cutler-hammer - kvc industrial supplies sdn bhd · cutler-hammer january 2001 vol. 2, ref. no. ......

Post on 07-Apr-2018

249 Views

Category:

Documents

10 Downloads

Preview:

Click to see full reader

TRANSCRIPT

Cutler-HammerJanuary 2001Vol. 2, Ref. No. [0215]

IEC Contactors & StartersFixed Heater Overload Relays 34-33

Freedom Line

-' DimensionsTable 34-54. Approximate Dimensions andShipping Weights

FrameSize

F

K

P

Dimensions in Inches (mm)WideA

1.71(43.4)

2.13(54.1)4.09(103.9)

HighB

2.62(66.5)3.70(94.0)5.51(140.0)

DeepC

3.66(93.0)4.41(112.0)4.88(124.0)

MountingD

2.65(67.3)

E

1.46(37.1)

Ship.Wt.Lbs.Ikg)

.37(.17)

.71(.32)

2.01(.91)

S

A^

^1 QL

Frame Sizes F and K

Frame Size P

.18-(4.5)

C316F and C306TB1

C316TB1

2.95(75)

1.97^(50!3Independent

OverloadRelay

(2) M4Fixings

C316K and C306TB1

Figure 34-16. Stand-Alone Overload Relays — Approximate Dimensions in Inches (mm)

Figure 34-15. Approximate Dimensions

1Product SelectionFreedom Series Integral Overload RelaysTable 34-55. Bimetal Class 10 —IEC Sizes A-F

Table 34-56. Bimetal Class 10 —IEC Sizes G-K and IEC Sizes L-S

TripClass

MotorFLA

Manual/AutomaticReset NO-NCElectrically SeparatedCatalogNumber

PriceU.S. S

TripClass

MotorFLA

Manual/ AutomaticReset NO-NCElectrically SeparatedCatalogNumber

PriceU.S. S

For IEC Contactor Sizes A-F For IEC Contactor Sizes G-K

Frame Size K Overload RelayCat. No. C316KNA3

ai u Li"- 'V< v

^

10 .25 -.40.40 - .63.63-1.00

1.00-1.401.30-1.801.70-2.402.20-3.102.80 - 4.003.50 - 5.004.50-6.506.00-8.507.50-11 .0

10.0-14.013.0-19.018.0-24.024.0 - 32.0

C316FNA3CC316FNA3DC316FNA3EC316FNA3FC316FNA3GC316FNA3HC316FNA3JC316FNA3KC316FNA3LC316FNA3MC316FNA3NC316FNA3PC316FNA3QC316FNA3RC316FNA3SC316FNA3T

65.5065.5065.5065.5065.5065.5065.5065.5065.5065.5067.5067.5067.5067.5073.0079.00

10 18.0-25.022.0-32.029.0 - 42.036.0 - 52.045.0 - 63.060.0-80.0

C316KNA3AC316KNA3BC316KNA3CC316KNA3DC316KNA3EC316KNA3F

101.00101.00107.00116.00116.00138.00

For (EC Contactor Sizes L-S10 65-90

80-100100-1351 1 0 - 1 5 0130-175150-200

C316PNA3AC316PNA3BC316PNA3CC316PNA3DC316PNA3EC316PNA3F

207.00336.00336.00336.00336.00336.00

Discount Symbol. . . . . . . . . . . . . . . . . . . . . . . . 1CD7

CAT.201.01.T.E For more information contact Cutler-Hammer at: www.ch.cutler-hammer.com/catalog F.T-N

Cutler-HammerJanuary 2001Vol. 2, Ref. No. [0213]

IEC Contactors & StartersFixed Heater Overload Relays 34-31

Freedom Line

ContentsDescription

Product Family OverviewProduct Description......Application Description...Features . . . . . . . . . . •), ,iStandards and

Certifications . . . . . . . . . .Fixed Heater Overload Relays

Product Description......Features . . . . . . . . . . . . . . .Standards and

Certifications . . . . . . . . . .Technical Data . . . . . . . . . .Accessories. . . . . . . . . . . . .Trip Curves . . . . . . . . . . . . .Dimensions.. . . . . . . . . . . .Product Selection..... . . .

Technical D a t a . . . . . . . . . . . . .Accessories . . . . . . . . . . . . . . .

Auxiliary Contacts ..,,...»DC Magnet Coils . . . . . . . .

Special Modifications.......Renewal P a r t s . . . . . . . . . . . . .Dimensions . . . . . . . . . . . . . . .

1

nm34-2134-2134-22

34-22

34-3134-31

34-3134-3134-3234-3234-3334-3334-4334-48

34-5034-5534-5634-61

Frame Size F Overload RelayCat. No. C316FNA3

Product DescriptionCutler-Hammer Integral OverloadRelays are for use with FreedomSeries contactors. They are designedand manufactured to meet IEC (Inter-national'Electrotechnical Commis-sion) recommendations and otherinternational standards necessary foracceptance in many countries aroundthe world.

Features• EN60947-4-1 IEC 947-4-1 Compli-

ance — the new International Stan-dard for low voltage switchgear andcontrol devices.

• Direct heated bimetal elements.• Class 10 trip characteristics through

200 amperes and Class 30 on 400and 850 ampere relays.

• Single-phase and phase unbalancesensitive.

• Ambient temperature compensated.• Adjustable trip current, overload trip

indication.• NO-NC electrically isolated contacts,

contact test lever.• Manual/automatic reset.• DIN rail and panel mounting

adapter.

Standards and Certifications• UL listed —File E130332• CSA certified — File LR15332M94

Technical DataTable 34-48. Contact Ratings(35% Power Factor)Rating

Insulation Voltage660V AC (IEC)600V AC (UL & CSA)Thermal Rating 10A

Volts Make Break

120230480600

30.0A15.0A7.5A6.0A

3.0A1.5AJ5A.6A

Table 34-49. Power Terminal Torque in Ib-inCatalogNumber

C306TB1/C316FC316TB1/C316K

Line

2021.2

Load

1 240I14-8AWG)45(6-4AWG)50 (3 AWG)

Table 34-50. Overload Relay UL/CSA Contact Ratings Control Circuit (AC Volts 120V | 240V 480V 600V

NC Contact B600Make and Break AmpsBreak AmpsContinuous Amps

3035

151.55

7.5.75

5

6.6

5

NO Contact C600Make and Break AmpsBreak AmpsContinuous Amps

151.52.5

7.5

.75

2.5

3.375.375

2.5

3

.3

2.5

® DC ratings cover Freedom Series coils only.

Table 34-51. Overload Configurations — C316 OverloadSizeOverload

F

£

P

P

Contactor

A-F

G-K

L-M

N-S

Mounting Arrangements

Connecting links are provided for close coupling.For independent mounting, an accessory kitC306TB1 is required.Connecting links are provided for close coupling.For independent mounting, an accessory kitC316TB1 is required which replaces the connectorsand repositions the calibration marks with anadditional label.Connecting links are provided for close couplingwith a calibration label to reposition the marks.Connecting links are provided for close coupling asan accessory. Other links and overstuck calibrationlabel must be discarded. NOTE: an overstuckcalibration label for 60 - 80A FLC is supplied.

CAT.201.01.T.E For more information contact Cutler-Hammer at: www.ch.cutler-hammer.com/catalog F.T'N

top related