Cable Code: A2XY/2XY REF SPEC : IS : 7098 (PT-1) : 1988 PHYSICAL PARAMETERS
Al Cu (mm) (mm) 4 ----- 1/7 1.8 8 6 1 1/7 1.8 9 10 1 6 1.8 10 16 6 6 1.8 11 25 6 6 1.8 12 35 6 6 1.8 13 50 6 6 1.8 15 70 12 12 1.8 16 95 15 15 1.8 18 120 15 18 1.8 20 150 15 18 2.0 22 185 30 30 2.0 24 240 30 34 2.0 27 300 30 34 2.0 30 400 53 53 2.2 33 500 53 53 2.2 36 630 53 53 2.2 40 800 53 53 2.4 47 1000 53 53 2.6 51
ELECTRICAL PARAMETERS
Al Cu Al Cu. Al Cu. 4 ----- 4.61 ---- 5.90 0.136 0.29 --- --- --- 48 47 45 0.376 0.572 6 4.61 3.08 5.900 3.94 0.128 0.34 48 45 45 60 59 57 0.564 0.858 10 3.08 1.83 3.940 2.34 0.118 0.42 62 62 61 80 78 77 0.940 1.430 16 1.91 1.15 2.440 1.47 0.108 0.50 81 80 83 104 102 106 1.504 2.288 25 1.20 0.727 1.540 0.931 0.102 0.52 99 90 115 130 115 145 2.350 3.575 35 0.868 0.524 1.110 0.671 0.097 0.60 117 110 135 155 140 175 3.290 5.005 50 0.641 0.387 0.820 0.495 0.092 0.63 138 125 170 185 165 215 4.700 7.150 70 0.443 0.268 0.567 0.343 0.088 0.68 168 155 210 225 200 270 6.580 10.010 95 0.320 0.193 0.411 0.248 0.085 0.79 204 185 255 265 235 330 8.930 13.590 120 0.253 0.153 0.325 0.197 0.082 0.79 230 210 300 300 265 380 11.280 17.160 150 0.206 0.1240 0.265 0.1590 0.082 0.79 265 230 342 335 300 430 14.100 21.450 185 0.164 0.0991 0.211 0.1270 0.082 0.79 295 260 385 380 335 495 17.390 26.460 240 0.125 0.0754 0.162 0.0976 0.079 0.84 340 300 450 435 385 590 22.560 34.320 300 0.100 0.0601 0.130 0.0778 0.078 0.86 390 335 519 490 430 670 28.200 42.900 400 0.0778 0.0470 0.1023 0.0618 0.077 0.88 450 380 605 550 480 780 37.600 57.200 500 0.0605 0.0366 0.0808 0.0489 0.076 0.90 500 480 700 610 530 900 47.000 71.500 630 0.0469 0.0283 0.0648 0.0391 0.075 0.94 555 485 809 680 590 1020 59.220 90.090 800 0.0367 0.0221 0.0503 0.0319 0.075 0.97 625 530 935 740 630 1140 75.200 114.400 1000 0.0291 0.0176 0.0444 0.0268 0.068 1.01 690 570 1065 780 660 1250 94.000 143.000
SIZE cross- sectional
area(Sq MM)
Max. Cond.D.C. Resistance at
20°C in Ohm/km
Approx. Cond. AC Resistaance at 90°C
in Ohm/Km
App. Reactance at
50HZ in ohms/km
App. Capecitance of cable in micro
F/KM
2995
Short Circuit Current Rating for 1 sec .
duration in K. Amps
3030 3990 4985 6290 7630 9945 3740
1195 1540 1890 2375
Air Duct Air
225 330
990
1540 1945 2485
530 615
605 790 1035 1285
810
175
2.2 2.4
430 220 380 360 440
1.6 1.7 1.8 2.0
With Copper Conductor 2XY
Approx. Weight of cable in kg /Km
65 75 95
90 115 155
Ground
1.4
(mm) 0.7 0.7 0.7 0.7 0.9 0.9 1.0 1.1 1.1 1.2
2.8
With Al Conductor A2XY
120
Duct
2.6
Note: Normal Current rating are given in stranded condition . If site conditions are different , current rating should be multiplied by Rating Factor
TABLE -13 TECHNICAL DETAIL FOR V-MARC-1.1 KV SINGLE CORE
AL/COPPER COND. XLPE INSULATED, UN-ARMOURED CABLES
CONDUCTOR : MATERIAL : Aluminium / Copper *Shape:~AL. Cond.:-6 & 10 SQ MM -Solid circular , 16 sqmm & above : Stranded compacted circular ~ Copper Cond :- 4 & 6 sq.mm-solid/stranded non compacted circular ,10 sq. mm Stranded compacted circular 16 sq mm & above : Stranded compacted circular
Ground
SIZE Cross
Sectional Area (Sq MM)
Minimum No of Strand in
Conductor
Nominal Thickness of outer Sheath
Approx. Over all Diameter
Nominal Thickness of Insulation
With Aluminium cond With Copper cond Normal *Current Rating in Amps
Cable Code: A2XY/2XY REF SPEC : IS : 7098 (PT-1) : 1988 PHYSICAL PARAMETERS
Al Cu (mm) (mm) (mm) (mm) 4 ----- 1/7 0.7 0.30 1.80 13 6 1 1/7 0.7 0.30 1.80 14 10 1 6 0.7 0.30 1.80 17 16 6 6 0.7 0.30 1.80 17 25 6 6 0.9 0.30 2.00 19 35 6 6 0.9 0.30 2.00 20 50 6 6 1.0 0.30 2.00 22 70 12 12 1.1 0.30 2.00 25 95 15 15 1.1 0.40 2.20 28 120 15 18 1.2 0.40 2.20 31 150 15 18 1.4 0.40 2.20 33 185 30 30 1.6 0.50 2.40 37 240 30 34 1.7 0.50 2.60 41 300 30 34 1.8 0.60 2.80 44 400 53 53 2.0 0.60 3.00 48 500 53 53 2.2 0.70 3.40 54 630 53 53 2.4 0.70 3.60 62
ELECTRICAL PARAMETERS
Al Cu Al Cu. Al Cu. 4 ----- 4.61 ---- 5.90 0.098 0.11 34 28 30 44 37 39 0.376 0.572 6 4.61 3.08 5.900 3.94 0.090 0.13 43 37 40 55 47 50 0.564 0.858 10 3.08 1.83 3.940 2.34 0.084 0.16 57 48 53 74 61 67 0.940 1.430 16 1.91 1.15 2.440 1.47 0.080 0.18 78 61 70 94 78 85 1.504 2.288 25 1.20 0.727 1.540 0.931 0.080 0.20 95 80 99 120 100 125 2.350 3.575 35 0.868 0.524 1.110 0.671 0.080 0.23 116 94 117 145 120 155 3.290 5.005 50 0.641 0.387 0.820 0.495 0.078 0.24 140 110 140 170 145 190 4.700 7.150 70 0.443 0.268 0.567 0.343 0.077 0.26 170 140 176 210 175 235 6.580 10.010 95 0.320 0.193 0.411 0.248 0.084 0.29 200 165 221 250 210 290 8.930 13.590 120 0.253 0.153 0.325 0.197 0.072 0.29 225 185 258 285 240 330 11.280 17.160 150 0.206 0.1240 0.265 0.1590 0.072 0.29 255 210 294 315 270 375 14.100 21.450 185 0.164 0.0991 0.211 0.1270 0.072 0.29 285 235 339 355 300 425 17.390 26.460 240 0.125 0.0754 0.162 0.098 0.072 0.31 325 270 102 410 350 510 22.560 34.320 300 0.100 0.0601 0.130 0.078 0.071 0.33 370 305 461 460 390 590 28.200 42.900 400 0.0778 0.0470 0.1023 0.0618 0.070 0.33 435 350 542 520 440 670 37.600 57.200 500 0.0605 0.0366 0.0808 0.0489 0.070 0.34 481 405 624 580 480 750 47.000 71.500 630 0.0469 0.0283 0.0648 0.0391 0.069 0.36 537 470 723 680 575 875 59.220 90.090
Note: Normal Current rating are given in stranded condition . If site conditions are different , current rating should be multiplied by Rating Factor
Nominal Thickness of
Insulation
Minimum thickness of inner Sheath
Short Circuit Current Rating for 1 sec .
duration in K. Amps With Aluminium cond With Copper cond
Ground Duct Air Ground Duct Air
CONDUCTOR : MATERIAL : Aluminium / Copper *Shape:~AL. Cond.:-6 & 10 SQ MM -Solid circular , 16 sqmm & above : Stranded compacted circular ~ Copper Cond :- 4 & 6 sq.mm-solid/stranded non compacted circular ,10 sq. mm Stranded compacted circular 16 sq mm & above : Stranded compacted shaped
SIZE cross- sectional
area(Sq MM)
Max. Cond.D.C. Resistance at
20°C in Ohm/km Approx. Cond. AC Resistaance
at 90°C in Ohm/Km App.
Reactance at 50HZ in
ohms/km
App. Capecitance of cable in micro
F/KM
Normal *Current Rating in Amps
5285 12975
3330 8290 4195 10385
1990 4995 2675 6395
1380 3295 1740 3975
990 2190 1175 2675
580 1190 740 1620
395 690 475 880
345 460 365 495
With Copper Conductor 2XY
180 230 320 395
TABLE -14 TECHNICAL DETAIL FOR V-MARC-1.1 KV TWO CORES
AL/COPPER COND. XLPE INSULATED, UN-ARMOURED CABLES
SIZE Cross
Sectional Area (Sq MM)
Minimum No of Strand in
Conductor
Nominal Thickness of outer Sheath
Approx. Over all Diameter
Approx. Weight of cable in kg /Km
With Al Conductor A2XY
Cable Code: A2XY/2XY REF SPEC : IS : 7098 (PT-1) : 1988 PHYSICAL PARAMETERS
Al Cu (mm) (mm) (mm) (mm) 4 ----- 1/7 0.7 0.30 1.80 14 6 1 1/7 0.7 0.30 1.80 16 10 1 6 0.7 0.30 1.80 18 16 6 6 0.7 0.30 1.80 18 25 6 6 0.9 0.30 2.00 21 35 6 6 0.9 0.30 2.00 22 50 6 6 1.0 0.30 2.00 25 70 12 12 1.1 0.40 2.20 30 95 15 15 1.1 0.40 2.20 32 120 15 18 1.2 0.40 2.20 35 150 15 18 1.4 0.50 2.40 39 185 30 30 1.6 0.50 2.60 43 240 30 34 1.7 0.60 2.80 49 300 30 34 1.8 0.60 3.00 53 400 53 53 2.0 0.70 3.20 59 500 53 53 2.2 0.70 3.60 66 630 53 53 2.4 0.70 3.80 73
ELECTRICAL PARAMETERS
Al Cu Al Cu. Al Cu. 4 ----- 4.61 ---- 5.90 0.098 0.11 34 28 30 44 37 39 0.376 0.572 6 4.61 3.08 5.900 3.94 0.090 0.13 43 37 40 55 47 50 0.564 0.858 10 3.08 1.83 3.940 2.34 0.084 0.16 57 48 53 74 61 67 0.940 1.430 16 1.91 1.15 2.440 1.47 0.080 0.18 78 61 70 94 78 85 1.504 2.288 25 1.20 0.727 1.540 0.931 0.080 0.20 95 80 99 120 100 125 2.350 3.575 35 0.868 0.524 1.110 0.671 0.080 0.23 116 94 117 145 120 155 3.290 5.005 50 0.641 0.387 0.820 0.495 0.078 0.24 140 110 140 170 145 190 4.700 7.150 70 0.443 0.268 0.567 0.343 0.077 0.26 170 140 176 210 175 235 6.580 10.010 95 0.320 0.193 0.411 0.248 0.074 0.29 200 165 221 250 210 290 8.930 13.590 120 0.253 0.153 0.325 0.197 0.072 0.29 225 185 258 285 240 330 11.280 17.160 150 0.206 0.1240 0.265 0.1590 0.072 0.29 255 210 294 315 270 375 14.100 21.450 185 0.164 0.0991 0.211 0.1270 0.072 0.29 285 235 339 355 300 435 17.390 26.460 240 0.125 0.0754 0.162 0.0976 0.072 0.31 325 270 402 410 350 510 22.560 34.320 300 0.100 0.0601 0.130 0.0778 0.071 0.33 370 305 461 460 390 590 28.200 42.900 400 0.0778 0.0470 0.1023 0.0618 0.070 0.33 435 350 542 520 440 670 37.600 57.200 500 0.0605 0.0366 0.0808 0.0489 0.070 0.34 481 405 624 580 480 750 47.000 71.500 630 0.0469 0.0283 0.0648 0.0391 0.069 0.36 537 470 723 680 575 875 59.220 90.090
Normal *Current Rating in Amps Short Circuit Current Rating for 1 sec .
duration in K. Amps With Aluminium cond With Copper cond
Note: Normal Current rating are given in stranded condition . If site conditions are different , current rating should be multiplied by Rating Factor
Ground Duct Air Ground Duct Air
SIZE cross- sectional
area(Sq MM)
Max. Cond.D.C. Resistance at
20°C in Ohm/km Approx. Cond. AC Resistaance
at 90°C in Ohm/Km App.
Reactance at 50HZ in
ohms/km
App. Capecitance of cable in micro
F/KM
6095 14975 7630 18990
CONDUCTOR : MATERIAL : Aluminium / Copper *Shape:~AL. Cond.:-6 & 10 SQ MM -Solid circular , 16 sqmm & above : Stranded compacted circular ~ Copper Cond :- 4 & 6 sq.mm-solid/stranded non compacted circular ,10 sq. mm Stranded compacted circular 16 sq mm & above : Stranded compacted shaped
3145 7580 3830 9395 4845 11990
1630 3780 2040 4790 2475 5935
775 1685 1090 2380 1340 3095
410 675 520 995 630 1290
220 280 315 415 395 560
TABLE -15 TECHNICAL DETAIL FOR V-MARC-1.1 KV
THREE CORES ,AL/COPPER COND. XLPE INSULATED, UN-ARMOURED CABLES
SIZE Cross
Sectional Area (Sq MM)
Minimum No of Strand in
Conductor
Nominal Thickness of
Insulation
Minimum thickness of inner Sheath
Nominal Thickness of outer Sheath
Approx. Over all Diameter
Approx. Weight of cable in kg /Km
With Al Conductor A2XY
With Copper Conductor 2XY
Cable Code: 3.5Core A2XY/2XY REF SPEC : IS : 7098 (PT-1) : 1988 PHYSICAL PARAMETERS
Phase Al
Neutral Cu (mm) (mm) (mm) (mm)
3x25+16 6/6 6/6 0.90/0.70 0.30 2.00 22 3x35+16 6/6 6/6 0.90/0.70 0.30 2.00 24 3x50+25 6/6 6/6 1.00/0.90 0.30 2.00 27 3x70+35 12/6 12/6 1.10/0.90 0.40 2.20 31 3x95+50 15/6 15/6 1.10/1.00 0.40 2.20 34 3x120+70 15/12 18/12 1.20/1.10 0.40 2.20 38 3x150+70 15/12 18/12 1.40/1.10 0.50 2.40 43 3x185+95 30/15 30/15 1.60/1.10 0.50 2.60 46 3x240+120 30/15 34/18 1.70/1.20 0.60 2.80 52 3x300+150 30/15 34/18 1.80/1.40 0.60 3.00 57 3x400+185 53/30 53/30 2.00/1.60 0.70 3.40 65 3x500+240 53/30 53/34 2.20/1.70 0.70 3.60 73 3x630+300 53/30 53/34 2.40/1.80 0.70 4.00 82
ELECTRICAL PARAMETERS
Al Cu Al Cu. Al Cu. 3x25+16 1.20 0.727 1.54 0.931 0.080 0.20 95 80 99 120 100 125 2.35 3.58 3x35+16 0.868 0.524 1.11 0.67 0.080 0.23 116 94 117 145 120 155 3.29 5.01 3x50+25 0.641 0.387 0.820 0.495 0.078 0.24 140 110 140 170 145 190 4.70 7.15 3x70+35 0.443 0.268 0.567 0.343 0.077 0.26 170 140 176 210 175 235 6.58 10.01 3x95+50 0.320 0.193 0.411 0.248 0.074 0.29 200 165 221 250 210 290 8.93 13.59 3x120+70 0.253 0.153 0.325 0.197 0.072 0.29 225 185 258 285 240 330 11.28 17.16 3x150+70 0.206 0.124 0.265 0.159 0.072 0.29 255 210 294 315 270 375 14.10 21.45 3x185+95 0.164 0.0991 0.211 0.127 0.072 0.29 285 235 339 355 300 435 17.39 26.46 3x240+120 0.125 0.0754 0.162 0.0980 0.072 0.31 325 270 402 410 350 510 22.56 34.32 3x300+150 0.100 0.0601 0.130 0.0780 0.071 0.33 370 305 461 460 390 590 28.20 42.90 3x400+185 0.0778 0.0470 0.1023 0.0618 0.070 0.33 435 350 542 520 440 670 37.60 57.20 3x500+240 0.0605 0.0366 0.0808 0.0489 0.070 0.34 481 405 624 580 480 750 47.00 71.50 3x630+300 0.0469 0.0283 0.0648 0.0391 0.069 0.36 537 470 723 680 575 875 59.22 90.09
Note: Normal Current rating are given in stranded condition . If site conditions are different , current rating should be multiplied by Rating Factor
Ground Duct Air Ground Duct Air
CONDUCTOR : MATERIAL : Aluminium / Copper *Shape:~AL. Cond.:-6 & 10 SQ MM -Solid circular , 16 sqmm & above : Stranded compacted circular ~ Copper Cond :- 4 & 6 sq.mm-solid/stranded non compacted circular ,10 sq. mm Stranded compacted circular 16 sq mm & above : Stranded compacted shaped
SIZE cross- sectional
area(Sq MM)
Max. Cond.D.C. Resistance at
20°C in Ohm/km Approx. Cond. AC Resistaance
at 90°C in Ohm/Km App.
Reactance at 50HZ in
ohms/km
App. Capecitance of cable in micro
F/KM
Normal *Current Rating in Amps Short Circuit Current Rating for 1 sec .
duration in K. Amps With Aluminium cond With Copper cond
8880 21990
3595 8680 4390 10780 5580 13990
2275 5490 2790 6775
6990 17490
1195 2675 1475 3580 1890 4490
590 1130 675 1435 880 1990
TABLE -16 TECHNICAL DETAIL FOR V-MARC-1.1 KV
THREE & HALF CORES ,AL/COPPER COND. XLPE INSULATED, UN-ARMOURED CABLES
SIZE Cross
Sectional Area (Sq MM)
Minimum No of Strand in
Conductor
Nominal Thickness of
Insulation
Minimum thickness of inner Sheath
Nominal Thickness of outer Sheath
Approx. Over all Diameter
Approx. Weight of cable in kg /Km
With Al Conductor A2XY
With Copper Conductor 2XY
Cable Code: A2XY/2XY REF SPEC : IS : 7098 (PT-1) : 1988 PHYSICAL PARAMETERS
Al Cu (mm) (mm) (mm) (mm) 4 ----- 1/7 0.7 0.30 1.80 17 6 1 1/7 0.7 0.30 1.80 18 10 1 6 0.7 0.30 1.80 20 16 6 6 0.7 0.30 1.80 20 25 6 6 0.9 0.30 2.00 24 35 6 6 0.9 0.30 2.00 26 50 6 6 1.0 0.30 2.00 29 70 12 12 1.1 0.40 2.20 34 95 15 15 1.1 0.40 2.20 37 120 15 18 1.2 0.50 2.40 41 150 15 18 1.4 0.50 2.60 45 185 30 30 1.6 0.50 2.80 50 240 30 34 1.7 0.60 3.00 56 300 30 34 1.8 0.70 3.20 63 400 53 53 2.0 0.70 3.60 70 500 53 53 2.2 0.70 3.80 79 630 53 53 2.4 0.70 4.00 88
ELECTRICAL PARAMETERS
Al Cu Al Cu. Al Cu. 4 ----- 4.61 ---- 5.90 0.098 0.11 34 28 30 44 37 39 0.376 0.572 6 4.61 3.08 5.900 3.94 0.090 0.13 43 37 40 55 47 50 0.564 0.858 10 3.08 1.83 3.940 2.34 0.084 0.16 57 48 53 74 61 67 0.940 1.430 16 1.91 1.15 2.440 1.47 0.080 0.18 78 61 70 94 78 85 1.504 2.288 25 1.20 0.727 1.540 0.931 0.08 0.20 95 80 99 120 100 125 2.350 3.575 35 0.868 0.524 1.110 0.671 0.080 0.23 116 94 117 145 120 155 3.290 5.005 50 0.641 0.387 0.820 0.495 0.078 0.24 140 110 140 170 145 190 4.700 7.150 70 0.443 0.268 0.567 0.343 0.077 0.26 170 140 176 210 175 235 6.580 10.010 95 0.320 0.193 0.411 0.248 0.074 0.29 200 165 221 250 210 290 8.930 13.590 120 0.253 0.153 0.325 0.197 0.072 0.29 225 185 258 285 240 330 11.280 17.160 150 0.206 0.1240 0.265 0.1590 0.072 0.29 255 210 394 315 270 375 14.100 21.450 185 0.164 0.0991 0.211 0.1270 0.072 0.29 285 235 339 355 300 435 17.390 26.460 240 0.125 0.0754 0.162 0.0976 0.072 0.31 325 270 402 410 350 510 22.560 34.320 300 0.100 0.0601 0.130 0.0778 0.071 0.33 370 305 461 460 390 590 28.200 42.900 400 0.0778 0.0470 0.1023 0.0618 0.070 0.33 435 350 542 520 440 670 37.600 57.200 500 0.0605 0.0366 0.0808 0.0489 0.070 0.34 481 405 624 580 480 750 47.000 71.500 630 0.0469 0.0283 0.0648 0.0391 0.069 0.36 537 470 723 680 575 875 59.220 90.090
CONDUCTOR : MATERIAL : Aluminium / Copper *Shape:~AL. Cond.:-6 & 10 SQ MM -Solid circular , 16 sqmm & above : Stranded compacted circular ~ Copper Cond :- 4 & 6 sq.mm-solid/stranded non compacted circular ,10 sq. mm Stranded compacted circular 16 sq mm & above : Stranded compacted shaped
Normal *Current Rating in Amps Short Circuit Current Rating for 1 sec .
duration in K. Amps With Aluminium cond With Copper cond
Note: Normal Current rating are given in stranded condition . If site conditions are different , current rating should be multiplied by Rating Factor
Ground Duct Air Ground Duct Air
SIZE cross- sectional
area(Sq MM)
Max. Cond.D.C. Resistance at
20°C in Ohm/km Approx. Cond. AC Resistaance
at 90°C in Ohm/Km App.
Reactance at 50HZ in
ohms/km
App. Capecitance of cable in micro
F/KM
7990 19960 9975 25990
4095 9995 5040 12035 6375 15975
2140 5140 2530 6330 3240 7840
990 2190 1375 3095 1690 3985
440 840 655 1295 785 1680
245 340 340 495 395 630
TABLE -17 TECHNICAL DETAIL FOR V-MARC-1.1 KV
FOUR CORES ,AL/COPPER COND. XLPE INSULATED, UN-ARMOURED CABLES
SIZE Cross
Sectional Area (Sq MM)
Minimum No of Strand in
Conductor
Nominal Thickness of
Insulation
Minimum thickness of inner Sheath
Nominal Thickness of outer Sheath
Approx. Over all Diameter
Approx. Weight of cable in kg /Km
With Al Conductor A2XY
With Copper Conductor 2XY
Cable Code: A2XFaY/2XFaY,A2XWaY/2XWaY REF SPEC : IS : 7098 (PT-1) : 1988 PHYSICAL PARAMETERS
Nominal Thickness of armour
Nominal Thickness of outer Sheath
Approx. Over all Diameter
Nominal Diameter of wire
Minimum Thickeness of outer sheath.
Approx. Over all Diameter
Al Cu (mm) (mm) (mm) (mm) Al Cond. A2XFaY
Cu. Cond. 2XFaY (mm) (mm) (mm) Cu. Cond.
2XWaY 4 ----- 1/7 1.0 N/A N/A N/A N/A N/A 1.40 1.24 10 125 6 1 1/7 1.0 N/A N/A N/A N/A N/A 1.40 1.24 11 165 10 1 6 1.0 N/A N/A N/A N/A N/A 1.40 1.24 12 215 16 6 6 1.0 N/A N/A N/A N/A N/A 1.40 1.24 13 290 25 6 6 1.2 N/A N/A N/A N/A N/A 1.40 1.24 14 445 35 6 6 1.2 N/A N/A N/A N/A N/A 1.40 1.24 15 540 50 6 6 1.3 N/A N/A N/A N/A N/A 1.40 1.24 17 710 70 12 12 1.4 N/A N/A N/A N/A N/A 1.40 1.24 19 925 95 15 15 1.4 0.80 1.40 21 590 1175 1.60 1.40 22 1225 120 15 18 1.5 0.80 1.40 23 685 1440 1.60 1.40 24 1480 150 15 18 1.7 0.80 1.40 24 790 1715 1.60 1.40 25 1765 185 30 30 1.9 0.80 1.40 26 940 2095 1.60 1.40 28 2125 240 30 34 2.0 0.80 1.40 30 1190 2670 1.60 1.40 30 2770 300 30 34 2.1 0.80 1.56 32 1375 3260 1.60 1.56 33 3340 400 53 53 2.4 0.80 1.56 36 1730 4220 2.00 1.56 38 4360 500 53 53 2.6 0.80 1.56 39 2140 5230 2.00 1.56 41 5440 630 53 53 2.8 0.80 1.72 44 2675 6605 2.00 1.72 46 6795 800 53 53 3.1 0.80 1.72 48 3330 8310 2.00 1.88 51 8640 1000 53 53 3.3 0.80 1.88 54 4090 10290 2.50 2.04 56 10780
ELECTRICAL PARAMETERS
Al Cu Al Cu. Al Cu. 4 ----- 4.61 ---- 5.90 0.152 0.22 --- --- --- 48 47 45 0.376 0.572 6 4.61 3.08 5.900 3.94 0.144 0.26 45 45 40 60 59 57 0.564 0.858 10 3.08 1.83 3.940 2.34 0.133 0.31 59 62 53 80 78 77 0.940 1.430 16 1.91 1.15 2.440 1.47 0.122 0.40 76 80 73 104 102 106 1.504 2.288 25 1.20 0.727 1.540 0.931 0.116 0.40 99 90 115 130 115 145 2.350 3.575 35 0.868 0.524 1.110 0.671 0.110 0.47 117 110 140 155 140 175 3.290 5.005 50 0.641 0.387 0.820 0.495 0.103 0.50 138 125 170 185 165 215 4.700 7.150 70 0.443 0.268 0.567 0.343 0.099 0.55 168 155 210 225 200 270 6.580 10.010 95 0.320 0.193 0.411 0.248 0.097 0.64 204 185 255 265 235 330 8.930 13.590 120 0.253 0.153 0.325 0.197 0.093 0.67 230 210 300 300 265 380 11.280 17.160 150 0.206 0.1240 0.265 0.1590 0.091 0.67 265 230 342 335 300 430 14.100 21.450 185 0.164 0.0991 0.211 0.1270 0.090 0.67 295 260 385 380 335 495 17.390 26.460 240 0.125 0.0754 0.162 0.0976 0.086 0.72 340 300 450 435 385 590 22.590 34.320 300 0.100 0.0601 0.130 0.0778 0.085 0.75 390 335 519 490 430 670 28.200 42.900 400 0.0778 0.0470 0.1023 0.0618 0.085 0.75 450 380 605 550 480 780 37.600 57.200 500 0.0605 0.0366 0.0808 0.0489 0.083 0.77 500 430 700 610 530 900 47.000 71.500 630 0.0469 0.0283 0.6480 0.0391 0.082 0.81 555 485 809 680 590 1020 59.220 90.090 800 0.0367 0.0221 0.0503 0.0319 0.081 0.88 625 530 935 740 630 1140 75.200 114.400 1000 0.0291 0.0176 0.0444 0.0268 0.081 0.88 690 570 1065 780 660 1250 94.000 143.000
4590
Note: Normal Current rating are given in stranded condition . If site conditions are different , current rating should be multiplied by Rating Factor
Nominal Thickness
of Insulation
Approx. Weight of cable in kg /Km
ARMOURING WITH FLATE STRIP(A2XFaY/2XFaY) ARMOURING WITH ROUND WIRES(A2XWaY/2XWaY)
Approx. Weight of cable in kg /Km
Al Cond. A2XWaY
85
Short Circuit Current Rating for 1 sec .
duration in K. Amps
With Aluminium cond With Copper cond
Ground Duct Air Ground Duct Air
CONDUCTOR : MATERIAL : Aluminium / Copper *Shape:~AL. Cond.:-6 & 10 SQ MM -Solid circular , 16 sqmm & above : Stranded compacted circular ~ Copper Cond :- 4 & 6 sq.mm-solid/stranded non compacted circular ,10 sq. mm & above : Stranded compacted circular
SIZE cross- sectional
area(Sq MM)
Max. Cond.D.C. Resistance at
20°C in Ohm/km
Approx. Cond. AC Resistaance at 90°C in
Ohm/Km
App. Reactance at
50HZ in ohms/km
App. Capecitance of cable in micro F/KM
Normal *Current Rating in Amps
2875 3590
1890 2330
1240 1495
840 990
640 730
415 510
280 335
155 190
120
TABLE -18 TECHNICAL DETAIL FOR V-MARC-1.1 KV
SINGLE CORE ,AL/COPPER COND. XLPE INSULATED, GI WIRE/STRIP ARMOURED CABLES
SIZE Cross
Sectional Area (Sq MM)
Minimum No of Strand in
Conductor
Cable Code: A2XFY/2XFY,A2XWY/2XWY REF SPEC : IS : 7098 (PT-1) : 1988 PHYSICAL PARAMETERS
Nominal Thickness of armour
Nominal Thickness of outer Sheath
Approx. Over all Diameter
Nominal Diameter of wire
Minimum Thickeness of outer sheath.
Approx. Over all Diameter
Al Cu (mm) (mm) (mm) (mm) Al Cond. A2XFY
Cu. Cond. 2XFY (mm) (mm) (mm) Cu. Cond.
2XWY 4 ----- 1/7 0.7 N/A N/A N/A N/A N/A 1.40 1.24 15 530 6 1 1/7 0.7 N/A N/A N/A N/A N/A 1.40 1.24 16 575 10 1 6 0.7 N/A N/A N/A N/A N/A 1.40 1.24 18 760 16 6 6 0.7 N/A N/A N/A N/A N/A 1.40 1.40 19 895 25 6 6 0.9 0.80 1.40 20 630 945 1.60 1.40 21 1140 35 6 6 0.9 0.80 1.40 21 740 1195 1.60 1.40 23 1390 50 6 6 1.0 0.80 1.40 23 890 1490 1.60 1.40 25 1685 70 12 12 1.1 0.80 1.56 26 1080 1930 1.60 1.56 28 2230 95 15 15 1.1 0.80 1.56 29 1330 2475 2.00 1.56 31 2990 120 15 18 1.2 0.80 1.56 31 1580 3095 2.00 1.56 34 3585 150 15 18 1.4 0.80 1.72 34 1875 3740 2.00 1.72 37 4295 185 30 30 1.6 0.80 1.72 37 2230 4485 2.00 1.88 40 5190 240 30 34 1.7 0.80 1.88 42 2790 5780 2.50 2.04 45 6770 300 30 34 1.8 0.80 2.04 45 3275 6990 2.50 2.20 49 8190 400 53 53 2.0 0.80 2.36 50 4095 9035 2.50 2.36 52 10295 500 53 53 2.2 0.80 2.52 55 4990 10985 3.15 2.68 60 13275 630 53 53 2.4 0.80 2.68 63 6085 13990 3.15 2.84 66 16290
ELECTRICAL PARAMETERS
Al Cu Al Cu. 4 ----- 4.61 0.098 0.11 34 28 30 44 37 39 0.376 0.572 6 4.61 3.08 0.090 0.13 43 37 40 55 47 50 0.564 0.858 10 3.08 1.83 0.084 0.16 57 48 53 74 61 67 0.940 1.430 16 1.91 1.15 0.080 0.18 78 61 70 94 78 85 1.504 2.288 25 1.20 0.727 0.080 0.20 95 80 99 120 100 125 2.350 3.575 35 0.868 0.524 0.080 0.23 116 94 117 145 120 155 3.290 5.005 50 0.641 0.387 0.078 0.24 140 110 140 170 145 190 4.700 7.150 70 0.443 0.268 0.077 0.26 170 140 176 210 175 235 6.580 10.010 95 0.320 0.193 0.074 0.29 200 165 221 250 210 290 8.930 13.590 120 0.253 0.153 0.072 0.29 225 185 258 285 240 330 11.280 17.160 150 0.206 0.1240 0.072 0.29 255 210 294 315 270 375 14.100 21.450 185 0.164 0.0991 0.072 0.29 285 235 339 355 300 435 17.390 26.460 240 0.125 0.0754 0.072 0.31 325 270 402 410 350 510 22.560 34.320 300 0.100 0.0601 0.071 0.33 370 305 461 460 390 590 28.200 42.900 400 0.0778 0.0470 0.070 0.33 435 350 542 520 440 670 37.600 57.200 500 0.0605 0.0366 0.070 0.34 481 405 624 580 480 750 47.000 71.500 630 0.0469 0.0283 0.069 0.36 537 470 723 680 575 875 59.220 90.090
0.70
0.40 0.50 0.50 0.60 0.60 0.70
0.30 0.30 0.40 0.40
0.30 0.30 0.30 0.30 0.30 0.30
0.820
0.1590
Cu. 5.90 3.94 2.34 1.47 0.931 0.671 0.495
Note: Normal Current rating are given in stranded condition . If site conditions are different , current rating should be multiplied by Rating Factor
0.0489 0.0391
0.0618
0.197 0.325
0.1270 0.0976 0.0778
0.265
0.130 0.1023
CONDUCTOR : MATERIAL : Aluminium / Copper *Shape:~AL. Cond.:-6 & 10 SQ MM -Solid circular , 16 sqmm & above : Stranded compacted circular ~ Copper Cond :- 4 & 6 sq.mm-solid/stranded non compacted circular ,10 sq. mm Stranded compacted circular 16 sq mm & above : Stranded compacted shaped
0.0808 0.0648
0.211 0.162
0.343 0.248
0.567 0.411
Al ----
5.900 3.940 2.440 1.540 1.110
Normal *Current Rating in Amps Short Circuit Current
Rating for 1 sec . duration in K. Amps
2890 3845 4435 5340 7095 8490
With Aluminium cond With Copper cond
Ground Duct Air Ground Duct Air
SIZE cross- sectional
area(Sq MM)
Max. Cond.D.C. Resistance at
20°C in Ohm/km Approx. Cond. AC Resistaance at
90°C in Ohm/Km App.
Reactance at 50HZ in
ohms/km
App. Capecitan
ce of cable in micro F/KM
2430
Al Cond. A2XWY
485 540 635 690 845 930 1090 1375 1835 2140
TABLE -19 TECHNICAL DETAIL FOR V-MARC-1.1 KV
TWO CORES ,AL/COPPER COND. XLPE INSULATED, GI WIRE/STRIP ARMOURED CABLES
SIZE Cross
Sectional Area (Sq MM)
Minimum No of Strand in
Conductor
Nominal Thickness
of Insulation
ARMOURING WITH FLATE STRIP(A2XFY/2XFY) ARMOURING WITH ROUND WIRES(A2XWY/2XWY)
Approx. Weight of cable in kg /Km
Approx. Weight of cable in kg /Km
Minimum Thickness
of Inner Sh.
(mm)
Cable Code: A2XFY/2XFY,A2XWY/2XWY REF SPEC : IS : 7098 (PT-1) : 1988 PHYSICAL PARAMETERS
Nominal Thickness of armour
Nominal Thickness of outer Sheath
Approx. Over all Diameter
Nominal Diameter of wire
Minimum Thickeness of outer sheath.
Approx. Over all Diameter
Al Cu (mm) (mm) (mm) (mm) Al Cond. A2XFY
Cu. Cond. 2XFY (mm) (mm) (mm) Cu. Cond.
2XWY 4 ----- 1/7 0.7 N/A N/A N/A N/A N/A 1.40 1.24 18 665 6 1 1/7 0.7 N/A N/A N/A N/A N/A 1.40 1.24 19 765 10 1 6 0.7 N/A N/A N/A N/A N/A 1.40 1.24 20 925 16 6 6 0.7 0.80 1.24 19 590 600 1.60 1.40 20 995 25 6 6 0.9 0.80 1.40 21 775 1195 1.60 1.40 23 1440 35 6 6 0.9 0.80 1.40 23 935 1490 1.60 1.40 25 1830 50 6 6 1.0 0.80 1.40 26 1095 1995 1.60 1.56 29 2295 70 12 12 1.1 0.80 1.56 29 1430 2675 2.00 1.56 32 3290 95 15 15 1.1 0.80 1.56 32 1740 3485 2.00 1.56 35 4095 120 15 18 1.2 0.80 1.56 35 2095 4195 2.00 1.72 39 4890 150 15 18 1.4 0.80 1.72 42 2490 5180 2.00 1.88 43 5975 185 30 30 1.6 0.80 1.88 44 2985 6290 2.50 2.04 48 7495 240 30 34 1.7 0.80 2.04 49 3740 8190 2.50 2.20 53 9490 300 30 34 1.8 0.80 2.20 54 4475 9995 2.50 2.36 58 11290 400 53 53 2.0 0.80 2.52 60 5580 12990 3.15 2.68 65 15190 500 53 53 2.2 0.80 2.68 66 6890 15975 3.15 2.84 72 18495 630 53 53 2.4 0.80 2.84 74 8530 19975 4.00 3.00 81 23675
ELECTRICAL PARAMETERS
Al Cu Al Cu. 4 ----- 4.61 0.098 0.11 34 28 30 44 37 39 0.376 0.572 6 4.61 3.08 0.090 0.13 43 37 40 55 47 50 0.564 0.858 10 3.08 1.83 0.084 0.16 57 48 53 74 61 67 0.940 1.430 16 1.91 1.15 0.080 0.18 78 61 70 94 78 85 1.504 2.288 25 1.20 0.727 0.080 0.20 95 80 99 120 100 125 2.350 3.575 35 0.868 0.524 0.080 0.23 116 94 117 145 120 155 3.290 5.005 50 0.641 0.387 0.078 0.24 140 110 140 170 145 190 4.700 7.150 70 0.443 0.268 0.077 0.26 170 140 176 210 175 235 6.580 10.010 95 0.320 0.193 0.074 0.29 200 165 221 250 210 290 8.930 13.590 120 0.253 0.153 0.072 0.29 225 185 258 285 240 330 11.280 17.160 150 0.206 0.1240 0.072 0.29 255 210 294 315 270 375 14.100 21.450 185 0.164 0.0991 0.072 0.29 285 235 339 355 300 435 17.390 26.460 240 0.125 0.0754 0.072 0.31 325 270 402 410 350 510 22.560 34.320 300 0.100 0.0601 0.071 0.33 370 305 461 460 390 590 28.200 42.900 400 0.0778 0.0470 0.070 0.33 435 350 542 520 440 670 37.600 57.200 500 0.0605 0.0366 0.070 0.34 481 405 624 580 480 750 47.000 71.500 630 0.0469 0.0283 0.069 0.36 537 470 723 680 575 875 59.220 90.090
CONDUCTOR : MATERIAL : Aluminium / Copper *Shape:~AL. Cond.:-6 & 10 SQ MM -Solid circular , 16 sqmm & above : Stranded compacted circular ~ Copper Cond :- 4 & 6 sq.mm-solid/stranded non compacted circular ,10 sq. mm Stranded compacted circular 16 sq mm & above : Stranded compacted shaped
0.130 0.0778
Note: Normal Current rating are given in stranded condition . If site conditions are different , current rating should be multiplied by Rating Factor
0.1023 0.0618 0.0808 0.0489 0.0648 0.0391
0.265 0.1590 0.211 0.1270 0.162 0.0976
0.567 0.343 0.411 0.248 0.325 0.197
1.540 0.931 1.110 0.671 0.820 0.495
5.900 3.94 3.940 2.34 2.440 1.47
Duct Al Cu. ---- 5.90
0.70 12575
Air
SIZE cross- sectional
area(Sq MM)
Max. Cond.D.C. Resistance at
20°C in Ohm/km Approx. Cond. AC Resistaance at
90°C in Ohm/Km App.
Reactance at 50HZ in
ohms/km
App. Capecitanc e of cable in micro F/KM
Normal *Current Rating in Amps Short Circuit Current
Rating for 1 sec . duration in K. Amps
With Aluminium cond With Copper cond
Ground Duct Air Ground
0.60 5975 0.70 7940 0.70 9480
0.40 3230 0.50 4195 0.50 5095
0.30 1985 0.40 2345 0.40 2745
0.30 995 0.30 1195 0.30 1435
595
0.30 740 0.30 895
0.30 645 0.30
TABLE -20 TECHNICAL DETAIL FOR V-MARC-1.1 KV
THREE CORES ,AL/COPPER COND. XLPE INSULATED, GI WIRE/STRIP ARMOURED CABLES
SIZE Cross
Sectional Area (Sq MM)
Minimum No of Strand in
Conductor
Nominal Thickness
of Insulation
Minimum Thickness
of Inner Sh.
ARMOURING WITH FLATE STRIP(A2XFY/2XFY) ARMOURING WITH ROUND WIRES(A2XWY/2XWY)
Approx. Weight of cable in kg /Km
Approx. Weight of cable in kg /Km
(mm) Al Cond. A2XWY
Cable Code: 3.5Core - A2XFY/2XY,A2XWY,2XWY REF SPEC : IS : 7098 (PT-1) : 1988 PHYSICAL PARAMETERS
Nominal Thickness of armour
Nominal Thickness of outer Sheath
Approx. Over all Diameter
Nominal Diameter of wire
Minimum Thickeness
of outer sheath.
Approx. Over all
Diameter Phase
Al Neutral
Cu (mm) (mm) (mm) (mm) Al Cond. A2XFY
Cu. Cond. 2XFY (mm) (mm) (mm) Cu. Cond.
2XWY 3x25+16 6/6 6/6 0.90/0.70 0.80 1.40 23 895 1390 1.60 1.40 25 1690 3x35+16 6/6 6/6 0.90/0.70 0.80 1.40 25 990 1790 1.60 1.40 27 1990 3x50+25 6/6 6/6 1.00/0.90 0.80 1.40 28 1190 2290 1.60 1.56 30 2695 3x70+35 12/6 12/6 1.10/0.90 0.80 1.56 32 1595 3195 2.00 1.56 35 3680 3x95+50 16/6 15/6 1.10/1.00 0.80 1.56 35 1990 4090 2.00 1.56 38 4595
3x120+70 15/12 18/12 1.20/1.10 0.80 1.72 39 2390 5075 2.00 1.72 42 5690 3x150+70 15/12 18/12 1.40/1.10 0.80 1.72 43 2795 5980 2.00 1.88 46 6785 3x185+95 30/15 30/15 1.60/1.10 0.80 1.88 47 3375 7395 2.50 2.04 51 8675 3x240+120 30/15 34/18 1.70/1.20 0.80 2.04 53 4295 9490 2.50 2.20 56 10495 3x300+150 30/15 34/18 1.80/1.40 0.80 2.20 57 4985 11495 2.50 2.36 60 12995 3x400+185 53/30 53/30 2.00/1.60 0.80 2.52 66 6390 14475 3.15 2.68 71 16985 3x500+240 53/30 53/34 2.20/1.70 0.80 2.68 74 7695 17790 3.15 2.84 79 21490 3x630+300 53/30 53/34 2.40/1.80 0.80 3.00 82 9890 22975 4.00 3.00 88 27975
ELECTRICAL PARAMETERS
Al Cu Al Cu. 3x25+16 1.20 0.727 0.080 0.20 95 80 99 120 100 125 2.35 3.58 3x35+16 0.868 0.524 0.080 0.23 116 94 117 145 120 155 3.29 5.01 3x50+25 0.641 0.387 0.078 0.24 140 110 140 170 145 190 4.70 7.15 3x70+35 0.443 0.268 0.077 0.26 170 140 176 210 175 235 6.58 10.01 3x95+50 0.320 0.193 0.074 0.29 200 165 221 250 210 290 8.93 13.59
3x120+70 0.253 0.153 0.072 0.29 225 185 258 285 240 330 11.28 17.16 3x150+70 0.206 0.1240 0.072 0.29 255 210 294 315 270 375 14.10 21.45 3x185+95 0.164 0.0991 0.072 0.29 285 235 339 355 300 435 17.39 26.46 3x240+120 0.125 0.0754 0.072 0.31 325 270 402 410 350 510 22.56 34.32 3x300+150 0.100 0.0601 0.071 0.33 370 305 461 460 390 590 28.20 42.90 3x400+185 0.0778 0.0470 0.070 0.33 435 350 542 520 440 670 37.60 57.20 3x500+240 0.0605 0.0366 0.070 0.34 481 405 624 580 480 750 47.00 71.50 3x630+300 0.0469 0.0283 0.069 0.36 537 470 723 680 575 875 59.22 90.09
Note: Normal Current rating are given in stranded condition . If site conditions are different , current rating should be multiplied by Rating Factor
Al Cu. 1.54 0.931
0.820
Air
1.11 0.671 0.495
0.567 0.343 0.411 0.248
0.197 0.265
CONDUCTOR : MATERIAL : Aluminium / Copper *Shape:~AL. Cond.:-6 & 10 SQ MM -Solid circular , 16 sqmm & above : Stranded compacted circular ~ Copper Cond :- 4 & 6 sq.mm-solid/stranded non compacted circular ,10 sq. mm Stranded compacted circular 16 sq mm & above : Stranded compacted shaped
SIZE cross- sectional
area(Sq MM)
Max. Cond.D.C. Resistance at
20°C in Ohm/km Approx. Cond. AC Resistaance at
90°C in Ohm/Km App.
Reactance at 50HZ in
ohms/km
App. Capecitance of cable in micro F/KM
Normal *Current Rating in Amps Short Circuit Current
Rating for 1 sec . duration in K. Amps
With Aluminium cond With Copper cond
Ground Duct Air Ground Duct
0.50 4675
0.70 10980 0.70 14490
0.60 5690 0.60 6680 0.70 8975
0.40 2595 0.40 3090 0.50 3580
1095
0.30 1575 0.40 2190
0.30 1280 0.30
TABLE -21 TECHNICAL DETAIL FOR V-MARC-1.1 KV
THREE & HALF CORES,AL/COPPER COND. XLPE INSULATED, GI WIRE/STRIP ARMOURED CABLES
SIZE Cross
Sectional Area (Sq MM)
Minimum No of Strand in
Conductor
Nominal Thickness
of Insulation
Minimum Thickness
of Inner Sh.
ARMOURING WITH FLATE STRIP(A2XFY/2XFY) ARMOURING WITH ROUND WIRES(A2XWY/2XWY)
Approx. Weight of cable in kg /Km
Approx. Weight of cable in kg /Km
(mm) Al Cond. A2XWY
0.162
0.1023 0.0618
0.159 0.325
0.211 0.127 0.0980
0.0808 0.0648
0.0489 0.0391
0.130 0.0780
Cable Code: A2XFY/2XFY, A2XWY/2XWY REF SPEC : IS : 7098 (PT-1) : 1988 PHYSICAL PARAMETERS
Nominal Thickness of armour
Nominal Thickness of outer Sheath
Approx. Over all Diameter
Nominal Diameter of wire
Minimum Thickeness
of outer sheath.
Approx. Over all
Diameter
Al Cu (mm) (mm) (mm) (mm) Al Cond. A2XFY
Cu. Cond. 2XFY (mm) (mm) (mm) Cu. Cond.
2XWY 4 ----- 1/7 0.7 N/A N/A N/A N/A N/A 1.40 1.24 18 635 6 1 1/7 0.7 N/A N/A N/A N/A N/A 1.40 1.24 19 745
10 1 6 0.7 N/A N/A N/A N/A N/A 1.40 1.40 21 940 16 6 6 0.7 0.80 1.40 20 695 1085 1.60 1.40 22 1295 25 6 6 0.9 0.80 1.40 24 890 1495 1.60 1.40 26 1760 35 6 6 0.9 0.80 1.40 27 1095 1990 1.60 1.40 28 2195 50 6 6 1.0 0.80 1.56 30 1380 2485 1.60 1.56 32 2840 70 12 12 1.1 0.80 1.56 34 1790 3395 2.00 1.56 37 3995 95 15 15 1.1 0.80 1.56 37 2195 4390 2.00 1.72 40 5130
120 15 18 1.2 0.80 1.72 41 2680 5590 2.00 1.88 44 6295 150 15 18 1.4 0.80 1.88 46 3195 6775 2.50 2.04 49 7985 185 30 30 1.6 0.80 2.04 51 3880 8290 2.50 2.20 54 9685 240 30 34 1.7 0.80 2.20 57 4840 10490 2.50 2.36 65 11975 300 30 34 1.8 0.80 2.36 63 5830 12975 3.15 2.52 68 15390 400 53 53 2.0 0.80 2.68 71 7310 16980 3.15 2.84 76 19495 500 53 53 2.2 0.80 2.84 79 8990 20970 4.00 3.00 86 24975 630 53 53 2.4 0.80 3.00 88 10975 26985 4.00 3.00 94 30470
ELECTRICAL PARAMETERS
Al Cu Al Cu. 4 ----- 4.61 0.098 0.11 34 28 30 44 37 39 0.376 0.572 6 4.61 3.08 0.090 0.13 43 37 40 55 47 50 0.564 0.858
10 3.08 1.83 0.084 0.16 57 48 53 74 61 67 0.940 1.430 16 1.91 1.15 0.080 0.18 78 61 70 94 78 85 1.504 2.288 25 1.20 0.727 0.080 0.20 95 80 99 120 100 125 2.350 3.575 35 0.868 0.524 0.080 0.23 116 94 117 145 120 155 3.290 5.005 50 0.641 0.387 0.078 0.24 140 110 140 170 145 190 4.700 7.150 70 0.443 0.268 0.077 0.26 170 140 176 210 175 235 6.580 10.010 95 0.320 0.193 0.074 0.29 200 165 221 250 210 290 8.930 13.590
120 0.253 0.153 0.072 0.29 225 185 258 285 240 330 11.280 17.160 150 0.206 0.1240 0.072 0.29 255 210 294 315 270 375 14.100 21.450 185 0.164 0.0991 0.072 0.29 285 235 339 355 300 435 17.390 26.460 240 0.125 0.0754 0.072 0.31 325 270 402 410 350 510 22.560 34.320 300 0.100 0.0601 0.071 0.33 370 305 460 460 390 590 28.200 42.900 400 0.0778 0.0470 0.070 0.33 435 350 542 520 440 670 37.600 57.200 500 0.0605 0.0366 0.070 0.34 481 405 624 580 480 750 47.000 71.500 630 0.0469 0.0283 0.069 0.36 537 470 723 680 575 875 59.220 90.090
0.130 0.0778
Note: Normal Current rating are given in stranded condition . If site conditions are different , current rating should be multiplied by Rating Factor
0.1023 0.0618 0.0808 0.0489 0.0648 0.0391
0.265 0.1590 0.211 0.1270 0.162 0.0976
0.567 0.343 0.411 0.248 0.325 0.197
1.540 0.931 1.110 0.671 0.820 0.495
5.900 3.94 3.940 2.34 2.440 1.47
Ground Duct Al Cu. ---- 5.90
0.70 15975
Air
CONDUCTOR : MATERIAL : Aluminium / Copper *Shape:~AL. Cond.:-6 & 10 SQ MM -Solid circular , 16 sqmm & above : Stranded compacted circular ~ Copper Cond :- 4 & 6 sq.mm-solid/stranded non compacted circular ,10 sq. mm Stranded compacted circular 16 sq mm & above : Stranded compacted shaped
SIZE cross- sectional
area(Sq MM)
Max. Cond.D.C. Resistance at
20°C in Ohm/km Approx. Cond. AC Resistaance at
70°C in Ohm/Km App.
Reactance at 50HZ in
ohms/km
App. Capecitance of cable in micro F/KM
Normal *Current Rating in Amps Short Circuit Current
Rating for 1 sec . duration in K. Amps
With Aluminium cond With Copper cond
Ground Duct Air
0.70 8195 0.70 9990 0.70 13485
0.50 4495 0.50 5175 0.60 6380
0.40 2395 0.40 2895 0.50 3490
0.30 1195 0.30 1440 0.30 1735
540
0.30 660 0.30 915
0.30 595 0.30
TABLE -22 TECHNICAL DETAIL FOR V-MARC-1.1 KV
FOUR CORES ,AL/COPPER COND. XLPE INSULATED, GI WIRE/STRIP ARMOURED CABLES
SIZE Cross
Sectional Area (Sq MM)
Minimum No of Strand in
Conductor
Nominal Thickness
of Insulation
Minimum Thickness
of Inner Sh.
ARMOURING WITH FLATE STRIP(A2XFY/2XFY) ARMOURING WITH ROUND WIRES(A2XWY/2XWY)
Approx. Weight of cable in kg /Km
Approx. Weight of cable in kg /Km
(mm) Al Cond. A2XWY
Cable Code: 2XY,2XFY,2XWY REF SPEC : IS : 7098 (PT-1) : 1988 PHYSICAL PARAMETERS
Nom. Thick. of
outer Sheath
Nominal Thickness of armour
Minimum Thickness of outer Sheath
Nominal Diameter
of wire
Minimum Thickeness
of outer sheath.
(mm) (mm) (mm) Solid cond. Std. cond. Solid cond. Std. cond. (mm) (mm) Solid cond. Std. cond. Solid cond. Std. cond. (mm) (mm) Solid cond. Std. cond. Solid cond. Std. cond. 2 0.70 0.30 1.80 11 12 175 182 N/A N/A N/A N/A N/A N/A 1.40 1.24 12 13 313 327 3 0.70 0.30 1.80 11 12 202 203 N/A N/A N/A N/A N/A N/A 1.40 1.24 13 13 356 371 4 0.70 0.30 1.80 12 13 236 238 N/A N/A N/A N/A N/A N/A 1.40 1.24 14 14 410 427 5 0.70 0.30 1.80 13 14 274 276 N/A N/A N/A N/A N/A N/A 1.40 1.24 15 15 466 485 6 0.70 0.30 1.80 14 15 313 315 N/A N/A N/A N/A N/A N/A 1.40 1.24 15 16 524 545 7 0.70 0.30 1.80 14 15 343 346 N/A N/A N/A N/A N/A N/A 1.40 1.24 15 16 551 571 10 0.70 0.30 1.80 17 18 470 475 N/A N/A N/A N/A N/A N/A 1.60 1.40 19 20 746 774 12 0.70 0.30 1.80 18 19 537 542 0.80 1.40 18.3 19 743 768 1.60 1.40 20 21 819 848 14 0.70 0.30 1.80 18 20 607 613 0.80 1.40 19.1 20 821 847 1.60 1.40 21 22 899 929 16 0.70 0.30 2.00 20 21 696 703 0.80 1.40 20.0 21 902 929 1.60 1.40 22 23 1042 1079 19 0.70 0.30 2.00 21 22 799 807 0.80 1.40 21.0 22 1011 1040 1.60 1.40 23 24 1158 1196 24 0.70 0.30 2.00 24 26 990 1001 0.80 1.40 24.2 25 1238 1273 1.60 1.40 26 27 1409 1456 27 0.70 0.30 2.00 24 26 1087 1099 0.80 1.40 24.7 26 1333 1370 1.60 1.40 26 28 1506 1554 30 0.70 0.30 2.00 25 27 1188 1202 0.80 1.40 25.5 27 1439 1477 2.00 1.40 27 28 1617 1667 37 0.70 0.30 2.00 27 30 1424 1440 0.80 1.40 27.4 29 1684 1725 2.00 1.56 29 31 1928 1985 40 0.70 0.40 2.00 28 31 1528 1546 0.80 1.56 28.8 30 1823 1868 2.00 1.56 30 32 2048 2108 44 0.70 0.40 2.20 31 33 1732 1751 0.80 1.56 31.1 33 2026 2076 2.00 1.56 34 35 2454 2533 52 0.70 0.40 2.20 32 35 1994 2016 0.80 1.56 32.4 34 2285 2338 2.00 1.56 35 37 2728 2810 61 0.70 0.40 2.20 34 37 2294 2320 0.80 1.56 34.3 36 2588 2645 2.00 1.56 37 39 3055 3143
TECHNICAL DETAIL FOR V-MARC-1.1 KV
2.5 SQ MM COPPER COND. XLPE INSULATED, GALVANIZED STEEL WIRE/STRIP ARMOURED CONTROL CABLES
No of Cores
Minimum Thick. of
Inner Sheath
UNARMOURED(2XY) ARMOURING WITH FLATE STRIP(2XFY) ARMOURING WITH ROUND WIRES(2XWY)
Approx. Overall Dimeter (mm)
Approx Net Wt. of cable(Kg/Km)
Approx. Over all Diameter
Approx. Weight of cable in kg /Km
Approx. Over all Diameter
Approx. Weight of cable in kg /Km
Nominal Thickness
of Insulation
Cable Code: 2XY,2XFY,2XWY REF SPEC : IS : 7098 (PT-1) : 1988 PHYSICAL PARAMETERS
Nom. Thick. of
outer Sheath
Nominal Thickness of armour
Minimum Thickness of outer Sheath
Nominal Diameter of wire
Minimum Thickeness
of outer sheath.
(mm) (mm) (mm) Solid cond. Std. cond. Solid cond. Std. cond. (mm) (mm) Solid cond. Std. cond. Solid cond. Std. cond. (mm) (mm) Solid cond. Std. cond. Solid cond. Std. cond. 2 0.70 0.30 1.80 9.8 10.2 138 144 N/A N/A N/A N/A N/A N/A 1.40 1.24 12 12.2 275 288 3 0.70 0.30 1.80 10.2 10.7 153 158 N/A N/A N/A N/A N/A N/A 1.40 1.24 12 12.7 307 322 4 0.70 0.30 1.80 11.0 11.5 174 179 N/A N/A N/A N/A N/A N/A 1.40 1.24 13 13.5 349 365 5 0.70 0.30 1.80 11.8 12.3 198 204 N/A N/A N/A N/A N/A N/A 1.40 1.24 14 14.3 393 411 6 0.70 0.30 1.80 12.6 13.2 223 230 N/A N/A N/A N/A N/A N/A 1.40 1.24 15 15.2 438 458 7 0.70 0.30 1.80 12.6 13.2 241 248 N/A N/A N/A N/A N/A N/A 1.40 1.24 15 15.2 456 476
10 0.70 0.30 1.80 15.4 16.2 325 334 N/A N/A N/A N/A N/A N/A 1.40 1.24 17 18.2 602 629 12 0.70 0.30 1.80 15.8 16.7 366 375 N/A N/A N/A N/A N/A N/A 1.40 1.24 18 18.7 652 680 14 0.70 0.30 1.80 16.5 17.4 409 419 0.80 1.40 18 20 634 654 1.60 1.24 19 19.4 711 740 16 0.70 0.30 1.80 17.4 18.3 454 464 0.80 1.40 19 21 693 713 1.60 1.40 20 20.7 829 864 19 0.70 0.30 1.80 18.2 19.2 516 527 0.80 1.40 22 22 769 790 1.60 1.40 21 21.6 913 950 24 0.70 0.30 2.00 21.4 22.6 656 671 0.80 1.40 22 25 936 961 1.60 1.40 23 24.6 1105 1150 27 0.70 0.30 2.00 21.8 23.1 714 729 0.80 1.40 23 25 1001 1026 1.60 1.40 24 25.1 1174 1219 30 0.70 0.30 2.00 22.5 23.8 776 792 0.80 1.40 25 26 1074 1100 1.60 1.40 25 25.8 1254 1301 37 0.70 0.30 2.00 24.2 25.6 920 937 0.80 1.40 26 28 124 1272 1.60 1.40 26 27.6 1439 1491 40 0.70 0.30 2.00 25.1 26.6 985 1003 0.80 1.40 27 29 1323 1352 1.60 1.40 27 28.6 1526 1580 44 0.70 0.30 2.00 27.0 28.6 1078 1098 0.80 1.40 29 31 1447 1477 1.60 1.40 29 30.6 1666 1725 52 0.70 0.30 2.00 28.1 29.8 1234 1254 0.80 1.40 31 32 1620 1652 1.60 1.56 30 31.8 1850 1912 61 0.70 0.30 2.20 30.2 32.0 1441 1465 0.80 1.56 35 34 1827 1891 2.00 1.56 33 34.7 2250 2329
Approx. Weight of cable in kg /Km
Approx. Over all Diameter
TECHNICAL DETAIL FOR V-MARC-1.1 KV
1.5 SQ MM COPPER COND. XLPE INSULATED, GALVANIZED STEEL WIRE/STRIP ARMOURED CONTROL CABLES
No of Cores
ARMOURING WITH FLATE STRIP(2XFY) ARMOURING WITH ROUND WIRES(2XWY)
Approx. Weight of cable in kg /Km
Minimum Thick. of Inner Sh. Approx. Overall
Dimeter (mm) Approx Net Wt. of
cable(Kg/Km)
UNARMOURED(2XY)
Approx. Over all Diameter
Nominal Thickness
of Insulation
top related