This document is intended for the sole use of Tank Consultants, Inc. and its customers. Any unauthorized reproduction of this document is prohibited. © 2014
Tank Consultants, Inc. A Division of TEAM® Team Industrial Services
4333 West 21st Tulsa, OK 74107 Phone (918) 583-3968
www.tank-consultants.com engineering@tank-consultants.com
API-653 INTERNAL TANK INSPECTION EVALUATION MFL
Revision 0 Dated 10.14.15
Tank No: 2 Product Service: Unknown
Inspection Date September 23, 2015 Grand River Dam Authority
Chouteau, OK
Job TC9338
Inspectors: S. Saxbury (API-653 #50761), A. Majors and S. Barrows
Reviewed By
Terry Wach
PE, API-653 #50849
API-653 INTERNAL TANK INSPECTION EVALUATION Tank No: 2 September 23, 2015 Chouteau, OK Grand River Dam Authority
TC9338 This document is intended for the sole use of Tank Consultants, Inc. and its
customers. Any unauthorized reproduction of this document is prohibited. © 2015 Page 2 of 9
Revision History
Date No Revision
10.14.15 0 Original Report Issued
API-653 INTERNAL TANK INSPECTION EVALUATION Tank No: 2 September 23, 2015 Chouteau, OK Grand River Dam Authority
TC9338 This document is intended for the sole use of Tank Consultants, Inc. and its
customers. Any unauthorized reproduction of this document is prohibited. © 2015 Page 3 of 9
Table of Contents Revision History ......................................................................................................................... 2
Table of Contents ....................................................................................................................... 3
Tank Data .................................................................................................................................. 4
Evaluation Summary .................................................................................................................. 5
General ................................................................................................................................... 5
Foundation ............................................................................................................................. 5
Bottom .................................................................................................................................... 6
External Shell ......................................................................................................................... 7
Internal Shell ........................................................................................................................... 7
Access Structures ................................................................................................................... 8
Appendix .................................................................................................................................... 9
Standard Field Report
Calculations
Survey
Bottom Corrosion Evaluation
Fill Height Shell Corrosion Rate Evaluation
Equipment Calibration
TCI Equipment and Calibration Log
Photographs
API-653 INTERNAL TANK INSPECTION EVALUATION Tank No: 2 September 23, 2015 Chouteau, OK Grand River Dam Authority
TC9338 This document is intended for the sole use of Tank Consultants, Inc. and its
customers. Any unauthorized reproduction of this document is prohibited. © 2015 Page 4 of 9
Tank Data
Description [Units] Tank Type Vertical GPS Location [Latitude Longitude] Nominal Diameter/Width [FT] 34.00 Nominal Height [FT] 24.17 Fill Height [FT] 24.17 Nominal Capacity 3,571 BARRELS Year Built 1979 Built By Unknown Construction Standard API-650 6th Name Plate Information Product Stored Unknown Product Specific Gravity 1.00 Product Flash Point [Degrees Fahrenheit] Flashpoint Pumping In Rate [Barrels/Hour] Pumpinrate Pumping Out Rate Pumpoutrate Foundation Concrete Ringwall Bottom Construction Welded Bottom Installation Date Bottom Slope Cone Up Bottom Coating None Shell Construction Welded Shell Material A283-C Fixed Roof Type Dome Floating Roof Type None Scope of Work - Inspection Type(s) INTERNAL, MFL
API-653 INTERNAL TANK INSPECTION EVALUATION Tank No: 2 September 23, 2015 Chouteau, OK Grand River Dam Authority
TC9338 This document is intended for the sole use of Tank Consultants, Inc. and its
customers. Any unauthorized reproduction of this document is prohibited. © 2015 Page 5 of 9
Evaluation Summary General
Shell Coupling G had dry product staining. The fitting should be removed, a thread sealant applied, and the fitting replaced.
There was a wet product stain on the bottom extension on the southeast side of the tank. If the tank bottom is to be replaced, then no further corrective action is required. If the tank bottom is not to be replaced, the area on the internal cornerweld should be blasted, cleaned and inspected.
The inspection interval is 5 years for external inspections. The next external inspection should be performed by September of 2020.
The inspection interval is 20 years for internal inspections. The next internal inspection should be performed by September of 2035.
Foundation
The tank was surveyed internally. The details of that survey can be found in the Appendix. The settlement data shows the tank to be 0.48 inches out of level with the low point located at or near Survey Point 8 or 93.46 feet counter-clockwise from Survey Point 1. Survey Point 1 was located three feet counter-clockwise from Wwest Manway A, and the survey proceeded counter-clockwise around the tank shell perimeter. The largest out-of-plane settlement was 0.14 inches. A maximum permissible out-of-plane settlement of 0.50 inches was calculated per API-653 Appendix B.3.2.1. None of the survey points exceed this value. No corrective action recommended.
The tank bottom near the shell was inspected for bulges, ridges, sags and edge settlement that might indicate areas of excessive stress. Because the tank shell does not sit on a grade foundation, settlement near the shell was evaluated per API-653, Appendix B, Sections B.3.3 and the associated footnote. The edge settlement at Radials 1, 3, 4, 6, 7 and 8 exceeded 3/8 inches per foot. Radials 1, 6, 7 and 8 were acceptable and did not require corrective action. The tank bottom welds within 13 feet on either side of Radials 3 and 4 and within 5 feet of the shell should be examined using magnetic particle or dye penetrant testing.
API-653 INTERNAL TANK INSPECTION EVALUATION Tank No: 2 September 23, 2015 Chouteau, OK Grand River Dam Authority
TC9338 This document is intended for the sole use of Tank Consultants, Inc. and its
customers. Any unauthorized reproduction of this document is prohibited. © 2015 Page 6 of 9
There was an excessive amount of vegetation growing around the tank. The vegetation should be removed.
Bottom
An extremely limited visual inspection of the tank bottom was performed to locate topside pits 0.070 inches deep and deeper in the bottom plates and 0.055 inches deep and deeper in the critical zone (within three inches of the shell) for a 5-year inspection interval. Areas of corrosion below the thresholds were found in Bottom Plates 9 and 10. The visual inspection could not be completed due to an excessive amount of dirt and product residue. Consideration should be given to replacing the tank bottom. Alternatively, if the bottom is not replaced, the bottom should be blasted, cleaned, and inspected for topside corrosion. Topside pits with 0.135 inches or less remaining wall (0.070 deep and deeper) outside the critical zone should be repaired. Topside pits with 0.155 inches or less of remaining wall (0.055 inches deep and deeper) inside the critical zone should be repaired.
A Magnetic Flux Leakage (MFL) scan was performed on approximately 92 percent of the tank bottom at a remaining wall threshold of 0.135 inches thick in the bottom plates and 0.155 inches thick in the critical zone (within three inches of the shell) for a 5-year inspection interval. There was corrosion below the thresholds on Bottom Plates 1, 2, 3, 4, 6, 7, 8, 10, 11, 12, 13, 14, and 15. The lowest indication found was 0.070 inches located on Bottom Plate 13. If the tank bottom is not replaced, soilside corrosion areas with 0.135 inches or less of remaining wall thickness outside the critical zone should be repaired. Soilside corrosion areas with 0.155 inches or less of remaining wall thickness inside the critical zone should be repaired.
Ultrasonic Edge Scrubs (UES) were performed on the tank bottom at the 8 survey locations. The thicknesses ranged from 0.100 to 0.270 inches. Corrosion at or below the threshold was found at Radials 2, 6, 7 and 8.
Corrosion areas were found in the critical zone that exceeded 24 inches in length. The bottom plates in these areas should be replaced or a finite element analysis should be performed to better determine the stresses from using oversized repair plates and their acceptability.
API-653 INTERNAL TANK INSPECTION EVALUATION Tank No: 2 September 23, 2015 Chouteau, OK Grand River Dam Authority
TC9338 This document is intended for the sole use of Tank Consultants, Inc. and its
customers. Any unauthorized reproduction of this document is prohibited. © 2015 Page 7 of 9
An ultrasonic thickness reading was taken at random on each bottom plate. The thickness readings ranged from 0.248 to 0.470 inches.
The flat-bottom sump was 48 inches in diameter and 24 inches deep. The bottom thicknesses ranged from 0.200 to 0.350 inches. The side wall thicknesses ranged from 0.250 to 0.380 inches. There was a band of corrosion with pitting up to 0.110 inches deep located in the side wall 8 inches above the sump bottom.
External Shell
The fill height analysis found that this tank was adequate for continued service. No corrective action is required.
There were minor buckles in the shell. The buckles and their locations should be noted in the tank record.
Internal Shell
There was light, widespread corrosion on the internal shell. The internal shell had isolated areas of corrosion ranging from approximately 0.010 to 0.050 inches deep near the cornerweld. No repair is required.
Inspection of the internal cornerweld was limited due to product residue and dirt. There was corrosion in the visible areas of the cornerweld. Consideration should be given to cleaning and re-inspecting the cornerweld. The areas of corrosion should be weld repaired.
Shell Items B and J did not appear to penetrate the internal shell.
The internal shell had isolated areas of corrosion ranging from approximately 0.010 to 0.050 inches deep near the cornerweld. No repair is required.
The gauge pole supports lacked pad plates on the internal shell. Consideration should be given to installing pad plates on the internal shell under the gauge pole supports.
API-653 INTERNAL TANK INSPECTION EVALUATION Tank No: 2 September 23, 2015 Chouteau, OK Grand River Dam Authority
TC9338 This document is intended for the sole use of Tank Consultants, Inc. and its
customers. Any unauthorized reproduction of this document is prohibited. © 2015 Page 8 of 9
Access Structures
There was coating failure on the ladder and roof handrail. The areas of coating failure with corrosion should be cleaned and painted.
API-653 INTERNAL TANK INSPECTION EVALUATION Tank No: 2 September 23, 2015 Chouteau, OK Grand River Dam Authority
TC9338 This document is intended for the sole use of Tank Consultants, Inc. and its
customers. Any unauthorized reproduction of this document is prohibited. © 2015 Page 9 of 9
Appendix Standard Field Report
Calculations
Survey
Bottom Corrosion Evaluation
Fill Height Shell Corrosion Rate Evaluation Equipment Calibration
TCI Equipment and Calibration Log Photographs
1.0 TRUECustomer Tank No
City, ST Inspected
Scope Job No
Tank / Nameplate Information Latitude Longitude
34.00 HGT [FT] 24.17 LEN [FT]106.81 FILL HGT 24.17 BARRELS1979 MFG
Other
Edition Appendices
Other
Other
Other
Other Double Bottom Leak Detection
Other
Other Insulated Cut Down and Re-Erected Lap Welded Double Wall
Access/LadderOther
GRAVITY 1.00 API 10.0 Product Heated Level [FT]
Other
Other Primary Seal Internal Vertical Ladder Secondary Seal External Rolling Ladder
External PaintPrevious Inspection History / External Coating DateInternal Inspection
Max Temp [F]Fixed Roof Type Cone Open Dome Geodesic Dome Other
Floating Roof Type None Open Floating Roof Internal Floating Roof
Shell Construction Welded Riveted Other
Spiral Radial Vertical Ladder Catwalk Other
Product Storage Unknown
Bottom Slope Cone Up Cone Down Flat Drain Dry Wedge Unknown Bottom Coating None Thin Film Epoxy Thick Fiberglass Unknown Other
Date Installed
Bottom Construction Welded Riveted Other Date Installed
Cathodic Protection Date Installed
Head Type Flat Dished Hemi Elliptical Other None
Foundation Grade Material Grade Crushed Stone Sand/Soil Concrete Ringwall Ringwall Concrete Pad Steel Saddles Concrete Saddles Saddles Skids Platform/Legs Unknown Other
Other Nameplate Information
Tank Type / DescriptionTank Type Vertical Horizontal Rectangle Tote Other
PWHT - Post Weld Heat TreatConstruction
Standard API-650 API-620 API-12C API-12F UL STI ASME SWRI Unknown
API 6th
Year Built UnknownShell Material A283-C
DIAMETER [FT] BARRELS/GALLONSCircumference [FT] Capacity 3,571
INTERNAL, MFL TC9338
Inspection InformationInspectors S. Saxbury (API-653 #50761), A. Majors and S. Barrows
Scope of Work INTERNAL, MFL
Tank Consultants, Inc. 4333 West 21st Tulsa, OK 74107 (918) 583-3968 tank-consultants.com
Grand River Dam Authority GRDA 2Chouteau, OK 09.23.2015
TCI
Location
This document is intended for the sole use of Tank Consultants, Inc. and its customers.Any unauthorized reproduction is prohibited. © 2015 Page 1 of 20Rev-1.16 - 08.11.15
Customer Tank NoCity, ST InspectedScope Job No
1 OK NOT OK
Other
MIN [IN] MAX [IN]
4 63 7
Saddles [FT]
Number / Quantity Distance Between Saddles Saddle Width [IN] Distance From End
Number / Quantity OKBolt Diameter [IN] Corroded threadsSpacing [FT]
1 OK NOT OK Obvious Settlement Grade sloped toward tank Discontinuous Ringwall Grade against tank Broken Concrete Standing water against tank Exposed Rebar Void areas under tank Washed Out Areas
Saddle Failure Condition(s) No Pad Plates Pad Plates Not Seal Welded Saddle Corrosion
1 OK NOT OK1 Excessive Vegetation Deterioration of dike wall
Buildup of Debris Deterioration of tank berm
Anchors
Loose nuts
Foundation Failure Condition(s)
Housekeeping Around the Tank
Foundation Comments
Comment(s)
Ringwall DimensionsDistance From Shell to Edge of RingwallDistance From Top of Ringwall to Grade
INTERNAL, MFL TC9338
Foundation
Foundation Type / Details Grade Material Grade Crushed Stone Sand/Soil Concrete Ringwall Ringwall Concrete Pad Steel Saddles Concrete Saddles Saddles Skids Platform/Legs Unknown Other
Tank Consultants, Inc. 4333 West 21st Tulsa, OK 74107 (918) 583-3968 tank-consultants.com
Grand River Dam Authority 2Chouteau, OK 09.23.2015
TCI
Location
This document is intended for the sole use of Tank Consultants, Inc. and its customers.Any unauthorized reproduction is prohibited. © 2015 Page 2 of 20Rev-1.16 - 08.11.15
Customer Tank NoCity, ST InspectedScope Job No
1 OK NOT OK
Peeling Cracking Areas Not Coated Thin 1 Stained
OK NOT OKNone Corrugated Banded
Sprayed Foam
Torn Holes Areas Not InsulatedDescribe Coating / Insulation Problems Found
External Shell Corrosion 1 OK NOT OK Active Corrosion Shell Corrosion Old Corrosion Bottom Extension Corrosion Corrosion Damage
Describe Corrosion Problems Found
External Shell Welds Condition(s) 1 OK NOT OK Pinholes or Porosity Lack of fusion Cracks Slag Corrosion Weld Plug Tested Arc Strikes
Describe Weld Problems Found
Shell Distortion and Buckling 1 OK NOT OK Major Buckles Distortion Around Piping
1 Minor BucklesDescribe Shell Distortion and Buckling Problems Found
Shell Improper Construction Practices 1 OK NOT OK Square Corner insert plates Telltale Holes Plugged Weld Spacings not to API STD's No Telltale Holes Lap Welded Patches Other Un-Reinforced Penetrations
Describe Shell Improper Construction Practices Problems Found
Comments
Comments
Comments
Comments
Shell InsulationType
Condition(s) Like New Good Fair Poor None
Comments
INTERNAL, MFL TC9338
External Shell
External Shell CoatingCondition(s) Like New Good Fair Poor None
Tank Consultants, Inc. 4333 West 21st Tulsa, OK 74107 (918) 583-3968 tank-consultants.com
Grand River Dam Authority 2Chouteau, OK 09.23.2015
TCI
Location
This document is intended for the sole use of Tank Consultants, Inc. and its customers.Any unauthorized reproduction is prohibited. © 2015 Page 3 of 20Rev-1.16 - 08.11.15
Customer Tank NoCity, ST InspectedScope Job NoINTERNAL, MFL TC9338
External Shell
Tank Consultants, Inc. 4333 West 21st Tulsa, OK 74107 (918) 583-3968 tank-consultants.com
Grand River Dam Authority 2Chouteau, OK 09.23.2015
TCI
Location
Ground Cables OK NOT OK Broken Cable 1 None Found Broken Shell Attachment
OK NOT OKNone
Tape Does Not Have Free Movement Floats, Guides or Attachments Not in Working Order
Product Leaks 0 OK NOT OK
Additional Shell Problems Found
1 OK NOT OK Corrosion Detached Buckling Broken Welds No Top Angle
Quantity SizeRecord Qty and Size of All Shell Vents
Shell Vents Distance From Roof
Comments
Thickness 0.250Distance From Roof 0
Vertical Leg 2.5Horizontal Leg 2.5
Comments
Top Angle, Wind Girder and Shell Vents
Coating Failure
Dimensions [IN] Top Angle Wind Girder
Level GaugeEquipment Manufacturer Type/Model
CommentsCoupling G had dry product staining.
There was a wet product stain on the bottom extension on the southeast side of the tank.
This document is intended for the sole use of Tank Consultants, Inc. and its customers.Any unauthorized reproduction is prohibited. © 2015 Page 4 of 20Rev-1.16 - 08.11.15
Customer Tank No 2City, ST Location Inspected 09.23.2015Scope Job No TC9338
REPADSHAPES
[FT] [IN] [IN] NOZZLELABEL DESCRIPTION LOCATION HEIGHT SIZE TT1 SHAPE WID HGT THK NECK SPACE WELD TO3
A Manway 0.00 30.00 24.00 1 62.00 50.00 0.258 0.499 4.25 CWB Plug 20.45 18.00 4.00 15.00 CWC Nozzle 26.44 12.00 4.00 1 16.00 12.00 0.242 0.342 5.00 CWD Nozzle (R3) 38.90 6.00 1E Nozzle 39.80 30.00 6.00 1 20.00 16.00 0.241 0.441 21.50 CWF Nozzle (R3) 40.80 3.00 1G Coupling 45.60 18.00 1.25 16.50 CWH Vertical Ladder 53.25I Nozzle (R3, Blinded) 80.00 6.00 1J Plug 84.28 18.00 4.00 15.50 CW
Shell Nozzles andAppurtenances
1: TT (Tell Tale Hole): 0 = NO, 1 = YES(Un-plugged), P=YES(Plugged) 3: WELD TO: CW=Cornerweld, AR=Repad of Item A, A=Weld of Item A, HW=Horizontal Weld, VW=Vertical Weld, TS=Tombstone Type Repad
REPAD [IN] WELD SPACING [IN]
Tank Consultants, Inc. 4333 West 21st Tulsa, OK 74107 (918) 583-3968 tank-consultants.com
Grand River Dam AuthorityChouteau, OKINTERNAL, MFL
TCI
RND RECREC HEX TMB
This document is intended for the sole use of Tank Consultants, Inc. and its customers.Any unauthorized reproduction is prohibited. © 2015 Page 5 of 20Rev-1.16 - 08.11.15
Customer 2City, ST 09.23.2015
Location TC9338Scope
Shell Vertical Seams
Vertical Seam Locations - For Ring 11 5.78 15 292 32.50 16 303 59.22 17 314 85.94 18 325 19 336 20 347 21 358 22 369 23 37
10 24 3811 25 3912 26 4013 27 4114 28 42
Shell Ring Heights, Thickness Readings and Construction
Total 24.01 0.03125 Joint NbrRing Height [FT] Nominal Bottom Middle Top Type Rivets Rivet Seal Type
1A 7.96 0.281 0.265 0.263 0.260
1B 0.249 0.252 0.251
1C 0.262 0.262 0.263
1D 0.254 0.257 0.254
2 7.92 0.219 0.202 0.200 0.195
3 7.92 0.219 0.198 0.200 0.202
Job No
INTERNAL, MFL
For Ring 1: Shell plates measured at the four quadrants. Courses measured at 12" above the bottom, the middle of the course and 12" below the top of the course. For Upper Rings: Thickness of each ring measured at 3 points minimum per ring. Joint Type - butt welded, lap welded, butt riveted, lap riveted. Rivet Seal Type - Unsealed Rivets, Seal Welded Rivets, Expoxy Sealed Rivets.
Thickness [IN] Readings @
Tank Consultants, Inc. 4333 West 21st Tulsa, OK 74107 (918) 583-3968 tank-consultants.com
Grand River Dam Authority Tank No
Chouteau, OK Inspected
TCI
This document is intended for the sole use of Tank Consultants, Inc. and its customers.Any unauthorized reproduction is prohibited. © 2015 Page 6 of 20Rev-1.16 - 08.11.15
Customer Tank No
City, ST Inspected
Scope Job No
Record the General Nozzle Orientation on Diagram Below.Inspect and Record Shell Nozzle Details on the Shell Nozzles and Appurtenances PageStarting Location Direction
Nozzle Layout
Comments
INTERNAL, MFL TC9338
West Manway A CCW
Nozzle Layout \\nasserver\clients\GRDA\TC9338\Tank 2 GRDA TC9338 Nozzle Layout.wmf
Tank Consultants, Inc. 4333 West 21st Tulsa, OK 74107 (918) 583-3968 tank-consultants.com
Grand River Dam Authority 2Chouteau, OK 09.23.2015
TCI
Location
DRAWING NOT TO SCALE
This document is intended for the sole use of Tank Consultants, Inc. and its customers.Any unauthorized reproduction is prohibited. © 2015 Page 7 of 20Rev-1.16 - 08.11.15
Customer Tank NoCity, ST InspectedScope Job No
Access - Stairs, Platforms and Handrails 1 OK NOT OK Broken Welds Cable Members Bent Members Corrosion
1 Coating Failure Chain MembersStairway
Radial Spiral Catwalk 1 Ladder
OtherStructure
Platform Walkway1 Roof Handrail
OtherOSHAREQ
MIN 24"
MIN 24"
MIN 4"
MIN 42"
MAX 96"2
Note1
YES NO YES NO YES NO
REQ'D
REQ'D
OSHA REQ OSHA REQMIN 22" MIN 16"
- MAX 30'
30 - 50 10" - 14"
30" - 36" MIN 7"
NOTE1 MIN 3/4"MAX 96"2 27" - 30"
YES NO MAX 9.5" MAX 8' 1.5" - 12"
Comments
Slip-Resistant (REQ'D) Rung-to-Roof [IN] 8.00NOTES: 1 - 2x2x3/8" or 1.5" pipe minimum 2 - The spacing of uprights may meet the intentions of the OSHA midrail requirement.
Stairways, Platforms, and Handrails - Describe Problems Found
STAIRWAY Properties Cage Verticals [IN] 8.00Midrail (REQ'D) Cage Hoops [FT] 3.92
Upright Member Size Rung Size [IN] 3/4Upright Spacing [IN] Rung-To-Cage [IN] 27.00
Angle [Degrees] Rung-to-Rung [IN] 12.00Handrail Height [IN] Rung-To-Shell [IN] 7.75
Width [IN] Width [IN] 16.75Rise [IN] / Run [IN] Height [FT] 24.00
STAIRWAYDIMENSIONS EXISTING DIMENSIONS EXISTING
Midrail PresentSlip-Resistant Surface
NOTES: 1 - The spacing of uprights may meet the intentions of the OSHA midrail requirement. 2 - 2x2x3/8" or 1.5" pipe minimum
Spacing of Uprights [IN] 81.50Size of Upright Member 2.5"x2.5"x1/4"
Toe Board Height [IN] 4.00Handrail Height [IN] 42.00
Width [IN]Length [IN] 1265.00
INTERNAL, MFL TC9338
DIMENSIONS EXISTINGHANDRAIL
Tank Consultants, Inc. 4333 West 21st Tulsa, OK 74107 (918) 583-3968 tank-consultants.com
Grand River Dam Authority 2Chouteau, OK 09.23.2015
TCI
Location
This document is intended for the sole use of Tank Consultants, Inc. and its customers.Any unauthorized reproduction is prohibited. © 2015 Page 8 of 20Rev-1.16 - 08.11.15
Customer Tank NoCity, ST InspectedScope Job No
Adverse Condition(s) 1 OK NOT OK Holes Excessive Waviness Areas That Hold Water Corrosion Damage Active Corrosion
Coating Condition(s) 1 OK NOT OK
Peeling Stained Cracking Insulated Thin
Open VentsPressure/Vacuum
Missing/Damaged Parts Flame Arrestor Screens Missing/Damaged Corrosion Damage Painted Closed Service Vents
Rise [IN] Run [IN]
Additional Comments
One 3-inch gooseneck center ventOne 24-inch emergency vent, one 6-inch pressure vent
Roof Slope (As Measured with a 2' - 4' Level)
Problem Detail(s)
INTERNAL, MFL TC9338
External Fixed Roof
Condition Like New Good Fair Poor None
Venting Type(s), Quantity, Setting(s) and Condition(s)
Tank Consultants, Inc. 4333 West 21st Tulsa, OK 74107 (918) 583-3968 tank-consultants.com
Grand River Dam Authority 2Chouteau, OK 09.23.2015
TCI
Location
This document is intended for the sole use of Tank Consultants, Inc. and its customers.Any unauthorized reproduction is prohibited. © 2015 Page 9 of 20Rev-1.16 - 08.11.15
Customer Tank NoCity, ST InspectedScope Job NoINTERNAL, MFL TC9338
External Fixed Roof
Tank Consultants, Inc. 4333 West 21st Tulsa, OK 74107 (918) 583-3968 tank-consultants.com
Grand River Dam Authority 2Chouteau, OK 09.23.2015
TCI
Location
Fixed Roof Layout \\nasserver\clients\GRDA\TC9338\Tank 2 GRDA TC9338 Roof Layout.wmf
Fixed Roof Layout
BC
D
E
DRAWING NOT TO SCALE
A
This document is intended for the sole use of Tank Consultants, Inc. and its customers.Any unauthorized reproduction is prohibited. © 2015 Page 10 of 20Rev-1.16 - 08.11.15
Customer Tank No 2City, ST Inspected 09.23.2015
Location Job No TC9338Scope
Items Not Coated Missing Nuts or Bolts
Label Description Size Radius [FT] CommentA Open Vent 3" 0 gooseneck ventB High Level Alarm 4" 15C Nozzle 4" 15D Manway 24" 15 emergency ventE Gauge Hatch 6" 15
Note: Positive radius values are distances from center. Negative radius values are distances from shell
Tank Consultants, Inc. 4333 West 21st Tulsa, OK 74107 (918) 583-3968 tank-consultants.com
Grand River Dam AuthorityChouteau, OK
INTERNAL, MFL
External Fixed Roof Fittings
TCI
This document is intended for the sole use of Tank Consultants, Inc. and its customers.Any unauthorized reproduction is prohibited. © 2015 Page 11 of 20Rev-1.16 - 08.11.15
Customer Tank NoCity, ST InspectedScope Job No
Radius [FT] [IN] Minimum 0.204Quadrant Location Thickness Maximum 0.209
N C 0.205N 0.208N 0.204S 0.209S 0.205E 0.205E 0.209W 0.207W 0.205
INTERNAL, MFL TC9338
External Roof Thickness Readings
Tank Consultants, Inc. 4333 West 21st Tulsa, OK 74107 (918) 583-3968 tank-consultants.com
Grand River Dam Authority 2Chouteau, OK 09.23.2015
TCI
Location
This document is intended for the sole use of Tank Consultants, Inc. and its customers.Any unauthorized reproduction is prohibited. © 2015 Page 12 of 20Rev-1.16 - 08.11.15
Customer Tank NoCity, ST InspectedScope Job No
1 OK NOT OK
Cornerweld Condition(s) 0 OK NOT OK Pinholes 1 Corrosion Slag Porosity Cracks 1 Product Residue Arc strikes Coated Not Inspected (Explain)
Record the Location, Depth and Extent of Any Deep Corrosion Area(s)
Shell Weld Condition(s) 1 OK NOT OK Arc strikes Porosity Slag Pinholes Coated Not Inspected (Explain) Corrosion Cracks
Record the Location, Depth and Extent of Any Deep Corrosion Area(s)
Appurtenance Welds & Internal Piping 1 OK NOT OKInternal Appurtenance / Nozzle Welds
Incomplete Shell Welds Not Visible Due to Coating/Residue Not Welded to Shell Pinholes or Porosity Corrosion Cracks in Weld
Internal Piping Welds Support Bases Not Seal Welded Hole in Internal Piping Inadequate Pipe Supports No Pad Plates on Pipe Supports Supports Weld to Pipe and Bottom
Improper Construction Practices 1 OK NOT OK Attachments Not Fully Welded Lap Welded Patches False Bottoms (Shell Not Slotted) Shell Burrs
Problem Details
Shell Items B and J did not appear to project through the shell.
The gauge pole supports lacked pad plates on the internal shell.
The internal shell had isolated areas of corrosion ranging from approximately 0.010 to 0.050 inches deep near the cornerweld.
Widespread Localized
CommentsInspection of the internal cornerweld was limited due to product residue and dirt. There was corrosion in the visible areas of the cornerweld.
Comments
INTERNAL, MFL TC9338
Internal Shell
Corrosion on the Internal Shell None Light Medium Heavy
Tank Consultants, Inc. 4333 West 21st Tulsa, OK 74107 (918) 583-3968 tank-consultants.com
Grand River Dam Authority 2Chouteau, OK 09.23.2015
TCI
Location
This document is intended for the sole use of Tank Consultants, Inc. and its customers.Any unauthorized reproduction is prohibited. © 2015 Page 13 of 20Rev-1.16 - 08.11.15
Customer Tank NoCity, ST InspectedScope Job No
Internal Fixed Roof
Roof Support Type / Condition 1 OK NOT OK
ROW QTY RADIUS [FT] ROW QTY RADIUS [FT] ROW QTY RADIUS [FT]
CENTER 0.00 3 61 4 72 5 8
OK NOT OK
OtherA B
OtherA B
Welded Corroded Out of Plumb Bolted Twisted Broken Weld Riveted Damaged No Drain Hole Bowed
OK NOT OK
FlatPlate
T-Type
OtherA B
OtherA B
Welded to Bottom Welded Bearing Plate Not Seal Welded Damaged Riveted No Guide Clips Bolted Broken Weld Corroded No Bearing Plate
Condition(s)
Outer Base(s) None H-Type Flat Plate T-Type Other
Bearing Plate Size and Thickness
Roof Column Base(s) - Type(s) and Size(s)
H-Type
Center Base None H-Type Flat Plate T-Type Other
Bearing Plate Size and Thickness
Outer Column(s) None Combination Structure Pipe Columns Other
Condition(s)
Roof Columns - Quantity and Radial Location
Roof Columns - Type(s) and Size(s)
PIPE COLUMNCOMBINATION
STRUCTURE
Center Column None Combination Structure Pipe Columns Other
INTERNAL, MFL TC9338
Support Type Structural Supported Self Supported Other Other
Tank Consultants, Inc. 4333 West 21st Tulsa, OK 74107 (918) 583-3968 tank-consultants.com
Grand River Dam Authority 2Chouteau, OK 09.23.2015
TCI
AB
AB
BAA
Location
This document is intended for the sole use of Tank Consultants, Inc. and its customers.Any unauthorized reproduction is prohibited. © 2015 Page 14 of 20Rev-1.16 - 08.11.15
Customer Tank NoCity, ST InspectedScope Job No
Internal Fixed Roof
INTERNAL, MFL TC9338
Tank Consultants, Inc. 4333 West 21st Tulsa, OK 74107 (918) 583-3968 tank-consultants.com
Grand River Dam Authority 2Chouteau, OK 09.23.2015
TCI
Location
1 OK NOT OK Twisted Sagging Damaged Bowed Corroded Rafters Not Radial
Hole(s) in the Roof Indicated by Daylight 1 OK NOT OK Hole Corrosion Un-Capped Opening
Rafter Condition(s)
Detail(s) of Problems Found
This document is intended for the sole use of Tank Consultants, Inc. and its customers.Any unauthorized reproduction is prohibited. © 2015 Page 15 of 20Rev-1.16 - 08.11.15
13' 0.13'' DIFF [IN] AVG [IN] MIN [IN] MAX [IN]
RADIALS 0.48 0.100 0.270-17.0' 10 -5 -4 -3 -2 -1 0' RIM
RADIAL CENTER PT01 PT02 PT03 PT04 PT05 PT06 PT07 PT08 PT09 PT10 PT11 SHELL SPACE MIN [IN] MAX [IN]1 3.88 3.97 4.18 4.16 4.15 4.12 4.10 4.11 0.180 0.2702 3.88 4.11 4.12 4.13 4.12 4.10 4.10 4.10 0.100 0.2603 3.88 4.08 4.26 4.23 4.20 4.15 4.11 4.09 0.250 0.2604 3.88 4.02 4.17 4.19 4.22 4.16 4.12 4.09 0.250 0.2605 3.88 3.97 4.10 4.12 4.13 4.08 4.07 4.08 0.160 0.2706 3.88 4.05 4.16 4.15 4.16 4.17 4.15 4.10 0.110 0.2707 3.88 4.03 4.16 4.16 4.15 4.13 4.11 4.11 0.100 0.2608 3.88 3.99 4.19 4.20 4.21 4.18 4.15 4.12 0.150 0.260
Distance [FT] From Shell - Every Foot for First Five Feet and a Maximum of 20' or Half the Radius Thereafter. Record the Distances Below.UT Edge Scrubs
Internal Bottom Survey Inverted Rod Readings [FT], Floating Roof Rim Spaces [IN] and Bottom UT Edge Scrubs [IN]STARTS @ West Manway A DIR (CCW/CW) CCW CHORD SPACING [FT-IN]
City, ST Chouteau, OK Inspected 09.23.2015Scope INTERNAL, MFL Job No TC9338
Tank Consultants, Inc. 4333 West 21st Tulsa, OK 74107 (918) 583-3968 tank-consultants.com
Customer Grand River Dam Authority Tank No 2
TCI
Location
This document is intended for the sole use of Tank Consultants, Inc. and its customers.Any unauthorized reproduction is prohibited. © 2015 Page 16 of 20Rev-1.16 - 08.11.15
Customer Tank NoCity, ST InspectedScope Job No
Bottom Condition(s) 1 OK NOT OK Welded 1 Water Washed Riveted Brush Blasted Double Bottom Standing Water Product Residue
Internal Corrosion Inspection 0 OK NOT OK1 Weld Seam Corrosion Hole(s)1 Areas of Pitting Plates Not Seal Welded1 Isolated Pitting 1 Critical Zone Corrosion
OK NOT OK
1 None Holidays Thick Coating Peeling Thin Coating Blisters Cracks Needs repair Areas Removed for UT Should be Replaced
Bottom Coating(s)Thickness [mils]
INTERNAL, MFL TC9338
Bottom Inspection
Bottom Nominal Thickness - Sketch/Annular Plates Inner Plates
Comments
An extremely limited visual inspection of the tank bottom was performed to locate topside pits 0.070 inches deep and deeper in the bottom plates and 0.055 inches deep and deeper in the critical zone (within three inches of the shell) for a 5-year inspection interval. Areas of corrosion below the thresholds were found in Bottom Plates 9 and 10. The visual inspection could not be completed due to an excessive amount of dirt and product residue.
The internal cornerweld had several areas of corrosion.
Tank Consultants, Inc. 4333 West 21st Tulsa, OK 74107 (918) 583-3968 tank-consultants.com
Grand River Dam Authority 2Chouteau, OK 09.23.2015
TCI
Location
This document is intended for the sole use of Tank Consultants, Inc. and its customers.Any unauthorized reproduction is prohibited. © 2015 Page 17 of 20Rev-1.16 - 08.11.15
Customer Tank NoCity, ST InspectedScope Job NoINTERNAL, MFL TC9338
Bottom Inspection
Tank Consultants, Inc. 4333 West 21st Tulsa, OK 74107 (918) 583-3968 tank-consultants.com
Grand River Dam Authority 2Chouteau, OK 09.23.2015
TCI
Location
0 OK NOT OKDate By
1 09.23.15 TCI
0 OK NOT OK Humps
1 Edge Settlement Greater Than 3/8" Per Foot
Extent of Voids Under Bottom OK NOT OK
Sump Condition(s) 0 OK NOT OK Coated Debris Holes Contains Water or Product Corrosion Not Inspected
Other Conditions or Problems Found
Comments The edge settlement at Radials 1, 3, 4, 6, 7 and 8 exceeded 3/8 inches per foot.
Comments
Comments
The flat-bottom sump was 48 inches in diameter and 24 inches deep. The bottom thicknesses ranged from 0.200 to 0.350 inches. The side wall thicknesses ranged from 0.250 to 0.380 inches. There was a band of corrosion with pitting up to 0.110 inches deep located in the side wall 8 inches above the sump bottom.
Helium Test
Comments
A Magnetic Flux Leakage (MFL) scan was performed on approximately 92 percent of the tank bottom at a remaining wall threshold of 0.135 inches thick in the bottom plates and 0.155 inches thick in the critical zone (within three inches of the shell) for a 5 year inspection interval. There was corrosion below the thresholds on Bottom Plates 1, 2, 3, 4, 6, 7, 8, 10, 11, 12, 13, 14, and 15. The lowest indication found was 0.070 inches located on Bottom Plate 13.
Corrosion areas were found in the critical zone that exceeded 24 inches in length.
Ultrasonic Edge Scrubs (UES) were performed on the tank bottom at the 8 survey locations. The thicknesses ranged from 0.100 to 0.270 inches. Corrosion at or below the threshold was found at Radials 2, 6, 7 and 8.
Bottom Humps, Sags or SettlementSags
MFL Scan approximately 92 percent of the tank bottomMag ParticleHoliday Test
Vacuum BoxLap WeldsCornerweld
Bottom TestingTesting Performed Areas Inspected
This document is intended for the sole use of Tank Consultants, Inc. and its customers.Any unauthorized reproduction is prohibited. © 2015 Page 18 of 20Rev-1.16 - 08.11.15
Customer Tank NoCity, ST InspectedScope Job NoINTERNAL, MFL TC9338
Bottom Inspection
Tank Consultants, Inc. 4333 West 21st Tulsa, OK 74107 (918) 583-3968 tank-consultants.com
Grand River Dam Authority 2Chouteau, OK 09.23.2015
TCI
Location
Bottom Layout
Bottom Layout \\nasserver\clients\GRDA\TC9338\Tank 2 GRDA TC9338 Bottom Layout.wmf
DRAWING NOT TO SCALE
- Soilside Corrosion Area- Topside Corrosion Area
0.160"-0.270"Radial 5
Vertical W
eld 4
Vertical W
eld 3
Rad
ial 6
Ver
tical
Wel
d 5
0.150"-0.260"
0.250"-0.260"
Vertical W
eld 1
Vertical W
eld 2
Radial 4
Radial 3
Radial 7
0.188"-0.270"Radial 1
0.250"-0.260"
Radial 8
0.11
0"-0
.270
"
Rad
ial 2
0.100"-0.260"
0.10
0"-0
.260
"
Manway A
1012
56
1 2
4
3
9
13 14 15
7 8
11
-12" x 12" Soilside Corrosion
This document is intended for the sole use of Tank Consultants, Inc. and its customers.Any unauthorized reproduction is prohibited. © 2015 Page 19 of 20Rev-1.16 - 08.11.15
Tank Consultants, Inc. 4333 West 21st Tulsa, OK 74107 (918) 583-3968 tank-consultants.com
Customer Tank No 2City, ST Inspected 09.23.2015
Location Job No TC9338Scope
Bottom Thickness [IN] Readings Min 0.247 Max 0.260PlateNo THK1 THK2 THK3 THK4 THK5 Comment
1 0.2502 0.2513 0.2494 0.2585 0.2476 0.2507 0.2608 0.2579 0.250
10 0.24811 0.25412 0.25113 0.25614 0.250
Grand River Dam AuthorityChouteau, OK
INTERNAL, MFL
TCI
This document is intended for the sole use of Tank Consultants, Inc. and its customers.Any unauthorized reproduction is prohibited. © 2015 Page 20 of 20Rev-1.16 - 08.11.15
Foundation Type Concrete Ringwall Diameter [FT] 34.00Bottom Construction Lap Welded Height [FT] 24.17
Fixed Roof Type DomeBottom Shape Cone Up Year Built 1979
Bottom Coating None Construction Code API-650
Product UnknownSpecific Gravity 1.00
Tank Consultants, Inc.4333 West 21stTulsa, OK 74107
(918) 583-3968 Fax (918) 583-3966www.tank-consultants.com
Job Number - TC9338
API-653 Tank Settlement Evaluation
Grand River Dam AuthorityChouteau, OK
Survey Date - 09.23.2015Tank No - 2
TankPicture/Sketch
Prepared By
T.Wach P.E. (API-653 #50849)
Surveyed By
S. Saxbury (API-653 #50761), A. Majors and S. Barrows
Report Date - 09.23.2015
TCI
Tank - 2 Settlement Evaluation Report Job Number - TC9338
Grand River Dam Authority Report Date - 09.23.2015
Location - Chouteau, OK API-653 Tank Settlement Evaluation
Table of Contents Page
Settlement Evaluation.............................................................................................................. 3
Settlement Summary Data / Calculations.............................................................................. 4
Settlement Charts.................................................................................................................... 6
Field Data.................................................................................................................................. 9
This document is intended for the sole use of Tank Consultants, Inc. and its customers.Any unauthorized reproduction of this document is prohibited. © 2014
Tank - 2 Settlement Evaluation Report Job Number - TC9338
Grand River Dam Authority Report Date - 09.23.2015
Location - Chouteau, OK API-653 Tank Settlement Evaluation
Settlement Evaluation Summary
Grand River Dam Authority contracted with Tank Consultants, Inc. to provide an internal settlement survey for Tank 2 located in Chouteau, OK. The settlement evaluation was per API-653, 5th Edition, November 2014 Appendix B. According to records provided by the customer, the tank was built in 1979 per API-650 construction standard. The tank has a concrete ringwall foundation.
The elevation survey consisted of 8 survey points equidistant around the tank shell perimeter. Survey Point 1 was located at or near the Manway A and the survey proceeded counter-clockwise around the tank shell perimeter.
The settlement data was fitted to an optimum cosine curve using the least squares method and plotted in graph form. The settlement data shows the tank to be 0.48 inches out of level with the low point located at or near Survey Point 8 or 93.46 feet counter-clockwise from Survey
Point 1. The measure of statistical validity (R2) was 0.90 per B.2.2.4.e.
The out-of-plane, or differential settlement, was calculated for each actual survey point's elevation and plotted in graph form. The largest out-of-plane settlement was 0.14 inches. A maximum permissible out-of-plane settlement of 0.50 inches was calculated per Appendix B.3.2.1. None of the survey points exceed this value.
The tank bottom near the shell was inspected for bulges, ridges, sags and edge settlement that might indicate areas of excessive stress. Because the tank shell does not sit on a grade foundation, settlement near the shell was evaluated per API-653, Appendix B, Sections B.3.3 and the associated footnote. One or more radials exceeded the B/R threshold of 0.37 inches/feet. Further engineering analysis was required. The most severe edge settlement was 3.48 inches located at 5 feet from the shell at radial 3. Radial(s) 1, 2, 5, 6, 7, 8 are OK and require no further corrective action. For Radial(s) 3, 4 the cornerweld and all bottom lap welds in the affected area(s) should be examined by magnetic particle testing. Alternatively, a rigorous stress analysis (FEA) could be performed to better determine the stresses and their acceptability without repair or further NDE Examination.
This document is intended for the sole use of Tank Consultants, Inc. and its customers.Any unauthorized reproduction of this document is prohibited. © 2014 Page 3 of 10
Tank Consultants, Inc. · 4333 West 21st · Tulsa OK 74137 · 918 583-3968 · tank-consultants.comAPI 653 Appendix B Settlement Summary Data /CalculationsGrand River Dam Authority - Chouteau, OK - Tank 2 Job No - TC9338
TCI
Date 09.23.15 09.23.15 09.23.15 09.23.15 09.23.15 09.23.15Radial Distance Settlement Cosine B.2.2.5 Si Smax Elevation Elevation Elevation Elevation Elevation Elevation Elevation Elevation
4 40.06 0.12 0.04 0.00 0.12 0.50 0.02 #REF! #REF! #REF! #REF! #REF! #REF! #REF!5 53.41 0.00 0.09 0.00 0.14 0.50 0.03 #REF! #REF! #REF! #REF! #REF! #REF! #REF!6 66.76 0.24 0.22 0.00 0.07 0.50 0.01 #REF! #REF! #REF! #REF! #REF! #REF! #REF!7 80.11 0.36 0.36 0.00 0.04 0.50 0.00 #REF! #REF! #REF! #REF! #REF! #REF! #REF!8 93.46 0.48 0.44 0.00 0.06 0.50 -0.01 #REF! #REF! #REF! #REF! #REF! #REF! #REF!1 0.00 0.36 0.39 0.00 0.04 0.50 0.00 #REF! #REF! #REF! #REF! #REF! #REF! #REF!2 13.35 0.24 0.26 0.00 0.01 0.50 0.01 #REF! #REF! #REF! #REF! #REF! #REF! #REF!3 26.70 0.12 0.12 0.00 0.02 0.50 0.02 #REF! #REF! #REF! #REF! #REF! #REF! #REF!4 40.06 0.12 0.04 0.00 0.12 0.50 0.02 #REF! #REF! #REF! #REF! #REF! #REF! #REF!
This document is intended for the sole use of Tank Consultants, Inc. and its customers.Any unauthorized reproduction of this document is prohibited. © 2014 Page 4 of 10
Tank Consultants, Inc. · 4333 West 21st · Tulsa OK 74137 · 918 583-3968 · tank-consultants.comAPI 653 Appendix B Settlement Summary Data /CalculationsGrand River Dam Authority - Chouteau, OK - Tank 2 Job No - TC9338
TCI
[IN] [FT] [IN/FT] Safety [IN] [IN]Radial B R B/R Factor Bew Be Max Actual
1 2.28 5 0.455 3.43 2.81 3.42 39 OK - None Required2 1.68 5 0.336 6.32 2.81 3.42 OK - None Required3 3.48 5 0.695 1.47 2.81 3.42 Magnetic Particle/FEA4 2.42 3 0.807 1.60 2.08 2.43 1 Magnetic Particle/FEA5 1.68 5 0.335 6.32 2.81 3.42 OK - None Required6 2.16 5 0.432 3.82 2.81 3.42 63 OK - None Required7 2.04 5 0.407 4.28 2.81 3.42 OK - None Required8 2.28 5 0.456 3.43 2.81 3.42 39 OK - None Required9
101112131415161718192021222324252627282930313233343536
Alpha [Degrees]Action
This document is intended for the sole use of Tank Consultants, Inc. and its customers.Any unauthorized reproduction of this document is prohibited. © 2014 Page 5 of 10
Tank - 2 Settlement Evaluation Report Report ID - TC9338Grand River Dam Authority Report Date - 09.23.2015Location - Chouteau, OK API-653 Tank Settlement Evaluation
0.48"
0.00
0.10
0.20
0.30
0.40
0.50
0.60
40 53 67 80 93 0 13 27 40
Se
ttle
me
nt[
IN]
Circumferential Distance [FT]
Planar SettlementSettlement - 09.23.15
Cosine - 09.23.15
This document is intended for Tank Consultants, Inc. and its customers.Any unauthorized reproduction of this document is prohibited. © 2014 Page 6 of 10
Tank - 2 Settlement Evaluation Report Report ID - TC9338Grand River Dam Authority Report Date - 09.23.2015Location - Chouteau, OK API-653 Tank Settlement Evaluation
0.14"
0.50"
0.00
0.10
0.20
0.30
0.40
0.50
0.60
40 53 67 80 93 0 13 27 40
Se
ttle
me
nt
[IN
]
Circumferential Distance [FT]
Out-of-Plane or Differential Settlement Si - 09.23.15
Smax - 09.23.15
This document is intended for Tank Consultants, Inc. and its customers.Any unauthorized reproduction of this document is prohibited. © 2014 Page 7 of 10
Tank - 2 Settlement Evaluation Report Report ID - TC9338Grand River Dam Authority Report Date - 09.23.2015Location - Chouteau, OK API-653 Tank Settlement Evaluation
-4.50
-4.40
-4.30
-4.20
-4.10
-4.00
-3.90
-3.80-18 -16 -14 -12 -10 -8 -6 -4 -2 0
Edge Settlement [FT] From Shell [FT]
Radial 3 Actual Radial 3 Projected
This document is intended for Tank Consultants, Inc. and its customers.Any unauthorized reproduction of this document is prohibited. © 2014 Page 8 of 10
Tank Consultants, Inc. · 4333 West 21st · Tulsa OK 74137 · 918 583-3968 · www.tank-consultants.comAPI 653 Tank Bottom Settlement Data
Customer Tank NoLocation Date Surveyed 09.23.15
Surveyed By S. Saxbury (API-653 #50761), A. Maj TC9338
Tank Diameter 34 [FT] Radial 1 Survey Starts @ Manway ATank Height 24.167 [FT] Survey Direction [CW/CCW]
Actual Product Level 0 [FT] Number of Radials 8Foundation Type Concrete Ringwall Actual Radial Spacing [FT] 13.35Fixed Roof Type Dome Inverted Elevations TRUE
Radial Distance Ring 1 Hgt SettlementNumber [FT] #1 #2 #3 #4 [IN] Change Absolute [IN]
Grand River Dam Authority 2Chouteau, OK
Job Number
Counter-Clockwise
Set Up - Rod Readings/Elev's [FT] @ Bottom @ Shell Elevation [FT]
TCI
1 0.00 4.11 0.00 0.00 0.362 13.35 4.10 0.01 0.01 0.243 26.70 4.09 0.02 0.02 0.124 40.06 4.09 0.02 0.02 0.125 53.41 4.08 0.03 0.03 0.006 66.76 4.10 0.01 0.01 0.247 80.11 4.11 0.00 0.00 0.368 93.46 4.12 -0.01 -0.01 0.489 0.00
101112131415161718192021222324252627282930313233343536
#1 #2 #3 #4 Adjust BM
BM 0.00
Calculations - Minimum Elevation @ Radial, Elevation, Total Settlement 8 -0.01 0.48
Benchmark LocationDescription
Benchmark Rod Reading [FT] @ Set Up # Elevation [FT]
This document is intended for the sole use of Tank Consultants, Inc. and its customers.Any unauthorized reproduction of this document is prohibited. © 2015 Page 9 of 10
Tank Consultants, Inc. · 4333 West 21st · Tulsa OK 74137 · 918 583-3968 · www.tank-consultants.com API 653 Tank Bottom Settlement Evaluation Data
Customer Grand River Dam Authority Tank NoLocation Chouteau, OK Job Number
Surveyed By S. Saxbury (API-653 #50761), A. Majors and S. Barrows Date Surveyed
Tank Diameter 34 Survey Starts @Tank Height 24.167 Survey Direction
Foundation Type Concrete Ringwall Number of RadialsFixed Roof Type Dome Calculated/Actual Chord Spacing [FT] 13.01
Inverted Elevations
Radial Center Ring 1NBR -17 -10 -5 -4 -3 -2 -1 0 Height [IN]
1 3.88 3.97 4.18 4.16 4.15 4.12 4.10 4.112 3.88 4.11 4.12 4.13 4.12 4.10 4.10 4.103 3.88 4.08 4.26 4.23 4.20 4.15 4.11 4.094 3.88 4.02 4.17 4.19 4.22 4.16 4.12 4.095 3.88 3.97 4.10 4.12 4.13 4.08 4.07 4.086 3.88 4.05 4.16 4.15 4.16 4.17 4.15 4.107 3.88 4.03 4.16 4.16 4.15 4.13 4.11 4.118 3.88 3.99 4.19 4.20 4.21 4.18 4.15 4.129
10111213141516171819202122232425262728
2TC9338
09.23.15
Rod Readings / Elevations [FT] @ Distance [FT] From Center / Shell… + Values (From Center), - Values (From Shell)
Manway ACounter-Clockwise
8
TRUE
TCI
This document is intended for the sole use of Tank Consultants, Inc. and its customers. Any unauthorized reproduction of this document is prohibited. © 2015 Page 10 of 10
BOTTOM CORROSION ANALYSISTO DETERMINE REPAIR THRESHOLDS Tel 918-583-3968 Fax 918-583-3966
AND INSPECTION INTERVALS 4333 West 21st Street
PER API-653 3rd and 4th EDITION Tulsa, OK 74107-3444
SECTION 4.4.5 www.tank-consultants.com
where: Units:
Age = Age of Bottom Plates YearsTo = Original Bottom Thickness Inches
MRT = Minimum Allowable Bottom Thickness Inches0.1" (No Coating or Thin Coating)0.05" (Thick Coating or Leak Detection & Containment)
RTip = Remaining Thickness From Topside Pitting After Repairs InchesRTbc = Remaining Thickness From Soilside Corrosion After Repairs InchesStPr = Maximum Topside Corrosion Rate Inches/YrUPr = Maximum Soilside Corrosion Rate Inches/Yr
Or = Inspection Interval Years
NOTE:
StPr = 0 if the tank bottom is internally lined (see API RP 652)
UPr = 0 if tank bottom is Cathodically Protected (CP) (see API RP 651)
TopsideCorrosion
Soilside Corrosion
Evaluate for bare steel, thin coating, thick or reinforced coating, and leak detection & containment (LD&C)Evaluate for the inner plates, sketch plates and the critical zone (within 3 inches of the shell).
TCI Tank Consultants, Inc.
( )rr
ipbcr UPStP
MRTRTRTO
+−
=,min
Age
RTTStP
ipo
r
−=
Age
RTTUP bco
r
−=
Page 1 of 3 10/14/2015 1:03 PM
Tank 2 GRDA TC9338 Bottom Corrosion
Bottom Corrosion AnalysisTO DETERMINE REPAIR THRESHOLDS Job Number:
AND INSPECTION INTERVALS Customer Name:PER API-653 3rd and 4th EDITION Location:
SECTION 4.4.5 Tank Number:
MEASURED DATA: INPUT:
Enter year of inspection 2015
Enter year bottom constructed 1979
Enter assumed original inner plate thickness (To) 0.250 inches
Enter assumed original sketch plate thickne (ToSP) 0.250 inches
Enter desired inspection interval (Or) 20 years, maximum 20 years
Inner Plate Topside Corrosion…
enter recordable pit depth 0.070 inches
enter maximum pit depth 0.070 inches
Inner Plate Soilside Corrosion…
enter MFL scan threshold 0.180 inches
enter minimum thickness 0.070 inches
Sketch Plate Topside Corrosion…
N/A (since same as Inner Plates)
N/A (since same as Inner Plates)
Sketch Plate Soilside Corrosion…
N/A (since same as Inner Plates)
N/A (since same as Inner Plates)
Critical Zone Topside Corrosion… No Is the Critical Zone to be replaced?
enter recordable pit depth 0.055 inches
enter maximum pit depth 0.055 inches
Critical Zone Soilside Corrosion…
enter MFL scan threshold 0.195 inches
enter minimum thickness 0.100 inches
REPAIR THRESHOLDS AND PATCH PLATE THICKNESSES:
Inner Plate Topside Pit Depth Repair Threshold 0.070 inches, cannot be less than recordable pit depth
Inner Plate Soilside Corrosion Repair Threshold (RTbc) 0.180 inches, cannot exceed MFL scan threshold
Inner Plate Soilside Corrosion Patch Plate Thickness 0.250 inches, usually 0.250"
Sketch Plate Topside Pit Depth Repair Threshold
Sketch Plate Soilside Corrosion Repair Threshold (RTbcSP)
Sketch Plate Soilside Corrosion Patch Plate Thickness
Critical Zone Topside Pit Depth Repair Threshold 0.055 inches, cannot be less than critical zone recordable pit depth
Critical Zone Soilside Corrosion Repair Threshold (RTbcCZ) 0.195 inches, cannot exceed critical zone MFL scan threshold
Critical Zone Soilside Corrosion Patch Plate Thickness 0.250 inches, usually 0.250"
TC9338Grand River Dam AuthorityChouteau, OK2
TCI Tank Consultants, Inc.
Page 2 of 3 10/14/2015 10:48 AM
Tank 2 GRDA TC9338 Bottom Corrosion
Bottom Corrosion AnalysisTO DETERMINE REPAIR THRESHOLDS Job Number:
AND INSPECTION INTERVALS Customer Name:PER API-653 3rd and 4th EDITION Location:
SECTION 4.4.5 Tank Number:
OUTPUT 1 OF 2: DETERMINE THE INSPECTION INTERVAL BASED ON POSSIBLE REPAIR THRESHOLDS AND PATCH PLATE THICKNESSES
No CPCase #1 Case #2 Case #3 Case #4 Case #5 Case #6 Case #7
Bare Steel Thin Coat Thick Coat Bare Steel Thin Coat Thick Coat LD&CAge of Tank Floor (years) (Age) 36 36 36 36 36 36 36
Inner Plate Topside Corrosion Repair Threshold (RTip) 0.1800 0.1800 0.1800 0.1800 0.1800 0.1800 0.1800
Maximum Inner Plate Topside Corrosion Rate After Repairs (inches per year) (StPr) 0.0019 0.0000 0.0000 0.0019 0.0000 0.0000 0.0019
Maximum Inner Plate Soilside Corrosion Rate After Repairs (inches per year) (UPr) 0.0019 0.0019 0.0019 0.0000 0.0000 0.0000 0.0019
Minimum Remaining Wall Thickness of the Inner Plates Per API-653 (MRT) 0.1000 0.1000 0.0500 0.1000 0.1000 0.0500 0.0500
Sketch Plate Topside Corrosion Repair Threshold (RTipSP) N/A N/A N/A N/A N/A N/A N/A
Maximum Sketch Plate Topside Corrosion Rate After Repairs (inches per year) (StPrSP) N/A N/A N/A N/A N/A N/A N/A
Maximum Sketch Plate Soilside Corrosion Rate After Repairs (inches per year) (UPrSP) N/A N/A N/A N/A N/A N/A N/A
Minimum Remaining Wall Thickness of the Sketch Plates Per API-653 (MRTSP) N/A N/A N/A N/A N/A N/A N/A
Critical Zone Topside Corrosion Repair Threshold (RTipCZ) 0.1950 0.1950 0.1950 0.1950 0.1950 0.1950 0.1950
Maximum Critical Zone Topside Corrosion Rate After Repairs (inches per year) (StPrCZ) 0.0015 0.0000 0.0000 0.0015 0.0000 0.0000 0.0015
Maximum Critical Zone Soilside Corrosion Rate After Repairs (inches per year) (UPrCZ) 0.0015 0.0015 0.0015 0.0000 0.0000 0.0000 0.0015
Minimum Remaining Wall Thickness in the Critical Zone Per API-653 (MRTCZ) 0.1250 0.1250 0.1250 0.1250 0.1250 0.1250 0.1250
Check Patch Plate Thickness for Inner Plates OK OK OK OK OK OK OK
Check Patch Plate Thickness for Sketch Plates N/A N/A N/A N/A N/A N/A N/A
Check Patch Plate Thickness for Critical Zone OK OK OK OK OK OK OK
Inspection Interval After Repairs…
For Inner Plate Corrosion (years) (Or) 20.0 20.0 20.0 20.0 20.0 20.0 20.0
For Sketch Plate Corrosion (years) (OrSP) N/A N/A N/A N/A N/A N/A N/A
For Critical Zone Corrosion (years) (OrCZ) 20.0 20.0 20.0 20.0 20.0 20.0 20.0
INSPECTION INTERVAL (YEARS) 20.0 20.0 20.0 20.0 20.0 20.0 20.0
NEXT SCHEDULED INSPECTION 2035 2035 2035 2035 2035 2035 2035
OUTPUT 2 OF 2: DETERMINE THE REQUIRED REPAIR THRESHOLDS TO ACHIEVE THE DESIRED INSPECTION INTERVAL: 20 Years
No CP
Case #1 Case #2 Case #3 Case #4 Case #5 Case #6 Case #7
Bare Steel Thin Coat Thick Coat Bare Steel Thin Coat Thick Coat LD&C
Repair All Topside Pits on the Inner Plates Greater Than ___ (inches) Deep 0.070 0.095 0.125 0.095 0.150 0.200 0.090
Repair All Soilside Corrosion on the Inner Plates Less Than ___ (inches) in Thickness 0.180 0.155 0.125 0.155 0.100 0.050 0.160
Repair All Topside Pits on the Sketch Plates Greater Than ___ (inches) Deep N/A N/A N/A N/A N/A N/A N/A
Repair All Soilside Corrosion on the Sketch Plates Less Than ___ (inches) in Thickness N/A N/A N/A N/A N/A N/A N/A
Repair All Topside Pits in the Critical Zone Greater Than ___ (inches) Deep 0.055 0.080 0.080 0.080 0.125 0.125 0.055
Repair All Soilside Corrosion in the Critical Zone Less Than ___ (inches) in Thickness 0.195 0.170 0.170 0.170 0.125 0.125 0.195
Developed by JTD, Version 10-8-2004Modified by AF 5-30-2007
Without CP With CP
Without CP With CP
TC9338
Grand River Dam Aut
Chouteau, OK
2
TCI Tank Consultants, Inc.
Page 3 of 3 10/14/2015 10:48 AM
Tank 2 GRDA TC9338 Fill Height
Job Number:TO DETERMINE THE ACCEPTABLE Customer Name:
PRODUCT FILL HEIGHT Location:PER API-650 5.6.3 and API-653 4.3.3 Tank Number:
Ref API-650 12th Ed. & API-653 4th Ed Inspection Date:
DESIGN DATA:
34.00 Diameter (FT) 653 API Analysis (new = 650, existing = 653)
24.17 Height (FT) 200 Design Temp. (°F)24.17 Liquid Level (FT) 1.00 Specific Gravity3 Number of Shell Rings
CALCULATIONS:
Shell Shell Product Allowable Joint Calculated Corrosion Thickness Fill Ht
Course Height Fill Ht. Stress Eff. Minimum Allowance Measured Check
Hring (inch) H (ft) S (psi) E Tmin CA (inch) Tactual
Ring No. 1 95.40 24.17 23,595 0.85 0.1021 0.0000 0.2490 OK
Ring No. 2 94.90 16.22 23,595 0.85 0.1000 0.0000 0.1950 OK
Ring No. 3 94.90 8.31 25,960 0.85 0.1000 0.0000 0.1980 OK
Ring No. 4 0.70 0.0000 0.0000
Ring No. 5 0.70 0.0000 0.0000
Ring No. 6 0.70 0.0000 0.0000
Ring No. 7 0.70 0.0000 0.0000
Ring No. 8 0.70 0.0000 0.0000
Ring No. 9 0.70 0.0000 0.0000Ring No. 10 0.70 0.0000 0.0000
23.77 ft Total Ring HeightNominal Volume:
IN Top Angle Ht. (if any) Cu Ft23.77 FT Total Shell Ht. BBL
Refer to API-650 5.6.3 and AAPI-653 4.3.3 for application of the One-Foot method.
For Tmin : The fill height analysis found that this tank was adequate for continued service.
With a product specific gravity of 1 the fill height should be limited to 23.77 feet.
To use a fill height of 24.17 feet, the specific gravity should not exceed 2.44.
NOTES:
Copyright © 2015 Version 1.02
Fill Height Analysis
TC9338Grand River Dam AuthorityChouteau, OK
One-Foot
2
A283-C
A283-C
A283-C
9/23/2015
PlateMaterial
21,9423,908
TCI Tank Consultants, Inc.
10/14/2015
TO DETERMINE THE EXTERNAL INSPECTION AND Job Number:ULTRASONIC THICKNESS INSPECTION INTERVAL Customer Name:
PER API-653 4th EDITION, ADDENDUM 3 Location: SECTIONS 6.3.2 and 6.3.3 Tank Number:
Inspection Date:
DESIGN DATA:
34.00 Diameter (FT) 653 API Analysis24.17 Height (FT) 200 Design Temp. (°F)24.17 Liquid Level (FT) 1.00 Specific Gravity3 Number of Shell Rings 1/1/1979 Date of Construction 36.73 years
11/13/2012 Date of Prev. Inspection 2.86 years
ANALYSIS CRITERIA:
1) Corrosion rates were determined by minimum thicknesses of the shell rings.
2) This analysis did short-term corrosion rates.
3) This analysis compares the corrosion rate of
4) Minimum thickness was calculated using the One-Foot method.
5) Joint efficiency is 1.0 unless the corrosion is within 1 inch of a weld or 6 inches of a rivet.
CALCULATIONS:
Shell Joint Allowable Calculated Remaining
Course Eff. Stress Minimum Nominal Previous Current Long-term Short-term Critical LifeE S (psi) Tmin Tnom Tpreviousl Tactual (in/yr) (in/yr) (in/yr) (yr)
Ring No. 1 1.00 23,595 0.1000 0.2810 0.0000 0.2490 0.00087 N/A 0.00087 171.01
Ring No. 2 1.00 23,595 0.1000 0.2190 0.0000 0.1950 0.00065 N/A 0.00065 145.38
Ring No. 3 1.00 25,960 0.1000 0.2190 0.0000 0.1980 0.00057 N/A 0.00057 171.40
Ring No. 4 0.0000 0.0000
Ring No. 5 0.0000 0.0000
Ring No. 6 0.0000 0.0000
Ring No. 7 0.0000 0.0000
Ring No. 8 0.0000 0.0000
Ring No. 9 0.0000 0.0000
Ring No. 10 0.0000 0.0000
Minimum remaining life: 145.38 yr
External inspection interval (5 yr max): 5.00 yr Next external inspection by: Sep 2020
Ultrasonic testing interval (15 yr max): 15.00 yr Next UT reading by: Sep 2030
NOTES:
Copyright © 2015 Version 1.02
not consider
9/23/2015
Corrosion Rate Analysis
TC9338
Grand River Dam Authority
Chouteau, OK
2
Corrosion RateThickness
all shell rings.
TC9338 Grand River Dam Authority Chouteau, OK Tank 2 Page 1 of 19
1A 1B
1C 1D
TC9338 Grand River Dam Authority Chouteau, OK Tank 2 Page 2 of 19
2A 2B
2C 2D
TC9338 Grand River Dam Authority Chouteau, OK Tank 2 Page 3 of 19
3A 3B
3C 3D
TC9338 Grand River Dam Authority Chouteau, OK Tank 2 Page 4 of 19
4A 4B
4C 4D
TC9338 Grand River Dam Authority Chouteau, OK Tank 2 Page 5 of 19
5A 5B
5C 5D
TC9338 Grand River Dam Authority Chouteau, OK Tank 2 Page 6 of 19
6A 6B
6C 6D
TC9338 Grand River Dam Authority Chouteau, OK Tank 2 Page 7 of 19
7A 7B
7C 7D
TC9338 Grand River Dam Authority Chouteau, OK Tank 2 Page 8 of 19
8A 8B
8C 8D
TC9338 Grand River Dam Authority Chouteau, OK Tank 2 Page 9 of 19
9A 9B
9C 9D
TC9338 Grand River Dam Authority Chouteau, OK Tank 2 Page 10 of 19
10A 10B
10C 10D
TC9338 Grand River Dam Authority Chouteau, OK Tank 2 Page 11 of 19
11A 11B
11C 11D
TC9338 Grand River Dam Authority Chouteau, OK Tank 2 Page 12 of 19
12A 12B
12C 12D
TC9338 Grand River Dam Authority Chouteau, OK Tank 2 Page 13 of 19
13A 13B
13C 13D
TC9338 Grand River Dam Authority Chouteau, OK Tank 2 Page 14 of 19
14A 14B
14C 14D
TC9338 Grand River Dam Authority Chouteau, OK Tank 2 Page 15 of 19
15A 15B
15C 15D
TC9338 Grand River Dam Authority Chouteau, OK Tank 2 Page 16 of 19
16A 16B
16C 16D
TC9338 Grand River Dam Authority Chouteau, OK Tank 2 Page 17 of 19
17A 17B
17C 17D
TC9338 Grand River Dam Authority Chouteau, OK Tank 2 Page 18 of 19
18A 18B
18C 18D
TC9338 Grand River Dam Authority Chouteau, OK Tank 2 Page 19 of 19
19A 19B
19C 19D
top related