Sent by Intec on (DD-MM-YYYY) Drg./Doc. No. LOCATION /
GRID Discipline Concerned QUERY Drawing Required / Discrepancy Image Comment Response from Consultant Remarks from Intec Status
1
01.04.2015A-TD-201 3rd BASEMENT FLOOR PLAN R6
GRID-B&6A MEP CLASHCABLE TRAY CLASH WITH MECH.EQUIPMENT
LAYOUT REVISED Close
2
01.04.2015A-TD-201 3rd BASEMENT FLOOR PLAN R6
GRID-D1&2 MEP CLASH CABLE TRAY CLASH WITH HVAC DUCT LAYOUT REVISED Close
3
01.04.2015A-TD-201 3rd BASEMENT FLOOR PLAN R6
GRID-E&6 MEP CLASH CABLE TRAY CLASH WITH HVAC DUCT NO CLASH Close
4
01.04.2015A-TD-201 3rd BASEMENT FLOOR PLAN R6
GRID-E & 11 MEP CLASHCABLE TRAY CLASH WITH MECH.EQUIPMENT
LAYOUT REVISED Close
5
01.04.2015A-TD-201 3rd BASEMENT FLOOR PLAN R6
GRID-K1&6A MEP CLASH CABLE TRAY CLASH WITH HVAC DUCT DUCT LEVEL REVISED Close
TECHNICAL QUERY:
20F6BC70.JPG
2032F3C8.JPG
DD183516.JPG
C:\Users\HP ELITEBOOK 8760W\Desktop\BIM_LOG_MEP 1
S.N
Sent by Intec on (DD-MM-YYYY) Drg./Doc. No. LOCATION /
GRID Discipline Concerned QUERY Drawing Required / Discrepancy Image Comment Response from Consultant Remarks from Intec Status
6
01.04.2015A-TD-201 3rd BASEMENT FLOOR PLAN R6
GRID-9A&A1 MEP CLASHSPRINKLER PIPE CLASH WITH HVAC DUCT
NO CLASH Close
7
01.04.2015A-TD-201 3rd BASEMENT FLOOR PLAN R6
GRID-B&8 MEP CLASHSPRINKLER PIPE CLASH WITH HVAC DUCT
NO CLASH Close
8
01.04.2015A-TD-201 3rd BASEMENT FLOOR PLAN R6
GRID-C&4 MEP CLASHSPRINKLER PIPE CLASH WITH HVAC DUCT
LAYOUT REVISED Layout not revised Close
9
01.04.2015A-TD-201 3rd BASEMENT FLOOR PLAN R6
GRID-D1&12 MEP CLASHSPRINKLER PIPE CLASH WITH MECH. EQUIPMENT
LAYOUT REVISED Layout not revised Close
10
01.04.2015A-TD-201 3rd BASEMENT FLOOR PLAN R6
GRID-B&6 MEP CLASHRAIN WATER PIPE CLASH WITH HVAC DUCT
LAYOUT REVISED Close
3EF85994.JPG
AD59812E.JPG
FEAC356C.JPG
669B7A5A.JPG
76658378.JPG
C:\Users\HP ELITEBOOK 8760W\Desktop\BIM_LOG_MEP 2
S.N
Sent by Intec on (DD-MM-YYYY) Drg./Doc. No. LOCATION /
GRID Discipline Concerned QUERY Drawing Required / Discrepancy Image Comment Response from Consultant Remarks from Intec Status
11
01.04.2015A-TD-201 3rd BASEMENT FLOOR PLAN R6
GRID-M&1A MEP CLASHRAIN WATER PIPE CLASH WITH HVAC DUCT
NO CLASH Close
13
01.04.2015A-TD-201 3rd BASEMENT FLOOR PLAN R6
CAL MEP CLASHSPRINKLER PIPE CLASH WITH STRUCTURE BEAM
LAYOUT REVISED Close
15
01.04.2015A-TD-201 3rd BASEMENT FLOOR PLAN R6
GRID-B&8 MEPHVAC DUCT CLASH WITH STRUCTURE COLUMN
LAYOUT REVISED Close
16
01.04.2015A-TD-201 3rd BASEMENT FLOOR PLAN R6
GRID-P&1A MEP CLASHHVAC DUCT CLASH WITH STRUCTURE COLUMN
LAYOUT REVISED Close
17
02.04.2015
A-TD-202 2nd BASEMENT FLOOR PLAN R6 13-3-13
GRID-E&7 MEP CLASH CABLE TRAY CLASH WITH EACH OTHER LAYOUT REVISED Close
2E9C5046.JPG
F6C29BD0.JPG
9C11025E.JPG
1ABDBE1C.JPG
19B432CC.JPG
2AF03EBA.JPG
5AC871E3.jpg
C:\Users\HP ELITEBOOK 8760W\Desktop\BIM_LOG_MEP 3
S.N
Sent by Intec on (DD-MM-YYYY) Drg./Doc. No. LOCATION /
GRID Discipline Concerned QUERY Drawing Required / Discrepancy Image Comment Response from Consultant Remarks from Intec Status
18
02.04.2015
A-TD-202 2nd BASEMENT FLOOR PLAN R6 13-3-13
GRID-I&2 MEP CLASH CABLE TRAY CLASH WIH FIRE PIPE LAYOUT REVISED Close
19
02.04.2015
A-TD-202 2nd BASEMENT FLOOR PLAN R6 13-3-13
GRID-E&10B MEP CLASHCABLE TRAY CLASH WITH MECH.EQUIPMENT
LAYOUT REVISED Close
20
02.04.2015
A-TD-202 2nd BASEMENT FLOOR PLAN R6 13-3-13
GRID-L1&12 MEP CLASHSPRINKLER PIPE CLASH WITH MECH. EQUIPMENT
LAYOUT REVISED Close
21
02.04.2015
A-TD-202 2nd BASEMENT FLOOR PLAN R6 13-3-13
GRID-O&4 MEP CLASHSPRINKLER PIPE CLASH WITH HVAC DUCT
NO CLASH Close
22
02.04.2015
A-TD-202 2nd BASEMENT FLOOR PLAN R6 13-3-13
GRID-M&1A MEP CLASHRAIN WATER PIPE CLASH WITH HVAC DUCT
NO CLASH Close
460228E9.JPG
E03223DF.JPG
E7DF3845.JPG
8D6CEF61.JPG
4733D2C3.JPG
C:\Users\HP ELITEBOOK 8760W\Desktop\BIM_LOG_MEP 4
S.N
Sent by Intec on (DD-MM-YYYY) Drg./Doc. No. LOCATION /
GRID Discipline Concerned QUERY Drawing Required / Discrepancy Image Comment Response from Consultant Remarks from Intec Status
23
02.04.2015
A-TD-202 2nd BASEMENT FLOOR PLAN R6 13-3-13
GRID-D1&2A MEP CLASHCABLE TRAY CLASH WITH STRUCTURE COLUMN CAP
NO CLASH Close
24
02.04.2015
A-TD-202 2nd BASEMENT FLOOR PLAN R6 13-3-13
GRID-K1&10B MEP CLASHCABLE TRAY CLASH WITH STRUCTURE COLUMN CAP
NO CLASH Close
25
02.04.2015
A-TD-202 2nd BASEMENT FLOOR PLAN R6 13-3-13
GRID-L&2 MEP CLASHCABLE TRAY CLASH WITH STRUCTURE COLUMN CAP
LAYOUT REVISED Close
26
02.04.2015
A-TD-202 2nd BASEMENT FLOOR PLAN R6 13-3-13
GRID-K2&12 MEP CLASHSPRINKLER & PIPE CLASH WITH STRUCTURE BEAM
LAYOUT REVISED Close
27
02.04.2015
A-TD-202 2nd BASEMENT FLOOR PLAN R6 13-3-13
GRID-C1&8 MEP CLASHHVAC DUCT CLASH WITH STRUCTURE BEAM
DUCT LEVEL REVISED Close
97424917.JPG
BB27EA3D.JPG
9DF8F453.jpg
A86884D9.JPG
4B4F154F.JPG
E53EDB35.JPG A3F7280B.JPG87BDFD98.JPG850A9515.JPG 21415CEB.JPG E20C3131.JPGC58B7B67.JPGC90EE10D.JPG79A4A3A3.JPGE94000A9.JPG 4F8E919F.JPGE554AC05.JPGE6E8C15B.JPG A291ABDA.JPG1752E483.JPGF1995489.JPG DBB632A2.JPGD8529B7.JPGE7A7FC6D.jpg 4F8E3603.jpg1E153C1A.jpgF9676B38.jpg183FD8A3.jpg4C04D579.jpg7D79CEEF.jpg5928E5D5.jpgF849ABAB.jpg4CD52DF1.jpgAF321477.jpgD28BAC9D.jpg9ECED1E6.jpgF2068109.jpg25BBD0FF.jpg