installation contactors up to 32 a

Post on 16-Jan-2017

225 Views

Category:

Documents

3 Downloads

Preview:

Click to see full reader

TRANSCRIPT

Installation Contactors series 200 and 400

IKA225, IKD225, IKA232, IKD232, IKA432, IKD432

SERIES 200•2-polesinstallationcontactors•Thermalcurrent:25Aand32A•RatedcurrentAC-1:25Aand32A

SERIES 400•4-polesinstallationcontactors•Thermalcurrent:32A•RatedcurrentAC-1:32A

ADVANCED OPERATION•IKDforACorDCremotecontrol•IKAforACremotecontrol

OTHER BENEFITS•Hum-freeinstallationcontactorsIKDarespeciallysuitable forapplicationssuchusresidential,hospitals,hotelsand buisinesspremises•Overvoltageprotectionbuilt-ininstallationscontactorsIKD•InstallationcontactorsIKDdonotcauseinrushvoltages andcurrents•ExtremelylongmechanicallifeofinstallationcontactorsIKD•StandardInstallationcontactorsIKAaregeneralusefulin allapplications•ItisalsopossibletomountanauxiliaryswitchIKNon IKA225,IKA232,IKA432andIKD432

®

NEW

TECHNICAL DATA

Type IKA225 IKD225 IKA232 IKD232 IKA432 IKD432

GE

NE

RA

L

Standards IEC/EN 60947-4-1, IEC/EN 61095

Module width (1 module width = 17,5 mm) 1 2

Mechanical endurance op. c. 3 x 106 107 3 x 106 107 3 x 106 107

Ambient temperature °C -15…+55

Storage temperature °C -40…+80

No. of contactors side-by-side ≤ 40 °C40 - 55 °C

max. 3max. 2

Contact reliability 17 V; ≥ 50 mA

Min. distance of open contacts mm 3,6

Power dissipation per pole W 2,0 2,0 2,5 2,5 2,5 2,5

Overcurrent withstand capability A 72 72 72 72 68 68

Max. back-up fuse for short-circuit protection gG (gL) - coordination type 1 Iv A 25 25 32 32 32 32

Max. operating frequencyDC-1AC-1 / AC-7a / AC-3 / AC-7b / lamp loadsNo load

3006003000

Weight kg 0,13 0,13 0,13 0,13 0,24 0,26

MA

IN C

IRC

UIT

Rated insulation voltage Ui V 440

Rated impulse withstand woltage Uimp kV 4

Thermal current Ith A 25 25 32 32 32 32

Rated operational voltage Ue V 230 230 230 230 400 400

Rated frequency f Hz 50/60

Rated operational current:AC-1 - Non-inductive or slightly inductive loads, resistance furnacesAC-7a - Slightly inductive loads in household appliances and similar applications

Ie A 25 25 32 32 32 32

Operational power for AC-1 / AC-7asingle-phase 230 V

Pe kW5,4 5,4 7,0 7,0 7,0 7,0

three-phase 230 V 12 12three-phase 400 V 21 21

Electrical endurance for AC-1 / AC-7a op. c 200.000 NO: 150.000 NC: 100.000 150.000

Rated operational current:AC-3 - Squrrel-cage motors, starting: switching off motors during runningAC-7b - Motor-loads for household applications

Ie A NO: 9NC: 6

NO: 9NC: 6

NO: 9NC: 6

NO: 9NC: 6 8,5 8,5

Operational power for AC-3 / AC-7b

single-phase 230 V

Pe kW

NO: 1,3 NC: 0,75 NO: 1,3 NC: 0,75 NO: 1,3 NC: 0,75 NO: 1,3 NC: 0,75 1,3 1,3

three-phase 230 V 2,2 2,2

three-phase 400 V 4 4

Electrical endurance for AC-3 / AC-7b op. c. 300.000 500.000

Rated operational current DC-1 - Non-inductive or slightly inductive loads, resistive furnaces

L/R ≤ 1 ms Ie A 25 / 24 V / 1 pole 25 / 24 V / 1 pole 32 / 24 V / 1 pole 32 / 24 V / 1 pole 32 / 24 V / 1 pole 32 / 24 V / 1 pole

Electrical endurance for DC-1 op. c. 100.000

Incandescent lamps and tungsten halogen lamps Ie per pole at 230 V 50 Hz Ie A 8 8 10 10 10 10

Energy saving lamps, compact fluo. lamps and fluo. lamps with el. control gear Ie per pole at 230 V 50 Hz Ie A 3 3 3,5 3,5 3,5 3,5

Fluorescent lamps - uncorrected or series corrected Ie per pole at 230 V 50 Hz Ie A 8 8 10 10 10 10

Fluorescent lamps - parallel correction Ie per pole at 230 V 50 Hz Ie A 1,5 1,5 2 2 2 2

Transformers for low-voltage tungsten halogen lamps Ie per pole at 230 V 50 Hz Ie A 3 3 3,5 3,5 3,5 3,5

Metal halide lamps with el. control gear Ie per pole at 230 V 50 Hz Ie A 2,5 2,5 3 3 3 3

High-pressure sodium-vapour lamps with el. control gear Ie per pole at 230 V 50 Hz Ie A 2,5 2,5 3 3 3 3

Electrical endurance for lamps op. c. 100.000

Terminal capacity rigidflexible S mm2 1…10

1…6

Screw M3,5

Screw head PZ1

Tightening torque Nm 1,2

CO

NT

RO

L C

IRC

UIT

Range of control voltage Uc % 85…110

Kind of voltage AC AC, DC AC AC, DC AC AC, DC

Control voltage Uc V 12, 24, 48, 110, 115, 120, 220, 230

Frequency (AC) f Hz 50/60 40…500 50/60 40…500 50/60 40…500

Surge immunity test (1,2/50 μs) acc. to IEC/EN 61000-4-5 kV 2

Coil consumption switch-onoperation VA / W 12 / 10

2,8 / 1,22,1 / 2,12,1 / 2,1

12 / 102,8 / 1,2

2,1 / 2,12,1 / 2,1

33 / 255,5 / 1,6

2,6 / 2,6*2,6 / 2,6*

Delays makebreak ms 15 - 25

10 - 30 15 - 4520 - 50

15 - 2510 - 30

15 - 4520 - 50

10 - 3010 - 30

15 - 4520 - 70

Terminal capacity rigidflexible S mm2 1…2,5

1…2,5

Screw M3,5

Screw head PZ1

Tightening torque Nm 0,6

*Coil consumption for version -04 is 3,8 VA / 3,8 W

Type IKA225 IKD225 IKA232 IKD232 IKA432 IKD432

GE

NE

RA

L

Standards IEC/EN 60947-4-1, IEC/EN 61095

Module width (1 module width = 17,5 mm) 1 2

Mechanical endurance op. c. 3 x 106 107 3 x 106 107 3 x 106 107

Ambient temperature °C -15…+55

Storage temperature °C -40…+80

No. of contactors side-by-side ≤ 40 °C40 - 55 °C

max. 3max. 2

Contact reliability 17 V; ≥ 50 mA

Min. distance of open contacts mm 3,6

Power dissipation per pole W 2,0 2,0 2,5 2,5 2,5 2,5

Overcurrent withstand capability A 72 72 72 72 68 68

Max. back-up fuse for short-circuit protection gG (gL) - coordination type 1 Iv A 25 25 32 32 32 32

Max. operating frequencyDC-1AC-1 / AC-7a / AC-3 / AC-7b / lamp loadsNo load

300600

3000

Weight kg 0,13 0,13 0,13 0,13 0,24 0,26

MA

IN C

IRC

UIT

Rated insulation voltage Ui V 440

Rated impulse withstand woltage Uimp kV 4

Thermal current Ith A 25 25 32 32 32 32

Rated operational voltage Ue V 230 230 230 230 400 400

Rated frequency f Hz 50/60

Rated operational current:AC-1 - Non-inductive or slightly inductive loads, resistance furnacesAC-7a - Slightly inductive loads in household appliances and similar applications

Ie A 25 25 32 32 32 32

Operational power for AC-1 / AC-7asingle-phase 230 V

Pe kW5,4 5,4 7,0 7,0 7,0 7,0

three-phase 230 V 12 12three-phase 400 V 21 21

Electrical endurance for AC-1 / AC-7a op. c 200.000 NO: 150.000 NC: 100.000 150.000

Rated operational current:AC-3 - Squrrel-cage motors, starting: switching off motors during runningAC-7b - Motor-loads for household applications

Ie A NO: 9NC: 6

NO: 9NC: 6

NO: 9NC: 6

NO: 9NC: 6 8,5 8,5

Operational power for AC-3 / AC-7b

single-phase 230 V

Pe kW

NO: 1,3 NC: 0,75 NO: 1,3 NC: 0,75 NO: 1,3 NC: 0,75 NO: 1,3 NC: 0,75 1,3 1,3

three-phase 230 V 2,2 2,2

three-phase 400 V 4 4

Electrical endurance for AC-3 / AC-7b op. c. 300.000 500.000

Rated operational current DC-1 - Non-inductive or slightly inductive loads, resistive furnaces

L/R ≤ 1 ms Ie A 25 / 24 V / 1 pole 25 / 24 V / 1 pole 32 / 24 V / 1 pole 32 / 24 V / 1 pole 32 / 24 V / 1 pole 32 / 24 V / 1 pole

Electrical endurance for DC-1 op. c. 100.000

Incandescent lamps and tungsten halogen lamps Ie per pole at 230 V 50 Hz Ie A 8 8 10 10 10 10

Energy saving lamps, compact fluo. lamps and fluo. lamps with el. control gear Ie per pole at 230 V 50 Hz Ie A 3 3 3,5 3,5 3,5 3,5

Fluorescent lamps - uncorrected or series corrected Ie per pole at 230 V 50 Hz Ie A 8 8 10 10 10 10

Fluorescent lamps - parallel correction Ie per pole at 230 V 50 Hz Ie A 1,5 1,5 2 2 2 2

Transformers for low-voltage tungsten halogen lamps Ie per pole at 230 V 50 Hz Ie A 3 3 3,5 3,5 3,5 3,5

Metal halide lamps with el. control gear Ie per pole at 230 V 50 Hz Ie A 2,5 2,5 3 3 3 3

High-pressure sodium-vapour lamps with el. control gear Ie per pole at 230 V 50 Hz Ie A 2,5 2,5 3 3 3 3

Electrical endurance for lamps op. c. 100.000

Terminal capacity rigidflexible S mm2 1…10

1…6

Screw M3,5

Screw head PZ1

Tightening torque Nm 1,2

CO

NT

RO

L C

IRC

UIT

Range of control voltage Uc % 85…110

Kind of voltage AC AC, DC AC AC, DC AC AC, DC

Control voltage Uc V 12, 24, 48, 110, 115, 120, 220, 230

Frequency (AC) f Hz 50/60 40…500 50/60 40…500 50/60 40…500

Surge immunity test (1,2/50 μs) acc. to IEC/EN 61000-4-5 kV 2

Coil consumption switch-onoperation VA / W 12 / 10

2,8 / 1,22,1 / 2,12,1 / 2,1

12 / 102,8 / 1,2

2,1 / 2,12,1 / 2,1

33 / 255,5 / 1,6

2,6 / 2,6*2,6 / 2,6*

Delays makebreak ms 15 - 25

10 - 30 15 - 4520 - 50

15 - 2510 - 30

15 - 4520 - 50

10 - 3010 - 30

15 - 4520 - 70

Terminal capacity rigidflexible S mm2 1…2,5

1…2,5

Screw M3,5

Screw head PZ1

Tightening torque Nm 0,6

*Coil consumption for version -04 is 3,8 VA / 3,8 W

Contact Arrangements, Operation Positions,Dimensions, Ordering data

CONTACT ARRANGEMENTS

DIMENSIONS

ORDERING DATA

OPERATION POSITIONS

IKA225-02IKD225-02IKA232-02IKD232-02

IKA432-31IKD432-31

IKA432-22IKD432-22

IKA432-30IKD432-30

IKA225-01IKD225-01IKA232-01IKD232-01

IKA225-20IKD225-20IKA232-20IKD232-20

IKA225-11IKD225-11IKA232-11IKD232-11

IKA225-10IKD225-10IKA232-10IKD232-10

IKA432-04IKD432-04

IKA432-40IKD432-40

Published by Iskra Sistemi, d. d. • Version 3.0, March 2013 • design Nimbus d.o.o

Stegne21,SI-1000Ljubljana,SloveniaTel.:+38615131000,Fax:+38615111532E-mail:info@iskrasistemi.si,www.iskrasistemi.si

IK225-20/230V

ControlvoltageVersionofcontactsType

IKA IKA, IKD IKD

Sealing Cover

Series 400 Series 200