product guide, transformer protection ret650, iec
Post on 11-Sep-2021
5 Views
Preview:
TRANSCRIPT
Relion® 650 series
Transformer protection RET650Product Guide
Contents
1. 650 series overview..............................................3
2. Application...........................................................3
3. Available functions...............................................7
4. Differential protection.........................................17
5. Current protection..............................................18
6. Voltage protection..............................................19
7. Frequency protection.........................................20
8. Secondary system supervision..........................21
9. Control................................................................21
10. Logic..................................................................22
11. Monitoring.........................................................23
12. Metering............................................................26
13. Human Machine interface.................................26
14. Basic IED functions...........................................27
15. Station communication.....................................28
16. Hardware description........................................29
17. Connection diagrams........................................30
18. Technical data...................................................37
19. Ordering............................................................73
Disclaimer
The information in this document is subject to change without notice and should not be construed as a commitment by ABB AB. ABB AB assumesno responsibility for any errors that may appear in this document.
© Copyright 2011 ABB AB.
All rights reserved.
Trademarks
ABB and Relion are registered trademarks of ABB Group. All other brand or product names mentioned in this document may be trademarks orregistered trademarks of their respective holders.
Transformer protection RET650 1MRK 504 127-BEN -Product version: 1.1 Issued: February 2011
2 ABB
1. 650 series overview
The 650 series IEDs provide optimum 'off-the-shelf', ready-to-use solutions. It is configuredwith complete protection functionality anddefault parameters to meet the needs of awide range of applications for generationtransmission and sub-transmission grids.
The 650 series IEDs include:
• Complete ready-made solutions optimizedfor a wide range of applications forgeneration, transmission and sub-transmission grids.
• Support for user-defined names in the locallanguage for signal and functionengineering.
• Minimized parameter setting based ondefault values and ABB's new global basevalue concept. You only need to set thoseparameters specific to your ownapplication, such as the line data.
• GOOSE messaging for horizontalcommunication.
• Extended HMI functionality with 15dynamic three-color-indication LEDs perpage, on up to three pages, andconfigurable push-button shortcuts fordifferent actions.
• Programmable LED text-based labels.• Settable 1A/5A -rated current inputs.
2. Application
RET650 provides fast and selectiveprotection, monitoring and control for two-and three-winding transformers,autotransformers, generator-transformer unitsand shunt reactors. The transformer IED isdesigned to operate correctly over a widefrequency range in order to accommodatepower system frequency variations duringdisturbances and generator start-up and shut-down.
A very fast differential protection function,with automatic CT ratio matching and vectorgroup compensation, makes this IED theideal solution even for the most demandingapplications. Since RET650 has very lowrequirements on the main CTs, nointerposing CTs are required. The differentialprotection function is provided with 2ndharmonic and wave-block restraint features toavoid tripping for magnetizing inrush current,and 5th harmonic restraint to avoid trippingfor overexcitation.
The differential function offers a highsensitivity for low-level internal faults. Theunique and innovative sensitive differentialprotection feature of the RET650 provides thebest possible coverage for winding internalturn-to-turn faults, based on well-knowntheory of symmetrical components .
Low impedance restricted earth-faultprotection function are available ascomplimentary sensitive and fast mainprotection against winding earth faults. Thisfunction includes a directional zero-sequencecurrent criterion for additional security.
Tripping from Pressure relief/Buchholz andtemperature devices can be done through thetransformer IED where pulsing, lock-outcontact output and so on, is performed. Thebinary inputs are heavily stabilized againstdisturbance to prevent incorrect operations atfor example, dc system capacitive dischargesor DC earth faults.
Versatile phase, earth, negative and zerosequence overcurrent functions, which can bemade directional, provide further alternativebackup protection. Thermal overload withtwo time-constants, volts per hertz, over/under voltage are also available.
A built-in disturbance and event recordersprovide valuable data to the user about statusand operation for post-fault disturbanceanalysis.
Breaker failure protection allows high speedback-up tripping of surrounding breakers.
Transformer protection RET650 1MRK 504 127-BEN -Product version: 1.1 Issued: February 2011
Revision: -
ABB 3
Disturbance recording is available to allowindependent post-fault analysis after primarydisturbances.
Three packages have been defined for thefollowing applications:
• Two-winding transformer in singlebreaker arrangements (A01)
• Three-winding transformer in singlebreaker arrangements (A05)
• Tap changer control (A07)
The packages are configured and ready fordirect use. Analog and tripping IO has beenpre-defined for basic use. Other signals needto be applied as required for each application.
The graphical configuration tool ensuressimple and fast testing and commissioning.
Transformer protection RET650 1MRK 504 127-BEN -Product version: 1.1 Issued: February 2011
4 ABB
T2W PDIF
87T 3Id/I
CC RBRF
50BF 3I> BF
CC RBRF
50BF 3I> BF
OC4 PTOC
50/51 3I>
OC4 PTOC
51/67 3I>
CC RPLD
52PD PD
EF4 PTOC
51N IN>
CC RPLD
52PD PD
TR PTTR
49 Ith
C MSQI
Meter.
V MMXU
Meter.
C MMXU
Meter.
CV MMXN
Meter.
TCS SCBR
Cond
TCS SCBR
Cond
SPVN ZBAT
Cond
TR8 ATCC
90 U
TCM YLTC
84
UV2 PTUV
27 U<
OV2 PTOV
59 U>
PH PIOC
50 3I>>
TR PTTR
49 Ith
REF PDIF
87N IdN/I
Other configured functions
REF PDIF
87N IdN/I
EF4 PTOC
51N/67N IN>
DRP RDRE
Mont.
YY
¨
ROV2 PTOV
59N 3U0>
RET650 A01 - 2 Winding Transformer protection 10AI (8I+2U)
20 MVA110±11*1.5% / 21 kV
105 / 550 AYNd5
20 kV Bus
110 kV Bus
200/1
600/120kV/100V
200/1
600/1
IEC61850
ANSI IEC
Function Enabled in Settings
IEC61850
ANSI IEC
Function Disabled in Settings
W1
W2
IEC09000645-2-en.vsd
IEC09000645 V2 EN
Figure 1. A typical protection application for a two-winding transformer in single breakerarrangement
Transformer protection RET650 1MRK 504 127-BEN -Product version: 1.1 Issued: February 2011
ABB 5
RET650 A05 - 3 Winding Transformer protection 20AI 2*(6I+4U)
W1
T3W PDIF
87T 3Id/I
CC RBRF
50BF 3I> BF
CC RBRF
50BF 3I> BF
OC4 PTOC
50/51 3I>
OC4 PTOC
51/67 3I>
CC RPLD
52PD PD
CC RBRF
50BF 3I> BF
CC RPLD
52PD PD
EF4 PTOC
51N IN>
CC RPLD
52PD PD
TR PTTR
49 Ith
TR PTTR
49 Ith
V MSQI
Meter.
C MSQI
Meter.
V MMXU
Meter.
C MMXU
Meter.
CV MMXN
Meter.
V MSQI
Meter.
C MSQI
Meter.
V MMXU
Meter.
C MMXU
Meter.
CV MMXN
Meter.
TCS SCBR
Cond
TCS SCBR
Cond
TCS SCBR
Cond
SPVN ZBAT
Cond
TR8 ATCC
90 U
TCM YLTC
84
UV2 PTUV
27 U<
OV2 PTOV
59 U>
PH PIOC
50 3I>>
TR PTTR
49 Ith
REF PDIF
87N IdN/I
Other configured functions
REF PDIF
87N IdN/I
REF PDIF
87N IdN/I
OEX PVPH
24 U/f>
OC4 PTOC
51/67 3I>
EF4 PTOC
51N/67N IN>
EF4 PTOC
51N/67N IN>
DRP RDRE
Mont.
CV MMXN
Meter.
YY
¨
ROV2 PTOV
59N 3UO>
35 kV Bus
110 kV Bus
10 kV Bus
IEC61850
ANSI IEC
Function Enabled in Settings
IEC61850
ANSI IEC
Function Disabled in Settings
Transformer Data:40/40/15 MVA
110±11*1.5% / 36.75 / 10.5 kV210/628/825 A
YNyn0d5
110kV/100V
300/1
1000/1
800/1
800/1
300/1
10kV/100V
35kV/100V
1000/1W3 W2
IEC09000646-2-en.vsd
IEC09000646 V2 EN
Figure 2. A typical protection application for a three-winding transformer in single breakerarrangement
Transformer protection RET650 1MRK 504 127-BEN -Product version: 1.1 Issued: February 2011
6 ABB
RET650 A07 – OLTC Control for 1 or 2 Transformers 10AI (6I+4U)
TR PTTR
49 Ith
EF4 PTOC
50N/51N IN>
CV MMXN
Meter.
T1
OC4 PTOC
50/51 3I>
ETP MMTR
Meter.
ROV PTOV
59N 3U0>
T2TRx ATCC
90 UUV2 PTOV
27 U<
OV2 PTOV
59 U>
TR PTTR
49 Ith
EF4 PTOC
50N/51N IN>
CV MMXN
Meter.OC4 PTOC
50/51 3I>
ETP MMTR
Meter.
ROV2 PTOV
59N 3Uo>TR8 ATCC
90 U
UV2 PTUV
27 U<
OV2 PTOV
59 U>
T1
T2
YY
°
YY
°
TCM YLTC
84
TCM YLTC
84
TCS SCBR
Cond
TCS SCBR
Cond
SPVN ZBAT
Cond
Other configured functions
DRP RDRE
Mont.
T1 Data:20 MVA
110±11*1.5% / 21 kV105 / 550 A
YNd5XT=11 %
T2 Data:20 MVA
110±11*1.5% / 21 kV105 / 550 A
YNd5XT=11 %
20 kV Bus #1 20 kV Bus #2
IEC61850
ANSI IEC
Function Enabled in Settings
IEC61850
ANSI IEC
Function Disabled in Settings
600/1
20kV/100V
600/1
20kV/100V
W2
W2
IEC09000647-2-en.vsd
IEC09000647 V2 EN
Figure 3. A typical tap changer control application for one or two transformers
Transformer protection RET650 1MRK 504 127-BEN -Product version: 1.1 Issued: February 2011
ABB 7
3. Available functions
Main protection functions
IEC 61850/Functionblock name
ANSI Function description Transformer
RET650 (
A01)
2W
/1C
B
RET650 (
A05)
3W
/1C
B
RET650 (
A07)
OLTC
Differential protection
T2WPDIF 87T Transformer differential protection, twowinding
1
T3WPDIF 87T Transformer differential protection, threewinding
1
REFPDIF 87N Restricted earth fault protection, lowimpedance
2 3
HZPDIF 87 1Ph High impedance differentialprotection
2 2
Transformer protection RET650 1MRK 504 127-BEN -Product version: 1.1 Issued: February 2011
8 ABB
Back-up protection functions
IEC 61850/Functionblockname
ANSI Function description Transformer
RET650 (
A01)
2W
/1C
B
RET650 (
A05)
3W
/1C
B
RET650 (
A07)
OLTC
Current protection
PHPIOC 50 Instantaneous phase overcurrentprotection
2 3
OC4PTOC 51/67 Four step directional phase overcurrentprotection
2 3 2
EFPIOC 50N Instantaneous residual overcurrentprotection
2 3
EF4PTOC 51N/67N
Four step directional residualovercurrent protection
2 3 2
TRPTTR 49 Thermal overload protection, two timeconstants
2 3 2
CCRBRF 50BF Breaker failure protection 2 3
CCRPLD 52PD Pole discordance protection 2 3
GUPPDUP 37 Directional underpower protection 1 1 2
GOPPDOP 32 Directional overpower protection 1 1 2
DNSPTOC 46 Negative sequence based overcurrentfunction
1 2
Voltage protection
UV2PTUV 27 Two step undervoltage protection 1 1 2
OV2PTOV 59 Two step overvoltage protection 1 1 2
ROV2PTOV 59N Two step residual overvoltageprotection
1 1 2
OEXPVPH 24 Overexcitation protection 1
Frequency protection
Transformer protection RET650 1MRK 504 127-BEN -Product version: 1.1 Issued: February 2011
ABB 9
IEC 61850/Functionblockname
ANSI Function description Transformer
RET650 (
A01)
2W
/1C
B
RET650 (
A05)
3W
/1C
B
RET650 (
A07)
OLTC
SAPTUF 81 Underfrequency function 4 4 4
SAPTOF 81 Overfrequency function 4 4 4
SAPFRC 81 Rate-of-change frequency protection 2 2 4
Transformer protection RET650 1MRK 504 127-BEN -Product version: 1.1 Issued: February 2011
10 ABB
Control and monitoring functions
IEC 61850/Function blockname
ANSI Function description Transformer
RET650 (
A01)
2W
/1C
B
RET650 (
A05)
3W
/1C
B
RET650 (
A07)
OLTC
Control
QCBAY Bay control 1 1 1
LOCREM Handling of LR-switch positions 1 1 1
LOCREMCTRL LHMI control of Permitted SourceTo Operate (PSTO)
1 1 1
TR8ATCC 90 Automatic voltage control for tapchanger, parallel control
1 1 2
TCMYLTC 84 Tap changer control andsupervision, 6 binary inputs
1 1 2
SLGGIO Logic Rotating Switch for functionselection and LHMI presentation
15 15 15
VSGGIO Selector mini switch extension 20 20 20
DPGGIO IEC 61850 generic communication I/O functions double point
16 16 16
SPC8GGIO Single point generic control 8 signals 5 5 5
AUTOBITS AutomationBits, command functionfor DNP3.0
3 3 3
I103CMD Function commands forIEC60870-5-103
1 1 1
I103IEDCMD IED commands for IEC60870-5-103 1 1 1
I103USRCMD Function commands user definedfor IEC60870-5-103
4 4 4
I103GENCMD Function commands generic forIEC60870-5-103
50 50 50
I103POSCMD IED commands with position andselect for IEC60870-5-103
50 50 50
Secondary system supervision
TCSSCBR Breaker close/trip circuit monitoring 3 3 3
Transformer protection RET650 1MRK 504 127-BEN -Product version: 1.1 Issued: February 2011
ABB 11
IEC 61850/Function blockname
ANSI Function description Transformer
RET650 (
A01)
2W
/1C
B
RET650 (
A05)
3W
/1C
B
RET650 (
A07)
OLTC
Logic
SMPPTRC 94 Tripping logic 2 3 2
TMAGGIO Trip matrix logic 12 12 12
OR Configurable logic blocks, OR gate 283 283 283
INVERTER Configurable logic blocks, Invertergate
140 140 140
PULSETIMER Configurable logic blocks, Pulsetimer
40 40 40
GATE Configurable logic blocks,Controllable gate
40 40 40
XOR Configurable logic blocks, exclusiveOR gate
40 40 40
LOOPDELAY Configurable logic blocks, loop delay 40 40 40
TIMERSET Configurable logic blocks, timerfunction block
40 40 40
AND Configurable logic blocks, AND gate 280 280 280
SRMEMORY Configurable logic blocks, set-resetmemory flip-flop gate
40 40 40
RSMEMORY Configurable logic blocks, reset-setmemory flip-flop gate
40 40 40
FXDSIGN Fixed signal function block 1 1 1
B16I Boolean 16 to Integer conversion 16 16 16
B16IFCVI Boolean 16 to Integer conversionwith logic node representation
16 16 16
IB16A Integer to Boolean 16 conversion 16 16 16
IB16FCVB Integer to Boolean 16 conversionwith logic node representation
16 16 16
Monitoring
CVMMXN Measurements 6 6 6
Transformer protection RET650 1MRK 504 127-BEN -Product version: 1.1 Issued: February 2011
12 ABB
IEC 61850/Function blockname
ANSI Function description Transformer
RET650 (
A01)
2W
/1C
B
RET650 (
A05)
3W
/1C
B
RET650 (
A07)
OLTC
CMMXU Phase current measurement 10 10 10
VMMXU Phase-phase voltage measurement 6 6 6
CMSQI Current sequence componentmeasurement
6 6 6
VMSQI Voltage sequence measurement 6 6 6
VNMMXU Phase-neutral voltage measurement 6 6 6
CNTGGIO Event counter 5 5 5
DRPRDRE Disturbance report 1 1 1
AxRADR Analog input signals 4 4 4
BxRBDR Binary input signals 6 6 6
SPGGIO IEC 61850 generic communication I/O functions
64 64 64
SP16GGIO IEC 61850 generic communication I/O functions 16 inputs
16 16 16
MVGGIO IEC 61850 generic communication I/O functions
16 16 16
MVEXP Measured value expander block 66 66 66
SPVNZBAT Station battery supervision 1 1 1
SSIMG 63 Insulation gas monitoring function 2 2 2
SSIML 71 Insulation liquid monitoring function 2 2 2
SSCBR Circuit breaker condition monitoring 2 3 2
I103MEAS Measurands for IEC60870-5-103 1 1 1
I103MEASUSR Measurands user defined signals forIEC60870-5-103
3 3 3
I103AR Function status auto-recloser forIEC60870-5-103
1 1 1
I103EF Function status earth-fault forIEC60870-5-103
1 1 1
Transformer protection RET650 1MRK 504 127-BEN -Product version: 1.1 Issued: February 2011
ABB 13
IEC 61850/Function blockname
ANSI Function description Transformer
RET650 (
A01)
2W
/1C
B
RET650 (
A05)
3W
/1C
B
RET650 (
A07)
OLTC
I103FLTPROT Function status fault protection forIEC60870-5-103
1 1 1
I103IED IED status for IEC60870-5-103 1 1 1
I103SUPERV Supervison status forIEC60870-5-103
1 1 1
I103USRDEF Status for user defined signals forIEC60870-5-103
20 20 20
Metering
PCGGIO Pulse counter logic 16 16 16
ETPMMTR Function for energy calculation anddemand handling
3 3 3
Transformer protection RET650 1MRK 504 127-BEN -Product version: 1.1 Issued: February 2011
14 ABB
Designed to communicate
IEC 61850/Function blockname
ANSI Function description Transformer
RET650 (
A01)
2W
/1C
B
RET650 (
A05)
3W
/1C
B
RET650 (
A07)
OLTC
Station communication
IEC 61850 communicationprotocol, LAN1
1 1 1
DNP3.0 for TCP/IPcommunication protocol, LAN1
1 1 1
IEC61870-5-103 IEC60870-5-103 serialcommunication via ST
1 1 1
GOOSEINTLKRCV Horizontal communication viaGOOSE for interlocking
59 59 59
GOOSEBINRCV GOOSE binary receive 4 4 4
GOOSEVCTRCONF GOOSE VCTR configuration forsend and receive
1 1 1
VCTRSEND Voltage control sending block forGOOSE
1 1 1
GOOSEVCTRRCV Voltage control receiving blockfor GOOSE
3 3 3
GOOSEDPRCV GOOSE function block to receivea double point value
32 32 32
GOOSEINTRCV GOOSE function block to receivean integer value
32 32 32
GOOSEMVRCV GOOSE function block to receivea mesurand value
16 16 16
GOOSESPRCV GOOSE function block to receivea single point value
64 64 64
Transformer protection RET650 1MRK 504 127-BEN -Product version: 1.1 Issued: February 2011
ABB 15
Basic IED functions
IEC 61850/Function blockname
Function description
Basic functions included in all products
INTERRSIG Self supervision with internal event list 1
SELFSUPEVLST Self supervision with internal event list 1
SNTP Time synchronization 1
TIMESYNCHGEN Time synchronization 1
DTSBEGIN,DTSEND,TIMEZONE
Time synchronization, daylight saving 1
IRIG-B Time synchronization 1
SETGRPS Setting group handling 1
ACTVGRP Parameter setting groups 1
TESTMODE Test mode functionality 1
CHNGLCK Change lock function 1
TERMINALID IED identifiers 1
PRODINF Product information 1
PRIMVAL Primary system values 1
SMAI_20_1-12 Signal matrix for analog inputs 2
3PHSUM Summation block 3 phase 12
GBASVAL Global base values for settings 6
ATHSTAT Authority status 1
ATHCHCK Authority check 1
FTPACCS FTP access with password 1
DOSFRNT Denial of service, frame rate control for front port 1
DOSLAN1 Denial of service, frame rate control for LAN1 1
DOSSCKT Denial of service, socket flow control 1
Transformer protection RET650 1MRK 504 127-BEN -Product version: 1.1 Issued: February 2011
16 ABB
4. Differential protection
Transformer differential protectionT2WPDIF/T3WPDIF
The Transformer differential protection, two-winding (T2WPDIF) and Transformerdifferential protection, three-winding(T3WPDIF) are provided with internal CTratio matching and vector groupcompensation and settable, zero sequencecurrent elimination.
The function can be provided with two orthree-phase sets of current inputs. All currentinputs are provided with percentage biasrestraint features, making the IED suitable fortwo- or three-winding transformerarrangements.
Two-winding applications
xx05000048.vsd
IEC05000048 V1 EN
two-windingpowertransformer
Three-winding applications
xx05000052.vsd
IEC05000052 V1 EN
three-windingpowertransformer withall threewindingsconnected
xx05000049.vsd
IEC05000049 V1 EN
three-windingpowertransformer withunconnecteddelta tertiarywinding
Figure 4. CT group arrangement fordifferential protection andother protections
The setting facilities cover for applications ofthe differential protection to all types ofpower transformers and auto-transformerswith or without load tap changer as well asfor shunt reactors or and local feeders within
the station. An adaptive stabilizing feature isincluded for heavy through-faults.
Stabilization is included for inrush currents aswell as for overexcitation condition. Adaptivestabilization is also included for systemrecovery inrush and CT saturation forexternal faults. A high set unrestraineddifferential current protection is included fora very high speed tripping at a high internalfault currents.
An innovative sensitive differential protectionfeature, based on the theory of symmetricalcomponents, offers the best possiblecoverage for power transformer winding turn-to-turn faults.
Restricted earth fault protectionREFPDIF
Restricted earth fault protection, lowimpedance REFPDIF
Restricted earth-fault protection, low-impedance function (REFPDIF) can be usedon all directly or low-impedance earthedwindings. The REFPDIF function can providehigher sensitivity (down to 5%) and higherspeed as it measures each windingindividually and thus does not need inrushstabilization.
The low-impedance function is a percentagebiased function with an additional zerosequence current directional comparisoncriterion. This gives excellent sensitivity andstability for through faults. The functionallows use of different CT ratios andmagnetizing characteristics on the phase andneutral CT cores and mixing with otherfunctions and protection IEDs on the samecores.
1Ph High impedance differentialprotection HZPDIF
The 1Ph High impedance differentialprotection HZPDIF function can be usedwhen the involved CT cores have the sameturn ratio and similar magnetizingcharacteristics. It utilizes an externalsummation of the currents in theinterconnected CTs and a series resistor and a
Transformer protection RET650 1MRK 504 127-BEN -Product version: 1.1 Issued: February 2011
ABB 17
voltage dependent resistor externally to theIED.
HZPDIF can be used as high impedance REFprotection.
5. Current protection
Instantaneous phase overcurrentprotection PHPIOC
The instantaneous three phase overcurrentfunction has a low transient overreach andshort tripping time to allow use as a high setshort-circuit protection function.
Four step phase overcurrentprotection OC4PTOC
The four step phase overcurrent protectionfunction OC4PTOC has an inverse or definitetime delay independent for step 1 and 4separately. Step 2 and 3 are always definitetime delayed.
All IEC and ANSI time delayed characteristicsare available.
The directional function is voltage polarizedwith memory. The function can be set to bedirectional or non-directional independentlyfor each of the steps.
Instantaneous residual overcurrentprotection EFPIOC
The Instantaneous residual overcurrentprotection EFPIOC has a low transientoverreach and short tripping times to allowuse for instantaneous earth-fault protection,with the reach limited to less than typicaleighty percent of the transformer impedanceat minimum source impedance. EFPIOC canbe configured to measure the residual currentfrom the three-phase current inputs or thecurrent from a separate current input.EFPIOC can be blocked by activating theinput BLOCK.
Four step residual overcurrentprotection EF4PTOC
The four step residual overcurrent protection(EF4PTOC) has a settable inverse or definitetime delay independent for step 1 and 4separately. Step 2 and 3 are always definitetime delayed.
All IEC and ANSI time delayed characteristicsare available.
The directional function is voltage polarized,current polarized or dual polarized.
EF4PTOC can be set directional or non-directional independently for each of the steps.
A second harmonic blocking can be setindividually for each step.
Thermal overload protection, twotime constant TRPTTR
If a power transformer or generator reachesvery high temperatures the equipment mightbe damaged. The insulation within thetransformer/generator will have forcedageing. As a consequence of this the risk ofinternal phase-to-phase or phase-to-earthfaults will increase. High temperature willdegrade the quality of the transformer/generator insulation.
The thermal overload protection estimatesthe internal heat content of the transformer/generator (temperature) continuously. Thisestimation is made by using a thermal modelof the transformer/generator with two timeconstants, which is based on currentmeasurement.
Two warning levels are available. Thisenables actions in the power system to bedone before dangerous temperatures arereached. If the temperature continues toincrease to the trip value, the protectioninitiates a trip of the protected transformer/generator.
Breaker failure protection CCRBRF
Breaker failure protection (CCRBRF) ensuresfast back-up tripping of surrounding breakersin case the own breaker failure to open.
Transformer protection RET650 1MRK 504 127-BEN -Product version: 1.1 Issued: February 2011
18 ABB
CCRBRF can be current based, contact based,or an adaptive combination of these twoprinciples.
A current check with extremely short resettime is used as check criterion to achieve ahigh security against unnecessary operation.
A contact check criteria can be used wherethe fault current through the breaker is small.
Breaker failure protection (CCRBRF) currentcriteria can be fulfilled by one or two phasecurrents, or one phase current plus residualcurrent. When those currents exceed the userdefined settings, the function is activated.These conditions increase the security of theback-up trip command.
CCRBRF function can be programmed to givea three-phase re-trip of the own breaker toavoid unnecessary tripping of surroundingbreakers at an incorrect initiation due tomistakes during testing.
Pole discordance protectionCCRPLD
Circuit breakers and disconnectors can endup with the poles in different positions (close-open), due to electrical or mechanicalfailures. This can cause negative and zerosequence currents which cause thermal stresson rotating machines and can causeunwanted operation of zero sequence ornegative sequence current functions.
Normally the own breaker is tripped tocorrect such a situation. If the situationpersists the surrounding breakers should betripped to clear the unsymmetrical loadsituation.
The pole discordance function operates basedon information from the circuit breaker logicwith additional criteria from unsymmetricalphase currents when required.
Directional over/underpowerprotection GOPPDOP/GUPPDUP
The directional over-/under-power protectionGOPPDOP/GUPPDUP can be used wherevera high/low active, reactive or apparent powerprotection or alarming is required. The
functions can alternatively be used to checkthe direction of active or reactive power flowin the power system. There are a number ofapplications where such functionality isneeded. Some of them are:
• detection of reversed active power flow• detection of high reactive power flow
Each function has two steps with definitetime delay. Reset times for both steps can beset as well.
Negative sequence basedovercurrent function DNSPTOC
Negative sequence based overcurrentfunction (DNSPTOC) is typically used assensitive earth-fault protection of powerlines, where incorrect zero sequencepolarization may result from mutualinduction between two or more parallel lines.
Additionally, it is applied in applications onunderground cables, where zero sequenceimpedance depends on the fault currentreturn paths, but the cable negative sequenceimpedance is practically constant.
The directional function is current andvoltage polarized. The function can be set toforward, reverse or non-directionalindependently for each step.
DNSPTOC protects against all unbalancedfaults including phase-to-phase faults. Theminimum start current of the function mustbe set to above the normal system unbalancelevel in order to avoid unintentionalfunctioning.
6. Voltage protection
Two step undervoltage protectionUV2PTUV
Undervoltages can occur in the power systemduring faults or abnormal conditions. Twostep undervoltage protection (UV2PTUV)function can be used to open circuit breakersto prepare for system restoration at power
Transformer protection RET650 1MRK 504 127-BEN -Product version: 1.1 Issued: February 2011
ABB 19
outages or as long-time delayed back-up toprimary protection.
UV2PTUV has two voltage steps, where step1 is settable as inverse or definite timedelayed. Step 2 is always definite time delayed.
Two step overvoltage protectionOV2PTOV
Overvoltages may occur in the power systemduring abnormal conditions such as suddenpower loss, tap changer regulating failures,open line ends on long lines etc.
OV2PTOV has two voltage steps, where step1 can be set as inverse or definite timedelayed. Step 2 is always definite time delayed.
OV2PTOV has an extremely high reset ratioto allow settings close to system servicevoltage.
Two step residual overvoltageprotection ROV2PTOV
Residual voltages may occur in the powersystem during earth faults.
Two step residual overvoltage protectionROV2PTOV function calculates the residualvoltage from the three-phase voltage inputtransformers or measures it from a singlevoltage input transformer fed from an opendelta or neutral point voltage transformer.
ROV2PTOV has two voltage steps, wherestep 1 can be set as inverse or definite timedelayed. Step 2 is always definite time delayed.
Overexcitation protectionOEXPVPH
When the laminated core of a powertransformer or generator is subjected to amagnetic flux density beyond its designlimits, stray flux will flow into non-laminatedcomponents not designed to carry flux andcause eddy currents to flow. The eddycurrents can cause excessive heating andsevere damage to insulation and adjacentparts in a relatively short time. The functionhas settable inverse operating curves andindependent alarm stages.
7. Frequency protection
Underfrequency protection SAPTUF
Underfrequency occurs as a result of lack ofgeneration in the network.
Underfrequency protection SAPTUF is usedfor load shedding systems, remedial actionschemes, gas turbine startup and so on.
SAPTUF is provided with an undervoltageblocking.
Overfrequency protection SAPTOF
Overfrequency protection function SAPTOF isapplicable in all situations, where reliabledetection of high fundamental power systemfrequency is needed.
Overfrequency occurs at sudden load dropsor shunt faults in the power network. Closeto the generating plant, generator governorproblems can also cause over frequency.
SAPTOF is used mainly for generationshedding and remedial action schemes. It isalso used as a frequency stage initiating loadrestoring.
SAPTOF is provided with an undervoltageblocking.
Rate-of-change frequencyprotection SAPFRC
Rate-of-change frequency protection function(SAPFRC) gives an early indication of a maindisturbance in the system. SAPFRC can beused for generation shedding, load sheddingand remedial action schemes. SAPFRC candiscriminate between positive or negativechange of frequency.
SAPFRC is provided with an undervoltageblocking.
Transformer protection RET650 1MRK 504 127-BEN -Product version: 1.1 Issued: February 2011
20 ABB
8. Secondary systemsupervision
Breaker close/trip circuitmonitoring TCSSCBR
The trip circuit supervision function TCSSCBRis designed to supervise the control circuit ofthe circuit breaker. The invalidity of a controlcircuit is detected by using a dedicatedoutput contact that contains the supervisionfunctionality.
The function operates after a predefinedoperating time and resets when the faultdisappears.
9. Control
Bay control QCBAY
The Bay control QCBAY function is usedtogether with Local remote and local remotecontrol functions is used to handle theselection of the operator place per bay.QCBAY also provides blocking functions thatcan be distributed to different apparatuseswithin the bay.
Local remote LOCREM /Localremote control LOCREMCTRL
The signals from the local HMI or from anexternal local/remote switch are applied viathe function blocks LOCREM andLOCREMCTRL to the Bay control (QCBAY)function block. A parameter in function blockLOCREM is set to choose if the switch signalsare coming from the local HMI or from anexternal hardware switch connected viabinary inputs.
Voltage control TR8ATCC,TCMYLTC
Automatic voltage control for tap changer,TR8ATCC and Tap changer control andsupervision, 6 binary inputs TCMYLTC areused for control of power transformers with a
motor driven load tap changer. The functionsprovide automatic regulation of the voltageon the secondary side of transformers oralternatively on a load point further out inthe network.
Control of a single transformer, as well ascontrol of up to two transformers within asingle RET650, or parallel control of up tofour transformers in two separate RET650 ispossible. Note that the last alternative isachieved by using the GOOSE interbaycommunication on the IEC 61850-8-1protocol. For parallel control of powertransformers, three alternative methods areavailable, the master-follower method, thecirculating current method and the reversereactance method.
In RET650 a local HMI page with voltagecontrol status and manual control possibilitiesis available. Manual control is under authoritycontrol if so defined.
IEC09000670-1-en.vsd
IEC09000670 V1 EN
Figure 5. Manual control via local HMI
Voltage control includes many extra featuressuch as possibility of to avoid simultaneoustapping of parallel transformers, extensivetap changer monitoring including contactwear and hunting detection, monitoring ofthe power flow in the transformer so that forexample, the voltage control can be blockedif the power reverses etc.
In manual operating mode it is possible togive raise- or lower-commands to the loadtap changer from the local HMI. Suchfacilities are pre-made in the factory.
Transformer protection RET650 1MRK 504 127-BEN -Product version: 1.1 Issued: February 2011
ABB 21
Logic rotating switch for functionselection and LHMI presentationSLGGIO
The logic rotating switch for functionselection and LHMI presentation function(SLGGIO) (or the selector switch functionblock) is used to get a selector switchfunctionality similar to the one provided by ahardware selector switch. Hardware selectorswitches are used extensively by utilities, inorder to have different functions operating onpre-set values. Hardware switches arehowever sources for maintenance issues,lower system reliability and an extendedpurchase portfolio. The logic selectorswitches eliminate all these problems.
Selector mini switch VSGGIO
The Selector mini switch VSGGIO functionblock is a multipurpose function used for avariety of applications, as a general purposeswitch.
VSGGIO can be controlled from the menu orfrom a symbol on the single line diagram(SLD) on the local HMI.
IEC 61850 generic communicationI/O functions DPGGIO
The IEC 61850 generic communication I/Ofunctions (DPGGIO) function block is used tosend double indications to other systems orequipment in the substation. It is especiallyused in the interlocking and reservationstation-wide logics.
Single point generic control 8signals SPC8GGIO
The Single point generic control 8 signals(SPC8GGIO) function block is a collection of8 single point commands, designed to bringin commands from REMOTE (SCADA) tothose parts of the logic configuration that donot need extensive command receivingfunctionality (for example, SCSWI). In thisway, simple commands can be sent directlyto the IED outputs, without confirmation.Confirmation (status) of the result of thecommands is supposed to be achieved by
other means, such as binary inputs andSPGGIO function blocks. The commands canbe pulsed or steady.
AutomationBits AUTOBITS
The Automation bits function (AUTOBITS) isused to configure the DNP3 protocolcommand handling.
10. Logic
Tripping logic SMPPTRC
A function block for protection tripping isprovided for each circuit breaker involved inthe tripping of the fault. It provides the pulseprolongation to ensure a trip pulse ofsufficient length, as well as all functionalitynecessary for correct co-operation withautoreclosing functions.
The trip function block includes functionalityfor breaker lock-out.
Trip matrix logic TMAGGIO
Trip matrix logic TMAGGIO function is usedto route trip signals and other logical outputsignals to different output contacts on the IED.
TMAGGIO output signals and the physicaloutputs allows the user to adapt the signalsto the physical tripping outputs according tothe specific application needs.
Configurable logic blocks
A number of logic blocks and timers areavailable for the user to adapt theconfiguration to the specific application needs.
• OR function block.
• INVERTER function blocks that inverts theinput signal.
• PULSETIMER function block can be used,for example, for pulse extensions orlimiting of operation of outputs.
Transformer protection RET650 1MRK 504 127-BEN -Product version: 1.1 Issued: February 2011
22 ABB
• GATE function block is used for whetheror not a signal should be able to pass fromthe input to the output.
• XOR function block.
• LOOPDELAY function block used to delaythe output signal one execution cycle.
• TIMERSET function has pick-up and drop-out delayed outputs related to the inputsignal. The timer has a settable time delay.
• AND function block.
• SRMEMORY function block is a flip-flopthat can set or reset an output from twoinputs respectively. Each block has twooutputs where one is inverted. The memorysetting controls if the block should be resetor return to the state before theinterruption, after a power interruption. Setinput has priority.
• RSMEMORY function block is a flip-flopthat can reset or set an output from twoinputs respectively. Each block has twooutputs where one is inverted. The memorysetting controls if the block should be resetor return to the state before theinterruption, after a power interruption.Reset input has priority.
Boolean 16 to Integer conversionB16I
Boolean 16 to integer conversion function(B16I) is used to transform a set of 16 binary(logical) signals into an integer.
Boolean 16 to Integer conversionwith logic node representationB16IFCVI
Boolean 16 to integer conversion with logicnode representation function (B16IFCVI) isused to transform a set of 16 binary (logical)signals into an integer.
Integer to Boolean 16 conversionIB16A
Integer to boolean 16 conversion function(IB16A) is used to transform an integer into aset of 16 binary (logical) signals.
Integer to Boolean 16 conversionwith logic node representationIB16FCVB
Integer to boolean conversion with logicnode representation function (IB16FCVB) isused to transform an integer to 16 binary(logic) signals.
IB16FCVB function can receive remote valuesover IEC61850 depending on the operatorposition input (PSTO).
11. Monitoring
Measurements CVMMXN, CMMXU,VNMMXU, VMMXU, CMSQI, VMSQI
The measurement functions are used to get on-line information from the IED. These servicevalues make it possible to display on-lineinformation on the local HMI and on theSubstation automation system about:
• measured voltages, currents, frequency,active, reactive and apparent power andpower factor
• primary and secondary phasors• current sequence components• voltage sequence components
Event counter CNTGGIO
Event counter (CNTGGIO) has six counterswhich are used for storing the number oftimes each counter input has been activated.
Disturbance report DRPRDRE
Complete and reliable information aboutdisturbances in the primary and/or in thesecondary system together with continuousevent-logging is accomplished by thedisturbance report functionality.
Transformer protection RET650 1MRK 504 127-BEN -Product version: 1.1 Issued: February 2011
ABB 23
Disturbance report DRPRDRE, alwaysincluded in the IED, acquires sampled data ofall selected analog input and binary signalsconnected to the function block that is,maximum 40 analog and 96 binary signals.
The Disturbance report functionality is acommon name for several functions:
• Event list• Indications• Event recorder• Trip value recorder• Disturbance recorder
The Disturbance report function ischaracterized by great flexibility regardingconfiguration, starting conditions, recordingtimes, and large storage capacity.
A disturbance is defined as an activation ofan input to the AxRADR or BxRBDR functionblocks, which are set to trigger thedisturbance recorder. All signals from start ofpre-fault time to the end of post-fault timewill be included in the recording.
Every disturbance report recording is savedin the IED in the standard Comtrade format.The same applies to all events, which arecontinuously saved in a ring-buffer. The localHMI is used to get information about therecordings. The disturbance report files maybe uploaded to PCM600 for further analysisusing the disturbance handling tool.
Event list DRPRDRE
Continuous event-logging is useful formonitoring the system from an overviewperspective and is a complement to specificdisturbance recorder functions.
The event list logs all binary input signalsconnected to the Disturbance report function.The list may contain up to 1000 time-taggedevents stored in a ring-buffer.
Indications DRPRDRE
To get fast, condensed and reliableinformation about disturbances in theprimary and/or in the secondary system it isimportant to know, for example binarysignals that have changed status during a
disturbance. This information is used in theshort perspective to get information via thelocal HMI in a straightforward way.
There are three LEDs on the local HMI(green, yellow and red), which will displaystatus information about the IED and theDisturbance report function (trigged).
The Indication list function shows all selectedbinary input signals connected to theDisturbance report function that havechanged status during a disturbance.
Event recorder DRPRDRE
Quick, complete and reliable informationabout disturbances in the primary and/or inthe secondary system is vital, for example,time-tagged events logged duringdisturbances. This information is used fordifferent purposes in the short term (forexample corrective actions) and in the longterm (for example functional analysis).
The event recorder logs all selected binaryinput signals connected to the Disturbancereport function. Each recording can containup to 150 time-tagged events.
The event recorder information is availablefor the disturbances locally in the IED.
The event recording information is anintegrated part of the disturbance record(Comtrade file).
Trip value recorder DRPRDRE
Information about the pre-fault and faultvalues for currents and voltages are vital forthe disturbance evaluation.
The Trip value recorder calculates the valuesof all selected analog input signals connectedto the Disturbance report function. The resultis magnitude and phase angle before andduring the fault for each analog input signal.
The trip value recorder information isavailable for the disturbances locally in theIED.
The trip value recorder information is anintegrated part of the disturbance record(Comtrade file).
Transformer protection RET650 1MRK 504 127-BEN -Product version: 1.1 Issued: February 2011
24 ABB
Disturbance recorder DRPRDRE
The Disturbance recorder function suppliesfast, complete and reliable information aboutdisturbances in the power system. Itfacilitates understanding system behavior andrelated primary and secondary equipmentduring and after a disturbance. Recordedinformation is used for different purposes inthe short perspective (for example correctiveactions) and long perspective (for examplefunctional analysis).
The Disturbance recorder acquires sampleddata from selected analog- and binary signalsconnected to the Disturbance report function(maximum 40 analog and 96 binary signals).The binary signals available are the same asfor the event recorder function.
The function is characterized by greatflexibility and is not dependent on theoperation of protection functions. It canrecord disturbances not detected byprotection functions.
The disturbance recorder information for thelast 100 disturbances are saved in the IEDand the local HMI is used to view the list ofrecordings.
Measured value expander blockMVEXP
The current and voltage measurementsfunctions (CVMMXN, CMMXU, VMMXU andVNMMXU), current and voltage sequencemeasurement functions (CMSQI and VMSQI)and IEC 61850 generic communication I/Ofunctions (MVGGIO) are provided withmeasurement supervision functionality. Allmeasured values can be supervised with foursettable limits: low-low limit, low limit, highlimit and high-high limit. The measure valueexpander block has been introduced toenable translating the integer output signalfrom the measuring functions to 5 binarysignals: below low-low limit, below low limit,normal, above high-high limit or above highlimit. The output signals can be used asconditions in the configurable logic or foralarming purpose.
Station battery supervisionSPVNZBAT
The station battery supervision functionSPVNZBAT is used for monitoring batteryterminal voltage.
SPVNZBAT activates the start and alarmoutputs when the battery terminal voltageexceeds the set upper limit or drops belowthe set lower limit. A time delay for theovervoltage and undervoltage alarms can beset according to definite time characteristics.
In the definite time (DT) mode, SPVNZBAToperates after a predefined operate time andresets when the battery undervoltage orovervoltage condition disappears.
Insulation gas monitoring functionSSIMG
Insulation gas monitoring function (SSIMG) isused for monitoring the circuit breakercondition. Binary information based on thegas pressure in the circuit breaker is used asinput signals to the function. In addition, thefunction generates alarms based on receivedinformation.
Insulation liquid monitoringfunction SSIML
Insulation liquid monitoring function (SSIML)is used for monitoring the circuit breakercondition. Binary information based on theoil level in the circuit breaker is used as inputsignals to the function. In addition, thefunction generates alarms based on receivedinformation.
Circuit breaker monitoring SSCBR
The circuit breaker condition monitoringfunction SSCBR is used to monitor differentparameters of the circuit breaker. Thebreaker requires maintenance when thenumber of operations has reached apredefined value. The energy is calculatedfrom the measured input currents as a sum of
Iyt values. Alarms are generated when thecalculated values exceed the thresholdsettings.
Transformer protection RET650 1MRK 504 127-BEN -Product version: 1.1 Issued: February 2011
ABB 25
The function contains a blockingfunctionality. It is possible to block thefunction outputs, if desired.
12. Metering
Pulse counter logic PCGGIO
Pulse counter (PCGGIO) function countsexternally generated binary pulses, forinstance pulses coming from an externalenergy meter, for calculation of energyconsumption values. The pulses are capturedby the BIO (binary input/output) moduleand then read by the PCGGIO function. Ascaled service value is available over thestation bus.
Function for energy calculation anddemand handling ETPMMTR
Outputs from the Measurements (CVMMXN)function can be used to calculate energyconsumption. Active as well as reactivevalues are calculated in import and exportdirection. Values can be read or generated aspulses. Maximum demand power values arealso calculated by the function.
13. Human Machineinterface
Local HMI
GUID-23A12958-F9A5-4BF1-A31B-F69F56A046C7 V2 EN
Figure 6. Local human-machine interface
The LHMI of the IED contains the followingelements:
• Display (LCD)• Buttons• LED indicators• Communication port
The LHMI is used for setting, monitoring andcontrolling .
The Local human machine interface, LHMIincludes a graphical monochrome LCD with aresolution of 320x240 pixels. The charactersize may vary depending on selectedlanguage. The amount of characters and rowsfitting the view depends on the character sizeand the view that is shown.
The LHMI can be detached from the mainunit. The detached LHMI can be wallmounted up to a distance of five meters fromthe main unit. The units are connected withthe Ethernet cable included in the delivery.
The LHMI is simple and easy to understand.The whole front plate is divided into zones,each with a well-defined functionality:
Transformer protection RET650 1MRK 504 127-BEN -Product version: 1.1 Issued: February 2011
26 ABB
• Status indication LEDs• Alarm indication LEDs which can
indicate three states with the colorsgreen, yellow and red, with userprintable label. All LEDs are configurablefrom the PCM600 tool
• Liquid crystal display (LCD)• Keypad with push buttons for control
and navigation purposes, switch forselection between local and remotecontrol and reset
• Five user programmable function buttons• An isolated RJ45 communication port for
PCM600
14. Basic IED functions
Self supervision with internal eventlist
The Self supervision with internal event list(INTERRSIG and SELFSUPEVLST) functionreacts to internal system events generated bythe different built-in self-supervisionelements. The internal events are saved in aninternal event list.
Time synchronization
Use time synchronization to achieve acommon time base for the IEDs in aprotection and control system. This makescomparison of events and disturbance databetween all IEDs in the system possible.
Time-tagging of internal events anddisturbances are an excellent help whenevaluating faults. Without timesynchronization, only the events within theIED can be compared to one another. Withtime synchronization, events anddisturbances within the entire station, andeven between line ends, can be compared atevaluation.
In the IED, the internal time can besynchronized from a number of sources:
• SNTP• IRIG-B• DNP• IEC60870-5-103
Parameter setting groups ACTVGRP
Use the four sets of settings to optimize theIED operation for different system conditions.Creating and switching between fine-tunedsetting sets, either from the local HMI orconfigurable binary inputs, results in a highlyadaptable IED that can cope with a variety ofsystem scenarios.
Test mode functionality TESTMODE
The protection and control IEDs have manyincluded functions. To make the testingprocedure easier, the IEDs include the featurethat allows individual blocking of a single-,several-, or all functions.
There are two ways of entering the test mode:
• By configuration, activating an inputsignal of the function block TESTMODE
• By setting the IED in test mode in thelocal HMI
While the IED is in test mode, all functionsare blocked.
Any function can be unblocked individuallyregarding functionality and event signaling.This enables the user to follow the operationof one or several related functions to checkfunctionality and to check parts of theconfiguration, and so on.
Change lock function CHNGLCK
Change lock function (CHNGLCK) is used toblock further changes to the IEDconfiguration and settings once thecommissioning is complete. The purpose is toblock inadvertent IED configuration changesbeyond a certain point in time.
Authority status ATHSTAT
Authority status (ATHSTAT) function is anindication function block for user log-onactivity.
Transformer protection RET650 1MRK 504 127-BEN -Product version: 1.1 Issued: February 2011
ABB 27
Authority check ATHCHCK
To safeguard the interests of our customers,both the IED and the tools that are accessingthe IED are protected, by means ofauthorization handling. The authorizationhandling of the IED and the PCM600 isimplemented at both access points to the IED:
• local, through the local HMI• remote, through the communication ports
15. Stationcommunication
IEC 61850-8-1 communicationprotocol
The IED supports the communicationprotocols IEC 61850-8-1 and DNP3 over TCP/IP. All operational information and controlsare available through these protocols.However, some communication functionality,for example, horizontal communication(GOOSE) between the IEDs, is only enabledby the IEC 61850-8-1 communication protocol.
The IED is equipped with an optical Ethernetrear port for the substation communicationstandard IEC 61850-8-1. IEC 61850-8-1protocol allows intelligent electrical devices(IEDs) from different vendors to exchangeinformation and simplifies systemengineering. Peer-to-peer communicationaccording to GOOSE is part of the standard.Disturbance files uploading is provided.
Disturbance files are accessed using the IEC61850-8-1 protocol. Disturbance files areavailable to any Ethernet based applicationvia FTP in the standard Comtrade format.Further, the IED can send and receive binaryvalues, double point values and measuredvalues (for example from MMXU functions),together with their quality, using the IEC61850-8-1 GOOSE profile. The IED meets theGOOSE performance requirements for
tripping applications in substations, asdefined by the IEC 61850 standard. The IEDinteroperates with other IEC 61850-compliantIEDs, tools, and systems and simultaneouslyreports events to five different clients on theIEC 61850 station bus.
The event system has a rate limiter to reduceCPU load. The event channel has a quota of10 events/second. If the quota is exceededthe event channel transmission is blockeduntil the event changes is below the quota,no event is lost.
All communication connectors, except for thefront port connector, are placed on integratedcommunication modules. The IED isconnected to Ethernet-based communicationsystems via the fibre-optic multimode LCconnector (100BASE-FX).
The IED supports SNTP and IRIG-B timesynchronization methods with a time-stamping resolution of 1 ms.
• Ethernet based: SNTP and DNP3• With time synchronization wiring: IRIG-B
The IED supports IEC 60870-5-103 timesynchronization methods with a timestamping resolution of 5 ms.
Table 1. Supported communicationinterface and protocol alternatives
Interfaces/Protocols
Ethernet100BASE-
FX LC
STconnector
IEC61850-8-1
●
DNP3 ●
IEC60870-5-103
●
● = Supported
Horizontal communication viaGOOSE for interlocking
GOOSE communication can be used forexchanging information between IEDs via theIEC 61850-8-1 station communication bus.
Transformer protection RET650 1MRK 504 127-BEN -Product version: 1.1 Issued: February 2011
28 ABB
This is typically used for sending apparatusposition indications for interlocking orreservation signals for 1-of-n control. GOOSEcan also be used to exchange any boolean,integer, double point and analog measuredvalues between IEDs.
DNP3 protocol
DNP3 (Distributed Network Protocol) is a setof communications protocols used tocommunicate data between components inprocess automation systems. For a detaileddescription of the DNP3 protocol, see theDNP3 Communication protocol manual.
IEC 60870-5-103 communicationprotocol
IEC 60870-5-103 is an unbalanced (master-slave) protocol for coded-bit serialcommunication exchanging information witha control system, and with a data transfer rateup to 38400 bit/s. In IEC terminology, aprimary station is a master and a secondarystation is a slave. The communication isbased on a point-to-point principle. Themaster must have software that can interpretIEC 60870-5-103 communication messages.
16. Hardware description
Layout and dimensions
Mounting alternatives
The following mounting alternatives areavailable (IP40 protection from the front):
• 19” rack mounting kit• Wall mounting kit• Flush mounting kit• 19" dual rack mounting kit
See ordering for details about availablemounting alternatives.
Flush mounting the IED
H
I
K
J
C
F
G
B
A
ED
IEC09000672.ai
IEC09000672 V1 EN
Figure 7. Flush mounting the IED into a panelcut-out
A 240 mm G 21.55 mm
B 21.55 mm H 220 mm
C 227 mm I 265.9 mm
D 228.9 mm J 300 mm
E 272 mm K 254 mm
F ∅6 mm
A
B
C
IEC09000673.ai
IEC09000673 V1 EN
Figure 8. Flush mounted IED
A 222 mm
B 27 mm
C 13 mm
Transformer protection RET650 1MRK 504 127-BEN -Product version: 1.1 Issued: February 2011
ABB 29
Rack mounting the IED
A C
B
E
D
IEC09000676.ai
IEC09000676 V1 EN
Figure 9. Rack mounted IED
A 224 mm + 12 mm with ring-lug connector
B 25.5 mm
C 482.6 mm (19")
D 265.9 mm (6U)
E 13 mm
A
BC
E
D
IEC09000677.ai
IEC09000677 V1 EN
Figure 10. Two rack mounted IEDs side by side
A 224 mm + 12 mm with ring-lug connector
B 25.5 mm
C 482.6 mm (19")
D 13 mm
E 265.9 mm (6U)
Wall mounting the IED
C
F
G
B
A
ED
IEC09000678.ai
IEC09000678 V1 EN
Figure 11. Wall mounting the IED
A 270 mm E 190.5 mm
B 252.5 mm F 296 mm
C ∅6.8 mm G 13 mm
D 268.9 mm
GUID-5C185EAC-13D0-40BD-8511-58CA53EFF7DE V1 EN
Figure 12. Main unit and detached LHMIdisplay
A 25.5 mm E 258.6 mm
B 220 mm F 265.9 mm
C 13 mm G 224 mm
D 265.9 mm
Transformer protection RET650 1MRK 504 127-BEN -Product version: 1.1 Issued: February 2011
30 ABB
17. Connection diagrams
1MRK006501-FB 2 PG 1.1 IEC V1 EN
Figure 13. Designation for 6U, 1/2x19" casingwith 1 TRM and 1 AIM (A05)
Module Slot Rear Position
COM pCOM X0, X1, X4, X9,X304
PSM pPSM X307, X309, X410
TRM p2 X101, X102
AIM p4 X103, X104
BIO p5 X331, X334
BIO p6 X336, X339
Transformer protection RET650 1MRK 504 127-BEN -Product version: 1.1 Issued: February 2011
ABB 31
1MRK006501-GB 2 PG 1.1 IEC V1 EN
Figure 14. Designation for 6U, 1/2x19" casingwith 1 TRM (A01/A07)
Module Slot Rear Position
COM pCOM X0, X1, X4, X9,X304
PSM pPSM X307, X309, X410
TRM p2 X101, X102
BIO p3 X321, X324
BIO p4 X326, X329
BIO p5 X331, X334
BIO p6 X336, X339
Transformer protection RET650 1MRK 504 127-BEN -Product version: 1.1 Issued: February 2011
32 ABB
Connection diagrams for RET650 A01
1MRK006501-GB 3 PG 1.1 IEC V1 EN
Figure 15. Communication module (COM)
1MRK006501-GB 4 PG 1.1 IEC V1 EN
Figure 16. Power supply module (PSM)48-125V DC
1MRK006501-GB 5 PG 1.1 IEC V1 EN
Figure 17. Power supply module (PSM),110-250V DC
1MRK006501-GB 6 PG 1.1 IEC V1 EN
Figure 18. Transformer module (TRM)
Transformer protection RET650 1MRK 504 127-BEN -Product version: 1.1 Issued: February 2011
ABB 33
1MRK006501-GB 7 PG 1.1 IEC V1 EN
Figure 19. Binary input/output (BIO) option(Terminal X321, X324)
1MRK006501-GB 8 PG 1.1 IEC V1 EN
Figure 20. Binary input/output (BIO) option(Terminal X326, X329)
Connection diagrams for RET650 A05
1MRK006501-FB 3 PG 1.1 IEC V1 EN
Figure 21. Communication module (COM)
1MRK006501-FB 4 PG 1.1 IEC V1 EN
Figure 22. Power supply module (PSM)48-125V DC
Transformer protection RET650 1MRK 504 127-BEN -Product version: 1.1 Issued: February 2011
34 ABB
1MRK006501-FB 5 PG 1.1 IEC V1 EN
Figure 23. Power supply module (PSM),110-250V DC
1MRK006501-FB 6 PG 1.1 IEC V1 EN
Figure 24. Transformer module (TRM)
1MRK006501-FB 7 PG 1.1 IEC V1 EN
Figure 25. Analog input module (AIM)
1MRK006501-FB 8 PG 1.1 IEC V1 EN
Figure 26. Binary input/output (BIO) option(Terminal X331, X334)
Transformer protection RET650 1MRK 504 127-BEN -Product version: 1.1 Issued: February 2011
ABB 35
1MRK006501-FB 9 PG 1.1 IEC V1 EN
Figure 27. Binary input/output (BIO) option(Terminal X336, X339)
Connection diagrams for RET650 A07
1MRK006501-EB 3 PG 1.1 IEC V1 EN
Figure 28. Communication module (COM)
1MRK006501-EB 4 PG 1.1 IEC V1 EN
Figure 29. Power supply module (PSM)48-125V DC
1MRK006501-EB 5 PG 1.1 IEC V1 EN
Figure 30. Power supply module (PSM),110-250V DC
Transformer protection RET650 1MRK 504 127-BEN -Product version: 1.1 Issued: February 2011
36 ABB
1MRK006501-EB 6 PG 1.1 IEC V1 EN
Figure 31. Transformer module (TRM)
1MRK006501-EB 7 PG 1.1 IEC V1 EN
Figure 32. Binary input/output (BIO) option(Terminal X321, X324)
1MRK006501-EB 8 PG 1.1 IEC V1 EN
Figure 33. Binary input/output (BIO) option(Terminal X326, X329)
Transformer protection RET650 1MRK 504 127-BEN -Product version: 1.1 Issued: February 2011
ABB 37
18. Technical data
General
Definitions
Referencevalue
The specified value of an influencing factor to which are referred thecharacteristics of the equipment
Nominalrange
The range of values of an influencing quantity (factor) within which, underspecified conditions, the equipment meets the specified requirements
Operativerange
The range of values of a given energizing quantity for which the equipment,under specified conditions, is able to perform its intended functionsaccording to the specified requirements
Energizing quantities, rated valuesand limits
Transformer protection RET650 1MRK 504 127-BEN -Product version: 1.1 Issued: February 2011
38 ABB
Analog inputs
Table 2. Energizing inputs
Description Value
Rated frequency 50/60 Hz
Operating range Rated frequency ± 5 Hz
Current inputs Rated current, In 0.1/0.5 A1) 1/5 A2)
Thermal withstandcapability:
• Continuously 4 A 20 A
• For 1 s 100 A 500 A
• For 10 s 20 A 100 A
Dynamic currentwithstand:
• Half-wave value 250 A 1250 A
Input impedance <100 mΩ <20 mΩ
Voltage inputs Rated voltage, Un 100 V AC/ 110 V AC/ 115 V AC/ 120 V AC
Voltage withstand:
• Continuous 420 V rms
• For 10 s 450 V rms
Burden at rated voltage <0.05 VA
1) Residual current2) Phase currents or residual current
Transformer protection RET650 1MRK 504 127-BEN -Product version: 1.1 Issued: February 2011
ABB 39
Auxiliary DC voltage
Table 3. Power supply
Description Type 1 Type 2
Uauxnominal 100, 110, 120, 220, 240 VAC, 50 and 60 Hz
48, 60, 110, 125 V DC
110, 125, 220, 250 V DC
Uauxvariation 85...110% of Un (85...264 V
AC)
80...120% of Un (38.4...150 V
DC)
80...120% of Un (88...300 V
DC)
Maximum load of auxiliaryvoltage supply
35 W
Ripple in the DC auxiliaryvoltage
Max 15% of the DC value (at frequency of 100 Hz)
Maximum interruption time inthe auxiliary DC voltagewithout resetting the IED
50 ms at Uaux
Binary inputs and outputs
Table 4. Binary inputs
Description Value
Operating range Maximum input voltage 300 V DC
Rated voltage 24...250 V DC
Current drain 1.6...1.8 mA
Power consumption/input <0.3 W
Threshold voltage 15...221 V DC (parametrizable in the range insteps of 1% of the rated voltage)
Transformer protection RET650 1MRK 504 127-BEN -Product version: 1.1 Issued: February 2011
40 ABB
Table 5. Signal output and IRF output
IRF relay change over - type signal output relay
Description Value
Rated voltage 250 V AC/DC
Continuous contact carry 5 A
Make and carry for 3.0 s 10 A
Make and carry 0.5 s 30 A
Breaking capacity when the control-circuittime constant L/R<40 ms, at U< 48/110/220V DC
≤0.5 A/≤0.1 A/≤0.04 A
Table 6. Power output relays without TCS function
Description Value
Rated voltage 250 V AC/DC
Continuous contact carry 8 A
Make and carry for 3.0 s 15 A
Make and carry for 0.5 s 30 A
Breaking capacity when the control-circuittime constant L/R<40 ms, at U< 48/110/220V DC
≤1 A/≤0.3 A/≤0.1 A
Table 7. Power output relays with TCS function
Description Value
Rated voltage 250 V DC
Continuous contact carry 8 A
Make and carry for 3.0 s 15 A
Make and carry for 0.5 s 30 A
Breaking capacity when the control-circuittime constant L/R<40 ms, at U< 48/110/220V DC
≤1 A/≤0.3 A/≤0.1 A
Control voltage range 20...250 V DC
Current drain through the supervision circuit ~1.0 mA
Minimum voltage over the TCS contact 20 V DC
Transformer protection RET650 1MRK 504 127-BEN -Product version: 1.1 Issued: February 2011
ABB 41
Table 8. Ethernet interfaces
Ethernet interface Protocol Cable Data transfer rate
LAN/HMI port (X0)1) - CAT 6 S/FTP or better 100 MBits/s
LAN1 (X1) TCP/IP protocol Fibre-optic cablewith LC connector
100 MBits/s
1) Only available for the external HMI option.
Table 9. Fibre-optic communication link
Wave length Fibre type Connector Permitted path
attenuation1)
Distance
1300 nm MM 62.5/125μm glassfibre core
LC <8 dB 2 km
1) Maximum allowed attenuation caused by connectors and cable together
Table 10. X4/IRIG-B interface
Type Protocol Cable
Screw terminal, pinrow header
IRIG-B Shielded twisted pair cableRecommended: CAT 5, Belden RS-485 (9841-9844) or Alpha Wire (Alpha 6222-6230)
Table 11. Serial rear interface
Type Counter connector
Serial port (X9) Optical serial port, type ST for IEC60870-5-103
Influencing factors
Table 12. Degree of protection of flush-mounted IED
Description Value
Front side IP 40
Rear side, connection terminals IP 20
Table 13. Degree of protection of the LHMI
Description Value
Front and side IP 42
Transformer protection RET650 1MRK 504 127-BEN -Product version: 1.1 Issued: February 2011
42 ABB
Table 14. Environmental conditions
Description Value
Operating temperature range -25...+55ºC (continuous)
Short-time service temperature range -40...+70ºC (<16h)Note: Degradation in MTBF and HMIperformance outside the temperature rangeof -25...+55ºC
Relative humidity <93%, non-condensing
Atmospheric pressure 86...106 kPa
Altitude up to 2000 m
Transport and storage temperature range -40...+85ºC
Table 15. Environmental tests
Description Type test value Reference
Cold tests operation storage
96 h at -25ºC16 h at -40ºC 96 h at -40ºC
IEC 60068-2-1
Dry heat tests operation storage
16 h at +70ºC 96 h at +85ºC
IEC 60068-2-2
Damp heattests
steady state cyclic
240 h at +40ºChumidity 93% 6 cycles at +25 to +55ºChumidity 93...95%
IEC 60068-2-78 IEC 60068-2-30
Transformer protection RET650 1MRK 504 127-BEN -Product version: 1.1 Issued: February 2011
ABB 43
Type tests according to standards
Table 16. Electromagnetic compatibility tests
Description Type test value Reference
100 kHz and 1 MHz burstdisturbance test
IEC 61000-4-18IEC 60255-22-1, level 3
• Common mode 2.5 kV
• Differential mode 1.0 kV
Electrostatic discharge test IEC 61000-4-2IEC 60255-22-2, level 4
• Contact discharge 8 kV
• Air discharge 15 kV
Radio frequency interferencetests
• Conducted, common mode 10 V (emf), f=150 kHz...80MHz
IEC 61000-4-6IEC 60255-22-6, level 3
• Radiated, amplitude-modulated
20 V/m (rms), f=80...1000MHz and f=1.4...2.7 GHz
IEC 61000-4-3IEC 60255-22-3, level 3
Fast transient disturbancetests
IEC 61000-4-4IEC 60255-22-4, class A
• Communication ports 2 kV
• Other ports 4 kV
Surge immunity test IEC 61000-4-5IEC 60255-22-5, level 3/2
• Communication 1 kV line-to-earth
• Other ports 2 kV line-to-earth, 1 kV line-to-line
Power frequency (50 Hz)magnetic field
IEC 61000-4-8, level 5
• 3 s 1000 A/m
• Continuous 100 A/m
Transformer protection RET650 1MRK 504 127-BEN -Product version: 1.1 Issued: February 2011
44 ABB
Table 16. Electromagnetic compatibility tests, continued
Description Type test value Reference
Power frequency immunitytest
• Common mode
• Differential mode
300 V rms 150 V rms
IEC 60255-22-7, class AIEC 61000-4-16
Voltage dips and shortinterruptions
Dips:40%/200 ms70%/500 msInterruptions:0-50 ms: No restart0...∞ s : Correct behaviour atpower down
IEC 60255-11IEC 61000-4-11
Electromagnetic emissiontests
EN 55011, class AIEC 60255-25
• Conducted, RF-emission(mains terminal)
0.15...0.50 MHz < 79 dB(µV) quasi peak< 66 dB(µV) average
0.5...30 MHz < 73 dB(µV) quasi peak< 60 dB(µV) average
• Radiated RF-emission
30...230 MHz < 40 dB(µV/m) quasi peak,measured at 10 m distance
230...1000 MHz < 47 dB(µV/m) quasi peak,measured at 10 m distance
Transformer protection RET650 1MRK 504 127-BEN -Product version: 1.1 Issued: February 2011
ABB 45
Table 17. Insulation tests
Description Type test value Reference
Dielectric tests: IEC 60255-5
• Test voltage 2 kV, 50 Hz, 1 min1 kV, 50 Hz, 1 min,communication
Impulse voltage test: IEC 60255-5
• Test voltage 5 kV, unipolar impulses,waveform 1.2/50 μs, sourceenergy 0.5 J1 kV, unipolar impulses,waveform 1.2/50 μs, sourceenergy 0.5 J, communication
Insulation resistancemeasurements
IEC 60255-5
• Isolation resistance >100 MΏ, 500 V DC
Protective bonding resistance IEC 60255-27
• Resistance <0.1 Ώ (60 s)
Table 18. Mechanical tests
Description Reference Requirement
Vibration response tests(sinusoidal)
IEC 60255-21-1 Class 2
Vibration endurance test IEC60255-21-1 Class 1
Shock response test IEC 60255-21-2 Class 1
Shock withstand test IEC 60255-21-2 Class 1
Bump test IEC 60255-21-2 Class 1
Seismic test IEC 60255-21-3 Class 2
Product safety
Table 19. Product safety
Description Reference
LV directive 2006/95/EC
Standard EN 60255-27 (2005)
Transformer protection RET650 1MRK 504 127-BEN -Product version: 1.1 Issued: February 2011
46 ABB
EMC compliance
Table 20. EMC compliance
Description Reference
EMC directive 2004/108/EC
Standard EN 50263 (2000)EN 60255-26 (2007)
Transformer protection RET650 1MRK 504 127-BEN -Product version: 1.1 Issued: February 2011
ABB 47
Differential protection
Table 21. Transformer differential protection T2WPDIF, T3WPDIF
Function Range or value Accuracy
Operating characteristic Adaptable ± 1.0% of Ir for I < Ir± 1.0% of Ir for I > Ir
Reset ratio >94% -
Unrestrained differential currentlimit
(1.00-50.00)xIBaseon high voltagewinding
± 1.0% of set value
Base sensitivity function (0.05 - 0.60) xIBase
± 1.0% of Ir
Minimum negative sequencecurrent
(0.02 - 0.20) xIBase
± 1.0% of Ir
Operate angle, negative sequence (30.0 - 90.0)degrees
± 1.0 degrees
Second harmonic blocking (5.0-100.0)% offundamentaldifferential current
± 2.0% of Ir
Fifth harmonic blocking (5.0-100.0)% offundamentaldifferential current
± 12.0% of Ir
Connection type for each of thewindings
Y or D -
Phase displacement between highvoltage winding, W1 and each ofthe windings, W2 and W3. Hournotation
0–11 -
Operate time, restrained function 25 ms typically at0 to 5 x Ib
-
Reset time, restrained function 25 ms typically at5 to 0 x Ib
-
Operate time, unrestrainedfunction
20 ms typically at0 to 5 x Ib
-
Reset time, unrestrained function 25 ms typically at5 to 0 x Ib
-
Transformer protection RET650 1MRK 504 127-BEN -Product version: 1.1 Issued: February 2011
48 ABB
Table 22. Restricted earth fault protection, low impedance REFPDIF
Function Range or value Accuracy
Operate characteristic Adaptable ± 1.0% of Irr for I < Ir
± 1.0% of I for I > Ir
Reset ratio >95% -
Base sensitivity function (4.0-100.0)% of IBase ± 1.0% of Ir
Directional characteristic,for zero sequencedirectional function
(60 - 90) degrees ± 2.0 degree
Operate time, trip function 25 ms typically at 0 to 10x IdMin
-
Reset time, trip function 30 ms typically at 10 to 0x IdMin
-
Table 23. 1Ph High impedance differential protection HZPDIF
Function Range or value Accuracy
Operate voltage (20-400) VI=U/R
± 1.0% of Ir
Reset ratio >95% -
Maximum continuous voltage U>Trip2/series resistor ≤200 W -
Operate time 15 ms typically at 0 to 10 x Ud -
Reset time 90 ms typically at 10 to 0 x Ud -
Critical impulse time 2 ms typically at 0 to 10 x Ud -
Transformer protection RET650 1MRK 504 127-BEN -Product version: 1.1 Issued: February 2011
ABB 49
Current protection
Table 24. Instantaneous phase overcurrent protection PHPIOC
Function Range or value Accuracy
Operate current (5-2500)% of lBase ± 1.0% of Ir at I £ Ir± 1.0% of I at I > Ir
Reset ratio > 95% -
Operate time 20 ms typically at 0 to 2 x Iset -
Reset time 35 ms typically at 2 to 0 x Iset -
Critical impulse time 10 ms typically at 0 to 2 x Iset -
Operate time 10 ms typically at 0 to 10 x Iset -
Reset time 45 ms typically at 10 to 0 x Iset -
Critical impulse time 2 ms typically at 0 to 10 x Iset -
Dynamic overreach < 5% at t = 100 ms -
Transformer protection RET650 1MRK 504 127-BEN -Product version: 1.1 Issued: February 2011
50 ABB
Table 25. Four step phase overcurrent protection OC4PTOC
Function Setting range Accuracy
Operate current (5-2500)% of lBase ± 1.0% of Ir at I ≤ Ir± 1.0% of I at I > Ir
Reset ratio > 95% -
Min. operating current (1-10000)% of lBase ± 1.0% of Ir at I ≤ Ir ±1.0%
of I at I > Ir
Independent time delay (0.000-60.000) s ± 0.5% ±25 ms
Minimum operate timefor inverse characteristics
(0.000-60.000) s ± 0.5% ±25ms
Inverse characteristics,see table 61, table 62 andtable 63
17 curve types See table 61, table 62 andtable 63
Operate time,nondirectional startfunction
20 ms typically at 0 to 2 x Iset -
Reset time, nondirectionalstart function
30 ms typically at 2 to 0 x Iset -
Operate time, directionalstart function
30 ms typically at 0 to 2 x Iset -
Reset time, directionalstart funciton
25 ms typically at 2 to 0 x Iset -
Critical impulse time 10 ms typically at 0 to 2 x Iset -
Impulse margin time 15 ms typically -
Transformer protection RET650 1MRK 504 127-BEN -Product version: 1.1 Issued: February 2011
ABB 51
Table 26. Instantaneous residual overcurrent protection EFPIOC
Function Range or value Accuracy
Operate current (1-2500)% of lBase ± 1.0% of Ir at I £ Ir± 1.0% of I at I > Ir
Reset ratio > 95% -
Operate time 20 ms typically at 0 to 2 x Iset -
Reset time 30 ms typically at 2 to 0 x Iset -
Critical impulse time 10 ms typically at 0 to 2 x Iset -
Operate time 10 ms typically at 0 to 10 x Iset -
Reset time 40 ms typically at 10 to 0 x Iset -
Critical impulse time 2 ms typically at 0 to 10 x Iset -
Dynamic overreach < 5% at t = 100 ms -
Transformer protection RET650 1MRK 504 127-BEN -Product version: 1.1 Issued: February 2011
52 ABB
Table 27. Four step residual overcurrent protection EF4PTOC
Function Range or value Accuracy
Operate current (1-2500)% of lBase ± 1.0% of Ir at I £ Ir± 1.0% of I at I > Ir
Reset ratio > 95% -
Operate current fordirectional comparison
(1–100)% of lBase ± 1.0% of Ir
Min. operating current (1-10000)% of lBase ± 1.0% of Ir at I < Ir ±
1.0% of I at I < Ir
Minimum operate timefor inverse characteristics
(0.000-60.000) s ± 0.5% ± 25 ms
Timers (0.000-60.000) s ± 0.5% ±25 ms
Inverse characteristics,see table 61, table 62 andtable 63
17 curve types See table 61, table 62 andtable 63
Minimum polarizingvoltage
(1–100)% of UBase ± 0.5% of Ur
Minimum polarizingcurrent
(2-100)% of IBase ±1.0% of Ir
Real part of source Zused for currentpolarization
(0.50-1000.00) W/phase -
Imaginary part of sourceZ used for currentpolarization
(0.50–3000.00) W/phase -
Operate time, non-directional start function
30 ms typically at 0.5 to 2 x Iset -
Reset time, non-directional start function
30 ms typically at 2 to 0.5 x Iset -
Operate time, directionalstart function
30 ms typically at 0,5 to 2 x IN -
Reset time, directionalstart function
30 ms typically at 2 to 0,5 x IN -
Transformer protection RET650 1MRK 504 127-BEN -Product version: 1.1 Issued: February 2011
ABB 53
Table 28. Thermal overload protection, two time constants TRPTTR
Function Range or value Accuracy
Base current 1 and 2 (30–250)% of IBase ± 1.0% of Ir
Operate time:
2 2
2 2ln p
b
I It
I It
æ ö-ç ÷= ×ç ÷-è ø
EQUATION1356 V1 EN (Equation 1)
I = Imeasured
Ip = load current before
overload occurs
Time constant τ = (1–500)minutes
IEC 60255–8, class 5 + 200 ms
Alarm level 1 and 2 (50–99)% of heat contenttrip value
± 2.0% of heat content trip
Operate current (50–250)% of IBase ± 1.0% of Ir
Reset level temperature (10–95)% of heat contenttrip
± 2.0% of heat content trip
Table 29. Breaker failure protection CCRBRF
Function Range or value Accuracy
Operate phase current (5-200)% of lBase ± 1.0% of Ir at I £ Ir± 1.0% of I at I > Ir
Reset ratio, phase current > 95% -
Operate residual current (2-200)% of lBase ± 1.0% of Ir at I £ Ir± 1.0% of I at I > Ir
Reset ratio, residual current > 95% -
Phase current level forblocking of contact function
(5-200)% of lBase ± 1.0% of Ir at I £ Ir± 1.0% of I at I > Ir
Reset ratio > 95% -
Timers (0.000-60.000) s ± 0.5% ±10 ms
Operate time for currentdetection
35 ms typically -
Reset time for currentdetection
10 ms maximum -
Transformer protection RET650 1MRK 504 127-BEN -Product version: 1.1 Issued: February 2011
54 ABB
Table 30. Pole discordance protection CCRPLD
Function Range or value Accuracy
Operate value, currentasymmetry level
(0-100) % ± 1.0% of Ir
Reset ratio >95% -
Time delay (0.000-60.000) s ± 0.5% ± 25 ms
Table 31. Directional over/underpower protection GOPPDOP, GUPPDUP
Function Range or value Accuracy
Power level (0.0–500.0)% of SBase ± 1.0% of Sr at S < Sr
± 1.0% of S at S > Sr1)
(1.0-2.0)% of SBase < ± 50% of set value 2)
(2.0-10)% of SBase < ± 20% of set value 3)
Characteristic angle (-180.0–180.0) degrees 2 degrees
Timers (0.010 - 6000.000) s ± 0.5% ± 25 ms
1) Accuracy valid for 50 Hz. At 60 Hz both accuracies are ±2.0%2) Accuracy valid for 50 Hz. At 60 Hz the accuracy is -50/+100%3) Accuracy valid for 50 Hz. At 60 Hz the accuracy is ±40%
Transformer protection RET650 1MRK 504 127-BEN -Product version: 1.1 Issued: February 2011
ABB 55
Table 32. Negative sequence based overcurrent function DNSPTOC
Function Range or value Accuracy
Operate current (2.0 - 5000.0) % of IBase ± 1.0% of Ir at I <Ir± 1.0% of I at I > Ir
Reset ratio > 95 % -
Low voltage level for memory (0.0 - 5.0) % of UBase < ± 0,5% of Ur
Relay characteristic angle (-180 - 180) degrees ± 2,0 degrees
Relay operate angle (1 - 90) degrees ± 2,0 degrees
Timers (0.00 - 6000.00) s ± 0.5% ± 25 ms
Operate time, non-directional 30 ms typically at 0 to 2 x Iset
20 ms typically at 0 to 10 x Iset
-
Reset time, non-directional 40 ms typically at 2 to 0 x Iset -
Operate time, directional 30 ms typically at 0 to 2 x Iset
20 ms typically at 0 to 10 x Iset
-
Reset time, directional 40 ms typically at 2 to 0 x Iset -
Critical impulse time 10 ms typically at 0 to 2 x Iset
2 ms typically at 0 to 10 x Iset
-
Impulse margin time 15 ms typically -
Dynamic overreach < 10% at t = 300 ms -
Transformer protection RET650 1MRK 504 127-BEN -Product version: 1.1 Issued: February 2011
56 ABB
Voltage protection
Table 33. Two step undervoltage protection UV2PTUV
Function Range or value Accuracy
Operate voltage, low andhigh step
(1–100)% of UBase ± 0.5% of Ur
Reset ratio <105% -
Inverse time characteristicsfor low and high step, seetable 65
- See table 65
Definite time delay, step 1 (0.00 - 6000.00) s ± 0.5% ± 25 ms
Definite time delays, step 2 (0.000-60.000) s ± 0.5% ±25 ms
Minimum operate time,inverse characteristics
(0.000–60.000) s ± 0.5% ± 25 ms
Operate time, start function 30 ms typically at 2 to 0.5 x Uset -
Reset time, start function 40 ms typically at 0.5 to 2 x Uset -
Critical impulse time 10 ms typically at 2 to 0 x Uset -
Impulse margin time 15 ms typically -
Table 34. Two step overvoltage protection OV2PTOV
Function Range or value Accuracy
Operate voltage, low andhigh step
(1-200)% of UBase ± 0.5% of Ur at U < Ur
± 0.5% of U at U > Ur
Reset ratio >95% -
Inverse time characteristicsfor low and high step, seetable 64
- See table 64
Definite time delay, step 1 (0.00 - 6000.00) s ± 0.5% ± 25 ms
Definite time delays, step 2 (0.000-60.000) s ± 0.5% ± 25 ms
Minimum operate time,Inverse characteristics
(0.000-60.000) s ± 0.5% ± 25 ms
Operate time, start function 30 ms typically at 0 to 2 x Uset -
Reset time, start function 40 ms typically at 2 to 0 x Uset -
Critical impulse time 10 ms typically at 0 to 2 x Uset -
Impulse margin time 15 ms typically -
Transformer protection RET650 1MRK 504 127-BEN -Product version: 1.1 Issued: February 2011
ABB 57
Table 35. Two step residual overvoltage protection ROV2PTOV
Function Range or value Accuracy
Operate voltage, step 1 (1-200)% of UBase ± 0.5% of Ur at U < Ur
± 0.5% of U at U > Ur
Operate voltage, step 2 (1–100)% of UBase ± 0.5% of Ur at U < Ur
± 0.5% of U at U > Ur
Reset ratio >95% -
Inverse time characteristicsfor low and high step, seetable 66
- See table 66
Definite time setting, step 1 (0.00–6000.00) s ± 0.5% ± 25 ms
Definite time setting, step 2 (0.000–60.000) s ± 0.5% ± 25 ms
Minimum operate time forstep 1 inverse characteristic
(0.000-60.000) s ± 0.5% ± 25 ms
Operate time, start function 30 ms typically at 0 to 2 x Uset -
Reset time, start function 40 ms typically at 2 to 0 x Uset -
Critical impulse time 10 ms typically at 0 to 2 x Uset -
Impulse margin time 15 ms typically -
Table 36. Overexcitation protection OEXPVPH
Function Range or value Accuracy
Operate value, start (100–180)% of (UBase/frated) ± 0.5% of U
Operate value, alarm (50–120)% of start level ± 0.5% of Ur at U ≤ Ur
± 0.5% of U at U > Ur
Operate value, high level (100–200)% of (UBase/frated) ± 0.5% of U
Curve type IEEE
2
(0.18 ):
( 1)k
IEEE tM
×=
-
EQUATION1319 V1 EN (Equation 2)
where M = (E/f)/(Ur/fr)
Class 5 + 40 ms
Minimum time delay forinverse function
(0.000–60.000) s ± 0.5% ± 25 ms
Alarm time delay (0.000–60.000) s ± 0.5% ± 25 ms
Transformer protection RET650 1MRK 504 127-BEN -Product version: 1.1 Issued: February 2011
58 ABB
Frequency protection
Table 37. Under frequency protection SAPTUF
Function Range or value Accuracy
Operate value, start function (35.00-75.00) Hz ± 2.0 mHz
Operate value, restore frequency (45 - 65) Hz ± 2.0 mHz
Operate time, start function At 50 Hz: 200 ms typically at fset
+0.5 Hz to fset -0.5 Hz
At 60 Hz: 170 ms typically at fset
+0.5 Hz to fset -0.5 Hz
-
Reset time, start function At 50 Hz: 60 ms typically at fset -0.5
Hz to fset +0.5 Hz
At 60 Hz: 50 ms typically at fset -0.5
Hz to fset +0.5 Hz
-
Operate time delay (0.000-60.000)s <250 ms
Restore time delay (0.000-60.000)s <150 ms
Table 38. Overfrequency protection SAPTOF
Function Range or value Accuracy
Operate value, start function (35.00-75.00) Hz ± 2.0 mHz atsymmetricalthree-phasevoltage
Operate time, start function At 50 Hz: 200 ms typically at fset
-0.5 Hz to fset +0.5 Hz
At 60 Hz: 170 ms at fset -0.5 Hz to
fset +0.5 Hz
-
Reset time, start function At 50 and 60 Hz: 55 ms typically atfset +0.5 Hz to fset-0.5 Hz
-
Timer (0.000-60.000)s <250 ms
Transformer protection RET650 1MRK 504 127-BEN -Product version: 1.1 Issued: February 2011
ABB 59
Table 39. Rate-of-change frequency protection SAPFRC
Function Range or value Accuracy
Operate value, start function (-10.00-10.00) Hz/s ± 10.0 mHz/s
Operate value, restore enablefrequency
(45.00 - 65.00) Hz ± 2.0 mHz
Timers (0.000 - 60.000) s <130 ms
Operate time, start function At 50 Hz: 100 ms typicallyAt 60 Hz: 80 ms typically
-
Secondary system supervision
Table 40. Breaker close/trip circuit monitoring TCSSCBR
Function Range or value Accuracy
Operate time delay (0.020 - 300.000) s ± 0,5% ± 110 ms
Transformer protection RET650 1MRK 504 127-BEN -Product version: 1.1 Issued: February 2011
60 ABB
Control
Table 41. Voltage control TR8ATCC, TCMYLTC
Function Range or value Accuracy
Transformer reactance on ATCC side (0.1–200.0)Ω, primary -
Time delay for lower commandwhen fast step down mode isactivated
(1.0–100.0) s -
Voltage control set voltage (85.0–120.0)% of UB2 ±0.5% of Ur
Outer voltage deadband (0.2–9.0)% of UB2 ± 5,0% of set value
Inner voltage deadband (0.1–9.0)% of UB2 ± 5,0% of set value
Upper limit of busbar voltage (80–180)% of UB2 ± 0.5% of Ur
Lower limit of busbar voltage (70–120)% of UB2 ± 0.5% of Ur
Undervoltage block level (0–120)% of UB2 ± 0.5% of Ur
Time delay (long) for automaticcontrol commands
(3–1000) s ± 0.5% ± 110 ms
Time delay (short) for automaticcontrol commands
(1–1000) s ± 0.5% ± 110 ms
Minimum operating time in inversemode
(3–120) s ± 0.5% ± 110 ms
Line resistance (0.00–150.00)Ω, primary -
Line reactance (-150.00–150.00)Ω, primary -
Load voltage adjustment constants (-20.0–20.0)% of UB2 ± 5,0% of set value
Load voltage auto correction (-20.0–20.0)% of UB2 ± 5,0% of set value
Overcurrent block level (0–250)% of IBase ± 1.0% of Ir at I≤Ir± 1.0% of I at I>Ir
Level for number of counted raise/lower within one hour
(0–30) operations/hour -
Level for number of counted raise/lower within 24 hours
(0–100) operations/day -
Time window for hunting alarm (1–120) minutes -
Hunting detection alarm, maxoperations/window
(3–30) operations/window -
Alarm level of active power inforward and reverse direction
(-9999.99–9999.99) MW ± 1.0% of Sr
Transformer protection RET650 1MRK 504 127-BEN -Product version: 1.1 Issued: February 2011
ABB 61
Table 41. Voltage control TR8ATCC, TCMYLTC, continued
Function Range or value Accuracy
Alarm level of reactive power inforward and reverse direction
(-9999.99–9999.99) MVAr ± 1.0% of Sr
Time delay for alarms from powersupervision
(1–6000) s ± 0.5% ± 110 ms
Tap position for lowest and highestvoltage
(1–63) -
Type of code conversion Binary, BCD, Gray,ContactPerTap
-
Time after position change beforethe value is accepted
(1–60) s ± 0.5% ± 25 ms
Tap changer constant time-out (1–120) s ± 0.5% ± 25 ms
Raise/lower command output pulseduration
(0.5–10.0) s ± 0.5% ± 25 ms
Logic
Table 42. Tripping logic SMPPTRC
Function Range or value Accuracy
Trip action 3-ph -
Timers (0.000-60.000) s ± 0.5% ± 10 ms
Transformer protection RET650 1MRK 504 127-BEN -Product version: 1.1 Issued: February 2011
62 ABB
Table 43. Configurable logic blocks
Logic block Quantity with cycle time Range or value Accuracy
5 ms 20 ms 100 ms
AND 60 60 160 - -
OR 60 60 160 - -
XOR 10 10 20 - -
INVERTER 30 30 80 - -
SRMEMORY 10 10 20 - -
RSMEMORY 10 10 20 - -
GATE 10 10 20 - -
PULSETIMER 10 10 20 (0.000–90000.000) s ± 0.5% ± 25 ms
TIMERSET 10 10 20 (0.000–90000.000) s ± 0.5% ± 25 ms
LOOPDELAY 10 10 20
Monitoring
Table 44. Measurements CVMMXN
Function Range or value Accuracy
Voltage (0.1-1.5) ×Ur ± 0.5% of Ur at U£Ur
± 0.5% of U at U > Ur
Connected current (0.2-4.0) × Ir ± 0.5% of Ir at I £ Ir± 0.5% of I at I > Ir
Active power, P 0.1 x Ur< U < 1.5 x Ur
0.2 x Ir < I < 4.0 x Ir
± 1.0% of Sr at S ≤ Sr
± 1.0% of S at S > Sr
1)
Reactive power, Q 0.1 x Ur< U < 1.5 x Ur
0.2 x Ir < I < 4.0 x Ir
± 1.0% of Sr at S ≤ Sr
± 1.0% of S at S > Sr
1)
Apparent power, S 0.1 x Ur < U < 1.5 x Ur
0.2 x Ir< I < 4.0 x Ir
± 1.0% of Sr at S ≤ Sr
± 1.0% of S at S > Sr
Apparent power, S Threephase settings
cos phi = 1 ± 0.5% of S at S > Sr
± 0.5% of Sr at S ≤ Sr
Power factor, cos (φ) 0.1 x Ur < U < 1.5 x Ur
0.2 x Ir< I < 4.0 x Ir
< 0.02 2)
1) Accuracy valid for 50 Hz. At 60 Hz both accuracies are ±2.0%2) Accuracy valid for 50 Hz. At 60 Hz the accuracy is <0.04.
Transformer protection RET650 1MRK 504 127-BEN -Product version: 1.1 Issued: February 2011
ABB 63
Table 45. Event counter CNTGGIO
Function Range or value Accuracy
Counter value 0-10000 -
Max. count up speed 10 pulses/s -
Transformer protection RET650 1MRK 504 127-BEN -Product version: 1.1 Issued: February 2011
64 ABB
Table 46. Disturbance report DRPRDRE
Function Range or value Accuracy
Current recording - ± 1,0% of Ir at I ≤ Ir± 1,0% of I at I > Ir
Voltage recording - ± 1,0% of Ur at U ≤
Ur
± 1,0% of U at U >Ur
Pre-fault time (0.05–3.00) s -
Post-fault time (0.1–10.0) s -
Limit time (0.5–8.0) s -
Maximum number of recordings 100, first in - first out -
Time tagging resolution 1 ms See timesynchronizationtechnical data
Maximum number of analog inputs 30 + 10 (external +internally derived)
-
Maximum number of binary inputs 96 -
Maximum number of phasors in the TripValue recorder per recording
30 -
Maximum number of indications in adisturbance report
96 -
Maximum number of events in the Eventrecording per recording
150 -
Maximum number of events in the Eventlist
1000, first in - first out -
Maximum total recording time (3.4 srecording time and maximum number ofchannels, typical value)
340 seconds (100recordings) at 50 Hz, 280seconds (80 recordings)at 60 Hz
-
Sampling rate 1 kHz at 50 Hz1.2 kHz at 60 Hz
-
Recording bandwidth (5-300) Hz -
Transformer protection RET650 1MRK 504 127-BEN -Product version: 1.1 Issued: February 2011
ABB 65
Table 47. Event list DRPRDRE
Function Value
Buffer capacity Maximum number of events inthe list
1000
Resolution 1 ms
Accuracy Depending on timesynchronizing
Table 48. Indications DRPRDRE
Function Value
Buffer capacity Maximum number of indications presentedfor single disturbance
96
Maximum number of recorded disturbances 100
Table 49. Event recorder DRPRDRE
Function Value
Buffer capacity Maximum number of events in disturbance report 150
Maximum number of disturbance reports 100
Resolution 1 ms
Accuracy Depending ontimesynchronizing
Table 50. Trip value recorder DRPRDRE
Function Value
Buffer capacity
Maximum number of analog inputs 30
Maximum number of disturbance reports 100
Transformer protection RET650 1MRK 504 127-BEN -Product version: 1.1 Issued: February 2011
66 ABB
Table 51. Disturbance recorder DRPRDRE
Function Value
Buffer capacity Maximum number of analog inputs 40
Maximum number of binary inputs 96
Maximum number of disturbance reports 100
Maximum total recording time (3.4 s recording time andmaximum number of channels, typical value)
340 seconds (100 recordings)at 50 Hz280 seconds (80 recordings) at60 Hz
Table 52. Station battery supervision SPVNZBAT
Function Range or value Accuracy
Lower limit for the batteryterminal voltage
(60-140) % of Ubat ± 1.0% of set battery voltage
Reset ratio, lower limit <105 % -
Upper limit for the batteryterminal voltage
(60-140) % of Ubat ± 1.0% of set battery voltage
Reset ratio, upper limit >95 % -
Timers (0.000-60.000) s ± 0.5% ± 110 ms
Table 53. Insulation gas monitoring function SSIMG
Function Range or value Accuracy
Pressure alarm 0.00-25.00 -
Pressure lockout 0.00-25.00 -
Temperature alarm -40.00-200.00 -
Temperature lockout -40.00-200.00 -
Timers (0.000-60.000) s ± 0.5% ± 110 ms
Table 54. Insulation liquid monitoring function SSIML
Function Range or value Accuracy
Alarm, oil level 0.00-25.00 -
Oil level lockout 0.00-25.00 -
Temperature alarm -40.00-200.00 -
Temperature lockout -40.00-200.00 -
Timers (0.000-60.000) s ± 0.5% ± 110 ms
Transformer protection RET650 1MRK 504 127-BEN -Product version: 1.1 Issued: February 2011
ABB 67
Table 55. Circuit breaker condition monitoring SSCBR
Function Range or value Accuracy
Alarm levels for open andclose travel time
(0-200) ms ± 0.5% ± 25 ms
Alarm levels for number ofoperations
(0 - 9999) -
Setting of alarm for springcharging time
(0.00-60.00) s ± 0.5% ± 25 ms
Time delay for gas pressurealarm
(0.00-60.00) s ± 0.5% ± 25 ms
Time delay for gas pressurelockout
(0.00-60.00) s ± 0.5% ± 25 ms
Metering
Table 56. Pulse counter PCGGIO
Function Setting range Accuracy
Cycle time for report ofcounter value
(1–3600) s -
Table 57. Function for energy calculation and demand handling ETPMMTR
Function Range or value Accuracy
Energy metering MWh Export/Import,MVArh Export/Import
Input from MMXU. No extra errorat steady load
Hardware
IED
Table 58. Degree of protection of flush-mounted IED
Description Value
Front side IP 40
Rear side, connection terminals IP 20
Table 59. Degree of protection of the LHMI
Description Value
Front and side IP 42
Transformer protection RET650 1MRK 504 127-BEN -Product version: 1.1 Issued: February 2011
68 ABB
Dimensions
Table 60. Dimensions
Description Value
Width 220 mm
Height 265.9 mm (6U)
Depth 249.5 mm
Weight box <10 kg (6U)
Weight LHMI 1.3 kg (6U)
Inverse time characteristics
Table 61. ANSI Inverse time characteristics
Function Range or value Accuracy
Operating characteristic:
( )1= + ×
-
æ öç ÷ç ÷è ø
P
At B k
I
EQUATION1249-SMALL V1 EN
I = Imeasured/Iset
k = (0.05-999) in steps of 0.01unless otherwise stated
-
ANSI Extremely Inverse A=28.2, B=0.1217, P=2.0 ANSI/IEEE C37.112,class 5 + 40 ms
ANSI Very inverse A=19.61, B=0.491, P=2.0
ANSI Normal Inverse A=0.0086, B=0.0185, P=0.02, tr=0.46
ANSI Moderately Inverse A=0.0515, B=0.1140, P=0.02
ANSI Long Time ExtremelyInverse
A=64.07, B=0.250, P=2.0
ANSI Long Time Very Inverse A=28.55, B=0.712, P=2.0
ANSI Long Time Inverse k=(0.05-999) in steps of 0.01A=0.086, B=0.185, P=0.02
Transformer protection RET650 1MRK 504 127-BEN -Product version: 1.1 Issued: February 2011
ABB 69
Table 62. IEC Inverse time characteristics
Function Range or value Accuracy
Operating characteristic:
( )1= ×
-
æ öç ÷ç ÷è ø
P
At k
I
EQUATION1251-SMALL V1 EN
I = Imeasured/Iset
k = (0.05-999) in steps of 0.01 -
IEC Normal Inverse A=0.14, P=0.02 IEC 60255-151,class 5 + 40 ms
IEC Very inverse A=13.5, P=1.0
IEC Inverse A=0.14, P=0.02
IEC Extremely inverse A=80.0, P=2.0
IEC Short time inverse A=0.05, P=0.04
IEC Long time inverse A=120, P=1.0
Table 63. RI and RD type inverse time characteristics
Function Range or value Accuracy
RI type inverse characteristic
1
0.2360.339
= ×
-
t k
I
EQUATION1137-SMALL V1 EN
I = Imeasured/Iset
k = (0.05-999) in steps of 0.01 IEC 60255-151,class 5 + 40 ms
RD type logarithmic inversecharacteristic
5.8 1.35= - ×æ öç ÷è ø
tI
Ink
EQUATION1138-SMALL V1 EN
I = Imeasured/Iset
k = (0.05-999) in steps of 0.01 IEC 60255-151,class 5 + 40 ms
Transformer protection RET650 1MRK 504 127-BEN -Product version: 1.1 Issued: February 2011
70 ABB
Table 64. Inverse time characteristics for overvoltage protection
Function Range or value Accuracy
Type A curve:
=- >
>
æ öç ÷è ø
tk
U U
U
EQUATION1436-SMALL V1 EN
U> = Uset
U = Umeasured
k = (0.05-1.10) in steps of0.01 unless otherwise stated
Class 5 +40 ms
Type B curve:
2.0
480
32 0.5 0.035
=×
- >× - -
>
æ öç ÷è ø
tk
U U
U
EQUATION1437-SMALL V1 EN
k = (0.05-1.10) in steps of0.01 unless otherwise stated
Type C curve:
3.0
480
32 0.5 0.035
=×
- >× - -
>
æ öç ÷è ø
tk
U U
U
EQUATION1438-SMALL V1 EN
k = (0.05-1.10) in steps of0.01 unless otherwise stated
Transformer protection RET650 1MRK 504 127-BEN -Product version: 1.1 Issued: February 2011
ABB 71
Table 65. Inverse time characteristics for undervoltage protection
Function Range or value Accuracy
Type A curve:
=< -
<
æ öç ÷è ø
kt
U U
U
EQUATION1431-SMALL V1 EN
U< = Uset
U = UVmeasured
k = (0.05-1.10) in steps of0.01 unless otherwise stated
Class 5 +40 ms
Type B curve:
2.0
4800.055
32 0.5
×= +
< -× -
<
æ öç ÷è ø
kt
U U
U
EQUATION1432-SMALL V1 EN
U< = Uset
U = Umeasured
k = (0.05-1.10) in steps of0.01 unless otherwise stated
Transformer protection RET650 1MRK 504 127-BEN -Product version: 1.1 Issued: February 2011
72 ABB
Table 66. Inverse time characteristics for residual overvoltage protection
Function Range or value Accuracy
Type A curve:
=- >
>
æ öç ÷è ø
tk
U U
U
EQUATION1436-SMALL V1 EN
U> = Uset
U = Umeasured
k = (0.05-1.10) insteps of 0.01
Class 5 +40 ms
Type B curve:
2.0
480
32 0.5 0.035
=×
- >× - -
>
æ öç ÷è ø
tk
U U
U
EQUATION1437-SMALL V1 EN
k = (0.05-1.10) insteps of 0.01
Type C curve:
3.0
480
32 0.5 0.035
=×
- >× - -
>
æ öç ÷è ø
tk
U U
U
EQUATION1438-SMALL V1 EN
k = (0.05-1.10) insteps of 0.01
Transformer protection RET650 1MRK 504 127-BEN -Product version: 1.1 Issued: February 2011
ABB 73
19. Ordering
GuidelinesCarefully read and follow the set of rules to ensure problem-free order management.Please refer to the available functions table for included application functions.
To obtain the complete ordering code, please combine code from the tables, as given in the example below.
Exemple code: RET650*1.1-A01X00-X00-B1A5-B-A-SA-AB1-RA2B1-AAXX-E. Using the code of each position #1-11specified as RET650*1-2 2-3-4 4-5-6-7 7-8 8-9 9 9-10 10 10 10-11
# 1 - 2 - 3 - 4 - 5 6 - 7 - 8 - 9 - 10 - 11
RET650* - - - - - - - - -
Posi
tion
SOFTWARE #1 Notes and Rules
Version number
Version no 1.1
Selection for position #1. 1.1
Configuration alternatives #2 Notes and Rules
Configuration alternatives #2 Notes and Rules
Single breaker, 2 winding, IEC A01
Single breaker, 3 winding, IEC A05
Tap changer control, IEC A07
ACT configuration
ABB standard configuration X00
Selection for position #2. X00
Software options #3 Notes and Rules
No option X00
Selection for postition #3 X00
First HMI language #4 Notes and Rules
English IEC B1
Selection for position #4.
Additional HMI language #4
No second HMI language X0
Chinese A5
Selection for position #4. B1
Transformer protection RET650 1MRK 504 127-BEN -Product version: 1.1 Issued: February 2011
74 ABB
Casing #5 Notes and Rules
Rack casing, 6 U 1/2 x 19" B
Selection for position #5. B
Mounting details with IP40 of protection from the front #6 Notes and Rules
No mounting kit included X
Rack mounting kit for 6 U 1/2 x 19" A
Wall mounting kit for 6U 1/2 x 19" D
Flush mounting kit for 6U 1/2 x 19" E
Wall mounting bracket 6U 1/2 x 19" G
Selection for position #6.
Connection type for Power supply, Input/outputand Communication modules
#7 Notes and Rules
Compression terminals S
Ringlug terminals R
Power supply
Slot position:
pPSM
100-240V AC, 110-250V DC, 9BO A
48-125V DC, 9BO B
Selection for position #7.
Human machine interface #8 Notes and Rules
Local human machine interface, OL3000, IEC6U 1/2 x 19", Basic
A
Detached LHMI
No detached mounting of LHMI X0
Detached mounting of LHMI incl. Ethernet cable, 1m B1
Detached mounting of LHMI incl. Ethernet cable, 2m B2
Detached mounting of LHMI incl. Ethernet cable, 3m B3
Detached mounting of LHMI incl. Ethernet cable, 4m B4
Detached mounting of LHMI incl. Ethernet cable, 5m B5
Selection for position #8. A
Transformer protection RET650 1MRK 504 127-BEN -Product version: 1.1 Issued: February 2011
ABB 75
Connection type for Analog modules #9 Notes and Rules
Compression terminals S
Ringlug terminals R
Analog system
Slot position: p2
Transformer module, 6I + 4U, 1/5A, 100/220V A1 Only in A05 and A07
Transformer module, 8I + 2U, 1/5A, 100/220V A2 Only in A01
Slot position: p4
Analog input module, 6I + 4U, 1/5A, 100/220V B1 Only in A05
Selection for position #9.
Binary input/output module #10 Notes and Rules
Slot position (rear view) p3
p4
p5
p6
Available slots in 1/2 case Only if no AIM selected
No board in slot X X X AIM in P4 for A05
Binary input/output module 9 BI, 3 NOTrip, 5 NO Signal, 1 CO Signal
A A A A P5 and P6 option only valid for A01 and A07
Selection for position #10. A A
Communication and processing module #11 Notes and Rules
Slot position (rear view)
pCO
M
14BI, IRIG-B, Ethernet, LC, ST B
Selection for position #11. B
Accessories
Rack mounting kit for 2 x 6U 1/2 x 19" Quantity: 1KHL400240R0001
External resistor unit
High impedance resistor unit 1-ph with resistor and voltagedependent resistor for 20-100V operating voltage
Quantity:
1 2 RK795101-MA
High impedance resistor unit 1-ph with resistor and voltagedependent resistor for 100-400V operating voltage
Quantity:
1 2 RK795101-CB
Configuration and monitoring tools
Front connection cable between LCD-HMI and PC Quantity: 1MRK 001 665-CA
Transformer protection RET650 1MRK 504 127-BEN -Product version: 1.1 Issued: February 2011
76 ABB
LED Label special paper A4, 1 pc Quantity: 1MRK 002 038-CA
LED Label special paper Letter, 1 pc Quantity: 1MRK 002 038-DA
Manuals
Note: One (1) IED Connect CD containing user documentation (Operation manual, Technical manual,Installation manual, Commissioning manual, Application manual, Communication protocol manual,DNP, Communication protocol manual, IEC61850, Communication protocol manual, IEC60870-5-103,Type test certificate, Engineering manual and Point list manual, DNP3, Connectivity packages and LEDlabel template is always included for each IED.
Rule: Specify additional quantity of IED Connect CD requested
User documentation Quantity: 1MRK 003 500-AA
Rule: Specify the number of printed manuals requested
Operation manual IEC Quantity: 1MRK 500 093-UEN
Technical manual IEC Quantity: 1MRK 504 125-UEN
Commissioning manual IEC Quantity: 1MRK 504 126-UEN
Application manual IEC Quantity: 1MRK 504 124-UEN
Communication protocol manual, DNP3 IEC Quantity: 1MRK 511 241-UEN
Communication protocol manual, IEC 61850 IEC Quantity: 1MRK 511 242-UEN
Communication protocol manual, IEC 60870-5-103 IEC Quantity: 1MRK 511 243-UEN
Engineering manual IEC Quantity: 1MRK 511 245-UEN
Installation manual IEC Quantity: 1MRK 514 014-UEN
Point list manual, DNP3 IEC Quantity: 1MRK 511 244-UEN
Transformer protection RET650 1MRK 504 127-BEN -Product version: 1.1 Issued: February 2011
ABB 77
Reference information
For our reference and statistics we would be pleased to be provided with the following application data:
Country: End user:
Station name: Voltage level: kV
Related documents
Documents related to RET650 Identity number
Application manual 1MRK 504 124-UEN
Technical manual 1MRK 504 125-UEN
Commissioning manual 1MRK 504 126-UEN
Product Guide, configured 1MRK 504 127-BEN
Type test certificate 1MRK 504 127-TEN
650 series manuals Identity number
Communication protocol manual, DNP3 1MRK 511 241-UEN
Communication protocol manual, IEC 61850 1MRK 511 242-UEN
Communication protocol manual, IEC 60870-5-103 1MRK 511 243-UEN
Point list manual, DNP3 1MRK 511 244-UEN
Engineering manual 1MRK 511 245-UEN
Operation manual 1MRK 500 093-UEN
Installation manual 1MRK 514 014-UEN
Transformer protection RET650 1MRK 504 127-BEN -Product version: 1.1 Issued: February 2011
78 ABB
79