digital panel meter energy me - larsen & toubro. wl - wc 4000 energy...digital panel meter energy...

Post on 01-Feb-2021

93 Views

Category:

Documents

5 Downloads

Preview:

Click to see full reader

TRANSCRIPT

  • Digital Panel Meter

    Energy Meter

    4000 LED Series

    INSTRUCTION MANUAL

    2. LED Indication

    1.FeaturesAccuracy class 1 as per IEC , class 0.5 as per IEC 62053-22· 62053-21True RMS measurement·Simultaneous sampling of Volts & Amps·Positive accumulation of active energy even with CT polarity reversal, reverse lock programmable·User programmable password protection·Auto scrolling·Auto-scaling of Kilo, Mega, Giga·Low PT, CT burden·Programmable PT, CT ratio·Field programmable 3 Phase 4 Wire, 3 Phase 3 Wire, 1 Phase configuration·OLD register to store the previously cleared energy value·Wide operating range of 80 to 300 V AC/DC auxiliary supply·Site selectable 1A/5A·Energy display format programmable-counter based or resolution based·

    3.Technical Specification

    ENERGY METER

    WL 4000

    REV

    PRG

    M

    K

    -

    Pulse ON(only for Wh parameteris selected)

    CommunicationON

    Mega ON

    Kilo ON

    Both ONGiga}

    Reverse

    41 5.0 P.P

    Radiated, radio-frequency,electromagnetic field immunity testImmunity to electromagneticHF fields through conducted lines

    Input voltage

    Input current

    Frequency

    Aux voltage

    Aux burden

    Freq range

    Test of power consumption

    Voltage dips and interrupts

    Short time over current protection

    Fast transients burst test

    Surge immunity test

    Rated power frequency magnetic fields

    Emission

    Immunity to electrostatic discharge

    Measuringcircuit

    Auxilliarycircuit

    Electricalrequirements

    Electro-magnetic

    compatibility(EMC)

    50 - 550 VLL

    Burden : 0.2VA max per phase

    -/5A and -/1A site selectable

    Current range from 10% to 120% of In (50mA-6A),Starting current : 0.4% of full scale

    PT Primary and Secondary user programmablefor LT and HT applications

    CT Primary and Secondary user programmablefor LT and HT applications

    40 - 70 Hz

    80 - 300V AC/DC

  • 8. Mounting Dimensions7. Wiring Diagram

    AMF IP240V AC

    AMF IP240V AC

    Load Line

    Received (Import) Delivered (Export)

    3 Phase 4 Wire System

    Load Line

    Received (Import) Delivered (Export)

    3 Phase 3 Wire System

    Load Line

    Received (Import) Delivered (Export)

    Single Phase System

    AMF IP240V AC

    4.3.Display

    Option/Range

    415

    100V-999kvTo set 11.10kV Set first four digits(1110) as explained above pressUP/DOWN key to place decimal pointat appropriate location.M & K both LED will glow for Giga

    41 5.0 P.P

    3P 4W3P 3W1 Phase

    3P 4W

    ConFIG.(Defines thepower systemconfiguration.)

    PT Primary4150P.P

    First four digit : Parameter value5th & 6th digit : Parameter to edit

    ProgrammingParameter Default

    CUSTOMER INTERACTION CENTRE ( )CIC

    TOLL-Free: 1800 233 5858, 1800 200 5858

    Telephone : 022 6774 5858

    email: cic@LNTEBG.com

    In case of complaint please contact

    Electrical Standard Products

    L&T Business Park, Tower 'B' / 3rd Floor

    Saki Vihar Road, Powai Mumbai 400 072

    Website: www.Lntebg.com

    L&T Electrical & Automation

    5. Memory Map

    float

    float

    float

    float

    float

    float

    float

    40101

    40103

    40105

    40107

    40117

    40119

    40121

    Datatype

    Watts Total

    Watts R phase

    Watts Y phase

    Watts B phase

    PF Avg (inst)

    PF R phase

    PF Y phase

    ParameterAddress

    float

    float

    float

    float

    float

    float

    float

    40123

    40125

    40127

    40129

    40131

    40159

    40161

    Datatype

    PF B phase

    VA total

    VA R phase

    VA Y phase

    VA B phase

    Wh

    VAh

    ParameterAddress

    4. Programming Mode4.1 Programming keys

    To select Edit Mode and save parameter

    DOWN to decrement value or parameter

    4.2 General Programming Guide·�Press UP + Down to enter Programming Mode

    Enter Password (default value 0000)·�Blink indicates Edit Mode is ON·�Press DOWN to decrement value·�0/9/8/7/6/5/4/3/2/1

    ·�Press UP to move to the next digit till 4th digitIf Password is correct, meter display readsFor Clear Mode move to step .2.14For Programming Mode move to step .2.24

    4.2.1.Clear Mode·�Press UP to Enter Clear Mode Display reads “ ”·�Press UP to clear parameter. Display prompts “ ”·�Press DOWN to change for “ ” (yes) to clear valuesy·�Press UP to clear

    If password is incorrect, meter will display nextparameter but cannot be edited.

    4.2.2. Programming ModePress Down To Enter Programming Mode·�

    ·�Press UP key to select the Edit Modeindicates Edit Mode is� � ONBlink

    Press DOWN to decrement values or·�to select from available optionsPress UP to accept the value of the parameter·�Press DOWN to edit next parameters till end·�after the configuration of last parameter displayscreen will prompt “ ”, Display reads “ ” (YES)SAVE YPress to change to “ ” (NO)·� DOWNPress UP to save.·�

    4.4. Enabling and Disabling Auto ScrollingPress DOWN for 6 secsDisplay Shows: EnbL. Au.Again press DOWN for 6 secDisplay Shows: dSbL. Au.

    PT Secondary 4150P.S

    CT Secondary 5000C.S

    CT Primary 5000C.P

    VA Selection UE C.HUA.

    Parameter options

    Baud rate

    Parity

    Reverse lock

    415.0

    5.000

    5.000

    Wh

    VEC.Har

    9600

    Even

    No

    1.000

    0000

    Resolution

    Wh

    Method of VA Selection:Arithmetic /Vector harmonics /Vector

    50V to 550V

    0.5A - 99KA

    0.5A - 6A

    Options: Wh/PF/W/VA

    2400, 4800, 9600 19.2k

    Even/Odd/none

    Yes/NoIf YES it blocks energy accumulation incase the CT polarity reverse.

    1 to 247

    0000 to 9999

    Resolution/Counter

    Wh/VAh

    Slave Id 1000SL

    Energy Selection

    Energy

    PASSWORD

    WL

    40

    00

    05

    01

    A

    Steps for MountingInsert meter to panelwithout clamps

    Insert both clamps

    1

    2

    3

    4mm

    54mm

    12

    3

    I

    I

    90 + .2 0- 0.0

    90 + .2 0- 0.0

    6. Display Parameters6 in.1 Display of Parameters meter

    Display Meaning

    Active Energy

    Active Energy Old

    Apparent Energy

    Apparent Energy Old

    Power Factor

    Apparent Power

    Power Factor r-phase

    Power Factor y-phase

    Display Meaning

    Power Factor b-phase

    Watts r-phase

    Watts y-phase

    Watts b-phase

    Watts Total

    Apparent Power r-phase

    Apparent Power y-phase

    Apparent Power b-phase

    6 2 Energy Value Interpretation.

    Sl.No. Displayon Meter

    Parameterselection

    Energyselection

    1. Wh Wh Wh

    Programming mode

    2. VAh Wh VAh

    In auto scroll mode, the parameter name (eg. Wh)

    will be displayed for 1 sec. after which the energy

    value will be displayed for next 4 sec.

  • Digital Panel Meter

    Energy Meter

    4000 LCD Series

    INSTRUCTION MANUAL

    2. LED Indication

    1. Features· Accuracy class 1 as per IEC 62053-21, class 0.5 as per IEC 62053-22· True RMS measurement· Simultaneous sampling of Volts & Amps· Positive accumulation of active energy even with CT polarity reversal, reverse lock programmable· User programmable password protection· Auto scrolling· Auto-scaling of Kilo, Mega, Giga values· Low PT, CT burden· Programmable PT, CT ratio· Field programmable 3 Phase 4 Wire, 3 Phase 3 Wire, 1 Phase configuration· OLD register to store the previously cleared energy value· Wide operating range of 80 to 300 V AC/DC auxiliary supply· Site selectable 1A/5A· Energy display format programmable-counter based or resolution based

    3.Technical Specification

    CommunicationON

    Input voltage

    Input current

    Frequency

    Aux voltage

    Aux burden

    Freq range

    Test of power consumption

    Voltage dips and interrupts

    Short time over current protection

    Fast transients burst test

    Surge immunity test

    Rated power frequency magnetic fields

    Emission

    Radiated, radio-frequency, electromagnetic field immunity test

    Immunity to electromagnetic HF fields through conducted lines

    Immunity to electrostatic discharge

    Measuring circuit

    Auxiliary circuit

    Electrical requirements

    Electro-Magnetic

    Compatibility (EMC)

    50 - 520 VLL

    Burden : 0.2VA max per phase

    -/5A and -/1A site selectable

    Current range from 50mA - 5A with overload capacity upto 120% In (i.e., 6A)

    PT Primary and Secondary user programmable for LT and HT applications

    CT Primary and Secondary user programmable for LT and HT applications

    40 - 70 Hz

    80 - 300V AC/DC

  • 8. Mounting Dimensions

    4.3.Display

    Option/Range

    415

    100V-999kvTo set 33kV Set first four digits(3300) as explained above. PressUP/DOWN key to place decimal point at appropriate location. K/M will indicate the Kilo/Mega. Both together will indicate Giga.

    3P 4W3P 3W1 Phase

    3P 4W

    4. Programming Mode4.1 Programming keys

    To select Edit Mode and save parameter

    DOWN to decrement value or parameter

    4.2 General Programming Guide· Press UP + Down to enter Programming Mode · Enter Password (default value 0000) · Blink indicates Edit Mode is ON· Press DOWN to decrement value 0/9/8/7/6/5/4/3/2/1 · Press UP to move to the next digit till 4th digit If Password is correct, meter display reads For Clear Mode move to step 4.2.1 For Programming Mode move to step 4.2.2

    4.2.1.Clear Mode· Press UP to Enter Clear Mode Display reads “ ”· Press UP to clear parameter. Display prompts “ ”· Press DOWN to change for “y” (yes) to clear values· Press UP to clear

    If Customer enters wrong password then Pass Error will be displayed (Meter will display next parameter but cannot be edited). If customer forgets the set password, kindly contact L&T Customer Interaction Center.

    First three digit : Parameter to edit4th to 7th digit : Parameter value

    Programming Parameter

    Default

    4.2.2. Programming Mode· Press Down To Enter Programming Mode· Press UP key to select the Edit Mode

    indicates Edit Mode is ONBlink· Press DOWN to decrement values or to select from available options· Press UP to accept the value of the parameter· Press DOWN to edit next parameters till end after the configuration of last parameter display screen will prompt “SAVE”, Display reads “Y” (YES)· Press DOWN to change to “ ” (NO)· Press UP to save

    PT Primary

    ConFIGDefines thepower systemconfiguration.

    CUSTOMER INTERACTION CENTRE (CIC)

    TOLL-Free: 1800 233 5858, 1800 200 5858

    Telephone : 022 6774 5858

    email: cic@LNTEBG.com

    In case of complaint please contact

    Electrical Standard Products

    L&T Business Park, Tower 'B' / 3rd Floor

    Saki Vihar Road, Powai Mumbai 400 072

    Website: www.Lntebg.com

    L&T Electrical & Automation

    4.4. Enabling and Disabling Auto ScrollingPress DOWN for 6 secs Display Shows: EnbL. Au.Again press DOWN for 6 secDisplay Shows: dSbL. Au.

    415.0

    5.000

    5.000

    50V to 550V

    0.5A - 99kA

    0.5A - 6A

    9600

    Even

    VECH

    1.000

    Wh

    Method of VA Selection: Arithmetic /Vector harmonics /Vector

    2400, 4800, 9600 19.2k

    Even/Odd/none

    1 to 247

    Options: Wh/PF/W/VA

    0000

    Resolution

    Wh

    0000 to 9999

    Resolution/Counte

    Wh /VAh

    NoYes/NoIf YES it blocks energy accumulation in case the CT polarity reverse.

    PASSWORD

    Energy

    Energy Selection

    VA Selection

    Parameter options

    Baud Rate

    Parity

    Slave Id

    CT Primary

    PT Secondary

    CT Secondary

    Reverse Lock

    Steps for MountingInsert meter to panelwithout clamps

    Insert both clamps

    1

    2

    3

    4mm

    54mm

    12

    3

    90 +2.0-0.0

    90 +2.0-0.0

    float

    float

    float

    float

    float

    float

    float

    Data type

    Watts Total

    Watts R phase

    Watts Y phase

    Watts B phase

    PF Avg (inst)

    PF R phase

    PF Y phase

    Parameter

    float

    float

    float

    float

    float

    float

    float

    40123

    40125

    40127

    40129

    40131

    40159

    40161

    Data type

    PF B phase

    VA total

    VA R phase

    VA Y phase

    VA B phase

    Wh

    VAh

    ParameterAddress

    6. Display Parameters6.1 Display of Parameters in meter

    Display Meaning

    Active Energy

    Active Energy Old

    Apparent Energy

    Apparent Energy Old

    Power Factor

    Apparent Power

    Power Factor r-phase

    Power Factor y-phase

    Display Meaning

    Power Factor b-phase

    Watts r-phase

    Watts y-phase

    Watts b-phase

    Watts Total

    Apparent Power r-phase

    Apparent Power y-phase

    Apparent Power b-phase

    6.2 Energy Value Interpretation

    Sl.No. Displayon Meter

    1. Wh

    2. VAh

    3 Phase 4 Wire System 3 Phase 3 Wire System Single Phase System

    AMF IP240V AC

    Load Line

    Received (Import) Delivered (Export)

    AMF IP240V AC

    Load Line

    Received (Import) Delivered (Export)

    Line

    Delivered (Export)

    AMF IP240V AC

    7. Wiring Diagram

    r

    5. Memory Map

    40101

    40103

    40105

    40107

    40117

    40119

    40121

    Address

    Parameterselection

    Energyselection

    Wh Wh

    Programming mode

    Wh VAh

    Load

    Received (Import)

    Ver

    1.1

    (Dece

    mber

    2019)

    Note:1. If energy value is reset or CT values are modified,then the existing energy value will be made zero and will be saved in another register called Wh.OLD (old energy).

top related