Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Brief Introduction for Automated Relay Testing

Kamin DaveApplication Engineer (Protective Relaying)

DOBLE ENGINEERING COMPANY

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Protection Relay Testing:

Testing of Differential Protection Relay type KBCH120

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: KBCH120

Two Differential Protection relaysAutomatic calculation for TAP values based on CTRSettings for Transformer & CT vector group compensations 2nd Harmonic Blocking during inrush period due to point on wave switching

Inrush Gap Detection Criterion

5th Harmonic Blocking for Over excitation phenomenaInverse Time Over Excitation Trip Characteristic

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: KBCH120MAKE : AREVAMODEL : KBCH120Relay Settings:Differential Element:

Rated MVA = 100HV = 220KVLV = 66KVTR VECTOR GROUP = YY0.CT CONNECTION = YYID> = 0.2PUTurn Point1 = 1.0PUID>> = 5.0PUSLP1 = 20% SLP2 = 80%In = 1A

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: KBCH120MAKE : AREVAMODEL : KBCH120Relay Settings:Differential Element:

HV CT Ratio = 300/1ALV CT Ratio = 1200/1ACF1 = 1.14CF2 = 1.37HV Vector Correction = YY0LV Vector Correction = YY0

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: KBCH120

FLC on TR Primary side:IFLC = (100*1000) / (1.7325*220)

= 262.36 AmpereFLC on TR Secondary side:

IFLC = (100*1000) / (1.7325*66)= 874.54 Ampere

CF1 = (1*300) / (262.36*1) = 1.14

CF2 = (1*1200) / (874.54*1) = 1.37

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Characteristic: Dual Slope

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Characteristic: Dual Slope

Idiff@SLP1 = (IBIAS)*(0.2) + (IS)

Idiff@SLP2 = (IS) + 0.2 + (Ibias - 1)*0.8

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Test Equipment

• Make : DOBLE

• Model : F6150

Software

• F6TesT Version 2.18-1028

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

IA

IB

IC

I1

I2

I3

KBCH

Test Circuit:

Source Configurations:Six current sources

Winding 1 currents

Winding 2 currents

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

• Pickup test for Winding1

• Pickup test for winding2

• Slope Characteristic test

Tests conducted:

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Winding Pickup Test

Use “RAMP” Module

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Winding Pickup Test:Pickup Test for Winding1 (WDG1):-Ipickup = (IS)*(1/CF1)

= (0.2)*0.8745= 0.1749A

Pickup Test for Winding2 (WDG2):-Ipickup = (IS)*(1/CF2)

= (0.2)*0.7287 = 0.1457A

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Winding Pickup Test:

How to Create Test Plan???

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Location Level

Add new Location or Double click on Existing Location

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Level

Add new Relay or Double click on Existing Relay

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Right click on Mouse & Press “Append”& create New Testplan

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Double click on “New test Plan”

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Right click on “Mouse” & Press on “Append”& Create new Test Module

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Select “RAMP” Module from list

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Press on “OK” & Create New Test Definition

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Select “6 Currents (Right bank)”

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Press on “Yes”

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

WDG1 current sources

Enter Expected Value = 0.175A

Enter “Action”details

Select “Trigger”

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Pickup Test: WDG1

Actual Test value = 0.197A

Click on “RUN”

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

WDG2 current sources

Enter Expected Value = 0.165A

Enter “Action”details

Select “Trigger”

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Pickup Test: WDG2

Actual Test value = 0.167A

WDG2 current sources

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Slope Characteristic Test

Use “DiffChar” Module

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Slope Characteristic Test:

Star conn. Star conn.

IP Is

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

How to Create Slope Characteristic???

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Click on “Add” & select “Differential”

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Select Bias current (Ibias) formula from list

Bias current Formula:Ibias = (IP+IS) / 2

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

R

YY0 YY0

Star conn. Star conn.YY0

SoftwareConfiguration

Amplitude Compensation

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Click on “Pickup” Column & then after Click on “Modify”

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Enter Pickup settingSay; 0.2

Select IBias Vs Idiff

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Enter Slope 20% & 80% based on relay setting

SLP1=20%

SLP2=80%

How to AdjustSlope?

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Click on “Close”

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Right click on “Mouse”& click on “Append”

How to create New Test Module?

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

How to create New Test Module?

Select “DiffChar” Module from list

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Double Click on Test Module & create New Test Definition

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Select characteristic from list

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Select elements

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Enter Max. Test current (i.e. 12A)

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Select Trigger (i.e. Open to Close)

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Select test points on curve

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

click on Add Point to List

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Test Points are added for Test

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Right click on check box

Right Click on check box

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Click on “RUN”

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Red color shows Expected Curve & White color shows actual Curve

Test results

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

DOBLE ENGINEERING COMPANY305-SAKAR, O.P. ROADNR. ABS TOWERVADODARA-390 015INDIA. Tel:- +91 265 655 77 15EMAIL ID:- kdave@doble.comWebsite:- www.doble.com