low level led emergency light lightpath series low level fully recessed led
Post on 09-Feb-2022
3 Views
Preview:
TRANSCRIPT
5-1/12
• Low level, fully recessed LED Emergency Light• Vandal resistant design• Paintable/wall paper friendly housing designed
to seamlessly blend with any décor• Puts light on the floor… where it is needed• More effective in illuminating the path of egress
than traditional ceiling or wall-mounted emergency lights
• Uses three high-output white LEDs with just 11 watts of total load
• ADA Compliant and UL Listed to the UL 924 Standard
Low Level LED Emergency Light
LIGHTPATH SERIES
LOW LEVEL FULLY RECESSED LED
50 ft. spacing4ft path of egress
40 ft. spacing6 ft. path of egress
•Photometrics independently tested and compiled by ITL Boulder Testing Laboratories.
•Recommended spacing's based on requirements for meeting the Life Safety Standard minimum illuminance of 0.1 fc and
average illuminance of 1.0 fc. Assumes that the fixtures are wall mounted 18” above the floor in a corridor 4' or 6 wide
with 8' ceiling height and reflectances of 80/50/20.
•Note: Recommended spacing's calculated from laboratory data taken under controlled conditions in accordance with I.E.S.
approved methods. Actual performance results will vary due to field conditions.
•I.E.S. data is available from Isolite.
Recommended maximum Center to Center Spacings
Recommended maximum center-to-center spacings
Recommended spacing based on requirements for meeting the Life Safety Standard minimum illuminance of 0.1 fc andaverage illuminance of 1.0 fc. Assumes that the fixtures are wall mounted 18" above the floor in a corridor 4' or 6' widewith 8' ceiling height and reflectances of 80/50/20.
I.E.S. data is available from Isolite.
Project ______________________________________________
Date ___________________________ Type _________________
Catalog Number ______________________________________
Remarks ____________________________________________
Visit us on the web at www.isolite.com or email sales@isolite.com
Call the Isolite office nearest you.
HeadquaRteRs WesteRn office 31 Waterloo Avenue 3563 Sueldo, Suite MBerwyn, PA 19312 San Luis Obispo, CA 93401800-888-5483 800-799-5343610-647-8200 805-546-9669610-296-8952 Fax 805-546-9564 Fax
isoLite LightPath series Low Level Led emergency Light
specifications
features: · Low level, fully recessed LED Emergency Light designed to be mounted 18” above floor
· Compact and low profile design · Tamper Resistant Design with no shown mounting
hardware · Paintable/wall paper friendly housing designed
to seamlessly blend with any décor. · Puts light on the floor…where it is needed · More effective in illuminating the path of egress
than traditional ceiling or wall mounted emergency lights
· Designed for new construction or retrofit applications. Mounting hardware comes standard for both applications.
· Pre-ship back box for quick installation · Modular assembly and quick connector wiring
allows for easy and fast assembly · Optional infra-red remote transmitter with
selectable 30 second or 90 minute tests · Manual test switch and LED AC indicator lightconstruction: Durable powder coated white 1/8" die-cast
aluminum housing which can be field painted or wall papered
ordering information
dimensions
Example: LTP-CC-TD
series Battery type options
LTP LC = Lead Calcium TD = 15 minute Time Delay NC = NiCad CC = Custom Color LB* = Less Back Box * Select this option when you need to ship back box
in advance of fixture; indicate "LB" option, then order back box "LTPRIS" separately
accessories (order separately)
LTPRIS = Recessed Back Box for LTP (back box ships in advance for rough in)
TLRT = Infra Red Remote Control Tester
Battery: · Option of Lead Calcium or NiCad · 2 Hour run time standardillumination: · 3 High-output white LEDs with just 11 watts
of total load · Up to 50 feet on center spacing over 4-foot path
of egressapprovals: · Listed by UL to the UL 924 standard and
CSA C22-2 No. 141-10 · Meets or exceeds all performance standards as
required by NFPA 101, NFPA 70, NEC and OSHA · Meets preferred emergency egress lighting method
described in the NFPA 101 Life Safety Code Section A.7.8.1.3
· NYC Calendar number pending · Chicago approved · ADA compliant · Buy America Compliant: Qualifies for Buy America
Act, Section 25, paragraph 25.4 as stipulated in the ARRA (American Recovery and Reinvestment Act) section 1605 for Levels 1&2
electronics: · Solid State microprocessor controlled circuitry · Line latch, brown out and battery LVCO standard · Automatic self diagnostic circuit which discretely
monitors lamp load, transfer circuit, battery capacity, door operation and motor drive
· Field-selectable 120 or 277 VAC 60HZ inputWarranty: · 3-year warranty
9.1”
5.2”
2.4” Doorin emergency
position
WallLamphead
ExistingConstructionInstallation
8.0”rough in
SpliceBoxCover
4.1”rough in
3.9”
4.1”
Battery Trayinstalls throughfront opening
DrywallClip
DrywallClip
18”
from
floor
CL
14.5”
2x 1.2”
7.9”3.9”
4.1”
2.8”
.8”
2.0”
New Construction Installation
top related