Model 2003 Installation and Operation Manual
2
Par
t No.
512
473
Dra
win
g N
o. 1
29-0
212a
03/
09
Subject to modifications without notice
Pepperl+Fuchs Groupwww.pepperl-fuchs.com
USA: +1 330 486 0002pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com
Singapore: +65 6779 9091pa-info@sg.pepperl-fuchs.com
Copyright Pepperl+Fuchs
Germany: +49 621 776 2222
Table of Contents
Page 2 System Purpose and Description Purpose,Systemdescription,Importantnotes
Page 3 Identifying Your System Definesspecificfeaturesofthesystem
Page 3 General Information System&materialspecifications,Spareparts,Tools
&testequipment,Systemaccessories
Page 4 Enclosure and Device Design Designrequirements,Adjacentenclosures,Device
ventilation,Temperaturelimitations
Page 5 Installation Overview Installationdiagram
Page 6 Getting Started Establishingconnectionsizes,Determiningenclosure
inlet&outletconnectionlocations
Page 7 System Mounting LH,RH,TM,BM&WMconfigurations,
FM&PMconfigurations
Page 8 Hardware Mounting Enclosureprotectionvent,Warningnameplates
Page 9 Mounting Plate Dimensions Mountingplatedimensiondiagrams
Page 10 Pneumatic Tubing Requirements Protectivegassupplyrequirements,Pneumatic
connectionrequirements
Page 12 Tubing Connection Points LH,RH,TM,BM,WM,FM,&PMconfigurations
Page 13 Tubing Installation LH,RH,TM,BM,WM,FM&PMTubing
configurations
Page 14 Electrical Supply Requirements Generalwiringrequirements,EPCUpower&alarm
signal,Enclosurewiringmethods&connections
Page 15 Electrical Power Control Unit Generallayout&conduitconnectionpoints
Page 16 EPCU Power Rating Powerratingnameplate,Assembledelectronics
Page 17 Electrical & Pneumatic Diagrams LH,RH,TM,BM,WM,FM,&PMconfigurations
Page 18 Conduit Installation EPCUelectricalconduit,Optionalintrinsicsafety
BarrierconduitandEPCUconduitconnectionparts
Page 19 Power Modules & Wiring Diagram EPCU120/220VAC&24-48VDCpowermodules
Page 20 Logic Module & Barrier Wiring OptionalISBwiringrequirements&diagram,EPCU
powercontrolmodes
Page 21 Barriers & Field Adjustments ISBdescription&factoryprogramming,LEDdisplay
indicators,Timerfunctions&settings
Page 22 Set-Up Procedure RapidExchangepurgingset-up
Page 23 Set-Up Procedure (cont.) RapidExchangepurgingset-up
Page 24 Operating Sequence ClassIpurgingoperation
Page 25 Troubleshooting Procedures
Page 26 Warranty and Liability Statements Warrantynotes,Generalterms,Limitations
Page 27 Customer Notes
Page 30 System Maintenance
Page 31 Systems Identification & Application Information
Purpose and Description
PurposePepperl+Fuchs'BebcoEPSSystemallowstheuseofgeneral-purposeornonratedelectricalorelectronicdevices,withexceptiontodevicesthatproduceexcessiveheat,utilizecombustiblegas,orexposearcingcontactstothehazardousatmosphere,inNEMA(NationalElectricalManufacturersAssociation)4or12enclosuresintheplaceofexplosionproofNEMA7enclosures.Otherpurposesincludeheat,moistureanddustcontaminationprevention.
DescriptionModel2003RapidExchange®purgingsystemoperatesonasupplyofcompressedinstrumentairorinertgas.Itregulatesandmonitorspressureofsealed(protected)enclosure(s),inordertorapidlyremoveandpreventflammablevaporaccumulationwithintheenclosure(s).Thesystemisdesignedtoaccomplishfourairexchangesandmaintaina"safe"(0.25")pressureononeormoreenclosuresnotexceedingatotalvolumeoffifteencubicfeet.AnEPV-3enclosureprotectionventisrequiredforproperoperation.Inaddition,thesystemincludesanelectricalpowercontrolunit(EPCU)thatmonitorssystemoperationandcontrolsenclosurepower.Allstart-uprequirementsmustbesatisfiedbeforetheEPCUwillenergizepowertotheenclosure(s).Thisprocessreducesthehazardous(classified)arearatingwithintheenclosure(s),inaccordancewiththeNEC-NFPA70,Article500,NFPA496andISA12.4.
Important NotesOne(1)permanentfilecopyandone(1)operationscopyofthismanualmustbestudiedandretainedbytheoperatorofthissystem.User’sagentsareresponsiblefortransferringthismanualtotheuser,priortostart-up.
Thecontentsofthismanualhavebeenarrangedtoallowtheuseofthisproductasastand-alonedeviceonequipmentandenclosuressuppliedbytheuseroritsagents.Themanual’sparametersencompassacombinationofbothNationalFireProtectionAssociation(NFPA)requirementsandPepperl+Fuchs,Inc.requirements.Pepperl+FuchsthereforeacknowledgestheuseofNFPA496asaguideline,thatwehaveenhancedcertainNFPArequirementsandthatadditionalinformationhasbeencompiledtocompletethisdocument.Themanualisintendedasacompleteguideandmustbeconsidered,unlessspecificallystatedotherwise,thatalldirectivescontainedhereinarerequirementsforsafe,practicalandefficientuseofthisproduct.
Thissystemisnotintendedforusetoprotectenclosuresordevicesthatcontainignitableconcentrationsofgasesorvapors.Thisexclusiongenerallyappliestoprocessorproductanalyzingsystemsequipment.
All specifications are subject to change without notice.
Model 2003 Installation and Operation Manual
3
Par
t No.
512
473
Dra
win
g N
o. 1
29-0
212a
03/
09
Subject to modifications without notice
Pepperl+Fuchs Groupwww.pepperl-fuchs.com
USA: +1 330 486 0002pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com
Singapore: +65 6779 9091pa-info@sg.pepperl-fuchs.com
Copyright Pepperl+Fuchs
Germany: +49 621 776 2222
Identifying Your System
Thisenclosureprotectionsystemisofferedinvariousstyles.Forproperinstallationandoperation,examinethesystemmodelnumbernameplatetoidentifythesystemstyle,areaclassification,andtype,asnotedbelow.
NOTE: Only FM certified Group B system available in STD style
General Information
System SpecificationsSystemdimensions: SeePages9&10Shippingweight(lbs.): STD-45/SA&FA-47Operatingtemp.range: -20°F-120°FSupplypressurerange: 80-120psimax.
Whenusingtheoptionalinlinefilter,max.supplypressureis80psiCapacity&filtration: 3.8oz.@40micronsSupplyrequirements: CleanairorinertgasSafepressuresetpoint: 0.25"@safepress.Safepressureflowrate: *0.1-3.5SCFHExchangepressure: 3"-5"Exchangeflowrate: **10SCFM/600SCFHExchangetime: 1minute/2.5cubicft.Systemsupplyport: 3/8"FPTEnclosuresupplyfitting: 3/8"tubefittingEnclosurereferencefitting: 1/4"tubefittingEPCUConduitportsize: 1/2"FPTEPCUpowerfequirements: 120VAC60Hz1Ø(European220voltageonly) 240VAC50Hz1ØEPCUpowerconsumption: 500mA
Powerrelaycontacts: 20Amps@240VAC 20Amps@28VDCAlarmrelayN.O.contact: 20Amps@240VAC 20Amps@28VDCAlarmrelayN.C.contact: 15Amps@240VAC 10Amps@28VDC
* Enclosureintegritydeterminesactualflowrate**Withregulatorsetto60psimin.duringexchange
Material SpecificationsFilterregulatorbody: Zincw/enamelfinishRegulatorhandle&bowl: PolycarbonateEnclosurepressuregauge: Alum.w/enamelfinishRapidexchangegauge: Polycase&brasstubeRapidexchangesolenoid: Brassw/enamelfinishTubefittings&valves: 316SSforgedbodyTubing: 316SS1/4".035weldedSystemnameplates: SilkscreenedLexan®&SSFastenerhardware: SSscrews&boltsMountingplate: 31614ga#3brushSSEPCUenclosurebody: Beadblastcastalum.Conduit&fittings(SA&FA): GalvanizedsteelEnclosurewarningnameplate: SilkscreenedSS
Lexan®isaregisteredtrademarkoftheGeneralElectricCorporation
Recommended Spare PartsQty Description Part#(supercedes)1 Enclosurepressureindicator 510023(001000)1 3/8"filterregulator 510064(002090)1 Enclosurepressurecontrolvalve 510131(003660)1 RapidExchange®valvebody(STDstyle) 510133(003680)1 3/8"solenoidvalvebody(SA&FAstyle) 510076(002230)1 Safepressureswitch 510356(005200)1 RapidExchange®pressureswitch 510358(005210)1 Series2000logicmodule-Ver.2.0 510279(005000)1 Series2000VACpowermodule 510304(005020)1 Series2000VDCpowermodule 510305(005021)1 Installation&operationmanual 129-02121 Enclosurewarningnameplate-CI 513008(EWN-1)
Referencepartnumberaboveforcurrentsparepartspricing.Immediatepricingisavailabletoallconfirmedcustomers.
Installation Tools & Testing Equipment1/2"chuckdrill
Completesetofdrillbits
1/2"&1"conduitknockoutpunchor1.375"holesaw
Completesetoftubing,conduitbending,instrumentfittingandelectricalcraftsmanhandtools
0-5"differentialpressuregaugeormanometer(connectedtotheprotectedenclosuretomeasuremaximumpressure)
2003 - STD - CI - NR - LH - ##
Series Model NumberSystem Style STD - Standard SA - Semiautomatic FA - Fully AutomaticArea Classification CI - Class I, Group C & D Area IB - Class I, Group B Area (STD Only)Power Control Mode NR - Normal Running CB - Conditional BypassMounting Configuration LH - left hand left side of enclosure RH - right hand right side of enclosure TM - top mount top of enclosure BM - bottom mount bottom of enclosure WM - wall mount wall surface FM* - frame mount external frame or rack PM* - panel mount enclosure surface cutout * FM & PM configurations feature flush mount EPCU. Flush mount EPCU is not suitable for Group B Area. ## - Additional factory installed accessories
Confidential according to ISO 16016
sheet
respons.
approved
norm 1 of 1
scale: 1:1
Label for Model 2003-[STD or SA or FA]-CI Type X
date: 2005-Dec-15Only valid as long as released in EDM or with a valid production documentation!
Twinsburg
2003 STD X UL ID NP SS2003 SA X UL ID NP SS2003 FA X UL ID NP SS
125-0842Bchange notice.
Dieses Dokument enthält sicherheitsrelevante Angaben. Es darf nicht ohne Absprache mit dem Normenfachmann geändert werden!
This document contains safety-relevant information. It must not be altered without the authorization of the norm expert!
TECHNICAL INFORMATION:
POLYCARB 0.01”MUST BE UL/CSA APPROVED
BLACK COPY ON WHITE BACKGROUNDFULL INFORMATION PERTAINING TO PRINT FONTS,DIMENSIONS AND COLOR SCHEMES ARE CONTAINED INTHIS COREL DRAW (.CDR) FILENAME UNDER DRAWINGNUMBER 125-0842B
LABEL MATERIAL:
ADHESIVE:
COLOR:
NOTE:
US.JMB
US.SSJ
US.AAS150-0691
2.50
1.50
SCALE = 1XAll dimensions are in inches.All outside corners R=0.13
Tolerances: 2-place dec. +/- .01
APPROVED BY FM APPROVALS AS ASSOCIATED TYPE X PRESSURIZATION CONTROL
EQUIPMENT FOR USE IN HAZARDOUS LOCATIONS. REDUCES THE INTERNAL AREA
OF A CONNECTED ENCLOSURE IN ACCORDANCE WITH DRAWING NUMBER MCL 2003.
APPROVED BY FM APPROVALS AS ASSOCIATED TYPE X PRESSURIZATION CONTROL
EQUIPMENT FOR USE IN HAZARDOUS LOCATIONS. REDUCES THE INTERNAL AREA
OF A CONNECTED ENCLOSURE IN ACCORDANCE WITH DRAWING NUMBER MCL 2003.
APPROVED BY FM APPROVALS AS ASSOCIATED TYPE X PRESSURIZATION CONTROL
EQUIPMENT FOR USE IN HAZARDOUS LOCATIONS. REDUCES THE INTERNAL AREA
OF A CONNECTED ENCLOSURE IN ACCORDANCE WITH DRAWING NUMBER MCL 2003.
75 CUBIC FEET MAXIMUM ENCLOSURE VOLUME
CLASS I, DIVISION 1, GROUPS C & D TO NONHAZARDOUS
75 CUBIC FEET MAXIMUM ENCLOSURE VOLUME
CLASS I, DIVISION 1, GROUPS C & D TO NONHAZARDOUS
75 CUBIC FEET MAXIMUM ENCLOSURE VOLUME
CLASS I, DIVISION 1, GROUPS C & D TO NONHAZARDOUS
PURGE CONTROL FOR USE IN HAZARDOUS LOCATIONS. CLASSIFIED BY UNDERWRITERS
LABORATORIES INC. ® IN ACCORDANCE WITH THE NATIONAL FIRE PROTECTION ASSOCIATION
STANDARD FOR PURGED AND PRESSURIZED ENCLOSURES FOR ELECTRICAL EQUIPMENT
PURGE CONTROL FOR USE IN HAZARDOUS LOCATIONS. CLASSIFIED BY UNDERWRITERS
LABORATORIES INC. ® IN ACCORDANCE WITH THE NATIONAL FIRE PROTECTION ASSOCIATION
STANDARD FOR PURGED AND PRESSURIZED ENCLOSURES FOR ELECTRICAL EQUIPMENT
PURGE CONTROL FOR USE IN HAZARDOUS LOCATIONS. CLASSIFIED BY UNDERWRITERS
LABORATORIES INC. ® IN ACCORDANCE WITH THE NATIONAL FIRE PROTECTION ASSOCIATION
STANDARD FOR PURGED AND PRESSURIZED ENCLOSURES FOR ELECTRICAL EQUIPMENT
NFPA 496-1996
4S11
NFPA 496-1996
4S11
NFPA 496-1996
4S11
T3C T3C
T3C
Model 2003-STD-CI Type X Model 2003-SA-CI Type X
Model 2003-FA-CI Type X
C
LASSIFIED
®
C
LASSIFIED
®
C
LASSIFIED®
LABEL P/N: 510965 LABEL P/N: 510967
LABEL P/N: 510969
Released EDM checkout 2008-JUL-17
Model 2003 Installation and Operation Manual
4
Par
t No.
512
473
Dra
win
g N
o. 1
29-0
212a
03/
09
Subject to modifications without notice
Pepperl+Fuchs Groupwww.pepperl-fuchs.com
USA: +1 330 486 0002pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com
Singapore: +65 6779 9091pa-info@sg.pepperl-fuchs.com
Copyright Pepperl+Fuchs
Germany: +49 621 776 2222
Model 2003 System AccessoriesEnclosure Protection Vents (one required with each system)EPV-3-SA-00 Straightw/sparkarrestorEPV-3-SA-90 Rtanglew/sparkarrestor
Additional ItemsSMK-2,-3or-10 SystemmountingkitRAH Div.1remotealarmhornRAB-1 Div.1remotealarmbeaconLCK LfittingconduitkitTCK TfittingconduitkitSRM-4000 SwitchresistormoduleNJ... P+FNAMURsensorNC-6 3/8"ninetyconnectorSC-6 3/8"straightconnectorEFC-4 1/4"flushconnectorEFC-6 3/8"flushconnectorEBC-6 3/8"bulkheadconnectorEPC-13 1"pipeconnector
Factory Installed ItemsIS1 ChannelAbarrierIS2* ChannelBbarrierIS3* ChannelCbarrierRP1 RedundantsafepressureswitchRP2 RedundantRapidExchangepressureswitchL Keylockassembly
*Requirescustomprogramminginformation
Enclosure & Device Design
Enclosure Design Requirements1. Allwindowsmustbeshatterproofandsizedassmallas
possible.
2. AllNFPA496requiredmarkingsmustbeplacedonornearallenclosuredoorsandcovers.
3. Theenclosuremustwithstandaninternalpressureoffive(5)inchesofwaterwithoutsustainingpermanentdeformationandresistallcorrosiveelementsinthesurroundingatmosphere.
4. Alllightweightobjectsintheenclosure,suchaspaperorinsulation,mustbefirmlysecured.
5. TheenclosureshouldbeconstructedfrommaterialssuchasmetalornonstaticpolycarbonatetomeetorexceedNEMA4or12performancerequirements,butdoesnotrequirethirdpartyapproval.
6. Theinstallationofobstructionsorotherbarriersthatblockorimpedetheflowofprotectivegasmustbeavoided.
7. Thecreationofairpocketsorotherareasthattrapflammablegaseswithintheenclosureordevicesmustbeavoided.
8. Theenclosureshouldbelocatedinanareawhereimpacthazardsareminimal.
9. Iftheenclosureisnonmetallicandcontainsequipmentthatutilizesorswitchespowerloadsgreaterthan2500VA,itmustbeconstructedfromsubstantiallynoncombustiblematerials,suchasmaterialsdesignedtomeetorexceedANSI/UL94ratingsof94V-0or945V.
Adjacent Enclosures1. Adjacentenclosuresmustbeprotectedbyoneofthe
followingmeans:
a) purgedorpressurizedinserieswiththeprotectedenclosure
b) purgedorpressurizedseparatelyor
c) protectedbyothermeans;e.g.,explosionproofenclosures,hermeticallysealeddevicesorintrinsicsafecircuits
2. Adjacentpurgedorpressurizedenclosuresmustbedesignedtomeetallconstructionrequirementsabove.
Total Volume Calculation1. Thetotalvolumeofallpressurizedenclosures,devicesand
wirewaysmustbeconsidered.
2. Allenclosure,device,andwirewayvolumesmustbecalculatedwithoutconsiderationofinternallyconsumedspace.
Device Ventilation1. Encloseddeviceswithintheprotectedenclosurethatdonot
exceed1.22in3offreevolumedonotrequireventilationtotheprotectedenclosure.
2. Ifthefreevolumeofaninternaldeviceexceeds1.22in3itmustbeprotectedbyoneofthefollowingmeans:
a) ventilatedonthetopandbottomsideswith1in2ofopeningforeach400in3ofvolumewithintheinternalprotectedenclosure,ataminimumdiameterof1/4"
b) purgedinserieswiththeprotectedenclosureorbepurgedseparatelyor
c) protectedbyothermeans;e.g.,explosionproofenclosures,hermeticallysealeddevices,orintrinsicsafecircuits.
Temperature Limitations1. Theenclosuremusthavenosurfaceareathatexceeds80
percentoftheflammableorignitablesubstance’sauto-ignitiontemperature.
2. Internaldevicesthatexceedthistemperaturemustbeprotectedbyoneofthefollowingmanners:
a) ThedeviceisenclosedinachamberthatisCULUSorFMlistedasahermeticallysealeddevicethatprohibitstheentranceofaflammableorignitablesubstance,andmaintainsasurfacetemperaturebelowtemperaturelimits.
b) Itcanbeprovenbytestingthatthedeviceswillnotignitethesubstanceinvolved.
c) ThedeviceispurgedinaseparateenclosurethatbearsanETW(enclosuretemperaturewarningnameplate).Devicesmaybeaccessedonlyafterpowerhasbeenremovedandthedevicehasbeenallowedtocooltosafetemperature,ortheareaispositivelyknowntobenonhazardous.
Model 2003 Installation and Operation Manual
5
Par
t No.
512
473
Dra
win
g N
o. 1
29-0
212a
03/
09
Subject to modifications without notice
Pepperl+Fuchs Groupwww.pepperl-fuchs.com
USA: +1 330 486 0002pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com
Singapore: +65 6779 9091pa-info@sg.pepperl-fuchs.com
Copyright Pepperl+Fuchs
Germany: +49 621 776 2222
Model 2003-STD-CI-LH Shown
Installation Overview
ENCLOSURE PROTECTION
VENT(required)
PROTECTED ENCLOSURE
ENCLOSURE SUPPLY TUBING
ENCLOSURE REFERENCE
TUBING
ENCLOSURE CONNECTION
FITTINGS
ENCLOSURE WARNING
NAMEPLATE
ENCLOSURE PROTECTION
SYSTEM
SYSTEM SUPPLY TUBING
EPCU BREATHER DRAIN FITTING
EPCU POWER & ALARM SIGNAL WIRING CONDUIT & SEAL
PROTECTIVE GAS SUPPLY
SERVICE VALVE
Model 2003 Installation and Operation Manual
6
Par
t No.
512
473
Dra
win
g N
o. 1
29-0
212a
03/
09
Subject to modifications without notice
Pepperl+Fuchs Groupwww.pepperl-fuchs.com
USA: +1 330 486 0002pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com
Singapore: +65 6779 9091pa-info@sg.pepperl-fuchs.com
Copyright Pepperl+Fuchs
Germany: +49 621 776 2222
Getting Started
Typical Single Protected Enclosure Connections
HELPFUL HINTSIfflammablegasesarelighterthanair,theinletconnectiontoeachenclosuremustenternearabottomcorner.Theoutletconnection,foranoptionalenclosureprotectionventorpipingtoanadjacentprotectedenclosure,mustexitnearanextremeoppositetopcorner.Seediagramstotheleft.
Ifflammablegasesareheavierthanair,inletandoutletconnectionsmustbereversed.
Inallcases,themostprevalentgasmustdeterminethelocationofinletandoutletconnections.
Determining Enclosure Inlet & Outlet Connection Locations
HELPFUL HINTSToensureadequateprotectivegasflowtoprotectedenclosure(s),allpipingandtubingmustbefullyreamed.
Precautionsmustbetakentopreventcrimpingandotherdamagetoprotectivegaspipingandtubing.
Whenprotectingmultipleenclosureswithasingleenclosureprotectionsystem,theenclosuresmustbeconnectedinseriesfromthesmallesttothelargesttoensureadequateprotectivegasflow.
INLET
INLET
Connectionsforheavierthanairgasesandvapors
OUTLET
OUTLET
Connectionsforlighterthanairgasesandvapors
PROTECTED ENCLOSURE
C
B
ENCLOSURE PROTECTION VENT(Required)
E
SUPPLY
REFERENCE
1/2" PROTECTIVE GAS SUPPLY
HEADER
ENCLOSURE PROTECTION
SYSTEM
Maximum tubing / pipe length and maximum number of bends / elbows
3/8"O.D.tubingfullyreamed
20feet10bends
3/8"O.D.tubingfullyreamed
Description
*Tubing or pipe diameter
Enclosure supply
System supply tubing
Enclosure reference
1/4"O.D.tubingfullyreamed
5feet5bends
20feet10bends
Multi - enclosure connections
1"I.D.pipefullyreamed
10feet5elbows
Optional remote venting
1"I.D.pipefullyreamed
30feet5elbows
A B EDC
ENCLOSURE PROTECTION
SYSTEM
PROTECTED ENCLOSURE
PROTECTED ENCLOSURE
D
SUPPLY
REFERENCE
B
TYPICAL MULTIPLE PROTECTED ENCLOSURE CONNECTIONS
1/2" PROTECTIVE GAS SUPPLY
HEADER
A
A
D
C
PROTECTED ENCLOSURE
*NOTE:Tubeandpipesizesaretradesizesandarenotequalininsidediameter.DONOTsubstitutetubeforpipewithsametradesize.
Model 2003 Installation and Operation Manual
7
Par
t No.
512
473
Dra
win
g N
o. 1
29-0
212a
03/
09
Subject to modifications without notice
Pepperl+Fuchs Groupwww.pepperl-fuchs.com
USA: +1 330 486 0002pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com
Singapore: +65 6779 9091pa-info@sg.pepperl-fuchs.com
Copyright Pepperl+Fuchs
Germany: +49 621 776 2222
System Mounting
IMPORTANT NOTESThe system should be mounted at EYE LEVEL.
Care must be taken to ensure the system and all protruding components are clear of all enclosure accesses (doors and covers) and conduit, pipe, tubing or cable entries.
LH, RH, TM, BM and WM configurations are intended for mounting adjacent to the protected enclosure.
LH, RH, TM & BM configurations are also suitable for 2" schedule 40 pipe mounting.
Determine the mounting configuration of your system using the diagrams on pages 9 & 10.
Remove and save the manila envelope (containing the enclosure warning nameplate) which may be taped to the outer surface of the mounting flange.
Although all systems are factory tested and calibrated, we strongly suggest a bench test of basic functions prior to installation.
Mounting LH, RH, TM, BM & WM Configurations1.Transferholepatternofsystemmountingplatetointended
surface.
2. Checkforobstructionshinderingboltfastening,drillandreamthemountingholesbeforemountingthesystem.
3. Securethesystemtotheenclosure,orothermountingsurface,usingone(1)SMK-3orequivalent-six(6)3/8"x3/4"stainlesssteelbolts,nutsandlockwashers.
*WMrequiresone(1)SMK-2orequivalent-four(4)3/8"x3/4"stainlesssteelbolts,nutsandlockwashers.
Mounting FM & PM Configurations
1. Transferpanelcutoutpatterntotheintendedsurface.
2. Checkforobstructionsthatcouldprohibitboltfasteningorsystempneumaticandelectricalconnections.
3. Cutpanelcutoutpatternontheintendedsurface.
4. Deburrallcutoutsurfaces.
5. SecuresystemtoenclosureusingSMK-10,orequivalent-ten(10)1/4"x3/4"stainlesssteelnuts,bolts,mountingclipsandlockwashers.
HELPFUL HINTSFMandPMconfigurationsaredesignedtomountthroughapanelcutoutone(1)inchsmallerthantheoverallheightandwidthofthesystemmountingplate,usingclipsandfastenersprovidedwithSMK-10.Thisdesignfeatureeliminatestheneedtodrillthesystemmountingboltholesintheprotectedenclosure.
FMconfigurationsareintendedformountingadjacenttotheprotectedenclosure.
PMconfigurationsareintendedformountingthroughacutoutintheprotectedenclosuresurface.
Typical Surface Mounted System(Model 1002-LPS-LH Type Z shown)
Typical Pipe Mounted System(Model 1002-LPS-LH Type Z shown)
Typical Panel/Frame Mounted System(Model 1002-LPS-PM Type Z shown)
Model 2003 Installation and Operation Manual
8
Par
t No.
512
473
Dra
win
g N
o. 1
29-0
212a
03/
09
Subject to modifications without notice
Pepperl+Fuchs Groupwww.pepperl-fuchs.com
USA: +1 330 486 0002pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com
Singapore: +65 6779 9091pa-info@sg.pepperl-fuchs.com
Copyright Pepperl+Fuchs
Germany: +49 621 776 2222
Hardware Mounting
Required Enclosure Protection VentAllconfigurationsmustbemountedinatrueverticalposition.
Theventmustbelocatedtoprovideaccessforroutinetestingofthevent’sflapperassembly.Aminimum8"clearanceisrequiredbelowtheventopening.
1. Determinethevent’smountingconfiguration,i.e.,-00verticalmountor-90sidemount.Seephotosbelow.
2.Determineventlocationandlayoutventmountingholeontheprotectedenclosure(asdeterminedonpage6,“GettingStarted”).
3. Usinga1.375"holesawor1"conduitpunch,drillanddeburrtheenclosureprotectionventmountinghole.
4. Removethehubmountingnutfromtheventhubandplacethehub,withO-ringintact,throughthemountinghole.TheO-ringmustbeontheoutsideoftheprotectedenclosure.
5. Reinstallthehubmountingnuttothemountinghubfrominsidetheprotectedenclosureandtighten.
Warning Nameplate(s)AnEWN(EnclosureWarningNameplate)mustbelocatedinaprominentpositiononornearallenclosureaccesses(doorsandcovers).
One(1)EWNisprovidedwitheachsystem,locatedinthemanilaenvelopetapedtothemountingflangeofthesystem.AdditionalEWNsareavailablefromPepperl+Fuchs.
AllEWNsprovidelabeledspacesallowingthecustomertomarktheprotectedenclosurewith:1)aTCode(temperatureidentificationnumber),2)Class,GroupandDivisionofsurroundingarea,and3)NFPApressurizationTypeX,YorZ,asmayberequiredbyplantandlocalcodesandisrequiredbyNFPA496.
AnETW(EnclosureTemperatureWarningnameplate)mustbelocatedinaprominentpositiononornearallenclosureaccesses(doorsandcovers)whenthetemperatureofaninternalcomponentexceeds80percentoftheignitiontemperatureoftheflammablevapor,gasordustinvolved.
AnETWwarnstheoperatortodeenergizeallequipmentforaspecifiedlengthoftime,allowingtheprotectedequipmenttocoolbeforeopeningtheprotectedenclosure.Thelengthoftimerequiredisdeterminedbythecustomerandcanbefactoryorfieldengraved.
AllEWNsandETWsarefurnishedwithanadhesiveback,butshouldalsoberivetedorscrewedtotheprotectedenclosure.
Enclosure temperature warning nameplate
Enclosure warning nameplate - Class II
Enclosure warning nameplate - Class IEPV - 3 - SA - 00Vertical Mount
EPV - 3 - SA - 90Side Mount
Model 2003 Installation and Operation Manual
9
Par
t No.
512
473
Dra
win
g N
o. 1
29-0
212a
03/
09
Subject to modifications without notice
Pepperl+Fuchs Groupwww.pepperl-fuchs.com
USA: +1 330 486 0002pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com
Singapore: +65 6779 9091pa-info@sg.pepperl-fuchs.com
Copyright Pepperl+Fuchs
Germany: +49 621 776 2222
23"
11.5"
SA & FAStyles Only
SA & FAStyles Only
4.25"
21"
10.75"
.6875"
3.5625"
11.25"
.375" O.D.TYP. 6
15.25"
23"
12"
SA & FAStyles Only
4.25"
20.5"
10.75"
11.5"
.68
75
"
.375" O.D.TYP. 6
3.5
62
5"
15.25"
23"
11.5"
SA & FAStyles Only
SA & FAStyles Only
4.25"
22.32"
10.75"
.6875"
3.5625"
11.25"
.375" O.D.TYP. 6
15.25"
2003-RH(Right hand configuration)
2003-LH(Left hand configuration)
2003-TM(Top mount configuration)
Mounting Plate Dimensions
IMPORTANT NOTEDimensions DO NOT include systems ordered with an area classification of IB (Class I, Division 1, Group B). Consult factory for mounting plate dimensions.
Model 2003 Installation and Operation Manual
10
Par
t No.
512
473
Dra
win
g N
o. 1
29-0
212a
03/
09
Subject to modifications without notice
Pepperl+Fuchs Groupwww.pepperl-fuchs.com
USA: +1 330 486 0002pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com
Singapore: +65 6779 9091pa-info@sg.pepperl-fuchs.com
Copyright Pepperl+Fuchs
Germany: +49 621 776 2222
2003-FM & 2003-PM(Frame & panel mount configuration)
23"
12"
SA & FAStyles Only
4.25"
22.3125"
10.75"
11.5".68
75
".375" O.D.
TYP. 63
.56
25
"
15.25"
2003-BM(Bottom mount configuration)
2003-WM(Wall mount configuration)
9.5"
2" 1"
.375" O.D.TYP. 4
TYPICAL -WMMOUNTING FLANGE
23"
11.5"
Add 4" to bothdimensions forSA & FA Styles
21"
6"
12.5"
12.5"Panel Cutout
Panel Cutout24"
.25" O.D.TYP. 10
25"
13.5"
1.25"
SA & FA Style
11"
14.5"
Mounting Plate Dimensions (continued)
IMPORTANT NOTEDimensions DO NOT include systems ordered with an area classification of IB (Class I, Division 1, Group B). Consult factory for mounting plate dimensions.
Model 2003 Installation and Operation Manual
11
Par
t No.
512
473
Dra
win
g N
o. 1
29-0
212a
03/
09
Subject to modifications without notice
Pepperl+Fuchs Groupwww.pepperl-fuchs.com
USA: +1 330 486 0002pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com
Singapore: +65 6779 9091pa-info@sg.pepperl-fuchs.com
Copyright Pepperl+Fuchs
Germany: +49 621 776 2222
Pneumatic Tubing Requirements
Protective Gas Supply RequirementsTheprotectivegassupplytotheprotectionsystemmustbeaclean,instrumentqualitycompressedairornitrogenandmustcontainnomorethantraceamountsofflammablegas,vaporordust.
Theprotectivegassupplycompressorintakemustoriginateinanonhazardouslocation.Suctionductpassingthroughahazardouslocationandtheprotectionsystemtubingandpipingmustbefabricatedfromnoncombustiblematerialssuitableforprevailinghazardsandenvironmentalconditions.
Theprotectivegassupplymustoriginatefromadedicatedinstrumentqualitycompressedairheader(1/2"pipeorlarger),nofartherthantwenty(20)feetfromtheprotectionsystem.LocalcompressorsandgascylindersshouldnotbeusedbeforeconsultingwithPepperl+Fuchs.
Theprotectivegassupplytotheprotectionsystemmustberegulatedfrom120psimaximumto80psiminimum.
Pneumatic Connection RequirementsALLFITTINGSMAYBECUSTOMERORFACTORYFURNISHED
1. Forsystemsupply,one(1)SC-63/8"malestraightconnectororone(1)NC-63/8"maleelbowconnectororequivalentfittingpersystem.
One(1)similarfittingwhichwillconnecttheinertgassupplytubingtotheinertgassupplyheaderconnectionpointandone(1)lotof3/8"O.D.,.035"wallthickness,weldedorseamlessstainlesssteeltubing.
2. Forenclosuresupply,one(1)EFC-63/8"flushconnector,orone(1)EBC-63/8"feed-throughconnectororequivalentfittingpersystem.
3.Forenclosurereference,one(1)EFC-41/4"flushconnector,orone(1)EBC-41/4"feed-throughconnectororequivalentfittingpersystem.
4.One(1)lotof1/4"O.D.,.035"wallthickness,weldedorseamlessstainlesssteeltubing.
5.Formultipleenclosureconnections,two(2)EPC-131"pipemountinghubsorequivalentand1"150#ratedpipecouplings&unionsperinterconnection.
One(1)lot150#rating1"galvanizedoraluminumpipeandfittings,fullyreamedandunrestricted.
PM Pneumatic Connection RequirementsInadditiontoitemnumbers1,4and5above,thefollowingfittingsarerequiredforallPMconfigurations.
1. ForsystemsupplyonPMconfigurations,one(1)additionalEBC-6orequivalent3/8"throughbulkheadfittingpersystemisrequired.
2. Foratmosphericreference,one(1)PRB-4orequivalent1/4"femalebulkheadfittingandstainlesssteelsinteredelementisrequired.
SC-6 NC-6
EBC-4 & EBC-6EFC-4 & EFC-6
EPC-13
ENCLOSURE SUPPLY & REFERENCE FITTINGS
SYSTEM SUPPLY FITTINGS
MULTIPLE ENCLOSURE CONNECTION FITTING
PRB-4
SYSTEM ATMOSPHERIC REFERENCE FITTING
Model 2003 Installation and Operation Manual
12
Par
t No.
512
473
Dra
win
g N
o. 1
29-0
212a
03/
09
Subject to modifications without notice
Pepperl+Fuchs Groupwww.pepperl-fuchs.com
USA: +1 330 486 0002pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com
Singapore: +65 6779 9091pa-info@sg.pepperl-fuchs.com
Copyright Pepperl+Fuchs
Germany: +49 621 776 2222
Tubing Connection Points
LH, RH, TM, BM, WM & FM Configuration Connection Points
PM Configuration Connection Points
HELPFUL HINTPneumaticconnectionsarebolded.
RapidExchange
controlvalve
Filterregulator
System supply inlet
Enclosure supply outlet
Mountingplate
Venturiorifice
Enclosurepressuregauge
Enclosure reference
inlet
Enclosurepressurecontrolvalve
EPCUpressurereference
tubing
Flamearrestorfitting
RapidExchange
controlvalve
Filterregulator
System supply inlet
Enclosure supply outlet
RESVconduit
Mountingplate
Venturiorifice
(notvisible)
Enclosurepressuregauge
Enclosure reference
inlet
Enclosurepressurecontrolvalve
EPCUpressurereference
tubing
Flamearrestorfitting
STD Style SA & FA Style(with Rapid Exchange
Solenoid Valve)
Enclosurepressuregauge
Atmospheric reference
inlet
Enclosurepressure
controlvalve
EPCUatmospheric
referencetubing
Flamearrestorfittings
RapidExchange
controlvalve
Filterregulator
System supply inlet
Enclosure supply outlet
RESVconduit
Mountingplate
Model 2003 Installation and Operation Manual
13
Par
t No.
512
473
Dra
win
g N
o. 1
29-0
212a
03/
09
Subject to modifications without notice
Pepperl+Fuchs Groupwww.pepperl-fuchs.com
USA: +1 330 486 0002pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com
Singapore: +65 6779 9091pa-info@sg.pepperl-fuchs.com
Copyright Pepperl+Fuchs
Germany: +49 621 776 2222
Tubing Installation
Tubing LH, RH, TM, BM, WM & FM ConfigurationsSystem supplyconnections
1. Selectorinstallaprotectivegassupplyheadertap,fittedwiththepropertubesizefittingandlocatedwithintwenty(20)feetoftheenclosureprotectionsystem.
2. Ifaservicevalveisplacedbetweentheprotectivegassupplyheaderandtheenclosureprotectionsystem,itmustbeinstalledincloseproximityoftheprotectedenclosureandbelabeledinaccordancewithNFPA496.
3. Selecttheappropriatefittingsrequiredtoconnecttheprotectivegassupplytotheprotectionsystemregulatorasdeterminedonpage11,“PneumaticTubingRequirements”.
4. Determineappropriatetubingroutefromtheprotectivegassupplyheadertotheprotectionsystemregulator.
5. Bendtubingusingindustrialgradebenders,checktubingfittoensureproperseatingbetweenthetubingandfittings.Fullyreamalltubingends.
6. Installtubingandtightenallfittingstofittingmanufacturer’sspecifications.Securetubingtoappropriatestructuralsupportsasrequired.
Enclosure supply & reference connections
1.Chooselocationfortheenclosuresupplyconnection(s)basedontherequirementsonpage6,“GettingStarted.”
2. Placetheenclosurereferenceconnectionfittingdirectlybehindtheenclosureprotectionsystemwheneverpossible.Forsystemsprotectingmultipleenclosuresinseries,theenclosurereferenceconnectionfittingmustbeplacedonthelastenclosureintheseries.Seepage6,“GettingStarted.”
3. Drillanddeburrenclosuresupplyandreferencefittingholesontheprotectedenclosure.Mountthefittings.
4. Determineappropriateroutefortheenclosuresupplyandreferencetubing.
5. Bendtubingusingindustrialgradebenders,checktubingfittoensureproperseatingbetweenthetubingandfittings.Fullyreamalltubingends.
6. Installtubingandtightenallfittingstofittingmanufacturer’sspecifications.Securetubingtoappropriatestructuralsupportsasrequired.
Tubing PM ConfigurationsEnclosure bulkhead fittings
1. Selectthefittingsrequiredtoinstallthesystemsupply,systemsupplybulkheadFittingandatmosphericreferencebulkheadfitting.Seepage11,“PneumaticTubingRequirements.”
2.Chooselocationforthesystemsupplybulkheadfitting.Thisfittingallowstheprotectivegassupplytopassthroughthewallofaprotectedenclosuretotheprotectionsystem’sregulatorsupplyinletconnection.
3. Chooselocationfortheatmosphericreferencebulkheadfitting.Thisfittingallowstheenclosurepressuregaugetoreferenceatmosphericpressure.
4. Drillanddeburrsystemsupplyandreferencebulkheadfittingholesintheprotectedenclosure.Mountthefittings.
System supply & reference connections
1. Selectorinstallaprotectivegassupplyheadertap,fittedwiththepropertubesizefittingandlocatedwithintwenty(20)feetoftheenclosureprotectionsystem.
2. Ifaservicevalveisplacedbetweentheprotectivegassupplyheaderandtheprotectionsystem,itmustbeincloseproximityoftheprotectedenclosureandlabeledinaccordancewithNFPA496.
3. Determineappropriatetubingroutefromtheprotectivegassupplyheadertothesystemsupplybulkheadfitting.
4. Determineappropriatetubingroutefromthesystemsupplybulkheadfittingtotheprotectionsystemregulator.
5. Determineappropriatetubingroutefromtheatmosphericreferencebulkheadfittingtotheenclosurepressuregauge’sreferenceinletconnection.
6. Bendtubingusingindustrialgradebenders,checktubingfittoensureproperseatingbetweenthetubingandfittings.Fullyreamalltubingends.
7. Installtubingandtightenallfittingstofittingmanufacturer’sspecifications.Securetubingasrequired.
HELPFUL HINTSAllworkmustbeperformedbytechniciansqualifiedinpneumatictubingandelectricalconduitinstallation.
Pepperl+Fuchsrecommendstheuseof.035"wallthickness,weldedorseamlessstainlesssteeltubing.
Ifflexibletubingisused,itmustbeinstalledinamannerthatprotectsitfromdamageandcorrosion.
Model 2003 Installation and Operation Manual
14
Par
t No.
512
473
Dra
win
g N
o. 1
29-0
212a
03/
09
Subject to modifications without notice
Pepperl+Fuchs Groupwww.pepperl-fuchs.com
USA: +1 330 486 0002pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com
Singapore: +65 6779 9091pa-info@sg.pepperl-fuchs.com
Copyright Pepperl+Fuchs
Germany: +49 621 776 2222
Electrical Supply Requirements
General Wiring RequirementsWARNING!This device contains electrical parts that can cause shock or injury.
Allelectricalconnections,conduitandfittingsontheprotectedenclosuremustbesuitableforthehazardouslocationinwhichtheyareinstalled.Inaddition,allconduitandwiremustbeinstalledinaccordancewithNECasrequiredandallrelevantplantandlocalcodes.
Conduitsealsmustbeutilizedonallelectricalconduitconnectionsandpouredwithanapprovedcompoundpriortooperationoftheprotectionsystem.
Exception:Donotusesealsonconduitusedasaprotected“wireway”tosupplyprotectivegastoadjacentprotectedenclosures.Thesameconduitcanbeutilizedforbothelectricalandpneumaticservicetoanadjacentprotectedenclosure(s),providedtheconduitisoversizedtoallowaminimumfreeclearanceequaltoorlargerthanthepipesizerequiredbetweenmultipleenclosuresasstatedonpage6,“GettingStarted.”
EPCU Power RequirementsTheelectricalpowercontrolunit's(EPCU)electricalpowersourcemustoriginatefromacircuitbreakerorfuseddisconnectsuitableforthehazardouslocationinwhichitisinstalled.Thepowersourceshouldbeuninterruptedandtheswitchmustbelocatedwithinfifty(50)feetoftheprotectedenclosure(s)andtheenclosureprotectionsystemandbeproperlymarked.ForEPCUpowerspecificationsseepage3,"System'sSpecifications."
Alarm Signal RequirementsPepperl+FuchsstronglyrecommendsuseoftheoptionalalarmsystemcontactsoftheEPCU,connectedtoanalarmsystemlocatedinaconstantlyattendedlocationtoindicatethefailureoftheenclosureprotectionsystem.ForEPCUalarmsignalspecificationsseepage3,"System'sSpecifications."
Typical Enclosure Wiring MethodsProtectedenclosuresmustbewiredsimilartoexplosionproofenclosures,inaccordancewithArticle500oftheNationalElectricCode-NFPA70.
Singleconductorwiringmustbeplacedinrigidmetalconduit,seal-flexconduit,orothermediumsapprovedforuseinthehazardouslocationsurroundingtheprotectedenclosure.Additionally,NFPA496requiresapprovedconduitsealsonallpressurizedenclosureconduitwiringentries,inaccordancewithNFPA70.Furthermore,theuseofanapprovedconduitsealissimplythemostpracticalwaytopreventexcessiveleakagethroughconduitconnections.
However,whileexplosion-proofenclosuresrequireconduitsealsonallcableentries,inaccordancewithNFPA70,othermethodsofsealedcableentriesthataresuitableforhazardouslocationscanbeused,suchascompressionglands.
Inconclusion,therearetwoprimarygoals.First,theinstallershouldensurethatallassociatedwiringandcableisprotectedbypressurizationorothermeans,suchasexplosion-proofconduitorintrinsicsafetybarriers.Secondly,theinstallermustensurethatallassociatedconduitandwirewaysaresealedtoconserveprotectivegas,unlesstheyareusedtosupplyprotectivegastootherenclosuresordevices.
Typical Enclosure Wiring Connections
Explosionproofdevice
Seal
Intrinsicallysafeorfiberopticdevice
Adjacentpressurized
device
Independentlypressurized
device
Intrinsicallysafeorfiberopticdevice
Seal
Conduit
Conduit
Conduit
Glandfitting
Cable
Seal
Pressurizedraceway
Protectedenclosureordevice
HELPFUL HINTPepperl+Fuchsrecognizesitmaybeimpracticaltopourallelectricalconduitsealspriortoinstallationinthefield.However,allconduitconnectionsmustbesealedforpropertestingandoperationoftheenclosureprotectionsystem.Therefore,Pepperl+Fuchsrecommendstheuseoftemporarysealssuchasductsealormaskingtapeforbenchorshoptesting,priortofinalfieldinstallation.
Model 2003 Installation and Operation Manual
15
Par
t No.
512
473
Dra
win
g N
o. 1
29-0
212a
03/
09
Subject to modifications without notice
Pepperl+Fuchs Groupwww.pepperl-fuchs.com
USA: +1 330 486 0002pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com
Singapore: +65 6779 9091pa-info@sg.pepperl-fuchs.com
Copyright Pepperl+Fuchs
Germany: +49 621 776 2222
Electrical Power Control Unit
IMPORTANT NOTESFor proper moisture drainage of the Type 7 enclosure, the installer must 1) move the Type 7 breather drain to one of the bottom conduit entrances or 2) use drain seals on all conduit connected to the bottom two conduit entrances.
The Type 7 breather drain is not provided or required with PM configurations.
Top two conduit entrances will be dedicated for Intrinsic Safe wiring ONLY when the EPCU is supplied with Pepperl+Fuchs' optional ISB intrinsic safety barriers.
General Layout & Electrical Conduit Connections
EPCU LED Displays
Powermodeselectorswitch
Type7explosionproof
screwcover
Type7explosionproof
enclosure
Powermodeselectorswitch
(optionalmountinghole-factoryuseonly-)
1/2"NPTnonduitnonnectionports
typical6(seeimportantnotes
below)
LEDdisplay
Type7explosionproofbreatherdrain(seeimportantnotesbelow)
EPCUelectricalratingnameplate
AlarmOnly Alarm&Bypass
Model 2003 Installation and Operation Manual
16
Par
t No.
512
473
Dra
win
g N
o. 1
29-0
212a
03/
09
Subject to modifications without notice
Pepperl+Fuchs Groupwww.pepperl-fuchs.com
USA: +1 330 486 0002pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com
Singapore: +65 6779 9091pa-info@sg.pepperl-fuchs.com
Copyright Pepperl+Fuchs
Germany: +49 621 776 2222
EPCU Power Rating
EPCU Electrical Power Rating Nameplate
Assembled EPCU Electronics Module
TheEPCU(ElectricalPowerControlUnit)ofthisType"X"purging/pressurizationsystemisofferedinvariousstyles.Forproperinstallationandoperation,beginbyexaminingtheEPCUelectricalratingnameplatetoidentifythesysteminputvoltageandpowerrequirements,enclosurepowerandalarmcontactratingsandthirdpartyapprovalmarkings.Next,matchtheLEDdisplayofyourEPCUwithoneofthedisplaysshownonpage15.TheEPCULEDDisplaywillhelpidentifytheoptionsfeaturedonyoursysteme.g.,normalrunningmodeorconditionalbypassClassIpurging(timer)orClassIIpressurization(notimer).
MODEL 2000 ELECTRICAL POWER CONTROL UNITCAUTION: OPEN CIRCUIT BEFORE REMOVING COVER
ATTENTION: OUVRIR LE CIRCUIT AVANT D'ENLEVER LE COUVERCLE
SERIAL NO. INPUT VOLTAGE & POWER REQUIREMENTS
CSA Encl. 3CLASS I, DIV. 1, Gr C&DCLASS II, DIV. 1, Gr E, F, G HASUL & FM APPROVALS ONLY
ENCL POWER & ALARM CONTACTS ARE RATED 120/240 VAC, 20 AMPS
120 SINGLE PHASE, 60 CYCLE, 1 AMP240 SINGLE PHASE, 50 CYCLE, 1 AMP
XXXXXX
EPCU INPUT POWER REQUIREMENTS
Factorysetattimeoforder
AREA CLASSIFICATION
DefinestheareaclassificationsforwhichtheEPCUissuitablefor
operation
REQUIRED WARNING STATEMENTS
EPCU SERIALNUMBER
Logic module
120/240 VAC Power module
Power module cable
Pressure switch module
Model 2003 Installation and Operation Manual
17
Par
t No.
512
473
Dra
win
g N
o. 1
29-0
212a
03/
09
Subject to modifications without notice
Pepperl+Fuchs Groupwww.pepperl-fuchs.com
USA: +1 330 486 0002pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com
Singapore: +65 6779 9091pa-info@sg.pepperl-fuchs.com
Copyright Pepperl+Fuchs
Germany: +49 621 776 2222
Electrical & Pneumatic Diagrams
LH, RH, TM, BM, WM & FM Configurations
PM Configurations
Requiredenclosureprotectionvent
Electricalpowercontrolunit
Enclosurepressuregauge
Systemsupply
Breatherdrain
Enclosuresupplytubing
Sinteredvent
Enclosurereference
tubing Enclosurereferencebulkheadfitting
Electricalpowersupplyconduit
hubConduitsealUnionConduitseal Union
Venturiorifice
Systemsupplytubing
RegulatorProtectedenclosure
Enclosuresupplybulkheadfitting
RapidExchange
pressuregauge*RapidExchange
controlvalve
Enclosurepressurecontrolvalve
Systemsupplyconnectionfitting
*SolenoidonSA&FAstyles
Systemsupply
Atmosphericpressurereferencebulkheadfitting
Systemsupplybulkheadfitting
Inlet
Conduitseal Union Conduitseal
Requiredenclosureprotectionvent
Electricalpowersupplyconduit
hub
Electricalpowercontrolunit
Atmosphericreference
tubing
Electricalpowerconduit
Enclosurepressuregauge
UnionElectricalpowertoenclosure
EnclosurePressurerefer-
ence
EnclosurePressurerefer-
ence
Protectedenclosure
Enclosuresupply
discharge
Systemsupplytubing
Regulator
RapidExchange
pressuregauge*RapidExchange
controlvalve
EnclosurepressurecontrolvalveSystemsupply
connectionfitting*Solenoidon
SA&FASstyles
Model 2003 Installation and Operation Manual
18
Par
t No.
512
473
Dra
win
g N
o. 1
29-0
212a
03/
09
Subject to modifications without notice
Pepperl+Fuchs Groupwww.pepperl-fuchs.com
USA: +1 330 486 0002pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com
Singapore: +65 6779 9091pa-info@sg.pepperl-fuchs.com
Copyright Pepperl+Fuchs
Germany: +49 621 776 2222
Conduit Installation
EPCU Electrical ConduitUnplugthefourunlabeledconduitentranceslocatedonthesidesandbottomoftheEPCUenclosure(Seepage15,"EPCULayout"forconduitentrancelayout).
TheinstallermustmounttheType7drainfittingsuppliedwiththesystem(exceptforPMconfigurations)inoneofthebottomconduitentrancesoftheEPCU,orutilizedrainsealsonallconduitconnectedtothebottomtwo(2)conduitentrancesoftheEPCU.
Followingtheinstructionslistedbelow,installallconduit,fittingsandseals(ordrainsealsifutilized)betweentheEPCU,alarmsystem(ifutilized)andtheprotectedenclosure(s).PlugallremainingEPCUconduitentrances.
1.Choosethelocationfortheenclosure’selectricalconduitconnection(s)basedontherequirementsonpage14,“ElectricalSupplyRequirements.”
2. Drillanddeburrenclosureconduitfittingholesintheprotectedenclosure.Mountthefittings.
3. Determineappropriateroutefortheenclosureelectricalenclosureandalarmsignalconduit.
4. Measure,cutandthreadconduit,checkconduitfittoinsureproperseating.Fullyreamallconduit.
5. Installconduitandtightenallfittingstofittingmanufacturersspecifications.Secureconduittoappropriatestructuralsupportsasrequired.
6. Sealallconduitwithanapprovedcompoundpriortooperationoftheprotectionsystem.
Optional Intrinsic Safety Barrier ConduitSystemssuppliedwithoptionalIntrinsicSafetyBarriers(ISB)willbesuppliedwithclearlylabeledisolatedconduitentries,asolidbodywirewaywithsnapcoverandplexiglasswiringpartitions.TheseaccessoriesprovideafullyisolatedwiringpathtothebarrierwiringterminallocatedonthelowerleftcorneroftheEPCULogicModule.AllISwiringmustbeisolated.
1.Choosethelocationfortheenclosure’sISconduitconnection(s)basedontherequirementsonpage14,“ElectricalSupplyRequirements.”
2. Drillanddeburrenclosureconduitfittingholesintheprotectedenclosure.Mountthefittings.
3. DetermineappropriateroutefortheISconduit.
4. Measure,cutandthreadconduit,checkconduitfittoensureproperseating.Fullyreamallconduit.
5. Installconduitandtightenallfittingstofittingmanufacturersspecifications.Secureconduittoappropriatestructuralsupportsasrequired.
6. Sealallconduitwithanapprovedcompoundpriortooperationoftheprotectionsystem.
EPCU Conduit Connection PartsFittingKitsCanBeFactoryFurnished
1. ToconnectenclosurepowerfromtheEPCUtotheprotectedenclosure,one(1)LCK(Lfittingconduitkit)orequivalentconduitelbow,couplingandsealfittings.
2. ForEPCUtoenclosurewiringconnectionwithone(1)additionalconduitconnectionpath,one(1)TCK(Tfittingconduitkit)orequivalentconduittee,couplingandsealfittings.
IMPORTANT NOTE: Model LCK & TCK are offered primarily to OEMs attempting to achieve a "field ready" installation. In all cases, limited pipe fitting skills will be required. Pre-cut 150# galvanized steel pipe nipples can be acquired from local plumbing shops, but a hole saw or punch and wrenches are required to install kits.
LCK “L” FittingConduit Kit
TCK “T” FittingConduit Kit
Model 2003 Installation and Operation Manual
19
Par
t No.
512
473
Dra
win
g N
o. 1
29-0
212a
03/
09
Subject to modifications without notice
Pepperl+Fuchs Groupwww.pepperl-fuchs.com
USA: +1 330 486 0002pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com
Singapore: +65 6779 9091pa-info@sg.pepperl-fuchs.com
Copyright Pepperl+Fuchs
Germany: +49 621 776 2222
Power Modules & Wiring Diagram
EPCU 120/240 VAC Power Module Layout
VAC & VDC Power Module Electrical Wiring Diagram
Isolatedcoilvoltagetransformer
Powercontrolswitchcableheader
Pressureswitchcableheader
Logicmodulecableheader
Redundantsafepressurerelay
Alarmrelay
Enclosurepowerrelays
Powermodulewiringterminal
Voltageinputselectorseader(factorysetfor
120VACpower)
1Ampinputfuse
RapidExchange
solenoidvalve(RESV)relay
RESVfactorywiringterminal
20Ampenclosurepowerfuse
EPCU 120/240 VAC power module
1 2 3 4 5 6 7 8 9 10
20AMPFUSES
Isolatedenclosure
powerrelays
Isolatedalarmrelay
NeuNeu
HotHot
NO Com NC
Remote alarmrelay terminals
OutInIn Out
Enclosure power supply
terminals
Field wired power module
terminalsNO NO NO NC
GndGnd
EPCU powersupply terminals
120VAC*240VAC(optionalvoltage)
*Europeansinglephase240VAConly.
Powerandalarmterminalsarefeed-thrudryswitchcontacts.
CautionshouldbeexercisedtoensurethattheEPCUwiringisproperlyconnected.
AllterminalconnectionstotheEPCUshouldbewiredwithspadeorroundlugs.
Using12gaugemaximumto16gaugeminimumwireonly,checkEPCUpowerrequirements(seepage14)andwiretotheEPCUpowersourceandalarmsystem(ifutilized).Thenroutepowersource(s)throughtheEPCUpowerinandoutterminalstoallnon-rateddeviceswithintheprotectedenclosure(s).
Model 2003 Installation and Operation Manual
20
Par
t No.
512
473
Dra
win
g N
o. 1
29-0
212a
03/
09
Subject to modifications without notice
Pepperl+Fuchs Groupwww.pepperl-fuchs.com
USA: +1 330 486 0002pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com
Singapore: +65 6779 9091pa-info@sg.pepperl-fuchs.com
Copyright Pepperl+Fuchs
Germany: +49 621 776 2222
Logic Module & Barrier Wiring
EPCU Logic Module & Pressure Switch Module
Optional ISB Wiring Requirements
Alloptionalintrinsicsafety(IS)wiringmustbeisolatedfromallotherelectricalwiringusingthededicatedISconduitentrancesandwirewayoftheEPCU.See"OptionalISBConduitInstallation"onpage18formoredetails.Inaddition,allwiringmustbeinstalledinaccordancewiththeNECandallrelevantlocalandplantcodes.
TheintrinsicsafetybarriersaredesignedtofunctioninconjunctionwithacustomerfurnishedswitchandSRM-4000switchresistormodule,oranNJ...NAMURsensor.Thecustomersuppliedswitchmusthavedrycontactswhichcontainnoinductanceorcapacitance.
TheSRM-4000switchresistormoduleandtheNJ...NAMURsensoraresuppliedwithapproximatelyten(10)feetofwiring.Using16to18gaugeshieldedwire,thecablelengthscanbeextendedtoamaximumof100feet.
Inallapplications,themoduleoftheswitchresistormodulecablemustbeinstalledasclosetothecustomersuppliedswitchaspossibleforproperoperation.
Wiringlugsarenotrecommendedforintrinsicsafetybarrierwiringconnections.
Seepage21forbarrieroperationandfactoryprograming.
EPCU Power Control Modes
Normal Running (NR) Mode
EPCUfeaturesanon-offpushbuttonpowercontrolswitchtoactivatecontrolfunctions.Switchmustbedepressedtoinitiatestart-up.Aftercompletionofstart-up,safepressuremustbelostorswitchmustbedepressedtodeenergizeenclosurepowerrelays.
Conditional Bypass (CB) Mode
EPCUfeaturesanon-off-bypasspowercontrolswitchtoactivatecontrolfunctions.Switchmustbesetto"on"positiontoinitiatestart-up.Afterenclosurepowerisenergized,safepressuremustbelostorswitchmustbesetto"off"positiontodeenergizeenclosurepower.Afterenclosurepowerisenergized,switchmaybesetto"bypass"position,totemporarilylatchenclosurepowerrelays.AflashingLEDthenindicatesbypassengaged,andtheenclosurecanthenbeaccessedwithoutdeenergizingpower(performedunderspecificconditions).Followingaccess,safepressuremustbereestablishedtoresumenormaloperation.Atthattime,theswitchmayberesettotheonposition,withoutdisruptionofenclosurepower.Alarmrelaynormallydeenergizesonlyuponlossofsafepressure,butcanbefactoryprogrammedtodeenergizewhenbypassisengaged,ifspecifiedattimeoforder.
A B C
INTRINSICALLY SAFE AUXILIARY INPUTS
- + - + - +
( - ) BLUE ( + ) BROWN
BarrierCsocket
BarrierB(installed)
BarrierAsocket
Barrierwiring
terminal
Pressureswitchcalibrationaccess
Barrierfault&activestatusindicators
Factoryprograming
header
Redundantcontroller
(GAL)
Powermodulecableheader
EDT,SLT&RETtimers
EPCU Logic Module
Primarysafepressureswitch
LEDstatusdisplay
EPCU Pressure Switch Module
Primarymicroprocessor
Spaceforoptionalredundantsafepressure
switch
SpaceforoptionalredundantRapidExchangeswitch
RapidExchange
switch
Model 2003 Installation and Operation Manual
21
Par
t No.
512
473
Dra
win
g N
o. 1
29-0
212a
03/
09
Subject to modifications without notice
Pepperl+Fuchs Groupwww.pepperl-fuchs.com
USA: +1 330 486 0002pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com
Singapore: +65 6779 9091pa-info@sg.pepperl-fuchs.com
Copyright Pepperl+Fuchs
Germany: +49 621 776 2222
Barriers & Field Adjustments
Optional Intrinsic Safety Barriers DescriptionTheEPCULogicModulecanaccommodateuptothreeintrinsicsafetybarriers,tointeractwithremotedevicesandaffectoperationoftheEPCU.Thebarriersareinstalledandprogrammedbythefactoryattimeoforder,andtheyaredesignedtofunctioneitherinconjunctionwithacustomerfurnishedswitchandaPepperl+Fuchsfurnishedresistornetworkcable,oraPepperl+Fuchsfurnishedproximitydetector.Eachbarrierdevelopsalowpowersignal,tocreateatwowireclosedloopcircuit.OperationalstatusofeachbarrierisindicatedbyagreenLEDtoshowactive(closedswitch)status,andbyaredLEDtoshowfaulted(linebreakage)cablestatus.Allbarrierscanbereprogrammedtoduplicateotherbarrierfunctionsasrequired,uponspecificrequest.
Optional ISB Factory Programing
Barrier A Function - when switch opens Disablesstart-upcycleDeenergizesenclosurepowerandalarmrelayFunctionsparalleltosafepressureswitch
Barrier B Function - when switch opens Notprogrammedforthismodel-customapplicationsonly
Barrier C Function - when switch closesEnergizesRESVrelay-customapplicationsonly
LED Display IndicatorsPower off: EnclosurepowerrelaysdeenergizedPower on: EnclosurepowerrelaysenergizedSafe pressure: Enclosurepressure>0.15"or0.50"w.c.Rapid Exchange: Enclosurepressure>2.0"w.c.Timer running: ExchangetimeractiveAlarm active: Enclosurepressure<0.15"w.c.Bypass engaged: Controlbypassactive-CBmode
Field Adjustable Timer FunctionsEDT(ExchangeDelayTimer)(FAstyleonly)providesatimedelaytopreventRapidExchangesolenoidvalvefromenergizinguntilsafepressurecanbestabilized.
SLT(SolenoidLatchingTimer)(FAstyleonly)providesatimedelaytokeeptheRapidExchangesolenoidvalveenergizeduntilRapidExchangepressureisdetected.Ifthepressureisnotdetected,theEPCUwillreset.
RET(RapidExchangeTimer)providesatimedelayafterRapidExchangepressureisdetected,toallowfourvolumeexchanges(tenvolumesformotors)priortoenergizingtheenclosurepowerrelays.InClassIareasonly,ifRapidExchangepressureislostorinterruptedduringtimedelaycycle,theEPCUwillreset.
EDT, SLT & RET Timer Settings
POSITION TIME IN SECONDS POSITION TIME IN MINUTES
0 5 0 5 1 10 1 10 2 15 2 15 3 20 3 20 4 25 4 25 5 30 5 30 6 35 6 35 7 40 7 40 8 45 8 45 9 50 9 50 A 55 A 55 B 60 B 60 C 65 C 65 D 70 D 70 E 75 E 75 F 80 F 80
NOTE:PowermustberemovedfromtheEPCUviathelocaldisconnectswitchforapproximately10secondsfortimeradjustmentstoreset.
0 12
3
4
5
6789
A
B
C
D
EF
Rotaryswitchbody
EDT & SLT Timer RET Timer
Model 2003 Installation and Operation Manual
22
Par
t No.
512
473
Dra
win
g N
o. 1
29-0
212a
03/
09
Subject to modifications without notice
Pepperl+Fuchs Groupwww.pepperl-fuchs.com
USA: +1 330 486 0002pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com
Singapore: +65 6779 9091pa-info@sg.pepperl-fuchs.com
Copyright Pepperl+Fuchs
Germany: +49 621 776 2222
Set-up Procedure
Model 2003 Rapid Exchange Purging Set-up1.Closetheenclosurepressurecontrolregulator(allstyles)
andRapidExchangecontrolvalve(STDStyleonly)fullybyturningclockwise(CW).
2.ConnecttheinertgassupplytothesystemsupplyInletandsettheRapidExchangepressuregaugeto60psi.
3. Temporarilyconnecta0-5inchwatercolumnpressuregaugeormanometertotheprotectedenclosure.
4.Checkoperationofenclosureprotectionventasdetailedabove.See"ImportantNotes."
5.Sealenclosure(s)andadjustenclosurepressurecontrolvalvebyopeningslowlycounterclockwise(CCW)toseta“safe”pressureontheenclosurepressuregauge.
Note:Ifpressuresettingisdifficulttostabilizeorset,seepage25,“TroubleshootingProcedures.”
IMPORTANT NOTESRegardless of any condition, the Type X Rapid Exchange system is designed to automatically withhold power to the protected enclosure while inducing Rapid Exchange, for at least five (5) minutes. Normal exchange times should be doubled if large obstructions block inert gas flow.
To test the vent’s operation, gently prod the vent flapper open with a soft pointed object, ( example: eraser end of a pencil) ensuring that the vent valve works freely. On vertically configured vents, this can be accomplished from within the protected enclosure. Side mounted -90 configured vents can be tested by removing the pipe plug at the bottom of the mounting tee. Multiple operations require only one test per day if enclosure is not opened or left unattended.
The volume exchange rate is based on a four (4) enclosure volume exchange. Multiply the required exchange time by 2.5 for applications requiring a ten (10) volume exchange (motors).
The start-up instructionnameplate exchange time slot will feature the standard factor for this system "ONE MINUTE PER 2.5 CUBIC FEET", but the unit may feature a set of direct factor nameplates with self-adhesive backing such as “TEN MINUTES,” for application to the start-up instructions, dependent on how the system was specified and purchased. Field modification of this nameplate, to show a direct factor, is acceptable as noted above if the method used to mark the nameplate does not deface the instructions listed. Materials used for the marking must be indelible and withstand prevailing environmental conditions.
6.STD Styles-OpenRapidExchangecontrolvalvefullybyturning90°CCWandquicklyensuretheenclosureprotectionventopens.
SA & FA Styles-Withtheaidofanassistanthavingtwo1/2"combinationwrenchesonhand,placelefthandonsystemmountingplateandpullRapidExchangemanualoperatorfirmlywithrighthandandquicklyensuretheenclosureprotectionventtopens.Ifenclosureprotectionventoperatesproperly,haveassistantcarefullyplacetheopenendofbothwrenchesbehindhandletoholdthemanualoperatorintheoutpositiontemporarily.
Note:Theenclosurepressuregaugeshouldmovequicklyoffscaletotheright,thisisnormalforallRapidExchangepurgingsystems.
7. Readjusttheregulatorto60psiminimum,whileinducingRapidExchange,thetestgaugeshouldthenreadapproximately2inchesofpressureandshouldnotfluctuate.(insufficientenclosurepressurewillcausetheenclosureprotectionventto"shuttle")DONOTexceed5inchesofpressurewithintheprotectedenclosure.
8.CloseenclosurepressurecontrolvalveandRapidExchangecontrolvalve(STDStyles)orremovethetwo1/2"combinationwrenchesfrombehindthehandle.
Note:TheRapidExchangepressuregaugemaynowindicateahighersetpressurethanwasoriginallyset,thisisnormalforallRapidExchangepurgingsystems.
9. SetRETtimer(seepage20fortimerlocationandsettings)forrequiredexchangetimebasedonsystemexchangerateofONEMINUTEPER2.5CUBICFEET,five(5)minuteminimum.
10.InstallandtightencoverofEPCU.Ensuretheconduitissealedwithapprovedcompounds.
11.Depresstheon-offpushbutton(NRmode)orturnselectorswitchtotheonposition(CBmode).EachLEDshouldilluminatefullyfortwoseconds(selftest),thenallLEDsshouldturnoffexceptPoweroff(solidred)andalarmactivated(flashingred)LEDs.
12.TurnenclosurepressurecontrolvalveslowlyCWtosettheenclosurepressureindicatortoa"Safe"0.25inchpressure.ThesafepressureLEDshouldbeon,thealarmactiveLEDshouldturnoff.Checkfora0.10to0.15inchtrippointbyslowlystrokingtheindicatorfrom0.10to0.25inchreadings.ThesafepressureandalarmactiveLEDsshouldturnonandoffwhentheindicatorreadsbetween0.10and0.15inches.
Note:FAStyleonly-RapidExchangesolenoidvalvewillengageautomaticallyupontimeoutoftheEDTtimer.Shouldtheoperatorrequireadditionaltimetosetastablesafepressureontheenclosurepressureindicator,resettheEDTtimersettingasdescribedonpage21.
Model 2003 Installation and Operation Manual
23
Par
t No.
512
473
Dra
win
g N
o. 1
29-0
212a
03/
09
Subject to modifications without notice
Pepperl+Fuchs Groupwww.pepperl-fuchs.com
USA: +1 330 486 0002pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com
Singapore: +65 6779 9091pa-info@sg.pepperl-fuchs.com
Copyright Pepperl+Fuchs
Germany: +49 621 776 2222
Set-up Procedure (cont.)
13.STD Style-OpenRapidExchangecontrolvalvefullybyturning90°CCWandquicklyensuretheenclosureprotectionventopens.TheRapidExchangeandtimeractiveLEDsshouldbeon.CheckfortrippointbyturningRapidExchangecontrolvalveonandoff.TheRapidExchangeandtimerrunningLEDsshouldturnonandoffasexchangeisengagedanddisengaged,withoutdisturbingthestatusofthesafepressureLED.
SA Style-PlacelefthandonsystemmountingplateandpullRapidExchangemanualoperatorfirmlywithrighthand,untilsolenoidlatches(toholdvalveopenautomatically)thenquicklyensuretheenclosureprotectionventopens.TheRapidExchangeandtimeractiveLEDsshouldbeon.CheckfortrippointbyturningEPCUpowerswitchoffandon(toresetunit).TheRapidExchangeandtimerrunningLEDsshouldnotturnonuntilvalveismorethanhalfopen.AllowsystemtorunthroughRETtimercycleandwatchforsolenoidtodisengage.ThevalveshouldbeabletoshutoffwithoutdisturbingthestatusofthesafepressureLED.
FA Style-RapidExchangesolenoidvalvewillengageautomaticallyupontimeoutoftheEDTtimer,thenquicklyensuretheenclosureprotectionventopens.TheRapidExchangeandtimeractiveLEDsshouldbeonandSLTtimerwillberunning.CheckfortrippointbyturningEPCUpowerswitchoffandon(toresetunit).TheRapidExchangeandtimerrunningLEDsshouldnotturnonuntilvalveismorethanhalfopen.Startingagain,allowsystemtorunthroughEDT,SLTandRETtimercyclesandwatchforsolenoidtodisengage.ThevalveshouldbeabletoshutoffwithoutdisturbingthestatusofthesafepressureLED.
14.HavingensuredthatthesafepressureandtimerrunningLEDsarefunctioningproperly,Operatingprocedureslocatedonpage24maynowbefollowedtostepthroughacompletestartupcycle,ensuringthatthesystemfunctionsnormallyduringallphasesofoperation.
15.Ceasetestingandremovetestequipment.
Model 2003-STD-CB-LHFront View
Start-upinstructionnameplate
Enclosurepressuregauge
RapidExchange
pressuregauge
Enclosurepressurecontrolvalve
LEDstatusnameplate
EXPEPCUenclosure
EXPbreather
drain
Modelidentificationnameplate
RapidExchange
controlvalve
RapidExchange
pressuregauge
Bypassoperating
instructions
EPCUpowerselectorswitch
SystemLEDdisplay
RapidExchange
manualoperator
Start-upinstructionnameplate
Enclosurepressuregauge
LEDstatusnameplate
EPCUpowerselectorswitch
SystemLEDdisplay
EXPEPCUenclosure
Model 2003-FA-CB-LHFront View
Model 2003 Installation and Operation Manual
24
Par
t No.
512
473
Dra
win
g N
o. 1
29-0
212a
03/
09
Subject to modifications without notice
Pepperl+Fuchs Groupwww.pepperl-fuchs.com
USA: +1 330 486 0002pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com
Singapore: +65 6779 9091pa-info@sg.pepperl-fuchs.com
Copyright Pepperl+Fuchs
Germany: +49 621 776 2222
Operating Sequence
WARNING! Do not exceed a “safe” pressure with the enclosure pressure control regulator.
Operators must follow step-by-step sequence of the start-up instructions nameplate on the protection system.
Do not use the bypass modes without first securing a "hot work" permit.
Never leave the system unattended in bypass modes.
Rapid Exchange Purging OperationWiththeinertgassupplyon,RETtimersetproperly(STDandSAStyles),EDT,SLTandRETtimerssetproperly(FAStyles),EPCUpowerandalarmsystemenergized(ifutilized).
1.Carefullyreadstart-upinstructionnameplateonsystem.
2.Checkoperationoftheenclosureprotectionvent(modelEPV-3,ifutilized),openingitmanuallyseveraltimes.Seepage22,“HelpfulHint.”
3.Sealprotectedenclosure(s).
4. Depresstheon-offpushbutton(NRmode)orturnselectorswitchtotheonposition(CBmode).EachLEDshouldilluminatefullyfortwoseconds,thenallLEDsshouldturnoffexceptpoweroff(solidred)andalarmactivated(flashingred)LEDs.
5.TurnenclosurepressurecontrolregulatorslowlyCCWtosettheenclosurepressureindicatortoa"safe"0.25inchpressure.ThesafepressureLEDshouldbeon,thealarmactiveLEDshouldturnoff.
6. STD Style-OpenRapidExchangecontrolvalvefullybyturning90°CCWandquicklyensuretheenclosureprotectionventopens.TheRapidExchangeandtimeractiveLEDsshouldturnon.
SA Style-PlacelefthandonsystemmountingplateandpullRapidExchangemanualoperatorfirmlywithrighthand,untilsolenoidlatches(toholdvalveopenautomatically)thenquicklyensuretheenclosureprotectionventopens.TheRapidExchangeandtimeractiveLEDsshouldturnon.
FA Style-RapidExchangesolenoidvalvewillengageautomaticallyupontimeoutoftheEDTtimer,thenquicklyensuretheenclosureprotectionventopens.TheRapidExchangeandtimeractiveLEDsshouldbeonandSLTTimerwillberunning.
Note:Onallstyles,ifthesafepressureortimerrunningLEDsblinkonandoffor"flicker"duringthiscycle,EPCUwillresetRETtimer.
7. StandbyuntiltheEPCURETtimercompletesthetimingcycleandenergizesenclosurepower.SafepressureLEDshouldstayon,timerrunningLEDshouldturnoffandpoweronLEDshouldturnon.
8. STD Style-CloseRapidExchangecontrolvalvefullybyturning90°CW.TheRapidExchangeandtimeractiveLEDsshouldbeoff.
SA & FA Styles-AftercompletionoftheRETtimimgcycle,timerRunningLEDshouldturnoffandpoweronLEDshouldturnon.Atthesametime,theRapidExchangesolenoidvalveshoulddeenergizeandtheRapidExchangeLEDshouldturnoff.
9.EnsuretheprotectionsystemenclosurepressureIndicatormaintainsa“safe”0.25inchpressureforone(1)minute.Readjustenclosurepressurecontrolvalveifrequired.
10.If"safe"0.25inchpressureislost,theEPCUwilldeenergizeenclosurepowerandactivatealarmsystem(ifutilized).
Model 2003 Installation and Operation Manual
25
Par
t No.
512
473
Dra
win
g N
o. 1
29-0
212a
03/
09
Subject to modifications without notice
Pepperl+Fuchs Groupwww.pepperl-fuchs.com
USA: +1 330 486 0002pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com
Singapore: +65 6779 9091pa-info@sg.pepperl-fuchs.com
Copyright Pepperl+Fuchs
Germany: +49 621 776 2222
Troubleshooting Procedures
Problem or Fault Possible Causes Corrective Action
Enclosurepressurecontrolvalvewillnotholdasafe.25inchpressure.
Leakagearoundgasketing,covers,seams,pipingandtubingconnections,conduitconnectionsandelectricalconduitsealsoftheenclosure.
Tightenenclosurelatches:Wheretighteningisnotfeasible,andgasketingmaterialsarenotpractical,holesorgapscanbeclosedwithsiliconesealantappliedfrominsidetheprotectedenclosure.
Enclosurepressureindicatorreadingisdifficulttostabilize.
Insufficientenclosureleakageoropeningoftheventuriorificeiscrimpedtoosmall.
Removetheorifice,cutoffthecrimpedendandreamthetube,thenrecrimpandreinstallthetubetonoteeffect.Astubeisshortened,reamed,andrecrimped,sensitivitydecreases,allowingeasieradjustmentofsetpointontheenclosure.
Enclosureprotectionvent"shuttles"orflutters"
Excessiveleakagefromprotectedenclosure.
Insuffcientprotectivegassupplyheaderpressure.
Checkallpointsaboveandverifyaminimum60psiinjectionpressurereadingontheRapidExchangepressureindicatorduringRapidExchange.
Witha0.0"-5"watercolumntestgaugeinstalledproperly(see"set-upprocedures"page22),slowlyincreasetheRapidExchangeiInjectionpressurewiththeRapidExchangevalveengageduntilthiseffectiseliminated.Donotexceed3inchesofpressurewithintheprotectedenclosure.
Enclosurepressureindicatorreadsa"safe"pressurebutthesafepressureLEDisnotilluminated.
ConduitsealbetweenEPCUandprotectedenclosureisnotpouredorisleakingpressurebackintotheEPCU.
EPCUbreatherdrainisclogged(allsystemsexceptPMconfigurations).Safepressureswitchisoutofcalibration.
Withareapositivelyknowntobenonhazardous,removescrewcoveroftheEPCUandattemptacompletestart-upprocedure.Ifthesystemworksproperly,checkenclosurepowerconduitsealforleakageandtheEPCUbreatherdrainforblockage.Ifthesystemdoesnotoperateproperly,calibratethesafepressureswitch.
CalibratebyslowlyadjustingCCWtodecreasethesetpoint,andCWtoraisethesetpoint.
(Donotattempttocalibratetheswitchuntilalleffortstomaketheswitchrespondproperlyhavefailed)
RapidExchangeLEDdoesnotiluminatewhenRapidExchangeisengaged.
FAStyleonly-TheRapidExchangesolenoidcontinuestocyclewithoutstartingtheRETtimer.
ConduitsealbetweenEPCUandprotectedenclosureisnotpouredorisleakingpressurebackintotheEPCU.
EPCUbreatherdrainisclogged(allsystemsexceptPMconfigurations).RapidExchangepressureswitchisoutofcalibration.
Withareapositivelyknowntobenonhazardous,removescrewcoveroftheEPCUandattemptacompletestart-upprocedure.Ifthesystemworksproperly,checkenclosurepowerconduitsealforleakageandtheEPCUbreatherdrainforblockage.Ifthesystemdoesnotoperateproperly,calibratetheRapidExchangepressureswitch.
WithRapidExchangeengaged,calibratebyslowlyadjustingclockwisetodecreasethesetpoint,andcounterclockwisetoraisethesetpoint.
(Donotattempttocalibratetheswitchuntilalleffortstomaketheswitchrespondproperlyhavefailed)
Problemspersists,orifthesystemdoesnotappeartobeoperatingproperly.
Persistingproblems. ContactPepperl+FuchsApplications/CustomerServiceDepartmentat(330)486-0002formoreinformation.
Thissectioncoversthemostcommonproblemsdocumentedwiththissystem.Anyproblemsnotcoveredinthissectionshouldbeaddresseddirectlytoourfactory.Pleaseaddressallserviceneedsto:
Pepperl+Fuchs, Inc. Customer Service Department
Model 2003 Installation and Operation Manual
26
Par
t No.
512
473
Dra
win
g N
o. 1
29-0
212a
03/
09
Subject to modifications without notice
Pepperl+Fuchs Groupwww.pepperl-fuchs.com
USA: +1 330 486 0002pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com
Singapore: +65 6779 9091pa-info@sg.pepperl-fuchs.com
Copyright Pepperl+Fuchs
Germany: +49 621 776 2222
PEPPERL+FUCHS STANDARD 24-MONTH WARRANTY1. LimitedWarranty.Pepperl+Fuchs,Inc.(“P+F")warrantsPurgeUnitsandcomponentsforPurgeUnitsmanufacturedbyP+F
(“Product"or“Products")tobefreefromdefectsinmaterialandworkmanshipunderNormalUseforaperiodoftwenty-four(24)monthsfromthedateofshipmentofsuchProductsfromP+F’swarehouseorplaceofmanufacture(orfromP+F’sauthorizedrepresentativeordistributor).OnlytheoriginalpurchaserofsuchProducts(the“Customer")shallbeentitledtothebenefitoftheforegoingLimitedWarranty.Norepresentative,agentorsalesmanofP+FisauthorizedtogiveorprovideanywarrantyormakeanyrepresentationcontrarytoorinadditiontotheforegoingLimitedWarranty.
2. InspectionandClaims.CustomermustinspectandtestallProductsuponreceipt.AllclaimsundertheLimitedWarrantyprovidedhereinmustbemadewithinthirty(30)daysofthediscoveryofthedefect.CustomermustobtainshippinginstructionsfromP+FpriortoreturninganyProduct,whichProductmustbereturnedatCustomer’sexpenseinaccordancewithP+F’sinstructions.
3. LimitationsandExclusions.“NormalUse"shallmeanuseandoperationwithinratedcapacities,atthecorrectvoltage,andwithanyrequiredmaintenanceasprovidedintheapplicableP+FOperatingManuals.TheLimitedWarrantyprovidedhereindoesnotapplyto(i)anyProductswhichhavebeenalteredormodifiedinanywayordisassembledbytheCustomeroranyoneelse,(ii)anyProductswhichhavebeensubjecttomisuse,negligenceoraccident,orimproperlyinstalled,changed,substitutedorreplaced,(iii)anypartorcomponentnotmanufacturedbyP+F,or(iv)anypartorcomponentthatissubjecttowearorconsumption.ForpartsorcomponentsnotmanufacturedbyP+F,theCustomeroranyotheruserorownershallhaveonlythewarrantyprovidedbythemanufacturerofsuchpartorcomponent.TheLimitedWarrantysetforthhereinisalsosubjecttothefollowing:
(1) TheLimitedWarrantyislimitedtoelectronicandmechanicalperformanceonly,asexpresslydetailedintheproductspecifications,anddoesnotapplytocosmeticappearance;
(2) TheLimitedWarrantyshallnotapplytoanycablesattachedto,orintegratedwith,anyProducts.
(3) TheLimitedWarrantyshallnotapplytoanyProductswhicharestored,orutilized,inharshenvironmentalorelectricalconditionsoutsideP+F’swrittenspecifications.
THELIMITEDWARRANTYSETFORTHHEREINISTHEONLYWARRANTYMADEBYP+FWITHRESPECTTOTHEPRODUCTS.ITISEXPRESSLYAGREEDANDUNDERSTOODTHATP+FMAKESNOWARRANTYOFMERCHANTABILITYORFITNESSFORAPARTICULARPURPOSE.EXCEPTFORTHELIMITEDWARRANTYSETFORTHHEREIN,THEREISNOOTHERWARRANTY,EXPRESS,IMPLIEDORSTATUTORY;ANDTHEREISNOAFFIRMATIONOFFACTORPROMISEBYP+FWITHREFERENCETOTHEPRODUCTS.INNOEVENTSHALLP+FBELIABLEFORACTUALORANTICIPATEDLOSTPROFITSORFORINCIDENTALORCONSEQUENTIALORPUNITIVEDAMAGESORFORDAMAGESRESULTINGFROMBUSINESSINTERRUPTION,ORINJURYORDEATHOFPERSONS,ORINJURYTOPROPERTY.P+F’SLIABILITYONANYCLAIMOFANYKINDARISINGOUTOF,CONNECTEDWITHORRESULTINGFROMTHEDESIGN,MANUFACTURE,SALE,REPAIROROPERATIONOFAPRODUCT,SHALLNOTEXCEEDTHEPRICEALLOCABLETOTHATPRODUCTORTHEPARTTHEREOFWHICHGIVESRISETOTHECLAIM.THEREMEDYSETFORTHINTHISLIMITEDWARRANTYCONSTITUTESTHESOLEANDEXCLUSIVEREMEDYOFTHECUSTOMER.P+FSHALLNOTBELIABLEFORPENALTIESOFANYDESCRIPTION.
4. LimitationofRemedies.IntheeventofP+F’sliability,whetheronthisLimitedWarrantyorbasedoncontract,tort(including,butnotlimitedto,negligenceandstrictliability)orotherwise,Customer’ssoleandexclusiveremedywillbelimitedto,atP+F’soption,therepairorreplacement(f/o/bP+F’splaceofmanufacture)byP+Fofanynon-conformingitemsforwhichclaimismadebyCustomerinaccordancewithparagraph2,ortherepaymentoftheportionofthepurchasepricepaidbyCustomerattributabletothenon-conformingitem.
5. ResponsibilityofCustomer:SafetyandProtectionPrecautions.P+FtakesgreatcaretodesignandbuildreliableanddependableProducts;however,someProductscanfaileventually.Customermusttakeprecautionstodesignitsequipmenttopreventpropertydamageandpersonalinjuryintheunlikelyeventofafailure.ASAMATTEROFPOLICY,P+FDOESNOTRECOMMENDTHEINSTALLATIONOFPRODUCTSASTHESOLEDEVICEFORTHEPROTECTIONOFPERSONNELORPROPERTYAND,THEREFORE,THECUSTOMERSHOULDBUILDINREDUNDANCYORDUALCONTROLUSINGAPPROVEDSAFETYDEVICESFORTHESEAPPLICATIONS.
6. Conflicts.IntheeventthereisanyconflictbetweentheprovisionsofthisLimitedWarrantyandanyprovisionscontainedinanyorders,offers,acceptancesorotherwritingsorstatementsprovidedormadebyCustomertoP+F,theprovisionsofthisLimitedWarrantyshallprevail,andthecontractbetweenP+FandtheCustomershallbedeemedformedonlyupontheprovisionssetforthinthisLimitedWarranty,andanyadditionalorconflictingprovisioninsertedbyCustomershallbeofnoforceoreffect.
Warranty Terms and Conditions
Model 2003 Installation and Operation Manual
27
Par
t No.
512
473
Dra
win
g N
o. 1
29-0
212a
03/
09
Subject to modifications without notice
Pepperl+Fuchs Groupwww.pepperl-fuchs.com
USA: +1 330 486 0002pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com
Singapore: +65 6779 9091pa-info@sg.pepperl-fuchs.com
Copyright Pepperl+Fuchs
Germany: +49 621 776 2222
Notes
Model 2003 Installation and Operation Manual
28
Par
t No.
512
473
Dra
win
g N
o. 1
29-0
212a
03/
09
Subject to modifications without notice
Pepperl+Fuchs Groupwww.pepperl-fuchs.com
USA: +1 330 486 0002pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com
Singapore: +65 6779 9091pa-info@sg.pepperl-fuchs.com
Copyright Pepperl+Fuchs
Germany: +49 621 776 2222
Notes
Model 2003 Installation and Operation Manual
29
Par
t No.
512
473
Dra
win
g N
o. 1
29-0
212a
03/
09
Subject to modifications without notice
Pepperl+Fuchs Groupwww.pepperl-fuchs.com
USA: +1 330 486 0002pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com
Singapore: +65 6779 9091pa-info@sg.pepperl-fuchs.com
Copyright Pepperl+Fuchs
Germany: +49 621 776 2222
Notes
Model 2003 Installation and Operation Manual
30
Par
t No.
512
473
Dra
win
g N
o. 1
29-0
212a
03/
09
Subject to modifications without notice
Pepperl+Fuchs Groupwww.pepperl-fuchs.com
USA: +1 330 486 0002pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com
Singapore: +65 6779 9091pa-info@sg.pepperl-fuchs.com
Copyright Pepperl+Fuchs
Germany: +49 621 776 2222
System Maintenance
Regular MaintenanceDraintheprotectionsystemregulatorfrequentlyandcleansystemwithnonsolventcleaningagentsonly.
Long-Term MaintenanceCalibratetheenclosurepressureindicatorto0inchesbyventingthepurgepressurereferenceportandtheprotectedenclosuretoatmosphereandadjustingthecalibrationscrewinthelowercenterportionoftheindicator’sface.
Fullyopentheenclosurepressurecontrolregulator,toblowoutanydepositsaroundthetipofthevalveandtoensurethattheenclosureprotectionventisoperatingproperly,thencarefullyreadjustsystemaccordingtotheset-upprocedureandoperatingsequenceonpages22through24.Replaceortightenstempackingnutasrequiredtoprohibitstempackingleakage.
Carefullydisassembletheenclosureprotectionventbylooseningthetwobottomhexnutsthatholdtheunittogether.
(DO NOT REMOVE CAP NUTS ON TOP OF VENT BODY)
Carefullycleantheflappervalveandventbodyseatswithwarmsoapandwater,beingcarefulnottoextendtheventvalvebeyonditsnormalopeningpoint,andbeingcarefulnottoexertanystressonthevalvehinge.
Examinetheentireprotectionsystemandtheprotectedenclosure(s),andreplaceanydefectivepartsduringroutineshutdownoftheprotectedenclosure(s).PartsareavailablefromPepperl+Fuchsonimmediatenoticeasrequired.
MAINTENANCE SCHEDULEDate Work performed Performed by
Model 2003 Installation and Operation Manual
31
Par
t No.
512
473
Dra
win
g N
o. 1
29-0
212a
03/
09
Subject to modifications without notice
Pepperl+Fuchs Groupwww.pepperl-fuchs.com
USA: +1 330 486 0002pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com
Singapore: +65 6779 9091pa-info@sg.pepperl-fuchs.com
Copyright Pepperl+Fuchs
Germany: +49 621 776 2222
Systems Identification & Application Information
Date of installation _____________________________________________________
Unit serial #____________________________________________________________
Item ___________________________________________________________________
Customer P.O.# ________________________________________________________
Customer project# _____________________________________________________
Service ________________________________________________________________
Type __________________________________________________________________
Features ______________________________________________________________
Application ____________________________________________________________
Notes: _______________________________________________________________________________________________
_____________________________________________________________________________________
_____________________________________________________________________________________
_____________________________________________________________________________________
_____________________________________________________________________________________
_____________________________________________________________________________________
_____________________________________________________________________________________
_____________________________________________________________________________________
_____________________________________________________________________________________
_____________________________________________________________________________________
5 1
8
4
2
6
7
3
www.pepperl-fuchs.com
PROCESS AUTOMATION – PROTECTING YOUR PROCESS
Worldwide/German Headquarters Pepperl+Fuchs GmbH Mannheim · GermanyTel. +49 621 776 2222E-Mail: pa-info@de.pepperl-fuchs.com
1
Asia Pacific HeadquartersPepperl+Fuchs PTE Ltd. SingaporeCompany Registration No. 199003130ETel. +65 6779 9091E-Mail: pa-info@sg.pepperl-fuchs.com
2
Central/Western Europe & Africa HeadquartersPepperl+Fuchs N.V. Schoten/Antwerp · BelgiumTel. +32 3 6442500E-Mail: pa-info@be.pepperl-fuchs.com
3
Middle East HeadquartersPepperl+Fuchs M.E (FZE) Dubai · UAETel. +971 4 883 8378E-Mail: pa-info@ae.pepperl-fuchs.com
4
North/Central America Headquarters Pepperl+Fuchs Inc. Twinsburg · Ohio · USATel. +1 330 486 0002E-Mail: pa-info@us.pepperl-fuchs.com
5
Northern Europe HeadquartersPepperl+Fuchs GB Ltd. Oldham · EnglandTel. +44 161 6336431E-Mail: pa-info@gb.pepperl-fuchs.com
6
Southern/Eastern Europe HeadquartersPepperl+Fuchs Elcon srl Sulbiate · ItalyTel. +39 039 62921E-Mail: pa-info@it.pepperl-fuchs.com
7
South America HeadquartersPepperl+Fuchs Ltda. São Bernado do Campo · SP · BrazilTel. +55 11 4339 9935E-Mail: pa-info@br.pepperl-fuchs.com
8
For over a half century, Pepperl+Fuchs has provided new concepts for the world of process automation. Our company sets standards in quality and innovative technology. We develop, produce, and distribute electronic interface modules, Human-Machine Interfaces and hazardous location protection equipment on a global scale, meeting the most demanding needs of industry. Resulting from our world-wide presence and our high flexibility in production and customer service, we are able to offer complete individual solutions – wherever and whenever you need us. We are the recognized experts in our technologies – Pepperl+Fuchs has earned a strong reputation by supplying the world’s largest process industry companies with the broadest line of proven components for a diverse range of applications.
Subject to modifications • © 2009 PEPPERL+FUCHS, INC. • Printed in USA • Part No. 512473 Drawing No. 129-0212a (TDOCT1366_ENG) 03/09
top related