Pumping Systems and Day Tanks . Presented By Ken Still, CB Kramer. Agenda. Introduction Basic System Generator Pump Selection Boiler Pump Selection Pump Types and Limits Day Tanks Day Tank Accessories Pump and Day Tank Control Conclusion. Introduction. Ken Still – CB Kramer - PowerPoint PPT Presentation

TRANSCRIPT

1

Pumping Systems and

Day Tanks

PresentedBy

Ken Still, CB Kramer

2

Agenda• Introduction• Basic System• Generator Pump Selection• Boiler Pump Selection• Pump Types and Limits• Day Tanks • Day Tank Accessories• Pump and Day Tank Control• Conclusion

3

Introduction• Ken Still – CB Kramer• Pump sets and day tanks typically operate as a

single system with a common controller.

4

Basic SystemMonitoring and Control

5

Generator Pump Selection

• 7 gph per 100KW = GPH• GPH x # gensets = GPH Total • GPH total x 4 = transfer

pump size

6

7

Boiler Pump Selection

• 30gph per 100 BHP = GPH• GPH x # boilers = GPH total• GPH total x 2.5 – 3 to

accommodate boiler mounted pump total flow

Typical boiler system selection

8

9

Typical System w Boiler Pumps

• Boiler Mounted pump limitations• Tight pump suction limits; 15”hg – 3psi• Boiler pump single point of failure• Boiler pumps requires 2.5-3 times flow rate

(sometimes 10-15x more) from transfer pump

10

Typical System w Boiler Pumps

11

Alternative Boiler System

80 - 90

12

Pump Types

• Match the pump to the application• Suction or pressure type

SUCTION PUMP SET PRESSURE (submersible) PUMPS

Pump Sets

• Submersible Pumps

13

• Pro• Submerged suction• Simple single tank

systems• Simple installation

• Con• Pressurized in-ground piping• Limited sizes• Difficult maintenance• Unmanned spaces• Piping Monitoring• Complicated multi-tank

redundant systems

14

Pressure Pump System

• Redundancy• Each tank must have

redundant pumps

Pump Sets

• Suction Pumps

15

• Pro• Buried piping under

suction• Ease of maintenance• Simpler multi tank

systems• Simple installation

• Con• Limited suction ability• Additional floor space

16

Suction Pump System

• Redundancy• A single duplex pump

set satisfies redundancy requirement

Suction Pump Set Options• High Pressure 100psi • Low Pressure <50 psi

17

mechanical pump set

pump set with motor starter panel

Pump set with motor starter and logic control panels

18

Suction Pump Set Contruction

Pump/motor sets

Control panel(s)

Gauges

Priming funnel

Relief valvesFlow switch

Suction strainer(s)

Reservoir base w/leak switch

19

Basic SystemMonitoring and Control

Day Tanks

20

Day Tanks

• Built and certified to UL142• Pressure tested to 5 psi• Almost always used on generators• Stand Alone• Belly Tank

• Sometimes used on boilers

21

Day Tanks

• Stand Alone• Generator Belly Tank

22

Belly Tanks• Completely isolate tank

from generator

Flexible fuel hose

Spring isolation

23

Independent Day Tanks

• Double Wall• Return Pump Option

24

Independent Day Tanks• Single Wall• Single Wall w/Tub Type Rupture Basin• Available w/o rupture basin

25

Day Tank Accessories• Automatic fill manifold• Multi-tank applications• Sized to precisely match required flow

26

Day Tank Accessories

• Return Pumps• Manipulate tank level

to test controls• Refresh fuel if it

overheats• Empty day tank in

emergency

27

Day Tank Accessories

• Accessories• Vent Caps• Level Indication• Level Monitoring• Others

28

Day Tank Sizing

• No rules or regulations requiring minimum sizes.

• Some regulations limiting maximum sizes• IFC limit to 660 gallons in certain installations

• Generator KW x .07 x hours desired = tank size• Often space dependent

29

Day Tank Construction• Fittings in top of tank (except drain)• Easy access to all fittings• Drop tubes on all supply and returns• Keep the inflow away from generator suction

30

• Primary functions• Monitor day tank level• Start/stop pumps• Open/close fill manifolds

• Secondary functions• Leak detection• Communications and alarms• Auxiliary controls

Pump and Day Tank Controls

31

Pump and Day Tank Controls

• Safe Design• High voltage separate

from low voltage• Easy serviceability and

compliance to NFPA and OSHAE standards

High voltage motor control panel

Low voltage logic control not to exceed 49 volts

32

Pump and Day Tank Controls

• NFPA 70e

33

Conclusion• Basic System• Generator Pump Selection• Boiler Pump Selection• Pump Types and Limits• Day Tanks • Day Tank Accessories• Pump and Day Tank Control