modbus – slc gateway user manual
Post on 29-May-2022
23 Views
Preview:
TRANSCRIPT
MODBUS – SLC gateway
user manual
Type: GW485LCD4P
Document version: 1.2
GW485LCD4P user manual (ver.: 1.0ß)
SAUTER Magyarország • Sauter Automatikai Kft. • 1148 Budapest, Fogarasi út 2-6. • Tel. +36 (1) 470-1000 • Fax +36 (1) 467-9000
sah@hu.sauter-bc.com • www.sauter.hu
2/33
Introduction
This device has been created because the CASE VAV software could monitor only one VAV
meanwhile this device is able to monitor 128 VAV. The read values could not be used in
building management system. But by this device there is a possibility to integrate the data of
the VAV into the building managing system via the Modbus Protocol.
The unit is powered with 15-32 VDC or 12-24 VAC.
Variable types
The type of the variables is the following:
– USINT: unsigned integer (0-65535)
– INT: integer (-32768 – 32767)
Modbus types
The Modbus type of the signals (types in the list below):
3 = Holding Register (Modbus function = 3 and 6)
4 = Input Register (Modbus function = 4)
Supported Modbus functions:
3 = Read Holding Register
4 = Read Input Register
6 = Write Single Register
Max 20 registers
Max 20 registers can be read in one message.
GW485LCD4P user manual (ver.: 1.0ß)
SAUTER Magyarország • Sauter Automatikai Kft. • 1148 Budapest, Fogarasi út 2-6. • Tel. +36 (1) 470-1000 • Fax +36 (1) 467-9000
sah@hu.sauter-bc.com • www.sauter.hu
3/33
Modbus communication
Modbus address can be 1-127.
Supported baud rate:
– 2400 bps
– 4800 bps
– 9600 bps
– 19200 bps
– 38400 bps
Stop bit: 1
Data bits: 8
Parity: None
Stop bit: 1
GW485LCD4P user manual (ver.: 1.0ß)
SAUTER Magyarország • Sauter Automatikai Kft. • 1148 Budapest, Fogarasi út 2-6. • Tel. +36 (1) 470-1000 • Fax +36 (1) 467-9000
sah@hu.sauter-bc.com • www.sauter.hu
4/33
Input register (Function code 4)
register data type description comment
30001 USINT Modbus address value is from 1 to 127
30002 USINT SLC overrun counter
30003 USINT SLC frame error counter
30004 USINT SLC crc error counter
30005 USINT SLC address error counter
30006 USINT Global no answer counter
30007 USINT Modbus overrun counter
30008 USINT Modbus frame error counter
30009 USINT Modbus crc error counter
30010 USINT VAV1 SLC address value is up to 200, if 0, polling disable
3XXX1 INT VAVXXX Setpoint (%) scale factor 10
3XXX2 INT VAVXXX Actual value (%) scale factor 10
3XXX3 USINT VAVXXX Position (°) scale factor 10
3XXX4 INT VAVXXX Position (%) scale factor 10
3XXX5 INT VAVXXX Differential pressure (%) scale factor 10
3XXX6 INT VAVXXX Second setpoint (%) scale factor 10
3XXX7 INT VAVXXX Second actual value (%) scale factor 10
3XXX8 N/A Not used (read 0xFFFF (65535))
3XXX9 USINT VAVXXX No answer counter
XXX: 1-128 (MAX 128 VAV!)
30002, 30007: The receive FIFO buffer can hold two characters. An overrun error will be
generated if a third character, in its entirety, is received before the FIFO is accessed.
30003, 30008: A framing error indicates that a Stop bit was not seen at the expected time.
30005: The numbers of errors occur when a polled VAV does not answer, but another send
a response message.
30006: Total number of errors, which does not respond to the question. Equal to the sum of
the 6th element of the register arrays.
The input registers are reset to 0 after restart.
GW485LCD4P user manual (ver.: 1.0ß)
SAUTER Magyarország • Sauter Automatikai Kft. • 1148 Budapest, Fogarasi út 2-6. • Tel. +36 (1) 470-1000 • Fax +36 (1) 467-9000
sah@hu.sauter-bc.com • www.sauter.hu
5/33
Holding register (Function code 3)
register data type description comment
40001 USINT Modbus address value is from 1 to 127
40002 USINT Modbus baud rate value is up to 4
40003 USINT Min. polling interval in second value is from 1 to 240
40004 USINT Global polled data kill bits value is up to 127
40005 USINT Display auto shift 0=Off, 1=ON
40006 USINT Display shift period 1-250 cycle (1 cycle = 4 sec + 2 sec with loop2)
40007 USINT Display holding period 1-250 cycle (1 cycle = 4 sec + 2 sec with loop2)
40008 USINT VAV comm. fault response 0=error message, 1= read 0xFFFF (65535)
40009 N/A Not used (read 0xFFFF (65535))
4XXX0 USINT VAVXXX SLC address value is up to 200, if 0, polling is disable
4XXX1 USINT VAV1 second loop read settings 0=Off, 1=Pressure, 2=Temperature
4XXX2 USINT VAVXXX polled data kill bits If 40007 reg. is not 0, this value is ignored.
4XXX3 USINT VAVXXX manual command value is up to 7
4XXX4 USINT VAVXXX manual command value scale factor 10, value is up to 1100 (110.0 %/°)
4XXX5 N/A Not used (read 0xFFFF (65535))
4XXX6 N/A Not used (read 0xFFFF (65535))
4XXX7 N/A Not used (read 0xFFFF (65535))
4XXX8 N/A Not used (read 0xFFFF (65535))
4XXX9 N/A Not used (read 0xFFFF (65535))
XXX: 1-128 (MAX 128 VAV!)
40001: The Modbus address can be between 1 and 127. Default value is 1. 40002: Modbus baud rate might be: 0: 2400 1: 4800 2: 9600 (Default) 3: 19200 4: 38400 40003: Polling interval on SLC bus. Default value is 1 s. 40004: All of polled VAV data type can be disable. Default value is 0 (enable all polling).
– 1. bit: Disable setpoint polling (1) – 2. bit: Disable actual value polling (2) – 3. bit: Disable position in degrees polling (4) – 4. bit: Disable position polling (8) – 5. bit: Disable differential pressure polling (16) – 6. bit: Disable second setpoint polling (32) – 7. bit: Disable second actual value polling (64)
This number is valid for all register arrays. If the value is 0, then you can define for each VAV. For example you must monitor only VAV angle in degrees, then this value is 27 (1+2+8+16).
GW485LCD4P user manual (ver.: 1.0ß)
SAUTER Magyarország • Sauter Automatikai Kft. • 1148 Budapest, Fogarasi út 2-6. • Tel. +36 (1) 470-1000 • Fax +36 (1) 467-9000
sah@hu.sauter-bc.com • www.sauter.hu
6/33
40005: Enable or disable displayed VAV scrolling on LCD display. 40006: Scroll to next VAV after 1-250 cycle. (1 cycle without second loop display is 4 sec
with second loop display is 6 sec) (Default=2) 40007: If you choose a VAV to display with ‘SET’ button, with this value can you set that
you want to see through many cycle. (1 cycle without second loop display is 4 sec with second loop display is 6 sec) (Default=15)
40008: If the VAV device does not send a response message, you will get 0xFFFF hex
(65535 dec) in register 3XXX1-3XXX7 with multiple read function. With single read function (read only 1 register) you can select the Modbus response: 0: exception responses from Modbus (04 hex: slave device failure) (Default) 1: 0xFFFF hex (65535 dec) 4XXX1: VAV SLC address can be 0-200. If the value is 0, this ‘register array’ will be
disabled. 4XXX2: VAV second loop setting. 0: Second loop polling diable 1: Room pressure control loop polling and displaying 2: Room temperature control loop polling and displaying 4XXX3: You can set the VAV in manual operation with this register. 0: Manual operation is disabled (Default) 1: Stop working 2: Damper close 3: Damper open 4: Set the angle to defined position (4XXX9 register’s value with scale factor 10) 5: Set the air flow (setpoint) to defined value (4XXX9 register’s value with scale
factor 10) 6: Vmin 7: Vmax 8: Adapt working angle After restart this value will be reset to 0. 4XXX4: This value is for angle or air flow with scale factor 10. After restart this value will be
reset to 0. XXX = 1-128 The holding registers will be stored in EEPROM memory expects 4XXX8 and 4XXX9 registers.
THIS DEVICE HAS 4 SLC NETWORK! Register arrays (XXX) mapped as fallow: 001-032: SLC network 1 033-064: SLC network 2 065-096: SLC network 3 097-128: SLC network 4
GW485LCD4P user manual (ver.: 1.0ß)
SAUTER Magyarország • Sauter Automatikai Kft. • 1148 Budapest, Fogarasi út 2-6. • Tel. +36 (1) 470-1000 • Fax +36 (1) 467-9000
sah@hu.sauter-bc.com • www.sauter.hu
7/33
Hardware overview
– LED’s functions
POWER: Power indicator LED (green)
TX1: VAV polling indicator (red)
RX1: VAV response indicator LED (green)
STATUS: Gateway status indicator LED (yellow), 1 second flash cycle as follows:
– 1/5 duty cycle: all of assigned VAV sends response
– 2x 1/5 duty cycle: you are in the settings menu
– 4/5 duty cycle: at least one VAV does not send response
TX2: Modbus response indicator LED (red)
RX2: Modbus polling indicator LED (green)
GW485LCD4P user manual (ver.: 1.0ß)
SAUTER Magyarország • Sauter Automatikai Kft. • 1148 Budapest, Fogarasi út 2-6. • Tel. +36 (1) 470-1000 • Fax +36 (1) 467-9000
sah@hu.sauter-bc.com • www.sauter.hu
8/33
– Connection:
This device is a ‘master’ on SLC network. The CASE VAV software is a ‘master’ too. You
can use only one ‘master’ on the VAV network.
GW485LCD4P user manual (ver.: 1.0ß)
SAUTER Magyarország • Sauter Automatikai Kft. • 1148 Budapest, Fogarasi út 2-6. • Tel. +36 (1) 470-1000 • Fax +36 (1) 467-9000
sah@hu.sauter-bc.com • www.sauter.hu
9/33
Display
Normal gateway operation:
– Start screens (after restart):
– If the device has not assigned VAV, you can see the follow:
GW485LCD4P user manual (ver.: 1.0ß)
SAUTER Magyarország • Sauter Automatikai Kft. • 1148 Budapest, Fogarasi út 2-6. • Tel. +36 (1) 470-1000 • Fax +36 (1) 467-9000
sah@hu.sauter-bc.com • www.sauter.hu
10/33
– When the device has assigned VAV, 2 displays changed every 2 seconds:
– You can change the displayed VAV with pushing ‘SET’ button:
– When the VAV is in manual operation, you can see a hand pictogram:
• Manual air flow, Vmin, Vmax:
GW485LCD4P user manual (ver.: 1.0ß)
SAUTER Magyarország • Sauter Automatikai Kft. • 1148 Budapest, Fogarasi út 2-6. • Tel. +36 (1) 470-1000 • Fax +36 (1) 467-9000
sah@hu.sauter-bc.com • www.sauter.hu
11/33
• Manual angle, stop, damper open, damper close:
Settings menu: The device has a settings menu.
– Push the ‘Reset’ button and after restart hold the ‘SET’ button, then you can see the follow:
– Release the ‘SET’ button, then short pressing this button can you change between ‘-YES-’ or ‘-NO-’. If you select ‘-YES-’, after 2 seconds the last releasing of the ‘SET’ button you must enter the password:
Wait until you press the ‘SET’ button.
GW485LCD4P user manual (ver.: 1.0ß)
SAUTER Magyarország • Sauter Automatikai Kft. • 1148 Budapest, Fogarasi út 2-6. • Tel. +36 (1) 470-1000 • Fax +36 (1) 467-9000
sah@hu.sauter-bc.com • www.sauter.hu
12/33
– When you push the button, the first number will be increased
– After 2 seconds the last releasing of the ‘SET’ button you can increase the second number:
THE PASSWORD IS 5555.
– When the password is correct, you can see the settings:
Wait until you press the ‘SET’ button.
– You can select the follow:
GW485LCD4P user manual (ver.: 1.0ß)
SAUTER Magyarország • Sauter Automatikai Kft. • 1148 Budapest, Fogarasi út 2-6. • Tel. +36 (1) 470-1000 • Fax +36 (1) 467-9000
sah@hu.sauter-bc.com • www.sauter.hu
13/33
– SLC settings:
– Scan VAV devices:
If you select the ‘Start’:
GW485LCD4P user manual (ver.: 1.0ß)
SAUTER Magyarország • Sauter Automatikai Kft. • 1148 Budapest, Fogarasi út 2-6. • Tel. +36 (1) 470-1000 • Fax +36 (1) 467-9000
sah@hu.sauter-bc.com • www.sauter.hu
14/33
– Polling interval:
– Set new interval:
Push the ‘SET’ button to increase the value.
After 2 seconds the last releasing of the ‘SET’ button the interval will be stored.
– Modbus settings:
– Modbus address:
GW485LCD4P user manual (ver.: 1.0ß)
SAUTER Magyarország • Sauter Automatikai Kft. • 1148 Budapest, Fogarasi út 2-6. • Tel. +36 (1) 470-1000 • Fax +36 (1) 467-9000
sah@hu.sauter-bc.com • www.sauter.hu
15/33
– Set new address:
Push the ‘SET’ button to increase the value.
After 2 seconds the last releasing of the ‘SET’ button the address will be stored.
– Modbus baud rate:
– Set new baud rate:
Push the ‘SET’ button to increase the value.
After 2 seconds the last releasing of the ‘SET’ button the baud rate will be stored.
GW485LCD4P user manual (ver.: 1.0ß)
SAUTER Magyarország • Sauter Automatikai Kft. • 1148 Budapest, Fogarasi út 2-6. • Tel. +36 (1) 470-1000 • Fax +36 (1) 467-9000
sah@hu.sauter-bc.com • www.sauter.hu
16/33
Use with nPO
Install communication driver:
1. Add new driver.
2. Select Modicon Modbus (VPIWNMR).
1.
2.
GW485LCD4P user manual (ver.: 1.0ß)
SAUTER Magyarország • Sauter Automatikai Kft. • 1148 Budapest, Fogarasi út 2-6. • Tel. +36 (1) 470-1000 • Fax +36 (1) 467-9000
sah@hu.sauter-bc.com • www.sauter.hu
17/33
3. Add name.
4. Edit Init file.
BAUD_RATE = 9600
BUS=M,D
SWAP = NO
FLOATSWAP = NO
LONGADDR = NO
RTSCTS = NO
IFG = 0
IFG_MS = 0
1.
2.
3.
GW485LCD4P user manual (ver.: 1.0ß)
SAUTER Magyarország • Sauter Automatikai Kft. • 1148 Budapest, Fogarasi út 2-6. • Tel. +36 (1) 470-1000 • Fax +36 (1) 467-9000
sah@hu.sauter-bc.com • www.sauter.hu
18/33
5. Select the gateway’s COM port.
6. Only “Finish”.
2.
1.
GW485LCD4P user manual (ver.: 1.0ß)
SAUTER Magyarország • Sauter Automatikai Kft. • 1148 Budapest, Fogarasi út 2-6. • Tel. +36 (1) 470-1000 • Fax +36 (1) 467-9000
sah@hu.sauter-bc.com • www.sauter.hu
19/33
7. You can use the communication driver after restart.
GW485LCD4P user manual (ver.: 1.0ß)
SAUTER Magyarország • Sauter Automatikai Kft. • 1148 Budapest, Fogarasi út 2-6. • Tel. +36 (1) 470-1000 • Fax +36 (1) 467-9000
sah@hu.sauter-bc.com • www.sauter.hu
20/33
Add new data point
The driver address structure:
01 4 001 0
MODBUS address
(1-99)
Function code
(3, or 4)
VAV register array (1-128)
(0 is a diagnostic array)
Array
element
VAV’s data point definition:
– 1st array, VAV SLC address (register array zero element):
This data point is both readable and writable. The value must be between 0 and 200 that
corresponds with the VAV’s SLC address. If the value is set to 0, so this array not will be
uploading.
GW485LCD4P user manual (ver.: 1.0ß)
SAUTER Magyarország • Sauter Automatikai Kft. • 1148 Budapest, Fogarasi út 2-6. • Tel. +36 (1) 470-1000 • Fax +36 (1) 467-9000
sah@hu.sauter-bc.com • www.sauter.hu
21/33
– 1st array, VAV setpoint (register array 1st element):
GW485LCD4P user manual (ver.: 1.0ß)
SAUTER Magyarország • Sauter Automatikai Kft. • 1148 Budapest, Fogarasi út 2-6. • Tel. +36 (1) 470-1000 • Fax +36 (1) 467-9000
sah@hu.sauter-bc.com • www.sauter.hu
22/33
– 1st array, VAV actual value (register array 2nd element):
GW485LCD4P user manual (ver.: 1.0ß)
SAUTER Magyarország • Sauter Automatikai Kft. • 1148 Budapest, Fogarasi út 2-6. • Tel. +36 (1) 470-1000 • Fax +36 (1) 467-9000
sah@hu.sauter-bc.com • www.sauter.hu
23/33
– 1st array, VAV damper position in degrees (register array 3rd element):
GW485LCD4P user manual (ver.: 1.0ß)
SAUTER Magyarország • Sauter Automatikai Kft. • 1148 Budapest, Fogarasi út 2-6. • Tel. +36 (1) 470-1000 • Fax +36 (1) 467-9000
sah@hu.sauter-bc.com • www.sauter.hu
24/33
– 1st array, VAV damper position (register array 4th element):
GW485LCD4P user manual (ver.: 1.0ß)
SAUTER Magyarország • Sauter Automatikai Kft. • 1148 Budapest, Fogarasi út 2-6. • Tel. +36 (1) 470-1000 • Fax +36 (1) 467-9000
sah@hu.sauter-bc.com • www.sauter.hu
25/33
– 1st array, VAV differential pressure (register array 5th element):
GW485LCD4P user manual (ver.: 1.0ß)
SAUTER Magyarország • Sauter Automatikai Kft. • 1148 Budapest, Fogarasi út 2-6. • Tel. +36 (1) 470-1000 • Fax +36 (1) 467-9000
sah@hu.sauter-bc.com • www.sauter.hu
26/33
– 1st array, VAV no response counter (register array 6th element):
GW485LCD4P user manual (ver.: 1.0ß)
SAUTER Magyarország • Sauter Automatikai Kft. • 1148 Budapest, Fogarasi út 2-6. • Tel. +36 (1) 470-1000 • Fax +36 (1) 467-9000
sah@hu.sauter-bc.com • www.sauter.hu
27/33
– 1st array, VAV polled data kill kill byte (register array 7th element):
GW485LCD4P user manual (ver.: 1.0ß)
SAUTER Magyarország • Sauter Automatikai Kft. • 1148 Budapest, Fogarasi út 2-6. • Tel. +36 (1) 470-1000 • Fax +36 (1) 467-9000
sah@hu.sauter-bc.com • www.sauter.hu
28/33
– 1st array, VAV manual command (register array 8th element):
GW485LCD4P user manual (ver.: 1.0ß)
SAUTER Magyarország • Sauter Automatikai Kft. • 1148 Budapest, Fogarasi út 2-6. • Tel. +36 (1) 470-1000 • Fax +36 (1) 467-9000
sah@hu.sauter-bc.com • www.sauter.hu
29/33
– 1st array, VAV manual command’s value (register array 9th element):
GW485LCD4P user manual (ver.: 1.0ß)
SAUTER Magyarország • Sauter Automatikai Kft. • 1148 Budapest, Fogarasi út 2-6. • Tel. +36 (1) 470-1000 • Fax +36 (1) 467-9000
sah@hu.sauter-bc.com • www.sauter.hu
30/33
To add more data point is similar to the former one, except that the number of registers
should be written in an appropriate way.
For example, VAV angle for the register array of 23rd can be added in the following:
GW485LCD4P user manual (ver.: 1.0ß)
SAUTER Magyarország • Sauter Automatikai Kft. • 1148 Budapest, Fogarasi út 2-6. • Tel. +36 (1) 470-1000 • Fax +36 (1) 467-9000
sah@hu.sauter-bc.com • www.sauter.hu
31/33
For example, the data of the VAV register array 1:
Here we can see that the register 1st array of 1 SLC address’s VAV data by uploading from
the converter but it is currently not available, because it does not receive data.
Change the address to 130, which can be found on the network: Right-click on the title above
the data points, and then click “Read / Write to”.
In the window that appears, enter a new address, and then click "Write", then "OK" button.
GW485LCD4P user manual (ver.: 1.0ß)
SAUTER Magyarország • Sauter Automatikai Kft. • 1148 Budapest, Fogarasi út 2-6. • Tel. +36 (1) 470-1000 • Fax +36 (1) 467-9000
sah@hu.sauter-bc.com • www.sauter.hu
32/33
Then the device fills the 130 SLC address’s VAV data to register array 1.