PRODUCT DRAWINGYORK INTERNATIONAL CORPORATION
P.O. Box 1592, York, PA 17405
CONTRACTOR _______________________ PURCHASER ____________________________________________
ORDER NO. __________________________ JOB NAME _______________________________________________
YORK CONTRACT NO. _________________ LOCATION _______________________________________________
YORK ORDER NO. ____________________ ENGINEER ______________________________________________
REFERENCE DATE ________ APPROVAL DATE ________ CONSTRUCTION DATE ________
Supersedes: 160.52-PA1(198) FORM 160.52-PA1(1098)
MILLENNIUM� LIQUID CHILLERSMODEL YK (STYLE D)
UNIT DIMENSIONS, FLOOR LAYOUT & NOZZLE ARRANGEMENT
COMPACT & MARINE WATER BOXES (150# & 300#)
NO. OF UNITS ________ REFRIGERANT R-134a
DESIGN LOAD CONDITIONS PER UNIT
TONS ______ . SPEED CODE ________, COOLING ______ GPM OF ______ FROM ______°F TO ______°F,CONDENSER WATER ______ GPM FROM ______°F TO ______ °F.KW INPUT _____________.
CONDENSER
WATER CIRCUIT, PASSES ___________. DWP ________ PSIG. FOULING FACTOR __________.PRESS. DROP __________ FT. NOZZLE ARRANGEMENT � IN ______ OUT _________.
COOLER
WATER CIRCUIT, PASSES ___________, DWP ________ PSIG. FOULING FACTOR __________.PRESS. DROP __________ FT. NOZZLE ARRANGEMENT � IN ______ OUT _________.
MOTOR
POWER __________ V, 3-PHASE, ________ HERTZ, FLA _________, LRA ____________ , INRUSHAMPS __________ WITH _____________ STARTING.
VARIABLE SPEED DRIVE o (FACTORY MOUNTED)
SOLID STATE STARTER o (FACTORY MOUNTED)
ELECTRO-MECHANICAL STARTER o (REMOTE MOUNTED)
OPTIONAL FEATURES AND REMARKS:
_________________________________________________________________________________________
_________________________________________________________________________________________
_________________________________________________________________________________________
_________________________________________________________________________________________
_________________________________________________________________________________________
_________________________________________________________________________________________
PERFORMANCE SPECIFICATIONS
MILLENNIUM MODEL Y K DCOOLER COND. COMPR. HZ MOTOR
YORK INTERNATIONAL2
NOMENCLATURE
ALLOWABLE COMPRESSOR/COOLER/CONDENSER/MOTOR COMBINATIONS
COMPRESSOR COOLER CONDENSER MOTOR CODES
CODE CODE CODE 60 HZ 50 HZ
G4CB, CC, CD, CE CB, CC, CD, DB, DC, DD
CH � CT 5CE � 5CODD, DE CB, CC, CD, DB, DC, DD, EB, EC, ED
DB, DC, DD DB, DC, DD, EB, EC, ED
H0/H4 EC, ED DB, DC, DD, EB, EC, ED, FB, FC, FD CH � CV 5CE � 5CR
FC, FD EB, EC, ED, FB, FC, FD
EB EB, EC, ED, FB, FC, FD
H1/H5 FB, FC, FD EB, EC, ED, FB, FC, FD, GB, GC, GD CN � CY 5CK � 5CU
GC, GD FB, FC, FD, GB ,GC, GD
FB, FC FA, FB, FC, FD, GB, GC, GD
H2/H6 GB, GC, GD FA, FB, FC, FD, GB, GC, GD CN � CZ 5CK � 5CU
HB, HC GB, GC, GD
H3/H8GB, GC, GD FB, FC, FD, GB, GC, GD CN � CZ (H8) 5CK � 5CU (H8)
HB, HC GB, GC, GD CN-CB (H3) 5CK � 5CX (H3)
GF, GH GB, GC, GD, HB, HC, HD
J1 HF, HH GB, GC, GD, HB, HC, HD, JB, JC, JDCW � DH 5CS � 5DH
J2 JF, JG, JH HB, HC, HD, JB, JC, JD
TF, TG, TH TB, TC, TD
HF, HH HB, HC, HD, JB, JC, JDDA � DJ 5DA � 5DH
JF, JG, JH HB, HC, HD, JB, JC, JD
J3 TF, TG, TH TB, TC, TD, VB, VC, VD
VF, VH TB, TC, TD, VB, VC, VD DA � DJ 5DA � 5DH
WF, WH VB, VC, VD
JF, JG, JH JB, JC, JD DA � DJ 5DA � 5DH
J4 TF, TG, TH TB, TC, TD, VB, VC, VD
VF, VH TB, TC, TD, VB, VC, VD DA � DJ 5DA - 5OJ
WF, WH VB, VC, VD
YK CB CB G4 — CM D SSpecial Modifications
Model Design Level
Cooler Code Motor Code
Condenser Code Power Supply– for 60 Hz
Compressor Code 5 for 50 Hz
FORM 160.52-PA1
3YORK INTERNATIONAL
NOTES1. Do not scale. Do not use for construction unless certified.
Dimensions symmetrical around C except as shown.
2. Overall dimensions shown do not include external piping. Pipingclearances must be provided as required. Service clearance mustbe provided as follows: 2 ft. at rear and overhead, 3 ft. at front. Ifa clear space is not available at one end for compressor removal,allow a minimum clearance width (at unit front or rear) of 3'�9".Tube removal space as shown in Fig. 33-36 (pages 58-61) mustbe provided at either end.
3. No special foundation required. Floor must be flat and levelwithin 1/4", capable of carrying the operating weight shownon pages 14-17 (See Note 11).
4. Dimension �B� is height of factory assembled unit � add 6" forshipping skids (optional at extra cost). Add 400 lbs. to shippingweight for skids.
5. Standard 150# water nozzles are furnished as weldingstubouts with grooves, allowing the option of welding, flanges,or use of Victaulic couplings. Standard 300# water nozzlesare furnished with raised-face flanges. Refer to Figs. 8 thru27 for nozzle arrangements.
6. Factory insulation of cooler surface is optional. Factory insula-tion does not include cooler water boxes. Insulation of boxesmust allow for removal. Add 125 lbs. for factory insulation.
7. For flanged (optional 150#) water nozzles on compact waterboxes, add 1" to overall length of unit when nozzles are on bothends of unit. For flanged water nozzles on one end only, add 1/2"to overall length.
8. Connected piping should allow for removal of compact waterboxes for tube access and cleaning.
9. The relief connections (See Figs. 5 & 6) should be ventedoutside the building by means of a properly sized line in accor-dance with �Safety Code for Mechanical Refrigeration�, ANSI /ASHRAE 15, and other applicable codes for personal safety.
10. WEIGHTS (See Pages 14-17). Weights for J Compressor Units(Table 2) for Shell Codes G-G through T-T are based on J1/J2Compressors. Add 1,000 lb. (454 kg.) to Shipping Weight andOperating Weight, and 250 lb. (113 kg) to Loading Per Isolatorif J3/J4 Compressor is furnished. Weight for Shell Codes T-Vthrough W-V are based on J3/J4 Compressors.
A. Shipping Weights � Indicates heaviest single piece ofequipment to rig.
Weights include control center, oil charge and isolatorpads.
Weights shown DO NOT include:
Marine Water Box Weights � see page 18
L
Refrigerant � see Tables 1 or 2 (Pages 14-17)
Motor � See Fig. 32 (Pages 56 & 57)
Solid State Starter � see Fig. 37 (Page 62)
Variable Speed Drive � see Fig. 38 (Page 63)
Thermal Insulation � add 125 lbs.
Shipping Skids � add 400 lbs.
B. Operating Weights � Weights shown include the ship-ping weights shown above plus water and refrigerantoperating charge.
C. Loading Per Isolator � Equals Operating Weight dividedby 4. Add motor weight divided by 4. If other options aresupplied, add weights shown divided by 4.
11. ISOLATORS
A. Standard unit is provided with neoprene vibration isola-tor mounts (shims for leveling by others). Add 7/8" (22mm) to unit height for neoprene mounts to obtain installedheight � see Figs. 28 or 29 (Pages 52 or 53).
B. When neoprene isolators are ordered, mounting platesare factory installed as shown in Figs. 28 or 29. Neo-prene isolator pads are field installed between foot sup-port and floor.
C. For a given unit, all four neoprene isolator pads are iden-tical. Pads are 1" (25 mm) thick with nominal 0.15" (4 mm)static deflection. Floor contact dimension depends uponoperating weight; determine unit operating weight (SeeNote 10B) and refer to Figs. 28 or 29 for pad size.
D. All units for upper floor location require optional level-adjusting spring type vibration isolators and brackets;add 1" (25 mm) to unit height for spring isolator mounts toobtain installed height. Refer to Figs. 30 or 31 (Pages 54or 55) for spring isolator mounts.
E. If optional level-adjusting spring type vibration isolatorsare to be applied see �Floor Layout � Spring Isolators�,Figs. 30 or 31.
F. When spring isolators are ordered, mounting bracketsare factory installed as shown in Figs. 30 or 31.
12. 7/8" diameter knockouts are located on the top cover for leadholes of the Solid State Starter (when furnished) for field powerwiring conduit (flexible) connections (holes to be sized andcut by others).
13. 7/8" diameter knockouts are located in removable plate on topof the Variable Speed Drive for lead holes for power wiringconduit. Plate will accommodate one or two 3" conduits, or amaximum of three 2-1/2" or smaller conduits. Holes to be sizedand cut by others.
YO
RK
INT
ER
NA
TIO
NA
L4
FIG. 1 � UNIT DIMENSIONS - G & H COMPRESSOR UNITS (STANDARD DIMENSIONS)
LD02152
NOTES:
1. To determine overall length add water box depth totube sheet length.
2. Water nozzles can be located on either end of unit.Add 1/2" to nozzle length for flanged connections.
3. Dimension �B� may increase depending on motor size.(See Fig. 32).
4. To determine overall installed height with isolators, seeNote 11.
LD01338(R)
2'�2-1/8"
H
1'�2-1/8"
14'�0"
7'�0"
C SHELLSL
1'�2-1/8"
E
G
K
COOLER
B 3, 4
DCLC CL
A
M
CONDENSER
N
L
7/8"
CONDENSERCOMPRESSOR
1"J
1-5/8"
MOTORTERMINALBOX
COOLER2'�2-3/4"
MICROCOMPUTERCONTROL PANEL
F
RELIEF VALVES(SEE FIG. 5)
OIL PUMPSTARTER
FORM 160.52-PA1
5YORK INTERNATIONAL
H0
/H4
CO
MP
RE
SS
OR
SC
OO
LE
R�
CO
ND
EN
SE
R S
HE
LL
CO
DE
SD
�D
D�
EE
�D
E�
EE
�F
F�
EF
�F
A6
'�4
"6
'�4
"6
'�6
"6
'�6
"6
'�9
"6
'�11
"7
'�2
"B
8'�
0-1
/2"
8'�
1"
8'�
0-1
/2"
8'�
1"
8'�
3-1
/2"
8'�
1"
8'�
3-1
/2"
C1
'�8
-1/2
"1
'�8
-1/2
"1
'�9
-1/2
"1
'�9
-1/2
"1
'�9
-1/2
"2
'�0
"2
'�0
"D
1'�
5-1
/2"
1'�
5-1
/2"
1'�
5-1
/2"
1'�
5-1
/2"
1'�
7"
1'�
5-1
/2"
1'�
7"
E0
'�5
-5/8
"0
'�5
-5/8
"0
'�5
-7/8
"0
'�5
-7/8
"0
'�5
-7/8
"0
'�5
-7/8
"0
'�5
-7/8
"F
1'�
8-1
/2"
1'�
8-1
/2"
1'�
8-1
/2"
1'�
8-1
/2"
1'�
8-1
/2"
1'�
8-1
/2"
1'�
8-1
/2"
G6
'�1
"6
'�0
-3/4
"6
'�1
"6
'�1
-1/2
"6
'�4
"6
'�1
-1/2
"6
'�4
"H
4�
1-3
/4"
4'�
1-3
/4"
4'�
1-3
/4"
4'�
1-3
/4"
4'�
1-3
/4"
4'�
2-3
/4"
4'�
2-3
/4"
J1
'�2
-1/8
"1
'�2
-1/8
"1
'�2
-1/8
"1
'�2
-1/8
"1
'�2
-1/8
"1
'�2
-1/8
"1
'�2
-1/8
"K
1'�
1"
1'�
1"
1'�
1"
1'�
1"
1'�
1"
1'�
1"
1'�
1"
L1
'�5
-1/4
"1
'�5
-1/4
"1
'�5
-1/4
"1
'�5
-1/4
"1
'�5
-1/4
"1
'�5
-1/4
"1
'�6
-1/4
"M
3'�
5"
3'�
5"
3'�
7"
3'�
7"
3'�
7"
4'�
0"
4'�
0"
N2
'�11
"2
'�11
"2
'�11
"2
'�11
"3
'�2
"2
'�11
"3
'�2
"
H1
/H5
CO
MP
RE
SS
OR
SC
OO
LE
R�
CO
ND
EN
SE
R S
HE
LL
CO
DE
SE
�E
E�
FF
�E
F�
FF
�G
G�
FG
�G
A6
'�6
"6
'�9
"6
'�11
"7
'�2
"7
'�6
"7
'�4
-1/2
"7
'�8
-1/2
"B
8'�
1"
8'�
3-1
/2"
8'�
1"
8'�
3-1
/2"
8'�
7-1
/2"
8'�
3-1
/2"
8'�
7-1
/2"
C1
'�9
-1/2
"1
'�9
-1/2
"2
'�0
"2
'�0
"2
'�0
"2
'�1
-1/4
"2
'�1
-1/4
"D
1'�
5-1
/2"
1'�
7"
1'�
5-1
/2"
1'�
7"
1'�
9"
1'�
7"
1'�
9"
E0
'�5
-7/8
"0
'�5
-7/8
"0
'�5
-7/8
"0
'�5
-7/8
"0
'�5
-7/8
"0
'�6
-1/4
"0
'�6
-1/4
"F
1'�
8-1
/2"
1'�
8-1
/2"
1'�
8-1
/2"
1'�
8-1
/2"
1'�
8-1
/2"
1'�
8-1
/2"
1'�
8-1
/2"
G6
'�1
-1/2
"6
'�4
"6
'�1
-1/2
"6
'�4
"6
'�8
"6
'�4
"6
'�8
"H
4'�
1-3
/4"
4'�
1-3
/4"
4'�
2-3
/4"
4'�
2-3
/4"
4'�
2-3
/4"
4'�
2-1
/4"
4'�
2-1
/4"
J1
'�2
-1/8
"1
'�2
-1/8
"1
'�2
-1/8
"1
'�2
-1/8
"1
'�2
-1/8
"1
'�2
-1/8
"1
'�2
-1/8
"K
1'�
1"
1'�
1"
1'�
1"
1'�
1"
1'�
1"
1'�
1"
1'�
1"
L1
'�5
-1/4
"1
'�5
-1/4
"1
'�5
-1/4
"1
'�6
-1/4
"1
'�5
-1/4
"1
'�6
-1/4
"1
'�5
-1/4
"M
3'�
7"
3'�
7"
4'�
0"
4'�
0"
4'�
0"
4'�
2-1
/2"
4'�
2-1
/2"
N2
'�11
"3
'�2
"2
'�11
"3
'�2
"3
'�6
"3
'�2
"3
'�6
"
H2
/H6
/H7
CO
MP
RE
SS
OR
SC
OO
LE
R�
CO
ND
EN
SE
R S
HE
LL
CO
DE
SF
�F
F�
GG
�F
G�
GH
�G
A7
'�2
"7
'�6
"7
'�4
-1/2
"7
'�8
-1/2
"8
'�0
"B
8'�
3-1
/2"
8'�
7-1
/4"
8'�
3-1
/2"
8'�
7-1
/4"
8'�
7-1
/4"
C2
'�0
"2
'�0
"2
'�1
-1/4
"2
'�1
-1/4
"2
'�3
"D
1'�
7"
1'�
9"
1'�
7"
1'�
9"
1'�
9"
E0
'�5
-7/8
"0
'�5
-7/8
"0
'�6
-1/4
"0
'�6
-1/4
"0
'�6
-1/4
"F
1'�
8-1
/2"
1'�
8-1
/2"
1'�
8-1
/2"
1'�
8-1
/2"
1'�
8-1
/2"
G6
'�4
-3/8
"6
'�7
-7/8
"6
'�4
-3/8
"6
'�7
-7/8
"6
'�7
-7/8
"H
4'�
2-3
/4"
4'�
2-3
/4"
4'�
2-1
/4"
4'�
2-1
/4"
4'�
3-3
/4"
J1
'�2
-1/8
"1
'�2
-1/8
"1
'�2
-1/8
"1
'�2
-1/8
"1
'�2
-1/8
"K
1'�
2"
1'�
2"
1'�
2"
1'�
2"
1'�
2"
L1
'�6
-1/4
"1
'�6
-1/4
"1
'�6
-1/4
"1
'�6
-1/4
"1
'�6
-1/4
"M
4'�
0"
4'�
0"
4'�
2-1
/2"
4'�
2-1
/2"
4'�
6"
N3
'�2
"3
'�6
"3
'�2
"3
'�6
"3
'�6
"
G4
CO
MP
RE
SS
OR
SC
OO
LE
R�
CO
ND
EN
SE
R S
HE
LL
CO
DE
SC
�C
C�
DD
�C
D�
DD
�E
A6
'�1
"6
'�1
"6
'�4
"6
'�4
"6
'�4
"B
7'�
10
-1/2
"8
'�0
-1/2
"7
'�1
0-1
/2"
8'�
0-1
/2"
8'�
1"
C1
'�7
"1
'�7
"1
'�8
-1/2
"1
'�8
-1/2
"1
'�8
-1/2
"D
1'�
5-1
/2"
1'�
5-1
/2"
1'�
5-1
/2"
1'�
5-1
/2"
1'�
5-1
/2"
E0
'�5
-5/8
"0
'�5
-5/8
"0
'�5
-5/8
"0
'�5
-5/8
"0
'�5
-5/8
"F
1'�
8-1
/2"
1'�
8-1
/2"
1'�
8-1
/2"
1'�
8-1
/2"
1'�
8-1
/2"
G5
'�11
"6
'�1
"5
'�11
"6
'�1
"6
'�0
-3/4
"H
3'�
7-3
/4"
3'�
7-3
/4"
4�
1-3
/4"
4'�
1-3
/4"
4'�
1-3
/4"
J1
'�2
-1/8
"1
'�2
-1/8
"1
'�2
-1/8
"1
'�2
-1/8
"1
'�2
-1/8
"K
1'�
1"
1'�
1"
1'�
1"
1'�
1"
1'�
1"
L1
'�5
-1/4
"1
'�5
-1/4
"1
'�5
-1/4
"1
'�5
-1/4
"1
'�5
-1/4
"M
3'�
2"
3'�
2"
3'�
5"
3'�
5"
3'�
5"
N2
'�11
"2
'�11
"2
'�11
"2
'�11
"2
'�11
"
H3
/H8
CO
MP
RE
SS
OR
SC
OO
LE
R�
CO
ND
EN
SE
R S
HE
LL
CO
DE
SG
�F
G�
GH
�G
A7
'�4
-1/2
"7
'�8
-1/2
"8
'�0
"B
8'�
3-1
/2"
8'�
7-1
/4"
8'�
7-1
/4"
C2
'�1
-1/4
"2
'�1
-1/4
"2
'�3
"D
1'�
7"
1'�
9"
1'�
9"
E0
'�6
-1/4
"0
'�6
-1/4
"0
'�6
-1/4
"F
1'�
8-1
/2"
1'�
8-1
/2"
1'�
8-1
/2"
G6
'�4
-3/8
"6
'�7
-7/8
"6
'�7
-7/8
"H
4'�
2-1
/4"
4'�
2-1
/4"
4-3
-3/4
"J
1'�
2-1
/8"
1'�
2-1
/8"
1'�
2-1
/8"
K1
'�2
"1
'�2
"1
'�2
"L
1'�
6-1
/4"
1'�
6-1
/4"
1'�
6-1
/4"
M4
'�2
-1/2
"4
'�2
-1/2
"4
'�6
"N
3'�
2"
3'�
6"
3'�
6"
YO
RK
INT
ER
NA
TIO
NA
L6
FIG. 2 � UNIT DIMENSIONS - J COMPRESSOR UNITS (STD. DIMENSIONS)
NOTES:
1. To determine overall length add water box depth totube sheet length.
2. Water nozzles can be located on either end of unit.Add 13 mm to nozzle length for flanged connections.
3. Dimension �B� may increase depending on motor size.(See Fig. 32).
4. To determine overall installed height with isolators, seeNote 11.
1-5/8"
MICROCOMPUTERCONTROL PANEL
COMPRESSOR
MOTORP
C SHELLSL
N
K
J
FE
FLOOR LINE (SEE NOTE 4)
G
7/8"
L
2'�2-1/8"H
A
C D
CONDENSER
COOLER
B 4, 5
R
LD03304
LD03303
COMPRESSORCONDENSER
1"
MOTORTERMINALBOX
COOLER
MICROCOMPUTERCONTROL PANEL
M 2'�2-3/4"
RELEIF VALVES(SEE FIG. 6)
LC LC
TS
OIL PUMPSTARTER
FO
RM
16
0.5
2-P
A17
YO
RK
INT
ER
NA
TIO
NA
L
J1/J2 COMPRESSORS
COOLER - COMPRESSOR SHELL CODES
G-G G-H H-G H - H H-J J-H J-J T-T
A 7'6" 7'10" 7'�10-1/2" 8'�2-1/2" 8'�6-1/2" 8'�9" 9'�1" 9'�1"
B 9'�3-3/4" 9'�3-3/4" 9'�3-3/4" 9'�9-3/4" 9'�9-3/4" 9'�9-3/4" 9'�9-3/4" 9'�9-1/2"
C 2'�0" 2'�0" 2'�2-1/4" 2'�2-1/4" 2'�2-1/4" 2'�5-1/2" 2'�5-1/2" 2'�5-1/2"
D 1'�9" 1'�11" 1'-9" 1'�11" 2'�1" 1'�11" 2'�1" 2'�1"
E 14'�0" 14'�0" 14'�0" 14'�0" 14'�0" 14'�0" 14'�0" 16'�0"
F 1'�11-3/4" 1'�11-3/4" 1'�11-3/4" 1'�11-3/4" 1'�11-3/4" 1'�11-3/4" 1'�11-3/4" 1'�11-3/4"
G 1'�2-3/4" 1'�2-3/4" 1'�2-3/4" 1'�2-3/4" 1'�2-3/4" 1'�2-3/4" 1'�2-3/4" 1'�2-3/4"
L 4'�5-1/4" 4'�5-1/4" 4'�7-1/4" 4'�7-1/4" 4'�7-1/4" 4'�9-3/4" 4'�9-3/4" 4'�9-3/4"
M 1'�7-1/2" 1'�7-1/2" 1'�7-1/2" 1'�7-1/2" 1'�7-1/2" 1'�7-1/2" 1'�7-1/2" 3'�7-1/2"
N 6'�11" 7'�5" 6'�11" 7'�5" 7'�5" 7'�5" 7'�5" 7'�5"
P 1'�3" 1'�3" 1'�3" 1'�3" 1'�3" 1'�3" 1'�3" 1'�3"
R 1'�8-1/2" 1'�8-1/2" 1'�8-1/2" 1'�8-1/2" 1'�8-1/2" 1'�8-1/2" 1'�8-1/2" 1'�8-1/2"
S 4'�0" 4'�0" 4'�4-1/2" 4'�4-1/2" 4'�4-1/2" 4'�11" 4'�11" 4'�11"
T 3'�6" 3'�10" 3'�6" 3'�10" 4'�2" 3'�10" 4'�2" 4'�2"
J3/J4 COMPRESSORS
COOLER - CONDENSER SHELL CODES
J-J T-T T-V V-T V-V W-V
A 9'�1" 9'�1" 9'�6" 9'�1" 9'�6" 9'�11"
B 10'�0-3/4" 10'�0-3/4" 10'�5-3/4" 10'�0-3/4" 10'�5-3/4" 10'�5-3/4"
C 2'�5-1/2" 2'�5-1/2" 2'�5-1/2" 2'�5-1/2" 2'�5-1/2" 2'�8"
D 2'�1" 2'�1" 2'�3-1/2" 2'�1" 2'�3-1/2" 2'�3-1/2"
E 14'�0" 16'�0" 16'�0" 16'�0" 16'�0" 16'�0"
F 1'�11-3/4" 1'�11-3/4" 1'�11-3/4" 1'�11-3/4" 1'�11-3/4" 2'�0-3/4"
G 1'�2-3/4" 1'�2-3/4" 1'�2-3/4" 1'�2-3/4" 1'�2-3/4" 1'�4-1/2"
L 4'�9-3/4" 4'�9-3/4" 4'�9-3/4" 4'�9-3/4" 4'�9-3/4" 5'�0-1/4"
M 1'�7-1/2" 3'�7-1/2" 3'�7-1/2" 3'�7-1/2" 3'�7-1/2" 3'�7-1/2"
N 7'�4-3/4" 7'�4-3/4" 7'�9-3/4" 7'�4-3/4" 7'�9-3/4" 7'�9-3/4"
P 1'�2-1/8" 1'�2-1/8" 1'�2-1/8" 1'�2-1/8" 1'�2-1/8" 1'�2-1/8"
R 2'�0-1/2" 1'�8-1/2" 2'�0-1/2" 1'�8-1/2" 2'�0-1/2" 2'�0-1/2"
S 4'�11" 4'�11" 4'�11" 4'�11" 4'�11" 5'�4"
T 4'�2" 4'�2" 4'�7" 4'�2" 4'�7" 4'�7"
J3 COMPRESSORS
COOLER - CONDENSER SHELL CODES
H - H H-J J-H
A 8'�2-1/2" 8'�6-1/2" 8'�9"
B 9'�8-3/4" 10'�0-3/4" 9'�8-3/4"
C 2'�2-1/4" 2'�2-1/4" 2'�5-1/2"
D 1'�11" 2'�1" 1'�11"
E 14'�0" 14'�0" 14'�0"
F 1'�11-3/4" 1'�11-3/4" 1��11-3/4"
G 1'�2-3/4" 1'�2-3/4" 1'�2-3/4"
L 4'�7-1/4" 4'�7-1/4" 4'�9-3/4"
M 1'�7-1/2" 1'�7-1/2" 1'�7-1/2"
N 7'�0-3/4" 7'�4-3/4" 7'�0-3/4"
P 1'�2-1/8" 1'�2-1/8" 1'�2-1/8"
R 2'�0-1/2" 2'�0-1/2" 2'�0-1/2"
S 4'�4-1/2" 4'�4-1/2" 4'�11"
T 3'�10" 4'�2" 3'�10"
CONDENSER CODE
NO. OF PASSES G H J T V
H 1, 2 or 3 5�7/8" 11�5/8" 1'�0-1/2" 1'�0-1/2" 1'�1-5/8
1 1'�1-3/4" 1'�8-7/8" 1'�9-5/8" 1'�9-5/8" 1'�11"
J 2 1'�1-3/4" 1'�6-1/8" 1'�7-1/2" 1'�7-1/2" 1'�10"
3 1'�1-3/4" 1'�4-5/8" 1'�6-3/4" 1'�6-3/4" 1'�7-1/2"
1 1'�1-3/4" 1'�8-7/8" 1'�9-5/8" 1'�9-5/8" 1'�11"
K 2 1'�1-3/4" 1'�6-1/8" 1'�7-1/2" 1'�7-1/2" 1'�10"
3 1'�1-3/4" 1'�8" 1'�10" 1'�10" 1'�11-1/4"
YO
RK
INT
ER
NA
TIO
NA
L8
CONDENSER
COMPRESSOR25 J
41
MOTORTERMINALBOX
COOLER679
MICROCOMPUTERCONTROL PANEL
F
RELIEF VALVES(SEE FIG. 5)
NOTES:
1. To determine overall length add water box depth totube sheet length.
2. Water nozzles can be located on either end of unit.Add 13 mm to nozzle length for flanged connections.
3. Dimension �B� may increase depending on motor size.(See Fig. 32).
4. To determine overall installed height with isolators, seeNote 11.
FIG. 3 � UNIT DIMENSIONS - G & H COMPRESSOR UNITS (METRIC DIMENSIONS)
LD02152
664
H
359
4267
2134
C SHELLSL
359
E
G
K
COOLER
B (See Notes 3 & 4)
A
DC
CONDENSER
LC CL
LD01338(R)
L
NM22
OIL PUMPSTARTER
FORM 160.52-PA1
9YORK INTERNATIONAL
H0
/H4
CO
MP
RE
SS
OR
SC
OO
LE
R�
CO
ND
EN
SE
R S
HE
LL
CO
DE
SD
�D
D�
EE
�D
E�
EE
�F
F�
EF
�F
A1
,93
01
,93
01
,98
11
,98
12
,05
72
,10
82
,18
4B
2,4
51
2,4
64
2,4
51
2,4
64
2,5
27
2,4
64
2,5
27
C5
21
52
15
46
54
65
46
61
06
10
D4
45
44
54
45
44
54
83
44
54
83
E1
43
14
31
49
14
91
49
14
91
49
F5
21
52
15
21
52
15
21
52
15
21
G1
,85
41
,84
81
,85
41
,86
71
,93
01
,86
71
,93
0H
1,2
64
1,2
64
1,2
64
1,2
64
1,2
64
1,2
89
1,2
89
J3
59
35
93
59
35
93
59
35
93
59
K3
30
33
03
30
33
03
30
33
03
30
L4
38
43
84
38
43
84
38
43
84
64
M1
,04
11
,04
11
,09
21
,09
21
,09
21
,21
91
,21
9N
88
98
89
88
98
89
96
58
89
96
5
H3
/H8
CO
MP
RE
SS
OR
SC
OO
LE
R�
CO
ND
EN
SE
R S
HE
LL
CO
DE
SG
�F
G�
GH
�G
A2
,24
82
,35
02
,43
8B
2,5
27
2,6
28
2,6
28
C6
41
64
16
86
D4
83
53
35
33
E1
59
15
91
59
F5
21
52
15
21
G1
,94
02
,02
92
,02
9H
1,2
76
1,2
76
1,3
14
J3
59
35
93
59
K3
56
35
63
56
L4
64
46
44
64
M1
,28
31
,28
31
,37
2N
96
51
,06
71
,06
7
H1
/H5
CO
MP
RE
SS
OR
SC
OO
LE
R�
CO
ND
EN
SE
R S
HE
LL
CO
DE
SE
�E
E�
FF
�E
F�
FF
�G
G�
FG
�G
A1
,98
12
,05
72
,10
82
,18
42
,28
62
,24
82
,35
0B
2,4
64
2,5
27
2,4
64
2,5
27
2,6
28
2,5
27
2,6
28
C5
46
54
66
10
61
06
10
64
16
41
D4
45
48
34
45
48
35
33
48
35
33
E1
49
14
91
49
14
91
49
15
91
59
F5
21
52
15
21
52
15
21
52
15
21
G1
,86
71
,93
01
,86
71
,93
02
,03
21
,93
02
,03
2H
1,2
64
1,2
64
1,2
89
1,2
89
1,2
89
1,2
76
1,2
76
J3
59
35
93
59
35
93
59
35
93
59
K3
30
33
03
30
33
03
30
33
03
30
L4
38
43
84
38
46
44
38
46
44
38
M1
,09
21
,09
21
,21
91
,21
91
,21
91
,28
31
,28
3N
88
99
65
88
99
65
1,0
67
96
51
,06
7
H2
/H6
CO
MP
RE
SS
OR
SC
OO
LE
R�
CO
ND
EN
SE
R S
HE
LL
CO
DE
SF
�F
F�
GG
�F
G�
GH
�G
A2
,18
42
,28
62
,24
82
,35
02
,43
8B
2,5
27
2,6
28
2,5
27
2,6
28
2,6
86
C6
10
61
06
41
64
16
86
D4
83
53
34
83
53
35
33
E1
49
14
91
59
15
91
59
F5
21
52
15
21
52
15
21
G1
,94
02
,02
91
,94
02
,02
92
,02
9H
1,2
89
1,2
89
1,2
76
1,2
76
1,3
14
J3
59
35
93
59
35
93
59
K3
56
35
63
56
35
63
56
L4
64
46
44
64
46
44
64
M1
,21
91
,21
91
,28
31
,28
31
,37
2N
96
51
,06
79
65
1,0
67
1,0
67
G4
CO
MP
RE
SS
OR
SC
OO
LE
R�
CO
ND
EN
SE
R S
HE
LL
CO
DE
SC
�C
C�
DD
�C
D�
DD
�E
A1
,85
41
,85
41
,93
01
,93
01
,93
0B
2,4
00
2,4
51
2,4
00
2,4
51
2,4
64
C4
83
48
35
21
52
15
21
D4
45
44
54
45
44
54
45
E1
43
14
31
43
14
31
43
F5
21
52
15
21
52
15
21
G1
,80
31
,85
41
,80
31
,85
41
,84
8H
1,11
11,
111
1,2
64
1,2
64
1,2
64
J3
59
35
93
59
35
93
59
K3
30
33
03
30
33
03
30
L4
38
43
84
38
43
84
38
M9
65
96
51
,04
11
,04
11
,04
1N
88
98
89
88
98
89
88
9
YO
RK
INT
ER
NA
TIO
NA
L1
0
FIG. 4 � UNIT DIMENSIONS - J COMPRESSOR UNITS (METRIC DIMENSIONS- mm)
NOTES:
1. To determine overall length add water box depth totube sheet length.
2. Water nozzles can be located on either end of unit.Add 13 mm to nozzle length for flanged connections.
3. Dimension �B� may increase depending on motor size.(See Fig. 32).
4. To determine overall installed height with isolators, seeNote 11.
COMPRESSORCONDENSER
25
MOTORTERMINALBOX
COOLER
MICROCOMPUTERCONTROL PANEL
M 679
RELEIF VALVES(SEE FIG. 6)
41
MICROCOMPUTERCONTROL PANEL
COMPRESSOR
MOTORP
C SHELLSL
N
K
J
FE
FLOOR LINE (SEE NOTE 4)
G
22
L
664H
A
LC LC
C D
CONDENSER
COOLER
B 4, 5
R
TS
OIL PUMPSTARTER
FO
RM
16
0.5
2-P
A1
11
YO
RK
INT
ER
NA
TIO
NA
L
J1/J2 COMPRESSORS
COOLER - COMPRESSOR SHELL CODES
G-G G-H H-G H-H H-J J-H J-J T-T
A 2,286 2,388 2,400 2,502 2,604 2,667 2,769 2,769
B 2,838 2,838 2,838 2,838 2,838 2,838 2,838 2,985
C 610 610 667 667 667 749 749 749
D 533 584 533 584 635 584 635 635
E 4,267 4,267 4,267 4,267 4,267 4,267 4,267 4,877
F 552 552 552 552 552 552 552 552
G 375 375 375 375 375 375 375 375
L 1,353 1,353 1,403 1,403 1,403 1,467 1,467 1,467
M 495 495 495 495 495 495 495 1,105
N 2,108 2,261 2,108 2,261 2,261 2,261 2,261 2,261
P 381 381 381 381 381 381 381 381
R 520 520 520 520 520 520 520 520
S 1,219 1,219 1,336 1,336 1,336 1,499 1,499 1,499
T 1,067 1,168 1,067 1,168 1,270 1,168 1,270 1,270
J3/J4 COMPRESSORS
COOLER - CONDENSER SHELL CODES
J-J T-T T-V V-T V-V W-V
A 2,769 2,769 2,896 2,769 2,896 3,023
B 3,067 3,067 3,194 3,067 3,194 3,194
C 749 749 749 749 749 813
D 635 635 699 635 699 699
E 4,267 4,877 4,877 4,877 4,877 4,877
F 603 603 603 603 603 629
G 375 375 375 375 375 419
L 1,467 1,467 1,467 1,467 1,467 1,530
M 495 1,105 1,105 1,105 1,105 1,105
N 2,254 2,254 2,381 2,254 2,381 2,381
P 359 359 359 359 359 359
R 622 622 622 622 622 622
S 1,499 1,499 1,499 1,499 1,499 1,626
T 1,270 1,270 1,397 1,270 1,397 1,397
J3 COMPRESSORS
COOLER - CONDENSER SHELL CODES
H-H H-J J-H
A 2,502 2,604 2,667
B 2,965 3,067 2,965
C 667 667 749
D 584 635 584
E 4,267 4,267 4,267
F 603 603 603
G 375 375 375
L 1,403 1,403 1,467
M 495 495 495
N 2,153 2,254 2,153
P 359 359 359
R 622 622 622
S 1,336 1,336 1,499
T 1,168 1,270 1,168
CONDENSER CODE
NO. OF PASSES G H J T V
H 1, 2 or 3 149 295 318 318 346
1 349 530 549 549 584
J 2 349 460 495 495 559
3 349 422 476 476 495
1 349 530 549 549 584
K 2 349 460 495 495 559
3 349 508 559 559 591
YORK INTERNATIONAL12
FIG. 5 � COOLER AND CONDENSER RELIEF VALVES LOCATION - G & H COMPRESSOR UNITS (STD. AND METRIC)
SHELL ACODE COOLER CONDENSER
C � 4'�11-7/8"D 4'�1-5/8" 5'�0-7/8"E 4'�3-5/8" 5'�3-7/8"F 4'�6-5/8" 5'�6-7/8"G 4'�11-3/4" 5'�10-7/8"H 5�2-3/4" �
SHELL A (mm)CODE COOLER CONDENSER
C � 1521D 1260 1546E 1311 1622F 1387 1699G 1518 1800H 1594 �
LD02158
G & HCOOLERS
D, E, & FCOOLERS
RELIEF VALVE(1-1/4" NPT)
2-1/8"(54 mm)
3-3/4"(95 mm)1' 9"
(533 mm)
LC CONDENSER
A
1' 5"
(432 mm)
RELIEF VALVES (1-1/4" NPT)
LC OF COOLER
A1' 5"
(432 mm)
LC OF COOLER
4' 0-3/4"(1238 mm)
2-1/4" (57 mm)LC OF COOLER
RELIEF VALVE(1-1/2" NPT)
A
1' 5"
(432 mm)
CCOOLER
4"(102 m
m)
DUAL RELIEFVALVES (1-1/4" NPT)
C, D, E, F & GCONDENSERS
FORM 160.52-PA1
13YORK INTERNATIONAL
FIG. 6 � COOLER AND CONDENSER RELIEF VALVES LOCATION - J COMPRESSOR UNITS (STD. AND METRIC)
2-1/8"(54 mm)
3-3/4"(95 mm)4'-3
-3/8"
(1259 mm)
LC CONDENSER
DUAL RELIEF VALVES (1-1/4"
A
G, H & JCOOLERS
1' 5"
(432 mm)
RELIEF VALVES (1-1/4" NPT)
LC OF COOLER
A
RELIEF VALVES (1-1/4" NPT)
T, V & W COOLERS
2' 2"
(660 mm) LC OF COOLER
A
2-1/8"(54 mm)
3-3/4"(95 mm)4'-8-5/8"
(1438 mm)
LC CONDENSERA
6"(152 m
m)
G, H & J CONDENSER
T & V CONDENSER
DUAL RELIEF VALVES1-1/2" NPT
4"(102 m
m)
SHELL ACODE COOLER CONDENSER
C 5'�2-1/4" 5'�10-3/4"D 5'�6-1/4" 6'�2-3/4"E 6'�0-1/4" 6'�6-3/4"F 6'�0-1/4" 6'�5-3/4"G 6'�0-1/4" 6'�10-3/4"H 6'�4-3/8" �
SHELL A (mm)CODE COOLER CONDENSER
C 1581 1797D 1683 1899E 1835 2000F 1835 1975G 1835 2102H 1940 �
LD03351
YORK INTERNATIONAL14
SHIPPING OPERATING REFRIGERANT LOADING PERSHELLS WEIGHT WEIGHT CHARGE ISOLATOR
(LBS) (KG) (LBS) (KG) (LBS) (KG) (LBS) (KG)
CBCB 16,560 7,512 19,120 8,673 1,025 465 4,780 2,168CBCC 16,610 7,534 19,200 8,709 1,025 465 4,800 2,177CBCD 16,750 7,598 19,400 8,800 1,025 465 4,850 2,200CCCB 16,780 7,611 19,430 8,813 1,025 465 4,858 2,203C C C C 16,830 7,634 19,510 8,850 1,025 465 4,878 2,212
C - CC C C D 16,970 7,698 19,710 8,940 1,025 465 4,928 2,235CDCB 17,030 7,725 19,780 8,972 1,025 465 4,945 2,243C D C C 17,080 7,747 19,860 9,008 1,025 465 4,965 2,252C D C D 17,220 7,811 20,060 9,099 1,025 465 5,015 2,275CECB 17,260 7,829 20,110 9,122 1,025 465 5,028 2,280C E C C 17,310 7,852 20,190 9,158 1,025 465 5,048 2,290C E C D 17,450 7,915 20,390 9,249 1,025 465 5,098 2,312CBDB 17,090 7,752 19,830 8,995 1,025 465 4,958 2,249CBDC 17,360 7,874 20,100 9,117 1,025 465 5,025 2,279CBDD 17,100 7,757 19,970 9,058 1,025 465 4,993 2,265CCDB 17,310 7,852 20,130 9,131 1,025 465 5,033 2,283C C D C 17,580 7,974 20,410 9,258 1,025 465 5,103 2,314
C - DC C D D 17,320 7,856 20,270 9,194 1,025 465 5,068 2,299CDDB 17,560 7,965 20,490 9,294 1,025 465 5,123 2,324C D D C 17,830 8,088 20,760 9,417 1,025 465 5,190 2,354C D D D 17,570 7,970 20,630 9,358 1,025 465 5,158 2,339CEDB 17,790 8,070 20,810 9,439 1,025 465 5,203 2,360C E D C 18,060 8,192 21,090 9,566 1,025 465 5,273 2,392C E D D 17,800 8,074 20,950 9,503 1,025 465 5,238 2,376DDCB 18,140 8,228 21,140 9,589 1,025 465 5,285 2,397D D C C 18,190 8,251 21,220 9,625 1,025 465 5,305 2,406
D - CD D C D 18,330 8,314 21,420 9,716 1,025 465 5,355 2,429DECB 18,300 8,301 21,360 9,689 1,025 465 5,340 2,422D E C C 18,350 8,324 21,440 9,725 1,025 465 5,360 2,431D E C D 18,490 8,387 21,640 9,816 1,025 465 5,410 2,454DBDB 18,140 8,228 21,220 9,625 1,150 522 5,305 2,406DBDC 18,400 8,346 21,480 9,743 1,150 522 5,370 2,436DBDD 18,140 8,228 21,350 9,684 1,150 522 5,338 2,421DCDB 18,360 8,328 21,530 9,766 1,150 522 5,383 2,442D C D C 18,630 8,451 21,810 9,893 1,150 522 5,453 2,473
D - DD C D D 18,370 8,333 21,670 9,830 1,150 522 5,418 2,457DDDB 18,670 8,469 21,970 9,966 1,150 522 5,493 2,491D D D C 18,940 8,591 22,240 10,088 1,150 522 5,560 2,522D D D D 18,680 8,473 22,110 10,029 1,150 522 5,528 2,507DEDB 18,830 8,541 22,190 10,065 1,150 522 5,548 2,516D E D C 19,100 8,664 22,460 10,188 1,150 522 5,615 2,547D E D D 18,840 8,546 22,330 10,129 1,150 522 5,583 2,532DBEB 19,340 8,773 22,780 10,333 1,150 522 5,695 2,583DBEC 19,550 8,868 23,090 10,474 1,150 522 5,773 2,618DBED 19,640 8,909 23,220 10,533 1,150 522 5,805 2,633DCEB 19,560 8,872 23,100 10,478 1,150 522 5,775 2,620D C E C 19,770 8,968 23,400 10,614 1,150 522 5,850 2,654
D-EDCED 19,860 9,008 23,540 10,678 1,150 522 5,885 2,669DDEB 19,870 9,013 23,530 10,673 1,150 522 5,883 2,668D D E C 20,080 9,108 23,840 10,814 1,150 522 5,960 2,703D D E D 20,170 9,149 23,970 10,873 1,150 522 5,993 2,718DEEB 20,030 9,086 23,750 10,773 1,150 522 5,938 2,693DEEC 20,240 9,181 24,050 10,909 1,150 522 6,013 2,727DEED 20,330 9,222 24,190 10,973 1,150 522 6,048 2,743
TABLE 1 – UNIT WEIGHTS LESS MOTOR ( G & H COMPRESSORS UNIT)
FORM 160.52-PA1
15YORK INTERNATIONAL
SHIPPING OPERATING REFRIGERANT LOADING PERSHELLS WEIGHT WEIGHT CHARGE ISOLATOR
(LBS) (KG) (LBS) (KG) (LBS) (KG) (LBS) (KG)ECDB 19,260 8,736 22,960 10,415 1,400 635 5,740 2,604E C D C 19,520 8,854 23,220 10,533 1,400 635 5,805 2,633
E-DECDD 19,260 8,736 23,090 10,474 1,400 635 5,773 2,618EDDB 19,490 8,841 23,280 10,560 1,400 635 5,820 2,640E D D C 19,750 8,959 23,540 10,678 1,400 635 5,885 2,669E D D D 19,490 8,841 23,410 10,619 1,400 635 5,853 2,655EBEB 20,230 9,176 24,200 10,977 1,400 635 6,050 2,744EBEC 20,450 9,276 24,510 11,118 1,400 635 6,128 2,779EBED 20,540 9,317 24,650 11,181 1,400 635 6,163 2,795ECEB 20,460 9,281 24,520 11,122 1,400 635 6,130 2,781
E-E ECEC 20,670 9,376 24,820 11,258 1,400 635 6,205 2,815ECED 20,760 9,417 24,960 11,322 1,400 635 6,240 2,830EDEB 20,680 9,380 24,830 11,263 1,400 635 6,208 2,816EDEC 20,900 9,480 25,150 11,408 1,400 635 6,288 2,852EDED 20,990 9,521 25,280 11,467 1,400 635 6,320 2,867EBFB 21,590 9,793 26,170 11,871 1,585 719 6,543 2,968EBFC 21,750 9,866 26,390 11,971 1,585 719 6,598 2,993EBFD 21,900 9,934 26,620 12,075 1,585 719 6,655 3,019ECFB 21,810 9,893 26,480 12,011 1,585 719 6,620 3,003
E-F ECFC 21,970 9,966 26,700 12,111 1,585 719 6,675 3,028ECFD 22,120 10,034 26,930 12,215 1,585 719 6,733 3,054EDFB 22,040 9,997 26,810 12,161 1,585 719 6,703 3,040EDFC 22,200 10,070 27,020 12,256 1,585 719 6,755 3,064EDFD 22,350 10,138 27,250 12,361 1,585 719 6,813 3,090FCEB 21,390 9,703 25,850 11,726 1,650 748 6,463 2,931FCEC 21,600 9,798 26,150 11,862 1,650 748 6,538 2,965
F-EFCED 21,690 9,839 26,290 11,925 1,650 748 6,573 2,981FDEB 21,620 9,807 26,180 11,875 1,650 748 6,545 2,969FDEC 21,840 9,907 26,490 12,016 1,650 748 6,623 3,004FDED 21,920 9,943 26,620 12,075 1,650 748 6,655 3,019FBFA 22,090 10,020 26,830 12,170 1,805 819 6,708 3,043FBFB 22,450 10,183 27,370 12,415 1,805 819 6,843 3,104FBFC 22,610 10,256 27,590 12,515 1,805 819 6,898 3,129FBFD 22,760 10,324 27,820 12,619 1,805 819 6,955 3,155FCFA 22,380 10,152 27,240 12,356 1,805 819 6,810 3,089
F-F FCFB 22,740 10,315 27,780 12,601 1,805 819 6,945 3,150FCFC 22,910 10,392 28,010 12,705 1,805 819 7,003 3,176FCFD 23,050 10,455 28,230 12,805 1,805 819 7,058 3,201FDFB 22,980 10,424 28,120 12,755 1,805 819 7,030 3,189FDFC 23,140 10,496 28,330 12,850 1,805 819 7,083 3,213FDFD 23,290 10,564 28,560 12,955 1,805 819 7,140 3,239FBGB 24,290 11,018 29,680 13,463 1,805 819 7,420 3,366FBGC 24,720 11,213 30,290 13,740 1,805 819 7,573 3,435FBGD 24,930 11,308 30,620 13,889 1,805 819 7,655 3,472FCGB 24,580 11,149 30,100 13,653 1,805 819 7,525 3,413
F-G FCGC 25,010 11,345 30,700 13,926 1,805 819 7,675 3,481FCGD 25,220 11,440 31,030 14,075 1,805 819 7,758 3,519FDGB 24,820 11,258 30,430 13,803 1,805 819 7,608 3,451FDGC 25,250 11,453 31,040 14,080 1,805 819 7,760 3,520FDGD 25,450 11,544 31,360 14,225 1,805 819 7,840 3,556
TABLE 1 – UNIT WEIGHTS LESS MOTOR (G & H COMPRESSORS UNITS) (Cont’d)
YORK INTERNATIONAL16
SHIPPING OPERATING REFRIGERANT LOADING PERSHELLS WEIGHT WEIGHT CHARGE ISOLATOR
(LBS) (KG) (LBS) (KG) (LBS) (KG) (LBS) (KG)
GBFA 24,110 10,936 29,350 13,313 1,900 862 7,338 3,328GBFB 24,480 11,104 29,900 13,563 1,900 862 7,475 3,391GBFC 24,640 11,177 30,110 13,658 1,900 862 7,528 3,414GBFD 24,790 11,245 30,340 13,762 1,900 862 7,585 3,441GCFA 24,450 11,091 29,830 13,531 1,900 862 7,458 3,383
G-FGCFB 24,810 11,254 30,370 13,776 1,900 862 7,593 3,444GCFC 24,970 11,326 30,580 13,871 1,900 862 7,645 3,468GCFD 25,120 11,394 30,810 13,975 1,900 862 7,703 3,494GDFA 24,900 11,295 30,470 13,821 1,900 862 7,618 3,455GDFB 25,260 11,458 31,010 14,066 1,900 862 7,753 3,517GDFC 25,430 11,535 31,230 14,166 1,900 862 7,808 3,541GDFD 25,580 11,603 31,460 14,270 1,900 862 7,865 3,568GBGB 26,320 11,939 32,210 14,610 1,900 862 8,053 3,653GBGC 26,750 12,134 32,820 14,887 1,900 862 8,205 3,722GBGD 26,950 12,225 33,140 15,032 1,900 862 8,285 3,758GCGB 26,650 12,088 32,680 14,824 1,900 862 8,170 3,706
G-G GCGC 27,080 12,283 33,290 15,100 1,900 862 8,323 3,775GCGD 27,290 12,379 33,610 15,245 1,900 862 8,403 3,811GDGB 27,110 12,297 33,330 15,118 1,900 862 8,333 3,780GDGC 27,530 12,488 33,930 15,391 1,900 862 8,483 3,848GDGD 27,740 12,583 34,250 15,536 1,900 862 8,563 3,884HBGB 28,440 12,900 35,150 15,944 2,235 1,014 8,788 3,986HBGC 28,870 13,095 35,760 16,221 2,235 1,014 8,940 4,055
H-GHBGD 29,070 13,186 36,080 16,366 2,235 1,014 9,020 4,091HCGB 29,010 13,159 35,960 16,311 2,235 1,014 8,990 4,078HCGC 29,440 13,354 36,570 16,588 2,235 1,014 9,143 4,147HCGD 29,650 13,449 36,890 16,733 2,235 1,014 9,223 4,183
TABLE 1 – UNIT WEIGHTS LESS MOTOR ( G & H COMPRESSORS UNITS) (Cont’d)
SHIPPING OPERATING REFRIGERANT LOADING PERSHELLS WEIGHT WEIGHT CHARGE ISOLATOR
(LBS) (KG) (LBS) (KG) (LBS) (KG) (LBS) (KG)GFGB 25,900 11,748 32,050 14,538 2,415 1,095 8,013 3,634GFGC 26,330 11,943 32,600 14,787 2,415 1,095 8,150 3,697
G-G GFGD 26,540 12,039 32,900 14,923 2,415 1,095 8,225 3,731GHGB 26,290 11,925 32,610 14,792 2,415 1,095 8,153 3,698GHGC 26,720 12,120 33,320 15,114 2,415 1,095 8,330 3,778GHGD 26,930 12,215 33,550 15,218 2,415 1,095 8,388 3,805GFHB 27,320 12,392 33,950 15,400 2,560 1,161 8,488 3,850GFHC 27,500 12,474 34,260 15,540 2,560 1,161 8,565 3,885
G-HGFHD 27,730 12,578 34,560 15,676 2,560 1,161 8,640 3,919GHHB 27,710 12,569 34,510 15,654 2,560 1,161 8,628 3,913GHHC 27,890 12,651 34,820 15,794 2,560 1,161 8,705 3,949GHHD 28,120 12,755 36,110 16,379 2,560 1,161 9,028 4,095HFGB 28,020 12,710 34,080 15,459 2,625 1,191 8,520 3,865HFGC 28,440 12,900 35,480 16,094 2,625 1,191 8,870 4,023
H-GHFGD 28,650 12,996 35,800 16,239 2,625 1,191 8,950 4,060HHGB 28,550 12,950 35,630 16,162 2,625 1,191 8,908 4,040HHGC 28,980 13,145 36,240 16,438 2,625 1,191 9,060 4,110HHGD 29,190 13,241 36,570 16,588 2,625 1,191 9,143 4,147HFHB 29,430 13,349 36,760 16,674 2,825 1,281 9,190 4,169HFHC 29,260 13,272 37,080 16,819 2,825 1,281 9,270 4,205
H - HHFHD 29,850 13,540 37,380 16,956 2,825 1,281 9,345 4,239HHHB 29,970 13,594 37,530 17,024 2,825 1,281 9,383 4,256H H H C 30,150 13,676 37,480 17,001 2,825 1,281 9,370 4,250H H H D 30,380 13,780 38,140 17,300 2,825 1,281 9,535 4,325
TABLE 2 - UNIT WEIGHTS LESS MOTOR (J COMPRESSOR UNITS � SEE NOTE 10)
FORM 160.52-PA1
17YORK INTERNATIONAL
TABLE 2 - UNIT WEIGHTS LESS MOTOR (J COMPRESSOR UNITS) (Cont�d) (SEE NOTE 10)
SHIPPING OPERATING REFRIGERANT LOADING PERSHELLS WEIGHT WEIGHT CHARGE ISOLATOR
(LBS) (KG) (LBS) (KG) (LBS) (KG) (LBS) (KG)HFJB 31,330 14,211 39,280 17,817 3,010 1,365 9,820 4,454HFJC 31,750 14,402 39,920 18,108 3,010 1,365 9,980 4,527
H-J HFJD 31,990 14,511 40,250 18,257 3,010 1,365 10,063 4,564HHJB 31,870 14,456 40,050 18,167 3,010 1,365 10,013 4,542HHJC 32,280 14,642 40,680 18,452 3,010 1,365 10,170 4,613HHJD 32,520 14,751 41,010 18,602 3,010 1,365 10,253 4,651JFHB 32,410 14,701 40,580 18,407 3,310 1,501 10,145 4,602JFHC 32,590 14,783 40,890 18,548 3,310 1,501 10,223 4,637JFHD 32,820 14,887 41,180 18,679 3,310 1,501 10,295 4,670JGHB 32,780 14,869 41,100 18,643 3,310 1,501 10,275 4,661
J-H JGHC 32,960 14,951 41,410 18,784 3,310 1,501 10,353 4,696JGHD 33,190 15,055 41,710 18,920 3,310 1,501 10,428 4,730JHHB 33,140 15,032 41,620 18,879 3,310 1,501 10,405 4,720JHHC 33,330 15,118 41,940 19,024 3,310 1,501 10,485 4,756JHHD 33,530 15,209 42,240 19,160 3,310 1,501 10,560 4,790JFJB 34,310 15,563 43,100 19,550 3,495 1,585 10,775 4,888JFJC 34,720 15,749 43,730 19,836 3,495 1,585 10,933 4,959JGJD 34,960 15,858 44,050 19,981 3,495 1,585 11,013 4,995JGJB 34,880 15,822 43,620 19,786 3,495 1,585 10,905 4,947
J-J JGJC 35,090 15,917 44,250 20,072 3,495 1,585 11,063 5,018JGJD 35,330 16,026 44,580 20,221 3,495 1,585 11,145 5,055JHJB 35,040 15,894 44,140 20,022 3,495 1,585 11,035 5,005JHJC 35,450 16,080 44,780 20,312 3,495 1,585 11,195 5,078JHJD 35,700 16,194 45,110 20,462 3,495 1,585 11,278 5,115TFTB 37,260 16,901 47,230 21,424 3,995 1,812 11,808 5,356TFTC 37,750 17,123 47,970 21,759 3,995 1,812 11,993 5,440TFTD 38,010 17,241 48,330 21,922 3,995 1,812 12,083 5,481TGTB 37,680 17,092 47,630 21,605 3,995 1,812 11,908 5,401TGTC 38,170 17,314 48,570 22,031 3,995 1,812 12,143 5,508
T-T TGTD 38,440 17,436 48,940 22,199 3,995 1,812 12,235 5,550THTB 38,110 17,287 48,440 21,972 3,995 1,812 12,110 5,493THTC 38,600 17,509 49,180 22,308 3,995 1,812 12,295 5,577THTD 38,860 17,627 49,540 22,471 3,995 1,812 12,385 5,618TFVB 41,430 18,793 52,410 23,773 4,290 1,946 13,103 5,943TFVC 41,630 18,883 52,780 23,941 4,290 1,946 13,195 5,985TFVD 42,450 19,255 53,910 24,454 4,290 1,946 13,478 6,113TGVB 41,860 18,988 53,020 24,050 4,290 1,946 13,255 6,012TGVC 42,060 19,078 53,390 24,218 4,290 1,946 13,348 6,054
T-V TGVD 42,880 19,450 54,520 24,730 4,290 1,946 13,630 6,183THVB 42,280 19,178 53,620 24,322 4,290 1,946 13,405 6,081THVC 42,480 19,269 53,990 24,490 4,290 1,946 13,498 6,122THVD 43,300 19,641 56,120 25,456 4,290 1,946 14,030 6,364VFTB 39,620 17,972 50,580 22,943 3,820 1,733 12,645 5,736VFTC 40,110 18,194 51,320 23,279 3,820 1,733 12,830 5,820
V-T VFTD 40,380 18,316 51,690 23,447 3,820 1,733 12,923 5,862VHTB 40,220 18,244 51,430 23,329 3,820 1,733 12,858 5,832VHTC 40,700 18,462 52,170 23,664 3,820 1,733 13,043 5,916VHTD 40,970 18,584 52,540 23,832 3,820 1,733 13,135 5,958VFVB 42,700 19,369 54,670 24,798 4,150 1,882 13,668 6,200VFVC 42,900 19,459 55,040 24,966 4,150 1,882 13,760 6,242
V-V VFVD 43,720 19,831 56,170 25,479 4,150 1,882 14,043 6,370VHVB 43,290 19,636 55,520 25,184 4,150 1,882 13,880 6,296VHVC 43,490 19,727 55,880 25,347 4,150 1,882 13,970 6,337VHVD 44,310 20,099 57,010 25,860 4,150 1,882 14,253 6,465WFVB 46,180 20,947 59,850 27,148 4,460 2,023 14,963 6,787WFVC 46,380 21,038 60,210 27,311 4,460 2,023 15,053 6,828
W-V WFVD 47,200 21,410 61,340 27,824 4,460 2,023 15,335 6,956WHVB 47,550 21,569 61,790 28,028 4,460 2,023 15,448 7,007WHVC 47,740 21,655 62,150 28,191 4,460 2,023 15,538 7,048WHVD 48,570 22,031 63,290 28,708 4,460 2,023 15,823 7,177
YORK INTERNATIONAL18
TABLE 3 � MARINE WATER BOX WEIGHTS � 150 LB. & 300 LB. � G & H COMPRESSOR UNITSWEIGHTS (To be added to Standard Unit weights).
SHIPPING WEIGHT OPERATING WEIGHT SHIPPING WEIGHT OPERATING WEIGHTCOOLER
INCREASE � LBS. INCREASE � LBS.COND.
INCREASE � LBS. INCREASE � LBS.CODE
1-PASS 2-PASS 3-PASS 1-PASS 2-PASS 3-PASSCODE
1-PASS 2-PASS 3-PASS 1-PASS 2-PASS 3-PASS
C, D, E 1,602 1,574 1,394 1,832 1,814 1,624 C, D 1,800 798 1,620 1,898 893 1,710
F 2,296 1,122 2,129 2,568 1,394 2,400 E 2,572 1,167 2,340 2,670 1,261 2,510
G 2,838 1,238 2,339 3,206 1,606 2,707 F 1,046 752 900 1,159 865 970
H 3,468 1,575 2,916 3,945 2,052 3,393 G 1,382 965 1,100 1,576 1,159 1380
TABLE 5 � MARINE WATER BOX WEIGHTS � 150 LB. & 300 LB. (KG) � G & H COMPRESSOR UNITS
SHIPPING WEIGHT OPERATING WEIGHT SHIPPING WEIGHT OPERATING WEIGHTCOOLER
INCREASE � KG INCREASE � KGCOND.
INCREASE � KG INCREASE � KGCODE
1-PASS 2-PASS 3-PASS 1-PASS 2-PASS 3-PASSCODE
1-PASS 2-PASS 3-PASS 1-PASS 2-PASS 3-PASS
C, D, E 727 714 632 831 823 737 C, D 816 362 735 861 405 776
F 1,041 509 966 1,165 632 1,089 E 1,167 529 1,061 1,211 572 1,139
G 1,287 562 1,061 1,454 728 1,228 F 474 341 408 526 392 440
H 1,573 714 1,323 1,789 931 1,539 G 627 438 499 715 526 626
WEIGHTS (To be added to Standard Unit weights).
TABLE 6 � MARINE WATER BOX WEIGHTS � 150 LB. (KG) � J COMPRESSOR UNITS
SHIPPING WEIGHT OPERATING WEIGHT SHIPPING WEIGHT OPERATING WEIGHTCOOLER
INCREASE � KG INCREASE � KGCOND.
INCREASE � KG INCREASE � KGCODE
1-PASS 2-PASS 3-PASS 1-PASS 2-PASS 3-PASSCODE
1-PASS 2-PASS 3-PASS 1-PASS 2-PASS 3-PASS
G 1,095 442 869 1,220 556 998 G 1,080 517 758 1,134 567 805
H 1,249 687 1,270 1,424 805 1,452 H 1,132 549 1,039 1,202 608 1,184
J, T 1,622 778 1,542 1,837 953 1,769 J, T 1,356 674 1,313 1,538 771 1,465
V 1,706 826 1,569 2,019 1,129 1,814 V 1,783 862 1,730 2,014 1,043 2,118
W 2,109 1,114 1,964 2,477 1,483 2,322
WEIGHTS (To be added to Standard Unit weights).
TABLE 4 � MARINE WATER BOX WEIGHTS � 150 LB. � J COMPRESSOR UNITSWEIGHTS (To be added to Standard Unit weights).
SHIPPING WEIGHT OPERATING WEIGHT SHIPPING WEIGHT OPERATING WEIGHTCOOLER
INCREASE � LBS. INCREASE � LBS.COND.
INCREASE � LBS. INCREASE � LBS.CODE
1-PASS 2-PASS 3-PASS 1-PASS 2-PASS 3-PASSCODE
1-PASS 2-PASS 3-PASS 1-PASS 2-PASS 3-PASS
G 2,415 975 1,915 2,690 1,225 2,200 G 2,380 1,140 1,670 2,500 1,250 1,775
H 2,775 1,514 2,800 3,140 1,775 3,200 H 2,495 1,210 2,290 2,650 1,340 2,610
J, T 3,576 1,715 3,400 4,050 2,100 3,900 J, T 2,990 1,485 2,895 3,390 1,700 3,230
V 3,760 1,820 3,460 4,450 2,490 4,000 V 3,930 1,900 3,815 4,440 2,300 4,670
W 4,650 2,455 4,330 5,460 3,270 5,120
FORM 160.52-PA1
19YORK INTERNATIONAL
FIG. 7 � MOTOR COMPRESSOR DIMENSIONS
COMPRESSOR WEIGHTS (Standard & Metric)
COMPR./ A B C D
MOTOR (mm) (mm) (mm) (mm)
G 4 1,026 949 854 171
H0/H4 1,026 949 854 171
H1/H5 1,026 949 854 171
H2/H6 1,067 949 854 171
H3/H8 1,067 949 854 171
J1/J2 1,216 1,121 933 178
J3/J4 1,416 1,207 1,035 178
COMPR./A B C D
MOTOR
G4 3'�4-3/8" 3'�1-3/8" 2'�9-5/8" 6-3/4"
H0/H4 3'�4-3/8" 3'�1-3/8" 2'�9-5/8" 6-3/4"
H1/H5 3'�4-3/8" 3'�1-3/8" 2'�9-5/8" 6-3/4"
H2/H6 3'�6" 3'�1-3/8" 2'�9-5/8" 6-3/4"
H3/H8 3'�6" 3'�1-3/8" 2'�9-5/8" 6-3/4"
J1/J2 3'�11-7/8" 3'�8-1/8" 3'�0-3/4" 7"
J3/J4 4'�7-3/4" 3'�11-1/2" 3'�4-3/4" 7"
COMPRESSOR WEIGHTCODE LBS. KG
G4, H0/H4, H1/H5, H2/H6/H7 & H3/H8 3,500 1,588J1 & J2 4,000 1,814J3 & J4 5,000 2,268
YORK INTERNATIONAL20
FIG. 8 � NOZZLE ARRANGEMENTS - COOLERS - G & H COMPRESSOR UNITS (150# COMPACT WATER BOXES � STD. DIMENSIONS)
COOLERCOOLER NOZZLE PIPE SIZE
NOZZLE DIMENSIONSSHELL
NO. OF PASSES 1-PASS 2-PASS 3-PASSCODE
1 2 3 AA FF BB DD EE FF BB DD FF
C 12" 8" 6" 1'�6-3/8" 1'�7" 1'�2-3/8" 1'�10-3/8" 7" 1'�7" 1'�0-1/2" 2'�0-1/4" 1'�7"
DB, DC, DD 12" 8" 8" 1'�6-5/8" 1'�8-1/2" 1'�1-5/8" 1'�11-5/8" 9" 1'�8-1/2" 0'�11-5/8" 2'�1-5/8" 1'�8-1/2"
DE 12" 8" 8" 1'�7-3/4" 1'�8-1/2" 1'�2-3/4" 2'�0-3/4" 9" 1'�8-1/2" 1'�0-3/4" 2'�2-3/4" 1'�8-1/2"
E 14" 10" 8" 1'�7-1/4" 1'�9-1/2" 1'�2-1/4" 2'�0-1/4" 9" 1'�9-1/2" 1'�0-1/4" 2'�2-1/4" 1'�9-1/2"
F 14" 10" 8" 1'�8-1/2" 2'�0" 1'�3-1/2" 2'�1-1/2" 9" 2'�0" 1'�1-1/2" 2'�3-1/2" 2'�0"
G 16" 12" 10" 1'�9-5/8" 2'�1-1/4" 1'�3-5/8" 2'�3-5/8" 10-3/4" 2'�1-1/4" 1'�0-5/8" 2'�6-5/8" 2'�1-1/4"
H 16" 12" 10" 1'�10-3/4" 2'�3" 1'�4-3/4" 2'�4-3/4" 10-3/4" 2'�3" 1'�1-3/4" 2'�7-3/4" 2'�3"
NOTES:1. Standard water nozzles are furnished as welding stub-outs with Victaulic grooves, allowing the option of welding, flanges, or use of
Victaulic couplings. Factory installed, class 150 (ANSI B16.5, round slip-on, forged carbon steel with 1/16" raised face), water flangednozzles are optional. Companion flanges, nuts, bolts, and gaskets are not furnished.
2. One-, two- and three-pass nozzle arrangements are available only in pairs shown and for all shell codes. Any pair of cooler nozzles maybe used in combination with any pair of condenser nozzles.
3. Cooler and condenser water must enter the water box through the bottom connection to achieve rated performance.4. Connected piping should allow for removal of compact water boxes for tube access and cleaning.
1-PASS
2-PASS
3-PASS
NOZZLE
ARRANGEMENTS
NO. OF COOLER
PASSES IN OUT
3G N
P F
NOZZLE
ARRANGEMENTS
NO. OF COOLER
PASSES IN OUT
D C
2E B
L K
M J
NOZZLE
ARRANGEMENTS
NO. OF COOLER
PASSES IN OUT
1A H
H A
LD01340
COOLER COOLER
FRONTOF
UNIT
FLOOR LINE
AA
7/8" FF
COMPRESSOR END MOTOR END
FF 7/8"
AA
FRONTOF
UNIT
FLOOR LINE
COMPRESSOR END MOTOR END
7/8"7/8"
COOLER COOLER
DD
BBDD
BB
FF
EE
FF
EEEE EE
FLOOR LINE
FRONTOF
UNIT
COMPRESSOR END MOTOR END
A H
B C
D E
J
L
K
M
DD
BB
7/8"
BB
7/8"
COOLER COOLER
FFFF
F
G
N
P DD
FORM 160.52-PA1
21YORK INTERNATIONAL
CONDENSER CONDENSER NOZZLE PIPE SIZE
NOZZLE DIMENSIONSSHELL
NO. OF PASSES 1-PASS 2-PASS 3-PASSCODE
1 2 3 CC GG BB DD GG BB DD GG
C 10" 8" 6" 2'�11-3/4" 1'�5-1/2" 2'�4-3/4" 3'�6-3/4" 1�5-1/2" 2'�5-3/4" 3'�7-1/4" 1'�5-1/2"
D 12" 8" 6" 2'�11-3/4" 1'�5-1/2" 2'�4-3/4" 3'�6-3/4" 1�5-1/2" 2'�5-3/4" 3'�7-3/4" 1'�5-1/2"
E 14" 10" 8" 3'�1-1/4" 1'�5-1/2" 2'�5-1/4" 3'�9-3/4" 1�5-1/2" 2'�6-1/4" 3'�10-1/4" 1'�5-1/2"
F 16" 12" 10" 3'�2-3/4" 1'�7" 2'�5" 4'�0-1/2" 1'�7" 2'�6-1/4" 4'�1-1/2" 1'�7"
G 16" 14" 10" 3'�4-3/4" 1'�9" 2'�6" 4'�3-1/2" 1'�9" 2'�7-1/4" 4'�3-3/4" 1'�9"
1-PASS
2-PASS
3-PASS
FIG. 9 � NOZZLE ARRANGEMENTS - CONDENSERS - G & H COMPRESSOR UNITS (150# COMPACT WATER BOXES � STD. DIMENSIONS)
NOZZLE
ARRANGEMENTS
NO. OF COND.
PASSES IN OUT
1P Q
Q P
NOZZLE
ARRANGEMENTS
NO. OF COND.
PASSES IN OUT
3V Y
X W
NOZZLE
ARRANGEMENTS
NO. OF COND.
PASSES IN OUT
2R S
T U
LD01341
CC
COND. COND.
P Q
7/8" 7/8"FLOOR LINE MOTOR ENDCOMPRESSOR END
GG GG
CC
FRONTOF
UNIT
7/8" 7/8"MOTOR ENDCOMPRESSOR END
COND. COND.
FRONTOF
UNIT
DD
BB
DD
BB
U
T
S
R
GG GG
FRONTOF
UNIT
DD
BBCOND. COND.
7/8"
COMPRESSOR END MOTOR END7/8"
DD
BB
GG GG
V
W Y
X
FLOOR LINE
FLOOR LINE
YORK INTERNATIONAL22
NOTES:1. Standard water nozzles are furnished as welding stub-outs with Victaulic grooves, allowing the option of welding, flanges, or use of
Victaulic couplings. Factory installed, class 150 (ANSI B16.5, round slip-on, forged carbon steel with 1/16" raised face), water flangednozzles are optional. Companion flanges, nuts, bolts, and gaskets are not furnished.
2. Add 7/8" to all height dimensions to obtain installed height when using neoprene mounts or optional spring vibration isolator mounts.3. One-, two- and three-pass nozzle arrangements are available only in pairs shown and for all shell codes. Any pair of cooler nozzles may
be used in combination with any pair of condenser nozzles.4. Connected piping should allow for removal of compact water boxes for tube access and cleaning.
NOZZLE
ARRANGEMENTS
NO. OF COOLER
PASSES IN OUT
1A H
H A
NOZZLE
ARRANGEMENTS
NO. OF COOLER
PASSES IN OUT
B C
2C B
J K
K J
1-PASS
2-PASS
3-PASS
LD02676
COOLER COOLER
FRONT
OF
UNIT
FLOOR LINE
AA
7/8" FF
COMPRESSOR END MOTOR END
FF 7/8"
AA
FRONT
OF
UNIT
FLOOR LINE
COMPRESSOR END MOTOR END
7/8"7/8"
COOLER COOLER
BB BB
FF
EE
FF
EEEE EE
FLOOR LINE
FRONT
OF
UNIT
COMPRESSOR END MOTOR END
A H
B C J K
BB
7/8"
BB
7/8"
COOLER COOLER
F N
FFFF
FIG. 10 � NOZZLE ARRANGEMENTS - COOLERS - J COMPRESSOR UNITS (150# COMPACT WATER BOXES - STANDARD DIMENSIONS)
COOLER
COOLERNOZZLE PIPE SIZE
NOZZLE DIMENSIONS
SHELL NO. OF PASSES 1-PASS 2-PASS 3-PASS
CODE 1 2 3 AA FF BB EE FF BB FF
G 14" 10" 8" 1'�11-1/8" 2'�0" 1'�11-1/8" 11" 2'�0" 1'�11-1/8" 2'�0"
H 16" 12" 10" 2'�0-3/4" 2'�2-1/4" 2'�0-3/4" 11" 2'�2-1/4" 2'�0-3/4" 2'�2-1/4"
J 18" 14" 12" 2'�1-3/4" 2'�5-1/2" 2'�1-3/4" 11" 2'�5-1/2" 2'�0-3/4" 2'�5-1/2"
T 18" 14" 12" 2'�1-3/4" 2'�5-1/2" 2'�1-3/4" 11" 2'�5-1/2" 2'�0-3/4" 2'�5-1/2"
V 20" 16" 12" 2'�5-1/4" 2'�5-1/2" 2'�5-1/4" 1'�1" 2'�5-1/2" 2'�5-1/4" 2'�5-1/2"
W 20" 18" 14" 2'�7-1/4" 2'�8" 2'�7-1/4" 1'�3" 2'�8" 2'�7-1/4" 2'�8"
NOZZLE
ARRANGEMENTS
NO. OF COOLER
PASSES IN OUT
3F N
N F
FORM 160.52-PA1
23YORK INTERNATIONAL
NOZZLE
ARRANGEMENTS
NO. OF COND.
PASSES IN OUT
2R S
T U
NOZZLE
ARRANGEMENTS
NO. OF COND.
PASSES IN OUT
1P Q
Q P
1-PASS
2-PASS
3-PASS
See Note*
See Note*
See Note*
FRONT
OF
UNIT
CC
COND. COND.
P Q
7/8" 7/8"FLOOR LINE
MOTOR ENDCOMPRESSOR END
GG GG
CC
7/8" 7/8"
MOTOR ENDCOMPRESSOR END
COND. COND.
FRONT
OF
UNIT
DD
BB
DD
BB
U
T
S
R
GG GGFLOOR LINE
FRONT
OF
UNIT
DD
BB
COND. COND.
7/8"
COMPRESSOR END MOTOR END
7/8"
DD
BB
GG GG
V
W Y
X
FLOOR LINE
LD02677
CONDENSER CONDENSER NOZZLE PIPE SIZE
NOZZLE DIMENSIONSSHELL
NO. OF PASSES 1-PASS 2-PASS 3-PASSCODE
1 2 3 CC GG BB DD GG BB DD GG
G* 16" 14" 10" 3'�4-3/4" 1'�9" 2'�6" 4'�3-1/2" 1'�9" 2'�7-1/4" 4'�3-3/4" 1'�9"
H 20" 16" 12" 3'�6-3/4" 1'�11" 2'�7-3/4" 4'�5-3/4" 1'�11" 2'�7-1/4" 4'�7-1/2" 1'�11"
J 20" 16" 14" 3'�8-3/4" 2'�1" 2'�8-1/4" 4'�9-1/4" 2'�1" 2'�9-1/4" 4'�10-3/4" 2'�1"
T 20" 16" 14" 3'�8-3/4" 2'�1" 2'�8-1/4" 4'�9-1/4" 2'�1" 2'�9-1/4" 4'�10-3/4" 2'�1"
V 20" 18" 14" 3'�11-1/4" 2'�3-1/2" 2'�9-3/4" 5'�0-3/4" 2'�3-1/2" 2'�11-1/4" 5'�2-7/8" 2'�3-1/2"
* NOTE: �G� Condenser Water Boxes are square; other codes are round as shown.
FIG. 11 � NOZZLE ARRANGEMENTS - CONDENSERS - J COMPRESSOR UNITS (150# COMPACT WATER BOXES - STD. DIMENSIONS)
NOZZLE
ARRANGEMENTS
NO. OF COND.
PASSES IN OUT
3V Y
X W
YORK INTERNATIONAL24
FIG. 12 � NOZZLE ARRANGEMENTS - COOLERS - G & H COMPRESSOR UNITS (150# MARINE WATER BOXES � STD. DIMENSIONS)
LD01342A
A
8
3
B
D
B
B
8
C
6
A
1OUT
COMPR. END
D D
A
1 6 OUTIN
7/8" MOTOR ENDCOMPR. END FLOORLINE
1
D D
IN
7/8" MOTOR END FLOORLINE
COMPR. ENDMOTOR ENDCOMPR. END MOTOR END
COMPR. ENDMOTOR ENDCOMPR END MOTOR END
FLOORLINE
FLOORLINE
FLOORLINE
FLOORLINE
D
7/8"
IN7
OUT
A
9
D
4
A
OUT
IN
7/8"
C D C
IN
5
10
7/8"
OUT
A
2IN
OUT
D C
7/8"
FRONT OF UNIT
FRONT OF UNIT
FRONT OF UNIT FRONT OF UNIT
FRONT OF UNIT
FRONT OF UNIT
1-PASS
1-PASS
2-PASS
2-PASS
3-PASS
3-PASS
NOTES:1. All dimensions are approximate. Certified dimensions are available upon request.2. Standard water nozzles are Schedule 40 pipe size, furnished as welding stub-outs with Victaulic grooves, allowing the option of
welding, flanges, or use of Victaulic couplings. Factory installed, class 150 (ANSI B16.5, round slip-on, forged carbon steel with 1/16"raised face), water flanged nozzles are optional. Companion flanges, nuts, bolts, and gaskets are not furnished.
3. One-, two-, and three-pass nozzle arrangements are available only in pairs shown and for all shell codes. Any pair of cooler nozzlesmay be used in combination with any pair of condenser nozzles. Compact water boxes on one heat exchanger may be used with MarineWater Boxes on the other heat exchanger.
4. Water must enter the water box through the bottom connection to achieve rated performance.5. Add 1/2" to �A� & �C� Dimensions when flanges are furnished.
COOLER COOLER NOZZLE DIMENSIONS
SHELL 1-PASS 2-PASS 3-PASS
CODE A D A B C D A B C D
C 3'�1-5/8" 1'�7" 3'�1-5/8" 1'�2-5/8" 1'�11-3/4" 1'�7" 3'�1-5/8" 1'�0-5/8" 1'�11-3/4" 1'�7"
DB, DC, DD 3'�3-7/8" 1'�8-1/2" 3'�3-7/8" 1'�1-5/8" 2'�3" 1'�8-1/2" 3'�3-7/8" 0'�11-7/8" 2'�3" 1'�8-1/2"
DE 3'�5" 1'�8-1/2" 3'�5" 1'�2-3/4" 2'�3" 1'�8-1/2" 3'�5" 1'�1" 2'�3" 1'�8-1/2"
E 3'�4-1/2" 1'�9-1/2" 3'�4-1/2" 1'�2-1/4" 2'�3" 1'�9-1/2" 3'�4-1/2" 1'�0-1/4" 2'�3" 1'�9-1/2"
F 3'�5-3/4" 2'�0" 3'�5-3/4" 1'�3-1/2" 2'�3" 2'�0" 3'�5-3/4" 1'�1-1/2" 2'�3" 2'�0"
G 3'�11-1/8" 2'�1-1/4" 3'�10-1/8" 1'�4-3/4" 2'�7" 2'�1-1/4" 3'�10-1/8" 1'�0-5/8" 2'�7" 2'�1-1/4"
H 4'�0-1/4" 2'�3" 3'�11-1/4" 1'�5-7/8" 2'�7" 2'�3" 3'�11-1/4" 1'�1-3/4" 2'�7" 2'�3"
FORM 160.52-PA1
25YORK INTERNATIONAL
GK(2-PASSBACK HEAD)
COOLER
3-PASS
IN OUT
5 10
9 4
COOLER
2-PASS
IN OUT
2 3
7 8
COOLER
1-PASS
IN OUT
1 6
6 1
FIG. 12 � (CONT�D)
LD01342B
H
COOLER NOZZLE PIPE SIZE
SHELL NO. OF PASSES
CODE 1 2 3
C 12" 8" 6"
D 12" 8" 8"
E 14" 10" 8"
F 14" 10" 8"
G 16" 12" 10"
H 16" 12" 10"
COOLER COOLER NOZZLE
SHELL DIMENSIONS (3-PASS)
CODE G H
C 7-1/4" 1'�3-5/8"
D 8-3/4" 1'�6-7/8"
E 9-3/4" 1'�8-7/8"
F 9-3/4" 1'�8-7/8"
G 9-3/4" 1'�9-3/8"
H 9-3/4" 1'�9-3/8"
COOLER COOLER NOZZLE
SHELL DIMENSIONS (2-PASS)
CODE G H K
C 8-3/4" 1'�6-5/8" 5-5/8"
D 8-3/4" 1'�6-7/8" 5-7/8"
E 9-3/4" 1'�8-7/8" 5-7/8"
F 9-3/4" 1'�8-7/8" 5-7/8"
G 11-1/4" 2'�0-3/8" 6-1/4"
H 11-1/4" 2'�0-3/8" 6-1/4"
COOLER COOLER NOZZLE
SHELL DIMENSIONS (1-PASS)
CODE G H
C 11-1/4" 1'�11-5/8"
D 11-1/4" 1'�11-7/8"
E 1'�0-1/4" 2'�1-7/8"
F 1'�0-1/4" 2'�1-7/8"
G 1'�1-1/4" 2'�4-3/8"
H 1'�1-1/4" 2'�4-3/8"
YORK INTERNATIONAL26
15
CL
CL
CL CL
CL CL
CL
C
CL CL
DD
11 16
A
7/8FLOORLINE
COMPR. END MOTOR END7/8
D
18
A
7/8
7/8 7/8
17
BB
CFLOORLINE
COMPR. END MOTOR END
DD
A
20
B
7/8 C
COMPR. END MOTOR END
FLOORLINE 7/8 7/8
7/8
MOTOR ENDCOMPR. END
FLOORLINE
A
D D
14
B
7/8
MOTOR ENDCOMPR. END
FLOORLINE
B
19
7/8
A12
13
D
MOTOR ENDCOMPR. END
FLOORLINE 7/8
A
11 16
DD
C
FRONT OF UNITFRONT OF UNIT
FRONT OF UNIT FRONT OF UNIT
FRONT OF UNIT FRONT OF UNIT
NOTES:
1. All dimensions are approximate. Certified dimensions are available upon request.
2. Standard water nozzles are Schedule 40 pipe size, furnished as welding stub-outs with Victaulic grooves, allowing the option ofwelding, flanges, or use of Victaulic couplings. Factory installed, class 150 (ANSI B16.5, round slip-on, forged carbon steel with 1/16"raised face), water flanged nozzles are optional. Companion flanges, nuts, bolts, and gaskets are not furnished.
3. One-, two-, and three-pass nozzle arrangements are available only in pairs shown and for all shell codes. Any pair of cooler nozzlesmay be used in combination with any pair of condenser nozzles. Compact water boxes on one heat exchanger may be used with MarineWater Boxes on the other heat exchanger.
4. Condenser water must enter the water box through the bottom connection for proper operation of the sub-cooler to achieve ratedperformance.
5. Add 1/2" to �A� & �C� dimensions when flanges are furnished.
FIG. 13 � NOZZLE ARRANGEMENTS - CONDENSERS - G & H COMPRESSOR UNITS (150# MARINE WATER BOXES � STD. DIMENSIONS)
1-PASS
2-PASS
3-PASS
1-PASS
2-PASS
3-PASS
COND. CONDENSER NOZZLE DIMENSIONS
SHELL 1-PASS 2-PASS 3-PASS
CODE A D A B C D A B C D
C 4'�10-1/2" 1'�5-1/2" 4'�10-1/2" 2'�7" 1'�10-3/4" 1'�5-1/2" 4'�10-1/2" 2'�6-1/2" 1'�10-3/4" 1'�5-1/2"
D 4'�10-1/2" 1'�5-1/2" 4'�10-1/2" 2'�7" 1'�10-3/4" 1'�5-1/2" 4'�10-1/2" 2'�6-1/2" 1'�10-3/4" 1'�5-1/2"
E 5'�1-7/8" 1'�5-1/2" 5'�1-7/8" 2'�6-3/4" 2'�0-5/8" 1'�5-1/2" 5'�1-7/8" 2'�5-1/4" 2'�0-5/8" 1'�5-1/2"
F 5'�6" 1'�7" 5'�5" 2'�7-3/4" 2'�2-1/4" 1'�7" 5'�5" 2'�6-3/4" 2'�2-1/4" 1'�7"
G 5'�9-7/8" 1'�9" 5'�8-7/8" 2'�8-3/4" 2'�4-1/8" 1'�9" 5'�8-7/8" 2'�7-1/4" 2'�4-1/8" 1'�9"
LD01343a
FORM 160.52-PA1
27YORK INTERNATIONAL
FIG. 13 � (CONT�D)
TUBESHEET
TUBESHEET
G
K(2-PASSBACK HEAD)
LD01343B
CONDENSER
1-PASS
IN OUT
11 16
16 11
CONDENSER
2-PASS
IN OUT
12 13
17 18
CONDENSER
3-PASS
IN OUT
15 20
19 14
CONDENSER COND. NOZZLE
SHELL DIMENSIONS (1-PASS)
CODE G H
C 9-5/8" 1'�8-5/8"
D 11-1/8" 1'�11-5/8"
E 1'�0-1/4" 2'�1-7/8"
F 1'�1-1/4" 2'�4"
G 1'�1-1/4" 2'�4-3/8"
CONDENSER COND. NOZZLE
SHELL DIMENSIONS (2-PASS)
CODE G H K
C 8-5/8" 1'�6-5/8" 5-1/2"
D 8-5/8" 1'�6-5/8" 5-1/2"
E 9-3/4" 1'�8-7/8" 5-3/4"
F 11-1/4" 2'�0" 5-3/4"
G 1'�0-1/4" 2'�2-3/8" 6"
COND. NOZZLE PIPE SIZE
SHELL NO. OF PASSES
CODE 1 2 3
C 10" 8" 6"
D 12" 8" 6"
E 14" 10" 8"
F 16" 12" 10"
G 16" 14" 10"
CONDENSER COND. NOZZLE
SHELL DIMENSIONS (3-PASS)
CODE G HC 7-5/8" 1'�4-5/8"
D 7-5/8" 1'�4-5/8"
E 8-3/4" 1'�6-7/8"
F 9-3/4" 1'�9"
G 9-5/8" 1'�9-1/8"
YORK INTERNATIONAL28
COMPR. END MOTOR END7/8" FLOORLINE
A
61
DD
IN OUT
COMPR. END MOTOR END7/8" FLOORLINE
D D
OUT IN1 6
2
3
A
8
IN
OUT
7/8" MOTOR END FLOORLINE
COMPR. END
D CC D
8
7
B
7/8"COMPR. END MOTOR END FLOORLINE
OUT
IN A
OUT
7/8"COMPR. END MOTOR END FLOORLINE
A
D C
4
IN9
B
DC
B
5IN
7/8" MOTOR END FLOORLINE
COMPR. END
D
A
10OUT
A
FRONT OF UNIT
FRONT OF UNITFRONT OF UNIT
FRONT OF UNIT FRONT OF UNIT
FRONT OF UNIT
NOTES:1. All dimensions are approximate. Certified dimensions are available upon request.2. Standard water nozzles are Schedule 40 pipe size, furnished as welding stub-outs with Victaulic grooves, allowing the option of
welding, flanges, or use of Victaulic couplings. Factory installed, class 150 (ANSI B16.5, round slip-on, forged carbon steel with 1/16"raised face), water flanged nozzles are optional. Companion flanges, nuts, bolts, and gaskets are not furnished.
3. Add 7/8" to all height dimensions to obtain installed height when using neoprene mounts or optional spring vibration isolator mounts.4. One-, two-, and three-pass nozzle arrangements are available only in pairs shown and for all shell codes. Any pair of cooler nozzles
may be used in combination with any pair of condenser nozzles. Compact water boxes on one heat exchanger may be used with MarineWater Boxes on the other heat exchanger.
5. Water must enter the water box through the bottom connection to achieve rated performance.6. Add 1/2" to �A� and �C� dimensions when flanges are furnished.
FIG. 14 � NOZZLE ARRANGEMENTS - COOLERS - J COMPRESSOR UNITS (150# MARINE WATER BOXES - STD. DIMENSIONS)
1-PASS 1-PASS
2-PASS2-PASS
3-PASS 3-PASS
LD02708A
COOLER COOLER NOZZLE DIMENSIONS
SHELL 1-PASS 2-PASS 3-PASS
CODE A D A B C D A B C D
G 3'�9-1/8" 2'�0" 3'�9-1/8" 1'�6-1/4" 2'�5" 2'�0" 3'�9-1/8" 1'�4-1/8" 2'�5" 2'�0"
H 4'�5-1/4" 2'�2-1/4" 4'�5-1/4" 2'�2-3/4" 2'�7-1/4" 2'�2-1/4" 4'�5-1/4" 2'�1-3/4" 2'�7-1/4" 2'�2-1/4"
J 3'�11-3/4" 2'�5-1/2" 3'�11-3/4" 1'�9-3/4" 2'�10-1/4" 2'�5-1/2" 3'�11-3/4" 1'�8-3/4" 2'�10-1/4" 2'�5-1/2"
T 3'�11-3/4" 2'�5-1/2" 3'�11-3/4" 1'�9-3/4" 2'�10-1/4" 2'�5-1/2" 3'�11-3/4" 1'�8-3/4" 2'�10-1/4" 2'�5-1/2"
V 4'�3-1/4" 2'�5-1/2" 4'�3-1/4" 2'�1-1/2" 2'�10-1/4" 2'�5-1/2" 4'�3-1/4" 1'�11-7/8" 2'�10-1/4" 2'�5-1/2"
W 4'�6-1/2" 2'�6" 4'�6-1/2" 2'�3-1/2" 3'�2" 2'�6" 4'�6-1/2" 2'�1-1/2" 3'�1-7/8" 2'�6"
FORM 160.52-PA1
29YORK INTERNATIONAL
FIG. 14 � (CONT�D)
COOLER
3-PASS
IN OUT
5 10
9 4
COOLER
2-PASS
IN OUT
2 3
7 8
COOLER
1-PASS
IN OUT
1 6
6 1
COOLER COOLER NOZZLE
SHELL DIMENSIONS (1-PASS)
CODE G H
G 1'�0-3/8" 2'�2-1/2"
H 1'�1-3/8" 2'�4-3/4"
J 1'�2-3/8" 2'�6-3/4"
T 1'�2-3/8" 2'�6-3/4"
V 1'�4" 2'�10"
W 1'�4" 2'�10"
COOLER COOLER NOZZLE
SHELL DIMENSIONS (2-PASS)
CODE G H K
G 10-3/8" 1'�10-1/2" 1'�2-3/4"
H 11-3/8" 2'�0-3/4" 1'�2-3/4"
J 1'�0-3/8" 2'�2-3/4" 1'�2-3/4"
T 1'�0-3/8" 2'�2-3/4" 1'�2-3/4"
V 1'�2" 2'�6" 1'�2-3/4"
W 1'�3" 2'�6" 1'�4-1/2"
COOLER NOZZLE PIPE SIZE
SHELL NO. OF PASSES
CODE 1 2 3
G 14" 10" 8"
H 16" 12" 10"
J 18" 14" 12"
T 18" 14" 12"
V 20" 16" 12"
W 20" 18" 14"
COOLER COOLER NOZZLE
SHELL DIMENSIONS (3-PASS)
CODE G H
G 9-3/8" 1'�8-1/2"
H 10-3/8" 1'�10-1/2"
J 11-3/8" 2'�0-3/4"
T 11-3/8" 2'�0-3/4"
V 1'�0-3/8" 2'�2-3/4"
W 1'�1" 2'�4"
K(2-PASSBACK HEAD)
GH
LD02708B
YORK INTERNATIONAL30
7/8" 7/8"COMPR. END MOTOR END
11 16
D D
FLOORLINE
A
D
18
A 17
7/8"7/8"COMPR. END MOTOR END
FLOORLINE
C
B
7/8" 7/8"COMPR. END MOTOR END
FLOORLINE
C
B
15
20
DD
A
7/8" 7/8"COMPR. END MOTOR END
FLOORLINE
C
B
A
D D
SEE NOTE 614
19
7/8"7/8"
COMPR. END MOTOR END
FLOORLINE
SEE NOTE 6
B
C
A12
13
D
7/8" 7/8"COMPR. END MOTOR END
FLOORLINE
11 16SEE NOTE 6
D D
A
FRONT OF UNIT FRONT OF UNIT
FRONT OF UNIT FRONT OF UNIT
FRONT OF UNITFRONT OF UNIT
NOTES:1. All dimensions are approximate. Certified dimensions are available upon request.2. Standard water nozzles are Schedule 40 pipe size, furnished as welding stub-outs with Victaulic grooves, allowing the option of
welding, flanges, or use of Victaulic couplings. Factory installed, class 150 (ANSI B16.5, round slip-on, forged carbon steel with 1/16"raised face), water flanged nozzles are optional. Companion flanges, nuts, bolts, and gaskets are not furnished.
3. Add 7/8" to all height dimensions to obtain installed height when using neoprene mounts or optional spring vibration isolator mounts.4. One-, two-, and three-pass nozzle arrangements are available only in pairs shown and for all shell codes. Any pair of cooler nozzles
may be used in combination with any pair of condenser nozzles. Compact water boxes on one heat exchanger may be used withMarine Water Boxes on the other heat exchanger.
5. Condenser water must enter the water box through the bottom connection for proper operation of the sub-cooler to achieve ratedperformance.
6. �G� Condenser Water Boxes are square; other codes are round as shown.7. Add 1/2" to �A� and �C� dimensions when flanges are furnished.
COND. CONDENSER NOZZLE DIMENSIONS
SHELL 1-PASS 2-PASS 3-PASS
CODE A D A B C D A B C D
G 5'�9-3/4" 1'�9" 5'�9-3/4" 2'�8-3/4" 2'�5" 1'�9" 5'�9-3/4" 2'�7-1/4" 2'�5" 1'�9"
H 5'�11" 1'�11" 5'�10-1/4" 2'�0-3/4" 2'�1" 1'�11" 5'�9-7/8" 2'�1-1/8" 1'�11-3/4" 1'�11"
J 6'�3-3/8" 2'�1" 6'�2-3/8" 2'�1-1/2" 2'�1-1/8" 2'�1" 6'�1-7/8" 2'�1-3/4" 2'�1-7/8" 2'�1"
T 6'�3-3/8" 2'�1" 6'�2-3/8" 2'�1-1/2" 2'�1-1/8" 2'�1" 6'�1-7/8" 2'-1-3/4" 2'�1-7/8" 2'�1"
V 6'�8-3/4" 2'�3-1/2" 6'�8-1/8" 2'�1-3/4" 2'�5-3/8" 2'�3-1/2" 6'�7" 2'�2-1/2" 2'�3-3/4" 2'�3-1/2"
FIG. 15 � NOZZLE ARRANGEMENTS - CONDENSERS - J COMPRESSOR UNITS (150# MARINE WATER BOXES - STD. DIMENSIONS)
LD02681A
1-PASS 1-PASS1-PASS 1-PASS
2-PASS 2-PASS2-PASS 2-PASS
3-PASS 3-PASS
FORM 160.52-PA1
31YORK INTERNATIONAL
CONDENSER1-PASS
IN OUT
11 1616 11
CONDENSER2-PASS
IN OUT
12 13
17 18
CONDENSER3-PASS
IN OUT
15 2019 14
FIG. 15 � (CONT�D)
COND. NOZZLE PIPE SIZE
SHELL NO. OF PASSES
CODE 1 2 3
G 16" 14" 10"
H 20" 16" 12"
J 20" 16" 14"
T 20" 16" 14"
V 20" 18" 14"
CONDENSER COND. NOZZLE
SHELL DIMENSIONS (3-PASS)
CODE G HG 0'�9-5/8" 1'�9-1/8"
H 0'�11-1/4" 2'�0-1/4"
J 1'�0-1/4" 2'�2-3/8"
T 1'�0-1/4" 2'�2-3/8"
V 1'�0-1/4" 2'�2-3/4"
CONDENSER COND. NOZZLE
SHELL DIMENSIONS (2-PASS)
CODE G H K
G 1'�0-1/4" 2'�2-3/8" 0'�5-7/8"
H 1'�1-5/8" 2'�5" 0'�11-5/8"
J 1'�1-5/8" 2'�5-1/8" 1'�0-1/2"
T 1'�1-5/8" 2'�5-1/8" 1'�0-1/2"
V 1'�2-1/4" 2'�6-3/4" 1'�1-5/8"
CONDENSER COND. NOZZLE
SHELL DIMENSIONS (1-PASS)
CODE G H
G 1'�1-1/4" 2'�4-3/8"
H 1'�3-1/2" 2'�8-3/4"
J 1'�3-1/2" 2'�8-7/8"
T 1'�3-1/2" 2'�8-7/8"
V 1'�3-1/2" 2'�9-3/8"
TUBESHEET
G
H
TUBESHEET
K(2-PASSBACK HEAD)
LD02681B
YORK INTERNATIONAL32
LD02413 LD02414
LD02416LD02415
1-PASS 1-PASS
2-PASS 2-PASS
3-PASS 3-PASS
LD02411 LD02412
FIG. 16 � NOZZLE ARRANGEMENTS - COOLERS - G & H COMPRESSOR UNITS (300# MARINE WATER BOXES � STD. DIMENSIONS)
NOTES:
1. All dimensions are approximate. Certified dimensions are available upon request.
2. Standard water nozzles are Schedule 40 pipe size. Factory installed, class 300 (ANSI B16.5, round slip-on, forged carbon steel with 1/16"raised face), water flanged nozzles are standard. Companion flanges, nuts, bolts, and gaskets are not furnished.
3. One-, two-, and three-pass nozzle arrangements are available only in pairs shown and for all shell codes. Any pair of cooler nozzles maybe used in combination with any pair of condenser nozzles. Compact water boxes on one heat exchanger may be used with Marine WaterBoxes on the other heat exchanger.
4. Water must enter the water box through the bottom connection to achieve rated performance.
COOLER COOLER NOZZLE DIMENSIONS
SHELL 1-PASS 2-PASS 3-PASS
CODE A D A B C D A B C D
C 2'�10-1/8" 1'�7" 2'�10-1/8" 1'�3-1/8" 2'�0" 1'�7" 2'�10-1/8" 1'�0-5/8" 2'�0" 1'�7"
DB, DC, DD 2'�11-3/8" 1'�8-1/2" 2'�11-3/8" 1'�3-1/4" 2'�3" 1'�8-1/2" 2'�11-3/8" 1'�1" 2'�3" 1'�8-1/2"
DE 3'�0-3/8" 1'�8-1/2" 3'�0-3/8" 1'�4-1/4" 2'�3" 1'�8-1/2" 3'�0-3/8" 1'�2" 2'�3" 1'�8-1/2"
E 3'�0-3/8" 1'�9-1/2" 3'�0-3/8" 1'�3" 2'�3" 1'�9-1/2" 3'�0-3/8" 1'�2" 2'�3" 1'�9-1/2"
F 3'�1-3/4" 2'�0" 3'�1-3/4" 1'�4-1/2" 2'�3" 2'�0" 3'�1-3/4" 1'�3-1/4" 2'�3" 2'�0"
G 3'�4-1/2" 2'�1-1/4" 3'�4-1/2" 1'�4-3/4" 2'�7-1/4" 2'�1-1/4" 3'�4-1/2" 1'�3-3/4" 2'�7-1/4" 2'�1-1/4"
H 3'�6" 2'�3" 3'�6" 1'�6-1/4" 2'�7-1/4" 2'�3" 3'�6" 1'�4-3/4" 2'�7-1/4" 2'�3"
7/8"7/8"
7/8"7/8"
7/8"7/8"
FORM 160.52-PA1
33YORK INTERNATIONAL
COOLER
3-PASS
IN OUT
5 10
9 4
COOLER
2-PASS
IN OUT
2 3
7 8
COOLER
1-PASS
IN OUT
1 6
6 1
FIG. 16 � (CONT�D)
LD02198
COOLER NOZZLE PIPE SIZE
SHELL NO. OF PASSES
CODE 1 2 3
C 12" 8" 6"
D 12" 8" 8"
E 14" 10" 8"
F 14" 10" 8"
G 16" 12" 10"
H 16" 12" 10"
COOLER COOLER NOZZLE
SHELL DIMENSIONS (3-PASS)
CODE G H
C 7-3/4" 1'�3-1/2"
D 9-1/4" 1'�5-7/8"
E 9-1/4" 1'�8"
F 9-1/4" 1'�8"
G 10-5/8" 1'�10-1/2"
H 10-5/8" 1'�10-1/2"
COOLER COOLER NOZZLE
SHELL DIMENSIONS (2-PASS)
CODE G H K
C 9" 1'�8" 6-7/8"
D 9-1/4" 1'�5-7/8" 7-1/4"
E 10-1/4" 1'�8" 7-1/4"
F 10-1/4" 1'�8" 7-1/4"
G 11-5/8" 2'�0-1/2" 8-1/4"
H 11-5/8" 2'�0-1/2" 8-1/4"
COOLER COOLER NOZZLE
SHELL DIMENSIONS (1-PASS)
CODE G H
C 11" 1'�11-3/4"
D 11" 1'�11-3/4"
E 1'�1-1/8" 2'�3-3/4"
F 1'�1-1/8" 2'�3-3/4"
G 1'�1-3/4" 2'�5"
H 1'�1-3/4" 2'�5"
G
TUBESHEET
TUBESHEET
H
K(2-PASSBACK HEAD)
YORK INTERNATIONAL34
FIG. 17 � NOZZLE ARRANGEMENT - CONDENSERS - G & H COMPRESSOR UNITS (300# MARINE WATER BOXES � STD. DIMENSIONS)
NOTES:
1. All dimensions are approximate. Certified dimensions are available upon request.
2. Standard water nozzles are Schedule 40 pipe size. Factory installed class 300 (ANSI B 16.5, round slip-on, forged carbon steel with 1/16"raised face), water flanged nozzles are standard. Companion flanges, nuts, bolts, and gaskets are not furnished.
3. One-, two-, or three-pass nozzle arrangements are available only in pairs shown and for all shell codes. Any pair of cooler nozzles may beused in combination with any pair of condenser nozzles. Compact water boxes on one heat exchanger may be used with Marine WaterBoxes on the other heat exchanger.
4. Condenser water must enter the water box through the bottom connection for proper operation of the sub-cooler to achieve rated performance.
COND. CONDENSER NOZZLE DIMENSIONSSHELL 1-PASS 2-PASS 3-PASSCODE A D A B C D A B C D
C 4'�8-1/4" 1'�5-1/2" 4'�8-1/4" 2'�0-1/4" 1'�7" 1'�5-1/2" 4'�8-1/4" 2'�0-1/4" 1'�7" 1'�5-1/2"D 4'�8-1/4" 1'�5-1/2" 4'�9-3/4" 1'�10-1/4" 1'�9" 1'�5-1/2" 4'�8-1/4" 2'�0-1/4" 1'�7" 1'�5-1/2"E 5'�0-3/4" 1'�5-1/2" 4'�11-1/4" 1'�11-3/4" 1'�9" 1'�5-1/2" 4'�11-3/4" 1'�11-3/4" 1'�9" 1'�5-1/2"F 5'�1-1/4" 1'�7" 5'�1-3/4" 2'�1-1/4" 1'�10" 1'�7" 5'�0-3/4" 2'�1-1/4" 1'�9" 1'�7"G 5'�5-3/4" 1'�9" 5'�5-3/4" 2'�1-3/4" 1'�11-1/2" 1'�9" 5'�5-1/4" 2'�1-3/4" 1'�10-1/2" 1'�9"
2-PASS
1-PASS
3-PASS
LD02196
LD02195
LD02197
7/8"7/8"
7/8"
7/8"
7/8"
7/8"
FORM 160.52-PA1
35YORK INTERNATIONAL
CONDENSER COND. NOZZLE
SHELL DIMENSIONS (1-PASS)
CODE G H
C 10-1/4" 1'�10-3/4"
D 11-3/4" 2'�1-3/4"
E 1'�0-1/2" 2'�3-1/4"
F 1'�2-1/4" 2'�7-1/4"
G 1'�2-1/4" 2'�7-1/4"
LD02198
TUBESHEET
TUBESHEET
K
G
H (2-PASSBACK HEAD)
FIG. 17 � (CONT�D)
COND. NOZZLE PIPE SIZE
SHELL NO. OF PASSES
CODE 1 2 3
C 10" 8" 6"
D 12" 8" 6"
E 14" 10" 8"
F 16" 12" 10"
G 16" 14" 10"
CONDENSER
3-PASS
IN OUT
15 20
19 14
CONDENSER
2-PASS
IN OUT
12 13
17 18
CONDENSER
1-PASS
IN OUT
11 16
16 11
CONDENSER COND. NOZZLE
SHELL DIMENSIONS (2-PASS)
CODE G H K
C 8-7/8" 1'�7-7/8" 10-1/2"
D 8-7/8" 1'�7-7/8" 10-1/2"
E 10-1/2" 1'�9-1/4" 11"
F 1'�1" 2'�4-1/4" 11"
G 1'�1-1/2" 2'�5" 11-1/2"
CONDENSER COND. NOZZLE
SHELL DIMENSIONS (3-PASS)
CODE G H
C 7-3/4" 1'�5-7/8"
D 7-3/4" 1'�5-7/8"
E 10" 1'�9-1/4"
F 1�0" 2'�2-1/4"
G 11�1/4" 2'�1-3/4"
YORK INTERNATIONAL36
FIG.18 � NOZZLE ARRANGEMENTS - COOLERS - G & H COMPRESSOR UNITS (COMPACT WATER BOXES - METRIC DIMENSIONS)
NOTES:1. Standard water nozzles are furnished as welding stub-outs with Victaulic grooves, allowing the option of welding, flanges, or use of
Victaulic couplings. Factory installed, class 150 (ANSI B16.5, round slip-on, forged carbon steel with 1.6 mm raised face), water flangesnozzles are optional. Companion flanges, nuts, bolts, and gaskets are not furnished.
2. One, two and three pass nozzle arrangements are available only in pairs shown and for all shell codes. Any pair of cooler nozzles may beused in combination with any pair of condenser nozzles.
3. Cooler and condenser water must enter the water box through the bottom connection to achieve rated performance.4. Connected piping should allow for removal of compact water boxes for tube access and cleaning.
1-PASS
2-PASS
3-PASS
LD01340
COOLER COOLER
FRONTOF
UNIT
FLOOR LINE
AA
22 FF
COMPRESSOR END MOTOR END
FF 22
AA
FRONT
OF
UNIT
FLOOR LINE
COMPRESSOR END MOTOR END
2222
COOLER COOLER
DD
BB
DD
BB
FF
EE
FF
EEEE EE
FLOOR LINE
FRONT
OF
UNIT
COMPRESSOR END MOTOR END
A H
B C
D E
J
L
K
M
DD
BB
22
BB
22
COOLER COOLER
FFFF
F
G
N
P DD
COOLERCOOLER NOZZLE PIPE SIZE (IN.)
NOZZLE DIMENSIONS (mm)SHELL
NO. OF PASSES 1-PASS 2-PASS 3-PASSCODE
1 2 3 AA FF BB DD EE FF BB DD FF
C 12" 8" 6" 467 483 365 568 178 483 318 616 483
DB, DC, DD 12" 8" 8" 473 521 346 600 229 521 295 651 521
DE 12" 8" 8" 502 521 375 629 229 521 324 679 521
E 14" 10" 8" 489 546 362 616 229 546 311 667 546
F 14" 10" 8" 521 610 394 648 229 610 343 699 610
G 16" 12" 10" 549 641 397 702 273 641 321 778 641
H 16" 12" 10" 578 686 425 730 273 686 349 806 686
NOZZLE
ARRANGEMENTS
NO. OF COOLER
PASSES IN OUT
1 A H
H A
NOZZLE
ARRANGEMENTS
NO. OF COOLER
PASSES IN OUT
D C
2E B
L K
M J
NOZZLE
ARRANGEMENTS
NO. OF COOLER
PASSES IN OUT
3 G N
P F
FORM 160.52-PA1
37YORK INTERNATIONAL
1-PASS
2-PASS
3-PASS
LD01341
FRONT
OF
UNIT
CC
COND. COND.
P Q
22 22FLOOR LINE
MOTOR ENDCOMPRESSOR END
GG GG
CC
22 22MOTOR ENDCOMPRESSOR END
COND. COND.
FRONT
OF
UNIT
DD
BB
DD
BB
U
T
S
R
GG GG
FRONT
OF
UNIT
DD
BB
COND. COND.
22
COMPRESSOR END MOTOR END
22
DD
BB
GG GG
V
W Y
X
FLOOR LINE
FLOOR LINE
CONDENSER CONDENSER NOZZLE PIPE SIZE (IN.)
NOZZLE DIMENSIONS (mm)SHELL
NO. OF PASSES 1-PASS 2-PASS 3-PASSCODE
1 2 3 CC GG BB DD GG BB DD GG
C 10" 8" 6" 908 445 730 1,086 445 756 1,099 445
D 12" 8" 6" 908 445 730 1,086 445 756 1,111 445
E 14" 10" 8" 946 445 743 1,162 445 768 1,175 445
F 16" 12" 10" 984 483 737 1,232 483 768 1,257 483
G 16" 14" 10" 1,035 533 762 1,308 533 794 1,314 533
FIG. 19 � NOZZLE ARRANGEMENTS - CONDENSERS - G & H COMPRESSOR UNITS (COMPACT WATER BOXES - METRIC DIMENSIONS)
NOZZLE
ARRANGEMENTS
NO. OF COND.
PASSES IN OUT
1P Q
Q P
NOZZLE
ARRANGEMENTS
NO. OF COND.
PASSES IN OUT
2R S
T U
NOZZLE
ARRANGEMENTS
NO. OF COND.
PASSES IN OUT
3V Y
X W
YORK INTERNATIONAL38
1-PASS
2-PASS
3-PASS
NOTES:1. Standard water nozzles are furnished as welding stub-outs with Victaulic grooves, allowing the option of welding, flanges, or use of
Victaulic couplings. Factory installed, class 150 (ANSI B16.5, round slip-on, forged carbon steel with 1/16" raised face), water flangednozzles are optional. Companion flanges, nuts, bolts, and gaskets are not furnished.
2. Add 22 mm to all height dimensions to obtain installed height when using neoprene mounts or optional spring vibration isolator mounts.3. One-, two- and three-pass nozzle arrangements are available only in pairs shown and for all shell codes. Any pair of cooler nozzles may
be used in combination with any pair of condenser nozzles.4. Connected piping should allow for removal of compact water boxes for tube access and cleaning.
LD02676
COOLER COOLER
FRONT
OF
UNIT
FLOOR LINE
AA
22 FF
COMPRESSOR END MOTOR END
FF 22
AA
FRONT
OF
UNIT
FLOOR LINE
COMPRESSOR END MOTOR END
2222
COOLER COOLER
BB BB
FF
EE
FF
EEEE EE
FLOOR LINE
FRONT
OF
UNIT
COMPRESSOR END MOTOR END
A H
B C J K
BB
22
BB
22
COOLER COOLER
F N
FFFF
FIG. 20 � NOZZLE ARRANGEMENTS - COOLERS - J COMPRESSOR UNITS (150# COMPACT WATER BOXES - METRIC DIMENSIONS)
NOZZLE
ARRANGEMENTS
NO. OF COOLER
PASSES IN OUT
B C
2C B
J K
K J
NOZZLE
ARRANGEMENTS
NO. OF COOLER
PASSES IN OUT
3F N
N F
COOLERCOOLER NOZZLE PIPE SIZE
NOZZLE DIMENSIONS (mm)SHELL
NO. OF PASSES 1-PASS 2-PASS 3-PASSCODE
1 2 3 AA FF BB EE FF BB FF
G 14" 10" 8" 587 610 587 279 610 587 610
H 16" 12" 10" 629 667 629 279 667 629 667
J 18" 14" 12" 654 749 654 279 749 629 749
T 18" 14" 12" 654 749 654 279 749 629 749
V 20" 16" 12" 743 749 743 330 749 743 749
W 20" 18" 14" 794 813 794 381 813 794 813
NOZZLE
ARRANGEMENTS
NO. OF COOLER
PASSES IN OUT
1A H
H A
FORM 160.52-PA1
39YORK INTERNATIONAL
1-PASS
2-PASS
3-PASS
See Note*
See Note*
See Note*
FRONT
OF
UNIT
CC
P Q
22 22FLOOR LINE
MOTOR ENDCOMPRESSOR END
GG GG
CC
22 22
MOTOR ENDCOMPRESSOR END
FRONT
OF
UNIT
DD
BB
DD
BB
U
T
S
R
GG GGFLOOR LINE
FRONT
OF
UNIT
DD
BB
22
COMPRESSOR END MOTOR END
22
DD
BB
GG GG
V
W Y
X
FLOOR LINE
LD02677
CONDENSER
CONDENSER NOZZLE PIPE SIZE
NOZZLE DIMENSIONS (mm)SHELL
NO. OF PASSES 1-PASS 2-PASS 3-PASSCODE
1 2 3 CC GG BB DD GG BB DD GG
G * 16" 14" 10" 1,035 533 762 1,308 533 794 1,314 533
H 20" 16" 12" 1,086 584 806 1,365 584 794 1,410 584
J 20" 16" 14" 1,137 635 819 1,454 635 845 1,492 635
T 20" 16" 14" 1,137 635 819 1,454 635 845 1,492 635
V 20" 18" 14" 1,200 699 857 1,543 699 895 1,597 699
* NOTE: �G� Condenser Water Boxes are square; other codes are round as shown.
FIG. 21 � NOZZLE ARRANGEMENTS - CONDENSERS - J COMPRESSOR UNITS (150# COMPACT WATER BOXES - METRIC DIMENSIONS)
NOZZLE
ARRANGEMENTS
NO. OF COND.
PASSES IN OUT
1P Q
Q P
NOZZLE
ARRANGEMENTS
NO. OF COND.
PASSES IN OUT
2R S
T U
NOZZLE
ARRANGEMENTS
NO. OF COND.
PASSES IN OUT
3V Y
X W
YORK INTERNATIONAL40
NOTES:1. All dimensions are approximate. Certified dimensions are available upon request.2. Standard water nozzles are Schedule 40 pipe size, furnished as welding stub-outs with Victaulic grooves, allowing the option of
welding, flanges, or use of Victaulic couplings. Factory installed, class 150 (ANSI B16.5, round slip-on, forged carbon steel with 1.6 mmraised face), water flanged nozzles are optional. Companion flanges, nuts, bolts, and gaskets are not furnished.
3. One-, two-, and three-pass nozzle arrangements are available only in pairs shown and for all shell codes. Any pair of cooler nozzlesmay be used in combination with any pair of condenser nozzles. Compact water boxes on one heat exchanger may be used with MarineWater Boxes on the other heat exchanger.
4. Water must enter the water box through the bottom connection to achieve rated performance.5. Add 13 mm to �A� & �C� Dimensions when flanges are furnished.
A
8
3
B
D
B
B
8
C
6
A
1OUT
COMPR. END
D D
A
1 6 OUTIN
22 MOTOR ENDCOMPR. END FLOORLINE
1
D D
IN
22 MOTOR END FLOORLINE
COMPR. ENDMOTOR ENDCOMPR. END MOTOR END
COMPR. ENDMOTOR ENDCOMPR END MOTOR END
FLOORLINE
FLOORLINE
FLOORLINE
FLOORLINE
D
22
IN7
OUT
A
9
D
4
A
OUT
IN
22
C D C
IN
5
10
22
OUT
A
2IN
OUT
D C
22
FRONT OF UNIT
FRONT OF UNITFRONT OF UNIT
FRONT OF UNIT FRONT OF UNIT
FRONT OF UNIT
COOLER COOLER NOZZLE DIMENSIONS (mm)
SHELL 1-PASS 2-PASS 3-PASS
CODE A D A B C D A B C D
C 956 483 956 371 603 483 956 321 603 483
DB, DC, DD 1,013 521 1,013 346 686 521 1,013 302 686 521
DE 1,041 521 1,041 375 686 521 1,041 330 686 521
E 1,029 546 1,029 362 686 546 1,029 311 686 546
F 1,060 610 1,060 394 686 610 1,060 343 686 610
G 1,197 641 1,172 425 787 641 1,172 321 787 641
H 1,226 686 1,200 454 787 686 1,200 349 787 686
LD01342AM
FIG. 22 � NOZZLE ARRANGEMENTS - COOLERS - G & H COMPRESSOR UNITS(150# MARINE WATER BOXES - METRIC DIMENSIONS)
1-PASS 1-PASS1-PASS 1-PASS
2-PASS 2-PASS
3-PASS 3-PASS
FORM 160.52-PA1
41YORK INTERNATIONAL
GK(2-PASSBACK HEAD)
LD01342BM
COOLER
2-PASS
IN OUT
2 3
7 8
COOLER
1-PASS
IN OUT
1 6
6 1
FIG. 22 � (CONT�D)
COOLER
3-PASS
IN OUT
5 10
9 4
COOLER COOLER NOZZLE
SHELL DIMENSIONS � mm (3-PASS)
CODE G H
C 184 397
D 222 479
E 248 530
F 248 530
G 248 543
H 248 543
COOLER NOZZLE PIPE SIZE
SHELL NO. OF PASSES
CODE 1 2 3
C 12" 8" 6"
D 12" 8" 8"
E 14" 10" 8"
F 14" 10" 8"
G 16" 12" 10"
H 16" 12" 10"
COOLER COOLER NOZZLE
SHELL DIMENSIONS � mm (2-PASS)
CODE G H K
C 222 473 143
D 222 479 149
E 258 530 149
F 258 530 149
G 286 619 159
H 286 619 159
COOLER COOLER NOZZLE
SHELL DIMENSIONS � mm (1-PASS)
CODE G H
C 286 600
D 286 606
E 311 657
F 311 657
G 337 721
H 337 721
YORK INTERNATIONAL42
15
CL
CL
CL CL
CL CL
CL
C
CL CL
DD
11 16
A
22FLOORLINE
COMPR. END MOTOR END22
D
18
A
22
22 22
17
BB
CFLOORLINE
COMPR. END MOTOR END
DD
A
20
B
22 C
COMPR. END MOTOR END
FLOORLINE 22 22
22
MOTOR ENDCOMPR. END
FLOORLINE
A
D D
14
B
22
MOTOR ENDCOMPR. END
FLOORLINE
B
19
22
A12
13
D
MOTOR ENDCOMPR. END
FLOORLINE 22
A
11 16
DDFRONT OF UNIT FRONT OF UNIT
FRONT OF UNITFRONT OF UNIT
FRONT OF UNITFRONT OF UNIT
C
1-PASS 1-PASS
2-PASS 2-PASS
NOTES:1. All dimensions are approximate. Certified dimensions are available upon request.2. Standard water nozzles are Schedule 40 pipe size, furnished as welding stub-outs with Victaulic grooves, allowing the option of
welding, flanges, or use of Victaulic couplings. Factory installed, class 150 (ANSI B16.5, round slip-on, forged carbon steel with 1.6mm raised face), water flanged nozzles are optional. Companion flanges, nuts, bolts, and gaskets are not furnished.
3. One-, two-, and three-pass nozzle arrangements are available only in pairs shown and for all shell codes. Any pair of cooler nozzlesmay be used in combination with any pair of condenser nozzles. Compact water boxes on one heat exchanger may be used withMarine Water Boxes on the other heat exchanger.
4. Condenser water must enter the water box through the bottom connection for proper operation of the sub-cooler to achieve ratedperformance.
5. Add 13 mm to �A� and �C� dimensions when flanges are furnished.
COOLER COOLER NOZZLE DIMENSIONS (mm)
SHELL 1-PASS 2-PASS 3-PASS
CODE A D A B C D A B C D
C 1486 444 1486 787 578 445 1486 775 578 445
D 1486 444 1486 787 578 445 1486 775 578 445
E 1572 444 1572 781 625 445 1572 743 625 445
F 1676 483 1676 806 667 483 1651 781 667 483
G 1774 533 1651 832 713 533 1749 794 714 533
LD01343AM
FIG. 23 � NOZZLE ARRANGEMENTS - CONDENSERS - G & H COMPRESSOR UNITS (150# MARINE WATER BOXES - METRIC DIMENSIONS)
3-PASS 3-PASS
FORM 160.52-PA1
43YORK INTERNATIONAL
FIG. 23 � (CONT�D)
CONDENSER
2-PASS
IN OUT
12 13
17 18
CONDENSER
1-PASS
IN OUT
11 16
16 11
LD01343B
TUBESHEET
TUBESHEET
K (2-PASSBACK HEAD)
G
H
CONDENSER
3-PASS
IN OUT
15 20
19 14
COND. NOZZLE PIPE SIZE
SHELL NO. OF PASSES
CODE 1 2 3
C 10" 8" 6"
D 12" 8" 6"
E 14" 10" 8"
F 16" 12" 10"
G 16" 14" 10"
COND. CONDENSER NOZZLE
SHELL DIMENSIONS � mm (1-PASS)
CODE G H
C 244 524
D 283 600
E 311 657
F 337 711
G 337 721
COND. CONDENSER NOZZLE
SHELL DIMENSIONS � mm (2-PASS)
CODE G H K
C 219 473 140
D 219 473 140
E 248 530 146
F 286 610 146
G 311 670 152
COND. CONDENSER NOZZLE
SHELL DIMENSIONS � mm (3-PASS)
CODE G H
C 194 422
D 194 422
E 222 479
F 248 533
G 244 635
YORK INTERNATIONAL44
NOTES:1. All dimensions are approximate. Certified dimensions are available upon request.2. Standard water nozzles are Schedule 40 pipe size, furnished as welding stub-outs with Victaulic grooves, allowing the option of
welding, flanges, or use of Victaulic couplings. Factory installed, class 150 (ANSI B16.5, round slip-on, forged carbon steel with 1/16"raised face), water flanged nozzles are optional. Companion flanges, nuts, bolts, and gaskets are not furnished.
3. Add 22 mm to all height dimensions to obtain installed height when using neoprene mounts or optional spring vibration isolator mounts.4. One-, two-, and three-pass nozzle arrangements are available only in pairs shown and for all shell codes. Any pair of cooler nozzles
may be used in combination with any pair of condenser nozzles. Compact water boxes on one heat exchanger may be used with MarineWater Boxes on the other heat exchanger.
5. Water must enter the water box through the bottom connection to achieve rated performance.6. Add 13 mm to �A� & �C� dimensions where flanges are furnished.
COOLER COOLER NOZZLE DIMENSIONS (mm)
SHELL 1-PASS 2-PASS 3-PASS
CODE A D A B C D A B C D
G 1146 610 1146 470 737 610 1146 410 737 610
H 1353 667 1353 679 794 667 1353 654 794 667
J 1213 749 1213 552 870 749 1213 527 870 749
T 1213 749 1213 552 870 749 1213 527 870 749
V 1302 749 1302 648 870 749 1302 606 870 749
W 1384 762 1384 698 965 762 1384 648 962 762
FIG. 24 � NOZZLE ARRANGEMENTS - COOLERS - J COMPRESSORS UNITS (150# MARINE WATER BOXES - METRIC DIMENSIONS)
COMPR. END MOTOR END22 FLOORLINE
A
61
DD
IN OUT
COMPR. END MOTOR END22 FLOORLINE
D D
OUT IN1 6
2
3
A
8
IN
OUT
22 MOTOR END FLOORLINE
COMPR. END
D CC D
8
7
B
22COMPR. END MOTOR END FLOOR LINE
OUT
IN A
OUT
22COMPR. END MOTOR END FLOORLINE
A
D C
4
IN9
B
DC
B
5IN
22 MOTOR END FLOORLINE
COMPR. END
D
A
10OUT
FRONT OF UNIT FRONT OF UNIT
FRONT OF UNITFRONT OF UNIT
FRONT OF UNITFRONT OF UNIT
1-PASS 1-PASS
2-PASS 2-PASS
3-PASS 3-PASS
LD02708AM
FORM 160.52-PA1
45YORK INTERNATIONAL
LD01342B
HG
K(2-PASSBACK HEAD)
COOLER
1-PASS
IN OUT
1 6
6 1
COOLER
2-PASS
IN OUT
2 3
7 8
COOLER
3-PASS
IN OUT
5 10
9 4
FIG. 24 � (CONT�D)
COOLER COOLER NOZZLE
SHELL DIMENSIONS � mm (2-PASS)
CODE G H K
G 263 571 375
H 289 629 375
J 314 679 375
T 314 679 375
V 356 762 375
W 381 762 419
COOLER COOLER NOZZLE
SHELL DIMENSIONS � mm (1-PASS)
CODE G H
G 314 673
H 340 730
J 365 781
T 365 781
V 406 864
W 406 864
COOLER NOZZLE PIPE SIZE
SHELL NO. OF PASSES
CODE 1 2 3
G 14" 10" 8"
H 16" 12" 10"
J 18" 14" 12"
T 18" 14" 12"
V 20" 16" 12"
W 20" 18" 14"
COOLER COOLER NOZZLE
SHELL DIMENSIONS � mm (3-PASS)
CODE G H
G 238 521
H 273 572
J 289 629
T 289 629
V 314 629
W 330 711
YORK INTERNATIONAL46
NOTES:
1. All dimensions are approximate. Certified dimensions are available upon request.
2. Standard water nozzles are Schedule 40 pipe size, furnished as welding stub-outs with Victaulic grooves, allowing the option ofwelding, flanges, or use of Victaulic couplings. Factory installed, class 150 (ANSI B16.5, round slip-on, forged carbon steel with 1.6mm raised face), water flanged nozzles are optional. Companion flanges, nuts, bolts, and gaskets are not furnished.
3. Add 22 mm to all height dimensions to obtain installed height when using neoprene mounts or optional spring vibration isolator mounts.
4. One-, two-, and three-pass nozzle arrangements are available only in pairs shown and for all shell codes. Any pair of cooler nozzlesmay be used in combination with any pair of condenser nozzles. Compact water boxes on one heat exchanger may be used withMarine Water Boxes on the other heat exchanger.
5. Condenser water must enter the water box through the bottom connection for proper operation of the sub-cooler to achieve ratedperformance.
6. Add 13 mm to �A� & �C� dimensions when flanges are furnished.
D
11
22 COMPR. END
A
FLOOR LINE
16
MOTOR END 22
D
22 COMPR. END MOTOR END
FLOOR LINE
A
D D
22
1611
1 PASS1 PASS
2 PASS 2 PASS
3 PASS 3 PASS
22 COMPR. END
A
FLOOR LINE
D
MOTOR END22C
18
17
B B
22 CMOTOR END
D
FLOOR LINE
A
13
12
COMPR. END 22
2222 COMPR. ENDMOTOR END
CFLOOR LINE
FRONT OF UNIT
A
D D
14
19
B
22MOTOR ENDCOMPR. END
FLOOR LINE22
B
A
FRONT OF UNITD D
15
20
C
FRONT OF UNIT FRONT OF UNIT
FRONT OF UNIT FRONT OF UNIT
COOLER CONDENSER NOZZLE DIMENSIONS (mm)
SHELL 1-PASS 2-PASS 3-PASS
CODE A D A B C D A B C D
C 1,486 444 1,486 787 578 445 1,486 775 578 445
D 1,486 444 1,486 787 578 445 1,486 775 578 445
E 1,572 444 1,572 781 625 445 1,572 743 625 445
F 1,676 483 1,676 806 667 483 1,651 781 667 483
G 1,774 533 1,749 832 713 533 1,749 806 714 533
FIG. 25 � NOZZLE ARRANGEMENTS - CONDENSERS - J COMPRESSOR UNITS (150# MARINE WATER BOXES - METRIC DIMENSIONS)
LD02713M
FORM 160.52-PA1
47YORK INTERNATIONAL
CONDENSER
3-PASS
IN OUT
15 20
19 14
CONDENSER
2-PASS
IN OUT
12 13
17 18
CONDENSER
1-PASS
IN OUT
11 16
16 11TUBESHEET
G
H
TUBESHEET
K(2-PASSBACK HEAD)
FIG. 25 � (CONT�D)
COND. NOZZLE PIPE SIZE
SHELL NO. OF PASSES
CODE 1 2 3
C 10" 8" 6"
D 12" 8" 6"
E 14" 10" 8"
F 16" 12" 10"
G 16" 14" 10"
COND. CONDENSER NOZZLE
SHELL DIMENSIONS � mm (3-PASS)
CODE G H
C 194 422
D 194 422
E 222 479
F 248 533
G 244 635
COND. CONDENSER NOZZLE
SHELL DIMENSIONS � mm (2-PASS)
CODE G H K
C 219 473 140
D 219 473 140
E 248 530 146
F 286 610 146
G 311 670 152
COND. CONDENSER NOZZLE
SHELL DIMENSIONS � mm (1-PASS)
CODE G H
C 244 524
D 283 600
E 311 657
F 337 711
G 337 721
LD02714
YORK INTERNATIONAL48
FIG. 26 � NOZZLE ARRANGEMENTS - COOLERS - G & H COMPRESSOR UNITS (300# MARINE WATER BOXES � METRIC DIMENSIONS)
NOTES:
1. All dimensions are approximate. Certified dimensions are available upon request.
2. Standard water nozzles are Schedule 40 pipe size. Factory installed, class 300 (ANSI B16.5, round slip-on, forged carbon steel with 1/16"raised face), water flanged nozzles are standard. Companion flanges, nuts, bolts, and gaskets are not furnished.
3. One-, two-, and three-pass nozzle arrangements are available only in pairs shown and for all shell codes. Any pair of cooler nozzles maybe used in combination with any pair of condenser nozzles. Compact water boxes on one heat exchanger may be used with Marine WaterBoxes on the other heat exchanger.
4. Water must enter the water box through the bottom connection to achieve rated performance.
LD02411 LD02412
LD02413 LD02414
LD02416LD02415
1-PASS 1-PASS
2-PASS 2-PASS
3-PASS 3-PASS
COOLER COOLER NOZZLE DIMENSIONS (mm)
SHELL 1-PASS 2-PASS 3-PASS
CODE A D A B C D A B C D
C 867 483 867 384 610 483 867 321 610 483
DB, DC, DD 899 521 899 387 686 521 899 330 686 521
DE 924 521 924 413 686 521 924 356 686 521
E 924 546 924 381 686 546 924 356 686 546
F 959 610 959 419 686 610 959 387 686 610
G 1,029 641 1,029 425 794 641 1,029 400 794 641
H 1,067 686 1,067 464 794 686 1,067 425 794 686
22 mm22 mm
22 mm22 mm
22 mm22 mm
FORM 160.52-PA1
49YORK INTERNATIONAL
FIG. 26 � (CONT�D)
LD02198
COOLER NOZZLE PIPE SIZE
SHELL NO. OF PASSES
CODE 1 2 3
C 12" 8" 6"
D 12" 8" 8"
E 14" 10" 8"
F 14" 10" 8"
G 16" 12" 10"
H 16" 12" 10"
COOLER COOLER NOZZLE
SHELL DIMENSIONS - mm (3-PASS)
CODE G H
C 197 394
D 235 454
E 235 508
F 235 508
G 270 572
H 270 572
COOLER COOLER NOZZLE
SHELL DIMENSIONS - mm (2-PASS)
CODE G H K
C 229 508 175
D 235 454 184
E 260 508 184
F 260 508 184
G 295 622 210
H 295 622 210
COOLER COOLER NOZZLE
SHELL DIMENSIONS - mm (1-PASS)
CODE G H
C 279 603
D 279 603
E 333 705
F 333 705
G 349 737
H 349 737
COOLER
2-PASS
IN OUT
2 3
7 8
COOLER
1-PASS
IN OUT
1 6
6 1
COOLER
3-PASS
IN OUT
5 10
9 4
G
TUBESHEET
TUBESHEET
H
K(2-PASSBACK HEAD)
YORK INTERNATIONAL50
FIG. 27 � NOZZLE ARRANGEMENT - CONDENSERS - G & H COMPRESSOR UNITS (300# MARINE WATER BOXES � METRIC DIMENSIONS)
LD02195
1-PASS
COND. CONDENSER NOZZLE DIMENSIONS (mm)SHELL 1-PASS 2-PASS 3-PASSCODE A D A B C D A B C D
C 1429 445 1429 616 483 445 1429 616 483 445D 1429 445 1467 565 533 445 1429 616 483 445E 1543 445 1505 603 533 445 1518 603 533 445F 1556 483 1568 641 559 483 1543 641 533 583G 1670 533 1670 654 597 533 1657 654 572 533
NOTES:
1. All dimensions are approximate. Certified dimensions are available upon request.
2. Standard water nozzles are Schedule 40 pipe size. Factory installed class 300 (ANSI B 16.5, round slip-on, forged carbon steel with 1/16"raised face), water flanged nozzles are standard. Companion flanges, nuts, bolts, and gaskets are not furnished.
3. One-, two-, or three-pass nozzle arrangements are available only in pairs shown and for all shell codes. Any pair of cooler nozzles may beused in combination with any pair of condenser nozzles. Compact water boxes on one heat exchanger may be used with Marine WaterBoxes on the other heat exchanger.
4. Condenser water must enter the water box through the bottom connection for proper operation of the sub-cooler to achieve rated performance.
LD02197
3-PASS
LD02196
2-PASS
22 mm 22 mm
22 mm
22 mm
22 mm
22 mm
FORM 160.52-PA1
51YORK INTERNATIONAL
CONDENSER
3-PASS
IN OUT
15 20
19 14
CONDENSER
2-PASS
IN OUT
12 13
17 18
CONDENSER
1-PASS
IN OUT
11 16
16 11
LD02198
FIG. 27 � (CONT�D)
TUBESHEET
TUBESHEET
K
G
H (2-PASSBACK HEAD)
CONDENSER COND. NOZZLE
SHELL DIMENSIONS � mm (2-PASS)
CODE G H K
C 225 505 267
D 225 505 267
E 267 540 279
F 330 718 279
G 343 737 292
CONDENSER COND. NOZZLE
SHELL DIMENSIONS � mm (1-PASS)
CODE G H
C 260 577
D 298 654
E 318 692
F 362 794
G 362 794
CONDENSER COND. NOZZLE
SHELL DIMENSIONS � mm (3-PASS)
CODE G H
C 197 454
D 197 454
E 254 540
F 305 667
G 286 654COND. NOZZLE PIPE SIZE
SHELL NO. OF PASSES
CODE 1 2 3
C 10" 8" 6"
D 12" 8" 6"
E 14" 10" 8"
F 16" 12" 10"
G 16" 14" 10"
YORK INTERNATIONAL52
ALL DIMENSIONS ARE IN INCHES
FIG. 28 � NEOPRENE ISOLATORS (STANDARD DIMENSIONS)
UNIT WEIGHT UP TO 28,835 LBS.
LD00701
UNIT WEIGHT 28,836 TO 53,530 LBS.
LD00702
UNIT WEIGHT 53,531 TO 100,464 LBS.
LD00703
LD00704
* See Fig. 1 or 2
FORM 160.52-PA1
53YORK INTERNATIONAL
ALL DIMENSIONS ARE IN MILLIMETERS
UNIT WEIGHT UP TO 13,080 Kgs.
LD00701(R)
UNIT WEIGHT 13,081 TO 24,281 Kgs.
LD00702(R)
UNIT WEIGHT 24,282 TO 45,570 Kgs.
LD00703(R)
LD00704FIG. 29 � NEOPRENE ISOLATORS (METRIC DIMENSIONS)
* See Fig. 3 or 4
YORK INTERNATIONAL54
ALL DIMENSIONS ARE IN INCHES
FIG. 30 � SPRING ISOLATORS (STANDARD DIMENSIONS)
LD00707
9-SPRING ISOLATORS
UNIT WEIGHT 58,350 LBS. TO 89,340 LBS.
UNIT WEIGHT 35,010 LBS. TO 58,349 LBS.
LD007066-SPRING ISOLATORS
4-SPRING ISOLATORS LD00705
UNIT WEIGHT 19,564 LBS. TO 35,009 LBS.
* See Fig. 1 or 2
* See Fig. 1 or 2
* See Fig. 1 or 2
FORM 160.52-PA1
55YORK INTERNATIONAL
ALL DIMENSIONS ARE IN MILLIMETERS
FIG. 31 – SPRING ISOLATORS (METRIC DIMENSIONS)
LD00707(R)9-SPRING ISOLATORS
UNIT WEIGHT 26,468 Kgs. TO 40,525 Kgs.
UNIT WEIGHT 15,881 Kgs. TO 26,467 Kgs.
LD00706(R)6-SPRING ISOLATORS
4-SPRING ISOLATORS LD00705(R)
UNIT WEIGHT 8,874 Kgs. TO 15,880 Kgs.
* See Fig. 3 or 4
* See Fig. 3 or 4
* See Fig. 3 or 4
YORK INTERNATIONAL56
FIG. 32 � TYPICAL DIMENSIONS AND WEIGHTS - STANDARD MOTORS (LOW VOLTAGE)
LD02538
MOTOR CODEA B C D E F G H
WEIGHT WEIGHT
60 HZ 50 HZ (LBS.) (KGS.)
CH � 31-1/4" 10-7/8" 10-7/8" 10-1/4" 17-3/4" 20" 20" 8" 940 427
CJ 5CE 31-1/4" 10-7/8" 10-7/8" 10-1/4" 17-3/4" 20" 20" 8" 940 427
CK 5CF 36" 11" 11" 8-1/4" 20" 20" 20" 8" 1,440 653
CL 5CG 36" 11" 11" 8-1/4" 20" 20" 20" 8" 1,440 653
CM 5CH 39-5/8" 11" 11" 8-1/4" 21-3/4" 20" 20" 8" 1,700 771
CN 5C1 39-5/8" 11" 11" 8-1/4" 21-3/4" 20" 20" 8" 1,700 771
CP 5CJ 39-5/8" 11" 11" 8-1/4" 21-3/4" 20" 20" 8" 1,700 771
CR 5CK 39-5/8" 11" 11" 8-1/4" 21-3/4" 20" 20" 8" 1,700 771
CS 5CL 40" 16-1/4" 10-3/4" 11-1/2" 24-1/4" 20" 20" 8" 2,635 1,195
CT 5CM 40" 16-1/4" 10-3/4" 11-1/2" 24-1/4" 20" 20" 8" 2,635 1,195
CU 5CN 40" 16-1/4" 10-3/4" 11-1/2" 24-1/4" 20" 20" 8" 2,635 1,195
CV 5CO 40" 16-1/4" 10-3/4" 11-1/2" 24-1/4" 20" 20" 8" 2,635 1,195
CW 5CP 46-1/8" 19-1/2" 12-1/2" 14-3/4" 24-3/4" 20" 24" 16" 2,930 1,329
CX 5CQ 46-1/8" 19-1/2" 12-1/2" 14-3/4" 24-3/4" 20" 24" 16" 2,930 1,329
CY 5CR 52-1/8" 19-1/2" 12-1/2" 14-3/4" 27-3/4" 20" 24" 16" 2,930 1,329
CZ 5CS 52-1/8" 19-1/2" 12-1/2" 14-3/4" 27-3/4" 20" 24" 16" 2,930 1,329
CA 5CT 57-1/4" 22-1/4" 20" 40-1/4" 32" 20" 24" 17" 5,750 2,608
CB 5CU 57-1/4" 22-1/4" 20" 40-1/4" 32" 20" 24" 17" 5,750 2,608
� 5CV 57-1/4" 22-1/4" 20" 40-1/4" 32" 20" 24" 17" 5,750 2,608
DA 5CW 65-1/4" 22-1/4" 20" 40-1/4" 36" 20" 24" 17" 6,800 3,084
DB 5CX 65-1/4" 22-1/4" 20" 40-1/4" 36" 20" 24" 17" 6,800 3,084
DC 5DA 65-1/4" 22-1/4" 20" 40-1/4" 36" 20" 24" 17" 7,300 3,311
� 5DB 65-1/2" 22-1/4" 20" 40-1/4" 36-1/4" 20" 24" 17" 7,300 3,311
FORM 160.52-PA1
57YORK INTERNATIONAL
LD02538
MOTOR CODEA B C D E F G H
WEIGHT WEIGHT
60 HZ 50 HZ (LBS.) (KGS.)
CH � 41-1/2" 20-7/8" 20-7/8" 30-3/8" 22-3/4" 20" 20" 8" 2,670 1,211
CJ 5CE 41-1/2" 20-7/8" 20-7/8" 30-3/8" 22-3/4" 20" 20" 8" 2,670 1,211
CK 5CF 46" 20-7/8" 20-7/8" 30-3/8" 24-3/4" 20" 20" 8" 3,100 1,406
CL 5CG 46" 20-7/8" 20-7/8" 30-3/8" 24-3/4" 20" 20" 8" 3,100 1,406
CM 5CH 46" 20-7/8" 20-7/8" 30-3/8" 24-3/4" 20" 20" 8" 3,100 1,406
CN 5C1 46" 20-7/8" 20-7/8" 30-3/8" 24-3/4" 20" 20" 8" 3,100 1,406
CP 5CJ 51-7/8" 20-7/8" 20-7/8" 30-3/8" 27-3/4" 20" 20" 8" 3,700 1,678
CR 5CK 51-7/8" 20-7/8" 20-7/8" 30-3/8" 27-3/4" 20" 20" 8" 3,700 1,678
CS 5CL 51-7/8" 20-7/8" 20-7/8" 30-3/8" 27-3/4" 20" 20" 8" 3,700 1,678
CT 5CM 51-7/8" 20-7/8" 20-7/8" 30-3/8" 27-3/4" 20" 20" 8" 3,700 1,678
CU 5CN 51-7/8" 20-7/8" 20-7/8" 30-3/8" 27-3/4" 20" 20" 8" 3,700 1,678
CV 5CO 57" 19" 14" 35-5/8" 32-1/4" 20" 20" 8" 4,500 2,041
CW 5CP 57" 19" 14" 35-5/8" 32-1/4" 20" 20" 8" 4,500 2,041
CX 5CQ 57" 19" 14" 35-5/8" 32-1/4" 20" 20" 8" 4,500 2,041
CY 5CR 57" 19" 14" 35-5/8" 32-1/4" 20" 24" 8" 4,500 2,041
CZ 5CS 57" 19" 14" 35-5/8" 32-1/4" 20" 24" 8" 4,500 2,041
CA 5CT 57-1/4" 22-1/4" 20" 40-1/4" 32" 20" 24" 17" 5,800 2,630
CB 5CU 57-1/4" 22-1/4" 20" 40-1/4" 32" 20" 24" 17" 5,800 2,630
� 5CV 57-1/4" 22-1/4" 20" 40-1/4" 32" 20" 24" 17" 5,800 2,630
DA 5CW 65-1/4" 22-1/4" 20" 40-1/4" 36" 20" 24" 17" 6,800 3,084
DB 5CX 65-1/4" 22-1/4" 20" 40-1/4" 36" 20" 24" 17" 6,800 3,084
DC 5DA 65-1/4" 22-1/4" 20" 40-1/4" 36" 20" 24" 17" 7,050 3,198
� 5DB 65-1/2" 22-1/4" 20" 40-1/4" 36-1/4" 20" 24" 17" 7,300 3,311
DD 5DC 65-1/2" 22-1/4" 20" 40-1/4� 36-1/4" 20" 24" 17" 7,300 3,311
DE 5DD 65-1/2" 22-1/4" 20" 40-1/4" 36-1/4" 20" 24" 17" 7,300 3,311
DF 5DE 65-1/2" 22-1/4" 20" 40-1/4" 36-1/4" 20" 24" 17" 7,500 3,402
DH 5DF 65-1/2" 22-1/4" 20" 40-1/4" 36-1/4" 20" 24" 17" 7,500 3,402
DJ 5DG 65-1/2" 22-1/4" 20" 40-1/4" 36-1/4" 20" 24" 17" 7,900 3,583
� 5DH 65-1/2" 22-1/4" 20" 40-1/4" 36-1/4" 20" 24" 17" 7,900 3,583
� 5OJ CONTACT FACTORY FOR DIMENSIONS AND WEIGHTS
FIG. 32 � TYPICAL DIMENSIONS AND WEIGHTS (CON�T) - STANDARD MOTORS (HIGH VOLTAGE)
YORK INTERNATIONAL58
* Add dimensions below if Marine Water Boxes supplied. (Not required if water boxes are removed.)
D CCOOLER
HCONDENSERS
G
B
A
7/8"
E
F
FLOOR LINE
14'�0" **(Tube pulling space (either end))
LD02155
COOLER CONDENSERSSHELL
A B C D E F G HCODE
C 1'�0-3/8" 0'�11-1/4" 2'�3-7/8" 5" 2'�2-3/8" 1'�4-1/2" 7-1/2" 1'�8"
D 1'�0-5/8" 1'�0-3/4" 2'�6-1/2" 5-1/4" 2'�1-1/8" 1'�6-1/2" 6-5/8" 1'�9-3/4"
E 1'�0-1/8" 1'�1-1/2" 2'�6-1/2" 6-1/4" 2'�1-3/8" 1'�9-1/4" 4-7/8" 2'�1-1/4"
F 1'�0-5/8" 1'�2-1/4" 2'�10" 7" 2'�1-1/8" 2'�0-1/2" 5" 2'�3-7/8"
G 1'�0-5/8" 1'�4-1/2" 3'�1-1/2" 6-1/2" 2'�1" 2'�4-1/8" 4-7/8" 2'�8-1/4"
H 1'�0-5/8" 1'�6-3/4" 3'�5-7/8" 6" � � � �
SHELL NO. OF 150# 300#
CODE PASSES COOLER CONDENSER COOLER CONDENSER
1 1'�9-3/4" 1'�6-1/2" 2'�0" 2'�0-3/8"
C 2 1'�4-3/4" 1'�4-1/2" 1'�8-1/2" 1'�9-7/8"
3 1'�1-3/4" 1'�2-1/2" 1'�6" 1'�7-3/8"
1 1'�9-3/4" 1'�9-1/2" 2'�0-3/4" 2'�3-3/8"
D 2 1'�4-3/4" 1'�4-1/2" 1'�8-5/8" 1'�9-7/8"
3 1'�4-3/4" 1'�2-1/2" 1'�8-5/8" 1'�7-3/8"
1 1'�11-3/4" 1'�11-3/4" 2'�2" 2'�6-1/8"
E 2 1'�6-3/4" 1'�6-3/4" 1'�10-3/4" 2'�0-5/8"
3 1'�4-3/4" 1'�4-3/4" 1'�8-5/8" 1'�10-1/8"
1 1'�11-3/4" 2'�1-3/4" 2'�2" 2'�8-5/8"
F 2 1'�6-3/4" 1'�9-3/4" 1'�10-3/4" 2'�3-5/8"
3 1'�4-3/4" 1'�6-3/4" 1'�8-5/8" 2'�0-5/8"
1 2'�1-3/4" 2'�1-3/4" 2'�6-1/4" 2'�9-3/8"
G 2 1'�9-3/4" 1'�11-3/4" 2'�2" 2'�6-7/8"
3 1'�6-3/4" 1'�6-3/4" 2'�0" 2'�1-3/8"
1 2'�1-3/4" � 2'�6-1/4" �
H 2 1'�9-3/4" � 2'�2" �
3 1'�6-3/4" � 2'�0" �
FIG. 33 � TUBE REMOVAL SPACE - G & H COMPRESSOR UNITS (STD. DIMENSIONS)
FORM 160.52-PA1
59YORK INTERNATIONAL
Add dimensions below if Marine Water Boxes supplied. (Not required if water boxes are removed.)
D CCOOLER
HCONDENSERS
G
B
A
7/8"
E
F
FLOOR LINE
J*(Tube pulling space (either end))
LD02155
FIG. 34 � TUBE REMOVAL SPACE - J COMPRESSOR UNITS (STD. DIMENSIONS)
SHELL NO. OF 1 5 0 #
CODE PASSES COOLER CONDENSER
1 2'�2-1/2" 2'�4-3/8"
G 2 1'�10-1/2" 2'�2-3/8"
3 1'�8-1/2" 1'�9-1/8"
1 2'�4-3/4" 2'�8-3/4"
H 2 2'�0-3/4" 2'�5"
3 1'�10-1/2" 2'�0-1/4"
1 2'�6-3/4" 2'�8-7/8"
J 2 2'�2-3/4" 2'�5-1/8"
3 2'�0-3/4" 2'�2-3/8"
1 2'�6-3/4" 2'�8-7/8"
T 2 2'�2-3/4" 2'�5-1/8"
3 2'�0-3/4" 2'�2-3/8"
1 2'�10" 2'�9-3/8"
V 2 2'�6" 2'�6-3/4"
3 2'�2-3/4" 2'�2-3/4"
1 2'�10" ��
W 2 2'�6" ��
3 2'�4" ��
COOLER CONDENSERSSHELL
A B C D E F G H JCODE
G 1'�4-3/8" 1'�0-3/4" 3'�1-1/2" 5-1/4" 2'�2-1/4" 2'�3-1/4" 4-7/8" 2'�8-1/4" 14'�0"
H 1'�5-1/2" 1'�2-1/4" 3'�6" 5-1/4" 2'�3-1/8" 2'�5-1/4" 5-3/8" 2'�11-1/4" 14'�0"
J 1'�6-1/4" 1'�6" 4'�0" 5-1/2" 2'�3-3/4" 2'�9-3/4" 5-1/2" 3'�3" 14'�0"
T 1'�6-1/4" 1'�6" 4'�0" 5-1/2" 2'�3-3/4" 2'�9-3/4" 5-1/2" 3'�3" 16'�0"
V 1'�6-1/4" 1'�6" 4'�0" 5-1/2" 2'�3-1/4" 3'�2-1/4" 4-3/4" 3'-9-1/2" 16'�0"
W 1'�6" 2'�2-1/4" 4'�7" 4-1/2" � � � � 16'�0"
YORK INTERNATIONAL60
SHELL NO. OF 150# 300#
CODE PASSES COOLER CONDENSER COOLER CONDENSER
1 552 470 610 619
C 2 425 419 521 556
3 349 368 457 492
1 552 546 629 695
D 2 425 419 524 556
3 425 368 524 492
1 603 603 660 765
E 2 477 477 578 625
3 425 425 524 562
1 603 654 660 829
F 2 477 552 578 702
3 425 477 524 625
1 654 654 794 848
G 2 552 603 660 784
3 477 477 610 645
1 654 � 768 �
H 2 552 � 660 �
3 477 � 610 �
D CCOOLER
HCONDENSERS
G
B
A
22
E
F
FLOOR LINE
4267 *(Tube pulling space (either end)
LD02155
* Add dimensions below if Marine Water Boxes supplied. (Not required if water boxes are removed.)
FIG. 35 � TUBE REMOVAL SPACE - G & H COMPRESSOR UNITS (METRIC DIMENSIONS � mm)
COOLER CONDENSERSSHELL
A B C D E F G HCODE
C 314 286 708 127 670 419 191 508
D 321 324 775 133 638 470 168 552
E 308 343 775 159 645 540 124 641
F 321 362 864 178 638 622 127 708
G 321 419 953 165 635 714 124 819
H 321 476 1064 152 � � � �
FORM 160.52-PA1
61YORK INTERNATIONAL
D CCOOLER
HCONDENSERS
G
B
A
22
E
F
FLOOR LINE
J(Tube pulling space (either end)
LD02155
Add dimensions below if Marine Water Boxes supplied. (Not required if water boxes are removed.)
FIG. 36 � TUBE REMOVAL SPACE - J COMPRESSOR UNITS (METRIC DIMENSIONS � mm)
SHELL NO. OF 1 5 0 #
CODE PASSES COOLER CONDENSER
1 673 721
G 2 572 670
3 521 537
1 730 832
H 2 629 737
3 876 616
1 781 835
J 2 679 740
3 629 670
1 781 835
T 2 679 743
3 629 670
1 864 848
V 2 762 781
3 679 679
1 864 ��
W 2 762 ��
3 711 ��
COOLER CONDENSERSSHELL
A B C D E F G H JCODE
G 416 324 953 133 667 692 124 819 4,267
H 445 362 1,067 133 689 743 137 895 4,267
J 464 457 1,219 140 705 857 140 991 4,267
T 464 457 1,219 140 705 857 140 991 4,877
V 464 457 1,219 140 692 972 121 1,156 4,877
W 457 667 1,397 114 � � � � 4,877
YORK INTERNATIONAL62
Solid StateSA SB SC SD SF SG SH
WEIGHT
Starter Mod. (LBS.)
7LK & 14LK 2'�10" 1'�9-3/8" 1'�5" 0'�11" 1'�10" 5-7/16" 1'�4-9/16" 200
26LK & 33LK 2'�11" 2'�1-3/8" 1'�9" 1' 1'�11" 5'-15/16" 1'�5-1/16" 300
COMPR. MOTORPOWER CONNECTIONENTRANCE
POWER WIRING ENTRANCE COVERWITH 7/8" DIA. KNOCKOUTS USEDAS LEAD HOLES FOR POWER WIRINGCONDUIT CONNECTORS (SEE NOTE 12)
SHSG
C OF POWER CONNECTIONLOCATIONL
SA
SF SOLIDSTATESTARTER
SD
4"(102 mm) A1 C3
SB
SC
FRONTOF UNIT
CONDENSER
B2
FRONT OF UNIT
1 A Dimension � See Dim. B on Fig. 322 B Dimension � See Dim. G on Figs. 1 & 3 or Dim. N on Figs, 2 & 43 C Dimension � See Dim. L on Figs. 1 & 3 or Dim. R or Figs. 2 & 4
LD02153
Solid StateSA SB SC SD SF SG SH
WEIGHT
Starter Mod. (kg)
7LK & 14LK 864 543 432 279 559 138 421 91
26LK & 33LK 889 645 533 305 584 151 433 136
FIG. 37 � SOLID STATE STARTER (OPTION) LOCATION
STD. DIMENSIONS
METRIC DIMENSIONS (mm)
FORM 160.52-PA1
63YORK INTERNATIONAL
FIG. 38 � VARIABLE SPEED DRIVE (OPTION) LOCATION
COMPR. MOTORPOWER CONNECTIONENTRANCE
POWER WIRINGENTRANCE LOCATION (SEE NOTE 13)
VHVG
VE
VA
VF
VARIABLE SPEED DRIVEVJ
VB
VD
VC
4"C3A1
FRONTOF UNIT
CONDENSER
B2
FRONT OF UNIT
LD02154
1 A Dimension � See Dim. B on Fig. 322 B Dimension � See Dim. G on Figs. 1 & 3 or Dim. N on Figs. 2 & 43 C Dimension � See Dim. L on Figs. 1 & 3 or Dim. R or Figs. 2 & 4
MOTORVA VB VC VD VE VF VG VH VJ
WEIGHT
SIZE (LBS.)
CF - CN, 5CC-5CI 4'�6" 3'�8" 1'�9" 1'�7" 0'�7-7/8" 2'�6" 7-5/8" 1'�10-3/8" 4-1/2" 1,150
CP - CT, 5CJ - 5CM 4'�11" 3'�11" 1'�9" 1'�7" 0'�6-7/8" 2'�11" 8-1/8" 2'�2-7/8" � 1,300
CU - CZ, 5CN - 5C5 4'�11" 4'�3" 1'�10" 2'�2-3/8" 1'�2-7/8" 3'�0" 9-1/2" 1'�8" � �
MOTORVA VB VC VD VE VF VG VH VJ
WEIGHT
SIZE (LBS.)
CF - CN, 5CC-5CI 4'�6" 3'�8" 1'�9" 1'�7" 0'�7-7/8" 2'�6" 7-5/8" 1'�10-3/8" 4-1/2" 1,150
CP - CT, 5CJ - 5CM 4'�11" 3'�11" 1'�9" 1'�7" 0'�6-7/8" 2'�11" 8-1/8" 2'�2-7/8" � 1,300
CU - CZ, 5CN - 5CS 4'�11" 4'�3" 1'�10" 2'�2-3/8" 1'�2-7/8" 3'�0" 9-1/2" 1'�8" � �
YORK INTERNATIONAL64
HOT GAS CONNECTION
TAPE INSULATION TO FILTERDRIER TO ALLOW REMOVAL FORREPLACEMENT OF FILTER
REFRIG. FROM OIL COOLER TO COOLER
1
1
1
7
4
6
11
2 5
4
1
3
1
17
6
CONDENSER
COOLER
DETAIL "B"
CONDENSER
COOLER
LIQUID LEVELSIGHT GLASS
DRAIN & CHARGINGCONNECTION
LIQUID LINE
SECTION "A" - "A"
SEE DET. B
TAPE INSULATIONAROUND FLANGESTO ALLOW FORREMOVAL. DO NOTGLUE.
INSULATION OVERLIFTING HOLE TOBE TAPED ON TOALLOW FOR REMOVAL. DONOT GLUE.(4 PLACES)
CONDENSER
COOLER
INSULATION ON WATER BOXES MUST BEREMOVABLE FOR SERVICE ACCESSAND/OR LIFTING
INSULATEEXPOSEDSURFACE OF OIL COOLER
HOT GAS CONNECTION SEE SECT. "A" - "A"
2" LIQUID LEVEL INDICATORSEE SECT. "A"-"A"
A 4" LIQUID LINE SEE SECT. "A" - "A"
SEEDET. B
A
FIG. 39 � THERMAL INSULATION RECOMMENDATIONS - G & H COMPRESSOR UNITS (STD. DIMENSIONS)
LD02625
ITEM COOLER CODE
NO.DESCRIPTION
C D E F G H
1 Insulation, 3/4" thick (sq. ft)
Cooler with:
Compact Water Boxes 284 290 290 313 368 368
Marine Water Boxes (150#) 312 324 328 350 418 418
Marine Water Boxes (300#) 330 337 343 380 440 450
Water Boxes Only
Compact Water Boxes 19 25 25 25 36 36
Marine Water Boxes (150#) 47 59 63 63 86 86
Marine Water Boxes (300#) 65 72 78 92 108 120
2 Insulation � 4-1/2" I.D. x 3/4" Wall (Ft.) 3 3 3 3 3 3
3 * Insulation � 3-1/2" I.D. x 3/4" Wall (Ft.) 5 5 5 5 5 5
4 Insulation � 2-7/8" I.D. x 3/4" Wall (Ft.) 2 2 2 2 2 2
5 Insulation � 1-3/8" I.D. x 3/4" Wall (Ft.) 2 2 2 2 2 2
6 Insulation � 1-1/8" I.D. x 3/4" Wall (Ft.) 7 7 7 7 7 7
7 Insulation � 3/8" I.D. x 3/4" Wall (Ft.) 4 4 4 4 4 4
* Used on units with hot gas bypass only.
FORM 160.52-PA1
65YORK INTERNATIONAL
FIG. 39A � THERMAL INSULATION RECOMMENDATIONS - G & H COMPRESSOR UNITS (METRIC DIMENSIONS)
LD02625
ITEM COOLER CODE
NO.DESCRIPTION
C D E F G H
1 Insulation, 19 mm thick (sq. m)
Cooler with:
Compact Water Boxes 27 27 27 29 34 35
Marine Water Boxes (150#) 29 30 31 33 39 39
Marine Water Boxes (300#) 31 32 32 36 41 42
Water Boxes Only
Compact Water Boxes 2 3 3 3 4 4
Marine Water Boxes (150#) 5 6 6 6 8 8
Marine Water Boxes (300#) 6 7 8 9 11 12
2 Insulation � 114 mm I.D. x 19 mm Wall (mm) 77 77 77 77 77 77
3 * Insulation � 89 mm I.D. x 19 mm Wall (mm) 127 127 127 127 127 127
4 Insulation � 73 mm I.D. x 19 mm Wall (mm) 51 51 51 51 51 51
5 Insulation � 35 mm I.D. x 19 mm Wall (mm) 51 51 51 51 51 51
6 Insulation � 29 mm I.D. x 19 mm Wall (mm) 179 179 179 179 179 179
7 Insulation � 10 mm I.D. x 19 mm Wall (mm) 102 102 102 102 102 102
* Used on units with hot gas bypass only.
HOT GAS CONNECTION
TAPE INSULATION TO FILTERDRIER TO ALLOW REMOVAL FORREPLACEMENT OF FILTER
REFRIG. FROM OIL COOLER TO COOLER
1
1
1
7
4
6
11
2 5
4
1
3
1
17
6
CONDENSER
COOLER
DETAIL "B"
CONDENSER
COOLER
LIQUID LEVELSIGHT GLASS
DRAIN & CHARGINGCONNECTION
LIQUID LINE
SECTION "A" - "A"
SEE DET. B
TAPE INSULATIONAROUND FLANGESTO ALLOW FORREMOVAL. DO NOTGLUE.
INSULATION OVERLIFTING HOLE TOBE TAPED ON TOALLOW FOR REMOVAL. DONOT GLUE.(4 PLACES)
CONDENSER
COOLER
INSULATION ON WATER BOXES MUST BEREMOVABLE FOR SERVICE ACCESSAND/OR LIFTING
INSULATEEXPOSEDSURFACE OF OIL COOLER
HOT GAS CONNECTION SEE SECT. "A" - "A"
2" LIQUID LEVEL INDICATORSEE SECT. "A"-"A"
A 4" LIQUID LINE SEE SECT. "A" - "A"
SEEDET. B
A
YORK INTERNATIONAL66
* Used on units with hot gas bypass only. 4-1/2" I.D. on W Cooler.
TAPE INSULATION AROUNDFLANGES TO ALLOW FOR REMOVAL. DO NOT GLUE.
COMPRESSOR
COOLER
INSULATION OVER LIFTINGHOLE TO BE TAPED ONTO ALLOW FOR REMOVALDO NOT GLUE (4 PLACES)
REFRIG. FROM OIL COOLER TO COOLER
BALL VALVE
OIL RESERVOIR
6" LIQUID LINESEE SECT. "A"-"A"
INSULATE EXPOSEDSURFACE OFOIL COOLER
DET. BCOMPRESSOR
OIL EDUCTOR
1
6
3 8 5
1
1
1
7 7
A
A
SECTION "A" - "A"
1 4
1
3
�
1 NPT DRAIN& CHARGING
2
CONDENSER
CONDENSER
COOLER
COOLER
HOT GAS CONNECTION
2" LIQUID LEVEL
INDICATOR6" LIQUID LINE
TAPE INSULATION TO FILTERDRYER TO ALLOW REMOVAL FOR REPLACEMENT OF FILTER1
6
51
��
HOT GAS CONN.SEE SECT. "A"-"A"
1
1
2" LIQUID LEVELINDICATOR
SEE SECT. "A" - "A"
SEE DET. B
SEEDET. B
FIG. 40 � THERMAL INSULATION RECOMMENDATIONS - J COMPRESSOR UNITS (STD. DIMENSIONS)
LD03375
ITEM COOLER CODE
NO.DESCRIPTION
C D E F G
1 Insulation, 3/4" thick (sq. ft)
Cooler with:
Compact Water Boxes 265 290 337 362 410
Marine Water Boxes (150#) 290 315 366 395 448
Water Boxes Only
Compact Water Boxes 22 25 28 31 35
Marine Water Boxes (150#) 58 63 78 83 94
2 Insulation � 4-1/2" I.D. x 3/4" Wall (Ft.) 2 2 2 2 2
3 * Insulation � 3-1/2" I.D. x 3/4" Wall (Ft.) 1 1 1 1 1
4 Insulation � 2-7/8" I.D. x 3/4" Wall (Ft.) 2 2 2 2 2
5 Insulation � 1-3/8" I.D. x 3/4" Wall (Ft.) 6 6 6 6 6
6 Insulation � 1-1/8" I.D. x 3/4" Wall (Ft.) 3 3 3 3 3
7 Insulation � 3/8" I.D. x 3/4" Wall (Ft.) 6 6 6 6 6
8 Insulation � 2-3/8" I.D. x 3/4� Wall (Ft.) 1 1 1 1 1
FORM 160.52-PA1
67YORK INTERNATIONAL
TAPE INSULATION AROUNDFLANGES TO ALLOW FOR REMOVAL. DO NOT GLUE.
COMPRESSOR
COOLER
INSULATION OVER LIFTINGHOLE TO BE TAPED ONTO ALLOW FOR REMOVALDO NOT GLUE (4 PLACES)
REFRIG. FROM OIL COOLER TO COOLER
BALL VALVE
OIL RESERVOIR
6" LIQUID LINESEE SECT. "A"-"A"
INSULATE EXPOSEDSURFACE OFOIL COOLER
DET. BCOMPRESSOR
OIL EDUCTOR
1
6
3 8 5
1
1
1
7 7
A
A
SECTION "A" - "A"
1 4
1
3
�
1 NPT DRAIN& CHARGING
2
CONDENSER
CONDENSER
COOLER
COOLER
HOT GAS CONNECTION
2" LIQUID LEVEL
INDICATOR6" LIQUID LINE
TAPE INSULATION TO FILTERDRYER TO ALLOW REMOVAL FOR REPLACEMENT OF FILTER1
6
51
��
HOT GAS CONN.SEE SECT. "A"-"A"
1
1
2" LIQUID LEVELINDICATOR
SEE SECT. "A" - "A"
SEE DET. B
SEEDET. B
* Used on units with hot gas bypass only. 114 mm I.D. on W Cooler.
FIG. 40A � THERMAL INSULATION RECOMMENDATIONS - J COMPRESSOR UNITS (METRIC DIMENSIONS)
ITEM COOLER CODE
NO.DESCRIPTION
C D E F G
1 Insulation, 19 mm thick (sq. m)
Cooler with:
Compact Water Boxes 25 27 32 34 38
Marine Water Boxes (150#) 27 29 34 36 42
Water Boxes Only
Compact Water Boxes 2 3 3 3 4
Marine Water Boxes (150#) 6 6 8 8 9
2 Insulation � 89 mm I.D. x 19 mm Wall (mm) 51 51 51 51 51
3 * Insulation � 73 mm I.D. x 19 mm Wall (mm) 26 26 26 26 26
4 Insulation � 35 mm I.D. x 19 mm Wall (mm) 51 51 51 51 51
5 Insulation � 29 mm I.D. x 19 mm Wall (mm) 153 153 153 153 153
6 Insulation � 10 mm I.D. x 19 mm Wall (mm) 77 77 77 77 77
7 Insulation � 22 mm I.D. x 19 mm Wall (mm) 153 153 153 153 153
8 Insulation � 60 mm I.D. x 19 mm Wall (mm) 26 26 26 26 26
YORK INTERNATIONAL68
FIG. 41 � FORM 3 & 7 SHIPMENT - G & H COMPRESSOR UNITS (STD. AND METRIC DIMENSIONS)
A
B
C
D
E
F G
H
CONDENSER
COOLER
LD02626
FORM 160.52-PA1
69YORK INTERNATIONAL
FIG. 41 � (CONT�D) FORM 3 & 7 SHIPMENT - G & H COMPRESSOR UNITS (STD. AND METRIC DIMENSIONS)
COOLER DIMENSIONS & SHIPPING WEIGHTS (Standard)
CONDENSER DIMENSIONS & SHIPPING WEIGHTS (Standard)
* For Dimension �A�, refer to Fig. 1 and add water box dimensions from appropriate Figures.
COOLER DIMENSIONS & SHIPPING WEIGHTS (Metric)
CONDENSER DIMENSIONS & SHIPPING WEIGHTS (Metric)
* For Dimension �A�, refer to Fig. 3 and add water box dimensions from appropriate Figures.
SHIPPING WT. (LBS.)
COOLER A B C D WITH COMPACT
CODE WATER BOXES
C * 3'�2" 3'�7-3/4" 5'�6-1/2" 7450
D * 3'�5" 3'�9-1/4" 5'�6-1/2" 8450
E * 3'�7" 4'�0-1/4" 5'�8-1/2" 9125
F * 4'�0" 4'�3-1/4" 5'�9" 10,055
G * 4'�2-1/2" 4'�7-3/4" 5'�11-5/8" 12,400
H * 4'�6" 4'�10-3/4" 6'�3-3/8" 14,320
SHIPPING WT. (LBS.)
COND. E F G H WITH COMPACT
CODE WATER BOXES
C 2'�11" 4'�6-3/4" 4'�11-3/4" 4'�0" 5,600
D 2'�11" 4'�6-3/4" 5'�1-3/4" 4'�0" 6,500
E 2'�11" 4'�9-1/4" 5'�2-1/4" 4'�0" 7,465
F 3'�2" 5'�2-1/4" 5'�4-3/4" 4'�2" 8,825
G 3'�6" 5'�6-1/4" 5'�8-3/4" 4'�4" 11,000
SHIPPING WT. (KG)
COOLER A B C D WITH COMPACT
CODE WATER BOXES
C * 965 1,111 1,689 3,379
D * 1,041 1,149 1,689 3,833
E * 1,092 1,226 1,740 4,139
F * 1,219 1,302 1,753 4,561
G * 1,283 1,416 1,819 5,624
H * 1,372 1,492 1,915 6,496
SHIPPING WT. (KG)
COND. E F G H WITH COMPACT
CODE WATER BOXES
C 889 1,391 1,518 1,219 2,540
D 889 1,391 1,568 1,219 2,948
E 889 1,454 1,581 1,219 3,386
F 965 1,581 1,645 1,270 4,003
G 1,067 1,988 1,746 1,321 4,990
YORK INTERNATIONAL70
A
B
C
D
E
F G
H
FIG. 42 � FORM 3 & 7 SHIPMENT - J COMPRESSOR UNITS (STD. AND METRIC DIMENSIONS)
CONDENSER
COOLER
LD02626
FORM 160.52-PA1
71YORK INTERNATIONAL
FIG. 42 � (CONT�D)
COOLER DIMENSIONS & SHIPPING WEIGHTS (Standard)
CONDENSER DIMENSIONS & SHIPPING WEIGHTS (Standard)
* For Dimension �A�, refer to Fig. 2 and add appropriate water box dimensions from appropriate Figures.
COOLER DIMENSIONS & SHIPPING WEIGHTS (Metric)
CONDENSER DIMENSIONS & SHIPPING WEIGHTS (Metric)
* For Dimension �A�, refer to Fig. 4 and add appropriate water box dimensions from appropriate Figures.
SHIPPING WT. (LBS.)COOLER
A B C D WITH COMPACTCODE
WATER BOXES
G * 4'�0" 4'�9-1/4" 5'�6" 10,300
H * 4'�4-1/2" 5'�1-1/2" 5'�6" 12,560
J * 4'�11" 5�7-3/4" 6'�0" 15,740
T * 4'�11" 5'�7-3/4" 6'�0" 17,310
V * 4'�11" 5'�7-3/4" 6'�0" 18,320
W * 5'�4" 6'�0-1/4" 7'�2" 22,570
SHIPPING WT. (LBS.)COND.
E F G H WITH COMPACTCODE
WATER BOXES
G 3'�6" 5'�4-1/4" 6'�2-1/4" 4'�9" 11,160
H 3'�10" 5'�5-3/4" 6'�8-1/4" 4'�11" 12,350
J 4'�2" 5'�9-3/4" 6'�8-1/4" 5'�1" 14,490
T 4'�2" 5'�9-3/4" 6'�8-1/4" 5'�1" 16,090
V 4'�7" 6'�2-3/4" 7'�0-1/4" 5'�3-1/2" 19,430
SHIPPING WT. (KG)
COOLER A B C D WITH COMPACT
CODE WATER BOXES
C * 1,219 1,454 1,676 4,672
D * 1,334 1,562 1,676 5,697
E * 1,499 1,721 1,829 7,140
F * 1,499 1,721 1,829 7,852
G * 1,499 1,721 1,829 8,310
H * 1,626 1,835 2,184 10,238
SHIPPING WT. (KG)
COND. E F G H WITH COMPACT
CODE WATER BOXES
C 1,067 1,632 1,886 1,448 5,062
D 1,168 1,670 2,038 1,499 5,602
E 1,270 1,772 2,038 1,549 6,573
F 1,270 1,772 2,038 1,549 7,298
G 1,397 1,899 2,140 1,613 8,813
Proud Sponsorof the 1998U.S. Olympic Team
36USC380
P.O. Box 1592, York, Pennsylvania USA 17405-1592 Subject to change without notice. Printed in USA
Copyright © by York International Corporation 1998 ALL RIGHTS RESERVED
Form160.52-PA1 (1098)
Supersedes: 160.52-PA1 (198)