WHY DCS ?

DCS stands for Distributed Control System which provides an Automation platform For controlling the plant process & Control Systems with optimum accuracy & efficiency.

Incorporating DCS enables remote communication with all the field devices from the Control Room.

The DCS has got processors which can process the signals really fast & can command the field devices i.e. Control Valves, Pneumatic Dampers, VFD-Motors, Pump’s Scoop-Control, Burners etc. to control the various process parameters viz. Press., Temp., Flow, Level, Load, Speed/Frequency etc.

DISTRIBUTION

• Functional Distribution.

• Geographic Distribution.

SIGNAL TYPES AI AO DI DO

Press. Transmitters

Level Transmitters

Flow Transmitters

RTD & Thermocouple

LVDT-Position T/X

Control Valves

Scoop Control

Motors-VFD

Dampers

Limit S/W

Pressure S/W

Torque S/W

ON-OFF Valves

Solenoid V/V

ON-OFF Valves

ON-OFF Dampers

RELAYS-TRIP Coils

Signal: 4-20 mA Signal: 4-20 mA Signal: 0-24 V Signal: 0-24 V

Source: ABB-DCS / DPL-300 MW

AI - MODULE

AO - MODULE DI - MODULE DO - MODULE

Input channels Input channels Input channels

Input channels

DCS - Configuration

Therefore as expected we have 4 basic input & output [I/O] modules called;

AI – Modules 4-20 mA AO -- Modules 4-20 mA DI – Modules 0-24V DO – Modules 0-24V

CI – Module: Comm. Interface which is the media of communication b/w IO Modules& the Controller.

• CI-MASTER: with Controller.

• CI- SLAVE: with the I/O modules.

Controller: AC – 800 M is the controller with microprocessor PM – 864 [speed 96MHz / 32 Mb RAM].

Profibus: We have a process field bus connection b/w the I/O Modules & the Controller.Further the Controllers are connected to the Engineering Station & Operating Stations via Serversthrough Fiber-Optic cables.

Source: ABB-DCS / DPL-300 MW

DCS – An Overview

Source: ABB-DCS / DPL-300 MWCI - MASTER

CI - SLAVE

CI - SLAVE

CI - SLAVE AI / AO / DI / DO - RACK

AI / AO / DI / DO - RACK

AI / AO / DI / DO - RACK

FIELBUS COMMUNICATION

Panel Configuration of a Typical DCS

Front View: showing the Controllers, Ethernet Switches & The Field Bus.

Rear View: showing the I/O Modules, the Power Distribution & JB connections.

DCS - Architecture

Source: ABB-DCS / DPL-300 MW

MAJOR BOILER CONTROL LOOPS MAJOR TURBINE CONTROL LOOPS 1. Furnace Draft Control Loop. 1. Speed/Frequency Control Loop. 2. 3-Element Control Loop. 2. Hotwell Level Control Loop. 3. Fuel Flow Control Loop. 3. Gland Sealing Press. Control Loop. 4. Air Flow Control Loop. 4. Lube Oil Control Temp Control Loop. 5. De-Aerator Level Control Loop. 5. Turbine Vacuum Control Loop. 6. De-Aerator Pressure Control Loop. 7. PRDS Control Loop.

8. Superheated Steam Temp. Control Loop.

VARIOUS CONTROL SYSTEMS IN A POWER-PLANT

De-Aerator Level Control

Deaerator Level Control Valve

Level T/X

4-20 mA as AI

A / D Converter

Binary Signals 0 & 1

D / A Converter

Binary Signals 0 & 1

4-20 mA as AO

Furnace Draft Control Loop

ID Fan Damper

De-Aerator Pressure Control Loop

Press. T/XPressure Control Valve

Superheated Steam Temp. Control Loop

Thermocouple

Spray Control Valve

3 ELEMENT DRUM LEVEL CONTROL LOOP

Press. T/X

ThermocoupleVFD – Drag Chain Feeders

Combustion Control Loop Fuel Flow Control Loop

Combustion Control Loop Air Flow Control Loop

Hotwell Level Control Loop

Level T/X

Hotwell Control Valve

Scoop Control

PRDS - Pressure Control Loop

Press. T/X Press. Reducing Valve

PRDS – Temp. Control Loop

Thermocouple/RTD

Spray Control Valve

Speed/Frequency Control Loop

WOODWARD – 505 E

AI AO

Remote SP

FIELD FIELDDCS

Interlocks

Auto/Manual Stn.

I

A/M

AI- Module AO- Module

WOODWARD 505 E

Press. T/X.Pr

LT-A LT-B PT FT FT

1 out of 2 Logic

PID 1/3 E

+

PID

MVR-SP

30 % Control Valve100 % Control Valve

FEED-FLOWSTEAM-FLOWDRUM-PRESS.DRUM-LEVEL

C-SP

MV

I/PI/P

FIELD

DCS

FIELD

4-20 mA

AO- CARD

AI- CARD

I

A/M

AI- Module AO- Module Turbine Control ValveSpeed Sensor

LOAD [MW]

Main Steam Pr.

Extraction Pr.

I

A/M

Trip SpeedF + F

F-Speed F - F

VFDDrag Chain Feeders

Combustion Control Loop Fuel Flow Control Loop

-