Electric Power System Modeling & Simulation
Michael Smith
02/15/2010
Outline• Introduction
• Power System Introduction/Background
• Data Requirements
• Model/Simulation Development
• Analysis
• Conclusion
IntroductionObjective:
• Understand the behavior of Electric Power (EP) systems
Properties of EP systems:
• Large scale, complicated, dynamic and nonlinear
• Composed of interdependent, heterogeneous components
• Result from incremental evolution in system configuration driven by response to failures and adoption of innovation
• Possess considerable system structure (e.g., power law statistics, HDS configuration)
100
101
102
103
104
105
106
107
108
10-3
10-2
10-1
100
North American Power System Outages (NERC Data 1984-2002)
Fre
quency o
f outa
ge
Number of customers affected by outage
2003 NE Outage
1965 NE Outage
1977 NY Outage
1996 Western Outage
Introduction/Motivation
The Cost of “Unreliability”
• Since 9/11, [reported] attacks on industrial process control systems have increased 10 fold
• 10 second electric power outage at LAX– Tower-to-tower communication
lost for three hours– Approximately 80 – 100 flights
delayed
• Ohio nuclear power plant disrupted by SQL Slammer worm
• Stock market crashes
August 14th Blackout1
2 Canadian Provinces
8 U.S. states
3 deaths
12 airports closed
23 cases of looting in Ottawa
100 power plants
9,266 square miles
61,800 MW of power lost
1.5 million Cleveland residents
without water
50 million people
$4-6 billion in economic activity lost
1. US DOE, Office of Electric Transmission and Distribution, December 1, 2003, Bill Parks
Power System Background
Pictorial View
• Components
• Generation Station, Transmission network, Substation, Loads
• Key Terms
• Voltage, Power, Load flow, Steady State, Transient, Dynamic
jX1
jX2
V0 0 V
generation station transmission lines substation load
Power Systems Background
Model view
Data Required for ModelingData for Load-Flow/Power-Flow Model
The first type of data requested is that needed to develop a load-flow/power-flow model of a power system area:– topology of the area with connection points (busses) as nodes and transmission lines and transformers
as edges, – transmission line parameters such as pi-model parameters, compensation and ratings/limits, – transformer parameters such as pi-model, turns ratio and ratings/limits, – tie-line locations and ratings, – generation location and ratings/limits, – load locations and load compensation, and – any complete load-flow/power-flow solutions for area (from model or instrumentation) with data
mentioned above, generator powers, load powers, line powers, and bus voltages and phase angles. Data for Dynamic Model
In order to perform transient analysis and stability studies additional power system data is required to supplement that identified above for load-flow/power-flow models. Example data that would assist with construction of a dynamic model include: – number, size and type of generators with any available mechanical, electrical, and control (governor,
voltage regulation, etc.) parameters, – mix of residential, commercial and industrial load at each bus,– location and specifications for distributed control devices such as tap-changing transformers, switched
shunt compensation, static Var compensators, flexible AC transmission systems, etc., – location and specifications for protection devices such as relays and load shedding, and– location and specifications of any other relevant control and/or protection devices.
Data for Model ValidationTime-series data (generator powers, load powers, line powers, voltages, voltage phase angles, frequency, currents, etc.) recorded from the power system in response to short-term load fluctuation, 24-hour load variation or known disturbance is requested to support model validation studies and dynamic grid analysis. Data captured over the short term would be sampled at sub-second or faster while long-term would be sampled on intervals of 15 minutes.
Sinusoidal Steady-State Analysis
Detailed Model View• Equivalent π transmission line models• Single phase assuming 3 phases are symmetrical• p.u. (per unit system) ease of power system analysis
Complex Current Injections & Network Line Powers
Real/Imaginary Network & Power Balance Equations
Simplified Generator/Load Equations
• Internal generator dynamics
• Fixed load model
– Power (fixed)
– Internal dynamics (none)
Model
disturbances
set points
mode
changesgrid
outputs
discrete system:
switching and saturation
qi+1 = h(qi, k(x,y), r)
q1
q0
q2
continuous system:
generators, loads and network
dx/dt = fq(x, y, u)
0 = gq(x, y)
G
GL
L
Hybrid Dynamical System (HDS)
ModelKey features:
• physics-based models of network, generators (electromechanical), and loads (aggregate)
• emphasis placed upon– capturing saturation and switching behavior
– drawing conclusions about system behavior (time evolution governed by dynamics) with limited data and uncertainty
– keeping an eye towards analysis
• Both dynamic and steady-state representations for the model
Model: dynamic vs. static modelHDS Model
qi+1 = h(qi, k(x,y), r)
dx/dt = fq(x, y, u)
0 = gq(x, y)
0 50 100 150 200 250 300 350 400 450 5000
0.2
0.4
0.6
0.8
1
Area C Load Busses
16
49
50
51
52
53
54
71
72
75
68
73
87
67
88
89
76
78
79
80
81
84
85
Static (load flow) Model
0 = f(x, y, u)
0 = g(x, y)
(switching is exogenous)
0 50 100 150 200 250 300 350 400 450 5000.9
0.95
1
1.05Area C Load Busses
16
49
50
51
52
53
54
71
72
75
68
73
87
67
88
89
76
78
79
80
81
84
85
static (equilibrium)
solutions
trajectory
Questions
top related