740RM008

69,00071,000

11.072,000 12.4

38ARZ00840RM00740RM00840RM012

87,00090,00093,000

10.610.610.4

100,000 12.7

38ARZ01240RM01240RM014

118,000123,000

10.310.4

133,000 12.4

38ARD01440RM01240RM01440RM016

135,000145,000152,

9.710.510.8

9.910.911.0

158,00012.5

15.1

38ARD01640RM01440RM01640RM024

176,000187,000194,000

10.010.210.1

10.410.510.2

204,000 13.9

40RM01640RM02440RM028

222,000232,000242,000

9.59.5

10.19.8 259,000 13.1

OCTAVE BANDS

D014

dB(A)OCTAVE BAND CENTER FREQUENCY

40RM007

40RM008

40RM012

40RM014

40RM016

40RM024

40RM028

40RM034

AIR HANDLER/ INDOOR COILCONDENSING UNIT ONLY

Net Cap. (Btuh) IPLV Net Cap. (Btuh) IPLV

38ARZ00740RM00740RM008

69,00071,000

11.072,000 12.4

40RM00740RM00840RM012

87,00090,00093,000

10.610.610.4

100,000 12.7

38ARZ01240RM01240RM014

118,000123,000

10.310.4

133,000 12.4

38ARD01440RM01240RM01440RM016

9.710.510.8

9.910.911.0

158,00012.5

15.1

38ARD01640RM01440RM01640RM024

176,000187,000194,000

10.010.210.1

10.410.510.2

204,000 11.9 13.9

38ARD02440RM01640RM02440RM028

222,000232,000242,000

9.59.5

10.19.8 259,000 13.1

OCTAVE BANDS

D014

dB(A)OCTAVE BAND CENTER FREQUENCY

40RM007

40RM008

40RM012

40RM014

40RM016

40RM024

40RM028

40RM034

CONDENSING UNIT AIR HANDLER/ INDOOR COILCONDENSING UNIT ONLY

Net Cap. (Btuh) IPLV Net Cap. (Btuh)

72,000 12.4

38ARZ00840RM00740RM00840RM012

87,00090,00093,000

10.610.610.4

100,000 12.7

40RM01240RM014

118,000123,000

10.310.4

133,000 12.4

38ARD01440RM01240RM01440RM016

9.710.5

9.910.911.0

158,00012.5

15.1

38ARD01640RM01440RM01640RM024

176,000187,000194,000

10.010.210.1

10.410.510.2

204,000 13.9

38ARD02440RM01640RM02440RM028

222,000232,000242,000

9.59.5

10.19.8 259,000 13.1

OCTAVE BANDS

D014

dB(A)OCTAVE BAND CENTER FREQUENCY

40RM007

40RM008

40RM012

40RM014

40RM016

40RM024

40RM028

40RM034

ARI Capacity ratings 60HzCONDENSING UNIT AIR HANDLER/ INDOOR COIL

SYSTEM** CONDENSING UNIT ONLY*** Net Cap. (Btuh) EER IPLV Net Cap. (Btuh) EER IPLV

38ARZ007 40RM007 40RM008

69,000 71,000

11.0 10.8

N/A N/A

72,000 12.4 N/A

38ARZ008 40RM007 40RM008 40RM012

87,000 90,000 93,000

10.6 10.6 10.4

N/A N/A N/A

100,000 12.7 N/A

38ARZ012 40RM012 40RM014

118,000 123,000

10.3 10.4

N/A N/A

133,000 12.4 N/A

38ARD014 40RM012 40RM014 40RM016

135,000 145,000 152,000

9.7 10.5 10.8

9.9 10.9 11.0

158,000 12.5

15.1

38ARD016 40RM014 40RM016 40RM024

176,000 187,000 194,000

10.0 10.2 10.1

10.4 10.5 10.2

204,000 11.9 13.9

38ARD024 40RM016 40RM024 40RM028

222,000 232,000 242,000

9.5 9.5 9.6

10.1 9.8 9.9

259,000 11.2 13.1

LEGEND

ASHRAE — American Society of Heating, Refrigeration and Air Condition Engineers EER — Energy Efficiency Ratio IPLV — Integrated Part Load Value N/A — Not Applicable SST — Saturated Suction Temperature *Air Conditioning and Refrigeration Institute. **Ratings in accordance with ARI Standard 360-2000. ***Condensing unit only ratings are at 45 F SST and 95 F entering-air temperature.

NOTES: 1. 38ARZ unit is in accordance with ARI 270-95 Sound Rating of Unitary Equipment. 2. Estimated sound power levels, dB re 1 Picowatt. 38ARD014-028 and 38AKS data is based upon a limited amount of actual testing with the estimated sound power data being generated from this data in accordance with ARI Standard 370 for large outdoor refrigerating and air-conditioning equipment. Since this data is estimated, the sound power levels should not be guaranteed or certified as being the actual sound power levels. 3. The acoustic center of the unit is located at the geometric center of the unit.

ESTIMATED SOUND POWER LEVELS (Lw) — 40RM007-034

UNIT CFM dB(A) OCTAVE BAND CENTER FREQUENCY

63 125 250 500 1000 2000 4000 40RM007 2400 86.3 93.2 89.2 85.2 84.2 80.2 78.2 74.2 40RM008 3000 88.3 95.3 91.3 87.3 86.3 82.3 80.3 76.3 40RM012 4000 91.6 98.6 94.6 90.6 89.6 85.6 83.6 79.6 40RM014 5000 91.1 97.3 93.3 89.3 90.3 84.3 82.3 78.3 40RM016 6000 92.7 98.9 94.9 90.9 91.9 85.9 83.9 79.9 40RM024 8000 96.4 102.6 98.6 94.6 95.6 89.6 87.6 83.6 40RM028 10000 96.2 102.5 98.5 94.5 95.5 89.5 87.5 83.5 40RM034 12000 98.5 104.7 100.7 96.7 97.7 91.7 89.7 85.7

5

38ARD028  40RM028  

  

305,000  

 40RM034 333,000

 318,000 9.810.3

N/A N/A

N/A 10.1

SOUND LEVELS, dB — 38AR UNITS

UNIT 38AR

SOUND RATING (60Hz) dB (A)

OCTAVE BANDS

63 125 250 500 1000 2000 4000 8000

Z007 Z008 Z012

80.0 84.0 85.0

71.5 84.1 88.7

76.8 84.5 85.4

75.3 80.4 81.7

74.0 78.6 80.9

73.9 77.2 82.1

74.1 76.9 76.2

73.5 78.8 73.6

64.0 72.5 67.1

D014 D016 D024

86.9 87.5 88.0

— — —

90.9 90.9 90.9

86.1 86.1 86.1

83.1 83.4 83.8

84.0 84.5 84.5

73.5 76.6 79.2

71.7 73.2 74.3

66.7 63.5 65.5

D028 94.8 — 91.4 88.1 85.8 86.4 81.5 75.2 67.4

Options and accessories 38AR, options

Enviro-Shield™ condenser options offer pre-coated coils that provide protection in mild coastal environments. Several options are available to match coil protection to site conditions for optimum durability. See table below. Consult your Carrier representative for further information.

Non-fused disconnect switch to remove power locally at the condensing unit. This switch also includes a power lockout capability to protect the service person. This lockout switch saves the service person time and effort because there is no need to access a distant disconnect switch while servicing the unit.

Carrier’s line of thermostats provide both programmable and non-programmable capability with the new Debonair® line of commercial programmable thermostats. The Commercial Electronic thermostats provide

7-day programmable capability for economical applications.

PremierLink™ Controller is a field retrofit split system control compatible with the Carrier Comfort Network (CCN) and other building automation systems (BAS). This control is designed to allow users the access and ability to change factory-defined settings thus expanding the function of the standard unit.

WITH ENVIRO Standard Moderate Coastal

Al Fins (Standard Coils)

Cu Fins

6

CONDENSER COIL OPTIONS COPPER‐TUBE COILS WITH ENVIRO‐SHIELD OPTION

ENVIRONMENTStandard Mild Coastal Moderate Coastal 

 Al Fins (Standard Coils)    X Cu Fins    X  Al Fins, Pre‐Coated    X

LEGEND Al — Aluminum Cu — Copper

Base Unit Dimensions – 38ARZ 007 – 012

Approximate Shipping Weight Approx. Shipping Dimensions38AR Size ( A x B x C )

(1504X1157X992) (59.2X45.5X39)

7

7

7

38ARZ Size Approximate Shipping Weight Approx. Shipping Dimensions

( A x B x C ) With Standard Al/Cu Coil With Optional Cu/Cu Coil KG LB KG LB mm inch

007 154 339 178 392 (1504X1157X992) (59.2X45.5X39) 008 192 422 238 524

012 213 467 259 570

38ARD Size Approximate Shipping Weight Approx. Shipping Dimensions

( A x B x C ) With Standard Al/Cu Coil With Optional Cu/Cu Coil KG LB KG LB mm inch

014 357 785 423 931 (1844X1124X1058) (72.6X44.25X41.7) 016 386 849 452 994

024 397 873 461 1014

Base Unit Dimensions – 38ARD 014 – 024

8

9

Base Unit Dimensions – 38ARD 028

38ARZ size

Approximate shipping weight Approx. shipping dimensions (A×B×C) With standard Al/Cu Coil With optional Cu/Cu Coil

KG LB KG LB mm Inch 028 580 1279 695 1532 2451×1380×1282 96.5×54.3×50.5

10

Performance data CONDENSING UNIT RATINGS 38ARZ007

SST (F) Air Temperature Entering Condenser (F) 80 85 95 100 105 115

25 TC kW SDT

53.6 4.24

101.0

52.3 4.49

106.0

49.4 5.02

115.0

48.0 5.31

120.0

46.5 5.60

125.0

43.6 6.24

135.0

30 TC kW SDT

59.1 4.33

102.0

57.6 4.57

107.0

54.6 5.10

117.0

53.0 5.39

122.0

51.5 5.69

126.0

48.3 6.33

136.0

35 TC kW SDT

64.9 4.42

104.0

63.3 4.67

109.0

60.1 5.20

118.0

58.4 5.49

123.0

56.7 5.79

128.0

53.4 6.43

138.0

40 TC kW SDT

71.0 4.53

106.0

69.3 4.77

110.0

65.8 5.31

120.0

64.1 5.60

125.0

62.3 5.90

129.0

58.7 6.55

139.0

45 TC kW SDT

77.4 4.65

107.0

75.6 4.89

112.0

71.9 5.43

122.0

70.1 5.72

126.0

68.2 6.02

131.0

64.3 6.68

141.0

50 TC kW SDT

84.2 4.78

109.0

82.3 5.03

114.0

78.4 5.56

123.0

76.4 5.86

128.0

74.3 6.16

133.0

70.2 6.81

142.0

38ARZ008

SST (F) Air Temperature Entering Condenser (F) 80 85 95 100 105 115

25 TC kW SDT

73.9 5.81 98.6

71.7 6.14

104.0

67.0 6.84

114.0

64.6 7.21

118.0

62.1 7.58

123.0

57.0 8.36

133.0

30 TC kW SDT

82.0 5.88 99.6

79.7 6.21

104.0

74.9 6.90

114.0

72.4 7.28

119.0

69.9 7.65

124.0

64.7 8.46

134.0

35 TC kW SDT

90.4 5.98

101.0

88.0 6.31

106.0

83.0 7.02

115.0

80.4 7.40

120.0

77.8 7.78

125.0

72.4 8.59

135.0

40 TC kW SDT

99.2 6.09

103.0

96.7 6.43

107.0

91.4 7.14

117.0

88.7 7.53

122.0

85.9 7.92

126.0

80.3 8.74

136.0

45 TC kW SDT

109.0 6.22

104.0

106.0 6.56

109.0

100.0 7.28

119.0

97.4 7.68

123.0

94.5 8.07

128.0

88.6 8.91

138.0

50 TC kW SDT

118.0 6.36

106.0

116.0 6.70

111.0

110.0 7.43

120.0

107.0 7.83

125.0

104.0 8.23

130.0

97.2 9.09

139.0

38ARZ012

SST (F) Air Temperature Entering Condenser (F) 80 85 95 100 105 115

25 TC kW SDT

102.0 8.04

101.0

99.3 8.38

106.0

93.8 9.13

116.0

90.9 9.55

121.0

88.1 9.95

126.0

81.9 10.85 136.0

30 TC kW SDT

112.0 8.26

103.0

109.0 8.60

107.0

103.0 9.31

117.0

99.8 9.65

12.02

96.7 10.05 127.0

90.3 10.95 136.0

35 TC kW SDT

122.0 8.52

104.0

119.0 8.85

109.0

113.0 9.55

118.0

109.0 9.95

123.0

106.0 10.35 128.0

99.0 11.15 137.0

40 TC kW SDT

133.0 8.81

106.0

130.0 9.15

110.0

123.0 9.85

120.0

119.0 10.25 125.0

115.0 10.55 129.0

108.0 11.35 139.0

45 TC kW SDT

144.0 9.12

108.0

141.0 9.45

112.0

133.0 10.15 122.0

130.0 10.55 126.0

126.0 10.85 131.0

118.0 11.65 140.0

50 TC kW SDT

156.0 9.45

109.0

152.0 9.85

114.0

145.0 10.55 123.0

141.0 10.85 128.0

137.0 11.25 133.0

128.0 12.05 142.0

38ARD014

SST (F) Air Temperature Entering Condenser (F) 80 85 95 100 105 115

20TC kW SDT

102.0 9.04

103.0

99.1 9.58

108.0

93.2 10.80 118.0

90.3 11.40 123.0

87.3 12.10 128.0

81.1 13.50 138.0

25TC kW SDT

114.0 9.09

103.0

111.0 9.64

108.0

105.0 10.90 118.0

102.0 11.50 123.0

98.8 12.20 128.0

92.2 13.60 138.0

30TC kW SDT

127.0 9.14

103.0

124.0 9.70

108.0

117.0 10.90 118.0

114.0 11.50 123.0

110.0 12.20 128.0

103.0 13.70 138.0

35TC kW SDT

140.0 9.19

103.0

137.0 9.75

108.0

130.0 11.00 118.0

126.0 11.60 123.0

123.0 12.30 128.0

115.0 13.70 138.0

40TC kW SDT

155.0 9.26

103.0

151.0 144.0 11.00 118.0

140.0 11.70 123.0

136.0 12.30 128.0

128.0 13.80 138.0

9.81 108.0

45TC kW SDT

170.0 9.37

103.0

166.0 9.90

108.0

158.0 11.10 118.0

154.0 11.70 123.0

150.0 12.40 128.0

141.0 13.90 138.0

50TC kW SDT

186.0 9.55

104.0

182.0 10.10 109.0

173.0 11.30 119.0

169.0 11.90 124.0

164.0 12.60 129.0

155.0 14.00 139.0

11

Performance data (cont) 38ARD016

SST (F) Air Temperature Entering Condenser (F) 80 85 95 100 105 115

20 TC kW SDT

141.0 12.01 101.0

137.0 12.60 105.0

129.0 13.70 115.0

124.0 14.30 120.0

120.0 14.90 125.0

110.0 16.10 135.0

25 TC kW SDT

156.0 12.40 102.0

152.0 12.90 107.0

143.0 14.00 116.0

138.0 14.60 121.0

133.0 15.20 126.0

123.0 16.40 136.0

30 TC kW SDT

171.0 12.70 104.0

166.0 13.20 108.0

157.0 14.30 118.0

152.0 14.90 123.0

147.0 15.50 127.0

136.0 16.70 137.0

35 TC kW SDT

187.0 13.10 105.0

182.0 13.60 110.0

172.0 14.70 119.0

166.0 15.30 12.04

161.0 15.90 129.0

150.0 17.10 138.0

40 TC kW SDT

203.0 13.50 107.0

198.0 14.00 112.0

187.0 15.10 121.0

181.0 15.70 126.0

176.0 16.30 130.0

164.0 17.50 140.0

45 TC kW SDT

221.0 13.90 109.0

215.0 14.50 114.0

204.0 15.60 123.0

198.0 16.10 127.0

192.0 16.70 132.0

179.0 17.90 141.0

50 TC kW SDT

239.0 14.40 111.0

233.0 14.90 116.0

221.0 16.10 125.0

215.0 16.70 129.0

208.0 17.20 134.0

195.0 18.40 143.0

38ARD024

SST (F) Air Temperature Entering Condenser (F) 80 85 95 100 105 115

20 TC kW SDT

184.0 16.20 105.0

179.0 17.00 110.0

170.0 18.50 119.0

165.0 19.40 124.0

160.0 20.20 129.0

148.0 21.70 139.0

25 TC kW SDT

202.0 16.80 107.0

197.0 17.50 112.0

186.0 19.00 121.0

181.0 19.80 126.0

176.0 20.60 131.0

163.0 22.20 140.0

30 TC kW SDT

220.0 17.30 109.0

214.0 18.00 113.0

203.0 19.50 123.0

197.0 20.30 127.0

191.0 21.10 132.0

179.0 22.70 141.0

35 TC kW SDT

239.0 18.00 111.0

233.0 18.60 116.0

220.0 20.10 125.0

214.0 20.80 129.0

208.0 21.60 134.0

194.0 23.20 143.0

40 TC kW SDT

259.0 18.70 113.0

253.0 19.30 118.0

239.0 20.70 127.0

232.0 21.50 131.0

225.0 22.20 136.0

211.0 23.80 145.0

45 TC kW SDT

280.0 19.40 116.0

273.0 20.10 120.0

259.0 21.50 129.0

252.0 22.20 134.0

244.0 22.90 138.0

229.0 24.50 147.0

50 TC kW SDT

302.0 20.20 118.0

295.0 20.90 123.0

280.0 22.30 132.0

272.0 23.00 136.0

264.0 23.70 140.0

247.0 25.20 149.0

LEGEND kW — Compressor Power SDT — Saturated Discharge Temperature at Compressor (F) SST — Saturated Suction Temperature (F) TC — Gross Cooling Capacity (1000 Btuh)

38ARD028 SST (F)

Air Temperature Entering Condenser (F) 80 85 95 100 105 115

25

TC kW SDT

253.2 25.45 109.4

244.6 26.57 113

228.4 26.87 122

202.7 33.11 129.2

186.8 36.61 136.4

179 38.12 140.9

30

TC kW SDT

267 25.7

110.3

258.3 26.72 113.9

240.5 28.625

122

217.7 33.39 129.2

199.4 36.89 137.3

191.5 38.45 141.8

35

TC kW SDT

280.8 25.88 111.2

272 26.87 114.8

252.6 30.38 122

232.7 33.67 129.2

211 37.17 138.2

203.8 38.78 142.7

40

TC kW SDT

309.8 26.36 113

300.7 27.31 116.6

280.2 30.9

123.8

259.2 34.28 131

237.8 37.82 138.2

228 39.545 143.6

45

TC kW SDT

342 26.92 113

330.8 28.39 116.6

318 31.51 125.6

287.4 34.92 134.6

262.2 39.34 140

254.6 40.65 146.3

50

TC kW SDT

371.5 27.52 114.8

363.7 29

118.4

341.2 32.15 127.4

317.8 35.55 132.8

288.8 40.52 141.8

278.7 41.575 147.65

12

Performance data (cont) COMBINATION RATINGS

38ARZ007/40RM007 Temp (F) Air

Entering Condenser

(Edb)

Evaporator Air — Cfm 1800 2400 3000

Evaporator Air — Ewb (F) 57 62 67 72 57 62 67 72 57 62 67 72

80 TC

SHC kW

63.4 63.4 4.40

66.1 58.4 4.45

71.7 49.0 4.55

77.8 39.2 4.66

69.0 69.0 4.50

69.8 67.2 4.52

74.9 56.0 4.60

81.1 43.6 4.72

72.9 72.9 4.57

72.9 72.9 4.57

76.9 62.5 4.64

83.1 47.6 4.76

85 TC

SHC kW

62.5 62.5 4.67

65.1 57.9 4.72

70.5 48.5 4.82

76.6 38.8 4.93

68.0 68.0 4.77

68.7 66.6 4.79

73.6 55.5 4.88

79.7 43.1 4.99

71.9 71.9 4.84

71.9 71.9 4.84

75.6 62.0 4.91

81.7 47.2 5.03

95 TC

SHC kW

60.8 60.8 5.22

62.9 56.8 5.26

68.2 47.5 5.36

74.1 37.9 5.48

66.1 66.1 5.32

66.5 65.2 5.33

71.1 54.6 5.42

77.0 42.2 5.54

69.7 69.7 5.39

69.8 69.8 5.39

73.1 60.9 5.46

78.9 46.2 5.58

100 TC

SHC kW

59.9 59.9 5.53

61.8 56.3 5.56

67.0 47.0 5.67

72.8 37.4 5.79

65.1 65.1 5.63

65.4 64.4 5.63

69.8 54.0 5.73

75.6 41.7 5.85

68.6 68.6 5.70

68.6 68.6 5.70

71.7 60.4 5.76

77.4 45.7 5.89

105 TC

SHC kW

59.0 59.0 5.84

60.7 55.7 5.87

65.7 46.5 5.98

71.4 36.9 6.10

64.0 64.0 5.94

64.2 63.7 5.94

68.5 53.5 6.03

74.1 41.2 6.16

67.5 67.5 6.01

67.5 67.5 6.01

70.3 59.8 6.07

75.9 45.2 6.20

115 TC

SHC kW

57.1 57.1 6.46

58.4 54.6 6.48

63.3 45.5 6.59

68.7 35.9 6.72

61.9 61.9 6.57

61.9 61.9 6.56

65.8 52.4 6.65

71.3 40.2 6.78

65.2 65.2 6.64

65.2 65.2 6.63

67.4 58.7 6.68

72.9 44.2 6.82

38ARZ007/40RM008 Temp (F) Air

Entering Condenser

(Edb)

Evaporator Air — Cfm 2400 3000 3750

Evaporator Air — Ewb (F) 57 62 67 72 57 62 67 72 57 62 67 72

80 TC

SHC kW

68.4 68.4 4.49

69.5 65.8 4.51

74.8 54.8 4.61

81.0 42.9 4.72

73.6 73.6 4.58

73.6 73.6 4.58

77.6 63.1 4.65

83.8 48.1 4.77

77.3 77.3 4.65

77.3 77.3 4.65

79.5 70.4 4.69

85.5 52.9 4.81

85 TC

SHC kW

67.4 67.4 4.76

68.4 65.2 4.78

73.6 54.3 4.88

79.7 42.4 5.00

72.6 72.6 4.86

72.6 72.6 4.86

76.3 62.6 4.93

82.4 47.6 5.05

76.1 76.1 4.92

76.1 76.1 4.92

78.2 69.8 4.96

84.0 52.4 5.08

95 TC

SHC kW

65.5 66.2 64.0 5.32

71.1 53.3 5.42

77.1 41.5 5.54

70.4 70.4 5.40

70.5 70.5 5.40

73.7 61.5 5.47

79.5 46.6 5.59

73.8 73.8 5.47

73.8 73.8 5.47

75.5 68.7 5.51

81.1 51.4 5.62

65.5 5.31

100 TC

SHC kW

64.5 64.5 5.62

65.1 63.3 5.63

69.7 52.8 5.72

75.6 41.0 5.85

69.3 69.3 5.71

69.3 69.3 5.72

72.3 60.9 5.78

78.0 46.1 5.90

72.6 72.6 5.78

72.6 72.6 5.78

74.0 68.0 5.82

79.5 50.9 5.93

105 TC

SHC kW

63.4 63.4 5.93

63.9 62.5 5.94

68.4 52.2 6.03

74.1 40.5 6.16

68.1 68.1 6.03

68.1 68.1 6.03

70.9 60.4 6.08

76.5 45.6 6.21

71.4 71.4 6.10

71.4 71.4 6.10

72.6 67.3 6.12

77.9 50.4 6.24

115 TC

SHC kW

61.4 61.4 6.55

61.6 61.1 6.55

65.8 51.2 6.64

71.2 39.4 6.78

65.9 65.9 6.65

65.8 65.8 6.65

68.0 59.2 6.70

73.4 44.6 6.83

68.9 68.9 6.72

68.9 68.9 6.73

69.7 66.0 6.74

74.8 49.4 6.86

38ARZ008/40RM007 Temp (F) Air

Entering Condenser

(Edb)

Evaporator Air — Cfm 1800 2400 3000

Evaporator Air — Ewb (F) 57 62 67 72 57 62 67 72 57 62 67 72

80 TC

SHC kW

75.3 74.3 5.77

81.2 65.8 5.82

88.5 56.3 5.91

96.1 46.4 6.00

82.5 82.5 5.84

86.4 75.7 5.88

93.6 63.5 5.97

101.0 50.9 6.07

88.0 88.0 5.90

89.9 84.1 5.93

96.8 70.0 6.01

104.0 54.9 6.12

85 TC

SHC kW

74.2 73.4 6.12

79.8 65.2 6.18

87.1 55.6 6.27

94.6 45.8 6.37

81.3 81.3 6.20

84.9 75.0 6.24

92.0 62.8 6.33

99.5 50.2 6.44

86.7 86.7 6.26

88.4 83.3 6.28

95.2 69.4 6.38

103.0 54.3 6.48

95 TC

SHC kW

71.8 71.6 6.83

77.2 63.8 6.89

84.2 54.3 6.98

91.6 44.6 7.10

79.0 79.0 6.91

82.0 73.6 6.95

88.8 61.5 7.05

96.2 49.0 7.17

84.1 84.1 6.99

85.4 81.7 7.00

91.9 68.1 7.10

99.2 53.0 7.22

100 TC

SHC kW

70.6 70.5 7.22

75.7 63.1 7.28

82.6 53.6 7.38

89.9 43.9 7.50

77.7 77.7 7.31

80.4 72.8 7.35

87.1 60.8 7.45

94.4 48.3 7.58

82.7 82.7 7.39

83.8 80.7 7.40

90.0 67.4 7.51

97.3 52.3 7.63

105 TC

SHC kW

69.4 69.4 7.61

74.2 62.4 7.67

81.1 53.0 7.78

88.3 43.3 7.91

76.4 76.4 7.70

78.8 72.0 7.75

85.4 60.1 7.86

92.6 47.7 7.99

81.3 81.3 7.79

82.2 79.8 7.80

88.2 66.7 7.91

95.4 51.7 8.04

115 TC

SHC kW

67.0 67.0 8.39

71.3 60.9 8.45

78.0 51.6 8.59

85.0 41.9 8.73

73.8 73.8 8.49

75.6 70.5 8.54

82.0 58.7 8.66

89.0 46.4 8.80

78.5 78.5 8.59

78.9 77.9 8.60

84.6 65.3 8.71

91.7 50.3 8.86

13

Performance data (cont) 38ARZ008/40RM008 Temp (F) Air

Entering Condenser

(Edb)

Evaporator Air — Cfm 2205 3000 3750

Evaporator Air — Ewb (F) 57 62 67 72 57 62 67 72 57 62 67 72

80 TC

SHC kW

81.7 81.7 5.83

85.9 74.2 5.88

93.2 62.4 5.97

101.0 50.2 6.07

89.0 89.0 5.92

90.8 85.2 5.94

97.5 70.9 6.02

105.0 55.4 6.12

91.6 91.6 5.95

92.6 89.4 5.96

98.8 74.7 6.04

106.0 57.7 6.14

85 TC

SHC kW

80.6 80.6 6.19

84.5 73.5 6.23

91.6 61.7 6.33

99.2 49.6 6.43

87.7 87.7 6.28

89.3 84.5 6.30

95.8 70.2 6.39

103.0 54.8 6.49

90.2 90.2 6.31

91.1 88.4 6.32

97.1 74.1 6.40

105.0 57.1 6.51

95 TC

SHC kW

78.3 78.3 6.90

81.7 72.1 6.95

88.5 60.4 7.05

95.9 48.4 7.17

85.2 85.2 7.00

86.3 82.9 7.02

92.5 69.0 7.11

99.9 53.6 7.23

87.6 87.6 7.04

88.2 86.4 7.05

93.8 72.8 7.13

101.0 55.9 7.25

100 TC 77.0

77.0 7.30

80.1 71.3 7.34

86.9 59.8 7.45

94.2 47.7 7.57

83.7 83.7 7.40

84.7 81.9 7.42

90.7 68.3 7.52

98.0 52.9 7.64

86.1 86.1 7.44

86.6 85.2 7.45

91.9 72.1 7.54

99.1 55.2 7.66

SHC kW

105 TC

SHC kW

75.7 75.7 7.69

78.6 70.6 7.74

85.2 59.1 7.86

92.4 47.0 7.98

82.3 82.3 7.80

83.0 80.9 7.82

88.9 67.6 7.92

96.1 52.2 8.05

84.6 84.6 7.84

85.0 83.9 7.85

90.1 71.4 7.94

97.2 54.6 8.07

115 TC

SHC kW

73.2 73.2 8.48

75.4 69.0 8.53

81.9 57.7 8.67

88.8 45.7 8.79

79.5 79.5 8.61

79.8 79.0 8.61

85.3 66.1 8.73

92.3 50.9 8.87

81.7 81.7 8.65

81.8 81.4 8.65

86.4 70.0 8.75

93.3 53.2 8.89

38ARZ008/40RM012 Temp (F) Air

Entering Condenser

(Edb)

Evaporator Air — Cfm 3000 4000 5000

Evaporator Air — Ewb (F) 57 62 67 72 57 62 67 72 57 62 67 72

80 TC

SHC kW

91.6 91.6 5.95

93.2 87.9 5.97

100.0 73.0 6.06

108.0 57.0 6.16

98.4 98.4 6.04

98.4 98.4 6.04

104.0 83.9 6.10

111.0 63.6 6.21

103.0 103.0 6.10

103.0 103.0 6.10

106.0 93.5 6.14

113.0 69.7 6.24

85 TC

SHC kW

90.2 90.2 6.31

91.6 87.0 6.33

98.2 72.3 6.42

106.0 56.4 6.53

96.9 96.9 6.40

96.9 96.9 6.40

102.0 83.1 6.47

109.0 63.0 6.58

101.0 101.0 6.47

101.0 101.0 6.46

104.0 92.6 6.50

111.0 69.1 6.61

95 TC

SHC kW

87.5 87.5 7.03

88.5 85.3 7.05

94.7 70.9 7.14

102.0 55.0 7.27

93.9 93.9 7.13

93.9 93.9 7.13

98.1 81.7 7.20

105.0 61.7 7.32

98.3 98.3 7.20

98.2 98.2 7.20

100.0 91.0 7.24

107.0 67.8 7.35

100 TC

SHC kW

86.0 86.0 7.44

86.8 84.3 7.45

92.8 70.2 7.55

100.0 54.3 7.68

92.3 92.3 7.54

92.3 92.3 7.54

96.1 81.0 7.61

103.0 61.0 7.73

96.5 96.5 7.61

96.5 96.5 7.61

98.4 90.1 7.65

105.0 67.1 7.76

105 TC

SHC kW

84.6 84.6 7.84

85.1 83.3 7.86

91.0 69.5 7.96

98.3 53.6 8.09

90.7 90.7 7.95

90.7 90.7 7.95

94.2 80.2 8.02

101.0 60.3 8.14

94.8 94.8 8.03

94.8 94.8 8.03

96.4 89.2 8.05

103.0 66.4 8.17

115 TC

SHC kW

81.6 81.6 8.65

81.8 81.3 8.66

87.3 68.1 8.77

94.3 52.2 8.9

87.4 87.4 8.77

87.4 87.4 8.77

90.3 78.8 8.83

97.1 58.9 8.97

91.3 91.3 8.85

91.4 91.4 8.85

92.4 87.4 8.87

98.7 65.1 9.00

38ARZ012/40RM012 Temp (F) Air

Entering Condenser

(Edb)

Evaporator Air — Cfm 3000 4000 5000

Evaporator Air — Ewb (F) 57 62 67 72 57 62 67 72 57 62 67 72

80 TC

SHC kW

110.0 110.0 8.19

115.0 99.4 8.32

124.0 83.3 8.55

134.0 66.8 8.82

119.0 119.0 8.41

121.0 114.0 8.48

130.0 94.6 8.70

139.0 73.6 8.96

126.0 126.0 8.59

126.0 125.0 8.60

133.0 105.0 8.80

143.0 79.9 9.06

85 TC

SHC kW

108.0 108.0 8.57

113.0 98.4 8.70

122.0 82.4 8.93

132.0 66.0 9.20

117.0 117.0 8.80

119.0 113.0 8.85

128.0 93.7 9.08

137.0 72.8 9.35

124.0 124.0 8.97

124.0 123.0 8.98

131.0 104.0 9.17

140.0 79.0 9.44

95 TC

SHC kW

105.0 105.0 9.34

110.0 96.6 9.45

118.0 80.7 9.69

127.0 64.3 9.96

114.0 114.0 9.57

115.0 111.0 9.61

123.0 91.9 9.83

132.0 71.1 10.10

120.0 120.0 9.73

120.0 120.0 9.74

126.0 102.0 9.93

135.0 77.3 10.20

100 TC

SHC kW

104.0 104.0 9.76

107.0 95.5 9.86

116.0 79.7 10.10

125.0 63.4 10.40

112.0 112.0 9.98

113.0 109.0 10.00

121.0 90.9 10.20

130.0 70.2 10.50

118.0 118.0 10.10

118.0 118.0 10.10

124.0 101.0 10.30

132.0 76.4 10.60

105 TC

SHC kW

102.0 102.0 10.20

105.0 94.4 10.30

114.0 78.7 10.5

122.0 62.4 10.80

110.0 110.0 10.40

111.0 108.0 10.40

118.0 89.9 10.60

127.0 69.2 10.90

116.0 116.0 10.60

116.0 116.0 10.60

121.0 100.0 10.70

130.0 75.5 11.00

115 TC

SHC kW

98.4 98.4 11.00

101.0 92.2 11.10

109.0 76.7 11.30

117.0 60.5 11.60

106.0 106.0 11.20

106.0 105.0 11.20

113.0 87.8 11.40

122.0 67.3 11.70

111.0 111.0 11.40

111.0 111.0 11.40

116.0 97.9 11.50

124.0 73.6 11.80

14

Performance data (cont) 38ARZ012/40RM014 Temp (F) Air

Entering Condenser

(Edb)

Evaporator Air — Cfm 3750 5000 6250

Evaporator Air — Ewb (F) 57 62 67 72 57 62 67 72 57 62 67 72

80 TC

SHC kW

119.0 119.0 8.42

123.0 112.0 8.51

132.0 93.2 8.77

142.0 73.4 9.05

128.0 128.0 8.66

129.0 127.0 8.68

137.0 106.0 8.90

147.0 81.4 9.18

135.0 135.0 8.84

135.0 135.0 8.84

140.0 118.0 8.99

150.0 88.6 9.27

85 TC

SHC kW

118.0 118.0 8.80

121.0 111.0 8.89

130.0 92.3 9.14

140.0 72.5 9.43

126.0 126.0 9.05

127.0 126.0 9.06

135.0 105.0 9.28

144.0 80.5 9.56

133.0 133.0 9.22

133.0 133.0 9.22

138.0 117.0 9.37

147.0 87.8 9.65

95 TC

SHC kW

114.0 114.0 9.57

116.0 109.0 9.64

125.0 90.4 9.89

135.0 70.7 10.20

122.0 122.0 9.81

123.0 122.0 9.81

130.0 103.0 10.00

139.0 78.7 10.30

128.0 128.0 9.99

128.0 128.0 9.99

133.0 115.0 10.10

142.0 86.0 10.40

100 TC

SHC kW

112.0 112.0 9.98

114.0 108.0 10.00

123.0 89.3 10.30

132.0 69.7 10.60

120.0 120.0 10.20

120.0 120.0 10.20

127.0 102.0 10.40

136.0 77.7 10.70

126.0 126.0 10.40

126.0 126.0 10.40

130.0 114.0 10.50

139.0 85.0 10.80

105 TC

SHC kW

110.0 110.0 10.40

112.0 106.0 10.40

120.0 88.2 10.70

129.0 68.7 11.00

118.0 118.0 10.60

118.0 118.0 10.60

124.0 101.0 10.80

133.0 76.7 11.10

123.0 123.0 10.80

123.0 123.0 10.80

127.0 113.0 10.90

136.0 84.0 11.20

115 TC

SHC kW

106.0 106.0 11.20

107.0 104.0 11.20

115.0 86.1 11.50

124.0 66.6 11.80

114.0 114.0 11.40

113.0 113.0 11.40

119.0 99.1 11.60

127.0 74.6 11.90

119.0 119.0 11.60

119.0 119.0 11.60

121.0 110.0 11.70

130.0 81.9 12.00

38ARD014/40RM012 Temp (F) Air

Entering Condenser

(Edb)

Evaporator Air — Cfm 3000 4000 5000

Evaporator Air — Ewb (F) 57 62 67 72 57 62 67 72 57 62 67 72

80 TC

SHC kW

119.0 119.0 9.09

128.0 106.0 9.15

140.0 90.4 9.18

153.0 74.3 9.23

131.0 131.0 9.15

136.0 122.0 9.16

148.0 103.0 9.21

161.0 82.0 9.30

140.0 140.0 9.19

142.0 136.0 9.19

153.0 114.0 9.25

166.0 89.0 9.33

85 TC

SHC kW

118.0 118.0 9.66

126.0 105.0 9.72

138.0 89.5 9.75

151.0 73.4 9.81

130.0 130.0 9.72

134.0 121.0 9.72

146.0 102.0 9.77

159.0 81.2 9.87

138.0 138.0 9.75

140.0 135.0 9.75

151.0 113.0 9.80

164.0 88.1 9.89

95 TC 115.0

115.0 10.90

122.0 103.0 10.90

134.0 146.0 71.7 11.00

126.0 126.0 10.90

130.0 119.0 10.90

141.0 99.9 11.00

154.0 79.3 11.10

134.0 134.0 11.00

136.0 132.0 11.00

146.0 111.0 11.00

158.0 86.3 11.10

SHC 87.7 kW 11.00

100 TC

SHC kW

113.0 113.0 11.60

120.0 102.0 11.60

131.0 86.7 11.60

144.0 70.8 11.70

124.0 124.0 11.60

128.0 118.0 11.60

139.0 98.9 11.60

151.0 78.4 11.70

132.0 132.0 11.60

133.0 131.0 11.60

143.0 110.0 11.70

156.0 85.3 11.80

105 TC

SHC kW

111.0 111.0 12.20

118.0 101.0 12.30

129.0 85.7 12.30

141.0 69.8 12.40

122.0 122.0 12.30

125.0 117.0 12.30

136.0 97.9 12.30

148.0 77.5 12.40

130.0 130.0 12.30

131.0 129.0 12.30

140.0 109.0 12.40

153.0 84.3 12.40

115 TC

SHC kW

108.0 108.0 13.70

114.0 99.0 13.70

124.0 83.7 13.80

136.0 67.8 13.90

118.0 118.0 13.70

121.0 114.0 13.80

131.0 95.8 13.80

143.0 75.4 13.90

126.0 126.0 13.80

126.0 126.0 13.80

135.0 107.0 13.80

147.0 82.3 13.90

38ARD014/40RM014 Temp (F) Air

Entering Condenser

(Edb)

Evaporator Air — Cfm 3750 5000 6250

Evaporator Air — Ewb (F) 57 62 67 72 57 62 67 72 57 62 67 72

80 TC

SHC kW

130.0 130.0 9.14

137.0 120.0 9.18

150.0 101.0 9.22

163.0 81.6 9.32

143.0 143.0 9.20

145.0 138.0 9.20

157.0 115.0 9.27

171.0 90.5 9.38

151.0 151.0 9.24

151.0 151.0 9.23

162.0 128.0 9.30

176.0 98.5 9.43

85 TC

SHC kW

129.0 129.0 9.70

135.0 119.0 9.73

147.0 100.0 9.78

161.0 80.7 9.88

141.0 141.0 9.76

143.0 137.0 9.76

154.0 114.0 9.82

168.0 89.5 9.93

149.0 149.0 9.79

149.0 149.0 9.79

159.0 127.0 9.85

173.0 97.5 9.98

95 TC

SHC kW

125.0 125.0 10.90

131.0 117.0 11.00

143.0 98.0 11.00

156.0 78.7 11.10

137.0 137.0 11.00

138.0 134.0 11.00

149.0 112.0 11.00

162.0 87.5 11.10

145.0 145.0 11.00

145.0 145.0 11.00

154.0 125.0 11.10

167.0 95.6 11.20

100 TC

SHC kW

123.0 123.0 11.60

128.0 115.0 11.60

140.0 97.0 11.70

153.0 77.7 11.70

135.0 135.0 11.60

136.0 132.0 11.70

146.0 111.0 11.70

160.0 86.5 11.80

143.0 143.0 11.70

143.0 143.0 11.70

151.0 124.0 11.70

164.0 94.5 11.80

105 TC

SHC kW

122.0 122.0 12.30

126.0 114.0 12.30

137.0 95.9 12.30

150.0 76.7 12.40

132.0 132.0 12.30

133.0 131.0 12.30

144.0 110.0 12.40

157.0 85.4 12.50

140.0 140.0 12.30

140.0 140.0 12.40

148.0 123.0 12.40

161.0 93.5 12.50

115 TC

SHC kW

118.0 118.0 13.80

121.0 112.0 13.80

132.0 93.6 13.80

144.0 74.5 13.90

128.0 128.0 13.80

128.0 128.0 13.80

138.0 108.0 13.90

150.0 83.3 14.00

135.0 135.0 13.80

135.0 135.0 13.80

142.0 120.0 13.90

154.0 91.3 14.00

15

Performance data (cont) 38ARD014/40RM016 Temp (F) Air

Entering Condenser

(Edb)

Evaporator Air — Cfm 4500 6000 7500

Evaporator Air — Ewb (F) 57 62 67 72 57 62 67 72 57 62 67 72

80 TC

SHC kW

143.0 143.0 9.19

147.0 136.0 9.22

160.0 113.0 9.28

174.0 89.9 9.42

155.0 155.0 9.27

156.0 155.0 9.26

166.0 130.0 9.34

180.0 100.0 9.49

164.0 164.0 9.31

164.0 164.0 9.33

171.0 146.0 9.37

185.0 110.0 9.54

85 TC

SHC kW

141.0 141.0 9.75

145.0 134.0 9.77

157.0 112.0 9.85

171.0 89.0 9.98

153.0 153.0 9.82

153.0 153.0 9.82

164.0 129.0 9.90

178.0 99.5 10.00

162.0 162.0 9.87

162.0 162.0 9.89

168.0 144.0 9.93

182.0 109.0 10.10

95 TC

SHC kW

137.0 137.0 11.00

140.0 132.0 11.00

152.0 110.0 11.10

165.0 86.9 11.20

149.0 149.0 11.00

149.0 149.0 11.00

158.0 127.0 11.10

172.0 97.4 11.20

157.0 157.0 11.10

157.0 157.0 11.10

162.0 142.0 11.10

175.0 107.0 11.30

100 TC

SHC kW

135.0 135.0 11.60

138.0 131.0 11.60

149.0 109.0 11.70

162.0 85.8 11.80

146.0 146.0 11.70

146.0 146.0 11.70

155.0 126.0 11.80

168.0 96.3 11.90

154.0 154.0 11.70

154.0 154.0 11.80

159.0 141.0 11.80

172.0 106.0 11.90

105 TC

SHC kW

133.0 133.0 12.30

135.0 129.0 12.30

146.0 108.0 12.40

159.0 84.7 12.50

144.0 144.0 12.40

144.0 144.0 12.40

152.0 125.0 12.50

165.0 95.2 12.60

152.0 152.0 12.40

152.0 152.0 12.50

156.0 139.0 12.50

169.0 105.0 12.60

115 TC

SHC kW

129.0 129.0 13.80

130.0 126.0 13.80

140.0 106.0 13.90

153.0 82.5 14.00

139.0 139.0 13.90

139.0 139.0 13.90

146.0 122.0 13.90

158.0 92.9 14.10

146.0 146.0 13.90

146.0 146.0 13.90

150.0 137.0 13.90

162.0 103.0 14.10

38ARD016/40RM014 Temp (F) Air

Entering Condenser

(Edb)

Evaporator Air — Cfm 3750 5000 6250

Evaporator Air — Ewb (F) 57 62 67 72 57 62 67 72 57 62 67 72

80 TC

SHC kW

154.0 152.0 12.40

166.0 134.0 12.60

181.0 115.0 13.00

196.0 94.7 13.30

168.0 168.0 12.70

176.0 154.0 12.90

191.0 129.0 13.20

206.0 104.0 13.60

179.0 179.0 12.90

183.0 171.0 13.00

197.0 143.0 13.40

213.0 112.0 13.70

85 TC

SHC kW

152.0 150.0 12.90

163.0 133.0 13.20

178.0 113.0 13.50

193.0 93.4 13.90

166.0 166.0 13.20

173.0 153.0 13.40

188.0 128.0 13.80

203.0 102.0 14.20

176.0 176.0 13.50

180.0 169.0 13.60

194.0 210.0 111.0 14.30

141.0 13.90

95 TC

SHC kW

147.0 146.0 14.10

157.0 130.0 14.40

171.0 111.0 14.70

186.0 90.6 15.10

160.0 160.0 14.40

167.0 149.0 14.60

180.0 125.0 15.00

196.0 99.7 15.40

171.0 171.0 14.70

173.0 166.0 14.80

187.0 138.0 15.10

202.0 108.0 15.50

100 TC

SHC kW

144.0 144.0 14.80

154.0 128.0 15.00

168.0 109.0 15.30

182.0 158.0 158.0 15.10

163.0 148.0 15.20

177.0 123.0 15.60

191.0 98.1 16.00

167.0 167.0 15.30

170.0 163.0 15.40

182.0 137.0 15.70

197.0 106.0 16.20

89.1 15.70

105 TC

SHC kW

141.0 141.0 15.40

151.0 127.0 15.60

164.0 107.0 16.00

179.0 87.6 16.40

155.0 155.0 15.70

160.0 146.0 15.80

173.0 122.0 16.20

187.0 96.5 16.60

164.0 164.0 16.00

166.0 161.0 16.00

178.0 135.0 16.40

193.0 105.0 16.80

115 TC

SHC kW

136.0 136.0 16.80

144.0 124.0 16.90

157.0 104.0 17.30

170.0 84.4 17.70

149.0 149.0 17.10

152.0 142.0 17.20

165.0 118.0 17.50

178.0 93.3 17.90

158.0 158.0 17.30

159.0 156.0 17.30

170.0 132.0 17.70

183.0 101.0 18.10

38ARD016/40RM016 Temp (F) Air

Entering Condenser

(Edb)

Evaporator Air — Cfm 4500 6000 7500

Evaporator Air — Ewb (F) 57 62 67 72 57 62 67 72 57 62 67 72

80 TC

SHC kW

169.0 169.0 12.70

180.0 152.0 12.90

195.0 128.0 13.30

211.0 104.0 13.70

185.0 185.0 13.10

190.0 175.0 13.20

204.0 146.0 13.50

221.0 115.0 13.90

196.0 196.0 13.30

197.0 193.0 13.30

211.0 162.0 13.70

227.0 125.0 14.10

85 TC

SHC kW

167.0 167.0 13.30

177.0 151.0 13.50

192.0 127.0 13.90

208.0 103.0 14.30

182.0 182.0 13.60

186.0 173.0 13.70

201.0 144.0 14.10

217.0 113.0 14.50

193.0 193.0 13.90

194.0 191.0 13.90

207.0 160.0 14.30

223.0 123.0 14.70

95 TC

SHC kW

161.0 161.0 14.50

170.0 147.0 14.70

184.0 124.0 15.10

200.0 99.8 15.50

176.0 176.0 14.80

179.0 169.0 14.90

193.0 141.0 15.30

209.0 111.0 15.70

186.0 186.0 15.10

187.0 186.0 15.10

199.0 157.0 15.50

215.0 120.0 15.90

100 TC 159.0

159.0 15.10

166.0 145.0 15.30

181.0 122.0 15.70

196.0 98.2 16.10

173.0 173.0 15.50

176.0 167.0 15.50

189.0 139.0 15.90

204.0 109.0 16.40

183.0 183.0 15.70

183.0 183.0 15.70

194.0 155.0 16.10

210.0 119.0 16.50

SHC kW

105 TC

SHC kW

156.0 156.0 15.70

163.0 144.0 15.90

177.0 120.0 16.30

192.0 96.6 16.80

169.0 169.0 16.10

172.0 165.0 16.20

185.0 138.0 16.50

200.0 107.0 17.00

179.0 179.0 16.40

179.0 179.0 16.40

190.0 153.0 16.70

205.0 117.0 17.20

115 TC

SHC kW

150.0 150.0 17.10

155.0 140.0 17.20

168.0 117.0 17.60

183.0 93.2 18.10

163.0 163.0 17.50

164.0 160.0 17.50

175.0 134.0 17.80

190.0 104.0 18.30

172.0 172.0 17.70

172.0 172.0 17.70

180.0 150.0 18.00

195.0 114.0 18.50

16

Performance data (cont) 38ARD016/40RM024 Temp (F) Air

Entering Condenser

(Edb)

Evaporator Air — Cfm 6,000 8,000 10,000

Evaporator Air — Ewb (F) 57 62 67 72 57 62 67 72 57 62 67 72

80 TC

SHC kW

190.0 190.0 13.20

194.0 181.0 13.30

209.0 150.0 13.60

226.0 118.0 14.00

205.0 205.0 13.50

205.0 204.0 13.50

217.0 173.0 13.80

233.0 132.0 14.20

215.0 215.0 13.80

215.0 215.0 13.80

222.0 193.0 14.00

238.0 145.0 14.40

85 TC

SHC kW

187.0 187.0 13.80

191.0 179.0 13.90

205.0 149.0 14.20

222.0 117.0 14.60

202.0 202.0 14.10

202.0 201.0 14.10

213.0 171.0 14.40

229.0 131.0 14.80

211.0 211.0 14.40

211.0 211.0 14.40

218.0 191.0 14.50

234.0 144.0 15.00

95 TC

SHC kW

181.0 181.0 15.00

184.0 175.0 15.00

197.0 146.0 15.40

213.0 114.0 15.90

195.0 195.0 15.30

195.0 195.0 15.30

204.0 168.0 15.60

220.0 128.0 16.10

204.0 204.0 15.60

204.0 204.0 15.60

209.0 187.0 15.80

225.0 141.0 16.20

100 TC

SHC kW

178.0 178.0 15.60

180.0 173.0 15.70

193.0 144.0 16.00

209.0 112.0 16.50

191.0 191.0 16.00

191.0 191.0 16.00

200.0 166.0 16.20

216.0 126.0 16.70

200.0 200.0 16.20

200.0 200.0 16.20

205.0 185.0 16.40

220.0 139.0 16.80

105 TC

SHC kW

174.0 174.0 16.20

176.0 171.0 16.30

188.0 142.0 16.60

204.0 110.0 17.10

187.0 187.0 16.60

187.0 187.0 16.60

195.0 164.0 16.90

210.0 124.0 17.30

196.0 196.0 16.90

196.0 196.0 16.90

200.0 183.0 17.00

215.0 137.0 17.50

115 TC

SHC kW

167.0 167.0 17.60

168.0 166.0 17.60

179.0 138.0 18.00

194.0 107.0 18.40

179.0 179.0 17.90

179.0 179.0 17.90

185.0 160.0 18.10

200.0 121.0 18.60

187.0 187.0 18.20

187.0 187.0 18.20

190.0 178.0 18.30

203.0 133.0 18.70

38ARD024/40RM016 Temp (F) Air

Entering Condenser

(Edb)

Evaporator Air — Cfm 4500 6000 7500

Evaporator Air — Ewb (F) 57 62 67 72 57 62 67 72 57 62 67 72

80 TC

SHC kW

196.0 190.0 16.70

211.0 168.0 17.10

229.0 144.0 17.70

248.0 119.0 18.30

212.0 212.0 17.10

224.0 192.0 17.50

242.0 161.0 18.10

261.0 130.0 18.80

226.0 226.0 17.60

233.0 213.0 17.80

250.0 178.0 18.40

270.0 140.0 19.10

85 TC

SHC kW

193.0 188.0 17.40

207.0 166.0 17.80

225.0 142.0 18.40

244.0 117.0 19.00

209.0 209.0 17.90

220.0 190.0 18.20

238.0 160.0 18.80

257.0 128.0 19.50

223.0 223.0 18.30

229.0 211.0 18.50

246.0 176.0 19.10

265.0 138.0 19.80

95 TC

SHC kW

187.0 184.0 19.00

200.0 162.0 19.40

217.0 138.0 20.00

235.0 114.0 20.60

203.0 203.0 19.50

212.0 186.0 19.80

229.0 156.0 20.40

247.0 125.0 21.10

216.0 216.0 19.90

220.0 207.0 20.10

236.0 172.0 20.70

255.0 135.0 21.40

100 TC

SHC kW

184.0 182.0 19.90

197.0 161.0 20.30

213.0 136.0 20.80

231.0 112.0 21.40

200.0 200.0 20.40

208.0 184.0 20.60

224.0 154.0 21.20

242.0 123.0 21.90

212.0 212.0 20.80

216.0 204.0 20.90

231.0 170.0 21.50

249.0 133.0 22.20

105 TC

SHC kW

180.0 179.0 20.80

193.0 159.0 21.10

209.0 135.0 21.70

226.0 110.0 22.30

196.0 196.0 21.20

204.0 182.0 21.50

220.0 152.0 22.00

237.0 121.0 22.70

208.0 208.0 21.60

211.0 202.0 21.70

226.0 168.0 22.30

244.0 131.0 23.00

115 TC

SHC kW

173.0 173.0 22.60

185.0 155.0 22.90

200.0 131.0 23.50

216.0 106.0 24.00

189.0 189.0 23.10

195.0 178.0 23.30

210.0 148.0 23.80

226.0 117.0 24.40

200.0 200.0 23.50

202.0 197.0 23.50

216.0 164.0 24.00

233.0 127.0 24.70

38ARD024/40RM024 Temp (F) Air

Entering Condenser

(Edb)

Evaporator Air — Cfm 6,000 8,000 10,000

Evaporator Air — Ewb (F) 57 62 67 72 57 62 67 72 57 62 67 72

80 TC

SHC kW

219.0 219.0 17.30

229.0 199.0 17.70

248.0 167.0 18.30

267.0 134.0 19.00

237.0 237.0 17.90

241.0 228.0 18.10

259.0 190.0 18.70

278.0 148.0 19.40

250.0 250.0 18.40

251.0 250.0 18.40

265.0 211.0 18.90

285.0 161.0 19.60

85 TC

SHC kW

216.0 216.0 18.10

226.0 197.0 18.40

243.0 165.0 19.00

263.0 132.0 19.70

234.0 234.0 18.70

237.0 226.0 18.80

254.0 188.0 19.40

273.0 146.0 20.10

246.0 246.0 19.10

247.0 246.0 19.10

261.0 209.0 19.70

280.0 159.0 20.40

95 TC

SHC kW

209.0 209.0 19.70

217.0 192.0 20.00

234.0 161.0 20.60

253.0 128.0 21.30

226.0 226.0 20.30

228.0 221.0 20.40

244.0 184.0 20.90

263.0 142.0 21.70

238.0 238.0 20.70

238.0 238.0 20.70

250.0 205.0 21.20

269.0 155.0 21.90

100 TC

SHC kW

206.0 206.0 20.60

213.0 190.0 20.80

230.0 159.0 21.40

248.0 126.0 22.10

222.0 222.0 21.10

224.0 218.0 21.20

239.0 182.0 21.70

257.0 140.0 22.50

234.0 234.0 21.50

234.0 234.0 21.50

245.0 202.0 22.00

263.0 153.0 22.70

105 TC

SHC kW

202.0 202.0 21.40

209.0 188.0 21.70

225.0 157.0 22.20

242.0 124.0 22.90

218.0 218.0 22.00

219.0 215.0 22.00

233.0 180.0 22.60

251.0 138.0 23.30

229.0 229.0 22.40

229.0 229.0 22.40

239.0 200.0 22.80

257.0 151.0 23.50

115 TC

SHC kW

195.0 195.0 23.30

200.0 184.0 23.40

215.0 153.0 24.00

232.0 120.0 24.60

210.0 210.0 23.80

210.0 209.0 23.80

223.0 175.0 24.30

239.0 134.0 25.00

220.0 220.0 24.20

220.0 220.0 24.20

228.0 196.0 24.50

244.0 147.0 25.20

38ARD024/40RM028 Temp (F) Air

Entering Condenser

(Edb)

Evaporator Air — Cfm 7,500 10,000 12,500

Evaporator Air — Ewb (F) 57 62 67 72 57 62 67 72 57 62 67 72

80 TC

SHC kW

236.0 236.0 17.90

242.0 223.0 18.10

260.0 185.0 18.70

280.0 146.0 19.50

254.0 254.0 18.50

254.0 252.0 18.50

269.0 212.0 19.10

290.0 162.0 19.80

266.0 266.0 18.90

266.0 266.0 18.90

276.0 236.0 19.30

296.0 178.0 20.00

85 TC

SHC kW

233.0 233.0 18.70

238.0 221.0 18.80

256.0 184.0 19.50

275.0 144.0 20.20

250.0 250.0 19.30

250.0 249.0 19.30

265.0 210.0 19.80

285.0 161.0 20.60

262.0 262.0 19.70

262.0 262.0 19.70

271.0 234.0 20.00

290.0 176.0 20.80

95 TC

SHC kW

225.0 225.0 20.30

229.0 216.0 20.40

246.0 179.0 21.00

265.0 140.0 21.80

242.0 242.0 20.90

242.0 242.0 20.90

255.0 206.0 21.40

273.0 157.0 22.10

253.0 253.0 21.30

253.0 253.0 21.30

260.0 230.0 21.60

279.0 172.0 22.30

100 TC

SHC kW

221.0 221.0 21.10

225.0 214.0 21.20

241.0 178.0 21.80

260.0 138.0 22.50

237.0 237.0 21.70

237.0 237.0 21.70

249.0 204.0 22.10

268.0 155.0 22.90

248.0 248.0 22.10

248.0 248.0 22.10

255.0 227.0 22.40

273.0 170.0 23.10

105 TC

SHC kW

217.0 217.0 22.00

220.0 211.0 22.10

236.0 175.0 22.60

254.0 136.0 23.40

233.0 233.0 22.50

233.0 233.0 22.50

243.0 202.0 23.00

262.0 153.0 23.70

243.0 243.0 22.90

243.0 243.0 22.90

249.0 225.0 23.20

266.0 168.0 23.90

115 TC

SHC kW

209.0 209.0 23.80

211.0 206.0 23.80

225.0 171.0 24.40

242.0 132.0 25.10

223.0 223.0 24.30

223.0 223.0 24.30

232.0 197.0 24.60

249.0 148.0 25.40

233.0 233.0 24.70

233.0 233.0 24.70

237.0 219.0 24.90

253.0 164.0 25.60

38ARD028/40RM028

Temp (F) Air Entering Condenser

(Edb)

Evaporator Air - CFM 7,500 8,000 9,000 10,000 12,500

Evaporator Air - EWB (F) 62 67 72 62 67 72 62 67 72 62 67 72 62 67 72

80 TC

SHC kW

302 256 26.7

322 213 27.5

347 166 28.6

305 264 26.9

323 220 27.7

348 169 28.8

311 271 27.2

327 233 27.9

351 177 28.9

318 279 27.6

331 246 28.1

355 185 29.0

334 293 28.4

347 259 28.9

372 195 29.8

85 TC

SHC kW

296 253 27.7

317 211 28.6

341 164 29.7

299 260 27.9

318 219 28.8

342 168 29.9

306 267 28.3

321 231 29.0

345 176 30.0

314 275 28.6

325 244 29.2

349 184 30.2

329 289 29.5

341 256 30.0

366 193 31.1

95 TC

SHC kW

285 248 30.0

304 207 30.9

328 159 32.0

288 253 30.2

305 214 31.1

328 163 32.2

295 259 30.6

309 226 31.2

331 171 32.3

302 265 30.9

312 239 31.3

335 179 32.5

317 278 31.9

328 251 32.2

352 188 33.5

100 TC

SHC kW

280 243 31.3

297 204 32.1

320 158 33.1

284 249 31.5

298 211 32.2

321 162 33.2

290 254 31.8

301 224 32.3

324 170 33.4

296 260 32.2

305 236 32.5

328 178 33.6

311 273 33.1

320 248 33.5

344 187 34.6

105 TC

SHC kW

274 239 32.5

290 202 33.2

313 155 34.3

278 244 32.7

291 209 33.4

314 159 34.5

284 249 33.0

294 221 33.6

316 167 34.6

291 255 33.4

298 234 33.8

319 175 34.8

305 268 34.4

313 246 34.8

335 184 35.9

115 TC

SHC kW

268 235 35.1

283 189 35.8

304 150 36.8

272 239 35.3

284 196 35.9

304 154 36.9

278 244 35.6

287 207 36.0

307 162 37.1

284 249 35.9

289 218 36.2

310 170 37.3

298 261 36.9

304 229 37.3

325 179 38.4

122 TC

SHC kW

259 229 37.8

271 186 38.4

291 148 39.4

263 231 38.2

272 190 38.5

291 152 39.6

268 235 38.4

275 204 38.7

294 159 39.7

273 240 38.7

278 214 38.9

297 167 39.8

287 252 39.9

292 225 40.0

311 175 41.0

38ARD028/40RM034

Temp (F) Air Entering

Condenser (Edb)

Evaporator Air - CFM 9,000 10,000 12,000 15,000

Evaporator Air - EWB (F) 62 67 72 62 67 72 62 67 72 62 67 72

80 TC

SHC kW

319 286 27.7

340 238 28.6

367 185 29.7

334 313 28.4

351 269 29.1

376 204 30.1

347 342 28.8

361 303 29.4

387 228 30.3

357 357 29.7

372 316 30.2

399 238 31.2

85 TC

SHC kW

313 282 28.8

335 236 29.7

360 184 30.8

329 309 29.5

344 267 30.2

370 203 31.3

342 338 29.9

355 300 30.5

381 226 31.6

353 353 30.8

365 313 31.4

393 236 32.5

95 TC

SHC kW

301 275 31.2

321 231 32.1

346 178 33.2

316 298 31.8

333 263 32.5

355 197 33.7

330 326 32.3

341 294 32.7

366 220 34.0

340 340 33.3

351 306 33.7

377 230 35.0

100 TC

SHC kW

296 271 32.5

314 228 33.3

338 177 34.4

311 293 33.1

323 258 33.7

348 196 34.8

324 320 33.6

333 290 34.0

358 219 35.1

334 334 34.6

343 303 35.0

369 228 36.1

105 TC

SHC kW

290 267 33.8

306 225 34.5

331 174 35.6

305 288 34.4

316 255 35.0

339 193 36.1

318 313 34.9

325 287 35.3

349 216 36.4

327 327 35.9

335 300 36.3

359 225 37.5

115 TC

SHC kW

283 263 36.5

299 211 37.2

321 168 38.2

298 281 37.1

307 239 37.6

329 187 38.7

310 306 37.5

316 268 37.8

338 209 39.0

319 319 38.6

326 280 39.0

348 218 40.1

122 TC

SHC kW

273 256 39.3

287 208 39.9

308 165 41.0

287 271 40.0

295 235 40.3

315 184 41.3

298 294 40.4

303 263 40.6

324 205 41.5

307 307 41.6

312 275 41.8

334 214 42.8

Performance data (cont)

17

UNIT SIZE 38AR

NOMINAL VOLTAGE V-Ph-Hz

VOLTAGE RANGE* COMPRESSOR 1 COMPRESSOR 2 FAN MOTORS

(Qty 2) POWER SUPPLY

MIN MAX RLA LRA RLA LRA FLA (ea)

LRA (ea) MCA MOCP

Z007

208/230-3-60 187 254 22.4 170 -- -- 0.9 1.6 29.125 51.3 460-3-60 418 506 9.51 80 -- -- 0.5 0.9 12.5 20 380-3-60 342 418 9.51 80 -- -- 0.9 1.6 13 20 400-3-50 360 440 9.43 80 -- -- 0.5 0.9 12.4 20

Z008

208/230-3-60 187 254 25.6 190 -- -- 1.5 3.1 33.9 55 460-3-60 418 506 13.5 95 -- -- 0.8 1.6 17.9 30 380-3-60 342 418 16 135 -- -- 1.5 3.1 21.9 30 400-3-50 360 440 13.5 95 -- -- 0.8 1.6 17.9 30

Z012

208/230-3-60 187 254 35.7 237 -- -- 1.5 3.1 46.5 80 460-3-60 418 506 20.7 130 -- -- 0.8 1.6 26.9 45 380-3-60 342 418 21.4 160 -- -- 1.5 3.1 28.6 45 400-3-50 360 440 20.7 130 -- -- 0.8 1.6 26.9 45

D014

208/230-3-60 187 254 22.4 170 22.4 170 3.6 7.5 65 70 460-3-60 418 506 9.51 80 9.51 80 1.9 -- 28.5 35 380-3-60 342 418 9.51 80 9.51 80 3.6 7.5 32.8 35 400-3-50 360 440 9.43 80 9.43 80 1.7 -- 27.8 30

D016

208/230-3-60 187 254 25.6 190 25.6 190 3.6 7.5 73 80 460-3-60 418 506 13.5 95 13.5 95 1.9 -- 38.5 45 380-3-60 342 418 16 135 16 135 3.6 7.5 49 55 400-3-50 360 440 13.5 95 13.5 95 1.7 -- 38 45

D024

208/230-3-60 187 254 35.7 237 35.7 237 3.6 7.5 98.3 125 460-3-60 418 506 20.7 130 20.7 130 1.9 -- 56.5 70 380-3-60 342 418 21.4 160 21.4 160 3.6 -- 62 70 400-3-50 360 440 20.7 130 20.7 130 1.7 7.5 56 70

D028 208/230-3-60 187 254 45.7 255 45.7 255 5.5 - 125.3 150

460-3-60 418 506 22.9 145 22.9 145 2.8 - 62.9 80 380-3-60 342 418 27.1 155 27.1 155 3.9 - 75.6 90

LEGEND FLA — Full Load Amps kW — Total Fan Motor Input (kilowatts) LRA — Locked Rotor Amps MCA — Minimum Circuit Amps per NEC, Section 430-24

MOCP — Maximum Overcurrent Protection (amps) RLA — Rated Load Amps (compressor) *Units are suitable for use on electrical systems where voltage supplied to the unit terminals is not below or above the listed limits.

NOTES: 1. The MCA and MOCP values are calculated in accordance with theNational Electrical Code (NEC), Article 440. 2. Motor RLA and LRA values are established in accordance with Underwriters’ Laboratories (UL), Standard 1995.

18

Electrical data

Maximum Outdoor Temperature

115 F

Minimum Outdoor Ambient See Minimum Outdoor-Air Operating Temperature

table below. Minimum Return-Air

Temperature 55 F

Maximum Return-Air Temperature 95 F

Normal Acceptable Saturation Suction Temperature Range 25 to 55 F

Maximum Discharge Temperature 295 F

Minimum Discharge Superheat 60 F

UNIT 38AR

MAX ALLOW. LIFT (ft)

LIQUID LINE Max Allow. Pressure Drop (psi)

Max Allow. Temp Loss

(°F) 38ARZ007-012 38ARD014-028 60 7 2

UNIT 38AR

LINEAR LENGTH OF PIPING — FT 0-25 25-50 50-75 75-100

Line Size (in. OD) L S L S L S L S

Z007 3/8 11/8 3/8 11/8 3/8 11/8 3/8 11/8 Z008 3/8 11/8 1/2 11/8 1/2 11/8 1/2 13/8 Z012 1/2 13/8 1/2 13/8 1/2 13/8 1/2 13/8 D014 1/2 1 1/8 1/2 1 1/8 1/2 1 1/8 1/2 1 1/8 D016 1/2 13/8 1/2 13/8 1/2 13/8 5/8 13/8 D024 1/2 13/8 1/2 13/8 5/8 13/8 5/8 3/8

UNIT 38AR

LINEAR LENGTH OF PIPING — M (FT) 0–4 (0-13.1 ) 4-10 (13.1-32.8 ) 10-22 (32.8-72.2) 22–30.5(72.2-100)

Line Size (in. OD) L S L S L S L S

D028 5 /8 1 3 /8 5/8 13/8 7/8 15/8 7/8 15/8

UNIT 38AR

COND TEMP

(F)

MINIMUM OUTDOOR TEMP (F)

Std

38ARZ007-012 38ARD014-024 90 50

38ARD028 90 59

Application data

Operating limits LIQUID LINE DATA — 38ARD014-024 UNITS

Refrigerant piping IMPORTANT: Do not bury refrigerant piping underground.

NOTES: 1. Select air handler at no less than 300 cfm/ton (nominal condensing unit capacity). 2. Total combined draw of the field-supplied liquid line solenoid valve and air handler fan contactor must not exceed 22 va. If the specified va must be exceeded, use a remote relay to control the load.

Liquid line For applications with liquid lift greater than 20 ft, use 1/2-in. liquid line where 3/8 in. is shown; use 5/8- in. liquid line where 1/2 in. is shown. The maximum liquid lift is 60 ft.

MAXIMUM REFRIGERANT CHARGE

It is recommended that the refrigerant piping for all commercial split systems include a liquid line solenoid valve, a liquid line filter drier and a sight glass. For refrigerant lines longer than 75 lineal ft, a liquid line solenoid valve installed at the indoor unit and a suction accumulator are required. Refer to the Refrigerant Specialties Part Numbers table. REFRIGERANT PIPING SIZES

UNIT 38AR R-22 (lb) Z007 17.3 Z008 34.2 Z012 34.2 D014 (2)17.3 D016 (2)34.2 D024 (2)34.2 D028 (2)27.5

MINIMUM OUTDOOR-AIR OPERATING TEMPERATURE

LEGEND L — Liquid Line S — Suction Line NOTES: 1. Pipe sizes are based on a 2° F loss for liquid and suction lines. 2. Pipe sizes are based on the maximum linear length, shown for each column, plus a 50% allowance for fittings. 3. Charge units with R-22 refrigerant in accordance with unit installation instructions. 4. 38ARD has two independent refrigerant circuits and ref pipe sizes for 38ARD series are given for each circuit

REFRIGERANT SPECIALTIES PART NUMBERS

UNIT

LIQUID LINE SIZE

(in.)

LIQUID LINE SOLENOID VALVE

(LLSV)

LLSV COIL

SIGHT GLASS

FILTER DRIER SUCTION LINE

ACCUMULATOR

38ARZ007 3/8 200RB5T4M AMG-24/50-60 AMI1TT3 P502-8304S S-7063S

38ARZ008 3/8 200RB5T4M AMG-24/50-60 AMI1TT3 P502-8304S S-7063S 1/2 200RB5T4M AMG-24/50-60 AMI1TT4 P502-8304S S-7063S

38ARZ012 1/2 200RB6T4M AMG-24/50-60 AMI1TT4 P502-8307S S-7063

38ARD014 1/2 200RB5T4M Qty 2 AMG-24/50-60 Qty 2 AMI1TT4 Qty 2 P502-8304S Qty 2 S-7063S Qty 2

38ARD016 1/2 200RB5T4M Qty 2 AMG-24/50-60 Qty 2 AMI1TT4 Qty 2 P502-8304S Qty 2 S-7063S Qty 2 5/8 200RB5T5M Qty 2 AMG-24/50-60 Qty 2 AMI1TT5 Qty 2 P502-8304S Qty 2 S-7063S Qty 2

38ARD024 1/2 200RB6T4M Qty 2 AMG-24/50-60 Qty 2 AMI1TT5 Qty 2 P502-8307S* Qty 2 S-7063S Qty 2 5/8 200RB6T5M Qty 2 AMG-24/50-60 Qty 2 AMI1TT5 Qty 2 P502-8307S* Qty 2 S-7063S Qty 2

38A RD028 5/8 200RB6T5M Qty 2 AMG-24/50-60 Qty 2 AMI1TT5 Qty 2 P502-8307S* Qty 2 S-7063S Qty 2

19

abdulrehman.zia
Typewritten Text
abdulrehman.zia
Typewritten Text
abdulrehman.zia
Typewritten Text
abdulrehman.zia
Typewritten Text
abdulrehman.zia
Typewritten Text
abdulrehman.zia
Typewritten Text
13/8
abdulrehman.zia
Typewritten Text
abdulrehman.zia
Typewritten Text
abdulrehman.zia
Typewritten Text
7/8
abdulrehman.zia
Typewritten Text
15/8
abdulrehman.zia
Typewritten Text
abdulrehman.zia
Typewritten Text
7/8
abdulrehman.zia
Typewritten Text
abdulrehman.zia
Typewritten Text
abdulrehman.zia
Typewritten Text
15/8
abdulrehman.zia
Typewritten Text

20

Typical wiring schematic38ARZ 230V/460V

21

Typical wiring schematic38ARZ 380V

22

Typical wiring schematic 38ARD 230V/460V- (14-24)

23

Typical wiring schematic 38ARD 380V - (14-24)

24

Typical wiring schematic 38ARD (14-24)

Typical wiring schematic 38ARD028

25

230V,380V, 460V

Typical wiring schematic 38ARD028 230V,380V, 460V (cont.)

26

27

Model number nomenclature - 40RM 4 0 R M - 016 SD B 5 0 1 E D

40RM. Commercial Packaged Air Handler

Cooling Coil - Direct Expansion

Nominal Capacity Tons (kW) 007 6 (21) 016 15 (52) 008 7-1/2 (26) 024 20 (70)

028 25 (87) 012 10 (35) 034 30 (105) 014 12-1/2 (43)

S: SAMCO D: Double Skin

Expansion Device B Thermostatic Expansion Valves (40RM )

Voltage Designation (V-Ph-Hz)

3 208/230-1-60 (007-010 sizes only) 5 208/230-3-60 6 208/230/460-3-60 (all sizes 007-014; size 016

except YC and WD options)460-3-60 (sizes 016 with YC or WD options andall size 024-034 units)

8 230-3-50 9 400-3-50

Revision Number 0 Original Model

Factory-Installed Options

ED

FD

Painted, Standard Motor and Standard Drive

Painted, Standard Motor and Medium-Static Drive (Not available for 028 size for 60 Hz units.

RD

WD

Painted, Alternate Motor and Medium-Static Drive (Available for 60 Hz sizes 028 only

Painted, Alternate Motor and High-Static Drive 

Packaging 1 Standard Domestic 3 Export

RD and WD option codes for all 034 size units and 008, 010 units with 208/230-1-60 power designate standard motor and high-static drive.

NOTE: See the following table for the sizes available for each unit.

Quality Assurance

40RM007-034 6-25 Nominal Tons – 60 Hz

28

Physical data

40RM - ENGLISH

UNIT 40RM 007SD 008SD 012SD 014SD 016SD 024SD 028SD 034SD NOMINAL CAPACITY (Tons) 121/271/26 10 15 20 25 30OPERATING WEIGHT (lb)

Base Unit (Double skin) with TXV 448 452 472 804 819 824 1188 1198Plenum 97 97 97 140 140 140 180 180

FANS Qty...Diam. (in.) 1...15 1...15 1...15 2...15 2...15 2...15 2...18 2...18Nominal Airflow (cfm) 2400 3000 4000 5000 6000 8000 10,000 12,000 Airflow Range (cfm) 1800-3000 2250-3750 3000-5000 3750-6250 4500-7500 6000-10,000 7500-12,500 9000-15,000 Nominal Motor Hp (Standard Motor)*

208/230-1-60 1.3 2.4 - - - - - -208/230-3-60 and 460-3-60 2.4 2.4 2.4 2.9 3.7 5.0 7.5 10.0 575-3-60 1.0 2.0 2.0 3.0 3.0 5.0 7.5 10.0 230-3-50, 400-3-50 2.4 2.4 2.9 2.9 2.9 5.0 7.5 10.0

Motor Speed (rpm) 208/230-1-60 1725 1725 - - - - - -208/230-3-60 and 460-3-60 1725 1725 1725 1725 1725 1745 1745 1745575-3-60 1725 1725 1725 1725 1725 1745 1755 1755230-3-50, 400-3-50 1425

REFRIGERANT R-22Operating charge (lb) 3.0 3.0 1.5/1.5 2.0/2.0 2.5/2.5 3.5/3.5 4.5/4.5 5.0/5.0(approx per circuit)²

DIRECT-EXPANSION COIL Enhanced Copper Tubes, Aluminum Sine-Wave Fins Max Working Pressure (psig) 435Face Area (sq ft) 6.67 8.33 10.0 13.25 17.67 19.88 24.86 29.83 No. of Splits 1 1 2 2 2 2 2 2Split Type...Percentage - - Face...50/50 No. of Circuits per Split 12 15 9 9 12 13 15 18Rows...Fins/in. 3...15 3...15 3...17 3...15 3...15 3...17 3...15 3...15

STEAM COIL** Max Working Pressure (psig at 400 F) 175Total Face Area (sq ft) 6.67 6.67 6.67 13.33 13.33 13.33 15.0 15.0 Rows...Fins/in. 1...9 1...9 1...9 1...10 1...10 1...10 1...10 1...10

HOT WATER COIL** Max Working Pressure (psig) 150Total Face Area (sq ft) 6.67 6.67 6.67 13.33 13.33 13.33 15.0 15.0 Rows...Fins/in. 2...8.5 2...8.5 2...8.5 2...8.5 2...8.5 2...8.5 2...12.5 2...12.5Water Volume

(gal) 8.3 13.9 14.3 (ft3) 1.1 1.85 1.90

PIPING CONNECTIONS Quantity...Size (in.)

DX Coil - Suction (ODF) 1...11/8 1...11/8 2...11/8 2...11/8 2...11/8 2...11/8 2...13/8 2...13/8

DX Coil - Liquid Refrigerant (ODF) 1...5/8 2...5/8

Steam Coil, In (MPT) 1...21/2 1...21/2

Steam Coil, Out (MPT) 1...11/2 1...11/2

Hot Water Coil, In (MPT) 1...11/2 1...11/2 1...2Hot Water Coil, Out (MPT) 1...11/2 1...11/2 1...2Condensate (PVC) 1...11/4 ODM/1 IDF

FILTERS Washable - Factory Supplied 4...16 x 20 x 1 4...20 x 24 x 1Quantity...Size (in.) 4...16 x 24 x 1 4...16 x 24 x 1 4...20 x 25 x 1

Access Location Front

LEGEND DX - Direct Expansion TXV - Thermostatic Expansion Valve

*Refer to alternate Fan Motor Data table, pages 54 and 55, for alternate motor data. ²Units are shipped without refrigerant charge. **Please contact your local Carrier sales office for availability. Please contact your local Carrier sales office for the weights of single skin units.

29

Options and accessories Factory-installed optionsAlternate fan motors and drives are availableto pro­vide the widest possiblerange of performance.

Field-installed accessoriesTwo-row hot water coils have copper tubes mechani­cally bonded to aluminum plate fins and non-ferrousheaders.One-row steam coil has copper tubesand aluminum fins.The Inner Distributing Tube (IDT) designprovides uniformtemperaturesacrossthecoil face.The steamcoil hasa broadoperating pressurerange; up to 175 psig (1207 kPag) at400 F (204.4 C) and up to 300 psig (2069 kPag)at 300 F(148.9 C). The IDT steamcoils are especiallysuited to ap­plications where sub-freezingair enters the unit. Electric resistance heat coils have an open-wire design and are mounted in a rigid frame. Safety cutouts for high temperature conditions are standard. Terminal block for single-point power connection is included. Economizer (enthalpy contr olled) provides ventilation air and ``free'' cooling if outside ambient temperature and humidity are suitable.Can also be usedwith CO2 sensors to help meet indoor air quality requirements. Discharge plenum directs the air discharge directly into the occupied space; integral horizontal and vertical louvers enable redirection of airflow. Accessory is available un­painted or painted. Field assemblyrequired.

Standard units available from the factory are in Double skin.

Return-air grille provides a protective barrier over the return-air opening and givesa finishedappearanceto units installed in the occupied space. Accessoryis availableun­painted or painted. Subbase provides a stable, raised platform and room for condensatedrain trap connection for verticalfloor-mounted units. Accessoryis availableunpainted or painted. Over head suspension package includes necessarybrack­ets to support units in horizontal ceiling installations. CO2 sensors can be used in conjunction with the econ­omizer accessoryto help meet indoor air quality require­ments. The sensor signals the economizer to open when the CO2 level in the spaceexceedsthe set point. A Carrier Comfort Systemprogrammable thermostat can be usedto override the sensorif the outsideair temperatureis too high or too low. Carrier's line of ther mostats provide both program­mable and non-programmable capability with the new Debonair line of commercial programmable thermostats, the TEMP System controls offer communication capabil­ity with stagedheatingandcooling, the Commercial Elec­tronic thermostats provide 7-day programmablecapability for economicalapplications,while the Non-Programmable thermostatsoffer a multitude of stagedheating and cooling subbaseoptions. Condensate drain trap includesan overflow shutoff switch that can be wired to turn off the unit if the trap becomes plugged. Kit also includesa wire harnessthat can be con­nected to an alarm if desired. The transparent trap is de­signed for easyserviceand maintenance.

30

CARRIER THERMOSTATS DEBONAIR COMMERCIAL PROGRAMMABLE

THERMOSTAT

AUTO

Pm COOL

HEAT

®

TEMP SYSTEM THERMOSTAT

COMMERCIAL ELECTRONIC THERMOSTAT

NON-PROGRAMMABLE THERMOSTAT

H C

31

Options and accessories (cont)

40RM WITH DISCHARGE PLENUM, RETURN-AIR GRILLE AND SUBBASE

DISCHARGE PLENUM

RETURN-AIR GRILLE

SUBBASE FAN COIL UNIT

40RM WITH ECONOMIZER

ECONOMIZER

40RM WITH HOT WATER OR STEAM COIL

FAN COIL UNIT

HOT WATER OR STEAM COIL

40RM WITH CONDENSATE TRAP

32

Dimensions 40RM007SD-012SD

UNIT WEIGHT UNIT lb (kg) 40RM007SD 448 (203) 40RM008SD 452 (205) 40RM012SD 472 (214)

TXV - Thermostatic Expansion Valve

NOTES: 1. Dimensions in [ ] are in

millimeters.

2. Direction of air¯ow.

3. Recommended clearance: · Rear: 39(76.2 mm) (28-69[762 mm]

with electric heat accessory) · Front: 28-69(762 mm) · Right side: 28-69(762 mm) · Left Side: 28-69(762 mm) · Local codes or jurisdiction may

prevail. 4. Liquid piping not supplied by

Carrier. 5. Duct flange is factory supplied and

field installed.

All the above mentioned weights are for double skin units.

33

Dimensions (cont) 40RM014SD-024SD

UNIT UNITWEIGHT lb (kg)

40RM014SD 804 (364) 40RM016SD 819 (371) 40RM024SD 824 (373)

TXV - Thermostatic Expansion Valve

NOTES: 1. Dimensions in [ ] are in

millimeters.

2. Direction of airflow.

3. Recommended clearance: · Rear: 39 (76.2 mm) (28-69

[762 mm] with electric heat accessory)

· Front: 28-69(762 mm) · Right side: 28-69(762 mm) · Left Side: 28-69(762 mm) · Local codes or jurisdiction may

prevail. 4. Liquid piping not supplied by

Carrier. 5. Duct flange is factory supplied

and field installed.

All the weights men­tioned in the table are for double skin units.

UNIT

34

40RM028SD,034SD

TXV - Thermostatic Expansion Valve

NOTES: 1. Dimensions in [ ] are in

millimeters.

2. Direction of airflow.

3. Recommended clearance: · Rear: 39(76.2 mm) · Front: 28-69(762 mm) · Right side: 28-69(762 mm) · Left Side: 28-69(762 mm) · Local codes or jurisdiction may

prevail. 4. Liquid piping not supplied by

Carrier. 5. Duct flange is factory supplied

and field installed.

UNIT WEIGHT UNIT lb (kg) 40RM028SD 1188 (538) 40RM034SD 1198 (542)

All the above mentioned weights are for double skin units.

Dimensions (cont)

35

OVERHEAD SUSPENSION ACCESSORY

UNIT SIZES 007-012

UNIT SIZES 014-024

UNIT SIZES 028,034

NOTE: Dimensions in [ ] are millimeters.

Dimensions (cont)

36

PLENUM, RETURN-AIR GRILLE, AND SUBBASE ACCESSORIES

UNIT SIZES 007-012

UNIT SIZES 014-024

NOTE: Dimensions in [ ] are millimeters.

37

PLENUM, RETURN-AIR GRILLE, AND SUBBASE ACCESSORIES (cont) UNIT SIZES 028,034

NOTE: Dimensions in [ ] are millimeters.

Dimensions (cont)

38

HOT WATER AND STEAM COIL ACCESSORIES

UNIT SIZES 007-012

NOTE: Dimensions in [ ] are millimeters.

DIMENSION HOT WATER COIL STEAM COIL

A 11⁄2� MPT [38.1] 11⁄2� MPT [38.1] B 11⁄2� MPT [38.1] 21⁄2� MPT [63.5] C 23⁄8� [60.3] 31⁄8� [79.4] D 47⁄8� [123.8] 31⁄8� [79.4] E 21⁄8� [54.0] 49⁄16� [115.8] F 1�-111⁄4� [590.6] 1�-9� [584.2] G 3�- 4� [1016.0] 3�-4� [1016.0]

UNIT SIZES 014-024

NOTE : Dimensions in [ ] are millimeters.

DIMENSION HOT WATER COIL STEAM COIL

A 2� MPT [50.8] 11⁄2� MPT [38.1] B 2� MPT [50.8] 21⁄2� MPT [63.5] C 23⁄8� [60.3] 31⁄8� [79.4] D 47⁄8� [123.8] 31⁄8� [79.4] E 21⁄8� [54.0] 49⁄16� [115.8] F 1�-111⁄4� [590.6] 1�-9� [584.2] G 6�- 8� [2032.0] 6�-8� [2032.0]

39

40RM028SD,034SD

TXV - Thermostatic Expansion Valve

NOTES: 1. Dimensions in [ ] are in

millimeters.

2. Direction of airflow.

3. Recommended clearance: · Rear: 39(76.2 mm) · Front: 28-69(762 mm) · Right side: 28-69(762 mm) · Left Side: 28-69(762 mm) · Local codes or jurisdiction may

prevail. 4. Liquid piping not supplied by

Carrier. 5. Duct flange is factory supplied

and field installed.

UNIT WEIGHT UNIT lb (kg) 40RM028SD 1188 (538) 40RM034SD 1198 (542)

All the above mentioned weights are for double skin units.

40

ECONOMIZER ACCESSORY

UNIT SIZES 007-012

UNIT SIZES 014-024

UNIT SIZES 028,034

NOTES: 1. For horizontal unit applications, economizer can be attached to end of unit opposite duct connections. 2. Dimensions in [ ] are millimeters.

41

Dimensions (cont)ELECTRIC HEAT ACCESSORY

UNIT SIZES 007-012

UNIT SIZES 014-034

UNIT SIZE A B C D E F G H J

014-024 1�-31⁄4� [387.4]

4�-63⁄8� [1381.1]

25⁄16� [58.7]

2�-11⁄4� [641.4]

105⁄8� [269.9]

1�-4� [406.4]

1�-45⁄16� [414.3]

1�-63⁄4� [476.3]

1�-7⁄8� [327.0]

028,034 1�-33⁄8� [390.5]

5�-47⁄16� [1636.8]

21⁄16� [26.9]

2�-63⁄16� [766.8]

1�-1⁄4� [311.2]

1�-7� [482.6]

1�-45⁄16� [414.0]

1�-10� [558.8]

1�-47⁄16� [417.1]

NOTE: Dimensions in [ ] are millimeters.

42

Selection procedure (with example)— English (60 Hz) Cooling (DX) I Determine the cooling load and temperature and quantity of air entering the evaporator. Given: Total Capacity . . . . . . . . . . . . . . . . . . . . 200,000 Btuh

Sensible Heat Capacity . . . . . . . . . . . . . 130,000 Btuh

Air Temperature Entering Indoor Coil . . . . . . . . . . . . . . . . . . . . . . . . 80 F db, 67 F wb

Air Quantity Entering Indoor Coil . . . . . . . 6000 cfm

Ductwork Static Pressure Loss . . . . . . . . . . 0.8 in. wg

Power Supply . . . . . . . . . . . . . . . . . . . . . . . . . 230-3-60

II Determine unit selection and coil refrigerant temperature. Enter the Cooling Capacities table at 6000 cfm. Se­lect a 40RM016 unit which has a total capacity of 207,000 and 174,000 Btuh at 40 and 45 F coil re­frigerant temperature, respectively. By interpolation, coil refrigerant temperature of 41.1 F is needed to give a total capacity of 200,000 Btuh. Sensible capacity is approximately 149,000 Btuh. Cooling load is satisfied.

Fan I Determine fan speed and brake horsepower: From the Accessory Pressure Drop table, read a loss of 0.23 in. wg for a hot water coil at 6000 cfm. External static pressure = 0.80 + 0.23

= 1.03 in. wg

Enter 40RM016 Fan Performance table at 6000 cfm and 1.03 in. wg. Interpolate and determine fan speed of 866 rpm and 2.7 bhp.

II Determine motor and drive. Enter the fan motor data tables on page 54, and find that the 230 v standard motor for a 40RM016 unit is rated at 3.7 Hp. Since the bhp required is 2.7, a stand­ard motor satisfies the requirement and should be used. Next, find the type of drive that satisfies the 866 rpm requirement in the Drive Data tables on pages 59,60 . For a 40RM016 unit, the Medium-Static Drive table on page 59 shows an rpm range of 742 to 943. Since the rpm required is 866, the medium-static drive sat­isfies the requirement and should be used. Select the standard motor and medium-static drive combination (option code HC or FD). To select an outdoor unit for this 40RM016 indoor section, refer to the Combination Rating sheets for Carrier condensing units in the condensing unit Prod­uct Data Digest, or consult the Carrier Electronic Catalog.

43

Performance data (cont) FAN PERFORMANCE DATA — 0.0-1.2 in. wg ESP — 60 Hz, ENGLISH

UNIT AIRFLOW (Cfm)

EXTERNAL STATIC PRESSURE (in. wg) 0.0 0.2 0.4 0.6 0.8 1.0 1.2

Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp

40RM 007

1,800 2,100 2,400 2,700 3,000

320 373 427 480 533

0.22 0.31 0.42 0.54 0.69

442 483 526 570 616

0.32 0.42 0.53 0.67 0.82

534 569 606 646 687

0.42 0.53 0.64 0.78 0.94

611 642 676 712 750

0.52 0.63 0.75 0.89 1.05

678 708 739 773 808

0.61 0.73 0.86 1.00 1.16

739 767 796 828 862

0.70 0.82 0.96 1.11 1.28

795 821 849 880 912

0.80 0.92 1.06 1.21 1.39

40RM 008

2,250 2,600 3,000 3,400 3,750

359 415 478 542 598

0.32 0.45 0.62 0.82 1.03

472 516 569 624 673

0.44 0.57 0.75 0.95 1.17

560 599 645 695 740

0.55 0.68 0.86 1.08 1.29

634 669 712 758 800

0.65 0.79 0.98 1.20 1.42

700 732 773 815 855

0.75 0.90 1.09 1.31 1.60

759 790 828 869 906

0.86 1.01 1.20 1.43 1.66

814 843 879 918 954

0.96 1.11 1.32 1.55 1.78

40RM 012

3,000 3,500 4,000 4,500 5,000

444 518 592 666 740

0.58 0.82 1.11 1.44 1.83

541 604 669 735 803

0.71 0.95 1.25 1.59 1.98

621 677 736 797 861

0.83 1.08 1.38 1.72 2.12

691 742 797 854 914

0.94 1.20 1.51 1.86 2.26

753 801 853 907 964

1.05 1.32 1.63 1.99 2.39

809 855 904 956

1010

1.17 1.44 1.75 2.12 2.53

862 906 953

1003 1055

1.28 1.56 1.88 2.24 2.66

40RM 014

3,750 4,300 5,000 5,700 6,250

363 416 484 552 605

0.37 0.53 0.81 1.17 1.51

475 517 573 631 678

0.58 0.78 1.08 1.47 1.83

566 601 650 702 744

0.80 1.02 1.35 1.76 2.15

645 676 719 766 805

1.02 1.26 1.62 2.06 2.47

715 743 782 826 862

1.24 1.50 1.89 2.36 2.79

779 805 841 881 915

1.47 1.74 2.16 2.66 3.11

839 862 896 934 966

1.69 1.99 2.44 2.96 3.43

40RM 016

4,500 5,300 6,000 6,800 7,500

391 460 521 590 651

0.51 0.80 1.13 1.60 2.10

495 551 602 663 718

0.75 1.08 1.43 1.93 2.45

581 629 675 730 779

1.00 1.35 1.73 2.26 2.81

657 700 741 791 837

1.25 1.63 2.04 2.59 3.16

725 764 801 847 890

1.50 1.91 2.34 2.92 3.52

787 823 858 901 941

1.76 2.20 2.65 3.26 3.88

845 878 911 951 990

2.02 2.48 2.96 3.60 4.24

40RM 024

6,000 7,000 8,000 9,000

10,000

503 586 670 754 838

1.07 1.64 2.37 3.28 4.39

587 660 735 812 891

1.37 1.98 2.74 3.69 4.83

661 726 795 867 941

1.67 2.31 3.12 4.09 5.27

727 787 851 918 988

1.97 2.65 3.49 4.50 5.70

789 844 904 967

1034

2.28 2.99 3.86 4.90 6.14

846 898 954

1014 1077

2.59 3.33 4.23 5.31 6.85

900 948

1001 1059 1120

2.90 3.67 4.61 5.72 7.02

40RM 028

7,500 8,750

10,000 11,250 12,500

412 481 549 618 687

1.15 1.76 2.55 3.52 4.71

492 550 610 672 735

1.53 2.17 2.99 4.00 5.22

568 616 669 725 783

2.00 2.66 3.50 4.53 5.78

640 680 726 777 830

2.56 3.22 4.07 5.12 6.38

710 742 782 827 876

3.22 3.86 4.70 5.76 7.04

776 802 836 876 922

3.98 4.58 5.40 6.45 7.74

840 860 889 925 966

4.83 5.38 6.17 7.21 8.49

40RM 034

9,000 10,500 12,000 13,500 15,000

471 550 628 707 785

1.78 2.72 3.93 5.44 7.27

539 608 679 752 826

2.17 3.15 4.40 5.94 7.81

604 665 730 797 867

2.63 3.64 4.92 6.49 8.39

667 720 779 841 907

3.17 4.18 5.48 7.08 9.01

728 774 827 885 947

3.78 4.79 6.09 7.71 9.66

788 827 874 928 986

4.46 5.45 6.76 8.38

10.35

845 878 921 970

1024

5.22 6.18 7.47 9.10

11.07

See Legend and Notes on page 4 0 .

44

FAN PERFORMANCE DATA — 1.4-2.4 in. wg ESP — 60 Hz, ENGLISH

UNIT AIRFLOW (Cfm) 1.4

Rpm Bhp 1.6

Rpm Bhp

EXTERNAL STATIC PRESSURE (in. wg) 1.8 2.0 2.2

Rpm Bhp Rpm Bhp Rpm Bhp 2.4

Rpm Bhp

1,800 847 0.89 896 0.98 942 1.07 986 1.16 1027 1.25 — —

40RM 007

2,100 2,400 2,700

872 899 928

1.02 1.16 1.32

920 946 974

1.11 1.26 1.42

965 990

1018

1.21 1.36 1.52

1008 1033 1059

1.30 1.46 1.63

1050 1073 1099

1.40 1.55 1.73

— — —

— — —

3,000 959 1.49 1004 1.60 1046 1.71 1087 1.81 1126 1.92 — —

40RM 008

2,250 2,600 3,000 3,400

865 893 928 965

1.06 1.22 1.43 1.66

913 940 973

1010

1.16 1.33 1.54 1.78

958 984

1017 1052

1.27 1.43 1.65 1.89

1001 1027 1058 1092

1.37 1.54 1.76 2.00

1042 1067 1098 1131

1.47 1.65 1.87 2.12

— — — —

— — — —

3,750 1000 1.90 1043 2.02 1084 2.13 1124 2.25 1162 2.37 — —

3,000 911 1.39 958 1.50 1002 1.61 1044 1.72 1084 1.83 1123 1.94

40RM 012

3,500 4,000 4,500

953 999

1047

1.67 2.00 2.37

998 1042 1089

1.79 2.12 2.50

1041 1084 1129

1.90 2.24 2.62

1082 1124 1168

2.02 2.36 2.74

1122 1162

2.13 2.48 —

1159 1199

2.25 2.60 —

5,000 1097 2.79 1138 2.92 1177 3.05 — — — — — —

3,750 894 1.91 947 2.14 996 2.37 1044 2.60 1089 2.83 — —

40RM 014

4,300 5,000 5,700

916 948 984

2.23 2.71 3.25

967 997

1031

2.48 2.98 3.55

1016 1044 1076

2.73 3.26 3.86

1062 1089 1120

2.98 3.53 4.16

1107 1133 1162

— 3.24 3.81 4.46

— — — —

— — — —

6,250 1014 3.75 1060 4.07 1104 4.39 1147 4.71 1188 5.03 — —

4,500 899 2.29 951 2.56 999 2.84 1046 3.12 1091 3.41 1133 3.70

40RM 016

5,300 6,000 6,800

930 961 999

2.78 3.28 3.94

980 1009 1045

3.08 3.60 4.28

1027 1055 1089

3.38 3.92 4.63

1072 1098 1132

3.68 4.24 4.98

1116 1141 1173

3.99 4.57 5.33

1157 1181

4.30 4.91 —

7,500 1036 4.60 1080 4.97 1123 5.34 1164 5.71 — — — —

6,000 950 3.21 999 3.53 1045 3.85 1089 4.17 1131 4.50 1172 4.83

40RM 024

7,000 8,000 9,000

996 1047 1102

4.02 4.99 6.13

1042 1091 1143

4.37 5.37 6.54

1086 1133 1183

4.72 5.75 6.96

1129 1173

5.07 6.13 —

1169 — —

5.43 — —

— — —

— — —

10,000 1160 7.46 1200 7.91 — — — — — — — —

7,500 903 5.79 963 6.83 1021 7.98 1078 9.21 — — — —

40RM 028

8,750 10,000 11,250

917 941 972

6.26 7.01 8.02

972 991

1019

7.22 7.91 8.89

1025 1040 1064

8.26 8.89 9.83

1078 1089

9.38 9.93 —

— — —

— — —

— — —

— — —

12,500 1010 9.29 1053 10.15 1095 11.05 — — — — — —

9,000 901 6.07 955 6.98 1008 7.98 1060 9.05 — — — —

40RM 034

10,500 12,000 13,500

928 966

1011

6.98 8.24 9.86

978 1011 1052

7.84 9.07

10.67

1026 1055 1092

8.76 9.95

11.52

1073 1098

9.74 10.88

— — —

— — —

— — —

— — —

15,000 1062 11.84 — — — — — — — — — —

See Legend and Notes on page 40.

45

Performance data (cont)

LEGEND

FACTOR Y-SUPPLIED FILTER PRESSURE DROP

Bhp - Brake Horsepower Input to Fan

- ENGLISH

ESP - External Static Pressure

Bold indicates field supplied drive is required.Plain type indicates standard motor and standard drive.Underline indicates a different motor and drive combination other thanthe standard motor and standard drive combination is required. Refer tofan motor and drive tables, pages 54-60, to complete selection.

NOTES: 1. Maximum allowable fan speed is 1100 rpm for unit sizes 028 and

034; 1200 rpm for all other sizes. 2. Fan performance is based on deductions for wet coil, clean 1-in.

filters, and unit casing. See table at right for factory-supplied filter pressure drop.

3. For 60 Hz units, the medium-static drive and standard motor combi­nation is not available for 028 size.

UNIT AIRFLOW (Cfm)

PRESSURE DROP (in. wg)

40RM 007

1,800 2,400 3,000

0.05 0.08 0.11

40RM 008

2,250 3,000 3,750

0.07 0.11 0.15

40RM 012

3,000 4,000 5,000

0.11 0.17 0.23

40RM 014

3,750 5,000 6,250

0.06 0.10 0.13

40RM 016

4,500 6,000 7,500

0.08 0.12 0.17

40RM 024

6,000 8,000

10,000

0.12 0.19 0.26

40RM 028

7,500 10,000 12,500

0.15 0.22 0.30

40RM 034

9,000 12,000 15,000

0.19 0.29 0.40

ACCESSORY PLENUM AIR THROW DATA — ENGLISH (Ft)

UNIT AIRFLOW (Cfm)

VANE DEFLECTION Straight 211⁄2° 45°

40RM 007 2,400 39 33 24

40RM 008 3,000 45 38 28

40RM 012 4,000 55 46 33

40RM 014

5,000 45 38 28

40RM 016 6,000 50 43 31

40RM 024 8,000 60 51 37

40RM 028 10,000 76 65 47

40RM 034 12,000 85 72 52

NOTE: Throw distances shown are for 75 fpm terminal velocity. Use the following multipliers to determine throw values for other terminal velocities.

TERMINAL VELOCITY (Fpm) THROW FACTOR

50 X 1.50 100 X 0.75 150 X 0.50

46

ACCESSORY PRESSURE DROP — ENGLISH

(in. wg)

UNIT AIRFLOW (Cfm)

DISCHARGE PLENUM

RETURN AIR GRILLE

HEATING COILS ECONOMIZERHot Water Steam Electric

40RM 007

1,800 2,400 3,000

0.06 0.10 0.14

0.01 0.01 0.02

0.10 0.16 0.23

0.10 0.16 0.23

0.04 0.06 0.10

0.05 0.07 0.09

40RM 008

2,250 3,000 3,750

0.09 0.14 0.21

0.01 0.02 0.03

0.15 0.23 0.35

0.15 0.23 0.35

0.06 0.10 0.15

0.06 0.09 0.15

40RM 012

3,000 4,000 5,000

0.14 0.22 0.32

0.02 0.04 0.06

0.23 0.37 0.53

0.23 0.37 0.53

0.10 0.17 0.26

0.09 0.17 0.28

40RM 014

3,750 5,000 6,250

0.07 0.12 0.17

0.01 0.02 0.02

0.11 0.17 0.25

0.11 0.17 0.25

0.04 0.07 0.11

0.05 0.07 0.11

40RM 016

4,500 6,000 7,500

0.10 0.16 0.23

0.01 0.02 0.03

0.15 0.23 0.33

0.15 0.23 0.33

0.06 0.10 0.15

0.06 0.09 0.15

40RM 024

6,000 8,000

10,000

0.16 0.26 0.37

0.02 0.04 0.06

0.23 0.37 0.53

0.23 0.37 0.53

0.10 0.17 0.26

0.09 0.17 0.28

40RM 028

7,500 10,000 12,500

0.15 0.24 0.34

0.02 0.03 0.05

0.28 0.44 0.63

0.28 0.44 0.63

0.09 0.16 0.24

0.06 0.09 0.14

40RM 034

9,000 12,000 15,000

0.20 0.32 0.46

0.03 0.05 0.07

0.37 0.59 0.85

0.37 0.59 0.85

0.13 0.22 0.34

0.08 0.14 0.21

47

Electrical data

STANDARD MOTORS

UNIT V*-PH-Hz VOLTAGE LIMITS

FAN MOTOR POWER SUPPLY

Hp (kW) FLA Minimum

Circuit Amps

MOCP

208/230-1-60 187-253 1.3 (0.97) 7.6 9.5 15

208/230-3-60 187-253 2.4 (1.79) 5.2 6.5 15

40RM 007

460-3-60 414-506 2.4 (1.79) 2.6 3.3 15

575-3-60 518-632 1.0 (0.75) 1.4 8.0 15

230-3-50 207-253 2.4 (1.79) 5.2 6.5 15

400-3-50 360-440 2.4 (1.79) 2.6 3.3 15

208/230-1-60 187-253 2.4 (1.79) 11.0 13.8 20

40RM 008

208/230-3-60 187-253 2.4 (1.79) 5.2 6.5 15

460-3-60 414-506 2.4 (1.79) 2.6 3.3 15

575-3-60 518-632 2.0 (1.49) 2.3 2.9 15

230-3-50 207-253 2.4 (1.79) 5.2 6.5 15

400-3-50 360-440 2.4 (1.79) 2.6 3.3 15

208/230-3-60 187-253 2.4 (1.79) 5.2 6.5 20

40RM 012

460-3-60 414-506 2.4 (1.79) 2.6 3.3 15

575-3-60 518-632 2.0 (1.49) 2.3 2.9 15

230-3-50 207-253 2.9 (2.16) 7.5 9.4 15

400-3-50 360-440 2.9 (2.16) 3.4 4.3 15

208/230-3-60 187-253 2.9 (2.16) 7.5 9.4 15

40RM 460-3-60 414-506 2.9 (2.16) 3.4 4.3 15

014 575-3-60 518-632 3.0 (2.24) 3.8 4.8 15

230-3-50 207-253 2.9 (2.16) 7.5 9.4 15

400-3-50 360-440 2.9 (2.16) 3.4 4.3 15

208/230-3-60 187-253 3.7 (2.76) 10.2 12.8 20

40RM 016

460-3-60 414-506 3.7 (2.76) 4.8 6.0 15

575-3-60 518-632 3.0 (2.24) 3.8 4.8 15

230-3-50 207-253 2.9 (2.16) 7.5 9.4 15

400-3-50 360-440 2.9 (2.16) 3.4 4.3 15

208/230-3-60 187-253 5.0 (3.73) 15.3/12.8 19.1/16.0 30/25

40RM 460-3-60 414-506 5.0 (3.73) 6.4 8.0 15

024 575-3-60 518-632 5.0 (3.73) 5.1 6.4 15

230-3-50 207-253 5.0 (3.73) 15.2 19.0 30

400-3-50 360-440 5.0 (3.73) 7.6 9.5 15

208/230-3-60 187-253 7.5 (5.59) 22.4/19.4 28.0/24.3 50/40

40RM 460-3-60 414-506 7.5 (5.59) 9.7 12.1 20

028 575-3-60 518-632 7.5 (5.59) 7.8 9.8 15

230-3-50 207-253 7.5 (5.59) 22.8 28.5 50

400-3-50 360-440 7.5 (5.59) 11.4 14.3 25

208/230-3-60 187-253 10.0 (7.46) 29.3/26.8 36.6/33.5 60/60

40RM 460-3-60 414-506 10.0 (7.46) 13.4 16.8 30

034 575-3-60 518-632 10.0 (7.46) 10.3 12.9 20

230-3-50 207-253 10.0 (7.46) 32.2 40.3 70

400-3-50 360-440 10.0 (7.46) 16.1 20.1 30

See Legend and Notes on page 43.

48

ALTERNATE MOTORS

UNIT V*-PH-Hz VOLTAGE LIMITS

FAN MOTOR POWER SUPPLY

Hp (kW) FLA Minimum

Circuit Amps

MOCP

208/230-1-60 187-253 2.4 (1.79) 11.0 13.8 20

208/230-3-60 187-253 2.9 (2.16) 7.5 9.4 15

40RM 007

460-3-60 414-506 2.9 (2.16) 3.4 4.3 15

575-3-60 518-632 2.0 (1.49) 2.3 2.9 15

230-3-50 207-253 2.4 (1.79) 5.2 6.5 15

400-3-50 360-440 2.4 (1.79) 2.6 3.3 15

208/230-1-60 187-253 2.4 (1.79) 11.0 13.8 15

40RM 008

208/230-3-60 187-253 2.9 (2.16) 7.5 9.4 15

460-3-60 414-506 2.9 (2.16) 3.4 4.3 15

575-3-60 518-632 3.0 (2.24) 3.8 4.8 15

230-3-50 207-253 2.9 (2.16) 7.5 9.4 15

400-3-50 360-440 2.9 (2.16) 3.4 4.3 15

208/230-3-60 187-253 3.7 (2.76) 10.2 12.8 20

40RM 012

460-3-60 414-506 3.7 (2.76) 4.8 6.0 15

575-3-60 518-632 3.0 (2.24) 3.8 4.8 15

230-3-50 207-253 5.0 (3.73) 15.2 19.0 30

400-3-50 360-440 5.0 (3.73) 7.6 9.5 15

208/230-3-60 187-253 3.7 (2.76) 10.2 12.7 20

40RM 460-3-60 414-506 3.7 (2.76) 4.8 6.0 15

014 575-3-60 518-632 5.0 (3.73) 5.1 6.4 15

230-3-50 207-253 5.0 (3.73) 15.2 19.0 30

400-3-50 360-440 5.0 (3.73) 7.6 9.5 15

208/230-3-60 187-253 5.0 (3.73) 15.3/12.8 19.1/16.0 30/25

40RM 016

460-3-60 414-506 5.0 (3.73) 6.4 8.0 15

575-3-60 518-632 5.0 (3.73) 5.1 6.4 15

230-3-50 207-253 5.0 (3.73) 15.2 19.0 30

400-3-50 360-440 5.0 (3.73) 7.6 9.5 15

208/230-3-60 187-253 7.5 (5.59) 22.4/19.4 28.0/24.3 50/40

40RM 460-3-60 414-506 7.5 (5.59) 9.7 12.1 20

024 575-3-60 518-632 7.5 (5.59) 7.8 9.8 15

230-3-50 207-253 7.5 (5.59) 22.8 28.5 50

400-3-50 360-440 7.5 (5.59) 11.4 14.3 25

208/230-3-60 187-253 10.0 (7.46) 29.3/26.8 36.6/33.5 60/60

40RM 460-3-60 414-506 10.0 (7.46) 13.4 16.8 30

028 575-3-60 518-632 10.0 (7.46) 10.3 12.9 20

230-3-50 207-253 10.0 (7.46) 32.2 40.3 60

400-3-50 360-440 10.0 (7.46) 16.1 20.1 30

LEGEND FLA — Full Load Amps MOCP — Maximum Overcurrent Protection *Motors are designed for satisfactory operation within 10% of nominal voltages shown. Voltages should not exceed the limits shown in the Voltage Limits column.

NOTES: 1. Minimum circuit amps (MCA) and MOCP values are calculated in accordance

with NEC (National Electrical Code) (U.S.A. standard), Article 440. 2. Motor FLA values are established in accordance with UL (Underwriters’ Labo-

ratories) Standard 1995 (U.S.A. standard). 3. Unbalanced 3-Phase Supply Voltage

Never operate a motor where a phase imbalance in supply voltage is greater than 2%. Use the following formula to determine the percentage of voltage imbalance. % Voltage Imbalance

max voltage deviation from average voltage= 100 xaverage voltage

EXAMPLE: Supply voltage is 400-3-50.AB = 393 vBC = 403 vAC = 396 v

393 + 403 + 396 Average Voltage = 3

1192 = 3

= 397

Determine maximum deviation from average voltage. (AB) 397 − 393 = 4 v (BC) 403 − 397 = 6 v (AC) 397 − 396 = 1 v

Maximum deviation is 6 v.

Determine percent voltage imbalance. 6% Voltage Imbalance = 100 x

397

= 1.5%

This amount of phase imbalance is satisfactory because it is below the maxi-mum allowable 2%.

IMPORTANT: If the supply voltage phase imbalance is more than 2%, con-tact your local electric utility company immediately.

49

Electrical data (cont) ELECTRIC HEATER DATA

HEATER PART NO. UNIT V-PH-Hz

FAN MOTOR ELECTRIC HEATER(S)

MCA* MOCP*Nominal Actual Capacity (kW) FLA

Hp kW FLA Capacity (kW) Stage 1 Stage 2 Total

208-3-60

1.3† 2.4† 2.4

0.97 1.79 1.79

7.6 11.0 5.2

5 5 5

3.8 3.8 3.8

— — —

3.8 3.8 3.8

10.4 10.4 10.4

22.5 26.8 19.5

25 35 20

2.9 3.7

2.16 2.76

7.5 10.2

5 5

3.8 3.8

— —

3.8 3.8

10.4 10.4

22.4 25.8

25 30

CAELHEAT001A00 1.3† 2.4†

0.97 1.79

7.6 11.0

5 5

5.0 5.0

— —

5.0 5.0

12.0 12.0

24.5 28.8

25 35

240-3-60 2.4 1.79 5.2 5 5.0 — 5.0 12.0 21.5 25 2.9 2.16 7.5 5 5.0 — 5.0 12.0 24.4 25 3.7 2.76 10.2 5 5.0 — 5.0 12.0 27.8 30

2.4 1.79 5.2 5 5.0 — 5.0 12.0 21.5 25 240-3-50 2.9 2.16 7.5 5 5.0 — 5.0 12.0 24.4 25

5.0 3.73 15.2 5 5.0 — 5.0 12.0 34.0 40

2.4 1.79 2.6 5 5.0 — 5.0 6.00 10.8 15 480-3-60 2.9 2.16 3.4 5 5.0 — 5.0 6.00 11.8 15

CAELHEAT002A00 3.7 2.76 4.8 5 5.0 — 5.0 6.00 13.5 15

2.4 1.79 2.6 5 3.5 — 3.5 5.00 9.5 15 400-3-50 2.9 2.16 3.4 5 3.5 — 3.5 5.00 10.5 15

5.0 3.73 7.6 5 3.5 — 3.5 5.00 15.8 20

1.0 0.75 1.4 5 5.0 — 5.0 5.00 8.0 15 CAELHEAT003A00 575-3-60 2.0 1.49 2.3 5 5.0 — 5.0 5.00 9.2 15

3.0 2.24 3.8 5 5.0 — 5.0 5.00 11.0 15

1.3† 0.97 7.6 10 7.5 — 7.5 20.8 35.6 40

208-3-60 2.4† 2.4 2.9 3.7

1.79 1.79 2.16 2.76

11.0 5.2 7.5

10.2

10 10 10 10

7.5 7.5 7.5 7.5

— — — —

7.5 7.5 7.5 7.5

20.8 20.8 20.8 20.8

39.8 32.6 35.4 38.8

40 35 40 40

CAELHEAT004A00 240-3-60

1.3† 2.4† 2.4 2.9 3.7

0.97 1.79 1.79 2.16 2.76

7.6 11.0 5.2 7.5

10.2

10 10 10 10 10

10.0 10.0 10.0 10.0 10.0

— — — — —

10.0 10.0 10.0 10.0 10.0

24.1 24.1 24.1 24.1 24.1

39.6 43.8 36.6 39.4 42.8

40 50 40 40 50

40RM007-012 240-3-50

2.4 2.9 5.0

1.79 2.16 3.73

5.2 7.5

15.2

10 10 10

10.0 10.0 10.0

— — —

10.0 10.0 10.0

24.1 24.1 24.1

36.6 39.4 49.1

40 40 50

2.4 1.79 2.6 10 10.0 — 10.0 12.0 18.3 20 480-3-60 2.9 2.16 3.4 10 10.0 — 10.0 12.0 19.3 20

CAELHEAT005A00 3.7 2.76 4.8 10 10.0 — 10.0 12.0 21.0 25

2.4 1.79 2.6 10 6.9 — 6.9 10.0 15.8 20 400-3-50 2.9 2.16 3.4 10 6.9 — 6.9 10.0 16.8 20

5.0 3.73 7.6 10 6.9 — 6.9 10.0 22.0 25

1.0 0.75 1.4 10 10.0 — 10.0 10.0 14.3 15 CAELHEAT006A00 575-3-60 2.0 1.49 2.3 10 10.0 — 10.0 10.0 15.4 20

3.0 2.24 3.8 10 10.0 — 10.0 10.0 17.3 20

208-3-60

1.3† 2.4† 2.4 2.9

0.97 1.79 1.79 2.16

7.6 11.0 5.2 7.5

15 15 15 15

11.3 11.3 11.3 11.3

— — — —

11.3 11.3 11.3 11.3

31.3 31.3 31.3 31.3

48.6 52.9 45.6 48.5

50 60 50 50

3.7 2.76 10.2 15 11.3 — 11.3 31.3 51.9 60

CAELHEAT007A00 1.3† 2.4†

0.97 1.79

7.6 11.0

15 15

15.0 15.0

— —

15.0 15.0

36.1 36.1

54.6 58.9

60 60

240-3-60 2.4 1.79 5.2 15 15.0 — 15.0 36.1 51.6 60 2.9 2.16 7.5 15 15.0 — 15.0 36.1 54.5 60 3.7 2.76 10.2 15 15.0 — 15.0 36.1 57.9 60

2.4 1.79 5.2 15 15.0 — 15.0 36.1 51.6 60 240-3-50 2.9 2.16 7.5 15 15.0 — 15.0 36.1 54.5 60

5.0 3.73 15.2 15 15.0 — 15.0 36.1 64.1 70

2.4 1.79 2.6 15 15.0 — 15.0 18.0 25.8 30 480-3-60 2.9 2.16 3.4 15 15.0 — 15.0 18.0 26.8 30

CAELHEAT008A00 3.7 2.76 4.8 15 15.0 — 15.0 18.0 28.6 30

2.4 1.79 2.6 15 10.4 — 10.4 15.0 22.0 25 400-3-50 2.9 2.16 3.4 15 10.4 — 10.4 15.0 23.0 25

5.0 3.73 7.6 15 10.4 — 10.4 15.0 28.3 30

1.0 0.75 1.4 15 15.0 — 15.0 15.1 20.6 25 CAELHEAT009A00 575-3-60 2.0 1.49 2.3 15 15.0 — 15.0 15.1 21.7 25

3.0 2.24 3.8 15 15.0 — 15.0 15.1 23.6 25

50

ELECTRIC HEATER DATA (cont)

HEATER PART NO. UNIT V-PH-Hz

FAN MOTOR ELECTRIC HEATER(S)

MCA* MOCP*Nominal Actual Capacity (kW) FLA

Hp kW FLA Capacity (kW) Stage 1 Stage 2 Total 1.3† 2.4†

0.97 1.79

7.6 11.0

25 25

11.3 11.3

7.5 7.5

18.8 18.8

52.1 52.1

74.7 78.9

80 80

208-3-60 2.4 2.9 3.7

1.79 2.16 2.76

5.2 7.5

10.2

25 25 25

11.3 11.3 11.3

7.5 7.5 7.5

18.8 18.8 18.8

52.1 52.1 52.1

71.7 74.5 77.9

80 80 80

CAELHEAT010A00 1.3† 2.4†

0.97 1.79

7.6 11.0

25 25

15.0 15.0

10.0 10.0

25.0 25.0

60.1 60.1

84.7 88.9

90 90

240-3-60 2.4 2.9 3.7

1.79 2.16 2.76

5.2 7.5

10.2

25 25 25

15.0 15.0 15.0

10.0 10.0 10.0

25.0 25.0 25.0

60.1 60.1 60.1

81.7 84.6 87.9

90 90 90

40RM007-012 240-3-50

2.4 2.9 5.0

1.79 2.16 3.73

5.2 7.5

15.2

25 25 25

15.0 15.0 15.0

10.0 10.0 10.0

25.0 25.0 25.0

60.1 60.1 60.1

81.7 84.6 94.2

90 90

100

2.4 1.79 2.6 25 15.0 10.0 25.0 30.1 40.8 50 480-3-60 2.9 2.16 3.4 25 15.0 10.0 25.0 30.1 41.8 50

CAELHEAT011A00 3.7 2.76 4.8 25 15.0 10.0 25.0 30.1 43.6 50

2.4 1.79 2.6 25 10.4 6.9 17.4 25.1 34.6 25 400-3-50 2.9 2.16 3.4 25 10.4 6.9 17.4 25.1 35.6 40

5.0 3.73 7.6 25 10.4 6.9 17.4 25.1 40.8 50

1.0 0.75 1.4 25 15.0 10.0 25.0 25.1 33.1 35 CAELHEAT012A00 575-3-60 2.0 1.49 2.3 25 15.0 10.0 25.0 25.1 34.3 35

3.0 2.24 3.8 25 15.0 10.0 25.0 25.1 36.1 40

2.4† 1.79 11.0 35 15.0 11.3 26.3 73.0 105.0 110

208-3-60 2.4 2.9

1.79 2.16

5.2 7.5

35 35

15.0 15.0

11.3 11.3

26.3 26.3

73.0 73.0

97.7 100.6

100 110

3.7 2.76 10.2 35 15.0 11.3 26.3 73.0 104.0 110

2.4† 1.79 11.0 35 20.0 15.0 35.0 84.2 119.0 125 CAELHEAT013A00 240-3-60 2.4

2.9 1.79 2.16

5.2 7.5

35 35

20.0 20.0

15.0 15.0

35.0 35.0

84.2 84.2

111.7 114.6

125 125

3.7 2.76 10.2 35 20.0 15.0 35.0 84.2 118.0 125

40RM008,012 240-3-50

2.4 2.9 5.0

1.79 2.16 3.73

5.2 7.5

15.2

35 35 35

20.0 20.0 20.0

15.0 15.0 15.0

35.0 35.0 35.0

84.2 84.2 84.2

111.7 114.6 124.2

125 125 125

2.4 1.79 2.6 35 20.0 15.0 35.0 42.1 55.9 60 480-3-60 2.9 2.16 3.4 35 20.0 15.0 35.0 42.1 56.9 60

CAELHEAT014A00 3.7 2.76 4.8 35 20.0 15.0 35.0 42.1 58.6 60

2.4 1.79 2.6 35 13.9 10.4 24.3 35.1 47.1 50 400-3-50 2.9 2.16 3.4 35 13.9 10.4 24.3 35.1 48.1 50

5.0 3.73 7.6 35 13.9 10.4 24.3 35.1 53.4 60

CAELHEAT015A00 575-3-60 2.0 3.0

1.49 2.24

2.3 3.8

35 35

20.0 20.0

15.0 15.0

35.0 35.0

35.1 35.1

46.8 48.7

50 50

LEGEND

FLA — Full Load Amps Hp — Horsepower MCA — Minimum Circuit Amps MOCP — Maximum Overcurrent Protection (Amps) *Values shown are for single-point connection of electric heat accessory and air handler.

†Single-phase motors. All other motors are 3-phase.

NOTES: 1. Electrical resistance heaters are rated at 240 v, 480 v, or 575 v. To determine

heater capacity (kW) at unit nameplate multiply the 240-v, 480-v, or 575-v ca-pacity (kW) by the factor shown in the table below for the unit voltage.

2. The following equation converts kW of heat energy to Btuh: kW x 3,412 = Btuh.

3. Heater contactor coils are 24 v and require 8 va holding current. 4. Electric heaters are tested and ETL approved at maximum total external static

pressure of 1.9 in. wg. 5. MCA and MOCP values apply to both standard and alternate factory-supplied

motors.

HEATER RATING

VOLTAGE

ACTUAL HEATER VOLTAGE

200 208 230 240 400 440 460 480 550 575 600

240 0.694 0.751 0.918 1 — — — — — — — 480 — — — — 0.694 0.84 0.918 1 — — — 575 — — — — — — — — 0.915 1 1.089

51

Electrical data (cont) ELECTRIC HEATER DATA (cont)

HEATER PART NO. UNIT V-PH-Hz

FAN MOTOR ELECTRIC HEATER(S)

MCA* MOCP*Nominal Actual Capacity (kW) FLA

Hp kW FLA Capacity (kW) Stage 1 Stage 2 Total 2.9 2.16 7.5 10 7.5 — 7.5 20.8 35.4 40

208-3-60 3.7 5.0

2.76 3.73

10.2 15.3

10 10

7.5 7.5

— —

7.5 7.5

20.8 20.8

38.8 45.1

40 50

7.5 5.59 22.4 10 7.5 — 7.5 20.8 54.4 70

2.9 2.16 7.5 10 10.0 — 10.0 24.1 39.4 40 CAELHEAT016A00 240-3-60 3.7

5.0 2.76 3.73

10.2 12.8

10 10

10.0 10.0

— —

10.0 10.0

24.1 24.1

42.8 46.1

50 50

7.5 5.59 19.4 10 10.0 — 10.0 24.1 54.4 70

2.9 2.16 7.5 10 10.0 — 10.0 24.1 39.4 40 240-3-50 5.0 3.73 15.2 10 10.0 — 10.0 24.1 49.1 50

7.5 5.59 22.8 10 10.0 — 10.0 24.1 58.6 70

2.9 2.16 3.4 10 10.0 — 10.0 12.0 19.3 20

480-3-60 3.7 5.0

2.76 3.73

4.8 6.4

10 10

10.0 10.0

— —

10.0 10.0

12.0 12.0

21.0 23.0

25 25

CAELHEAT017A00 7.5 5.59 9.7 10 10.0 — 10.0 12.0 27.2 30

2.9 2.16 3.4 10 6.9 — 6.9 10.0 16.8 20 400-3-50 5.0 3.73 7.6 10 6.9 — 6.9 10.0 22.0 25

7.5 5.59 11.4 10 6.9 — 6.9 10.0 26.8 35

3.0 2.24 3.8 10 10.0 — 10.0 10.0 17.3 20 CAELHEAT018A00 575-3-60 5.0 3.73 5.1 10 10.0 — 10.0 10.0 19.6 20

7.5 5.59 7.8 10 10.0 — 10.0 10.0 22.1 25

2.9 2.16 7.5 20 15.0 — 15.0 41.7 61.5 70

208-3-60 3.7 5.0

2.76 3.73

10.2 15.3

20 20

15.0 15.0

— —

15.0 15.0

41.7 41.7

65.4 71.1

70 80

7.5 5.59 22.4 20 15.0 — 15.0 41.7 79.6 90

2.9 2.16 7.5 20 20.0 — 20.0 48.1 69.5 70 CAELHEAT019A00 240-3-60 3.7

5.0 2.76 3.73

10.2 12.8

20 20

20.0 20.0

— —

20.0 20.0

48.1 48.1

73.4 76.1

80 80

7.5 5.59 19.4 20 20.0 — 20.0 48.1 84.4 90

40RM014-024

240-3-50 2.9 5.0 7.5

2.16 3.73 5.59

7.5 15.2 22.8

20 20 20

20.0 20.0 20.0

— — —

20.0 20.0 20.0

48.1 48.1 48.1

69.5 79.1 86.4

70 80 90

2.9 2.16 3.4 20 20.0 — 20.0 24.1 34.3 35

480-3-60 3.7 5.0

2.76 3.73

4.8 6.4

20 20

20.0 20.0

— —

20.0 20.0

24.1 24.1

36.1 39.1

40 40

CAELHEAT020A00 7.5 5.59 9.7 20 20.0 — 20.0 24.1 43.2 50

2.9 2.16 3.4 20 13.9 — 13.9 20.0 29.3 30 400-3-50 5.0 3.73 7.6 20 13.9 — 13.9 20.0 45.1 50

7.5 5.59 11.4 20 13.9 — 13.9 20.0 49.2 50

3.0 2.24 3.8 20 20.0 — 20.0 20.1 29.9 30 CAELHEAT021A00 575-3-60 5.0 3.73 5.1 20 20.0 — 20.0 20.1 31.5 35

7.5 5.59 7.8 20 20.0 — 20.0 20.1 34.9 35

2.9 2.16 7.5 30 15.0 7.5 22.5 62.5 87.5 90

208-3-60 3.7 5.0

2.76 3.73

10.2 15.3

30 30

15.0 15.0

7.5 7.5

22.5 22.5

62.5 62.5

90.9 97.2

100 100

7.5 5.59 22.4 30 15.0 7.5 22.5 62.5 106.2 110

2.9 2.16 7.5 30 20.0 10.0 30.0 72.2 99.6 100 CAELHEAT022A00 240-3-60 3.7

5.0 2.76 3.73

10.2 12.8

30 30

20.0 20.0

10.0 10.0

30.0 30.0

72.2 72.2

103.0 106.2

110 110

7.5 5.59 19.4 30 20.0 10.0 30.0 72.2 114.5 125

2.9 2.16 7.5 30 20.0 10.0 30.0 72.2 99.6 100 240-3-50 5.0 3.73 15.2 30 20.0 10.0 30.0 72.2 109.2 110

7.5 5.59 22.8 30 20.0 10.0 30.0 72.2 118.7 125

2.9 2.16 3.4 30 20.0 10.0 30.0 36.1 49.4 50

480-3-60 3.7 5.0

2.76 3.73

4.8 6.4

30 30

20.0 20.0

10.0 10.0

30.0 30.0

36.1 36.1

51.1 53.1

60 60

CAELHEAT023A00 7.5 5.59 9.7 30 20.0 10.0 30.0 36.1 57.2 60

2.9 2.16 3.4 30 13.9 6.9 20.8 30.1 41.8 50 400-3-50 5.0 3.73 7.6 30 13.9 7.9 20.8 30.1 47.1 50

7.5 5.59 11.4 30 13.9 7.9 20.8 30.1 51.8 60

3.0 2.24 3.8 30 20.0 10.0 30.0 30.1 42.4 50 CAELHEAT024A00 575-3-60 5.0 3.73 5.1 30 20.0 10.0 30.0 30.1 44.0 50

7.5 5.59 7.8 30 20.0 10.0 30.0 30.1 47.4 50

52

ELECTRIC HEATER DATA (cont)

HEATER PART NO. UNIT V-PH-Hz

FAN MOTOR ELECTRIC HEATER(S)

MCA* MOCP*Nominal Actual Capacity (kW) FLA

Hp kW FLA Capacity (kW) Stage 1 Stage 2 Total 3.7 2.76 10.2 50 22.6 15.0 37.6 104.3 143.1 150

208-3-60 5.0 3.73 15.3 50 22.6 15.0 37.6 104.3 149.5 150 7.5 5.59 22.4 50 22.6 15.0 37.6 104.3 158.4 175

3.7 2.76 10.2 50 30.0 20.0 50.0 120.3 163.1 175 CAELHEAT025A00 240-3-60 5.0 3.73 12.8 50 30.0 20.0 50.0 120.3 166.4 175

7.5 5.59 19.4 50 30.0 20.0 50.0 120.3 174.6 200

2.9 2.16 7.5 50 30.0 20.0 50.0 120.3 159.7 175

40RM016,024 240-3-50 5.0

7.5 3.73 5.59

15.2 22.8

50 50

30.0 30.0

20.0 20.0

50.0 50.0

120.3 120.3

169.4 178.9

175 200

3.7 2.76 4.8 50 30.0 20.0 50.0 60.1 81.2 90

480-3-60 5.0 3.73 6.4 50 30.0 20.0 50.0 60.1 83.2 90

CAELHEAT026A00 7.5 5.59 9.7 50 30.0 20.0 50.0 60.1 87.3 90

2.9 2.16 3.4 50 20.8 13.9 34.7 50.1 66.9 70 400-3-50 5.0 3.73 7.6 50 20.8 13.9 34.7 50.1 72.1 80

7.5 5.59 11.4 50 20.8 13.9 34.7 50.1 76.9 80

3.0 2.24 3.8 50 30.0 20.0 50.0 50.2 67.5 70 CAELHEAT027A00 575-3-60 5.0 3.73 5.1 50 30.0 20.0 50.0 50.2 69.1 70

7.5 5.59 7.8 50 30.0 20.0 50.0 50.2 72.5 80

208-3-60 7.5 10.0

5.59 7.46

22.4 29.3

20 20

15.0 15.0

— —

15.0 15.0

41.7 41.7

80.1 88.7

90 100

CAELHEAT028A00 240-3-60 7.5 10.0

5.59 7.46

19.4 26.8

20 20

20.0 20.0

— —

20.0 20.0

48.1 48.1

84.3 94.0

90 110

240-3-50 7.5 10.0

5.59 7.46

22.8 32.2

20 20

20.0 20.0

— —

20.0 20.0

48.1 48.1

88.6 100.4

90 110

CAELHEAT029A00 480-3-60 7.5

10.0 5.59 7.46

9.7 13.4

20 20

20.0 20.0

— —

20.0 20.0

24.1 24.1

42.2 46.8

50 50

400-3-50 7.5 10.0

5.59 7.46

11.4 16.1

20 20

13.9 13.9

— —

13.9 13.9

20.0 20.0

39.3 45.2

40 50

CAELHEAT030A00 40RM028,034

575-3-60 7.5 10.0

5.59 7.46

7.8 10.3

20 20

20.0 20.0

— —

20.0 20.0

20.1 20.1

34.9 38.0

35 40

208-3-60 7.5

10.0 5.59 7.46

22.4 29.3

40 40

15.0 15.0

15.0 15.0

30.0 30.0

83.4 83.4

132.2 140.9

150 150

CAELHEAT031A00 240-3-60 7.5 10.0

5.59 7.46

19.4 26.8

40 40

20.0 20.0

20.0 20.0

40.0 40.0

96.2 96.2

144.5 153.8

150 175

240-3-50 7.5 10.0

5.59 7.46

22.8 32.2

40 40

20.0 20.0

20.0 20.0

40.0 40.0

96.2 96.2

148.8 160.5

150 175

CAELHEAT032A00 480-3-60 7.5

10.0 5.59 7.46

9.7 13.4

40 40

20.0 20.0

20.0 20.0

40.0 40.0

48.1 48.1

72.3 76.9

80 80

400-3-50 7.5 10.0

5.59 7.46

11.4 16.1

40 40

13.9 13.9

13.9 13.9

27.8 27.8

40.1 40.1

64.4 70.2

70 80

CAELHEAT033A00 575-3-60 7.5 10.0

5.59 7.46

7.8 10.3

40 40

20.0 20.0

20.0 20.0

40.0 40.0

40.2 40.2

60.0 63.1

60 70

LEGEND

FLA — Full Load Amps Hp — Horsepower MCA — Minimum Circuit Amps MOCP — Maximum Overcurrent Protection (Amps)

*Values shown are for single-point connection of electric heat accessory and air handler.

†Single-phase motors. All other motors are 3-phase.

NOTES: 1. Electrical resistance heaters are rated at 240 v, 480 v, or 575 v. To determine

heater capacity (kW) at unit nameplate multiply the 240-v, 480-v, or 575-v ca-pacity (kW) by the factor shown in the table below for the unit voltage.

2. The following equation converts kW of heat energy to Btuh: kW x 3,412 = Btuh.

3. Heater contactor coils are 24 v and require 8 va holding current. 4. Electric heaters are tested and ETL approved at maximum total external static

pressure of 1.9 in. wg. 5. MCA and MOCP values apply to both standard and alternate factory-supplied

motors.

HEATER RATING

VOLTAGE

ACTUAL HEATER VOLTAGE

200 208 230 240 400 440 460 480 550 575 600

240 0.694 0.751 0.918 1 — — — — — — —

480 — — — — 0.694 0.84 0.918 1 — — —

575 — — — — — — — — 0.915 1 1.089

53

Electrical data (cont)ELECTRIC HEATER DATA (cont)

HEATER PART NO. UNIT V-PH-Hz

FAN MOTOR ELECTRIC HEATER(S)

MCA* MOCP*Nominal Actual Capacity (kW) FLA

Hp kW FLA Capacity (kW) Stage 1 Stage 2 Total

208-3-60 7.5 10.0

5.59 7.46

22.4 29.3

50 50

22.6 22.6

15.0 15.0

37.6 37.6

104.3 104.3

158.3 166.9

175 175

CAELHEAT034A00 240-3-60 7.5 10.0

5.59 7.46

19.4 26.8

50 50

30.0 30.0

20.0 20.0

50.0 50.0

120.3 120.3

174.6 183.9

200 200

240-3-50 7.5 10.0

5.59 7.46

22.8 32.2

50 50

30.0 30.0

20.0 20.0

50.0 50.0

120.3 120.3

178.9 190.6

200 200

CAELHEAT035A00 480-3-60 7.5

10.0 5.59 7.46

9.7 13.4

50 50

30.0 30.0

20.0 20.0

50.0 50.0

60.1 60.1

87.3 91.9

90 100

400-3-50 7.5 10.0

5.59 7.46

11.4 16.1

50 50

20.8 20.8

13.9 13.9

34.7 34.7

50.1 50.1

76.9 82.8

80 90

CAELHEAT036A00 40RM028,034

575-3-60 7.5 10.0

5.59 7.46

7.8 10.3

50 50

30.0 30.0

20.0 20.0

50.0 50.0

50.2 50.2

72.5 75.6

80 80

208-3-60 7.5

10.0 5.59 7.46

22.4 29.3

70 70

30.0 30.0

22.6 22.6

52.6 52.6

145.9 145.9

173.9 182.6

175 200

CAELHEAT037A00 240-3-60 7.5 10.0

5.59 7.46

19.4 26.8

70 70

40.0 40.0

30.0 30.0

70.0 70.0

168.4 168.4

192.6 201.9

200 225

240-3-50 7.5 10.0

5.59 7.46

22.8 32.2

70 70

40.0 40.0

30.0 30.0

70.0 70.0

168.4 168.4

196.9 208.6

200 225

CAELHEAT038A00 480-3-60 7.5

10.0 5.59 7.46

9.7 13.4

70 70

40.0 40.0

30.0 30.0

70.0 70.0

84.2 84.2

96.3 100.9

100 110

400-3-50 7.5 10.0

5.59 7.46

11.4 16.1

70 70

27.8 27.8

20.8 20.8

48.6 48.6

70.2 70.2

84.4 90.3

90 100

CAELHEAT039A00 575-3-60 7.5 10.0

5.59 7.46

7.8 10.3

70 70

40.0 40.0

30.0 30.0

70.0 70.0

70.3 70.3

80.0 83.2

90 90

LEGEND

FLA — Full Load Amps Hp — Horsepower MCA — Minimum Circuit Amps MOCP — Maximum Overcurrent Protection (Amps) *Values shown are for single-point connection of electric heat accessory and air handler.

†Single-phase motors. All other motors are 3-phase.

NOTES: 1. Electrical resistance heaters are rated at 240 v, 480 v, or 575 v. To determine

heater capacity (kW) at unit nameplate multiply the 240-v, 480-v, or 575-v ca-pacity (kW) by the factor shown in the table below for the unit voltage.

2. The following equation converts kW of heat energy to Btuh: kW x 3,412 = Btuh.

3. Heater contactor coils are 24 v and require 8 va holding current. 4. Electric heaters are tested and ETL approved at maximum total external static

pressure of 1.9 in. wg. 5. MCA and MOCP values apply to both standard and alternate factory-supplied

motors.

HEATER RATING

VOLTAGE

ACTUAL HEATER VOLTAGE

200 208 230 240 400 440 460 480 550 575 600

240 0.694 0.751 0.918 1 - - - - - - -480 - - - - 0.694 0.84 0.918 1 - - -575 - - - - - - - - 0.915 1 1.089

54

Typical piping and wiring

VERTICAL INSTALLA TION - 40RM (TYPICAL)

LEGEND NOTES: NEC - National Electrical Code 1. All piping must follow standard refrigerant piping techniques. Refer to Carrier System Design TXV - Thermostatic Expansion Valve Manual for details.

2. All wiring must comply with the applicable local and national codes. Piping 3. Wiring and piping shown are general points-of-connection guides only and are not intended *Field supplied. for, or to include all details for, a specific installation. ²Double riser may be required. Consult con- 4. Liquid line solenoid valve (solenoid drop control) is recommended to prevent refrigerant

densing unit product data catalog for migration to the compressor. details. 5. Internal factory-supplied TXVs not shown.

55

Typical piping and wiring (cont)

HORIZONT AL INSTALLA TION - 40RM (TYPICAL)

LEGEND 2. All wiring must comply with the applicable local and national codes. NEC - National Electrical Code 3. Wiring and piping shown are general points-of-connection guides TXV - Thermostatic Expansion Valve only and are not intended for, or to include all details for, a spe­

cific installation. *Accessory item. 4. Liquid line solenoid valve (solenoid drop control) is recommended ²Field supplied. to prevent refrigerant migration to the compressor.

5. Internal factory-supplied TXVs not shown. NOTES: 1. All piping must follow standard refrigerant piping techniqes. Refer

to Carrier System Design Manual for details.

56

WIRE ROUTING, BASE UNIT - 40RM,

WIRE ROUTING, UNIT WITH ELECTRIC HEAT - 40RM,

NEC - National Electrical Code

57

Typical piping and wiring (cont)

CONTROL WIRING SCHEMA TIC - TYPICAL

EQUIP GND HC HTR IFC IFM TB

LEGEND - Equipment - Ground - Heater Contactor - Heater Element - Indoor Fan Contactor - Indoor Fan Motor - Terminal Block

Factory Wiring Field Wiring

58

Application data Operating limits The air handler fan must alwaysbe operating when the Maximum fan speed-40RM007-024

condensingunit is operating. . . . . . . . . . . . . . . . . 1200 rpm (20 r/s) Ductwork should be sized according to unit size, not

building load. For larger units with two fans, a split duct 40RM028,034 . . . . . . . . . . . . . . . . 1100 rpm (18.3 r/s) transition is recommendedat the fan outlets, but a plenum

General can be usedwith slight reduction in external static pressure capability.

Selectequipment to match or to be slightly lessthan peak For variable air volume (VAV) systemswith supply-to­load. This providesbetter humidity control, lessunit cycling,

and lesspart-load operation. Equipment shouldbe selected return air recycling,usethe equipment room asa return air

to perform at no lessthan 300 cfm/ton (40 L/s per kW). plenum.

FACTOR Y-INSTALLED NOZZLE AND DISTRIBUTOR DATA

UNIT TXV Qty...Part No.*

DISTRIBUTOR Qty...Part No.*

FEEDER TUBES PER DISTRIBUTOR

Qty...Size (in.) NOZZLE

Qty...Part No.

40RM007 1...XVE-5 1...1116 12...1/4 1...E5 40RM008 1...SVE-8 1...1126 15...1/4 1...C6 40RM012 2...XVE-4 2...1115 9...1/4 2...E4 40RM014 2...XVE-5 2...1115 9...1/4 2...E5 40RM016 2...XVE-8 2...1116 12...1/4 2...E6 40RM024 2...XVE-10 2...1116 13...1/4 2...E8 40RM028 2...EBSVE-11 2...1126 15...1/4 2...C10 40RM034 2...SVE-15 2...1126 18...1/4 2...C12

*Sporlan Valve Co. part numbers shown.

59

Application data (cont) FAN MOTOR DATA

STANDARD MOTOR - ENGLISH

UNIT 40RM 007

40RM 008

40RM 012

40RM 014

40RM

016 40RM 024

40RM 028

40RM 034

208/230-1-60 Speed (rpm) 1725 1725 - - - - - -Hp 1.3 2.4 - - - - - -Frame (NEMA) 56Y 56Y - - - - - -Shaft Dia (in.) 5/8 5/8 - - - - - -

208/230-3-60 and 460-3-60 Speed (rpm) 1725 1725 1725 1725 1725 1745 1745 1745 Hp 2.4 2.4 2.4 2.9 3.7 5.0 7.5 10.0 Frame (NEMA) 56Y 56Y 56Y 56Y 56Y S184T S213T S215T Shaft Dia (in.) 5/8 5/8 5/8 7/8 7/8 11/8 13/8 13/8

575-3-60 Speed (rpm) 1725 1725 1725 1725 1725 1745 1755 1755 Hp 1.0 2.0 2.0 3.0 3.0 5.0 7.5 10.0 Frame (NEMA) 56 56HZ 56HZ 56HZ 56HZ 184T S213T D215T Shaft Dia (in.) 5/8 7/8 7/8 7/8 7/8 11/8 13/8 13/8

230-3-50 and 400-3-50 Speed (rpm) 1425 1425 1425 1425 1425 1425 1425 1425 Hp 2.4 2.4 2.9 2.9 2.9 5.0 7.5 10.0 Frame (NEMA) 56Y 56Y 56Y 56Y 56Y 184T S213T S215T Shaft Dia (in.) 5/8 5/8 7/8 7/8 7/8 11/8 13/8 13/8

NEMA - National Electrical Manufacturers Association (U.S.A.)

ALTERNATE MOTOR - ENGLISH

UNIT 40RM 007

40RM

008 40RM

012 40RM 014

40RM

016 40RM 024

40RM 028

208/230-1-60 Speed (rpm) 1725 1725 - - - - -Hp 2.4 2.4 - - - - -Frame (NEMA) 56Y 56Y - - - - -Shaft Dia (in.) 5/8 7/8 - - - - -

208/230-3-60 and 460-3-60 Speed (rpm) 1725 1725 1725 1725 1725 1745 1745 Hp 2.9 2.9 3.7 3.7 5.0 7.5 10.0 Frame (NEMA) 56Y 56Y Y56Y Y56Y S184T S213T S215T Shaft Dia (in.) 7/8 7/8 7/8 7/8 11/8 13/8 13/8

575-3-60 Speed (rpm) 1725 1725 1725 1745 1745 1755 1750 Hp 2.0 3.0 3.0 5.0 5.0 7.5 10.0 Frame (NEMA) 56HZ 56HZ 56HZ 184T 184T S213T D215T Shaft Dia (in.) 7/8 7/8 7/8 11/8 11/8 13/8 13/8

230-3-50 and 400-3-50 Speed (rpm) 1425 1425 1425 1425 1425 1425 1425 Hp 2.4 2.9 5.0 5.0 5.0 7.5 10.0 Frame (NEMA) 56Y 56Y S184T S184T S184T S213T S215T Shaft Dia (in.) 7/8 7/8 7/8 11/8 11/8 13/8 13/8

NEMA - National Electrical Manufacturers Association (U.S.A.)

60

Application data (cont) STANDARD DRIVE DATA, 60 Hz - ENGLISH

UNIT 40RM 007

40RM 008

40RM 012

40RM 014

40RM 016

40RM 024

40RM 028

40RM 034

MOTOR DRIVE Motor Pulley Pitch Diameter (in.) 2.4-3.4 2.8-3.8 3.4-4.4 2.8-3.8 2.8-3.8 3.7-4.7 4.3-5.3 4.3-5.3

Pulley Factory Setting Full Turns Open 2.5 2.5 2.5 2.5 2.5 3.0 3.0 3.0

FAN DRIVE Pulley Pitch Dia (in.) 8.8 8.8 8.8 9.0 9.0 9.4 11.0 11.0 Pulley Bore (in.) 1 1 1 1 7/16 1 7/16 1 7/16 1 15/16 1 15/16

Belt No. - Section 1-A 1-A 1-A 1-A 1-A 2-B 2-B* 2-B*

Belt Pitch (in.) 40.3 41.3 42.3 42.3 42.3 41.8 (2) 42.8 (2) 43.8

(2) 42.8 (2) 43.8

FAN SPEEDS (rpm) Factory Setting 568 647 764 632 632 771 752 752 Range 470-666 549-745 666-863 537-728 537-728 679-863 682-841 674-831 Max Allowable Speed (rpm) 1200 1200 1200 1200 1200 1200 1100 1100 Change per 1/2 Turn of Moveable Motor Pulley Flange

19.6 19.6 19.7 19.1 19.1 15.3 13.1 13.1

MAX FULL TURNS FROM CLOSED POSITION 5 5 5 5 5 6 6 6

SHAFTS CENTER DISTANCE 10.44­ 10.44­ 10.44­ 10.44­ 10.44­ 9.12­ 6.67­ 6.67­(in.) 12.32 12.32 12.32 12.32 12.32 10.99 9.43 9.43

*Four belts shipped with unit. Use correct set of 2 belts sized according to the pulley setting.

MEDIUM-ST ATIC DRIVE DATA, 60 Hz - ENGLISH

UNIT 40RM 007

40RM 008

40RM 012

40RM 014

40RM 016

40RM 024

40RM 028

40RM 034

MOTOR DRIVE Motor Pulley Pitch Diameter (in.) 3.4-4.4 3.4-4.4 3.4-4.4 3.4-4.4 3.7-4.7 4.3-5.3 4.3-5.3 4.3-5.3

Pulley Factory Setting Full Turns Open 2.5 2.5 2.5 2.5 3.0 3.0 3.0 3.0

FAN DRIVE Pulley Pitch Dia (in.) 8.8 8.0 8.0 8.2 8.6 9.4 9.4 9.4 Pulley Bore (in.) 1 1 1 1 7/16 1 7/16 1 7/16 1 15/16 1 15/16

Belt No. - Section 1-A 1-A 1-A 1-A 1-B 2-B 2-B* 2-B*

Belt Pitch (in.) 42.3 40.3 40.3 41.3 41.8 41.8 (2) 38.8 (2) 39.8

(2) 38.8 (2) 39.8

FAN SPEEDS (rpm) Factory Setting 764 841 841 820 842 881 881 881 Range 666-863 733-949 733-949 715-926 742-943 798-984 798-984 798-984 Max Allowable Speed (rpm) 1200 1200 1200 1200 1200 1200 1100 1100 Change per 1/2 Turn of Moveable Motor Pulley Flange

19.7 21.6 21.6 21.1 16.7 15.3 15.3 15.3

MAX FULL TURNS FROM CLOSED POSITION 5 5 5 5 6 6 6 6

SHAFTS CENTER DISTANCE 10.44­ 10.44­ 10.44­ 10.44­ 10.44­ 9.16­ 6.67­ 6.67­(in.) 12.32 12.32 12.32 12.32 12.32 10.99 9.43 9.43

*Four belts shipped with unit. Use correct set of 2 belts sized according to the pulley setting.

61

HIGH-ST ATIC DRIVE DATA, 60 Hz - ENGLISH

UNIT 40RM 007

40RM 008

40RM 012

40RM 014

40RM 016

40RM 024

40RM 028

40RM 034

MOTOR DRIVE Motor Pulley Pitch Diameter (in.) 3.4-4.4 3.4-4.4 3.4-4.4 3.7-4.7 4.3-5.3 4.3-5.3 4.3-5.3 4.3-5.3

Pulley Factory Setting Full Turns Open 2.5 2.5 2.5 3.0 3.0 3.0 3.0 3.0

FAN DRIVE Pulley Pitch Dia (in.) 7.0 6.0* 6.0 7.4 7.9 7.4 8.6 8.6 Pulley Bore (in.) 1 1 1 1 7/16 1 7/16 1 7/16 1 15/16 1 15/16

Belt No. - Section 1-A 1-A 1-A 1-B 1-B 2-B 2-B 2-B Belt Pitch (in.) 41.3 37.3 37.3 39.8 39.8 36.8 37.8 37.8

FAN SPEEDS (rpm) Factory Setting 961 1121 1121 979 1060 1118 1024 1024

Range 838­1084

978­1200*²

978­1200²

873­1096

950­1171

1014­1200²

873­1075

873­1075

Max Allowable Speed (rpm) 1200 1200 1200 1200 1200 1200 1100 1100 Change per 1/2 Turn of Moveable Motor Pulley Flange

24.6 28.7 28.7 19.4 18.4 19.4 16.7 16.7

MAX FULL TURNS FROM CLOSED POSITION 5 5 5 6 6 6 6 6

SHAFTS CENTER DISTANCE (in.)

10.44­12.32

10.44­12.32

10.44­12.32

10.44­12.32**

9.16­10.99

8.16­10.02

6.67­9.43

6.67­9.43

*Values for 3-phase motor shown. For single-phase motor, pulley pitch diameter is 7 in. and resulting fan speed is 837-1096 rpm.

²It is possible to adjust drive so that fan speed exceeds maximum allowable. DO NOT exceed 1200 rpm.

**575-v unit has a center distance of 9.16-10.99.

62

Guide Specifications 38ARZ007-012 Commercial Air-Cooled Condensing Units HVAC Guide Specifications Size Range: 6 to 10 Tons, Nominal Carrier Model Numbers: 38ARZ, Sizes 007-012 Part 1 — General 1.01 SYSTEM DESCRIPTION Outdoor-mounted, air-cooled condensing unit suitable for on-the-ground or rooftop installation. Unit shall consist of a reciprocating or scroll air-conditioning compressor assembly, an air-cooled coil, propeller- type condenser fans, and a control box. Unit shall discharge supply air upward as shown on contract drawings. Unit shall be used in a refrigeration circuit matched with a packaged air-handling unit. 1.02 QUALITY ASSURANCE A. Unit shall be rated in accordance with ARI Standard 360-2000. B. Unit construction shall comply with ANSI/ASHRAE 15 safety code latest revision and comply with NEC. C. Unit shall be constructed in accordance with UL 1995 standard. D. Unit cabinet shall be capable of withstanding 500-hour salt spray exposure per ASTM B117 (scribed specimen). E. Air-cooled condenser coils for (38ARZ) shall be leak tested at 200 psig, and pressure tested at 428 psig. F. Unit shall be manufactured in a facility registered to ISO 9001:2000 manufacturing quality standard. 1.03 DELIVERY, STORAGE, AND HANDLING Unit shall be shipped as single package only, and shall be stored and handled according to unit manufacturer’s recommendations. 1.04 WARRANTY (FOR INCLUSION BY SPECIFYING ENGINEER.) Part 2 — Products 2.01 EQUIPMENT A. General: Factory-assembled, single piece, air-cooled condensing unit. Contained within the unit enclosure shall be all factory wiring, piping, controls, compressor, holding charge (R-22), and special features required prior to field start-up. B. Unit Cabinet: 1. Unit cabinet shall be constructed of galvanized steel, bonderized and coated with a prepainted baked enamel finish.

2. A heavy-gage roll-formed perimeter base rail with forklift slots and lifting holes shall be provided to facilitate rigging. C. Fans: 1. Condenser fans shall be direct driven, propeller type, discharging air vertically upward. 2. Fan blades shall be balanced. 3. Condenser fan discharge openings shall be equipped with PVC-coated steel wire safety guards. 4. Condenser fan and motor shaft shall be corrosion resistant. D. Compressor: 1. Compressor shall be of the hermetic scroll type 2. Compressor shall be mounted on rubber grommets. 3. Compressors shall include overload protection. 4. Compressors shall be equipped with a crankcase heater. 5. Compressor shall be equipped with internal high discharge temperature protection (38ARZ007 and 012 only). E. Condenser Coil: 1. Condenser coil shall be air-cooled and circuited for integral subcooler. 2. Coil shall be constructed of aluminum fins (copper fins optional) mechanically bonded to internally grooved seamless copper tubes which are then cleaned, dehydrated, and sealed. F. Refrigeration Components: Refrigeration circuit components shall include liquid line service valve, suction line service valve, a full charge of compressor oil, and a holding charge of refrigerant. G. Controls and Safeties: 1. Minimum control functions shall include: a. Control wire terminal blocks. b. Compressor lockout on auto-reset safety until reset from thermostat. 2. Minimum safety devices which are equipped with automatic reset (after resetting first at thermostat), shall include: a. High discharge pressure cutout. b. Low pressure cutout. c. High discharge temperature cutout (38ARZ008 only). H. Operating Characteristics: 1. The capacity of the condensing unit shall meet or exceed _____ Btuh at a suction temperature of

63

_____ F. The power consumption at full load shall not exceed _____ kW. 2. The combination of the condensing unit and the evaporator or fan coil unit shall have a total net cooling capacity of _____ Btuh or greater at conditions of _____ cfm entering-air temperature at the evaporator at _____ F wet bulb and _____ F dry bulb, and air entering the condensing unit at _____F. 3. The system shall have an EER of _____ Btuh/ Watt or greater at standard ARI conditions. I. Electrical Requirements: 1. Nominal unit electrical characteristics shall be _____ v, 3-ph, 60 Hz. The unit shall be capable of satisfactory operation within voltage limits of ____ v to _____ v. 2. Unit electrical power shall be single-point connection. 3. Unit control circuit shall contain a 24-v transformer for unit control. J. Special Features: 1. Low-Ambient Temperature Control: A low-ambient temperature control shall be available as a field-installed accessory. This low-ambient control shall regulate speed of the condenser-fan motors in response to the saturated condensing temperature of the unit. The control shall maintain correct condensing pressure at outdoor temperatures down to –20 F. 2. Gage Panel Package: Gage panel package shall include a suction and discharge pressure gage. 3. Optional Condenser Coil Materials: a. Pre-Coated Aluminum-Fin Coils: Coils shall have a durable epoxy-phenolic coating to provide protection in mildly corrosive coastal

environments. Coating shall be applied to the aluminum fin stock prior to the fin stamping process to create an inert barrier between the aluminum fin and copper tube. Epoxy-phenolic barrier shall minimize galvanic action between dissimilar metals. b. Copper-Fin Coils: Coils shall be constructed of copper-fins mechanically bonded to copper-tubes and copper tube sheets. A polymer strip shall prevent coil assembly from contacting sheet metal coil pan to minimize potential for galvanic corrosion between the coil and pan. All copper construction shall provide protection in moderate coastal environments. 4. Thermostat Controls: a. Programmable multi-stage thermostat shall have 7-day clock, holiday scheduling, large backlit display, remote sensor capability, and Title 24 compliance. b. Commercial Electronic Thermostat shall have 7-day timeclock, auto-changeover, multi-stage capability, and large LCD (liquid crystal display) temperature display. c. Carrier PremierLink™ Controller: This control will function with CCN (Carrier Comfort Network®) and ComfortVIEW™ software. It shall also be compatible with ComfortLink™ controllers. It shall be ASHRAE 62-99 compliant and Internet ready. It shall accept a CO2 sensor in the conditioned space and be Demand Control Ventilation (DCV) ready. The communication rate must be 38.4K or faster. It shall include an integrated economizer controller.

64

Guide specifications— 38ARD014-028 Commercial Air-Cooled Condensing Units HVAC Guide Specifications Size Range: 12 to 20 Tons, Nominal Carrier Model Number: 38ARD, Sizes 014-028 Part 1 — General 1.01 SYSTEM DESCRIPTION Outdoor-mounted, air-cooled condensing unit suitable for on-the-ground or rooftop installation. Unit shall have 2 independent refrigeration circuits. Unit shall consist of dual scroll compressors, an aircooled coil, propeller-type condenser fans, and a control box. Unit shall discharge supply air upward as shown on contract drawings. Unit shall be used in a refrigeration circuit matched with a packaged airhandling unit. 1.02 QUALITY ASSURANCE A. Unit shall be rated in accordance with ARI Standard 360-2000, and shall be certified and listed in the latest ARI directory. B. Unit construction shall comply with ANSI/ASHRAE safety code, latest revision, and comply with NEC. C. Unit shall be constructed in accordance with UL 1995 standard and shall carry the UL and UL, Canada label. D. Unit cabinet shall be capable of withstanding 500-hour salt spray exposure per ASTM B117 (scribed specimen). E. Air-cooled condenser coils shall be leak tested at 150 psig, and pressure tested at 480 psig. F. Unit shall be manufactured in a facility registered to ISO 9001:2000 manufacturing quality standard. 1.03 DELIVERY, STORAGE, AND HANDLING Unit shall be shipped as single package only, and shall be stored and handled according to unit manufacturer’s recommendations. 1.04 WARRANTY (FOR INCLUSION BY SPECIFYING ENGINEER.) Part 2 — Products 2.01 EQUIPMENT A. General: Factory-assembled, single piece, air-cooled condensing unit. Contained within the unit enclosure shall be all factory wiring, piping, controls, compressor, holding charge (R-22), and special features required prior to field start-up. B. Unit Cabinet: Unit cabinet shall be constructed of G-90 galvanized steel, bonderized and coated with a prepainted baked enamel finish. C. Fans: 1. Condenser fans shall be direct driven, propellertype, discharging air vertically upward. 2. Fan blades shall be balanced.

3. Condenser fan discharge openings shall be equipped with PVC-coated steel wire safety guards. 4. Condenser fan and motor shaft shall be corrosion resistant. D. Compressor: 1. Compressors shall be of the hermetic scroll type. 2. Compressors shall be mounted on rubber grommets. 3. Compressors shall include overload protection. 4. Compressors shall be equipped with a crankcase heater. 5. Compressors shall be equipped with internal high discharge temperature protection (38ARD016 and 028 only). E. Condenser Coil: 1. Condenser coil shall be air-cooled and circuited for integral subcooler. 2. Coil shall be constructed of aluminum fins (copper fins optional) mechanically bonded to internally grooved seamless copper tubes which are then cleaned, dehydrated, and sealed. F. Refrigeration Components: Refrigeration circuit components shall include high side pressure relief device, liquid line service valve, suction line service valve, a full charge of compressor oil, and a holding charge of refrigerant. G. Controls and Safeties: 1. Minimum control functions shall include: a. Power and control wire terminal blocks. b. Compressor lockout on auto-reset safety until reset from thermostat. c. Recycle time delay of five minutes to prevent compressor short cycling. 2. Minimum safety devices shall include: Automatic reset (after resetting first at thermostat): a. High discharge pressure cutout. b. Loss-of-charge cutout. c. Condenser fan motors to be protected against overload condition by internal overloads. Manual reset at the unit: Electrical overload protection through the use of define-purpose contactors and calibrated, ambient compensated, magnetic trip circuit breakers. Circuit breakers shall open all three phases in the event of an overload in any one of the phases or a single phase condition. H. Operating Characteristics: 1. The capacity of the condensing unit shall meet or exceed _____ Btuh at a suction temperature of _____ F. The power consumption at full load shall not exceed _____ kW.

65

2. The combination of the condensing unit and the evaporator or fan coil unit shall have a total net cooling capacity of _____ Btuh or greater at conditions of _____ cfm entering-air temperature at the evaporator at _____ F wet bulb and _____ F dry bulb, and air entering the condensing unit at _____ F. 3. The system shall have an EER of _____ Btuh/ Watt or greater at standard ARI conditions. I. Electrical Requirements: 1. Nominal unit electrical characteristics shall be _____ v, 3-ph, 60 Hz. The unit shall be capable of satisfactory operation within voltage limits of _____ v to _____ v. 2. Unit electrical power shall be single-point connection. 3. Unit control circuit shall contain a 24-v transformer for unit control. J. Special Features: 1. Low-Ambient Temperature Control: A low-ambient temperature control shall be available as a factory-installed option or as a field-installed accessory. This low-ambient control shall regulate speed of the condenser-fan motors in response to the saturated condensing temperature of the unit. The control shall maintain correct condensing pressure at outdoor temperatures down to –20 F. 2. Gage Panel Package: Gage panel package shall include a suction and discharge pressure gage. 3. Optional Condenser Coil Materials: a. Pre-Coated Aluminum-Fin Coils: Coils shall have a durable epoxy-phenolic coating to provide protection in mildly corrosive coastal

environments. Coating shall be applied to the aluminum fin stock prior to the fin stamping process to create an inert barrier between the aluminum fin and copper tube. Epoxy-phenolic barrier shall minimize galvanic action between dissimilar metals. b. Copper-Fin Coils: Coils shall be constructed of copper-fins mechanically bonded to copper-tubes and copper tube sheets. A polymer strip shall prevent coil assembly from contacting sheet metal coil pan to minimize potential for galvanic corrosion between the coil and pan. All copper construction shall provide protection in moderate coastal environments. 4. Thermostat Controls: a. Programmable multi-stage thermostat with 7-day clock, holiday scheduling, large backlit display, remote sensor capability, and Title 24 compliance. b. Commercial Electronic Thermostat with 7-day timeclock, auto-changeover, multistage capability, and large LCD (liquid crystal display) temperature display. c. Carrier PremierLink™ Controller: This control will function with Carrier Comfort Network® (CCN) and ComfortVIEW™ software. It shall also be compatible with ComfortLink™ controllers. It shall be ASHRAE 62-99 compliant and Internet ready. It shall accept a CO2 sensor in the conditioned space and be Demand Control Ventilation (DCV) ready. The communication rate must be 38.4K or faster. It shall include an integrated economizer controller.

66

Guide specifications 40RM

Commercial Packaged Air-Handling Unit HVAC Guide Specifications SizeRange: 2,400 to 12,000 CFM (1150 to 5650 L/s),

Nominal Airflow 6 to 30 Tons (21 to 105 kW), Nominal Cooling

Carrier Model Numbers: 40RM (Direct-Expansion Coil)

Part 1 - GENERAL 1.01 SYSTEM DESCRIPTION

A. Indoor, packaged air-handling unit for use in commer­cial split systems.Unit shall have a multiposition de­sign and shall be capable of horizontal or vertical installation on a floor or in a ceiling, with or without ductwork. (Only vertical units are to be applied with­out ductwork.)

B. Unit with direct-expansioncoil shall be usedin a re­frigerant circuit with a matching air-cooled con­densing unit.

1.02 QUALITY ASSURANCE

A. Coils shallbe designed & tested in accordance with ASHRAE 15 Safety Code for MechanicalRefrigera­tion (U.S.A.), latest edition.

B. Unit shall be constructed in accordance with ETL (U.S.A.) and ETL, Canada,standardsand shall carry the ETL and ETL, Canada, labels.

C. Unit insulation and adhesive shall comply with NFPA-90A (U.S.A.)requirements for flame spread and smoke generation.

D. Unit shall be manufactured in a facility registered to the ISO 9002 manufacturing quality standard.

E. Direct-expansionand chilledwater coilsshallbe burst and leak testedat 435 psi (2999 kPa).

1.03 DELIVERY AND STORAGE Units shall be stored and handled per manufacturer's recommendations.

Par t 2 - Products 2.01 EQUIPMENT

Indoor mounted,draw-thru, packaged air-handling unit that can be used in a suspended horizontal configu­ration or a vertical configuration. Unit shallconsistof forward-curved belt-driven centrifugal fan(s), motor & driveassembly,prewired fan motor contactor, factory­installedrefrigerant metering devices(direct-expansion coil units), cooling coil, 1-in. (25.4-mm) washable air filters, and condensate drain pans for vertical or hori­zontal configurations.

A. BaseUnit (Painted): 1. Cabinetshall be constructed of zinc coated steel

and polyester powder painted to protect them from corrosion in the harsh Middle Eastern climate and also to increase the colour life in high ultra­violet (UV) radiation regions.

2. Cabinet panels shall be fully insulatedwith 1/2 in.

(12.7-mm) fire-retardant material.

3. Unit shallcontain PVC condensate drain pans for both vertical and horizontal applications. Drain pansshallhaveconnectionson right and left sides of unit to facilitate field connection. Drain pans shallhave the ability to be slopedtoward the right or left side of the unit to prevent standing water from accumulatingin pans.

4. Unit shall have factory-supplied 1-in. (25.4 mm) washable-type filters installedupstream from the cooling coil. Filter access shall be from the front of the unit.

B. Coils: Coils shall consist of 3 rows (40RM, 40RMS), of coppertubes with sine-wave aluminum fins bonded to the tubes by mechanical expansion. Suction and liquid line connectionsor supplyanddischargecon­nections shallbe made on the sameside of the coil.

1. Direct-expansioncoilsshallfeaturefactory-installed thermostatic expansion valves (TXVs) for refrig­erant control. The TXVs shall be capable of ex­ternal adjustment. Direct-expansion heat pump coils shall have a factory-installedbypassline and check valve assemblyaround the TXVs to allow liquid flow from the coil to the outdoor unit during the heating mode. Coil tubing shall be internally rifled to maximize heat transfer.

C. Operating Characteristics:

Unit shall be capable of providing cfm (L/s) airflow at an external static pressureof in. wg (kPag).

D. Motor: Fan motor of the size and electrical characteristics specifiedon the equipment scheduleshall be factory supplied and installed. Motors rated at 1.3 through 3.7 hp (0.97 through 2.76 kW) shall have internal thermal overload pro­tection. Motors rated at 5, 71/2, and 10 hp (3.73, 5.60, and 7.46 kW) shall be protected by a circuit breaker.

67

E. Factory-InstalledOptions: 1. Alternate Motor and Drive:

An alternate motor and/or medium-or high-static drive shall be available to meet the airflow and external static pressure requirements specified on the equipment schedule.

F. Field-InstalledAccessories (ordered from NAO): 1.

2.

3.

Electric Heaters: Heaters for nominal 240, 480, or 575-volt, 3-phase, 60 Hz; and 240, 400-volt, 3 phase, 50 Hz power supplyshallbe factory-suppliedfor field installationasshownon the equipmentdraw­ings.ElectricheatassemblyshallbeETL (U.S.A.) and ETL, Canada, agency approved, and shall have single-point power wiring. Heater assem­bly shallincludecontactorswith 24-V coils, power wiring, 24-v control wiring terminal blocks, and a hinged accesspanel. Electric heatersshall not be usedwith air discharge plenum.

4.

Air Discharge Plenum: Plenumshallbe factory suppliedto provide free­blow air distribution for vertical floor-mounted units. A grille with moveable vanes for hori­zontal or vertical airflow adjustment shall be included. Plenum shall be field-assembledand field-installedon the unit's fan deckfor blow-thru air distribution. Plenum shall not be used with electric heaters.

5.

Return Air Grille: Grille shall be factory supplied for field installa­tion on the unit's return air opening.

6.

Unit Subbase: Subbaseassemblyshall be factory supplied for field installation. Subbase shall elevate floor-mounted vertical units to provide access for correct condensate drain connection.

7.

Economizer: Economizerfor ventilation or ``free'' cooling shall be factory provided for field installationon either return air opening of air handler. For free cool­ing applications,economizershallbe compatible with separate thermostat; economizer dampers shall open when outdoor air enthalpy is suitable for free cooling. Economizershallbe compatible with separate CO2 sensor accessory; economizer dampersshallopen when indoor CO2 level rises abovepredetermined setpoint. Economizershall include enthalpy control and damper actuator.

8.

Thermostat Controls: a. Debonair programmablemulti-stagethermo­

statwith 7-dayclock,holidayscheduling,large ThermoglowŸ display, remote sensorcapa­bility, and Title 24 compliance.

b. TEMP System programmable communicat­ing multi-stage thermostat with fan switch, time clock,LCD display,ÉF/ÉC capability, and CCN compatiblity.

c. CommercialElectronicThermostatwith 7-day time clock, auto-changeover, multi-stageca­pability, and large LCD temperature display.

d. Non-programmablethermostatwith fan switch subbase.

9.

Overhead SuspensionPackage: Package shall include necessary brackets to support units in a horizontal ceiling installation. CO2 Sensor: Sensorshallprovide the ability to signalthe econo­mizer to open when the spaceCO2 levelexceeds the predetermined set point. Sensor shall have the capability of being connected to Comfort Systemrelay pack or to economizer using field­supplied and -installed Honeywell dc adapter no. Q769C1004. CondensateDrain Trap: Trap shall have transparent, serviceabledesign for easycleaning.Kit shall includeoverflow shut­off switch and wiring harnessfor connection to an alarm if desired.

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations