iec61850 primer

Post on 16-Aug-2015

107 Views

Category:

Engineering

13 Downloads

Preview:

Click to see full reader

TRANSCRIPT

GE Multilin Proprietary and ConfidentialUnrestricted Use for GE Multilin Sales Channel

IEC 61850 Primer - Communication Networks

and Systems In Substations

February 16, 2005

GE Multilin Proprietary and ConfidentialUnrestricted Use for GE Multilin Sales Channel

2

February 16, 2005

61850 Scope

GE Multilin Proprietary and ConfidentialUnrestricted Use for GE Multilin Sales Channel

3

February 16, 2005

Abstract Communications Service Interface ACSI

•Defines a set of Objects

•Defines a set of Services to manipulate and access those objects

•Defines a base set of data types for describing objects

GE Multilin Proprietary and ConfidentialUnrestricted Use for GE Multilin Sales Channel

4

February 16, 2005

Anatomy of an IEC61850 Object Name

Physical Device(network address)

Logical Device(e.g. Relay1)

MMXU1 MMXU2

MXMX

AV

Logical Nodes

Functional Constraint

“MMXU2$MX$A” =Feeder #2 Current Measurements

GE Multilin Proprietary and ConfidentialUnrestricted Use for GE Multilin Sales Channel

5

February 16, 2005

Logical node groupsL System LN (2)

P Protection (28)

R Protection related (10)

C Control (5)

G Generic (3)

I Interfacing and archiving (4)

A Automatic control (4)

M Metering and measurement (8)

S Sensor and monitoring (4)

X Switchgear (2)

T Instrument transformers (2)

Y Power transformers (4)

Z Further power system equipment (15)

Examples:

PDIF: Differential protection

RBRF: Breaker failure

XCBR: Circuit breaker

CSWI: Switch controller

MMXU: Measurement unit

YPTR: Power transformer

GE Multilin Proprietary and ConfidentialUnrestricted Use for GE Multilin Sales Channel

6

February 16, 2005

Services Examples

• GetData – Read

• SetDataValues – Write

• GetDataDirectory – Read list of object names

GE Multilin Proprietary and ConfidentialUnrestricted Use for GE Multilin Sales Channel

7

February 16, 2005

ACSI Services

EnableSelf

DescribingDevices

GE Multilin Proprietary and ConfidentialUnrestricted Use for GE Multilin Sales Channel

8

February 16, 2005

IEC61850 Profiles

GE Multilin Proprietary and ConfidentialUnrestricted Use for GE Multilin Sales Channel

9

February 16, 2005

IEC61850 DocumentsBasic principles Part 1

Glossary Part 2

General Requirements Part 3

System and project management Part 4

Communication requirements Part 5

Substation Automation System Configuration Part 6

Basic Communication Structure Part 7

Part 9Sampled Measured Values

Part 8

Conformance testing Part 10

Mapping to Ethernet

Mapping to MMS and Ethernet

GE Multilin Proprietary and ConfidentialUnrestricted Use for GE Multilin Sales Channel

10

February 16, 2005

IEC61850 – Primary Parts

Part 6-1: Substation Configuration Language (SCL)

Part 7-2: Abstract Communications Service Interface (ACSI) and base types

Part 7-3: Common Data Classes (CDC)

Part 7-4: Logical Nodes

Part 8-1: Specific Communications Service Mappings (SCSM) - MMS & Ethernet

Part 9-2: SCSM - Sampled Values over Ethernet

Part 10-1: Conformance Testing

GE Multilin Proprietary and ConfidentialUnrestricted Use for GE Multilin Sales Channel

11

February 16, 2005

IEC61850 Substation Architecture

MU = Merging Unit

MU

PT1 OpticalCT

MU

PT2 CT2

MU

OpticalPT

OpticalCT

Relay Relay Relay

MU Publishes V/I/Status Datasets

Relay(s) Subscribe to Datasets

I/O I/O I/O

Station Bus - 10/100/1000 MB Ethernet

Process Bus

.1/1/10GB

Ethernet

Clk1 Clk2

RemoteAccess

Network

MU = Merging Unit

MU

PT1 OpticalCT

MU

PT2 CT2

MU

OpticalPT

OpticalCT

IED IED IED

MU Publishes V/I/Status Datasets

Relay(s) Subscribe to Datasets

I/O I/O I/O

- 10/100/1000 MB Ethernet

.1/1/10GB

Ethernet

Clk1 Clk2

RemoteAccess

Network

GE Multilin Proprietary and ConfidentialUnrestricted Use for GE Multilin Sales Channel

12

February 16, 2005

Sampled Measured Values

GE Multilin Proprietary and ConfidentialUnrestricted Use for GE Multilin Sales Channel

13

February 16, 2005

. . .

Peer to Peer Communications

Functional Requirements

Bkr 1

Relay

TripBkr 2

Relay

Bkr N

Relay

Bkr 3

Relay

BFI

• Message delivery to multiple devices simultaneously

• Fast Delivery (< 4ms)

GE Multilin Proprietary and ConfidentialUnrestricted Use for GE Multilin Sales Channel

14

February 16, 2005

IEC61850 Generic Object Oriented Substation Event - GOOSE• Device to multi-device communication – Local or Wide Area

•Bridgeable but Non-routable

•User-defined Dataset sent in an Ethernet Multicast message

•Message sent on change of state as well periodically to enable detection of device failure

• Reliability effected through message repeat

GOOSE Header:• Multicast Address

•Name

•Time Until Next GOOSE

•Etc.

User-Defined Dataset• Status Information

•Analog Values

•Data Quality

•Time

GE Multilin Proprietary and ConfidentialUnrestricted Use for GE Multilin Sales Channel

15

February 16, 2005

SCL – Substation Configuration Language

• Description language for communication in electrical substations related to the IEDs

• XML based language that allows a formal description of

– Substation automation system and the switchyard and the relation between them

– IED configuration

GE Multilin Proprietary and ConfidentialUnrestricted Use for GE Multilin Sales Channel

16

February 16, 2005

SCL File Types

SSD: System Specification Description. XML description of the entire system.

SCD: Substation Configuration Description. XML description of a single

substation.

ICD: IED Capability Description. XML description of items supported by an IED.

CID: Configured IED Description. XML configuration for a specific IED.

GE Multilin Proprietary and ConfidentialUnrestricted Use for GE Multilin Sales Channel

17

February 16, 2005

Benefits of IEC61850• High-level services enable self-describing

devices & automatic object discovery saving $$$$$ in configuration, setup and maintenance.

• Standardized naming conventions with power system context eliminates device dependencies and tag mapping saving $$$$ in config., setup, and maint.

• Standardized configuration file formats enables exchange of device configuration saving $$$$ in design, specification, config., setup, and maint.

GE Multilin Proprietary and ConfidentialUnrestricted Use for GE Multilin Sales Channel

18

February 16, 2005

Benefits of IEC61850 - 2

• Higher performance multi-cast messaging for inter-relay communications enables functions not possible with hard wires and save $$$$ in wiring and maintenance.

• Multi-cast messaging enables sharing of transducer (CT/PT) signals saving $$$$ by reducing wiring and connection costs