1.0 SYSTEM CONDITIONS
1.1 Nominal Voltage
1.2 Maximum Voltage
1.3 Number of Phases
1.4 Frequency
1.5 Max. symmetrical Fault level
1.6 Type of Neutral Earthing
1.7 Limited Earth Fault Current thro ET
2.0
2.1 Altitude above sea Level
2.2 Max / Min Air Temperatures
2.3Mean Max Air Temperature
2.4 Mean Max Exposed Sun-light Temp
2.5 Solar Radiation - Peak
2.6 Max. Relative Humidity at >300 C
2.7 Wind speeds
2.8 Regional open Air Climate
2.9 Excessive dust
2.10 Excessive Salt mist
2.11 Condensation
2.12 Vibration Due to heavy Vehicles
2.13 Service condition class
2.14 Local Control of Humidity & Temp
2.15 Environmental Conditions - Category
3.0 APPLICABLE STANDARDS
3.1 AC metal enclosed Switchgear
3.2 HV Switchgear Common specs.
3.3 HV Circuit Breakers
3.4 HV AC Disconnector & Earth Switches
3.5 HV AC Switches
3.6 For Other applicable standards
4.0 SWITCHGEAR CHARACTERISTICS
4.1 Manufacturer Name (vendor to specify)
4.2 Place of Manufacturing (vendor to specify)
A. 11kV SWITCHGEAR PANELS Common Parameters for All Types of Panels
NORMAL & SPECIAL SERVICE CONDITIONS
-
7/27/2019 Data Schedule1
2/39
4.3 Product Model/Type (vendor to specify)
4.4Switchgear shall be metal enclosed, air-insulated, with vacuum circuit-breaker,
and withdrawal type
4.5 Main Device (CB truck) shall be withdraw-able, roll-on floor operated
4.6 CB truck shall be Horizontal Isolation, Horizontal withdrawal type
4.7Application of the switchgear shall be suitable for Electricity Secondary
Distribution Network under specified service conditions
4.8 Usage Area/Class
4.9 Type of Bus-bar system
4.10 Compartments Partition class
4.11 Loss of Service continuity - Category
4.12 Rated Voltage (Ur )
4.13 Number of Phases4.14 Rated frequency (fr )
4.15 Rated Insulation Level:
- Rated LI withstand voltage
- Phase to Earth
- Across Isolating Distance
- Rated power frequency withstand voltage
- Phase to Earth
- Across the isolating distance
4.16
- Incomer
- Main Bus-bar
- Feeder
4.17 Rated short-time with-stand current (Ik)
- For Group-A Switchgear panels
- Main Circuit
- Earth Circuit
- For Group-B Switchgear panels
- Main Circuit
- Earth Circuit
4.18 Rated duration of short circuit (tk)4.19 Rated peak withstand current (Ip)
- For Group-A Switchgear panels
- Main Circuit
- Earth Circuit
- For Group-B Switchgear panels
- Main Circuit
- Earth Circuit
Rated Normal Current (Ir ) at +500 C and specified service conditions (Submit cal
-
7/27/2019 Data Schedule1
3/39
4.20Rated supply voltage of closing/opening devices And of auxiliary and control
circuits (Ua)
4.21 Rated Voltage & Frequency of spring charge motor
4.22 Degrees of Protection
- Enclosure
- Bus-bar & cable compartments, Internal partitions
- Circuit-Breaker Compartment
- Door Closed- Door Opened
- LV Compartment
- Shutters & Spouts
- Pressure relief Flaps
- VT compartment (where applicable)
4.23 Partial Discharge test voltage shall be as per
- Typical partial discharge values observed
4.24 Busbar & Line Earthing
- Main Bus-bar Earthing shall be by an separate integral Earth Switch or with
suitable interlocks using Cable Earth Switch
- cable/ Line (Circuit) Earthing shall be by integral Earth switch
5.0
CIRCUIT BREAKER & ISOLATOR/DISCONNECTOR CHARACTERISTICS ,for F class
switchgear additional & individual data schedule to be added for
ISOLATOR/DISCONNECTOR
Name of manufacturer (vendor to provide)
Model/Type Designation (Vendor to provide)
Generic Type
Isolation type
Fully solid Insulated/encapsulated
Applicable standards
Rated Voltage (Ur)
No of poles (phases)
Class
Rated frequency
Rated Normal Current at 500 C ambient
Temperature rise at full-load *
Rated Lightning withstand voltage
- Phase to earth
- Across the isolating distance
Rated power frequency withstand voltage
- Phase to earth
- Across the isolating distance
Rated short-time withstand current (Ik)- For Group-A panels at 3 sec (tk) duration
- For Group-B panels at 3 sec (tk) duration
Rated peak withstand current (Ip)
- For Group-A Panels
- For Group-B Panels
Rated Operating Sequence
Rated short-circuit breaking current (Isc)
- For Group-A panels (ac r.m.s Component)
-
7/27/2019 Data Schedule1
4/39
- For Group-B panels (ac r.m.s component)
Rated short-circuit making current
- For Group-A panels
- For Group-B panels
Rated Cable charging breaking current (Ic)
Rated Mechanical Endurance class
Rated Electrical Endurance Class
Rated supply voltage of closing/opening devices And of auxiliary and controlcircuits (Ua)
Rated Voltage & Frequency of spring charge motor
Rated time quantities (offered values to be mentioned by vendor)
- Opening time
- Arcing time
- Break-time
- Make time
- Pre-arcing time
- Closing time
6.0 ENCLOSURE & COMPARTMENTS OTHER TECHNICAL REQUIREMENTS
Layout and access- CB Compartment at Floor level & Having Front Access
- Cable & CT compartment at Floor Level, with rear access
- Bus-bar compartment is above Cable comp, with side & top access
- LV Compartment is above CB compartment. with front access
- VT Compartment, if located on rear-top shall have rear access
Material of Construction
- Main Bus-bar - Hard drawn, high conducting Electrolytic Copper
- Main Bus-bars cross-section size (width x Thickness), in mm
- Main Bus-bars in all compartments, connecting strips to VT , E/S and CVDs
shall be fully insulated with heat-shrink sleeves
- Earth-Bars cross section ( width x Thickness), in mm
- Enclosure body/Partitions/Shutters shall be metallic
- Thickness of the Enclosure sheet, in mm
- All nuts, bolts, washers, hinges shall be made of non-corrosive alloy steel or
stainless steel
Other requirements for Switchgear Panels
- Enclosure/partitions/Shutters to be Individually earthed
- Inter-panel jointing (assembly work) shall be made easy by using fewer
number of bolts & nuts of robust design, instead of using too many of smaller
size bolts & nuts
- Use of proper spring washers shall be mandatory for any inter-panel
assembly work, foundation bolts, jointing, fixing of mechanical and electrical
connections- All bolts & nuts shall be tightened to their respective torques and marked
with distinct colour (torque marks).
-The frame of each panel assembly work shall be so rigid that, during
installation, the aligning of internal components including CB truck movement
shall not be affected due to uneven floor surface conditions. Assembly work
shall not be sensitive
- Removable type circuit labels as described in this specification shall be fixed
both on front & back of each panel
-
7/27/2019 Data Schedule1
5/39
- Danger symbols shall be permanently marked on both front & back of each
panel (stickers are not acceptable)
- Painting work on panels shall not have any scratches/peel-offs/ chippings,
and quality requirements shall comply with the spec
- Two name plates, with all details as specified, shall be fixed one on front side
and other at rear side of each panel.
- CT name plates details shall be permanently fixed at panel rear wall, in LV
Cabinet, and on CT itself in every panel
-All metal work & Live components shall not have any sharp edges
All un-used holes/openings/orifices/cable entry holes/inter-compartmental
wiring apertures shall be closed with caps/plugs. (temporary arrangements
like silicone sealing/foam filling are not acceptable)
- All entry holes for earth bus-bars shall be fully closed without gaps with
proper sealing grommets, plates etc. (temporary arrangements like silicone
sealing/foam filling are not acceptable)
-Pressure relief flaps for internal arc protection shall be located on top of panel
For CB compartment
- Main Door Hinges shall be Robust design & Construction
- Pad-locking facility for main door, as specified, shall be provided
- Proper alignment of main contacts of CB shall be ensured
- Shutters shall be clearly paint marked with BUSBARS and FEEDERS
respectively with large white letters.
-Bus-bar shutter shall be RED coloured, and that of Feeder shall be LEMEN
YELLOW
-Caution symbols are also to be paint marked on the shutters along with
legend markings.
-Shall have integral manual shutter opening device. The device mechanismshall have facility for opening & latching individual shutter in open condition.
-Insertion of CB truck into the compartment shall override the manual shutter
operating device and normal shutter operation is restored
-Individual Shutters shall have pad locking facility when shutters are in closed
condition
-For BUS-SECTION panels, provide arrow markings on the shutters as specified
(indicating direction of bus-section connected)
-Viewing window, as specified, shall be fixed on front door
-Permanent phase colour markings shall be made (no stickers)
-For Bus-bar Compartment-Main Bus-bars shall be fully insulated with heat-shrink sleeves
-Loose taping on bus-bar joints & connections are not acceptable
-All bus-bar joints & connections shall be shrouded with insulating boots, as
specified.
-There shall not be any scope to enter water droplets (due to condensation)
into these joints & connections
-
7/27/2019 Data Schedule1
6/39
-
-Bus-bar end covers design shall be such that there shall be easy access
without any hindrance for installing or dismantling. But, the screws or bolts
used for this purpose shall not be accessible from outside.
-For Cable Compartment
- -All 11kV cable entry shall be from rear bottom of panels
-Capable of terminating 3Core XLPE and PILC cables up to 300mm2
--Cable terminal connections shall be suitable for making heat-shrinkterminations with right-angled or straight insulating boots.
-
-Clearance between 11kV connection terminals and bottom plate shall not be
less than 650mm.
-Viewing window, as specified, shall be fixed on rear door
-
-Proper alignment between cable entry holes at bottom and the cable
connecting terminals shall be maintained
-All panels shall be supplied with required number of un-insulated brass
wiping glands conforming to BS 2562 & Size Y
-Matching mounting holes (free holes without any welded nuts) at cable entry
points on bottom plate shall be made to fix the glands
-Cable entry & gland mounting holes shall be closed with temporarycaps/plugs/blanking plates when panels are supplied
-Permanent phase identification colour markings (preferably by screen
printing) shall be provided both inside the cable compartment and outside on
the rear cover
7.0 OPERATIONAL REQUIREMENTS
All normal operations shall be possible only when main door is in closed
condition
Ensure correct alignment of all front orifices with respective
mechanisms/handles
All orifices meant for operations, shall remain in closed in normal condition,
with the help of spring-loaded self-closing shutters/covers, and automaticallyget closed when the operating handles are removed from the orifices.
Rack-in rack-out operations shall be easy to be operated with single hand
Rack-in/rack-out operation shall be smooth without any bumpy/jerky
movements
Mechanical spring charging of CB shall be possible with main door both in open
& closed conditions
Mechanical spring charging shall be possible in both CB truck in TEST or
SERVICE positions
Mechanical tripping/opening of CB shall be made through the operation of
mechanical push-buttonMechanical tripping/opening of CB shall be possible in both main door closed
and open conditions
Mechanical tripping/opening of CB shall be possible in both CB truck in TEST or
SERVICE positions
Mechanical closing of CB shall be possible with CB truck in both TEST and
SERVICE positions.
-
7/27/2019 Data Schedule1
7/39
Under emergency requirements, mechanical closing of CB shall be possible in
main door open condition, by disabling the main door interlock
There shall be pad-locking arrangement for disabling mechanism of main door
interlock.
Related instructions for disabling the main door interlock shall be permanently
printed on front of main door.
Remote/Local selection for Electrical operation of CB shall be made through
cam operated selector switch fitted for the purpose on LV compartment door
Electrical closing & opening operations of CB shall be accomplished through
cam operated switch fitted for the purpose on the LV compartment door
Electrical closing operation of CB shall be incorporated with anti-pumping
feature
Electrical closing operation of CB shall be incorporated with trip-free feature
Earth switches shall be operated mechanically from front side of the panel with
the help of operating handles8.0 MECHANICAL & ELECTRICAL INDICATIONS
All mechanical status or position indications shall be through positively driven
mechanisms in both directions of their operations.
Precise mechanical position indicators shall be available at front of the panel to
indicate exact positions of CB truck in TEST or SERVICE positions.
Mechanical status indicators of spring charge mechanism shall be provided on
the CB truck. CLOSE status shall be indicated with suitable symbol along with
inscriptions engaged. OPEN status shall be indicated with a blank disengaged
using standard colour backgrounds
Mechanical status indicators of CB ON/OFF positions shall be available at front
of the panels by using standard colours for background and letters. If these are
provided on the CB truck, shall be clearly visible from front viewing window
both in TEST & SERVICE positions.
Mechanical status indicators of Earth Switches ON/OFF positions shall be
available at front of the panels by using standard colours for background and
ON/OFF inscription letters.
Operations counter shall be provided on CB truck and visible from viewing
window
Clear and permanent demarcation lines shall be marked inside CB
compartment to precisely indicate the positions of CB truck in TEST and
SERVICE positions
Electrical status indication of CB ON/OFF positions shall be made through
indicator lamps using standards colours of light
9.0 PAD-LOCKING PROVISIONS
CB compartment main door shall have padlocking facility
LV compartment door shall have padlocking facility
CB trip/close electrical cam switch shall have padlocking facility
Remote/Local electrical selector switch shall have padlocking facility
-
7/27/2019 Data Schedule1
8/39
Earth switches operation shall have padlocking facility in both ON/OFF
positions
CB trip/open mechanical push-button shall have padlocking facility
CB mechanical close push-button shall have padlocking facility
Shutter of CB compartment shall have padlocking facility
VT shutters/operating handle shall have padlocking facility
Main door interlock defeating mechanism shall have padlocking facility
Locking the isolator cum earthing switch in the isolated and earthed position
10.0
INTERLOCKS (MECHANICAL & ELECTRICAL) : Manufacturers need to provide all
required mechanical & electrical interlocks for safe and logical operation of
the switchgear panels. They may consider including additional interlocks,
wherever required, over and above the mandatory interlocks mentioned
below.
Additional & Individual DATA SHEET to be added for ISOLATOR
/DISCONNECTOR interlocking with reference to clause 8.3
WHEN
CB truck in SERVICE positionCB truck in SERVICE position
CB truck in SERVICE position
CB truck in SERVICE position
CB truck in SERVICE position
CB truck in SERVICE position
CB truck in SERVICE position
CB truck in SERVICE position
CB truck in SERVICE position
CB truck in SERVICE position
CB truck in SERVICE position
CB truck in SERVICE position
CB truck in INTERMEDIATE position
CB truck in INTERMEDIATE position
CB truck in INTERMEDIATE position
CB truck in INTERMEDIATE position
CB truck in TEST position
CB truck in TEST position
CB truck in TEST position
CB truck in TEST position
CB truck in TEST position
CB truck in TEST position
CB truck in TEST position
CB truck in TEST position
-
7/27/2019 Data Schedule1
9/39
CB truck in TEST position
CB truck in TEST position
CB truck in TEST position
CB truck in TEST position
CB truck in TEST position
CB truck in TEST position
CB truck in TEST position
Manual spring charging is initiated
Bus-bar Earth Switch is closed
B ENERGY METERS REQUIREMENTS
General- Conforming to latest IEC standards unless other-wise specified
- Generic type: Static/Digital with 5-Yrs warranty
- Shall be fitted only in Type-5/Type-6/Type-7 switchgear panels
- Suitable for Indoor application under specified special service conditions
- Maters shall be matched and rated to operate to required degree of accuracy
in conjunction with the related VT and CTs
- Flush mounted in LV compartment in concerned switchgear panels
- Meter cases (enclosures) shall be fully insulated
- Suitable for 3-ph un-balanced loads
- Meters shall have roller-counter type numbers/digits for display of reading
- The numbers/digits shall be 6mm high
- Meters shall have direct reading facility without need for multiplying factor
- Meters shall have facility to accept wire-seals on removable covers
- Each meter shall be supplied fitted with panels (loose supply not acceptable)
- Each Meter supplied along with its own calibration certificate
E E) PROTECTION RELATED DATA SCHEDULE FOR
TYPE-1 PANELS
TRANSFORMER CBS WITH OVER-CURRENT AND EARTH FAULT PROTECTION
SPECIFICATION (FOR 11/0.433KV TRANSFORMERS UP TO 1600KVA)
Current Transformers for O/C & E/F protection
-CT Ratio
-Number of CTs
-Class
-Burden
-Short Circuit current for 3 sec (based on Group-A/B/C of Panel)
-
7/27/2019 Data Schedule1
10/39
-Name of Manufacturer
-Manufacturer type/model designation
-Reference of Type test reports submitted (as per IEC standards)
Current Transformers for Instruments
-CT ratio
-Number of CTs
-Class
-Burden-Short Circuit current for 3 sec (based on Group-A/B of panel)
-Name of Manufacturer
-Manufacturer type/model designation
-Reference of Type test reports submitted (as per IEC standards)
Protection Relays (EDMIT) for O/C & E/F protection (51/51N & 50/50N)
Type: Over-current and Earth-Fault protection instantaneous and time
delayed Relay Characteristics
4-pole extremely inverse definite minimum time (EIDMT) over- current &
earth fault protection relay with high set instantaneous over current and
earth fault elements (51/51N & 50/50N). Including other IEC inverse
curves.Relay Generic type/design/settings
-Numeric with 5-Yrs warranty
-Name of Manufacturer & Country of Origin
-Manufacturer type/model designation
-Range of Over-current EIDMT setting
-High-set instantaneous over-current setting range
-Range of earth-fault EIDMT setting
-Range of high set instantaneous Earth-Fault setting
-Type of Indication shall be LED indication
-Rated tripping & relay supply voltage
-Suitable test block fitted for routine check
SOTF (Switch on to fault) Facility
Shall be wired through CB closing and Local/Remote switches
High set element of O/C & E/F shall enable tripping of the CB with minimum
time duration, if any fault occurs/prevails during closing operation of CB
SOFT relay setting will be done locally by KM staff
Trip circuit supervision shall be wired and enabled through the protection
relay for trip circuit supervision, CB open/close condition
Ammeters
Generic Type Moving Iron type, Flush mounted
Bezel sizeAccuracy class
No of Ammeters to be fitted (one for each phase)
Scale/Range: 0-100A, suitable for CT mentioned above
Suitable CT ratio
Name of Manufacturer & Country of Origin
Inter trip Facility
-
7/27/2019 Data Schedule1
11/39
-
7/27/2019 Data Schedule1
12/39
Relay type : Electromagnetic/static/numeric with 5 yrs warranty
Name of Manufacturer
Manufacturer type/model designation
Current rating
Rated insulation
Relay shall work with 2 pilot cores
Rated DC voltage
Current check-guard relay to be provided (for numeric relays)-Name of Manufacturer
-Manufacturer type/model Designation
-Generic type of relay (numeric etc)
- Over-current (O/C) setting range
- Earth-Fault (E/F) setting range
Pilot wire Supervision Relay to be provided
Name of Manufacturer
Manufacturer type/model Designation
Generic type of relay (numeric/static etc)
- Suitable pilot wire supervision scheme to be provided
- Panels with No. of sending & receiving end supervision relays
IDMT over-current & Earth-Fault Protection (51/51N)
Relay type : 4pole numeric with 5 yrs warranty with all the IEC inverse cu
Name of Manufacturer
Manufacturer type/model designation
Current rating
Voltage rating
3 x Over-current elements with settings range
1 x Earth-fault element with setting range
Suitable Test terminal facility for relay testing shall be provided
Type of trip Indication (LED)
OC & E/F fault protection trip shall have independent indications
SOTF (Switch on to fault) Facility
Shall be wired through CB closing and Local/Remote switches
High set element of O/C & E/F shall enable tripping of the CB with
minimum time duration, if any fault occurs/prevails during closing
operation of CB
SOFT relay setting will be done locally by KM staff
Trip circuit supervision shall be wired and enabled through the
protection relay for trip circuit supervision
Ammeter
Generic Type Moving Iron type, Flush mounted
No of Ammeters to be fitted (one for each phase)Scale/Range: 0-400A and suitable for CT mentioned above
Bezel size
Accuracy class
Suitable for CT ratio
Name of Manufacturer & Country of Origin
Tripping Supply
Tripping supply wires shall be wired from adjacent panels either from left or
right side
-
7/27/2019 Data Schedule1
13/39
Size of 30VDC supply wires for tripping shall be 4C X 4mm2 Stranded
CU/PVC/SWA/PVC as per BS 6346
Size of inter-trip wires shall be 4C x 2.5mm2 CU/PVC/SWA/PVC as per BS 6346
Pilot Cable termination
Connecting terminals in the pilot wire marshalling (control) box shall be
suitable for connecting 4C x 4mm2 CU/XLPE/SWA/PVC cable
5 numbers of M25 cable glands(brass) are to be provided at bottom of Pilot
Cable marshalling box for terminating
G) PROTECTION RELATED DATA SCHEDULE FOR
TYPE-3 PANELS
BUS-SECTION (BUS COUPLER + BUS-RISER) CB PANELS WITH OVER-CURRENT &
Current Transformers for O/C & E/F protection
CT Ratio
Number of CTs
Class
burden
Short circuit current for 3 sec (based on Group-A/B of Panel)
Name of Manufacturer & Country of OriginManufacturer type/model designation
Reference of Type test reports submitted (as per IEC standards)
Current Transformers for Instruments
CT ratio
Number of CTs
Class
Burden
Short circuit current for 3 sec (base on Group-A/B/C of Panel)
Name of Manufacturer & Country of Origin
Manufacturer type/model designation
Reference of Type test reports submitted (as per IEC standards)
IDMT over-current & Earth-Fault Protection (51/51N)
Relay type : 4 pole numeric with 5 yrs warranty
Name of Manufacturer & Country of Origin
Manufacturer type/model designation
Current rating
Voltage rating
3 x Over-current & 1 Earth-Fault IDMT and Definite characteristic
Relay characteristics: All IEC inverse curves
This relay shall be suitable for tripping directly and shall be wired fully
If relay is numeric type, it shall be wired for 3 Pole O/C + E/F relay
Suitable Test Terminal Block for relay testing shall be provided
Type of trip Indication ( LED)OC & E/F fault protection trip shall have independent indications
SOTF (Switch on to fault) Facility
Shall be wired through CB closing and Local/Remote switches
High set element of O/C & E/F shall enable tripping of the CB with minimum
time duration, if any fault occurs/prevails during closing operation of CB
SOFT relay setting will be done locally by KM staff
-
7/27/2019 Data Schedule1
14/39
Trip circuit supervision shall be wired and enabled through the protection relay
for trip circuit supervision
Ammeter
Generic Type Moving Iron type, Flush mounted
No of Ammeters to be fitted (one for each phase)
Scale/Range: (suitable for CT mentioned above)
Bezel Size
Accuracy ClassSuitable for CT ratio
Name of Manufacturer & Country of Origin
Tripping Supply
Supply voltage
Tripping supply wires wired from adjacent panels either from left or right side
Size of 30VDC supply wires for tripping shall be 4C X 4mm2 Stranded
CU/PVC/SWA/PVC as per BS 6346
H) PROTECTION RELATED DATA SCHEDULE FOR
TYPE-4 PANELS
FEEDER CB PANELS WITH PILOT WIRE PROTECTION AND DIRECTIONAL OVER
CURRENT (DOC) & DIRECTIONAL EARTH FAULT (DEF) PROTECTION
Current Transformers for Pilot wire protection
CT Ratio
Number of CTs
Class
burden
Short Circuit current for 3 sec (based on Group-A/B of panel)
Name of Manufacturer & Country of Origin (supplier to specify)
Manufacturer type/model designation (supplier to specify)
Knee Point Voltage (supplier to provide data & specify the formula)
[Supplier to Note: The Knee point voltage should be established by
calculation for 25/31.5 kA faults current using the formula provided by
the pilot wire protection relay manufacturer and with data of loop
resistance]
CT resistance for 300/5 ratio (in ohms)
CT resistance for 400/5 ratio (in ohms)
Excitation current at Knee Point Voltage
Reference of Type test reports submitted
Current Transformers for DO/C & DE/F protection
CT Ratio
Number of CTs
Classburden
Short Circuit current for 3 sec (based on Group-A/B of panel)
Name of Manufacturer & Country of Origin
Manufacturer type/model designation
Reference of Type test reports submitted
Current Transformers for Instruments
CT ratio
Number of CTs
-
7/27/2019 Data Schedule1
15/39
Class
Burden
Short Circuit current for 3 sec (based on Group-A/B of panel)
Name of Manufacturer & Country of Origin
Manufacturer type/model designation
Reference of Type test reports submitted
Pilot Wire Protection (PWP) - (87P)
Details same as those mentioned underType-2 panelDirectional O/C & Directional E/F Protection (67/67N)
Relay type : 4 pole numeric with 5 yrs warranty
Name of Manufacturer
Manufacturer type/model designation
Current rating
Voltage rating
If relay is numeric type it shall be wired for 3 pole O/C + E/F
3 Single pole Directional O/C IDMTL relays, 450 current leading, 5A,
voltage polarizing 110Vac 50Hz in phases R & B / 3 phase
Over current setting range
One single pole Directional E/F IDMTL relay, range 10-40%, 12.50
or150 current lagging (multiple angle selection relay)
Earth-Fault Setting Range
Suitable Test terminal facility for relay testing shall be provided
Type of trip Indication (Mechanical flag/LED)
OC & E/F fault protection trip shall have independent indications
SOTF (Switch on to fault) Facility
Shall be wired through CB closing and Local/Remote switches
High set element of O/C & E/F shall enable tripping of the CB with minimum
time duration, if any fault occurs/prevails during closing operation of CB
-
7/27/2019 Data Schedule1
16/39
-
7/27/2019 Data Schedule1
17/39
-
7/27/2019 Data Schedule1
18/39
-
7/27/2019 Data Schedule1
19/39
-
7/27/2019 Data Schedule1
20/39
kV 1
kV 12
No 3
Hz 50
kA 25/31.5
By Earthing Transformer (ET) at Primary Sub-
station
kA 4.5
Less than 100
50 / 5
45
75
1030
100
More than 15
Hot sub-tropical
Present
Present
Frequent Occurance
Possible
Indoor
None
3K6/3Z11/3Z4/3B2/3C2/3S3/3M2
IEC 62271-200
IEC 62271-1
IEC 62271-100
IEC 62271-102
IEC 62271-103
Refer main document
OfferedUNIT
DATA VALUES
Required
-
7/27/2019 Data Schedule1
21/39
Yes
Yes
Yes
Yes
Indoor
Single
PM
LSC2B
kV 12
No 3Hz 50
kV 75
kV 85
kV 28
kV 32
A 400
A 800
A 400
kA 25
kA 25
kA 31.5
kA 31.5
sec 3
kA 62.5
kA 62.5
kA 80
kA 80
lculation sheet if offered ratings are based on 400 C)
-
7/27/2019 Data Schedule1
22/39
V, DC 30
V, AC 240V ac, 50Hz
IP 41
IP 3X
IP 41IP XX
IP 41
IP 3X
IP 41
IP 41
IEC 60270
pC
Yes
Yes
Vacuum, (FMW C F )
Horizontal withdrawal &roll- on-floor type
Yes
IEC 62271-100, 62271-1
kV 12
No 3
Indoor
Hz 50
A 400
K
kV 75
kV 85
kV 28
kV 32
kV 25
kV 31.5
kA 62.5
kA 80
O 0.3sec CO - 3min - CO
kA
kA 25
-
7/27/2019 Data Schedule1
23/39
kA 31.5
kA 62.5
kA 80
A 25
Class M2 (10,000)
Class E2
V, DC 30
V, AC 240Vac, 50Hz
ms
ms
ms
ms
ms
ms
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Sheet Steel
Yes
Yes
Yes
Yes
Yes
Yes
Yes
-
7/27/2019 Data Schedule1
24/39
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
YesYes
Yes
Yes
Yes
-
7/27/2019 Data Schedule1
25/39
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
-
7/27/2019 Data Schedule1
26/39
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
-
7/27/2019 Data Schedule1
27/39
Yes
Yes
Yes
Yes
Yes
Yes
Yes
AND Interlock to be satisfied
CB is closed Cable E/S cannot be closedCB is closed Bus-bar E/S cannot be closed
CB is closed CB truck cannot be racked-out
CB is closed Cannot open the main door
CB is closed Cannot remove LV control Plug
CB is opened CB truck can be racked-out
CB is opened Cannot open the main door normally
CB is opened Cannot remove LV control plug
CB is opened Cable E/S cannot be closed
CB is opened Bus-bar E/S cannot be closed
Main contacts fully not
closedCB cannot be closed
CB is closedPrevent un-desirable operation of any
mechanical selectors/interlocks
- Cannot remove LV control plug
- Cannot open the main door
- CB cannot be closed
-Cannot charge the Spring mechanically or
Electrically
CB is closed CB truck cannot be racked-in
CB is closed Main door can be opened
CB is opened Main door can be opened
CB is opened and LV
plug connected CB truck can be racked-in
CB is opened, but LV
plug disconnectedCB truck cannot be racked-in
CB is opened LV plug can be removed
CB is closed LV plug can be removed
CB is opened, and
Feeder Cable is dead
Cable E/S can be closed
-
7/27/2019 Data Schedule1
28/39
CB is closed, and
Feeder cable is dead
Cable E/S can be closed
CB is opened, and
Feeder Cable is liveCable E/S cannot be closed
CB is opened, but LV
plug connectedCB truck cannot be racked-out
CB is opened, but LV
plug disconnected
CB truck can be racked-out
LV plug is connected CB can be closed
LV plug disconnected CB can be closed mechanically
Cable E/S is Closed CB truck cannot be racked-in
- Spring charge motor cannot be operated
-
CB trucks cannot be racked into SERVICE
position (in the section)
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
100/5A
3
5P10
15 VA
25/31.5 kA
-
7/27/2019 Data Schedule1
29/39
100/5A
3 No
1.0
15VA25/31.5kA
Yes
Yes
30VDC
Yes
Yes
Yes
Yes
Yes
72 x 721
3 Nos
100/5A
-
7/27/2019 Data Schedule1
30/39
-
7/27/2019 Data Schedule1
31/39
5A
5kV
Yes
30VDC
Yes
Yes
Yes
(50% +50%)
rves
5A
30VDC
50-200%
20-80%
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
3 NosYes
72x72mm
1
400/5A
-
7/27/2019 Data Schedule1
32/39
Yes
Yes
ARTH FAULT IDMT PROTECTION
400/5A
3
5P10
15 VA
25/31.5 kA
400/5A
3 No
1
15 VA
25/31.5 kA
5A
30VDC
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
-
7/27/2019 Data Schedule1
33/39
Yes
Yes
3 Nos
0-400A
72x72mm
1400/5A
30VDC
400/300/5A
3
X
15 VA
25/31.5 kA
-
-
Yes
-
-
400/5A
3
5P1015 VA
25/31.5 kA
400/5A
3
-
7/27/2019 Data Schedule1
34/39
5P10
15 VA
25/31.5 kA
5A
30VDC
Yes
Yes
50-200%
Yes10-80%
Yes
Yes
Yes
Yes
Yes
-
7/27/2019 Data Schedule1
35/39
-
7/27/2019 Data Schedule1
36/39
-
7/27/2019 Data Schedule1
37/39
-
7/27/2019 Data Schedule1
38/39
-
7/27/2019 Data Schedule1
39/39