C O N T E N T S
04 Main Unit Feature
06 Rating
08 Selection of Specification
09 Type of Mounting
10 Derating Table
11 Internal Resistance
12 Spring Charging Operation
13 Electrical Tripping Device
14 Accessory
19 ACB Protection Relay
28 Characteristic Curve
30 Outline Dimension
34 Circuit Diagram
36 APR Wiring Diagram
38 Ordering Information
43 ACB Operation Environment
[ Basic Standard ]IEC60947-2 International Electrotechnical Commission
EN 60947-2 European Standard
AS 3972-2 Australian Standard
NEMA PUB NO.SG3 National Electrical Manufactures Association
ANSI C37.13 American National Standard Institute
GOST R 50030.2-99 9 Government Standard of Russia
GOST R 50030.1-2000 Government Standard of Russia
[ Authorization ]KR/KOREA Korean Register of Shipping
GL/GERMANY Germanischer Lloyd
LR/U.K Lloyd’s Register of Shipping
ABS/U.S.A American Bureau of Shipping
BV/FRANCE Bureau Veritas
NK/JAPAN Nippon Kaiji Kyokai
Introduction of the compact and up-graded HiAN Type ACB,
providing the perfect solution of highly reliable,
space-saving and the advanced safe systems.
HiAN Type
Air Circuit Breaker
We build a better future!
HiAN Air Circuit Breaker
High BreakingCapacity
SmallLight Weight
SafetyConvenience
High AbilityDigital APR
H i S e r i e s H i A N A i r C i r c u i t B r e a k e r
Main Unit Feature
0 4 | H i S e r i e s
HiAN type ACB expanded interruption range (up to 85 kA)
with increased short-time withstand current (up to 85 kA)
and short-circuit current (up to 85 kA).
HiAN 630 ~ 1600AF
Long Service LifeThe mechanical endurance of all types are 10,000 cycles.
Zero Arc SpaceNo extra arc space will drastically reduce the height of the
switchboard.
Expanded Selective Interruption Range
490
320
HiAN 2000 ~ 3200AF
410 388
Space Saving DesignHiAN type ACBs have two frame sizes. The height and depth dimensions are identical in all sizes up to 3200AF Draw-out type (up to 1600AF): 490 mm (H)×320 mm (W)×388 mm (D) Draw-out type (From 2000AF up to 3200AF): 490 mm (H)×410 mm (W)×388 mm (D)
The panel cutout size for all ACBs is the same, so it is convenient to standardize the switchboard design.
The fully molded body of the ACBs increases the safety for all application.
HiAN 25~32 85 kA
HiAN 06~20 70 kA
Main Unit Feature
H i A N A i r C i r c u i t B r e a k e r | 0 5
Early make, late break neutral pole contact.The neutral pole contact closes earlier than the main circuit contacts, and opens later.
This effectively prevents the occurrence of the abnormal voltages between the phase lines and the neutral line,
thus ensures safety.
Safety and Convenience Easy access to control circuit Easy maintenance and inspection mechanism All out-going parts are molded Auxiliary contacts (4a+4b standard)
Various AccessoryAll accessory is easy to install and maintain Key interlock system Cycle counter Safety shutter Fixing blocks Door flange Position switchMal-insertion prevention device Arc shield.Mechanical interlock device Automatic transfer switch
➒
➑
➐
➓
➊
➋
➏
➍
➎
➌
Front View Designed for the HiAN ACB
➊ Front cover
➋ Charging handle
➌ Position lock device
➍ Close button
➎ Trip button
➏ Charging indicator
➐ Close and open indicator
➑ Cycle counter
➒ Control circuit
➓ Fault reset button
Digital protection relay
Name plate
Key lock device
Fixing blocks
Ratings for Industrial Plant Applications
Type HiAN 32HiAN 25HiAN 20HiAN 16HiAN 12HiAN 10HiAN 08HiAN 06
HiAN 32HiAN 25HiAN 20HiAN 16HiAN 12HiAN 10HiAN 08630 800 1000 1250 1600 2000 2500 3200
630 800 1000 1250 1600 2000 2500 3200
3, 4 Poles
320 320 320 320 320 2000 2000 2000
630 630 630 630 630 2500 2500
800 800 800 800 3200
1000 1000 1000
1250 1250
1600
AC 1000 V
AC 690 V
50 50 50 50 50 65 65 65
70 70 70 70 70 70 85 85
70 70 70 70 70 85 85 85
50 50 50 50 50 65 65 65
70 70 70 70 70 70 85 85
105 105 105 105 105 143 143 143
154 154 154 154 154 154 187 187
154 154 154 154 154 187 187 187
105 105 105 105 105 143 143 143
154 154 154 154 154 154 187 187
8
65 65 65 65 65 70 85 85
65 65 65 65 65 70 85 85
B
0.03
10
0.04
43 43 43 49 49 60 63 65
65 65 65 72 72 87 92 96
51 51 51 58 58 69 76 83
76 76 76 85 85 100 110 120
490
320 410
461.2
※ - Value is open air at 40- ⊙ : CESI Type Test- : GOST R Certifications- For 2 poles use both opposite ends poles of 3 poles ACBs.
IEC
VDE
BS
AS
IEC
VDE
BS
AS
ClosingOperatingTime
Weight(kg)
1 sec
with Inst.
Icu=100 % lcs
with Inst.
Icu=100 % lcs
without Inst.
(MCR)
without Inst.
(MCR)
Rated Current (A)
Neutral Phase Current (A)
Poles
Rated Primary Current of OCR [ICT] (A)
Rated Insulation Voltage (Ui) (V)
Rated Operation Voltage (Ue) (V)
Rated Breaking Capacity (kA sym) [lcu]
AC 690 V
AC 500 V
AC 415 V below
AC 600 V
AC 500 V below
Rated Making Capacity (kA peak) [lcm]
AC 690 V
AC 500 V
AC 415 V below
AC 600 V
AC 500 V below
Rated Impulse Withstand Voltage. (Uimp) [kV]
Rated Short-time Withstand
Current [lcw] (rms)
Rated Latching Current (kA)
Utilisation Category
Total Breaking Time (sec)
Charging Time (sec) max.
Closing Time (sec) max.
3 Poles, Fixed Type
3 Poles, Draw-out Type
4 Poles, Fixed Type
4 Poles, Draw-out Type
Dimension (mm) H
(3 Poles, Draw-out Type) W
D
H i S e r i e s H i A N A i r C i r c u i t B r e a k e r
Rating
0 6 | H i S e r i e s
⊙ ⊙ ⊙ ⊙ ⊙ ⊙
Ratings for Generator Applications
Type HiAN 32HiAN 25HiAN 20HiAN 16HiAN 12HiAN 08
HiAN 32HiAN 25HiAN 20HiAN 16HiAN 12HiAN 10HiAN 08800 1250 1600 2000 2500 3200
160≤Io≤320 160≤Io≤320 160≤Io≤320 1000≤Io≤2000 1000≤Io≤2000 1000≤Io≤2000
320≤Io≤630 320≤Io≤630 320≤Io≤630 1250≤Io≤2500 1250≤Io≤2500
400≤Io≤800 400≤Io≤800 400≤Io≤800 1600≤Io≤3200
500≤Io≤1000 500≤Io≤1000
630≤Io≤1250 630≤Io≤1250
800≤Io≤1600
AC 1000 V
AC 690 V
70/154 70/154 70/154 70/154 85/187 85/187
70/154 70/154 70/154 70/154 85/187 85/187
70/154 70/154 70/154 70/154 85/187 85/187
70/154 - 70/154 70/154 85/187 85/187
70/154 70/154 70/154 70/154 85/187 85/187
70/154 70/154 70/154 70/154 85/187 85/187
105 105 105 105 105 143
65 65 65 70 85 85
65 65 65 70 85 85
B
0.03
10
0.04
65 72 72 87 92 96
KR
LR
ABS
GL
BV
NK
ClosingOperatingTime
1 sec
Icu=100 % Ics
Amperes Rating (A)
Rated Current of OCR (A)
[Io] is Generator Rated Current
Rated Insulation Voltage (Ui) (V)
Rated Operation Voltage (Ue) (V)
Rated Breaking Capacity (kA, sym) [Icu] / Rated Making Capacity (kA peak) [Icm]
AC 480 V
AC 500 V
AC 480 V
AC 480 V
AC 480 V
AC 480 V
Other Ratings
Rated Short-time Withstand
Current [lcw] (rms)
Rated Latching Current (kA)
Utilisation Category
Total Breaking Time (sec)
Charging Time (sec) max.
Closing Time (sec) max.
Weight (kg) (3 Poles, Draw-out Type)
Rating
H i A N A i r C i r c u i t B r e a k e r | 0 7
A wide choice of specifications to suit your particular application
“HiAN ACB” classified into eight categories.
We are sure that our custom-built specification of “HiAN ACB” will contribute to your system design.
※
Selection of Specification
0 8 | H i S e r i e s
H i S e r i e s H i A N A i r C i r c u i t B r e a k e r
CONNECTED positionBoth the main and control circuitsare connected for normal service.
TEST positionThe main circuit is isolated and thecontrol circuits are connected. Thisposition permits operation testswithout the need for opening theswitchboard panel door.
ISOLATED positionBoth the main and control circuitsare disconnected. The switchboard panel door doesnot need to be opened.
Fixed TypeThis type of ACB has no draw-out cradle and is designed to be directly mounted in the switchboard.
Control Circuit TerminalsControl circuit terminals are front located to allow easy wiring/access.
Connection MethodsMain circuit terminals
Two types of main circuit terminal arrangements are available: vertical terminals, horizontal terminals.
Different types of terminal arrangements can be specified for the line and load sides. Unless otherwise specified by
the user, horizontal terminals are given to all types.
Horizontal terminals
ex) HiAN 12, 16
Vertical terminals
ex) HiAN 12, 16
Type of Mounting
H i A N A i r C i r c u i t B r e a k e r | 0 9
Selection of Specification / Type of Mounting
Draw-out TypeThis type of ACB consists of a breaker body and a draw-out cradle. The breaker body can be moved within or removed
from the draw-out cradle that is fixed in the switchboard. There are four breaker body positions: CONNECTED, TEST,
ISOLATED, and Removed. The switchboard panel door can be kept closed the CONNECTED, TEST, and ISOLATED positions
(“shut-in three positions”)
Derating Table
1 0 | H i S e r i e s
H i S e r i e s H i A N A i r C i r c u i t B r e a k e r
TypeRated
Current(A)
Bus-bar Size(mm3)
Derated Current(max.)(A)
30 40 50 60Remark
HiAN 06
HiAN 08
630
800
HiAN 10 1000
HiAN 12 1250
HiAN 16 1600
HiAN 20 2000
HiAN 25 2500
HiAN 32 3200
1×40×10
1×60×10
1×60×10
1×60×10
2×40×10
2×40×10
2×60×10
2×60×10
2×100×10
3×100×10
4×100×10
630
800
1000
1250
1250
1600
1600
2000
2500
3200
3200
630
800
1000
1250
1250
1600
1600
2000
2500
3200
3200
630
800
1000
1250
1250
1600
1600
2000
2500
3020
3200
630
800
1000
1250
1250
1560
1600
2000
2350
2760
3160
Fixed Type(Horizontal Mounting Bus-bar)
TypeRated
Current(A)
Bus-bar Size(mm3)
Derated Current(max.)(A)
30 40 50 60Remark
HiAN 06
HiAN 08
630
800
HiAN 10 1000
HiAN 12 1250
HiAN 16 1600
HiAN 20 2000
HiAN 25 2500
HiAN 32 3200
1×40×10
1×60×10
1×50×10
1×60×10
1×60×10
2×40×10
2×40×10
2×50×10
2×60×10
2×60×10
2×80×10
2×100×10
2×80×10
2×100×10
3×100×10
4×100×10
630
800
1000
1000
1250
1250
1600
1600
1600
2000
2000
2000
2500
2500
3190
3200
630
800
1000
1000
1250
1250
1480
1600
1600
1980
2000
2000
2430
2500
3010
3120
630
800
1000
1000
1140
1250
1330
1560
1600
1770
2000
2000
2180
2500
2830
2930
630
800
900
990
990
1150
1150
1350
1540
1540
1890
2000
1890
2220
2590
2740
Draw-out Type(Horizontal Mounting Bus-bar)
H i A N A i r C i r c u i t B r e a k e r | 1 1
Derating Table / Internal Resistance
HiAN 06/08/10 HiAN 12/16 HiAN 20 HiAN 25 HiAN 32
Internal Resistance(μΩ)
Draw-out Type
Fixed Type
Draw-out Type
Fixed Type
Draw-out Type
Fixed Type
PowerConsumption (W)
Reactance (mΩ)
66
38
26/42/66
15/24/38
0.12
0.12
48
20
75/123
31/51
0.1/0.085
0.1/0.085
30
16
120
64
0.080
0.080
24
14
150
87.5
0.065
0.065
22
13
225
133
0.055
0.055
Draw-out Type(Vertical Mounting Bus-bar)
RatedCurrent
(A)Type
60504030
1×40×10
1×60×10
1×50×10
1×60×10
1×60×10
2×40×10
2×40×10
2×50×10
2×60×10
2×60×10
2×80×10
2×100×10
2×80×10
2×100×10
3×80×10
2×100×10
3×100×10
4×100×10
630
800
1000
1000
1250
1250
1600
1600
1600
2000
2000
2000
2500
2500
3200
3190
3200
3200
630
800
1000
1000
1250
1250
1600
1600
1600
2000
2000
2000
2500
2500
3150
3010
3200
3200
630
800
1000
1000
1250
1250
1600
1600
1600
2000
2000
2000
2500
2500
2950
2830
3070
3200
630
800
950
1000
1100
1250
1440
1580
1600
1920
2000
2000
2360
2500
2750
2650
2860
3120
HiAN 06 630
800
1000
1250
1600
2000
2500
3200
HiAN 08
HiAN 10
HiAN 12
HiAN 16
HiAN 20
HiAN 25
HiAN 32
RemarkDerated Current(max.)(A)Bus-bar Size
(mm3)
Internal Resistance
Spring Charging Operation
H i S e r i e s H i A N A i r C i r c u i t B r e a k e r
Rating of motor charge type
Rated Voltage (V)
OperatingVoltage (V)
Inrush Current (Peak Value)(A)
Steady-StateCurrent (RMS)(A)
Charging Time (s)
ClosingCurrent (Peak)(A)
AC 220
AC 110
DC 200 ~ 220
DC 125
DC 100 ~ 110
DC 24
~ 246
~ 123
~ 246
~ 140
~ 126
~ 27
187
93.5
170
106
85
20
2.5 (220 V)
3.0 (110 V)
2.5 (220 V)
3.5 (125 V)
3.5 (110 V)
3.0 (24 V)
0.5
1.0
0.5
1.0
1.0
1.0
5
5
5
5
5
5
1.5 (220 V)
3.2 (110 V)
1.5 (220 V)
3.2 (125 V)
3.2 (110 V)
8.0 (24 V)
Motor Charging TypeFor this type of ACB, the closing springs are charged by a
motor. ON/OFF operation of the ACB can be performed
remotely.
The control circuits provide optimum control to the spring
charging and ACB ON/OFF operation.
A manual charging mechanism is also fitted to facilitate
inspection or maintenance work.
Charging the closing springs
A motor is used to charge the closing springs. When the
closing springs are released to close the ACB, they are
automatically charged again by the motor for the next ON
operation.
Closing the ACB
Turning on “remote” ON switch enables the ACB to be
remotely closed.
Opening the ACB
For opening the ACB remotely, specify the shunt trip device
or the undervoltage trip.
Manual Charging TypeFor this type of ACB, the closing springs are charged by the
spring charging handle.
ON/OFF operation of the ACB is performed by ON/OFF
buttons on the ACB.
Charging the closing springs
The closing springs can be charged by spring charging handle.
Closing the ACB
Press “CLOSE” button in the front cover to close ACB.
Opening the ACB
Press “OPEN” button in the front cover to open ACB.
Anti-pumping FunctionEven if the ON switch is kept on, ACB closing operation is
performed only once. To close the ACB again, turn off the
ON switch to charge the closing springs, and then turn on the
ON switch.
If ON and OFF signals are simultaneously given of the ACB,
the ON signal is ignored.
Anti-pumping Circuit
1 2 | H i S e r i e s
Electrical Tripping Device
Spring Charging Operation / Electrical Tripping Device
Rated Input Voltage
Stored Voltage
Rated Current
Rated frequency
Delay time
Standard
Order No. HVFS-T7 HVFS-T9
AC 110 V
DC 145 V
AC 220 V
DC 290 V
DC 2 A
50 / 60 Hz
1.5 sec
IEC 60694
Shunt Trip (SHT)The shunt trip is used to electrically open the breaker from
a remote place(s).
The shunt trip may be used to open the breaker by means
of external protective devices, such as over-current relays
or reverse power relays.
Both shunt trip and undervoltage trip may be fitted in a
single breaker.
Capacitor TripThe capacitor trip is used in conjunction with a shunt trip,
to ensure normal operation of the latter with in 30 seconds
after the control power (AC) is out or in a low voltage
condition.
A combination of capacitor trip and shunt trip work as a
normal AC-rated shunt trip, and may be used to open the
breaker by an external protective device.
Undervoltage Trip (UVT)The undervoltage trip (UVT) automatically opens the Air
Circuit Breaker when control power voltage drops below a
predetermined value.
When the voltage is restored to a value higher then the
pick-up voltage, the Air Circuit Breaker can be closed, The
undervoltage trip consists of a tripping coil and a trip
control device.
Two types of UVT are available: An instantaneous trip, which trip the Air Circuit Breaker
immediately, its circuit voltage drops below a
predetermined value. A time-delay trip, which operates with a time-delay of
500ms, thus providing coordination with the short time-
delay characteristic.
The UVT device is also available for DC applications in
conjunction with a current limiting resister (installed
externally to the breaker)
Shunt Trip Rating
Rating
Type ofUVT
Rated Voltage (V) Pick-up Voltage
Operating Voltage (V)
Drop-out VoltageExciting CoilCurrent (A)
IANS-T(Time-delayType)
IANS-U(Instan-taneous
Type)
480~500430~470360~400200~240100~120
480~500430~470360~400200~240100~120
200~220100~125
367.2~448.8329~402
275.4~336.6153~18776.5~93.5
153~18776.5~93.5
175~336164.5~301140~25284~14042~70
77~14043.8~70
0.15 (480 V)0.15 (450 V)0.15 (380 V)0.15 (220 V)0.15(110 V)
0.1 (200 V)0.1 (100 V)
367.2~448.8329~402
275.4~336.6153~18776.5~93.5
175~336164.5~301140~25284~14042~70
0.15 (480 V)0.15 (450 V)0.15 (380 V)0.15 (220 V)0.15 (110 V)
AC
AC
DC
H i A N A i r C i r c u i t B r e a k e r | 1 3
Accessory
H i S e r i e s H i A N A i r C i r c u i t B r e a k e r
1 4 | H i S e r i e s
Main Circuit Safety ShuttersThe Main circuit safety shutters auto-matically conceal the main circuitcontacts on the draw-out cradle whenthe ACB is drawn out.
The top and bottom shutters operatesimultaneously.
Breaker Fixing BoltsThe breaker fixing bolts hold thebreaker body securely to the draw-outcradle in connected position.
Use them if the ACB is subject tostrong vibration.
Position Padlock The position padlock lever preventsthe breaker body from inadvertentlybeing drawn out.
The position padlock lever in thepulled-out position locks the breakerbody in the CONNECTED, TEST, orISOLATED position.
Padlock is not supplied(shacklediameter 6 mm below).
Arc ShieldAttached to the draw-out cradle, thiscover eliminate the safety clearancerequirement above the breaker.
Test JumperThe test jumper is a plug-in type, andallows ON-OFF tests on all the HiANACBs with the breaker body drawn outfrom the draw-out cradle.
The standard jumper cable is 3.5 m long.
Wrong Inserting Prevention DeviceInterchangeability exists within the HiAN type ACBs.
Because of this feature, there is apossibility for an ACB of a differentspecification being placed into the draw-out cradle.
Using the wrong inserting preventiondevice eliminates such a possibility.
This device is capable of distinguishingnine different breaker bodies.
ON-OFF Cycle CounterThe ON-OFF cycle counter is amechanical 5-digit readout that showsthe number of ON-OFF cycles of theACB.Counter readings serve as a guide formaintenance or inspection.
Accessory
H i A N A i r C i r c u i t B r e a k e r | 1 5
Mechanical InterlockMechanical interlocks for interlocking 2 or 3ACBs in any arrangement is available.
Interlocking is possible between any framesize within the HiAN-ACB range.
Contact HHI for the details of any type with 3ACBs.
For example at vertical type, minimum pitch(575 mm) is possible if the proper insulatingdistance is obtained.
For large pitch, consult with HHI (maximum 1000 mm).
Auxiliary switch ratings
Category
Voltage ResistiveLoad (A)
ResistiveLoad (A) Min. applicable LoadInductive AC: cosØ≧0.3
Load (A) DC: L/R≧0.01Inductive AC: cosØ≧0.6Load (A) DC: L/R≧0.007
For General Service ➊ For Microload ➋
AC 100~250 V
AC 251~500 V
DC 30 V
DC 125~250 V
5
5
1
1
0.1
-
0.1
-
DC5 V 1 mA
0.1
-
0.1
-
5
5
1
1
➊ The chattering of b-contacts due to ON-OFF operation of the ACB lasts for less than 20 ms.➋ Do not supply different voltages to contacts of a switch.
Auxiliary SwitchesThe auxiliary switches operate during theACB ON-OFF operation. Connections to theswitches are made via ring terminals. The auxiliary switches for draw-out typeACBs operate in the all positions. The auxiliary switches are available forgeneral service and for microload. (4a 4b, standard)
Lifting LugLifting lugs are detachable tools that can beused to lift a draw-out cradle.Lifting lugs for body are available as an option.
ON-OFF Button CoverAn ON-OFF button cover prevents inadvertentor unauthorized operation of the ON or OFFbutton.
※
PNL Cut-out
Current Transformer for Neutral Line(Separate Type)When using a 3-pole ACB with the ground faultprotection function to protect a 3-phase, 4-wiresystem against ground fault, it is required toinstall an appropriate current transformer (CT) tothe neutral line of the system.
HHI can provide this neutral line CT as an option. For the 4-pole ACB, a measuring CT instead of theneutral line CT is already built into the neutralphase of the ACB when the ground faultprotection is fitted.
AC220 V, 50/60 Hz
10 W
220 (W)×90 (H)×150 (D) mm
5 kg
Ratings and specifications
Power Supply
Power Consumption
Dimensions
Weight
Door FlangeA door flange can be used as adecoration panel that covers thecutout on the switchboard panel, andprovides IP20 protection.
Door Flange Cutting
APR Checker, Type IANS-HOC5The APR checker allows easy checking of thelong time-delay trip, short time-delay trip,instantaneous trip, and ground fault tripfunctions and the pre-trip alarm function of theAPR in the field.
Connection Diagram for Neutral CT
Accessory
H i S e r i e s H i A N A i r C i r c u i t B r e a k e r
1 6 | H i S e r i e s
Key Lock(Lock-In-Open)An option of key lock is available in lock-in-open type that locks the ACB in theopen position. When this option is installed on a ACB, operators cannot operate theACB without matched key.
Key Interlock(Lock-In-Open)key interlock is a system of interlocking between ACBs, fitted with a key lock oflock-in-open type.
The key must be inserted to release the lock before closing ACB.The key can be removed when the ACB is opened and locked
After utilizing the lock-in-open type key lock, limited keys as default provides aneffective and reliable interlock system.Using the same keys also allows interlocking between an ACB and other devices(such as a switchboard door).A cylinder-type lock is supplied to ACB. (with angular movement 90°£ clockwise to trap key).
Example: Interlock for prevention of parallel feeding from two lines
ACB 3 cannot be closed ACB 2 cannot be closed ACB 1 cannot be closed
Accessory
H i A N A i r C i r c u i t B r e a k e r | 1 7
Accessory
H i S e r i e s H i A N A i r C i r c u i t B r e a k e r
1 8 | H i S e r i e s
Position switch, Operating sequence
Load Resistive Lamp Inductive Motor
AC 250 V
DC 30 V
DC 125 V
DC 250 V
10 A
6 A
0.6 A
0.30 A
1.5 A
3 A
0.1 A
0.05 A
6 A
6 A
0.6 A
0.30 A
2 A
3 A
0.1 A
0.05 A
The following table lists the available types of the switches.(1) CONNECTED position, indicator switches (2 max)(2) TEST position, indicator switches (2 max)(3) CONNECTED and TEST position, indicator switches (2 max)(4) ISOLATED position, indicator switches (2 max)(5) INSERTED position, indicator switches (2 max)(6) ISOLATED and INSERTED position, indicator switches (1 max, each)
Position SwitchesThe position switches operate to give indication of breaker positions: CONNECTED, TEST, ISOLATED. There are two contact arrangements: 2cConnections to the switches are made via screw terminals.
Short Circuit b ContactWhen the ACB is in the test position or further out positions, the Short Circuit b Contact makes [b] signalwith regardless the ACB status; Close or Open.The Short Circuit b Contact output [a] signal when the breaker is in the connected position only.This contact is to prevent wrong operation in test position in the case of the interlock with another ACB inthe system.
ACB Protection Relay
Accessory / ACB Protection Relay
H i A N A i r C i r c u i t B r e a k e r | 1 9
Step3
Determine the base current (lo) which is the reference
current for the AL, AS, AI and AP pick-up current settings.
Select one of the four base current values (lo)=(ICT)×0.5 or
0.63 or 0.8 or 1.0
Step4
Determine the long time-delay trip (AL), short time-delay
trip (AS), instantaneous trip (AI), Pre-trip alarm (AP) and
ground fault trip (AG) characteristics.
NOTE: The ground fault trip function is not available when the ratedprimary current (ICT) of the OCR is 160.
Step3Determine the long time-delay trip (AL), short time-delay trip(AS), instantaneous trip (AI), and pre-trip (AP) characteristics.
Determine the protective characteristics appropriate for your application
Type APR multi-protective device, the base current (lo) serves as the base to determine the long time-delay trip, short time-delay
trip, instantaneous trip and pre-trip alarm characteristics. The following steps show how to determine the optimum base current
(lo) that will provide the most appropriate characteristic to suit your application.
320, 630320, 630, 800320, 630, 800, 1000320, 630, 800, 1000, 1250320, 630, 800, 1000, 1250, 160020002000, 25002000, 2500, 3200
※ The rated secondary current of all current transformers (CT) is 0.2 A.
160 ≦ [lo] ≦ 800160 ≦ [lo] ≦ 1250160 ≦ [lo] ≦ 1600
1000 ≦ [lo] ≦ 20001000 ≦ [lo] ≦ 25001000 ≦ [lo] ≦ 3200
Step1
Determine the largest normal
load current (ILOAD) that will pass
through the Air Circuit Breaker.
Step2
Select the rated primary current
(ICT) of the multi-protective
device. The table below lists the
values of (ICT) available for the
respective breaker types.
Select (ICT) according to the
following criteria (ICT)≥(ILOAD)
Step1
Determine the rated generator
current (lGEN)
Step2
Determine the base current (lo)
which is the reference current
for the AL, AS, AI, AP pick-up
current settings of the multi-
protective device.
For General Feeder Circuits For Generator Protection
HiAN 06HiAN 08HiAN 10HiAN 12HiAN 16HiAN 20HiAN 25HiAN 32
Rated Primary Current (lCT) in (A) of OCRBreaker
HiAN 08HiAN 12HiAN 16HiAN 20HiAN 25HiAN 32
Breaker Rated Current (lo) in (A)
Type APR Multi-protective DeviceThis device is a high-reliability, multi-function protection relay, utilizing a 8-bit microprocessor.
In addition to three over-current protective functions, (long time-delay, short time-delay and instantaneous),
a pre-trip alarm and / or ground fault protective function can also be incorporated within one device.
Indication for long time-delay trip and pick-up, via the LED and terminals for field checking (APR checker
required), are included in the device.
Furthermore, two additional operation indication functions can be included.
By using these functions, simplified checking becomes possible.
APR Characteristics
Application Type Protective Function Indicating Function Optional Function
General Feeder
Generator
APR-1L-AL
APR-1L-AS
APR-1L-AM
APR-1L-GL
APR-1L-GS
APR-1L-GM
APR-2L-GS
APR-1D-GM
APR-1S-AL
APR-1S-AS
APR-2S-AS
AL
AL
AL
AL
AL
AL
AL
AL
AL
AL
AL
AS
AS
AS
AS
AS
AS
AS
AS
AS
AS
AS
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AP
AP
AP
AP
AP
AP
AP
AP
AG
AG
AG
AG
AG
MCR
MCR
MCR
MCR
MCR
MCR
MCR
NP
NP
NP
NP
NP
IU
IU
IU
IUt 2)
IUt 2)
CP/I 1)
CP/I 3)
CP/I 3)
CP/I 4)
CP/I 1)
CP/I 1)
LED 5)
LED 5)
LED 5)
LED 5)
LED 6)
LED 6)
LED
LED 6)
LCD
LCD
LCD
FT
FT
FT
FT
FT
FT
FT
FT
CV
CV
CV
CV
CV
CV
CV
CV
CV
AMS
AL Adjustable Long Time Delay Trip
AS Adjustable Short Time Delay Trip
AI Adjustable Instantaneous Trip
AP Adjustable Pre-trip Alarm
AG Adjustable Ground Fault Trip
MCR Making Current Release Function
NP Neutral Phase Protection Function
IU Integrated Indicating Operation LED & Contact1a contact makes the signal during 40 ms when aprotective function operates.Insulation level from earth is 1500 V.
IUt Integrated Indicating Operation LED & Contact2a contacts make the signal until the RESET button ispushed when protective function operates.Insulation level from earth is 1500 V.
CP/I Individual Indicationg Operation Contact2a contacts make the signal until the RESET button ispushed which protective function operates.Insulation level from earth is 1500 V.
LED Individual Indicating Operation LED.Each LED indicates until the RESET button is pushedwhich protective function operates.
1) 1a for AL, AS & AI / 1a for AP2) 2a for AL, AS, AI & AG3) 1a for AL, AS & AI / 1a for AP / 1a for AG
4)1a for AL, AS, AI & AG / 1a for AP5) The abonormal CPU status is indicated6) The operating function is indicated on the LCD.
※
Protective Function Indicating Function
ACB Protection Relay
H i S e r i e s H i A N A i r C i r c u i t B r e a k e r
2 0 | H i S e r i e s
AMS Network Diagram
LCD Displaying the Protective Function and the Additional Function
FT Field Test Function
CV External Control Voltage is required
AMS APR Monitoring System
Pre-trip Alarm (AP)When the current reached the settingvalue, this function operates. If thecurrent drops below the pick-upcurrent [IP], the function resetsautomatically.
Neutral Phase Protection (NP)This function protects the neutralconductor from the damage due to alarge current. The current and timesetting is the same as LTD.
APR Monitoring System (AMS)APR-1D-GM has the RS-485communication port, which can beapplied to the APR MonitoringSystem. Throught the interface unit,the ACB can be directly operated, andthe power and the load condition canbe supervised and monitored.
Making Current Release (MRC)The instantaneous trip function is thedefault, and the MCR function can beactive by switching the INST/MCRknob.This MRC function trips the ACB, ifthe current exceeds the pick-upcurrent setting only during the closingoperation. After the ACB completesthe closing, this function getsdisabled.
Field Test (FT)AL, AS and AL function can be testedby the APR itself.If detailed field test is required, theAPR Checker is available for all APRs.
RS-485
APR 1 APR 2 APR 3 APR 4 APR 5 APR N
AMS Server
TCP/IP (Ethernet)
HiCM360/860
Precise Protection CoordinationNon Position for Pick-up Current
The pick-up current setting dials for the long time-delay,
short time-delay, instantaneous trip and ground fault trip
functions have a NON position to make the associated
function inoperative, there by permitting a quick change or
selection of the required functions.
Fail-safe Function for System Security
In the event of a fault current exceeding ten times the
setting of the base current (lo) (five times for generator
protection) while the AL, AS and AI functions are set to the
NON position, the circuit breaker
“Fail-Safe” function will interrupt the fault current in a time
equal to the short-time delay setting (T2)
Optional Function
ACB Protection Relay
H i A N A i r C i r c u i t B r e a k e r | 2 1
ACB Protection Relay
H i S e r i e s H i A N A i r C i r c u i t B r e a k e r
2 2 | H i S e r i e s
I1 : LTD cur.
I2 : STD cur.
I3 : INST cur.
IG : INST cur.
T1 : GFT TIME
T2 : STD TIME
TG : GFT TIME
Characteristic
APR-1L-AL / APR-1L-GL
Type
Protectionfunction
LTD
Base Current (l0) ICT×0.5, 0.63, 0.8, 1.0
±15%
±15%
±20%
±7.5%
±15%
at I1×600% (0.5-1.25-2.5-5-10-15-20-25-30 sec)
I0×(Non-2-2.5-3-4-6-8-10)
80-160-240-320-400-480-560 msec I2t ON/OFF
I0×(Non-4-6-8-10-12-14-16 8 steps)
ICT×(Non-0.1-0.15-0.2-0.25-0.3-0.35-0.4)
80-160-240-320-400-480-560 msec
LTD, STD, INST (1a during 40 ms ON)
LTD Pick-up LED
-
I0×(Non-0.8-0.85-0.9-0.95-1.0-1.05-1.1 8 steps)
I1×1.05 Non Trip, I1×1.2 TripCurrent (l1)
Time (T1)
Current (l2)
Time (T2)
Current (l3)
Contact
LED
Control Voltage
STD
INST
GFT 1)Current (lG)
Time (TG)
FaultIndication
Additionalfunction
APR-1L-AL1) / APR-1L-GL Tolerance
※ 1) APR-1L-AL does not have the GFT function.
ACB Protection Relay
H i A N A i r C i r c u i t B r e a k e r | 2 3
I1 : LTD cur.I2 : STD cur.I3 : INST cur.
IG : GFT cur.Ip : PTA cur.T1 : LTD TIME
T2 : STD TIMETG : GFT TIMETp : PTA TIME
Characteristic
APR-1L-AS / APR-1L-AM / APR-1L-GS / APR-1L-GM
※ 1) APR-1L-AS and APR-1L-AM do not have the GFT function.
ACB Protection Relay
H i S e r i e s H i A N A i r C i r c u i t B r e a k e r
2 4 | H i S e r i e s
※ 1) APR-2S-AS does not have GFT function.2) LCD displays the current when it becomes 20% over than the rated current.
I1 : LTD cur.I2 : STD cur.I3 : INST cur.
IG : GFT cur.Ip : PTA cur.T1 : LTD TIME
T2 : STD TIMETG : GFT TIMETp : PTA TIME
APR-2L-GS / APR-2S-AS
Type
Protectionfunction
LTD
Base Current (l0) ICT×0.5, 0.63, 0.8, 1.0
±15%
±2%
±15%
±20%±7.5%±15%±20%
at I1×600% (0.5-1.25-2.5-5-10-15-20-25-30 sec)I0×(Non-2-2.5-3-4-6-8-10)80-160-240-320-400-480-560 msec I2t ON/OFFI0×(Non-4-6-8-10-12-14-16 8 steps) INST/MCR ON/OFFI0×(0.75-0.8-0.85-0.9-0.95-1.0-1.05-1.1)60-80-100-120-140-160-180-200 secICT×(Non-0.1-0.15-0.2-0.25-0.3-0.35-0.4)80-160-240-320-400-480-560 msec
LTD, STD, INST, PTA, GFT, System Alarm LEDAC/DC 100~250 VLTD, STD, INST TestR, S, T, N phase current2)
LTD, STD, INST (1a)PTA (1a)GFT (1a)
I0×(Non-0.8-0.85-0.9-0.95-1.0-1.05-1.1 8 steps)I1×1.05 Non Trip, I1×1.2 TripTime (T1)
Current (l2)Time (T2)
Current (l3)Current (lP)Time (TP)
Current (lG)Time (TG)
Contact
LEDControl Voltage
Field TestMonitoring
STD
INST
PTA
GFT1)
FaultIndicationAdditional
function
APR-2L-GS / APR-2S-AS1) Tolerance
Characteristic
ACB Protection Relay
H i A N A i r C i r c u i t B r e a k e r | 2 5
APR-1D-GM
I1 : LTD cur.I2 : STD cur.I3 : INST cur.
IG : GFT cur.Ip : PTA cur.T1 : LTD TIME
T2 : STD TIMETG : GFT TIMETp : PTA TIME
Characteristic
ACB Protection Relay
H i S e r i e s H i A N A i r C i r c u i t B r e a k e r
2 6 | H i S e r i e s
I1 : LTD cur.
I2 : STD cur.
I3 : INST cur.
T1 : LTD TIME
T2 : STD TIME
Characteristic
APR-1S-AL
Type
Protectionfunction
LTD
Base Current (l0) ICT×(0.5-1.0) 1% unit
±5%
±15%
±20%
at I1×120% (15-20-25-30-40-50-60 sec)
I0×(Non-2-2.5-2.7-3-3.5-4-4.5-5)
80-160-240-320-400-480-560 msec I2t ON/OFF
I0×(4-6-8-10-12-14-16-Non 8 steps) INST/MCR ON/OFF
LTD, STD, INST (1a during 40 ms ON)
LTD Pick-up LED
-
I0×(Non-0.8-0.9-1.0-1.05-1.1-1.15-1.2-1.25)
I1×1.05 Non Trip, I1×1.2 TripCurrent (l1)
Time (T1)
Current (l2)
Time (T2)
Current (l3)
Contact
LED
Control Voltage
STD
INST
FaultIndication
Additionalfunction
APR-1S-AL Tolerance
ACB Protection Relay
H i A N A i r C i r c u i t B r e a k e r | 2 7
APR-1S-AS
I1 : LTD cur.
I2 : STD cur.
I3 : INST cur.
Ip : PTA cur.
T1 : LTD TIME
T2 : STD TIME
Tp : PTA TIME
Characteristic
Type
Protectionfunction
LTD
Base Current (l0) ICT×(0.5-1.0) 1% unit
±5%
±10%
±20%
±5%
±15%
at I1×120% (15-20-25-30-40-50-60 sec)
I0×(Non-2-2.5-2.7-3-3.5-4-4.5-5)
80-160-240-320-400-480-560 msec I2t ON/OFF
I0×(4-6-8-10-12-14-16-Non 8 steps) INST/MCR ON/OFF
I0×(0.75-0.8-0.85-0.9-0.95-1.0-1.05-1.1)
at IP×120% (5-10-15-20-25-30-35-40-45 sec)
LTD, STD, INST (1a) / PTA (1a)
LTD, STD, INST, PTA, System Alarm LED
AC / DC 100~250 V
LTD, STD, INST Test
I0×(Non-0.8-1.0-1.05-1.1-1.15-1.2-1.25)
I1×1.05 Non Trip, I1×1.2 TripCurrent (l1)
Time (T1)
Current (l2)
Time (T2)
Current (l3)
Current (lp)
Time (Tp)
Contact
LED
Control Voltage
STD
INST
PTA
FaultIndication
Field Test
Additionalfunction
APR-1S-AS Tolerance
➊ GFT current setting range(10~40%)➋ LTD current setting range(80~110%)
➌ PTA current setting range(75~110%)➍ STD current setting range(200~1000%)
➎ INST current setting range(400~1600%)
General Feeder
Characteristic Curve
H i S e r i e s H i A N A i r C i r c u i t B r e a k e r
2 8 | H i S e r i e s
➊ LTD current setting range(80~125%)➋ PTA current setting range(75~110%)
➌ STD current setting range(200~500%)➍ INST current setting range(400~1600%)
Generator
Characteristic Curve
H i A N A i r C i r c u i t B r e a k e r | 2 9
Outline Dimension
H i S e r i e s H i A N A i r C i r c u i t B r e a k e r
3 0 | H i S e r i e s
Draw-out Type
Panel Cut-out
Fixed Type
Panel Cut-out
P : Front PNL Center LineC
Horizontal Bus-bar Type (Standard)
270
4-R5
28433
.5
12-Ø
4
334
CONTROL CIRCUIT TERMINALS
(FOR MARINE)
FIXING BLOCKS
48 504947373112 32 3433 3635 38 4643 4439 4140 42 4531213 11 10 9 8 4719 18 16 1521262829 27 24 23 2225 20 1430
X
40.5
320
100100 100
5.5
2-Ø
12
PC
PC
T
V W
FH
J
IG
N
K
115
115
115
Y
383.
2
45
4-R5
284
33.5
12-Ø
4
334
48 504947373112 32 3433 3635 38 4643 4439 4140 42 4531213 11 10 9 8 4719 18 16 1521262829 27 24 23 2225 20 14
CONTROL CIRCUIT TERMINALS
(SCREWLESS TYPE)
30
25150
T10
016
5.5
71
98.8
320
100100 100
5.5
456.
4
L
270
ON
40.9 134
353.5
CP
M
(3P)
PC
T
115
115
115
N
Outline Dimension
H i A N A i r C i r c u i t B r e a k e r | 3 1
60
60
80
100
100
HiAN 06~
HiAN 10
HiAN 12~
HiAN 16
HiAN 20
HiAN 25
HiAN 32
Dimension(mm)
Type A
Draw-out Fixed Draw-out Fixed Draw-out Fixed
B CD E F G H I J K L M N O T V W X Y
60
60
80
80
80
30
30
50
60
60
30
30
50
50
50
15
15
15
20
20
15
15
15
15
15
12.5
12.5
12.5
12.5
12.5
90
90
120
120
120
105
105
150
150
150
105
105
150
150
150
160
160
205
205
205
160
160
205
205
205
167.3
167.3
212.3
212.3
212.3
167.3
167.3
209.3
209.3
209.3
154.3
154.3
199.3
199.3
199.3
154.3
154.3
199.3
199.3
199.3
168.5
168.5
213.5
213.5
213.5
168.5
168.5
213.5
213.5
213.5
8
15
15
22
30
204
204
249
249
249
204
204
249
249
249
216
216
261
261
261
216
216
261
261
261
3 Pole
60
60
80
100
100
Dimension(mm)
Type A
Draw-out Fixed Draw-out Fixed Draw-out Fixed
B CD E F G H I J K L M N O T V W X Y
60
60
80
80
80
30
30
50
60
60
30
30
50
50
50
15
15
15
20
20
15
15
15
15
15
12.5
12.5
12.5
12.5
12.5
90
90
120
120
120
105
105
150
150
150
195
195
270
270
270
160
160
205
205
205
250
250
325
325
325
167.3
167.3
212.3
212.3
212.3
257.3
257.3
332.3
332.3
332.3
154.3
154.3
199.3
199.3
199.3
244.3
244.3
319.3
319.3
319.3
168.5
168.5
213.5
213.5
213.5
258.5
258.5
333.5
333.5
333.5
8
15
15
22
30
204
204
249
249
249
294
294
369
369
369
216
216
261
261
261
306
306
381
381
381
4 Pole
HiAN 06~
HiAN 10
HiAN 12~
HiAN 16
HiAN 20
HiAN 25
HiAN 32
EEE
293.6
490
ISOLATED
TEST
CONNECTED
48 504947373112 32 3433 3635 38 4643 4439 4140 42 4531213 11 10 9 8 4719 18 16 1521262829 27 24 23 2225 20 1430
AA
312.
2
216
EARTH TERMINAL MOUNT’G
70.5
4-Ø14 HOLEs
C
2-ØD
B
C
2-ØD
B
1515
T 10
0
30
15
29.9
25050
358
45
73.3
164
420
N
Outline Dimension
H i S e r i e s H i A N A i r C i r c u i t B r e a k e r
3 2 | H i S e r i e s
Draw-out Type
Panel Cut-out
P : Front PNL Center LineC
Vertical Bus-bar Type (Only for Draw-out Type)
270
4-R5
28433
.5
12-Ø
4
334
CONTROL CIRCUIT TERMINALS
FIXING BLOCKS
X
40.5
320
100100 100
5.5
2-Ø
12
CP
CP
V W
FH
J
GI
K
115
115
115
Y
383.
2
(FOR MARINE) PC
7559 69
18.9
Z
aa
b
a
286.
5
mmm
mmm
d
h
i
g
f
c’
j-Ø12.5 j-Ø
12.5
j-Ø12.5
15515
15
5 5e
100
for HiAN20for HiAN06~HiAN16 for HiAN25~HiAN32
Outline Dimension
H i A N A i r C i r c u i t B r e a k e r | 3 3
3 Pole
4 Pole
HiAN 20
HiAN 25
HiAN 32
Dimension(mm)
TypeF G H I J K V W X a b c、 d e f g h i j m n r
105
105
150
150
150
105
105
150
150
150
160
160
205
205
205
160
160
205
205
205
167.3
167.3
212.3
212.3
212.3
167.3
167.3
212.3
212.3
212.3
204
204
249
249
249
204
204
249
249
249
216
216
261
261
261
90
90
120
120
120
60
60
80
100
100
160.75
157.25
157.25
153.75
149.75
8
15
15
22
30
130.75
127.25
117.25
103.75
99.75
60
60
80
100
100
108
115
115
122
130
8
15
15
22
30
30
30
40
20
20
12
12
18
18
18
30
30
50
60
60
92.2
92.2
102.2
108.3
108.3
33.5
33.5
33.5
33
38
Y Z
216
216
261
261
261
277.8
277.8
367.8
367.8
367.8
HiAN 20
HiAN 25
HiAN 32
Dimension(mm)
TypeF G H I J K V W X a b c、 d e f g h i j m n r
105
105
150
150
150
195
195
270
270
270
160
160
205
205
205
250
250
325
325
325
167.3
167.3
212.3
212.3
212.3
257.3
257.3
332.3
332.3
332.3
204
204
249
249
249
294
294
369
369
369
216
216
261
261
261
90
90
120
120
120
60
60
80
100
100
160.75
157.25
157.25
153.75
149.75
8
15
15
22
30
130.75
127.25
117.25
103.75
99.75
60
60
80
100
100
108
115
115
122
130
8
15
15
22
30
30
30
40
20
20
16
16
24
24
24
30
30
50
60
60
92.2
92.2
102.2
108.3
108.3
33.5
33.5
33.5
33
38
Y Z
306
306
381
381
381
277.8
277.8
367.8
367.8
367.8
HiAN 06~
HiAN 10
HiAN 12~
HiAN 16
HiAN 06~
HiAN 10
HiAN 12~
HiAN 16
n
r
293.6
490
64
312.
2
216
EARTH TERMINAL MOUNT’G
70.5
4-Ø14 HOLEs
30
15
29.9
25050
358
420
ISOLATED
TEST
CONNECTED
Circuit Diagram
H i S e r i e s H i A N A i r C i r c u i t B r e a k e r
3 4 | H i S e r i e s
Draw-out Type
Over-Current Protective Device
Main CircuitCT: Current Transformer for APR
19 20
22 24 AP
25 26 AL AS AI
27
MHT
28 AG
Control Power Terminal (CP/I)
Under Voltage Trip (UVT)
11 12 Control Power Terminal
T1 T2 Remote Trip Terminal
Motor Charging/Closing Circuits
1 2 Charging Power Terminal
Condenser Trip
Auxiliary Switch
31~46 Auxiliary Contact
Position Switch
3 4 Closing Power Terminal
Indication Terminal
Indication Terminal
Indication Terminal
Magnetic Hold Trigger
M Charging motor
Shunt Trip (SHT)
7 8 Control Power Terminal
U V Control Power Terminal
P N Remote Trip Terminal
TEST position61-62 ON61-63 OFF64-65 ON64-66 OFF
CONNECTED position71-72 ON71-73 OFF74-75 ON74-76 OFF
INSERTED position84-85 ON84-86 OFF
ISOLATED position81-82 ON81-83 OFF
SHT Shunt trip coil
LRC Latch release coil
UVT Under voltage trip coil
*1 : Attach at rated voltage DC 125 V *2 : Option(MCR)
R1 Resistance
Circuit Diagram
H i A N A i r C i r c u i t B r e a k e r | 3 5
Control Circuit Lay-out APR-1S-AS Circuit
Draw-out Type
Fixed Type
Manufacturer wiring part User wiring part Disconnecting device
APR Wiring Diagram
H i S e r i e s H i A N A i r C i r c u i t B r e a k e r
3 6 | H i S e r i e s
3 Pole 4 Pole
APR - 1L - ALAPR -1S - AL
APR - 1L - AS
APR - 1L - AM
APR - 1L - GL
APR Wiring Diagram
H i A N A i r C i r c u i t B r e a k e r | 3 7
3 Pole 4 Pole
APR - 1L - GSAPR -2L - GS
APR - 1L - GM
APR - 1D - GM
APR - 1S - ASAPR - 2S - AS
Ordering Information
H i S e r i e s H i A N A i r C i r c u i t B r e a k e r
3 8 | H i S e r i e s
HiAN type ACBs have an extensive range of available accessories, enabling the circuit breaker to be custom-built to suit everyapplication. When ordering HiAN ACBs, please give us a complete order No. nomenclature as shown in following tables.
Order No. nomenclature
The 6th Order No. Suffix (Other accessories)
The 5th Order No. Suffix (Rating of CT)
The 4th Order No. Suffix (Kind of trip release)
The 3th Order No. Suffix (Over-current release)
The 2th Order No. Suffix (Charging mechanism)
The 1th Order No. Suffix (Breaker poles and mounting method)
The Basic Order No. (Breaker type)
NO.
Frame
IAN06 IAN08 IAN10 IAN12 IAN16 IAN20 IAN25 IAN32
630 A 800 A 1000 A 1250 A 1600 A 2000 A 2500 A 3200 A
PolesMounting
3 Poles
4 Poles
Fixed Type Draw-out Type Remark
3F
4F
3D
4D
NO.
H0
M1
M2
Description Description
Manual Charge
Motor Charge/AC110 V
Motor Charge/AC220 V
Motor Charge/DC110 V
Motor Charge/DC220 V
Motor Charge/DC24 V
NO.
General Protection Generator Protection
00
20
21
22
23
24
27
25
26
Function APR Type NO. Function APR Type
Without APR
AL-AS-AI, IU
AL-AS-AI-AP-MCR-NP, CP/ I
AL-AS-AI-AP-MCR-NP, IUt
AL-AS-AI-AG, IU
AL-AS-AI-AP-AG-MCR-NP, CP/ I
AL-AS-AI-AP-AG-MCR-NP, IUt
AL-AS-AI-AP-AG-MCR-NP, CP/ I
AL-AS-AI-AP-AG, CP/ I
-
APR-1L-AL
APR-1L-AS
APR-1L-AM
APR-1L-GL
APR-1L-GS
APR-1L-GM
APR-2L-GS
APR-1D-GM
The basic order NO. (Breaker frame)
The 1st order NO. (Poles and mounting method)
The 2nd order NO. (Charging mechanism description)
The 3rd order NO. (ACB protection relay)
M5
M6
M7
NO. DescriptionMotor Charge/DC48 V
Motor Charge/DC125 V
M8
M9
NO.
00
28
29
30
Without APR
AL-AS-AI, IU
AL-AS-AI-AP-MCR, CP/ I
AL-AS-AI-AP-MCR
-
APR-1S-AL
APR-1S-AS
APR-2S-AS
Ordering Information
H i A N A i r C i r c u i t B r e a k e r | 3 9
NO.
X5
X6
W1
W2
W3
W4
W5
W6
C1
C2
Description NO. Description Description Description
UVT(Delay)/AC430~470 V
UVT(Delay)/AC480~500 V
UVT(INST)/AC100 V
UVT(INST)/AC220 V
UVT(INST)/AC380 V
UVT(INST)/AC440 V
UVT(INST)/DC100 V
UVT(INST)/DC200 V
S1+T1
S2+T2
S3+T3
T4
T5
U1
U2
U3
U4
U5
U6
D1
D2
D3
NO. NO.
D4
I1
I2
I3
I4
I5
I6
X1
X2
X3
X4
V
T
H
J
320 A
630 A
800 A
1000 A
IAN06~IAN16
IAN06~IAN16
IAN08~IAN16
IAN10~IAN16
The 4th order NO. (Kind of trip release)
The 5th order NO. (Rated primary current of CT)
S1
S2
S3
S4
S5
S6
S7
S8
T1
T2
T3
SHUNT/AC100~150 V
SHUNT/AC180~250 V
SHUNT/AC380~420 V
SHUNT/AC421~480 V
SHUNT/DC90~125 V
SHUNT/DC150~230 V
SHUNT/DC24 V
SHUNT/DC48 V
UVT(Delay)/AC100~120 V
UVT(Delay)/AC200~240 V
UVT(Delay)/AC360~400 V
K
L
M
N
P
Zero
1250 A
1600 A
2000 A
2500 A
3200 A
None (Over current release ordering NO. “00”)
IAN12~IAN16
IAN16
IAN20~IAN32
IAN25~IAN32
IAN32
NO. Description Type NO. NO.Description DescriptionType Type
The 6th order NO. (Other accessories)
NO.
B
D
E
F
G
H
J
K
L
M
N
Q
R
S
T
U
V
W
X
Z
1
2
3
4
7
8
Acc’y Name NO. NO.Acc’y Name Acc’y Name
Key Lock (Lock In Open)
Cycle Counter
Safety Shutter
Fixing Block
Door Flange
Vertical Type Mount’g Bus-bar
Test Jumper
Short Circuit b Contact
Lifting Lugs & Hooks
Button Cover & Button Key
Neutral CT
Position Switch (Conn: 1C, Test: 1C)
Position Switch (Conn: 2C)
Position Switch (Test: 2C)
Position Switch(Inserted: 1C, Isolated: 1C)
Position Switch(Inserted: 2C)
Position Switch(Isolated: 2C)
Wrong Insert’n Prevent’n Device
Arc Shield
APR Checker
Mechanical Interlock (Hori. 2ST)
Mechanical Interlock (Hori. 3ST)
Mechanical Interlock (Vert. 2ST)
Mechanical Interlock (Vert. 3ST)
ATS(Automatic Transfer Switch)
MCR (Making Current Release)
When ordering more than one kind of accessory, please list order NO. according to the order of alphabet and Arabia numbers.
S4+T4
S1+U1
S2+U2
S3+U3
S4+U4
S5+U5
S6+U6
S5+T3
S1+T3
S7+T4
S7+T2
S6+T2
S6+T3
S1+T2
S1+T4
S2+T4
S5+T1
S5+T2
S5+T4
CTD/AC110 V
CTD/AC220 V
Specification Order Number
Setting values of over-current release
Other Accessories:Key lock in open position, safety shutter
Rated Primary Current of CT: 1250 A / 0.2 A
Kind of Trip: Shunt Trip / DC 100 V
Over-Current Release: for generalFeeder circuit, AL-AS-AI-IU
3 Pole, Draw-out Type
Motor-Charging / DC 100 V
Amperes Frame: 1250 ARated Breaking Capacity: AC500 V / 70 kA
Example
K
Base current (lo) 1250 APick-up Current [l1] 1250 A Time-delay [l1] 15 s
IAN12
IAN12 3 D
IAN12 3 D M 5
IAN12 3 D M 5 2 0
IAN12 3 D M 5 2 0 S 5
IAN12 3 D M 5 2 0 S 5
IAN12
AL
Pick-up Current [l2] 7500 A Time-delay [l2] 240 sAS
Pick-up Current [l3] 12500 AAI
3 D M 5 2 0 S 5 K EB
Ordering Information
H i S e r i e s H i A N A i r C i r c u i t B r e a k e r
4 0 | H i S e r i e s
HiAN ACB spare part list
No NoType TypeDescription Description
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77
78
79
80
IANS-20
IANS-21
IANS-22
IANS-23
IANS-24
IANS-25
IANS-26
IANS-27
IANS-28
IANS-29
IANS-30
IANS-116
IANS-216
IANS-316
IANS-416
IANS-132
IANS-232
IANS-332
IANS-432
IANS-A/RLY110
IANS-A/RLY220
IANS-A/RLY24
IANS-AB163
IANS-AB164
IANS-AB323
IANS-AB324
IANS-AS
IANS-ATS
IANS-BL
IANS-CA163S
IANS-CA164S
IANS-CA323S
IANS-CA324S
IANS-CJ
IANS-CK
IANS-SB
IANS-CT032E
IANS-CT063E
IANS-CT080E
IANS-CT110E
IANS-CT113E
IANS-CT116E
IANS-CT120E
IANS-CT225E
IANS-CT332E
IANS-DI16P
IANS-DI32P
IANS-DP
IANS-FB
IANS-HANDLE
IANS-HOC5
IANS-IC06E
IANS-IC08E
IANS-IC10E
IANS-IC12E
IANS-IC16E
IANS-IC20E
IANS-IC25E
IANS-IC32E
IANS-KL/B
IANS-L1
IANS-L2
IANS-L5
IANS-L6
IANS-L7
IANS-L8
IANS-LL
IANS-M1
IANS-M2
IANS-M5
IANS-M6
IANS-M7
IANS-M8
IANS-M9
IANS-MHT
IANS-NCT032E
IANS-NCT063E
IANS-NCT080E
IANS-NCT110E
IANS-NCT113E
ACB Protection Relay (APR-1L-AL)
ACB Protection Relay (APR-1L-AS)
ACB Protection Relay (APR-1L-AM)
ACB Protection Relay (APR-1L-GL)
ACB Protection Relay (APR-1L-GS)
ACB Protection Relay (APR-2L-GS)
ACB Protection Relay (APR-1D-GM)
ACB Protection Relay (APR-1L-GM)
ACB Protection Relay (APR-1S-AL)
ACB Protection Relay (APR-1S-AS)
ACB Protection Relay (APR-2S-AS)
Mech. Interlock (for HiAN 06~16, Horizontal 2st)
Mech. Interlock (for HiAN 06~16, Horizontal 3st)
Mech. Interlock (for HiAN 06~16, Vertical 2st)
Mech. Interlock (for HiAN 06~16, Vertical 3st)
Mech. Interlock (for HiAN 20~32, Horizontal 2st)
Mech. Interlock (for HiAN 20~32, Horizontal 3st)
Mech. Interlock (for HiAN 20~32, Vertical 2st)
Mech. Interlock (for HiAN 20~32, Vertical 3st)
Anti-pumping Relay (110 V)
Anti-pumping Relay (220 V)
Anti-pumping Relay (DC 24 V)
Arc Shield (HiAN 06~16, 3P)
Arc Shield (HiAN 06~16, 4P)
Arc Shield (HiAN 20~32, 3P)
Arc Shield (HiAN 20~32, 4P)
Aux. Switch
ATS Controller
Button Lock Device
Safety Shutter (HiAN 06~16, 3P)
Safety Shutter (HiAN 06~16, 4P)
Safety Shutter (HiAN 20~32, 3P)
Safety Shutter (HiAN 20~32, 4P)
Control Jack
Cycle Counter
Short Circuit b Contact
CT (320/0.2 A)
CT (630/0.2 A)
CT (800/0.2 A)
CT (1000/0.2 A)
CT (1250/0.2 A)
CT (1600/0.2 A)
CT (2000/0.2 A)
CT (2500/0.2 A)
CT (3200/0.2 A)
DI-unit (HiAN 06~16)
DI-unit (HiAN 20~32)
Door Flange
Fixing Block
Handle
APR Checker
Isolating Contact (630 A)
Isolating Contact (800 A)
Isolating Contact (1000 A)
Isolating Contact (1250 A)
Isolating Contact (1600 A)
Isolating Contact (2000 A)
Isolating Contact (2500 A)
Isolating Contact (3200 A)
Key Lock Unit (Lock in Open)
LRC Unit (AC 110 V)
LRC Unit (AC 220 V)
LRC Unit (DC 110 V)
LRC Unit (DC 220 V)
LRC Unit (DC 24 V)
LRC Unit (DC 48 V)
Lifting Lugs
Charging Motor Unit (AC 110 V)
Charging Motor Unit (AC 220 V)
Charging Motor Unit (DC 110 V)
Charging Motor Unit (DC 220 V)
Charging Motor Unit (DC 24 V)
Charging Motor Unit (DC 48 V)
Charging Motor Unit (DC 220 V)
MHT Unit
Neutral CT (320/0.2 A)
Neutral CT (630/0.2 A)
Neutral CT (800/0.2 A)
Neutral CT (1000/0.2 A)
Neutral CT (1250/0.2 A)
Ordering Information
H i A N A i r C i r c u i t B r e a k e r | 4 1
No NoType TypeDescription Description
81
82
83
84
85
86
87
88
89
90
91
92
93
94
95
96
97
98
99
100
101
102
103
104
105
106
107
108
109
110
111
112
113
114
115
116
117
118
119
120
121
IANS-NCT116E
IANS-NCT120E
IANS-NCT225E
IANS-NCT332E
IANS-PS
IANS-S1
IANS-S2
IANS-S3
IANS-S4
IANS-S5
IANS-S6
IANS-S7
IANS-S8
IANS-T1
IANS-T2
IANS-T3
IANS-T4
IANS-T5
IANS-TJ
IANS-U1
IANS-U2
IANS-UVT/Coil
IANS-WI
DAT06-3D
DAT06-4D
DAT08-3D
DAT08-4D
DAT10-3D
DAT10-4D
DAT12-3D
DAT12-4D
DAT16-3D
DAT16-4D
DAT20-3D
DAT20-4D
DAT25-3D
DAT25-4D
DAT32-3D
DAT32-4D
HAFS-T7
HAFS-T9
Neutral CT (1600/0.2 A)
Neutral CT (2000/0.2 A)
Neutral CT (2500/0.2 A)
Neutral CT (3200/0.2 A)
Position Switch
Shunt Trip Unit (AC 110 V)
Shunt Trip Unit (AC 220 V)
Shunt Trip Unit (AC 380 V)
Shunt Trip Unit (AC 450 V)
Shunt Trip Unit (DC 110 V)
Shunt Trip Unit (DC 220 V)
Shunt Trip Unit (DC 24 V)
Shunt Trip Unit (DC 48 V)
Under Voltage Trip Unit (AC 110 V)
Under Voltage Trip Unit (AC 220 V)
Under Voltage Trip Unit (AC 380 V)
Under Voltage Trip Unit (AC 450 V)
Under Voltage Trip Unit (AC 480 V)
Test Jumper
Under Voltage Trip Unit (DC 110 V)
Under Voltage Trip Unit (DC 220 V)
Under Voltage Trip Coil
Wrong Insertion Prevention Device
Draw-out frame Unit (HiAN 06, 3P)
Draw-out frame Unit (HiAN 06, 4P)
Draw-out frame Unit (HiAN 08, 3P)
Draw-out frame Unit (HiAN 08, 4P)
Draw-out frame Unit (HiAN 10, 3P)
Draw-out frame Unit (HiAN 10, 4P)
Draw-out frame Unit (HiAN 12, 3P)
Draw-out frame Unit (HiAN 12, 4P)
Draw-out frame Unit (HiAN 16, 3P)
Draw-out frame Unit (HiAN 16, 4P)
Draw-out frame Unit (HiAN 20, 3P)
Draw-out frame Unit (HiAN 20, 4P)
Draw-out frame Unit (HiAN 25, 3P)
Draw-out frame Unit (HiAN 25, 4P)
Draw-out frame Unit (HiAN 32, 3P)
Draw-out frame Unit (HiAN 32, 4P)
Condenser Trip Device (AC 110V)
Condenser Trip Device (AC 220V)
Ordering Information
H i S e r i e s H i A N A i r C i r c u i t B r e a k e r
4 2 | H i S e r i e s
HiAN ACB spare parts for marine applications
No Order No. Specifications 08 12 16 20 25 32
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
IANS-SP01
IANS-SP02
IANS-SP03
IANS-SP04
IANS-SP05
IANS-SP06
IANS-SP07
IANS-SP08
IANS-SP09
IANS-SP10
IANS-SP11
IANS-SP12
IANS-SP13
IANS-SP14
IANS-SP15
IANS-SP16
IANS-SP17
IANS-SP18
IANS-SP19
IANS-SP20
IANS-SP21
IANS-SP22
IANS-SP23
IANS-SP24
IANS-SP25
IANS-SP26
IANS-SP27
IANS-SP28
IANS-SP29
IANS-SP30
IANS-SP31
IANS-SP32
IANS-SP33
IANS-SP34
IANS-SP35
IANS-SP36
With Motor, APR, UVT Trip
With Motor, APR, UVT Trip
With Motor, APR, UVT Trip
With Motor, APR, UVT Trip
With Motor, APR, UVT Trip
With Motor, APR, UVT Trip
With Motor, APR, UVT Trip
With Motor, APR, UVT Trip
With Motor, APR, UVT Trip
With Motor, APR, UVT Trip
With Motor, APR, UVT Trip
With Motor, APR, UVT Trip
With Motor, APR, UVT Trip
With Motor, APR, UVT Trip
With Motor, APR, UVT Trip
With Motor, APR, UVT Trip
With Motor, APR, UVT Trip
With Motor, APR, UVT Trip
With Motor, APR, Shunt Trip
With Motor, APR, Shunt Trip
With Motor, APR, Shunt Trip
With Motor, APR, Shunt Trip
With Motor, APR, Shunt Trip
With Motor, APR, Shunt Trip
With Motor, APR, Shunt Trip
With Motor, APR, Shunt Trip
With Motor, APR, Shunt Trip
With Motor, APR, Shunt Trip
With Motor, APR, Shunt Trip
With Motor, APR, Shunt Trip
With Motor, APR, Shunt Trip
With Motor, APR, Shunt Trip
With Motor, APR, Shunt Trip
With Motor, APR, Shunt Trip
With Motor, APR, Shunt Trip
With Motor, APR, Shunt Trip
ACB Operation Environment
Ordering Information / ACB Operation Environment
H i A N A i r C i r c u i t B r e a k e r | 4 3
The standard environment for ACBs is as follows:
Ambient Temperature
-5 to +40
The average temperature for 24hours must not exceed 35
Relative Humidity
45% to 85%
Attitude
Below 2000m (6,600 feet)
Atmosphere
Excessive water vapor, oil vapor, smoke, dust or corrosive gases must not exist.
Sudden change in temperature, condensation, or icing must not occur.
Transportation Conditions
Never enter the area under the air circuit breaker when it is lifted or suspended using a lifter
or chain block.
The air circuit breaker may suddenly drop.
Installation Conditions
When installing the HiAN series air circuit breaker, refer to the installation instructions in the
catalogue and instruction manual.
IP Protection
Standard : IP20
A door flange can be used as a decoration panel that covers the cutout on the switchboard
panel, and provides IP20 protection.
With rubber shield : IP31
For IP31 protection please specify the door flange with a gasket.
Storage
Store the breaker in a dry indoor location to prevent condensation due to a sudden change in
temperature, which is quite harmful to the breaker insulation.
Store the breaker in a clean place free of corrosive gases, dirt and dust.
This catalog is subject to be up-dated without notice.
This catalog shall be applied to only HiAN type Air Circuit Breaker.
Please contact the representative of Hyundai Heavy Industries for further information.
Safety Notice
HH
IS-W
C-LE
-B16-04, 2005.11 D
esigned by Design K
orea
www.hyundai-elec.com
Head Office 1 Jeonha-dong, Dong-gu, Ulsan, Korea Tel. 82-52-230-8101~8 Fax. 82-52-230-8100
Seoul HYUNDAI B/D, 140-2, Gye-dong, Jongno-gu, Seoul, Korea (Sales & Marketing) Tel. 82-2-746-7510, 7589 Fax. 82-2-746-7648
Orlando 3452 Lake Lynda Drive, Suite 110, Orlando, Florida U.S.A. 32817 Tel. 1-407-249-7350 Fax.1-407-275-4940
London 2nd Floor, The Triangle, 5-17 Hammersmith Grove London, W6 0LG, UKTel. 44-20-8741-0501 Fax. 44-20-8741-5620
Tokyo 8th Fl., Yurakucho Denki Bldg.1-7-1, Yuraku-cho, Chiyoda-gu, Tokyo, Japan 100-0006Tel. 81-3-3212-2076, 3215-7159 Fax. 81-3-3211-2093
Cairo Apartment No. 503, 5th Fl., Bldg. No. 7 Block 2, 9th Division, El-nasr Road, New Maadi, Cairo, EgyptTel. 20-2-520-0148~9 Fax. 20-2-754-7528
Sofia 41, Rojen Blvd. 1271, Sofia BulgariaTel. 359-2-938-1068, 936-0300 Fax. 359-2-936-0742
Yangzhong Lianzhong Avenue, Xinba Scientific and Technologic Zone, Yangzhong City, Jiangsu Province, China(212-212)Tel. 86-511-842-0666, 0500 Fax. 86-511-842-0668, 0231
※Recyled paper used for environmental protection.
top related