®DSEULTRA®

STARTINGWITHQUALITY. SPECIFICATION

The DSE4410 is an Auto StartControl Module and the DSE4420 isan Auto Mains (Utility) FailureControl Module for single gen-setapplications. Both modules havebeen designed to work withelectronic and non electronicengines providing advanced enginemonitoring and protection features.The modules are available inmagnetic pick-up and Canbusversions.

The modules include a back-litLCD display which clearly show thestatus of the engine at all times.They monitor frequency, voltage,current, oil pressure, coolanttemperature and fuel level. Themodules have also been designedto display the warning andshutdown status of the engine.

Both modules include six digitalinputs and six outputs. Fouroutputs are configurable on themagnetic pick-up version and sixare configurable on the Canbusversion. The modules can eitherbe programmed using the frontpanel or by using the DSEConfiguration Suite PC software.

FEATURES• PC and front panel configurableCAN and magnetic pick-up versions• Six digital inputs• Six outputs (all six configurable onCANbus version, four configurableon magnetic pick-up version)

• Automatic mains (utility) supplymonitoring (DSE4420 only)

• Event log• 50/60 Hz calibration setting• Configurable timers• Automatic shutdown or warningwhen fault conditions are detected

• Manual and remote start• Engine pre-heat• Protected Solid State Outputs(PSS)

• Advanced metering capability• Front panel mounting• Front panel programming• Engine hours counter• LED indicators• Back-lit LCD display

BENEFITS• Transfers between mains (utility)and generator power(DSE4420 only)

• Hours counter provides accurateinformation for monitoring andmaintenance periods

• User-friendly set-up and buttonlayout. Multiple engine parametersare monitored simultaneously

• Module can be configured to suitindividual applications. Wide rangeof engines can be specifiedIP65/NEMA 12 rating offersadvanced resistance to wateringress

• License free PC software

OPERATIONThe module is operated using thefront STOP/RESET, MANUAL, AUTOand START push buttons.

Two additional push buttons next tothe LCD screen are provided toscroll through the modules’ meteringdisplays and to access the event log.

OVERSPEED PROTECTIONThe engine over speed trip settingcan be calibrated for 50Hz or 60Hznominal operation During enginecranking and for a user configurabletime after the engine starts running,all alarm conditions are suspendedto allow the engine to reach itsoptimum running speed.

CONFIGURATIONThe modules can be configuredusing the front panel or by remotePC using a USB connection leadand the DSE Configuration Suite PCsoftware.

ELECTRONIC ENGINECOMPATIBILITY• CAT• Cummins• Deutz• John Deere• MTU• Perkins• Scania• Volvo• Generic• Plus additional manufacturers

DC SUPPLY8V to 35V Continuous

CRANKING DROPOUTSAble to survive 0V for 50mS, providing supplywas at least 10V before dropout and supplyrecovers to 5V. This is achieved without theneed for internal batteries. LEDs and backlightwill not be maintained during cranking.

MAXIMUM OPERATING CURRENTTBC

MAXIMUM STANDBY CURRENTTBC

GENERATOR INPUT RANGE15V to 333V AC (L-N) absolute maximum50Hz - 60Hz (min 15V AC)

CHARGE FAIL/EXCITATION RANGE0V to 35V

VOLTAGE RANGE0.5V RMS minimum

FREQUENCY RANGE10,000 Hz (max)

15V to 333V AC (L-N) absolute maximum25V to 576V AC (L-L) absolute maximum50Hz - 60Hz (min 15V AC)

OVERALL180mm x 116mm x 42mm7.1” x 4.6” x 1.7”

PANEL CUT-OUT154mm x 98mm6” x 3.9”

MAXIMUM PANEL THICKNESS8mm (0.3”)

DSE4410 & DSE4420AUTO START & AUTO MAINS (UTILITY) FAILURE CONTROL MODULES

DC SUPPLY

MAGNETIC PICKUP

OUTPUTS

DIMENSIONS

MAINS (UTILITY) SENSING INPUT RANGE(DSE4420 ONLY)

OUTPUT A (FUEL)2 Amp DC at supply voltage

OUTPUT B (START)2 Amp DC at supply voltage

AUXILIARY OUTPUTS C,D2 Amp DC at supply voltage

BATTERY

-VE

+V

E SE

ND

ER

CO

MM

ON

FUE

LS

EN

DE

R

6 INPUTSPLANT +VEPLANT +VE

4 FET OUTPUTSENGINE ECU

H L

BATTERY NEGATIVE MUST BE GROUNDED

TERMINALS SUITABLE FOR 22-16 AWG (0.6mm - 1.3mm )FIELD WIRING

TIGHTENING TORQUE = 0.8Nm (7lb-in)

NOTE 1. THESE GROUND CONNECTIONS MUST BE ON THE EN-GINE BLOCK, AND MUST BE TO THE SENDER BODIES.

NOTE 3. MAINS BREAKER CLOSED OUTPUT SHOULD BECONFIGURED FOR DE-ENERGISE CLOSE MAINS, AND USE THENORMALLY CLOSED CONTACTS OF MBCR.

†NOTE 2. 120 R TERMINATING RESISTORMAY BE REQUIRED EXTERNALLYSEE ENGINE MANUFACTURERS LITERATURE

NOTE 1

15 16 12 13 14 17 18 19 20

1 32 4 5 10 11 21 22 23 24 25 26 6 7 8 9 14 12 13

U NL1

GEN VOLTS

+ -MPU

RE

CO

MM

EN

DE

DT

HA

TE

ME

RG

EN

CY

ST

OP

BR

EA

KS

TH

EFU

EL

AN

DC

RA

NK

OU

TP

UT

S

FUE

L

INP

UT

AC

ON

FIG

UR

ED

FOR

EM

ST

OP

US

ER

CO

NFI

GU

RA

BLE

-VE

INP

UT

B

US

ER

CO

NFI

GU

RA

BLE

-VE

INP

UT

C

US

ER

CO

NFI

GU

RA

BLE

-VE

INP

UT

D

US

ER

CO

NFI

GU

RA

BLE

-VE

INP

UT

E

US

ER

CO

NFI

GU

RA

BLE

-VE

INP

UT

F

US

ER

CO

NFI

GU

RA

BLE

OU

TP

UT

CG

EN

BR

EA

KE

RC

LOS

E

US

ER

CO

NFI

GU

RA

BLE

OU

TP

UT

DM

AIN

SB

RE

AK

ER

CLO

SE

US

ER

CO

NFI

GU

RA

BLE

+V

EO

UT

PU

TE

US

ER

CO

NFI

GU

RA

BLE

+V

EO

UT

PU

TF

MIN

2A

MP

MA

X20

AM

PA

NT

I-S

UR

GE

FUS

EB

AT

TE

RY

FUEL

WL

CRANK

GBCR

CHARGEALT

2A

MP

FUS

ES

2A

MP

FUS

ES

AP

PR

OP

RIA

TE

FUS

E

MPU

MAG PICK UP VERSION ONLY

TO LOAD

L3

N

L2

L1

L3

N

L2

L1

FROMMAINS(UTILITY)

FROMGENERATOR

FUE

LO

/PA

CR

AN

KO

/PB

PROGRAMMING PORT

USB

CON 1 CON 2

GBCR

DSE4420 ONLY

MODULE 4410/4420

MBCR

*

AP

PR

OP

RIA

TE

FUS

E

DO NOTCONNECT

THESCREEN

TO ENGINE

CONNECT THESCREEN TO

ENGINE ONLY

ELECTRONIC ENGINE VERSION ONLY

*

*

MBCR

®

RELATED MATERIALSTITLE PART NO’SDSE4410 Manual 057-092DSE4420 Manual 057-093DSE Configuration Suite PC Software Manual 057-101DSE4410 Installation Instructions 053-056DSE4420 Installation Instructions 053-057

DEEP SEA ELECTRONICS INC3230 Williams AvenueRockfordIL 61101-2668 USA

TELEPHONE+1 (815) 316 8706

FACSIMILE+1 (815) 316 8708

EMAILsales@deepseausa.com

WEBSITEwww.deepseausa.com

DEEP SEA ELECTRONICS PLCHighfield HouseHunmanby Industrial EstateHunmanby, North YorkshireYO14 0PH England

TELEPHONE+44 (0)1723 890099

FACSIMILE+44 (0)1723 893303

EMAILsales@deepseaplc.com

WEBSITEwww.deepseaplc.com

Registered in England & Wales No.01319649 VAT No.316923457

DEEP SEA ELECTRONICS maintains a policy of continuous development and reserves the right tochange the details shown on this data sheet without prior notice. The contents are intended for guidance only.

055-068/01/16 (2)

This data sheet is printed on 9lives 55 Silk, which is produced with 55% recycled fibrefrom both pre and post-consumer sources, together with 45% virgin ECF fibre.

DSE4410 & DSE4420

BS EN 61000-6-2EMC Generic Emission Standard for theIndustrial EnvironmentBS EN 61000-6-4EMC Generic Emission Standard for theIndustrial Environment

ENVIRONMENTAL

TESTING STANDARDS

INSTRUMENTATION AND ALARMS

ELECTRICAL SAFETYBS EN 60950Safety of Information Technology Equipment,including Electrical Business Equipment

TEMPERATURE (OPERATING)BS EN 60068-2-2Test Ab to +70oC 60067-2-2 HotTest Ab to -30oC 60068-2-1 Cold

VIBRATIONBS EN 60068-2-6Ten sweeps in each of three major axes5Hz to 8Hz @ +/-7.5mm, 8Hz to 500Hz @ 2gn

HUMIDITYBS 2011 part 2.1 60068-2-30Test Cb Ob Cyclic93% RH @ 40oC for 48 hours

SHOCKBS EN 60068-2-27Three shocks in each of three major axes15gn in 11mS

ELECTRICAL SAFETY/ELECTROMAGNETIC COMPATIBILITY

TESTING STANDARDS

The DSE4410 and DSE4420 both providecomprehensive metering and alarm indications:

Generator frequencyUnder/over speedGenerator volts (L-L, L-N)Engine oil pressureEngine coolant temperatureFuel level (warning or shutdown)Hours run counterBattery voltsFail to start/stopEmergency stopFailed to reach loading voltage/frequencyCharge failLow DC voltageCAN diagnosticsMains volts 3 phase (DSE4420 only)AMF indications (DSE4420 only)