energy saver for fan coil unit - .hk...fan coil unit (ac motor) power consumption 124 w power...
Post on 29-Jan-2021
1 Views
Preview:
TRANSCRIPT
-
Secodata Technologies Ltd.
Energy Saver forFan Coil Unit
Green I&T Day Aug 6
-
Company History2015
Established by City University students and teaching staff. Aiming HVAC* energy saving and health data collection solutions201
7201820182019
Production of Energy Saver. 3 patents registered
Customer installations. Up to 50% savings
Develop smart thermostat and health data collection solutions
Adding professional management people. Speed up market development
* HVAC: Heating, Ventilation and Air Conditioning
-
Market NeedsHVAC System uses vast amount of energyAbout HALF of the electricity used in commercial buildings is used in HVAC system.
Energy-saving requirements of Government and
EnterprisesGovernment and large companies (such as hotels) need to meet annual energy-saving targets.
Difficulties in HVAC management
It is difficult for general technical or management personnel to fully understand wide varieties of complicated HVAC systems.
Requires a simple and effective intelligent energy-saving systemSaves energy without increasing human resources
AC56%
SET 2015 Conference Paper: Space Cooling in Buildings in Hot and Humid Climates – a Review of the Effect of Humidity on the Applicability of Existing Cooling Techniques
-
Government Energy-saving Requirements
到2020年,全國萬元國內生產總值能耗比2015下降15%
-
Enterprise Energy-saving Requirements
-
Fan Coil Unit System
-
Connecting Energy Saver to Fan Coil Unit
Install in 40 minutes
HIGHMEDLOW(L)(N)
HIGHMEDLOW(L)(N)
Traditional connection
Energy Saver installed between thermostat and fan coil unit
-
Energy Saver Architecture Single stage architecture
Less complex than inverter
Low conversion loss
Sinusoidal output
Compensator power rating is less than t
he Motor power rating
Step-less fan speed control
3 patentsIntegration of Power Electronics
NLmain
VS
L
RotorRmain
Raux Laux
IM
Vx
ConverterVM
Crun
-
Direct BenefitsHigh
Speed(1120 rpm)
MiddleSpeed
(830 rpm)
LowSpeed
(630 rpm)
Ultra LowSpeed
(520 rpm)
Traditional Control 242W 235W 213W N/A
Energy Saving Control 237W
180W(55w)(reduced by 24 %)
124W(-88w)(reduced by 42 %)
90W(-120W)(reduced by 56 %)
Electricity Tariff
Save (7x24)- $481/year $770/year $1,051/year
ReducedCO2/year *
- 505kg/year 809kg/year 1,104kg/year
In-house laboratory test at City University of Hong Kong
* Public Electricity and Heat Production - summary tables of IEA (2002b)
-
Indirect Benefits
Maintains sinusoidal electric current
Rejects current harmonic distortion to motor
Reduces acoustic noise
Reduces electromagnetic emission
Prolongs lifespan of fan motor
With Energy Saver
Conventional Thermostat
-
Longer Motor Life
Fan Coil Unit (AC Motor)
Power consumption
124 W
Power consumption
213 W
In-house laboratory test at City University of Hong Kong – Low Speed Mode
Traditional control Energy Saver control
42% less energy consumption, 25.5˚C less operation temperature
-
Energy Saver Summary
Reduces Fan Coil Unit energy consumption
50% reduction in energy consumption
40 minutes installationSimply connect Ther
mostat and Fan Coil Unit
Low-investment
Reduce carbon footprint
3 Yearspayback
Corporate image
-
Energy Saver in a 5-star Chain Hotel in HK
Fan Coil Unit
AC Motor
Energy Saver+EnergyMeter
Energy Saving Measurement K
it
Energy Saver
Disabled
Power:66.37W
Energy SaverEnabled
Power:33.89W
Energy Reduction: (66.37 - 33.89) / 66.37 x 10
0% = 49%
-
2019 Market Development Plan
H2 PartnersOEM or global: Sinko, Carrier & Schneider
H1 SeminarsHK Hotel Assoication& CLP
H1 Build CasesIn hotel, office, ma
ll, hospital, government & university
H2 More RegionsSales partners in Ch
ina, Macao, Europe &South East Asia. Visit related trade shows & collect marketinformation
-
Advantages of Secodata
CITYU staff & students
R&D Support
Rich market & product development ex
perience
Professional Management Team
3 registered patents &
independent algorithms
Independent Patents
Huge potential. Existing customers including hotel chain &
office buildings
Targeting Buildings & Smart Cities
Develop for existing & future
needs
Energy & Carbon Footprint Saving
-
Thank you
Secodata TechnologiesEnergy Saver