detecting systems
Post on 07-Apr-2018
233 Views
Preview:
TRANSCRIPT
-
8/4/2019 Detecting Systems
1/18
FIRE SYSTEMSTYPE OF DETECTORS
-
8/4/2019 Detecting Systems
2/18
CONVENTIONAL DETECTORS-
Smoke detectors
Heat detectors
Light obscuring detectors
Infrared detectors
UV detectors
-
8/4/2019 Detecting Systems
3/18
SMOKEDETECTORS
-
8/4/2019 Detecting Systems
4/18
TWO TYPES-
Ionisation smokedetector-
Light scatteringsmoke detector-
-
8/4/2019 Detecting Systems
5/18
HEATDETECTORS
-Heat detectors are used
where smoking ispermitted.
-Response time is longer
than smoke detectors.
-
8/4/2019 Detecting Systems
6/18
TWO TYPES-
Fusible type- Bi-metallic coil type-
-
8/4/2019 Detecting Systems
7/18
LIGHTOBSCURING
-
8/4/2019 Detecting Systems
8/18
WORKING-
A beam of light is projected across the protected area close to the ceiling. The light fallsonto a photo-electric cell. Smoke rising from a fire passes through the light beam toobscure and interrupt the amount of light falling on the photo-electric cell. The flow ofelectric current from the cell reduces sufficiently to activate an alarm relay.
-
8/4/2019 Detecting Systems
9/18
INFRAREDDETECTORSFire also releases radiant energyin the form of visible light, infra-red and ultra-violet radiation.
Radiant energy travels in wavesfrom the fire.
-
8/4/2019 Detecting Systems
10/18
WORKING-
Flames have a distinctive flicker, normally in the range of 4 to 15Hz. The filter is used to exclude signals outside of this range.
-
8/4/2019 Detecting Systems
11/18
UVDETECTORS
-
8/4/2019 Detecting Systems
12/18
WORKING-
reacts with ultra-violet radiation. When the bulb receives radiant thesedetectors have a gas-filled bulb which energy, the gas is ionised toproduce an electric current. When this current exceeds the set point ofthe amplifier the alarm circuit closes to operate the alarm system.
-
8/4/2019 Detecting Systems
13/18
PLACING
THEDETECTORS
-
8/4/2019 Detecting Systems
14/18
PLACING AREAS- Should be installed in all areas of the
protected premises.
should include all rooms, halls, storage areas,basements
attics, lofts, and spaces above suspendedceilings including plenum areas utilized aspart of the HVAC system.
All closets, elevator shafts, enclosed stairways,dumbwaiter shafts, chutes, and othersubdivisions and all accessible spaces.
-
8/4/2019 Detecting Systems
15/18
when only one detector is required in a room or space, the detectorshould be placed as close to the center of the ceiling as possible.
If a center location is not possible, the detector may be placed nocloser than 4 inches from the wall.
Wall-mounted detectors should be located not less than 4 inches normore than 12 inches from the ceiling to the top of the detector, and atleast 4 inches from any corner wall junction.
Should not be placed in path of ducts and should maintain a distanceof atleat 3 feet because it can cause accumulation of dust.
-
8/4/2019 Detecting Systems
16/18
DETECTOR SPACING-
-
8/4/2019 Detecting Systems
17/18
WHERE NOT TO PLACEDETECTORS-
Excessively Dusty or Dirty Areas
Outdoors
Wet or Excessively Humid Areas
Elevator Lobbies
Extreme Temperatures
Areas with Combustion Particles
Manufacturing Areas
Fluorescent Light Fixtures
-
8/4/2019 Detecting Systems
18/18
Submitted by-
PRIYA AGARWALSAURABH AGARWAL
top related