fowler chapter 12 lecture 12 transformers

Post on 14-Jan-2016

73 Views

Category:

Documents

6 Downloads

Preview:

Click to see full reader

DESCRIPTION

FOWLER CHAPTER 12 LECTURE 12 TRANSFORMERS. TRANSFORMERS CHAPTER 12 TRANSFORMERS ARE MULTIPLE WINDING INDUCTORS. WORK ON THE PRINCIPLE OF MUTUAL INDUCTANCE. TRANSFORMERS ARE 2 OR MORE COILS LINKED BY MAGNETIC FLUX . PRIMARY COIL INDUCES A VOLTAGE IN A SECONDARY COIL BY MUTUAL INDUCTANCE. - PowerPoint PPT Presentation

TRANSCRIPT

FOWLER CHAPTER 12LECTURE 12 TRANSFORMERS

TRANSFORMERS CHAPTER 12TRANSFORMERS ARE MULTIPLE WINDING INDUCTORS.WORK ON THE PRINCIPLE OF MUTUAL INDUCTANCE.

TRANSFORMERS ARE 2 OR MORE COILS LINKED BY MAGNETIC FLUX.PRIMARY COIL INDUCES A VOLTAGE IN A SECONDARY COIL BY MUTUAL INDUCTANCE.THE AMOUNT OF MUTUAL OR SELF INDUCTION IS MEASURED IN HENRY’S.

YOU TUBE: Transformer Animation

YOU TUBE: How Transformers Work

http://www.youtube.com/watch?v=VucsoEhB0NA

http://www.youtube.com/watch?v=Q2mShGuG4RYHow electric motors work

http://www.youtube.com/watch?v=ZjwzpoCiF8A

http://www.youtube.com/watch?v=GMePE7NZcxwElectrical Transformer Tutorial

SYMBOLS

TRANFORMER WINDINGS

TRANSFORMERS TRANSFER POWER FROM PRIMARY TO SECONDARY WINDINGS.PRIMARY TAKES ELECTRICAL ENERGY AND CONVERTS IT TO MAGNETIC ENERGYSECONDARY TAKES MAGENTIC ENERGY AND CONVERTS IT TO ELECTRICAL ENERGY.THERE IS NO PHYSICAL COUPLING BETWEEN THE PRIMARY AND SECONDARY WINDINGS.

STEP UP/DOWN TRANSFORMERS

STEP UP

STEP DOWN

COEFFICIENT OF COUPLING (COC)

THE PORTION OF FLUX THAT LINKS ONE COIL TO ANOTHER.COC CAN VARY FROM 0 TO 1.AT 1, ALL THE FLUX IS COUPLED.COC CAN ALSO BE EXPRESSED. AS A %.100% = COUPLING OF 1.

COUPLING IN Fe CORE TRANSFORMERS IS NEARLY 100%. SINCE THERE IS LITTLE FLUX LEAKAGE INTO THE AIR.

AIR CORE TRANSFORMERS HAVE LOW COC DUE TO THE HIGH RELUCTANCE OF AIR,CAUSING A LARGE AMOUNT OF LEAKAGE.THIS IS CALLED LEAKAGE FLUX.THIS CAN BE CONTROLLED SOMEWHAT BY SPACING THE COILS CLOSER TOGETHER.IF COILS ARE PERPENDICULAR TO EACH OTHER COC IS CLOSE TO ZERO.

CHANGING VOLTAGE VAULESSTEP UP, STEP DOWN TRANSFORMERS.

WITH 100% COULPING THE TURNS RATIO AND VOLTAGE RATIO ARE EQUAL.

20KV500A10 MW

STEP UP TRANSFORMERAT POWER PLANT

400KV25A10 MW

LONG DISTANCETRANSMISSION LINES

400KV25A

20KV500A10 MW

STEP DOWN DISTRIBUTIONTRANSFORMER AT SUBSTATION

TO LOADS AND OTHERSTEP DOWNTRANSFORMERS.

ADVANTAGES OF HIGH VOLTAGE TRANSMISSION LINES

EFFICIENCY OF TRANSFORMERS

IN THE REAL WORLD CORES AND COILS OF TRANSFORMERS CONVERT SOME ELECTRICALENERGY INTO HEAT.

EFFICIENCY OF TRANSFORMERS IS EXPRESSED IN TERMS OF POWER.

100% PRI

SEC

P

PEFFICIENCY

EX.12-3 P309 WHAT IS THE EFFICIENCY OF A TRANSFORMER WITH A INPUT OF1880W INTO THE PRIMARY COIL AND 1730W OF OUTPUT FROM THE SECONDARY COIL.

W

EFFICIENCY

P

PEFFICIENCY

PRI

SEC

15017301880

%921001880

1730%

100%

150W LOSS, CALLED POWER LOSS.

POWER LOSS IN TRANSFORMERS IS CAUSED BY:

1.HYSTERSIS LOSS: CAUSED BY RESIDUAL MAGNETISM LEFT IN THE CORE EACH TIME THE FIELD REVERSES, WHICH CAUSES HEAT LOSS.

Steel has a "fat" hysteresis loop. It is difficult to demagnetize, so steel is used for permanent magnets. Substances, such as soft iron, with thin hysteresis loops, are used for transformer cores.

HYSTERSIS LOOP, THE NARROWER THE LOOP, THE LESS THE LOSS.HYSTERSIS LOSSES INCREASE WITH THE FREQUENCY OF PRIMARY CURRENT.

Eddy Currents, Magnetic Braking and Lenz's Law http://www.youtube.com/watch?v=otu-KV3iH_I

2. EDDY CURRENT LOSS ARE INDUCTED CURRENTS IN THE CORE FROM ITS OWN MAGNETIC FLUX. THESE EDDY CURRENTS FLOWING THRU THE CORES RESISTANCE PRODUCES HEAT.

http://www.youtube.com/watch?v=zJ23gmS3KHY

What Is Eddy Current

HOW CAN WE REDUCE EDDY CURRENT LOSES?BY INSULATING EACH LAMINATION OF THE CORE WITH A THIN LAYER OF OXIDE.THIS INCREASES THE RESISTANCE OF THE CORE WHICH REDUCES HEAT LOSS SINCE,

R

VIAS

R

VI ,R

Eddy Current Demo. http://www.youtube.com/watch?v=Yu1uRvErM80

3. COPPER LOSSPOWER LOSS IN THE WINDINGS OF THE TRANSFORMER.CAN BE FOUND FROM P= I²R, R IS THE OMIC RESISTANCE OF THE WINDING TURNS.

LOSS AND EFFICIENCYTRANSFORMERS ARE MOST EFFICIENT WHEN FULLY LOADED.EFFICIENCY DECREASES AS THE LOAD DECREASES.WHY? CURRENT FLOW IN THE TRANSFORMER PRIMARY DOES NOT DECREASE IN DIRECT PORPORTION TO THE DECREASE IN LOAD.PRIMARY CURRENT CAUSES CORE AND Cu LOSS WHEN LIGHTLY LOADED.

TRANSFORMER CORES.CLASSIFIED BY CORE MATERIALS. SUCH AS Fe AND AIR CORE, I AND E LAYERS ALTERNATEIN STACKING WHEN BUILDING THE CORE. MAKES AN AIR GAP WHICH HELPS KEEP THE INDUCTANCE MORE CONSTANT FOR DIFFERENCE CURRENTS.

http://www.youtube.com/watch?v=B8fTLXs50lUDisassembling laminated transformer core

TYPES OF TRANSFORMERSCLASSIFIED BY USE: POWER TRANSFORMERS, @ 60Hz, FROM 115 TO 1000’S VOLTS. USED FOR POWER DISTRIBUTION AND LIGHTING.

CONTROL TRANSFORMERS :USED BY SMALLER RECTIFIERS AND CONTROL CIRCUITS USING RELAYS SOLENOIDS.

AUDIO TRANSFORMERS. WORK AT FREQUENCIES UP TO 20KHz.

RF TRANSFORMERS f (RADIO RANGES) CAN BE Fe OR AIR CORE.

CONSTANT VOLTAGE TRANSFORMERS:PROVIDE STABLE SECONDARY VOLTAGE, DESPITE VARING PRIMARY VOLTAGE.

ISOLATION TRANSFORMERHAVE EQUAL PRIMARY AND SECONDARY VOLTAGE, USED TO ISOLATE ELECTRICAL EQUIPMENT FROM THE POWER DISTRIBUTION SYSTEM.

VARIOUS ISOLATION TRANSFORMERS

MORE ISOLATION TRANSFORMERS

AUTO TRANSFORMER: PRIMARY WINDING IS PART OF THE SECONDARY WINDING AND VICE-VERSA.

1,000 MVA, 1050/525kV single-phase autotransformer

VARIABLE TRANSFORMER: WORK AT POWER FREQUENCIES. THESE ARE AUDIOTRANSFORMERS WITH AN ADJUSTABLE SECONDARY.

IMPEDANCE MATCHING (IM) P.317THIRD MOST COMMON USE FOR TRANSFORMERS IS IMWHY? WHEN IM OF SOURCE IS MATCHED TO IM OF THE LOAD. MAX. POWER TRANSFER OCCURS.

A TRANSFORMER CAN MAKE A LOAD APPEAR TO THE SOURCE LARGER OR SMALLER THEN IT ACTUAL IS.

REFLECTED IMPEDANCE (Z) FROM THE SECONDARY APPEARS TO THE PRIMARY AS BEING EQUAL.

TRANSFORMER RATINGSVOLTAGE RATING ARE SPECIFIED FOR PRIMARY AND SECONDARY WINDINGS UNDER LOAD AND NO LOAD CONDITIONS.

POWER RATINGS:GIVEN IN WATTS GOING TO A RESISTIVE LOAD

Full Load Current Ratings of Self-CooledThree-Phase Transformers208 -7200V

Line to Line Voltage

kVA 208 240 480 600 2400 4160 7,200

30 83.3 72.2 36.1 28.9 7.22 4.16 2.41

45 125 108 54.1 43.3 10.8 6.25 3.61

75 208 180 90.2 72.2 18.0 10.4 6.01

112.5 312 271 135 108 27.1 15.6 9.02

150 416 361 180 144 36.1 20.8 12.0

225 625 541 271 217 54.1 31.2 18.0

300 833 722 361 289 72.2 41.6 24.1

500 1,388 1,203 601 481 120 69.4 40.1

750 2,082 1,804 902 722 180 104 60.1

1,000 2,776 2,406 1,203 962 241 139 80.2

1,500 4,164 3,608 1,804 1,443 361 208 120

2,000 ..... 4,811 2,406 1,925 481 278 160

2,500 ..... ..... 3,007 2,406 601 347 200

3,000 ..... ...... 3,609 2,887 722 416 241

3,750 ..... ..... 4,511 3,608 902 520 301

5,000 ..... ...... ..... 4,811 1,203 694 401

7,500 ..... ..... ...... ..... 1,804 1,041 601

10,000 ..... ...... ..... ..... 2,406 1,388 802

SERIES AND PARALLEL WINDINGS P.230SOME TRANFORMERS CAN BE BUILT WITH MULTIPLE PRIMARY AND SECONDARYWINDINGS WHICH CAN BE CONNECTED IN SERIES OR PARALLEL.

3 PHASE TRANSFORMERS

500 KVA 3 PHASE TRANSFORMERS

3 PHASE TRANSFORMER UNDER CONSTRUNTION

ULTIMATE USE FOR TRANSFORMERS: A SUPERCONDUCTING FUSION REACTOR

MAGNETIC CONFINMENT CONTAINTER FOR A PLASMA FUSION REACTOR

DRAWING SHOWING HOW MAGNETIC FIELDS COMPRESS 1 MILLION DEGREE PLASMA

INTERIOR OF A FUSION REACTOR

top related