TEST REPORT
Report No.: D1090.01-301-44
Rendered to:
PRL ALUMINUM ARCHITECTURAL PRODUCTS City of Industry, California
PRODUCT TYPE: Bi-Fold Door
SERIES/MODEL: Accordion Bi-Fold
SPECIFICATION: AAMA/WDMA/CSA 101/I.S.2/A440-08, NAFS - North American Fenestration Standard/Specification for Windows, Doors, and Skylights
Title Summary of Results
Primary Product Designator SP – PG45 2413 x 2108 mm Design Pressure ±2160 Pa (±45.11 psf)
Air Infiltration @ 1.57 psf 0.45 L/s/m2 (0.09 cfm/ft2) Air Infiltration @ 6.27 psf 1.05 L/s/m2 (0.21 cfm/ft2)
Water Penetration Resistance Test Pressure 330 Pa (6.89 psf)
Test Completion Date: 10/02/2013
Reference must be made to Report No. D1090.01-301-44, dated 01/13/14 for complete test specimen description and detailed test results.
Architectural Testing
Test Report No.: D1090.01-301-44 Report Date: 01/13/14
Record Retention End Date: 10/02/17 Page 1 of 9
1.0 Report Issued To: PRL Architectural Aluminum Products 14760 Don Julian Road City of Industry, California 91746 2.0 Test Laboratory: Architectural Testing, Inc. 4 Rancho Circle Lake Forest, California 92630 949-460-9600 3.0 Project Summary:
3.1 Product Type: Bi-Fold Door
3.2 Series/Model: Accordion Bi-Fold
3.3 Compliance Statement: Results obtained are tested values and were secured by using the designated test method(s). The specimen tested successfully met the performance requirements for a SP – PG45 2413 x 2108 mm rating.
3.4 Test Dates: 08/29/2013 – 10/02/2013
3.5 Test Record Retention End Date: All test records for this report will be retained until October 02, 2017.
3.6 Test Location: Architectural Testing, Inc. test facility in Lake Forest, California.
3.7 Test Sample Source: The test specimen was provided by the client. Representative samples of the test specimen will be retained by Architectural Testing for a minimum of four years from the test completion date.
3.8 Drawing Reference: The test specimen drawings are located in Appendix B
3.9 List of Official Observers:
Name Company Frank Fisher Hany Ibrahim
PRL Aluminum Architectural Products PRL Aluminum Architectural Products
Jarod Hardman Architectural Testing, Inc.
www.archtest.com
Test Report No.: D1090.01-301-44 Report Date: 01/13/14
Record Retention End Date: 10/02/17 Page 2 of 9
4.0 Test Specification:
AAMA/WDMA/CSA 101/I.S.2/A440-08, NAFS - North American Fenestration Standard/Specification for Windows, Doors, and Skylights
5.0 Test Specimen Description:
5.1 Product Sizes: Test Specimen:
Overall Area: 5.07 m²
(54.75 ft2)
Width Height
millimeters inches millimeters inches
Overall size 2413 95 2108 83 Panel Size 1146 45 – 1/8 2019 79 – 1/2
5.2 Frame Construction:
Frame Member Material Description Head Aluminum Thermally broken extrusion, Part #BF-01 Head Aluminum Head track end damn plate, Part #777-02-F01
Sill Aluminum Thermally broken extrusion, Part #BF-03
Sill Aluminum Clip in bottom roller track insert, Part #BF-03C-F03
Sill Polyvinyl Chloride Clip in roller track guide track, Part #999VY-11-FO3
Jambs Aluminum Thermally broken extrusion, Part #BF-04
Joinery Type Detail
Head Butt Secured through head extrusion with two #8 x 3" drill point Phillips flat head sheet metal screws and sealed with silicone sealant.
Sill Butt Secured through jamb extrusion with two #8 x 1" Phillips flat head sheet metal screws and sealed with silicone sealant.
www.archtest.com
Test Report No.: D1090.01-301-44 Report Date: 01/13/14
Record Retention End Date: 10/02/17 Page 3 of 9
5.0 Test Specimen Description: (Continued) 5.3 Panel Construction: Active Hinge Panel: Panel Member Material Description
Top, bottom, sides Aluminum Thermally broken extrusion, Part #BF-21-F50
Vertical Stile Aluminum Cover plate, Part #BF-61-F02, located on the top and bottom of both vertical stiles secured with two 1/2" Flat-head screws.
Top, bottom, sides Aluminum Glass stop extrusion, Part #BF-41, clip in Fixed Hinge Panel: Panel Member Material Description
Top, bottom, sides Aluminum Thermally broken extrusion, Part #BF-21-F50
Vertical Stile Aluminum
Cover plate, Part #BF-61-F02, located on the top and bottom of the vertical stile opposite the lock stile secured with two 1/2" Flat-head screws.
Vertical Lock Stile Aluminum Door stile gear box, Part# BF-60-F04, located on the top and bottom of the lock stile secured with two 1/2" Flat-head screws.
Top, bottom, sides Aluminum Glass stop extrusion, Part #BF-41
Joinery Type Detail
All corners Coped
Secured through top and bottom rails with one #10 x 1/2" Phillips flat head screw into the aluminum corner block, Part # BF-61-F01, mounted at each corner on the stiles.
www.archtest.com
Test Report No.: D1090.01-301-44 Report Date: 01/13/14
Record Retention End Date: 10/02/17 Page 4 of 9
5.0 Test Specimen Description: (Continued)
5.4 Weatherstripping:
Description Quantity Location
3/8" high vinyl wrapped foam bulb gasket. 2 Rows
One row located at the interior and the exterior edge of each panel at the head and sill.
1/4" high vinyl wrapped foam bulb gasket. 2 Rows
One row located at the interior and the exterior edge of each panel at the vertical stiles.
1/4" high vinyl wrapped foam bulb gasket. 1 Row One row centered in the frame at the
head, sill, and jambs.
3/8" high foam wedge gasket 1 Row One row at the interior leg of the frame at the head, sill, and jambs.
5.5 Glazing: No conclusions of any kind regarding the adequacy or inadequacy of the
glass in any glazed test specimen(s) can be made. Glass Type
Spacer Type
Interior Lite
Exterior Lite Glazing Method
1" IG 1/2" A1-D 1/4" Tempered
1/4" Tempered
Exterior glazed with snap in glazing bead.
Location Quantity Daylight Opening Glass Bite millimeters inches
Panel 2 955 x 1829 37 – 19/32 x 72 1/2"-3/4" 5.6 Drainage:
Drainage Method Size Quantity Location
Weephole 1/2" x 1/4" 3 4" from each end and mid-span through the exterior leg of the snap in sill roller track assembly.
www.archtest.com
Test Report No.: D1090.01-301-44 Report Date: 01/13/14
Record Retention End Date: 10/02/17 Page 5 of 9
5.0 Test Specimen Description: (Continued) 5.7 Hardware:
Description Quantity Location
Hinge, Part #BF-63-F01 4 1/2" from top and bottom of the panel jamb stile.
Hinge, Part #BF-62-F02 3 1/2" from the top and bottom of the vertical stile between panels, midspan of the vertical stile between panels.
Hinge, Part #BF-62-F01 3 Directly opposite of Hinge Part #BF-62-F02
Hinge pin & handle assembly, Part #BFH-07 1 Located midspan of the vertical stile
between panels in the hinge.
Lock rods, Part# 777-03-F01 2 Located at the center hinge stile of the active panel.
Intermediate hinge pin, Part #BFH-05 2
Located at the head and sill of the vertical stile between panels in the hinge assemblies.
Bottom sill jamb pivot, Part #BFH-03 1
Located at the sill corner of the fixed jamb panel on the exterior face of the panel stile.
Top jamb starter pivot, Part #BFH-01 1
Located at the head corner of the fixed jamb panel directly above Part #BFH-03 on the exterior face of the panel stile.
Half sill guide assembly, Part #BFH-09 1
Located at the sill corner of the active jamb panel on the exterior face of the panel stile.
Half roller assembly, Part #BFH-08 1
Located at the head corner of the active jamb panel directly above Part BFH-09 on the exterior face of the panel stile.
5.8 Reinforcement: No reinforcement was utilized.
5.9 Screen Construction: No screen was utilized.
www.archtest.com
Test Report No.: D1090.01-301-44 Report Date: 01/13/14
Record Retention End Date: 10/02/17 Page 6 of 9
6.0 Installation: The specimen was installed into an aluminum channel buck. The rough opening allowed for a 0" shim space. The exterior perimeter of the window was sealed with polyurethane sealant.
Location Anchor Description Anchor Location
Jambs #12 x 3-1/4"Phillips flat head screws.
10" from each corner through the jamb of the frame into the
aluminum buck.
Head and sill #10 x 1" Phillips pan head screws.
6" from the corner and 8" on center.
www.archtest.com
Test Report No.: D1090.01-301-44 Report Date: 01/13/14
Record Retention End Date: 10/02/17 Page 7 of 9
7.0 Test Results: The temperature during testing was 26.1°C (79°F). The results are tabulated as follows:
Test Specimen:
Title of Test Results Allowed Note
Operating Force, per ASTM E 2068
Initiate motion: 46.7 N (10.5 lbf) 178 N (40 lbf) max.
Maintain motion: 8.9 N (2.0 lbf) 111 N (25 lbf) max.
Force to latch: 71.2 N (16.0 lbf) Report Only
Locks: 11.1 N (2.5 lbf) 100 N (22.5 lbf) max.
Air Leakage, Infiltration per ASTM E 283
at 75 Pa (1.57 psf) 0.45 L/s/m2
(0.09 cfm/ft2) 1.5 L/s/m2
(0.3 cfm/ft2) max. 1 Air Leakage,
Infiltration per ASTM E 283 at 75 Pa (6.27 psf)
1.05 L/s/m2 (0.21 cfm/ft2)
1.5 L/s/m2 (0.3 cfm/ft2) max. 1
Water Penetration, per ASTM E 547 and ASTM E 331
at 330 Pa (6.89 psf)
Pass No leakage 2 Uniform Load Deflection,
per ASTM E 330 taken at lock stile
+2160 Pa (+45.11 psf) -2160 Pa (-45.11 psf)
5.8 mm (0.23") 6.6 mm (0.26")
Report Only 2, 3, 4, 5
Uniform Load Structural, per ASTM E 330
taken at lock stile +3240 Pa (+67.67 psf) -3240 Pa (-67.67 psf)
0.3 mm (0.01") <0.3 mm (<0.01")
3.6 mm (0.14") max. 3.6 mm (0.14") max. 2, 4, 5
Forced Entry Resistance, per ASTM F 842,
Type: A - Grade: 10 Pass No entry Forced Entry Resistance,
per AAMA 1304 Pass No entry
www.archtest.com
Test Report No.: D1090.01-301-44 Report Date: 01/13/14
Record Retention End Date: 10/02/17 Page 8 of 9
7.0 Test Results: (Continued)
Note 1: The tested specimen meets (or exceeds) the performance levels specified in AAMA/WDMA/CSA 101/I.S.2/A440 for air leakage resistance. Note 2: The client opted to start at a pressure higher than the minimum required. Test results are reported under Optional Performance. Note 3: The deflections reported are not limited by AAMA/WDMA/CSA 101/I.S.2/A440 for this product designation. The deflection data is recorded in this report for special code compliance and information only. Note 4: Loads were held for 10 seconds. Note 5: Tape and film were used to seal against air leakage during structural testing. In our opinion, the tape and film did not influence the results of the test.
www.archtest.com
Test Report No.: D1090.01-301-44 Report Date: 01/13/14
Record Retention End Date: 10/02/17 Page 9 of 9
Architectural Testing will service this report for the entire test record retention period. Test records that are retained such as detailed drawings, datasheets, representative samples of test specimens, or other pertinent project documentation will be retained by Architectural Testing, Inc. for the entire test record retention period. This report does not constitute certification of this product nor an opinion or endorsement by this laboratory. It is the exclusive property of the client so named herein and relates only to the specimen(s) tested. This report may not be reproduced, except in full, without the written approval of Architectural Testing, Inc. For ARCHITECTURAL TESTING, Inc. ___________________________________________ ________________________________________________ Jarod Hardman Leaton Kirk Laboratory Manager Director – Regional Operations JH: ms Attachments (pages): This report is complete only when all attachments listed are included. Appendix-A: Alteration Addendum (1) Appendix-B: Drawings (22) Complete drawings packet on file with Architectural Testing, Inc. This report produced from controlled document template ATI 00438, issued 01/31/12.
www.archtest.com
Test Report No.: D1090.01-301-44 Report Date: 01/13/14
Record Retention End Date: 10/02/17
Appendix A
Alteration Addendum
Alteration #1: Date – 09/18/2013 Cause for alteration – Failure of water test Remedial action taken – Addition of weep hole mid-span of the of sill
assembly.
www.archtest.com
Test Report No.: D1090.01-301-44 Report Date: 01/13/14
Record Retention End Date: 10/02/17
Appendix B
Drawings
Note: Complete drawings packet on file with Architectural Testing, Inc.
www.archtest.com