TM 21614-LCAC

UNITED STATES NAVY 15 DECEMBER 2006

TECHNICAL MANUAL

OPERATOR’S, AND MANINTENANCE MANUAL

FOR

AIR CONDITIONER, HORIZONTAL COMPACT, 33,000 BTU/HR

208 VOLT, THREE PHASE, 400HERTZ,

PART NO. LCAC-33KH-1 NSN 4120-01-512-2399

TM 21614-LCAC

i

OPERATOR’S MAINTENANCE MANUAL

FOR

AIR CONDITIONER

HORIZONTAL, COMPACT, 33,000 BTU/HR, 208 VOLT, 3-PHASE

400 HERTZ

PART NO. LCAC-33KH-1 (NSN 4120-01-512-2399)

TABLE OF CONTENTS

WP Sequence No. CHAPTER 1 – INTRODUCTORY INFORMATION WITH THEORY OF OPERATION General Information ...........................................................................................................................................0001-00 Description and Data ..........................................................................................................................................0002-00 Theory of Operation with Operation Logic (Sequence of Operation) ................................................................0003-00 Supporting Data for Repair Parts, Special Tools, TMDE, and Support Equipment ...........................................0004-00 ------------------------------------------------------------------------------------------------------------------------------------------------ ------------------------------------------------------------------------------------------------------------------------------------------------ CHAPTER 2 – OPERATOR INSTRUCTIONS Air Conditioner Control and Indicators..............................................................................................................0005-00 Air Conditioner Operation Under Usual Conditions ..........................................................................................0006-00 ------------------------------------------------------------------------------------------------------------------------------------------------ ------------------------------------------------------------------------------------------------------------------------------------------------ CHAPTER 3 – OPERATOR TROUBLESHOOTING PROCEDURES Operator Troubleshooting Introduction..............................................................................................................0008-00 Operator Malfunction/Symptom Index...............................................................................................................0009-00 Operator Troubleshooting Procedures................................................................................................................0010-00 ------------------------------------------------------------------------------------------------------------------------------------------------ ------------------------------------------------------------------------------------------------------------------------------------------------ CHAPTER 4 – OPERATOR MAINTENANCE INSTRUCTIONS Operator Preventive Maintenance Checks and Services ....................................................................................0011-00 Operator Maintenance Instructions ....................................................................................................................0012-00 ------------------------------------------------------------------------------------------------------------------------------------------------ ------------------------------------------------------------------------------------------------------------------------------------------------ CHAPTER 5 – ORGANIZATIONAL MAINTENANCE TROUBLESHOOTING Organizational Troubleshooting Introduction ....................................................................................................0013-00 Organizational Troubleshooting .........................................................................................................................0014-00 ------------------------------------------------------------------------------------------------------------------------------------------------ ------------------------------------------------------------------------------------------------------------------------------------------------ CHAPTER 6 – ORGANIZATIONAL MAINTENANCE INSTRUCTIONS Organizational Maintenance Service Upon Receipt ...........................................................................................0015-00 Condenser Blower Assembly Organizational Maintenance ...............................................................................0030-00 Evaporator Blower Assembly Organizational Maintenance...............................................................................0031-00

TM 21614-LCAC

ii

TABLE OF CONTENTS - Continued

WP Sequence No.

CHAPTER 7 – FIELD MAINTENANCE TROUBLESHOOTING PROCEDURES Field Maintenance Troubleshooting Introduction .......................................................................... 0045 00 Field Maintenance Malfunction/System Index............................................................................... 0046 00 Field Maintenance Troubleshooting Procedures ............................................................................ 0047 00 ------------------------------------------------------------------------------------------------------------------------------------------------ ------------------------------------------------------------------------------------------------------------------------------------------------ CHAPTER 8 – FIELD MAINTENANCE PROCEDURES Refrigeration System Description................................................................................................... 0048 00 Refrigeration System Service - (Discharging)................................................................................ 0049 00 Refrigeration System Service - (Purging)....................................................................................... 0050 00 Refrigeration System Service - (Brazing/Debrazing) ..................................................................... 0051 00 Refrigeration System Service - (Leak Test) ................................................................................... 0052 00 Refrigeration System Service - (Evacuation) ................................................................................. 0053 00 Refrigeration System Service - (Charging) .................................................................................... 0054 00 Refrigeration System Service - (Pressure Testing)......................................................................... 0055 00 Work Instruction Procedure for Cabinet and All subassemblies Installation ................................. 0056 00 Brazing Work Instructions.............................................................................................................. 0057 00 Compressor Removal/Replacement Procedures ............................................................................. 0058 00 Cabinet, Condenser, Blower Motor Assembly, and Heater Assembly installation ........................ 0059 00 Compressor and Related Refrigeration Components Field Maintenance ....................................... 0076 00 ------------------------------------------------------------------------------------------------------------------------------------------------ ------------------------------------------------------------------------------------------------------------------------------------------------ CHAPTER 9 – ILLUSTRATED PARTS LIST Introduction .................................................................................................................................... 0077 00 AIR CONDITONER, 33K (Figure 1)............................................................................................. 0077 00 COMPRESSOR (Figure 2)............................................................................................................. 0077 00 EVAPORATOR COIL ASSEMBLY (Figure 3)............................................................................ 0077 00 CONDENSER COIL ASSEMBLY (Figure 4)............................................................................... 0077 00 FILTER DRYER ASSEMBLY (Figure 5) ..................................................................................... 0077 00 SIGHT GLASS ASSEMBLY (Figure 6)........................................................................................ 0077 00 PRESSURE RELIEF VALVE ASSEMBLY (Figure 7) ................................................................ 0077 00 HOT GAS VALVE ASSEMBLY (Figure 8) ................................................................................. 0077 00 HEATER ASSEMBLY (Figure 9) ................................................................................................. 0077 00 EVAPORATOR BLOWER ASSEMBLY (Figure 10) .................................................................. 0077 00 CONDENSER BLOWER ASSEMBLY (Figure 11) ..................................................................... 0077 00 CABINET, PANEL, AND COVER (Figure 12) ............................................................................ 0077 00 J3 WIRING ASSEMBLY (Figure 13)............................................................................................ 0077 00 LCAC UNIT WIRING (Figure 14) ................................................................................................ 0077 00 JUNCTION BOX ASSEMBLY (Figure 15) .................................................................................. 0077 00 J8 WIRING ASSEMBLY (Figure 16)............................................................................................ 0077 00 J1 WIRING ASSEMBLY (Figure 17)............................................................................................ 0077 00 J2 WIRING ASSEMBLY (Figure 18)............................................................................................ 0077 00 TRANSFORMER ASSEMBLY LCAC-TR-01A (Figure 19) ....................................................... 0077 00 RECTIFIER ASSEMBLY LCAC-RR-01A (Figure 20) ................................................................ 0077 00 PART NUMBER INDEX .............................................................................................................. 0078 00 REFERENCE DESIGNATOR INDEX.......................................................................................... 0079 00 ------------------------------------------------------------------------------------------------------------------------------------------------ ------------------------------------------------------------------------------------------------------------------------------------------------

TM 21614-LCAC

iii/iv blank

TABLE OF CONTENTS - Continued

WP Sequence No.

CHAPTER 10– SCHEMATIC AND WIRING Schematic Diagram......................................................................................................................... 0080 00 Wiring List...................................................................................................................................... 0081 00 ------------------------------------------------------------------------------------------------------------------------------------------------ ------------------------------------------------------------------------------------------------------------------------------------------------ CHAPTER 11– PARTS LIST Refrigerant Systems Parts List........................................................................................................ 0082 00 Electrical Systems Parts List .......................................................................................................... 0083 00 Mechanical Systems Parts List ....................................................................................................... 0084 00 Tools and Test Equipment Parts List.............................................................................................. 0085 00 Expendable and Durable Items List................................................................................................ 0086 00 ------------------------------------------------------------------------------------------------------------------------------------------------ ------------------------------------------------------------------------------------------------------------------------------------------------ CHAPTER 12– DRAWINGS AND PARTS INFORMATION PL1 Remote Control Panel ............................................................................................................. 00xx 00 PL2 Condenser Blower Assembly.................................................................................................. 00xx 00 PL3 Evaporator Blower Assembly ................................................................................................. 00xx 00 PL4 Refrigeration Components ...................................................................................................... 00xx 00 PL5 Compressor and Mounting...................................................................................................... 00xx 00 PL6 Air Compressor Structural Parts ............................................................................................. 00xx 00

TM 21614-LCAC

0001-00-1

AIR CONDITIONER, COMPACT, HORIZONTAL, 0001-00 GENERAL INFORMATION SCOPE a. Type of Manual: Operator, Organizational and Field Maintenance. b. Part Number and Equipment Names: LCAC-33KH-1 Air Conditioner, Compact, Horizontal, 33,000 BTU/HR, 208 Volt, Three Phase, 400 Hertz. c. Purpose of Equipment: The air conditioner is used primarily to provide filtered, cooled or heated air, as required to maintain the service conditions necessary for the efficient operation of electronic equipment. The air conditioner also provides for the comfort of operating personnel. DESTRUCTION OF ELECTRONICS MATERIAL Destruction of electronics material to prevent enemy use shall be in accordance with TM 750-244-2. CORROSION PREVENTION AND CONTROL (CPC) Corrosion Prevention and Control (CPC) of Navy material is a continuing concern. It is important that any corrosion problems with this item be reported so that the problem can be corrected and improvements can be made to prevent the problem in future items. While corrosion is typically associated with rusting of metals, it can also include deterioration of other materials, such as rubber and plastic. Unusual cracking, softening, swelling, or breaking of these materials may be a corrosion problem.

TM 21614-LCAC

0002-00-1

AIR CONDITIONER, COMPACT, HORIZONTAL, 0002-00 DESCRIPTION AND DATA EQUIPMENT CHARACTERISTICS, CAPABILITIES AND FEATURES The air conditioner provides filtered, cooled or heated air for the Landing Craft, Air Cushion (LCAC). The capabilities and features of the air conditioner are as follows: Single unit design. Light-weight, compact, horizontal. Floor-mounted and air-cooled. Electric motor driven and designed for continuous operation under varying loads. Furnishes 33,000 BTU/HR for cooling; 24,000 BTU/HR for heating. Two stage heating provided. Stage one (Low Heat) 9,500 BTU/HR, stage two (High Heat) an additional 14,500 BTU/HR for a total 24,000 BTU/HR. Handles for lifting. Provided with a separate remote control panel. Connection for remote environmental control switch (cool-vent-heat) on craft. LOCATION AND DESCRIPTION OF MAJOR COMPONENTS

COMPONENT DESCRIPTION 1. Condenser Guard 2. Condenser Filter 3. Evaporator Side Door 4. Charging Access Valves 5. Remote Control Panel 6. Liquid Sight Indicator 7. Input Power Connector (J1) 8. Condensate Drain Hose and Drain Cutouts 9. Mist Eliminator 10. Evaporator Blower 11. Condenser Blower 12. Compressor 13. Condenser Coil 14. Evaporator Coil.

Protects condenser from external damage Filter air flowing through condenser coil. Permits access for evaporator blower assembly maintenance. High and low pressure refrigerant charging access valves. Protects unit from electrical current overload. Contains six circuit breakers and a spare circuit breaker. Indicates condition and level of refrigerant. For connections to 208 volt, 400 Hz, three-phase power source, with ground. Allows discharge of condensate during operation. Drain hose located in bottom of unit, evaporator side. Drain cutouts on bottom of unit in front of condenser section Ensures against water blow-off. For evaporator coil during high humidity. Draws air into evaporator section and exhausts it through the evaporator (cooling) coil and heater elements. Draws ambient air through the condenser coil and discharges the heated air back to the outside during cooling operations. Cycles refrigerant through the system during cooling operations. Serves as a heat exchanger by transferring heat from the refrigerant passing through the tubing to the air passing over the tubing and fins. Services as a heat exchanger by transferring heat from the air passing over the tubing and fins to the refrigerant passing through the tubing.

TM 21614-LCAC

0002-00-3

AIR CONDITIONER, COMPACT, HORIZONTAL, 0002-00 DESCRIPTION AND DATA - Continued EQUIPMENT CHARACTERISTICS, CAPABILITIES AND FEATURES - Continued

TM 21614-LCAC

0002-00-4

AIR CONDITIONER, COMPACT, HORIZONTAL, 0002-00 DESCRIPTION AND DATA - Continued EQUIPMENT CHARACTERISTICS, CAPABILITIES AND FEATURES – Continued

TM 21614-LCAC

0002-00-6

AIR CONDITIONER, COMPACT, HORIZONTAL, 0002-00 DESCRIPTION AND DATA - Continued EQUIPMENT CHARACTERISTICS, CAPABILITIES AND FEATURES - Continued

LEGEND FOR CONTROL PANEL CB1 CIRCUIT BREAKER 30A – COMPRESSOR CB2 CIRCUIT BREAKER 15A – EVAPORATOR MOTOR CB3 CIRCUIT BREAKER 15A – CONDENSER MOTOR CB4 CIRCUIT BREAKER 20A – ELECTRIC HEATER CB5 CIRCUIT BREAKER 2A – CONTROL CIRCUIT PRIMARY CB6 CIRCUIT BREAKER 4A – CONTROL CIRCUIT SECONDARY CB7 CIRCUIT BREAKER 5A – SPARE FM FREQUENCY MONITOR RELAY J1 CONNECTOR – INPUT POWER – RECEPTACLE J2 CONNECTOR – INTERCONNECT CABLE – RECEPTACLE JB CONNECTOR – REMOTE CONTROL – RECEPTACLE K1 RELAY – COMPRESSOR MOTOR K2 RELAY – EVAPORATOR MOTOR K3 RELAY – CONDENSER MOTOR K4 RELAY – HEATER ELEMENTS – LOW K5 RELAY – HEATER ELEMENTS – HIGH PM PHASE MONITOR – 3 PHASE – 208V, 400 Hz POWER RR RECTIFIER – 28VDC SS SEQUENCER – EVAPORATOR AND COMPRESSOR MOTOR START TJ TIME DELAY RELAY – CONDENSER MOTOR START TR TRANSFORMER – 208V / 28V CONTROL POWER

TM 21614-LCAC

0002-00-7

AIR CONDITIONER, COMPACT, HORIZONTAL, 0002-00 DESCRIPTION AND DATA - Continued EQUIPMENT CHARACTERISTICS, CAPABILITIES AND FEATURES - Continued

CONNECTORS NO. PART NO. DESCRIPTION J1 75-190024-75p INPUT POWER (PINS) J2 CT2R36-9SC (CANNON) INTERCONNECT CABLE RECEPTACLE (SOCKET) P2 CT6M36-9PC (CANNON) INTERCONNECT CABLE PLUG (PINS) J3 CT2R36-9PC (CANNON) INTERCONNECT CABLE RECEPTACLE (PINS) P3 CT6M36-9SC (CANNON) INTERCONNECT CABLE PLUG (SOCKET) J8 MS3470L16-8S ENVIRONMENTAL CONTROL PANEL (SOCKET)

TM 21614-LCAC

0002-00-8

AIR CONDITIONER, COMPACT, HORIZONTAL, 0002-00 DESCRIPTION AND DATA - Continued EQUIPMENT CHARACTERISTICS, CAPABILITIES AND FEATURES - Continued

High Pressure Switch Location (Reference Pg. 0002-00-4)

Low Pressure Switch Location

TM 21614-LCAC

0003-00-1

AIR CONDITIONER, COMPACT, HORIZONTAL, 0003-00 THEORY OF OPERATION WITH OPERATON LOGIC (SEQUENCE OF OPERATION) TECHNICAL PRINCIPALS OF OPERATION Refrigeration Cycle – Cooling (Refer to Refrigerant Schematic, PG 0003-00-3) The refrigeration system removes heat from a given area. The refrigeration cycle is as follows: 1. The compressor (1) takes cold, low pressure refrigerant gas and compresses it to a high temperature, high pressure

gas. The gas flows through the copper tubing to the condenser coil (3). 2. The condenser fan draws outside ambient air over and through the condenser coil (3). The high temperature, high

pressure gas from the compressor (1) is cooled by the flow of air and is changed into a high pressure liquid. 3. The sight glass moisture indicator (7) indicates the presence of moisture and quantity of refrigerant in the system. 4. The filter-drier (6) removes any moisture (water vapor) or dirt that may be carried by the liquid refrigerant. 5. The expansion valve (4) senses the temperature and pressure of the refrigerant as it leaves the evaporator coil. By

use of the remote bulb and “external equalizer line” the valve constantly adjusts the flow of liquid refrigerant to the evaporator coil (2).

6. As the high pressure liquid refrigerant leaves the expansion valve (4) and refrigerant distributor (5), it enters the

evaporator coil (2) and “flashes” to a gas. This is due to the low pressure created in the evaporator by the compressor (1). The evaporator blower circulates the warm air, from the conditioned space, over and through the evaporator coil (2). Liquid refrigerant absorbs heat as it changes from a liquid to a gas. As the air flow from the conditioned space comes in contact with the evaporator coil (2) the air is cooled. If the air is cooled below its “dew point” moisture will condense on the evaporator coil (2) and be carried to the condensate drain. Thus providing both cooling and dehumidification.

7. The low pressure refrigerant gas is then drawn back to the compressor (1) and the cycle is repeated. 8. The hot gas by-pass valve (11) is used to maintain a minimum evaporator temperature by allowing some hot

discharge gas to flow to the evaporator coil (2) through the refrigerant distributor (5) when the evaporator pressure is low. This prevents freeze-up (ice formation) of the evaporator coil under low ambient temperature operation.

Heating When the MODE SELECTOR switch is set for HEAT, three (3) heating elements located behind the evaporator coil are energized. These elements are protected from overheating by a thermal cutout switch. The two (2) stage heating capacity is provided by switching the electrical connections of the three (3) heating elements. This is automatic by the control circuit. Compressor Starting Sequence (Refer to Wiring Schematic WP 0003-00-4) To limit the starting current (in rush) of the air conditioning unit an electronic sequencer (SS) is utilized to prevent any two (2) motors starting at the same time. This is applicable to the cooling cycle as follows: 1. On call for “cooling” by the control thermostat the sequencer (SS) opens the control circuit to the evaporator fan

motor (B2) contactor (K2) shutting off the evaporator motor (B2). 2. The sequencer (SS) then energizes the control circuit to the compressor contactor (K1) turning “ON” the compressor

motor (B1). 3. After 5 seconds the sequencer (SS) energizes the evaporator fan motor (B2) contactor (K2) turning “ON” the

evaporator motor (B2).

TM 21614-LCAC

0003-00-4

TM 21614-LCAC

0003-00-5

AIR CONDITIONER, COMPACT, HORIZONTAL, 0003-00 THEORY OF OPERATION WITH OPERATION LOGIC (SEQUENCE OF OPERATION) - Continued OPERATION LOGIC (SEQUENCE OF OPERATION) Operation The operation of the unit is controlled by a Navy-supplied remote control panel. This remote control panel consists of a thermostat and mode selector switch which interfaces with connector “J8” on the environmental control panel. The mode selector switch offers five modes of operation – cool, vent, off, lo heat and hi heat. The mode selector switch (and thermostat) switches 28VDC+ (pin A-J8) to the other various pins on J8 in accordance with the desired mode of operation. Input Power 208 volt, 3-phase, 400 Hz power is connected to environmental control panel through J1. The power is monitored for proper frequency by the FM (frequency monitor) relay. In the event of incorrect frequency, the normally closed (NC) contacts (2-1) open preventing power through the circuit breaker (CB5) to the control transformer (TR) primary and compressor crankcase heater (CH) thus preventing operation of the unit. The power is also monitored for proper voltage, voltage unbalance between phases, proper phasing, and phase loss by the phase monitor (PM). In the event of incorrect phase or voltage, the normally open (NO) contacts (4-5) remain open preventing control power (28 VDC+) to connector J8 and the evaporator and compressor start sequencer (SS), thus preventing operation of the unit. Circuit Protection (Over-current) The motor circuit are protected by circuit breaker CB1 (compressor motor B1), CB2 (evaporator fan motor B2) and CB3 (condenser fan motor B3). The electric heater (HR1, HR2 and HR3) circuit is protected by circuit breaker CB4. The control transformer primary (5-2) and the compressor crankcase heater (CH) are protected by CB5. The control transformer secondary (7-8) NS protected by CB6. The circuit breaker opens the electrical circuit in the event of over-current. Thermal Protection The motors are protected by thermal switches embedded in the motor windings S1 for the evaporator motor (B2), S2 for the compressor motor (B1) and S3 for the condenser motor (B3). The electric heater elements (HR1, HR2, and HR3) are protected from overheating by switch S6 which senses the air temperature at the heater. The switches open the 28VDC electrical circuits in the event of over temperature. Pressure Protection (High or Low Refrigerant Pressure) The refrigerant system is protected by pressure switches S4 low pressure and S5 high pressure. The low pressure switch functions to prevent the compressor operation with low or no pressure due to loss of refrigerant, etc. The high pressure switch functions to prevent compressor operation with high refrigerant pressure due to blocked condenser airflow, etc. Switch Circuit (S1, S2, S3, S4 and S5) The switches are circuited such that they only disable the mode of operation in which they are directly protecting. Switches S2, S3, S4 and S5 control the units function in only the “cool” mode, thus leaving the “vent” and “heat” modes operational. Switch S1 (evaporator motor), being necessary for operation in any mode, disable the total control circuit. Operation By Mode Selector Switch “Vent Mode” – with or without the remote panel thermostat satisfied. J8 pin “A” (28VDC+) is electrically connected J8 pin “C” by the mode selector switch. 28VDC+ power from rectifier RR flows through fan switch (NC) of evaporator and compressor motor start sequence (SS). Then to the evaporator motor contactor K2 coil terminal +A1 through coil out terminal –A2 to resistor R to contactor terminal 14 then to J2/P2 – P3/J3 pin “E”. Continuing to terminal board (TB)

TM 21614-LCAC

0003-00-6

AIR CONDITIONER, COMPACT, HORIZONTAL, 0003-00 THEORY OF OPERATION WITH OPERATION LOGIC (SEQUENCE OF OPERATION) - Continued OPERATION LOGIC (SEQUENCE OF OPERATION) - Continued terminal 8 through the evaporator motor (B2) thermal protector S1 and back through TB-7 and through J3/B3 – P2/J2 pin “C” to the -28VDC terminal of the rectifier RR. Thus energizing contactor K2 which supplies the 208 volt, 3-phase, 400Hz power to the evaporator motor B2. Cool Mode Without remote panel thermostat satisfied J8 pin “A” (28VDC+) electrically connected to J8 pin “B” and “C” by the mode selector switch. 28VDC+ power from rectifier RR flow to the evaporator motor (vent) circuit as above and also to “Y” of the evaporator and compressor motor start sequencer SS starting a one minute delay sequence. After one (1) minute the fan switch within the SS sequencer opens the circuit to contactor K2 shutting down the evaporator motor and completes the 28VDC+ circuit within the sequencer SS to the “Y-out” terminal. Then to contactor K1 coil terminal +A1 through coil out terminal –A2 to resistor R to contactor terminal 14 then to J2/P2 – P3/J3 pin “G” continuing to terminal board (TB) terminal 9 through the thermal protectors S2, S3 and refrigerant pressure switches S4, S5 and back through TB-8, thermal protector S1 to TB-7 and through J3/P3 – P2/J2 pin “C” to the -28VDC terminal of the rectifier RR. Thus energizing contactor K1 which supplies the 208 volt, 3-phase, 400 Hz power to the compressor motor B1. After approximately 5 seconds (allowing for compressor motor to come up to speed), the fan switch within sequencer SS recloses restoring the evaporator (vent) circuit. Y-out of sequencer SS also supplies +28VDC power to the condenser motor start time delay relay “TD” terminal 3. Limited power, not enough to energize the contactor, flows through the TD out terminal 1 to terminal +A1 of condenser motor contactor K3 coil and out terminal –A2 to resistor R to contactor term 14 then to J2/P2 pin “G” then as above to -28 VDC terminal of the rectifier RR. The limited power through the TD activates the time delay of approximately 12 seconds and then allows full power through the TD to energize the K3 contactor which supplies the 208 volts, 3-phase, 400 Hz to the condenser fan motor. This sequence of events reduces the overall inrush current by ensuring that no more than one motor starts at the same time and that the largest motor starts first. After the initial start-up of the unit, the one (1) minute delay of sequencer SS is eliminated if the compressor has been “off” for more than one minute. Pin “B” circuit is controlled by the thermostat. Heat Mode (-LO) Without the remote panel thermostat satisfied J8 pin “A” (28VDC+) is electrically connected to J8 pins “D” and “C” by the mode selector switch. 28VDC+ power from rectifier RR flows to evaporator motor (vent) circuit as above and also to the +A1 terminal of heater contactor K4 coil, through the coil and out terminal -0A2 to resistor R to contactor terminal 14 then to J2/P2 pin “F” then as above to -28VDC terminal of the rectifier RR thus energizing heater contactor K4 which supplies the 208V, 3-phase, 400 Hz power to the HR1 element of the electric heater. Pin “D” circuit is controlled by the thermostat. Heat Mode (-HI) Without remote panel thermostat satisfied J8 pin “A” (28VDC) is electrically connected to J8 pins “D”, “E”, and “C” by the mode selector switch. 28VDC+ power from the rectifier RR flow to evaporator motor (vent) circuit and the lo heat circuit as above and also to the +A1 terminal of heater contactor K5 coil through the coil and out terminal –A2 to resistor R to contactor terminal 14 then to J2/P2 pin “F” then as above to -28VDC terminal of the rectifier RR. Thus energizing heater contactor K5 which supplies the 208 volt, 3-phase, 400 Hz power the HR2 and HR3 elements of the electric heater. The pin “E” circuit is controlled by thermostat while the pin “D” circuit is “on” continuously.

TM 21614-LCAC SUPPORTING DATA FOR REPAIR PARTS, SPECIAL TOOLS, 0004-00 TMDE, AND SUPPORTING DATA

0004-00-1

COMMON TOOLS AND EQUIPMENT Refer to WP 0085 00 Table 1 for tools and equipment. SPECAIL TOOLS, TMDE, AND SUPPORT EQUIPMENT No special tools and test equipment are required. END OF TASK

TM 21614-LCAC

0005-00-2

DESCRIPTION AND USE OF CONTROLS AND INDICATORS - Continued 0005-00 OPERATOR’S CONTROLS - Continued 4. Circuit Breakers Protective circuit breakers are located on the side of the remote control panel for emergency power disconnect to the equipment. A spare circuit breaker is also available for use. The breakers have an external reset. The following are identification symbols and control and overload functions of each circuit breaker. CB1 – Compressor – 30 Amp CB2 – Evaporator Motor – 15 Amp CB3 – Condenser Motor – 15 Amp CB4 – Electric Heater – 20 Amp CB5 – Control Circuit – Primary – 2 Amp CB6 – Control Circuit – Secondary – 4 Amp CB7 – Spare – 5 Amp

CIRCUIT BREAKER LOCATION END OF TASK

TM 21614-LCAC

0010-00-2

OPERATOR TROUBLESHOOTING PROCEDURES - Continued 0010-00

Table 1. Troubleshooting Procedures - Continued

MALFUNCTION TEST OR INSPECTION CORRECTIVE ACTION 3. NO HEAT OR VERY LOW HEAT

1. Check to be sure that mode selector switch is properly positioned.

2. Make sure that temperature

selector switch (thermostat) is set correctly.

3. Check for sufficient air movement

over heaters by placing a piece o f paper in front of the evaporator air intake panel. The paper should be held against the panel by the air.

Set switch to LO HEAT or HI HEAT. Adjust setting to warmer. Remove any obstructions from evaporator air intake and discharge panel.

4. EXCESS CYCLING OF COMPRESSOR

Listen for excessive compressor turning on and off.

Clean evaporator and condenser filters. Check the refrigerant charge in sight glass.

END OF TASK

TM 21614-LCAC

0012-00-2

OPERATOR MAINTENANCE INSTRUCTIONS - Continued 0012-00

ADJUST Control Module

MODE SELECTOR SWITCH 1. Rotate the temperature selector switch (thermostat) to cooler or warmer while the air conditioner is being operated in

either the cool or heat mode in order to achieve the desired temperature in the conditioned area. 2. Rotate the mode selector switch to the vent, low heat, high heat or cool position. END OF TASK

TM 21614-LCAC

0030-00-2

CONDENSER BLOWER ASSEMBLY ORGANIZATIONAL MAINTENANCE - Continued 0030-00

Figure 30-1. Condenser Blower Assembly

END OF TASK

TM 21614-LCAC

0049-00-1

REFRIGERATION SYSTEM SERVICING – (DISCHARGING) 0049-00 THIS WORK PACKAGE COVERS: Service (Discharging) INITIAL SETUP: Maintenance Level Field Tools and Special Tools Tool Kit, General Mechanics (Item 1, Table 1, WP 0085-00) Tool Kit, Service, Refrigeration Unit (Item 2, Table 1, WP 0085-00) Recovery and Recycle Unit, Refrigerant (Item 5, Table 1, WP 0085 00) Mask, Air Filtering (Item 29, Table 1, WP 0086-00) Equipment Condition Mode selector switch in OFF position. Main power source disconnected. Panels removed. Air conditioner removed from installation, if necessary.

Special Environmental Condition

WARNING

In accordance with Environmental Protection Agency regulations, refrigerants cannot be discharged into the atmosphere. A refrigerant recovery unit must be used whenever discharging the refrigerant system. Operation of the recovery/recycling unit must be by AUTHORIZED PERSONNEL ONLY.

WARNING

Disconnect air conditioner power.

WARNING

Be sure that the manifold hoses are correctly connected. BLUE Hose = Low Pressure, RED Hose = High Pressure.

TM 21614-LCAC

0049-00-3

REFRIGERATION SYSTEM SERVICING – (DISCHARGING) - Continued 0049-00 SERVICE – DISCHARGING – Continued

END OF TASK

TM 21614-LCAC

0050-00-1

REFRIGERATION SYSTEM SERVICING – (PURGING) 0050-00 THIS WORK PACKAGE COVERS: Service (Purging) INITIAL SETUP: Maintenance Level Field Tools and Special Tools Tool Kit, General Mechanics (Item 1, Table 1, WP 0085-00) Tool Kit, Service, Refrigeration Unit (Item 2, Table 1, WP 0085-00) Recovery and Recycle Unit, Refrigerant (Item 5, Table 1, WP 0085 00) Mask, Air Filtering (Item 29, Table 1, WP 0086-00) Materials/Parts Nitrogen (Item 4, WP 0086 00) Equipment Condition Refrigerant system discharged (WP 0049 00). Main power source disconnected. Air conditioner removed from installation, if necessary.

WARNING

Disconnect air conditioner power supply.

WARNING

Be sure that the manifold hoses are correctly connected. BLUE Hose = Low Pressure, RED Hose = High Pressure.

WARNING

The refrigeration system must be purged with dray nitrogen, during any brazing operation performed on any component. A flow of dry nitrogen at the rate of less than 1 – 2 cfm (0.028-0.057 m3/ minute) should be continued during all brazing operations to minimize internal oxidation and scaling.

CAUTION

Nitrogen cylinders are pressurized cylinders. The pressure in the cylinder can exceed 2000 PSI. A nitrogen pressure regulator must be used at all times when nitrogen is used for leak check or purge operations.

TM 21614-LCAC

0050-00-3

REFRIGERATION SYSTEM SERVICING – (PURGING) - Continued 0050-00 SERVICE – PURGING – Continued

END OF TASK

TM 21614-LCAC

0051-00-1

REFRIGERATION SYSTEM SERVICING – (BRAZING/DEBRAZING) 0051-00 THIS WORK PACKAGE COVERS: Service (General Information, Filler Alloy, Debrazing, Cleaning Debrazed Joints, Reassembly, Brazing) INITIAL SETUP: Maintenance Level Field Tools and Special Tools Tool Kit, General Mechanics (WP 0085 00). Tool Kit, Service, Refrigeration Unit (Item 2, Table 1, WP 0085-00) Solder, Gun Kit (Item 9, Table 1, WP 0085-00) Mask, Air Filtering (Item 29, Table 1, WP 0086-00) Materials/Parts Brazing alloy (silver) Items 5 & 6, Table 1, WP 0086 00) Nitrogen (Item 4, Table 1, WP 0086-00) Brazing flux (Item 7, Table 1, WP 0086-00) Adhesive cloth (Item 8, Table 1, WP 0086-00) Rags (Item 9, Table 1, WP 0086-00) Equipment Condition Refrigerant system discharged (WP 0049 00). Refrigerant system purged (WP 0050 00). Main power source disconnected. Panels removed. Air conditioner removed from installation.

WARNING

Disconnect air conditioner power supply.

WARNING

Be sure that the manifold hoses are correctly connected. BLUE Hose = Low Pressure, RED Hose = High Pressure.

SERVICE General Information All tubing in the refrigeration system is copper with a finish that permits thorough cleaning. All interconnecting fittings, such as elbows, tees, etc., are also copper. The bodies of all valves and all connections on other components are brass. All joints, except those provide with threaded fitting, are made by brazing in accordance with MIL-B-7883, except that radiographic examination is not required.

TM 21614-LCAC

0052-00-1

REFRIGERATION SYSTEM SERVICING – (LEAK TEST) 0052-00 THIS WORK PACKAGE COVERS: Service (Leak Test) INITIAL SETUP: Maintenance Level Field Tools and Special Tools Tool Kit, General Mechanics (Item 1, Table 1, WP 0085-00) Tool Kit, Service, Refrigeration Unit (Item 2, Table 1, WP 0085-00) Mask, Air Filtering (Item 29, Table 1, WP 0086-00) Test Equipment Electronic refrigerant gas leak detector Materials/Parts Nitrogen (Item 4, Table 1, WP 0086-00) Refrigerant R-22 (Item 10, Table 1, WP 0086-00) References WP 0049-00 WP 0050-00 WP 0054-00 Equipment Condition Main power source disconnected. Panels removed. Air conditioner removed from installation, if necessary.

WARNING

Disconnect air conditioner power supply.

WARNING

Be sure that the manifold hoses are correctly connected. BLUE Hose = Low Pressure, RED Hose = High Pressure.

NOTE

After repair or replacement of refrigeration component, replace the filter-drier prior to leak testing.

TM 21614-LCAC

0052-00-2

REFRIGERATION SYSTEM SERVICING – (LEAK TEST) - Continued 0052-00 SERVICE – LEAK TEST General The entire repaired area should be thoroughly leak tested after repair or replacement of any component, before it is recharged with refrigerant-22. Leak testing is also the method for troubleshooting when a system has lost all or part of its refrigerant charge through an undetermined cause. Testing Method There are two acceptable methods for leak testing the refrigeration system. 1. Refrigerant gas leak detector. If an electronic refrigerant gas leak detector is available it should be used in

accordance with the procedures contained in the detector manufacturer’s instruction booklet.

NOTE

The electronic refrigerant gas leak detector is highly sensitive to the presence of a minute quantity of gas in the air. Due to this factor it is quite effective in the detection of a small leak. However, due to the rapid dispersion of refrigerant gas into the surrounding air, difficulty may be encountered in pinpointing large leaks. The detector must be used in a well-ventilated but draft-free area.

2. Soap solution. In this method, a strong solution of a liquid detergent and water is brushed onto all points of possible

leakage while closely watching for the formation of bubbles. Testing Procedure To perform leak testing by use of the electronic detector, it is necessary that the system be pressurized with a proportion of refrigerant gas. To perform leak testing by use of the soap solution method, the system may be pressurized with dry nitrogen alone. 1. To pressurize a system that has some refrigerant charge, for either leak testing method: a. Remove the hose connection protective caps from the high and low pressure service valves. b. Connect the hoses from a charging manifold to the service valves. c. Connect a nitrogen pressure regulator and nitrogen bottle to the center hose connection of the charging

manifold. d. Open the unit service valves and the charging manifold valves. e. Open the nitrogen tank valve and pressurize the system to 300 PSIG (21.2 kg/cm2). f. Perform leak tests.

TM 21614-LCAC

0053-00-1

REFRIGERATION SYSTEM SERVICING – (EVACUATION) 0053-00 THIS WORK PACKAGE COVERS: Service (Evacuation) INITIAL SETUP: Maintenance Level Field Tools and Special Tools Tool Kit, General Mechanics (Item 1, Table 1, WP 0085-00) Tool Kit, Service, Refrigeration Unit (Item 2, Table 1, WP 0085-00) Mask, Air Filtering (Item 29, Table 1, WP 0086-00) Test Equipment Vacuum Pump (Item 3, Table 1, WP 0085-00) Materials/Parts Nitrogen (Item 4, Table 1, WP 0086-00) References WP 0076-00 WP 0052-00 WP 0054-00 Equipment Condition Refrigerant system leak tested (WP 0052 00) Refrigerant system discharged (WP 0049 00) Main power source disconnected. Air conditioner removed from installation, if necessary.

WARNING

Disconnect air conditioner power supply.

WARNING

Be sure that the manifold hoses are correctly connected. BLUE Hose = Low Pressure, RED Hose = High Pressure.

CAUTION

Do not evacuate a leaking system. The vacuum created can cause air, moisture, and dirt to enter system.

NOTE

Replace filter-dryer whenever refrigerant system is opened.

TM 21614-LCAC

0053-00-3

REFRIGERATION SYSTEM SERVICING – (EVACUATION) - Continued 0053-00 SERVICE – EVACUATION – Continued

END OF TASK

TM 21614-LCAC

0054-00-1

REFRIGERATION SYSTEM SERVICING – (CHARGING) 0054-00 THIS WORK PACKAGE COVERS: Service (Charging) INITIAL SETUP: Maintenance Level Field Tools and Special Tools Tool Kit, General Mechanics (Item 1, Table 1, WP 0085-00) Tool Kit, Service, Refrigeration Unit (Item 2, Table 1, WP 0085-00) Mask, Air Filtering (Item 29, Table 1, WP 0086-00) Test Equipment Charging cylinder or scale Materials/Parts Refrigerant R-22 (Item 10, Table 1, WP 0086-00) Equipment Condition Refrigerant system evacuated (WP 0053 00) Main power source disconnected. Air conditioner removed from installation, if necessary.

WARNING

Disconnect air conditioner power supply.

WARNING

Be sure that the manifold hoses are correctly connected. BLUE Hose = Low Pressure, RED Hose = High Pressure.

CAUTION

Never introduce liquid refrigerant into the low pressure (suction) service valve.

NOTE

Install top cover before charging unit.

NOTE

After the system has been satisfactorily evacuated, it must be full charged with R-22

TM 21614-LCAC

0054-00-4

REFRIGERATION SYSTEM SERVICING – (CHARGING) - Continued 0054-00 SERVICE – CHARGING – Continued

END OF TASK

TM 21614-LCAC

0055-00-1

REFRIGERATION SYSTEM SERVICING – (PRESSURE TESTING) 0055-00 THIS WORK PACKAGE COVERS: Service (Pressure Testing) INITIAL SETUP: Maintenance Level Field Tools and Special Tools Tool Kit, General Mechanics (Item 1, Table 1, WP 0085-00) Tool Kit, Service, Refrigeration Unit (Item 2, Table 1, WP 0085-00) Mask, Air Filtering (Item 29, Table 1, WP 0086-00) Equipment Condition Main power source disconnected. Air conditioner removed from installation, if necessary. SERVICE – PRESSURE TESTING

WARNING

Disconnect air conditioner power supply.

WARNING

Be sure that the manifold hoses are correctly connected. BLUE Hose = Low Pressure, RED Hose = High Pressure.

Charging Valve Caps Remove caps from high and low pressure service valves. Refrigeration System Pressure Testing 1. Connect low pressure gauge hose of manifold valve to suction service valve.

2. Check that manifold valves are closed.

3. Connect high pressure hose of manifold valves to discharge service valve.

4. Purge hoses – open momentarily and close discharge and suction hose connections at charging manifold.

TM 21614-LCAC

0055-00-2

REFRIGERATION SYSTEM SERVICING – (PRESSURE TESTING) - Continued 0055-00 SERVICE – PRESSURE TESTING – Continued Refrigeration System Pressure Testing – Continued 5. Start air conditioner. With the unit operating, allow gauges to stabilize. Take reading of the two gauges. 6. Compare gauge readings with the normal range of system pressure as shown on the Table of Normal Temperature –

Pressure Relationships. 7. Disconnect gauges. 8. Install service valve protective caps.

Table 1. Normal Temperature – Pressure Relationships Pressure Range (PSIG) Temperatures Indoor

50°F Outdoor (10°C)

75°F Outdoor (24°C)

100°F Outdoor (38°C)

120°F Outdoor (52°C)

90°F (32°C) Air to Unit (Dry Bulb)

55-65 Suction 150-180 Discharge

66-76 Suction 200-240 Discharge

76-86 Suction 280-325 Discharge

95-100 Suction 390-428 Discharge

80°F (27°C) Air to Unit (Dry Bulb)

50-60 Suction 140-170 Discharge

61-71 Suction 190-230 Discharge

71-81 Suction 270-315 Discharge

80-90 Suction 360-410 Discharge

END OF TASK

TM 21614-LCAC 0056 00 LCAC 33K WORK INSTRUCTION PROCEDURE FOR

CABINET AND ALL SUBASSEMBLIES INSTALLATION

0056 00-1

INITIAL SETUP: Tools and Special Tools Tool Kit, General Mechanics (Item 1, Table 2, WP 0085 00) Tool Kit, Service, Refrigeration Unit (Item 2, WP 0085 00) Recovery and Recycle Unit, Refrigerant (Item 5, WP 0085 00) Mask, Air Filtering (Item 29, Table 1, WP 0086 00) Materials/Parts Nitrogen (Item 4, WP 0086 00) Brazing alloy (Item 5 or 6, Table 1, WP 0086 00) Brazing flux (Item 7, Table 1, WP0086 00) Personnel Required One Equipment Condition Mode selector switch in OFF position. Main power source is disconnected Top cover removed Refrigerant system discharged (WP 0049 00) Special Environmental Condition

NOTE

In accordance with Environmental Protection Agency regulations, refrigerants cannot be discharged into the atmosphere. A refrigerant recovery and recycling unit must be use whenever discharging the refrigerant system.

Operation of the recovery/recycling unit must be by AUTHORIZED PERSONNEL ONLY.

TM 21614-LCAC 0056 00 LCAC 33K WORK INSTRUCTION PROCEDURE FOR

CABINET AND ALL SUBASSEMBLIES INSTALLATION

0056 00-2

INSTALLATION

1. Using HVAC Silicone sealant, seal all joint and seams in cabinet. Using 3M 800 industrial sealant, cover the bottom of the cabinet and the blower deck. Place the compressor pan over the mounting studs. Insulate according to diagram.

2. Secure the compressor pan using 8-32 x 5/8 countersunk screws (4 ea) and 8-32 x 5/8 pan head screws (2 ea) with lockwashers.

3. Install the power input harness using 8-32 x ¾ pan head screws (4 ea) with lockwashers. Place 8-32 x 1” countersunk screws (3 ea) in appropriate places and nut off using 8-32 nylon insert lock nuts (3 ea). Using WCG12 clamps (2 ea), and WCG8 clamp (1 ea) and 8-32 locknuts (3 ea), clamp harness to the bulkhead.

4. Install terminal board using 8-32 x 1-5/8” countersunk screws (2 ea), 9-position marker strips (2 ea), and 8-32 locknuts (4 ea).

5. Wire terminal board according to diagram and wire labels.

6. Place compressor spacers and resilient mounts over compressor studs. Install compressor. Install grommets and upper resilient mounts. Cover with compressor washer and tie down with 3/8 x 16 locknuts (4 ea.)

7. Wire compressor, crankcase heater, low pressure switch (1 side) and overload “D” according to diagram and labels using parachutes (3 ea). Place fish paper insulation in compressor terminal box and spray with AC-46 moisture and fungus resistant varnish. Install compressor terminal box cover using vendor provided 6/32 pan head screw.

8. Place blower deck in cabinet in most “up” position.

9. Install compressor shield to compressor pan using 8-32 x 5/8 pan head screws (11 ea) with lockwashers and 8-32 x 5/8 countersunk screws (3 ea.)

10. Place evaporator and condenser blower motor assembly on work platform. Wire to terminal board according to diagram.

11. Install evaporator blower motor assembly in appropriate position.

12. Install blower deck in correct position using 8-32 x 5/8 countersunk screws (11 ea.) and 8-32 x 5/8 pan head screws (5 ea.) with lockwashers. Attach evaporator blower housing to blower deck using 8-32 x 5/8 pan head screws (15 ea.) with lockwashers and 8-32 x ¾” pan head screw (1 ea.) with lockwasher (upper right corner of L/H housing). Install valve mount brackets (2 ea.) using 8-32 x 5/8” pan head screws (4 ea.) Screw valve clamps (2 ea.) to bracket suing 10-32 x 1-3/4” pan head screws (2 ea.) with lockwashers (right bracket) and 10-32 x 1-1/2” pan head screws (2 ea.) with lockwashers (left bracket). Install 8-32 x 5/8” pan head screws (2 ea.) with lockwashers in H/P switch position.

13. Install WCG8 clamp using 8-32 x 5/8” pan head screw (1 ea.) with lockwasher, on evaporator motor assembly base, looping and clamping cable to be free of blower housing intake.

14. Install left and right drain hoses using worm clamps (4 ea.) and coiling correctly.

15. Lift unit and install ¼-28 x 1” countersunk screws (4 ea.) into bottom of cabinet and into evaporator motor assembly base, securing assembly.

16. Install condenser coil using 8-32 x ¾” pan head screws (8 ea.) with lockwashers.

17. Install blower mount using 8-32 x 5/8” countersunk screws (3 ea.)

TM 21614-LCAC 0056 00 LCAC 33K WORK INSTRUCTION PROCEDURE FOR

CABINET AND ALL SUBASSEMBLIES INSTALLATION

0056 00-3/4 blank

18. Install access port bracket using 8-32 x 5/8” pan head screws (2 ea.) with lockwashers and 8-32 x 5/8 countersunk screws (2 ea.)

19. Install discharge louver using 8-32 x 5/8” pan head screws (2 ea.) with lockwashers and 8-32 x 5/8 countersunk screws (2 ea.)

20. Install access panel mounting strips using 8-32 x 5/8” countersunk screws (20 ea.). Attach panel to mounting strips using 8-32 x 5/8” countersunk screws (18 ea.)

21. Perform brazing procedures on unit (WP 0057 00).

END OF WORK PACKAGE

TM 21614-LCAC 0057 00 BRAZING WORK INSTRUCTIONS

FOR LCAC-33K ECU

0057 00-1

INITIAL SETUP Tools and Special Tools Tool Kit, General Mechanics (Item 1, Table 2, WP 0085 00) Tool Kit, Service, Refrigeration Unit (Item 2, WP 0085 00) Recovery and Recycle Unit, Refrigerant (Item 5, WP 0067 00) Mask, Air Filtering (Item 29, Table 1, WP 0086 00) Materials/Parts Brazing alloy (silver) (Items 5 and 5, Table 1, WP 0086 00) Nitrogen cylinder (Item 4, Table 1, WP 0086 00) Brazing flux (Item 7, Table 1, WP 0086 00) Abrasive cloth (Item 8, Table 1, WP 0086 00) Rags (Item 9, Table 1, WP 0086 00) References WP 0051 00 (Brazing/Debrazing) Personnel Required One Equipment Condition Refrigeration system discharged (WP 0049 00) Refrigeration system purged (WP 0050 00) Main power source is disconnected

WARNING Ensure power source is disconnected.

INSTALLATION (Refer to WP 0051 00, Brazing/Debrazing) 1. Install high and low service ports (take out schraders first). 2. Install sight glass assembly and bracket with #8 x ¾” screw with 14E3416 flat washer and two caps w chains – long

3/8 pipe to top. 3. Put ¼ pipe from bottom of liquid line “T” to high side (bottom) access port. 4. Place liquid line (bottom of sight glass assembly) to condenser coil. 5. Install low pressure access line from suction line on compressor to access port. 6. Install pressure relief assembly condenser coil. Use WCG16 clamp to position countersunk 8-32 x 1” screws and

locknut 7. Install 8-32 x 1” countersunk screw (3 ea.) and nut off 8-32 x 1-1/4” (1 ea) for drier. 8. Install pressure regulator/HP switch assembly on brackets (do not tighten yet). “In” port goes to discharge “T” on

compressor. “Out” to distributor cap tube to suction line ½” in. 9. Install discharge line from top of compressor “T” to pressure relief subassembly through bulkhead split heyco

bushing and install around pipe at bulkhead.

TM 21614-LCAC 0057 00

0057 00-2

10. Install drier assembly through bulkhead to liquid line (sight glass top) and to position of tx valve. Arrow on drier should indicate flow to Tx valve.

11. Install WCG8 clamps in applicable places, WDG37 clamp for drier and nut off. 12. Begin to braze joints in the same sequence of installation. Make sure to use wet rags to prevent burn damage. 13. Install evaporator coil assembly and screw in with cad 8-32 x ¾, lock washer and flat washer (6 ea.) Install and

braze suction line to L/P switch assembly and to coil header and Tx equalizer line to L/P assembly. 14. Reinstall Schrader inserts and pressure check. END OF WORK PACKAGE

TM 21614-LCAC 0058 00

COMPRESSOR REMOVAL/INSTALLATION PROCEDURES

0058 00-1

INITIAL SETUP: Tools and Special Tools Tool Kit, General Mechanics (Item 1, Table 2, WP 0085 00) Tool Kit, Service, Refrigeration Unit (Item 2, WP 0085 00) Recovery and Recycle Unit, Refrigerant (Item 5, WP 0085 00) Mask, Air Filtering (Item 29, Table 1, WP 0086 00) Lifting Device Test Equipment Multimeter Materials/Parts Nitrogen (Item 4, WP 0086 00) Brazing alloy (Item 5 or 6, Table 1, WP 0086 00) Brazing flux (Item 7, Table 1, WP 0086 00) References WP 0049 00 thru WP 0055 00 Personnel Required Two Equipment Condition Mode selector switch in OFF position. Main power source is disconnected Top cover removed (WP 0056 00) Refrigerant system discharged (WP 0049 00) System purged with nitrogen (WP 0050 00) Related tube connections debrazed (WP 0051 00) Special Environmental Condition

NOTE

Unit contains R-22, a chemical substance which harms public health and the environment by destroying ozone in the upper atmosphere, and that the equipment is to be serviced by qualified personnel only.

Operation of the recovery/recycling unit must be by AUTHORIZED PERSONNEL ONLY.

REMOVAL 1. Reclaim refrigerant (remove schraders to be sure). 2. Remove heater assembly for ease of brazing. 3. Remove hot gas valve and H/P switch off unit as follows: a. Debraze at discharge “T” on compressor and distributor on evaporator coil. b. Remove two screws holding H/P switch. c. Remove four screws and two clamps holding HGBP.

TM 21614-LCAC 0058 00

COMPRESSOR REMOVAL/INSTALLATION PROCEDURES

0058 00-2

4. Remove clamp and spacer holding hot gas injection line. 5. Remove sensing bulb from suction line on compressor. 6. Remove five hex head ¼-28 screws and 8 8-32 pan head screws securing condenser motor. Lift condenser motor

free. 7. Debraze liquid line at thermostatic expansion valve inlet. 8. Debraze HGBP cap from suction line. 9. Remove clamp holding HGBP inlet line. 10. Remove suction line from upper “L” on compressor inlet. 11. Remove six screws holding evaporator coil. Remove coil. 12. Remove compressor access cover and dewier all leads. 13. Free L/P switch by cutting parachute from E. Free C/H by cutting parachutes. 14. Remove all screws in blower deck. 15. Remove evaporator mounting angles. 16. Remove clamp holding evaporator motor cable to base. 17. Lift blower deck. 18. Remove four mounting ¼-28 countersunk screws holding evaporator motor from bottom of unit. 19. Remove access panel. 20. Remove evaporator motor. 21. Remove compressor shield. 22. Life blower deck to highest point and remove. Unbolt compressor and remove. END OF WORK PACKAGE

TM 21614-LCAC 0059 00 LCAC-33K WORK INSTRUCTION

FOR CABINET, CONDENSER BLOWER/MOTOR ASSEMBLY AND HEATER ASSEMBLY INSTALLATION

0059 00-1/2 blank

INITIAL SETUP: Tools and Special Tools Tool Kit, General Mechanics (Item 1, Table 2, WP 0085 00) Materials/Parts Lint Free Cloth (Item 9, WP 0086 00) Dry Cleaning Solvent (Item 16, WP 0086 00) Test Equipment Multimeter References Wiring List and Schematic Diagram (WP 0080 00 and WP 0081 00) Personnel Required One Equipment Condition Air conditioner shut down and cool. Power disconnected form unit. Top cover removed (WP 0056 00). INSTALLATION 1. Secure low pressure access line to cabinet using two WCG4 clamps, two 8-32 x 2” countersunk screws, two 1-1/4”

spacers, and two 8-32 locknuts. 2. Install condenser blower motor assembly using five ¼-28 x ¾” hex cap screws, five ¼” lockwashers, and five #10

flat washers. Secure motor assembly cable using one 8-32 x 5/8 pan head screw with lockwasher and one WCG8 clamp.

3. Attach and secure blower assembly housings to blower mount using eight 8-32 x 5/8 pan head screws with

lockwashers. 4. Install and silicone two heyco caps in access holes in blower deck. 5. Install heater assembly using four 8-32 x 5/8 pan head screws with lockwashers and two 8-32 x 5/8 countersunk

screws. 6. Connect wiring according to wiring diagram (WP 0080 00). END OF WORK PACKAGE

TM 21614-LCAC

0076-00-1

COMPRESSOR AND RELATD REFRIGERATION COMPONENTS FIELD MAINETNENCE 0076-00 THIS WORK PACKAGE COVERS: Removal, Decontamination, and Installation INITIAL SETUP: Maintenance Level Field Tools and Special Tools Tool Kit, General Mechanics (Item 1, Table 1, WP 0085-00) Tool Kit, Service, Refrigeration Unit (Item 2, Table 1, WP 0085-00) Recovery and Recycle Unit, Refrigerant (Item 5, Table 1, WP 0085 00) Lifting Device Mask, Air Filtering (Item 29, Table 1, WP 0086-00) Personnel Required Two people needed for compressor removal and installation. Equipment Condition Mode selector switch in OFF position. Main power source disconnected. Top Panel, evaporator side door, and evaporator filter removed. System refrigerant discharged (WP 0049 00). Evaporator and condenser blower assemblies removed. Heater coil assembly removed. Test Equipment Multimeter Materials/Parts Brazing alloy (silver) Items 5 & 6, Table 1, WP 0086 00) Nitrogen (Item 4, Table 1, WP 0086-00) Brazing flux (Item 7, Table 1, WP 0086-00)

Special Environmental Condition

NOTE

In accordance with Environmental Protection Agency regulations, refrigerants cannot be discharged into the atmosphere. A refrigerant recovery unit must be used whenever discharging the refrigerant system. Operation of the recovery/recycling unit must be by AUTHORIZED PERSONNEL ONLY.

TM 21614-LCAC

CHAPTER 9

ILLLUSTRATED PARTS LIST

TM 21614-LCAC 0077 00

0077 00-1

PARTS LIST This chapter provides the Illustrated Parts List (IPL) for the LCAC-33KH-1 Air Conditioner. It identifies the parts necessary for equipment support. Illustrations provide aid in identifying parts for requisitioning. PARTS LIST COLUMNS Fig. and Item No. (Column 1). Item numbers are assigned to each part in order to determine an exact location for each part. Item numbers that are not illustrated are listed with a dash (-) preceding the item number. NSN (Column 2). This column provides the National Stock Number (NSN) for parts with a NSN assigned. CAGE (Column 3). This column lists the Manufacturer Commercial and Government Entity (CAGE) for the applicable part number. Part Number (Column 4). This column provides the manufacturer’s part number for each part in the listing. Parts to which no part numbers have been assigned are designated “NO NUMBER” in the part number column. Description (Column 5). The item description is assigned according to the nomenclature placed in the drawing title block by the design activity. The noun name is listed, followed by modifiers and descriptive information to completely identify the part. a. Indentation. Parts listed are indented to show Next Higher Assembly (NHA) relationship. To determine the NHA of a part or assembly, note the column in which the first word of the description appears. b. Cross Reference Notes. Various figure cross reference notes appear throughout the parts list. They show NHA figure/detail figure relationship and provide configuration continuity. For example: (SEE FIGURE_____ FOR NHA) – Indicates where the installation or assembly is listed under its NHA. (SEE FIGURE ____ FOR DETAILS) – Indicates where the installation or assembly is broken down to its

component parts. Qty (Column 6). This column lists the number of units required per assembly or subassembly.

TM 21614-LCAC 0077 00

0077 00-2

Figure 1. Air Conditioner, 33K (Sheet 1 of 3)

TM 21614-LCAC 0077 00

0077 00-3

Figure 1. Air Conditioner, 33K (Sheet 2 of 3)

TM 21614-LCAC 0077 00

0077 00-4

Figure 1. Air Conditioner, 33K (Sheet 1 of 3)

TM 21614-LCAC 0077 00

0077 00-5

(1) FIG/

ITEM NO.

(2) NSN

(3) CAGEC

(4) PART NUMBER

(5) DESCRIPTION

(6) QTY

1 4120-01-512-2399 0V5R4 LCAC-33KH-1 AIR CONDITIONER, .....................

HORIZONTAL, COMPACT, 33KH, 208V, 3 PH, 400 HZ

REF

1 0V5R4 LCAC-MIL-Z-40-VAC-420

. COMPRESSOR, WELCO .............. MIL-Z-40-VAC-420 (SEE

FIGURE 2 FOR DETAILS)

1

2 0V5R4 LCAC-105025800 . COIL, EVAPORATOR (WITH ........DISTRIBUTER) HEATCRAFT 105025800 (SEE FIGURE 3 FOR DETAILS)

1

3 80205 MS51957-46 . SCREW, #8-32 x 5/8, PAN HD ...... 6 4 80205 MS35338-137 . WASHER, LOCK, #8...................... 6 5 0V5R4 LCAC-105025200 . COIL, CONDENSER (WITH ..........

DISTRIBUTER) HEATCRAFT 105025200 (SEE FIGURE 4 FOR DETAILS)

1

6 80205 MS51957-46 . SCREW, #8-32 x 5/8, PAN HD ...... 8 7 80205 MS35338-137 . WASHER, LOCK, #8...................... 8 8 0V5R4 LCAC-RIVE-3-GA-

RPB . VALVE, EXPANSION,....................

THERMAL (SPORLAN RIVE-3-GA-RPB)

1

9 0V5R4 LCAC-FD-01A . FILTER-DRYER ASSEMBLY.........(SEE FIGURE 5 FOR DETAILS)

1

10 81343 AS21919WDG34 . CLAMP, UMPCO WDG34.............. 1 11 80205 MS24693C54 . SCREW, #8-32 x 1, FLAT HD,.......

100 DEGREES CSK 1

12 0CTE3 8-32 . NUT, NYLON INSERT (A-JAX)...... 1 13 0V5R4 LCAC-SG-01A . SIGHT GLASS ASSEMBLY...........

(SEE FIGURE 6 FOR DETAILS)

1

14 80205 MS24693C54 . SCREW, #8-32 x 1, FLAT ..............HD, 100 DEGREES CSK

1

15 80205 MS35338-137 . WASHER, LOCK, #8...................... 1 16 0V5R4 LCAC-SK33K-23 . BRACKET, SIGHT GLASS ............ 1 17 0V5R4 LCAC-DRAIN HOSE . DRAIN HOSE WITH TRAP ............

(TRAP FORMED BY COILING DRAIN HOSE) ¾” OD -1/8” WALL BRAIDED REINFORCEMENT VINYL, WATTS BRAND

2

18 0V5R4 LCAC-DRAIN CLAMP . CLAMP, HOSE, DRAIN LINE, .......9/16 – 1-1/16

4

19 0V5R4 LCAC-SK33K-72 . CONDENSER DRAIN .................... 2 20 0V5R4 LCAC-PR-01A . PRESSUR RELIEF VALVE............

ASSEMBLY (SEE FIGURE 7 FOR DETAILS)

1

21 0V5R4 LCAC-HG-01A . HOT GAS VALVE...........................ASSEMBLY (SEE FIGURE 8 FOR DETAILS)

1

22 0V5R4 LCAC-S9500-E9949 . BRACKET, HGBP VALVE ............. 2

TM 21614-LCAC 0077 00

0077 00-6

(1) FIG/

ITEM NO.

(2) NSN

(3) CAGEC

(4) PART NUMBER

(5) DESCRIPTION

(6) QTY

23 80205 MS51958-70 . SCREW, #10-32 x 1-3/4, ................PAN HD

4

24 80205 #10

. WASHER, LOCK, #10 (AJAX)........ 4

25 0V5R4 LCAC-CD3604 WITH CD3688

. VALVE, LOW SIDE SERVICE........(SCHRAEDER C&D VALVE MFG. CO. CD3604 WITH CD3688)

1

26 0V5R4 LCAC-CD3604 WITH CD3688

. VALVE, LOW SIDE SERVICE........(SCHRAEDER C&D VALVE MFG. CO. CD3604 WITH CD3688)

1

27 0V5R4 LCAC-97039332 . FILTER, MIST ELIMINATOR..........(RESEARCH PRODUCTS -97039332)

1

28 0V5R4 LCAC-97038676

. AIR FILTER, CONDENSER ...........(RESEARCH PRODUCTS -97039332)

1

29 0V5R4 LCAC-SK33K-80 . GUARD, CONDENSER.................. 1 30 0V5R4 LCAC-HR-01A . HEATER ASSEMBLY (SEE ...........

FIGURE 9 FOR DETAILS) 1

31 80205 MS51957-46 . SCREW, #8-32 x 5/8, PAN HD...... 4 32 80205 MS24693C51 . SCREW, #8-32 x 5/8, FLAT...........

HD, 100 DEGREES CSK 2

33 80205 MS35338-137 . WASHER, LOCK, #8 ..................... 6 34 0V5R4 LCAC-SK33K-24 . LOUVERS, CONDENSER.............

AIR DISCHARGE 1

35 80205 MS51957-46 . SCREW, #8-32 x 5/8, PAN HD...... 4 36 80205 MS24693C51 . SCREW, #8-32 x 5/8, FLAT...........

HD, 100 DEGREES CSK 2

37 80205 MS35338-137 . WASHER, LOCK, #8 ..................... 6 38 0V5R4 LCAC-P20EB-2 . SWITCH, HIGH PRESSURE,........

S5 (JOHNSON CONTROLS P20EB-2) (PART OF HOT GAS VALVE ASSEMBLY, SEE FIGURE 8)

1

39 0V5R4 LCAC-ILPS-424-010E025E

. SWITCH, LOW PRESSURE,.........S4 (INTERTECH ILPS-424-010E025E)

1

40 0V5R4 LCAC-COPPER STRAP-LPS

. CLAMP, LP SWITCH,....................COPPER STRAP, 3/8”W x 6”L x .030 THK

1

41 80205 MS24693C54 . SCREW, #8-32 x 1, FLAT..............HD, 100 DEGREES CSK

1

42 0CTE3 8-32 . NUT, NYLON INSERT (A-JAX) ..... 1 43 0V5R4 LCAC-SK33K-101 . SHIELD, COMPRESSOR.............. 1 44 80205 MS51957-46 . SCREW, #8-32 x 5/8, PAN HD...... 12 45 80205 MS24693C51 . SCREW, #8-32 x 5/8, ....................

FLAT HD, 100 DEGREES CSK

7

TM 21614-LCAC 0077 00

0077 00-7

(1) FIG/

ITEM NO.

(2) NSN

(3) CAGEC

(4) PART NUMBER

(5) DESCRIPTION

(6) QTY

46 0V5R4 LCAC-EB-01A . EVAPORATOR BLOWER.............ASSEMBLY (SEE FIGURE 10 FOR DETAILS)

1

47 0V5R4 LCAC-CB-01A . CONDENSER BLOWER...............ASSEMBLY (SEE FIGURE 11 FOR DETAILS)

1

48 0V5R4 . CABINET AND COVERS (SEE FIGURE 12 FOR DETAILS) ......

1

49 0V5R4 LCAC-J3-01A . J3 WIRING ASSEMBLY (SEE FIGURE 13 FOR DETAILS) ....................

1

50 0V5R4 . LCAC UNIT WIRING (SEE ...................... FIGURE 14 FOR DETAILS)

1

51 0CTE3 #10-32 . EXTERNAL GROUND SCREW, (A-JAX) ......................................

1

52 0V5R4 S9160-JBA-3 . JUNCTION BOX ..........................ASSEMBLY (SEE FIGURE 15 FOR NHA)

1

END OF FIGURE

TM 21614-LCAC 0077 00

0077 00-8

Figure 2. Compressor (1) ITEM NO.

(2) NSN

(3) CAGEC

(4) PART NUMBER

(5) DESCRIPTION AND USABLE ON CODE (UOC)

(6) QTY

2

1 0V5R4 LCAC-MIL-Z-40-VAC-420

. COMPRESSOR, Welco .................. MIL-Z-40-VAC-420 (SEE

FIGURE 1 FOR NHA)

REF

2 0V5R4 LCAC-S9500-3/8-16LK

. NUT, 3/8-16 ..................................... 4

3 0V5R4 LCAC-MS27183-14

. WASHER, FLAT, MS27183-14 (96906)..........................................

4

4 0V5R4 LCAC-S9500-8165-3

. GROMMET S9500-8165-3 (0V5R4)................

4

5 5342-01-042-5759 0V5R4 LCAC- 13216E6137

. MOUNT, RESILIENT, WEA 13216E6137 (97403) ...................

4

6 0V5R4 LCAC-S9500-8165-1

. SPACER, S9500-8165-1(0V5R4)..................

4

7 0V5R4 LCAC-S9500-8165-2

. SPACER, RUBBER S9500-8165-2 (0V5R4).................

4

END OF FIGURE

TM 21614-LCAC 0077 00

0077 00-9

Figure 3. Evaporator Coil Assembly

(1) FIG/

ITEM NO.

(2) NSN

(3) CAGEC

(4) PART NUMBER

(5) DESCRIPTION

(7) QTY

3 0V5R4 LCAC-EP-01A EVAPORATOR COIL (SEE

FIGURE 1 FOR NHA) REF

1 0V5R4 SK33K-TB-001 . SENSING CAPILLARY 1 2 0V5R4 LCAC-RIVE-3-GA-

RPB . EXPANSION VALVE, THERMAL

IVE-3-GA-RPB 3 x 5 (70255) .....1

3 0V5R4 LCAC-105025800 . EVAPORATOR COIL 105025800 (Heatcraft)................

1

4 0V5R4 SK33K-TE-3020 . TUBE, 3/8” O.D................................ 1 END OF FIGURE

TM 21614-LCAC 0077 00

0077 00-10

Figure 4. Condenser Coil Assembly

(1) FIG/

ITEM NO.

(2) NSN

(3) CAGEC

(4) PART NUMBER

(5) DESCRIPTION

(7) QTY

4 0V5R4 LCAC-CD-01A CONDENSER COIL ASSEMBLY (SEE

FIGURE 1 FOR NHA) REF

1 0V5R4 LCAC-W02716 . ELBOW, 3/8, 90 DEGREE, LONG RADIUS W02716 (41947) .......................

1

2 0V5R4 LCAC-105025200 . CONDENSER COIL 105025200 (Heatcraft) ...............

1

3 0V5R4 SK33K-TS-3146 . TUBE, 3/8” O.D. .............................. 1 4 0V5R4 LCAC-W02312 . ELBOW, 3/8, 90 DEGREE, ST.

W02312 (41947) ....................... 1

END OF FIGURE

TM 21614-LCAC 0077 00

0077 00-11

Figure 5. Filter-Dryer Assembly

(1) FIG/

ITEM NO.

(2) NSN

(3) CAGEC

(4) PART NUMBER

(5) DESCRIPTION

(7) QTY

5 0V5R4 LCAC-FD-01A FILTER-DRYER ASSEMBLY

(SEE FIGURE 1 FOR NHA) REF

1 0V5R4 LCAC-C-053-S . FILTER-DRYER............................... 1 2 0V5R4 SK33K-TB-008 . TUBE, 3/8” O.D. (INLET) ................. 1 3 0V5R4 SK33K-TB-009 . TUBE, 3/8” O.D. (OUTLET) ............. 1

END OF FIGURE

TM 21614-LCAC 0077 00

0077 00-12

Figure 6. Sight Glass Assembly

TM 21614-LCAC 0077 00

0077 00-13

(1)

ITEM NO.

(2) NSN

(3) CAGEC

(4) PART NUMBER

(5) DESCRIPTION

(7) QTY

6 0V5R4 LCAC-SG-01A SIGHT GLASS ASSEMBLY (SEE

FIGURE 1 FOR NHA) REF

1 0V5R4 LCAC-HI-ITT3 . SIGHT GLASS – MOISTURE INDICATOR................................

1

2 0V5R4 LCAC-W02312 . ELBOW, 90 DEGREE, ST. W02312 (41947).........................

2

3 0V5R4 SK33K-TS-3056 . TUBE, 3/8” O.D................................ 1 4 0V5R4 LCAC-W40324 . TEE, 3/8 x 3/8 x ¼

W40324 (41947).........................1

5 0V5R4 SK33K-TS-3022 . TUBE, 3/8” O.D................................ 1 END OF FIGURE

TM 21614-LCAC 0077 00

0077 00-14

Figure 7. Pressure Relief Valve Assembly

TM 21614-LCAC 0077 00

0077 00-15

(1) ITEM

NO.

(2) NSN

(3) CAGEC

(4) PART NUMBER

(5) DESCRIPTION

(7) QTY

7 0V5R4 LCAC-PR-01A PRESSURE RELIEF VALVE

ASSEMBLY (SEE FIGURE 1 FOR NHA)

REF

1 0V5R4 LCAC-5120T1-2M-650 . VALVE, PRESSURE RELIEF 5120T1-2M-650 (FREEMAN)

1

2 0V5R4 SK33K-TB-003 . TUBE, 1/2 O.D................................. 1 3 0V5R4 LCAC-W40350 . TEE, 1/2 x 1/2 x ¼

W40350 (41947).........................2

4 0V5R4 SK33K-TB-004 . TUBE, ¼ O.D................................... 1 5 0V5R4 LCAC-W01206 . ADAPTER, ¼ NPT x 1/4

W01206 (41947).........................1

END OF FIGURE

TM 21614-LCAC 0077 00

0077 00-16

Figure 8. Hot Gas Valve Assembly

TM 21614-LCAC 0077 00

0077 00-17

(1) ITE

M NO.

(2) NSN

(3) CAGEC

(4) PART NUMBER

(5) DESCRIPTION

(7) QTY

8 0V5R4 LCAC-HG-01A HOT GAS VALVE ASSEMBLY (SEE

FIGURE 1 FOR NHA) REF

1 0V5R4 LCAC-ADRSE-2-0/80 . HOT GAS BY-PASS VALVE SPORLAN ADRSE-2-0/80.................

1

2 0V5R4 SK33K-TB-006 . TUBE, 3/8” O.D, OUTLET. .............. 1 3 0V5R4 SK33K-TB-005 . TUBE, 3/8” O.D., INLET .................. 1 4 0V5R4 SK33K-TB-007 . SENSING CAPILLARYTUBE, 0.125” O.D. 1 5 0V5R4 LCAC-P20EB-2 . HIGH PRESSURE SWITCH, S5 ..................... 1

END OF FIGURE

TM 21614-LCAC 0077 00

0077 00-18

Figure 9. Heater Assembly

TM 21614-LCAC 0077 00

0077 00-19

Wire No.

Labels From To

Wire Size

AWG

Wire Color

Type of End to End Connection

Length Of

Wire RD-1 HR1 HR2 14 RED #10 RING

PN10-10R FLAG

DNFR14-250B

4

RD-2 S6 HR2 14 RED #10 RING PN10-10R

FLAG DNFR14-

250B

17

BE-3 HR2 HR3 14 BLUE #10 RING PN10-10R

FLAG DNFR14-

250B

4

BE-4 S6 HR3 14 BLUE #10 RING PN10-10R

FLAG DNFR14-

250B

11

(1)

FIG/ ITEM

NO.

(2) NSN

(3) CAGEC

(4) PART NUMBER

(5) DESCRIPTION

(7) QTY

9 0V5R4 LCAC-HR-01A HEATER ASSEMBLY........................ 1

1 0V5R4 LCAC-2010 WAR . HEATER (HR), 208VAC, 3 PH, 6.6KW ..............................

1

2 0V5R4 SK33K-47 . BRACKET........................................ 2 3 0V5R4 LCAC-2201 . BUSHING......................................... 2 4 0V5R4 SK33K-98 . BRACKET........................................ 2 5 0V5R4 SK33K-49 . BRACKET, HEATER LIMIT

SWITCH 2

6 0V5R4 LCAC-S2049062212 . SWITCH, THERMAL, ELECTRIC HEATER, S6............

1

7 81349 M5086/2-14-2 . WIRE, ELECTRICAL, RED.............. AR 8 81349 M5086/2-14-6 . WIRE, ELECTRICAL, BLUE............ AR 9 06383 PN10-10R . TERMINAL, LUG, BARREL.............

#10 RING AR

10 06383 DNF18-250FIB . SPADE, QUICK DISCONNECT, FEMALE, INSULATED

AR

11 0V5R4 LCAC-CMB007 . CONNECTOR.................................. 1 END OF FIGURE

TM 21614-LCAC 0077 00

0077 00-20

Figure 10. Evaporator Fan Assembly

TM 21614-LCAC 0077 00

0077 00-21

(1) ITEM NO.

(2) NSN

(3) CAGEC

(4) PART NUMBER

(5) DESCRIPTION AND USABLE ON CODE (UOC)

(6) QTY

10 0V5R4 LCAC-EB-01A EVAPORATOR BLOWER

ASSEMBLY (SEE FIGURE 1 FOR NHA)................................

REF

1 80205 MS51958-83 . SCREW, MACHINE, ¼-28-1, FLAT HD, 100 DEGREES CSK, PHILLIPS DR...................

4

2 0V5R4 LCAC-SK33K-16 . BLOWER MOUNT, EVAPORATOR

1

3 80205 MS51957-46 . SCREW, #8-32 x 5/8, PAN HD, PHILLIPS DR

8

4 0V5R4 LCAC-SK33K-21 . SCROLL, EVAPORATOR FAN HOUSING

2

5 80205 MS51957-46 . SCREW, #8-32 x 5/8, PAN HD, PHILLIPS DR

8

6 0V5R4 LCAC-S9500-3543

. RING, INLET 4

7 0V5R4 LCAC-304-0430-000

. FAN, BLOWER WHEEL EVAPORATOR, PLUNKER 304-0430-000

1

8 96906 MS18065-20 . SETSCREW, ¼” x 3/8” NC, CUP POINT

2

9 0V5R4 LCAC-CI-030486 . MOTOR, EVAPORATOR, 3300 RPM, 208V, 400 HZ, WELCO TECHNOLOGIES CI-030486

1

10 0V5R4 LCAC-304-0428-000

. FAN, BLOWER WHEEL EVAPORATOR, PLUNKER 304-0428-000

1

11 96906 MS18065-20 . SETSCREW, ¼” x 3/8” NC, CUP POINT

2

12 80205 MS35308-334 . SCREW, 5/16-24 x 1, HEX HD 4 13 0CTE3 #5/16 . WASHER, FLAT (AJAX) 4 14 0CTE3 #5/16 x 24 . INSERT, NYLON (AJAX) 4

END OF FIGURE

TM 21614-LCAC 0077 00

0077 00-22

Figure 11. Condenser Blower Assembly

TM 21614-LCAC 0077 00

0077 00-23

(1) ITEM NO.

(2) NSN

(3) CAGEC

(4) PART NUMBER

(5) DESCRIPTION AND USABLE ON CODE (UOC)

(6) QTY

11 0V5R4 LCAC-CB-01A CONDENSER BLOWER

ASSEMBLY (SEE FIGURE 1 FOR NHA) ................................................

REF

1 80205 MS51957-46 . SCREW, #8-32 x 5/8, PAN HD, PHILLIPS DR ............................

8

2 0V5R4 LCAC-SK33K-7 . SCROLL, CONDENSER BLOWER HOUSING ................

2

3 80205 MS35308-306 . SCREW, ¼-28 x ¾, HEX HD 4 4 0V5R4 LCAC-SK33K-8 . PLATE,BLOWER

MOUNTING,CONDENSER.......1

5 MS35308-306 . SCREW, ¼-28 x ¾, HEX HD 2 6 0V5R4 LCAC-SK33K-22 . MOTOR MOUNT 1 7 80205 MS51957-46 . SCREW, #8-32 x 5/8, PAN HD,

PHILLIPS DR ............................16

8 0V5R4 LCAC-S9500-3543

. RING, INLET.................................. 4

9 0V5R4 LCAC-CI-030487 . MOTOR, CONDENSER, WELCO TECHNOLOGIES CI-030487 .....................................

1

10 0V5R4 LCAC-304-0437-000

. FAN, BLOWER WHEEL CONDENSER, PLUNKER 304-0437-000............................

2

11 96906 MS18065-20 . SETSCREW, ¼” x 3/8” NC, CUP POINT-ALLEN HD, 1/8 ............

4

12 80205 MS24693C298 . SCREW, ¼-28 x 1, FLAT HD, 100 DEGREES CSK, PHILLIPS DR............................

4

13 80205 MS35308-334 . SCREW, 5/16-24 x 1, HEX HD...... 4 14 0CTE3 #5/16 . WASHER, FLAT (AJAX)................ 4 15 0CTE3 #5/16 x 24 . INSERT, NYLON (AJAX)............... 4 16 OV5R4 SK33K-6 REFRIGERANT SCHEMATIC......... 1

END OF FIGURE

TM 21614-LCAC 0077 00

0077 00-24

Figure 12. Cabinet and Covers

TM 21614-LCAC 0077 00

0077 00-25

(1)

FIG/ ITEM

NO.

(2) NSN

(3) CAGEC

(4) PART NUMBER

(5) DESCRIPTION

(7) QTY

12 CABINET AND COVERS,

(SEE FIGURE 1 FOR NHA) REF

1 0V5R4 SK33K-1 CABINET ASSEMBLY, 33K 1 2 0V5R4 SK33K-5 . COVER, TOP 1 3 80205 MS24693C51 . SCREW, #8-32 x 5/8, PHIL..............

HD, 100 DEGREES CSK 24

4 0V5R4 SK33K-70 . ACCESS PANEL ASSEMBLY 1 5 80205 MS24693C51 . SCREW, #8-32 x 5/8, PHIL..............

HD, 100 DEGREES CSK 18

6 0V5R4 SK33K-11 . BLOWER DECK, EVAPORATOR 1 7 80205 MS24693C51 . SCREW, #8-32 x 5/8, PHIL..............

HD, 100 DEGREES CSK 11

8 80205 MS51957-46 . SCREW, #8-32 x 5/8, PAN HD ........ 5 9 80205 MS35338-137 . WASHER, LOCK, #8........................ 16

10 ASTM-C534TP2 . INSULATION, THERMAL MAKE ..... FROM INSULATION, P/N ASTM-C534TP2, .75THK

AR

END OF FIGURE

TM 21614-LCAC 0077 00

0077 00-26

Figure 13. J3 Wiring Assembly

TM 21614-LCAC 0077 00

0077 00-27

(1) FIG/

ITEM NO.

(2) NSN

(3) CAGEC

(4) PART NUMBER

(5) DESCRIPTION

(7) QTY

13 0V5R4 LCAC-J3-01A J3 WIRING ASSEMBLY REF

1 81349 M5086/2-12-5 . WIRE, ELECTRICAL, GREEN ........ AR 2 81349 M5086/2-10-0 . WIRE, ELECTRICAL, BLACK ......... AR 3 81349 M5086/2-10-2 . WIRE, ELECTRICAL,RED............... AR 4 81349 M5086/2-10-6 . WIRE, ELECTRICAL, BLUE............ AR 5 81349 M5086/2-14-0 . WIRE, ELECTRICAL, BLACK ......... AR 6 81349 M5086/2-14-2 . WIRE, ELECTRICAL,RED............... AR 7 81349 M5086/2-14-6 . WIRE, ELECTRICAL, BLUE............ AR 8 81349 M5086/2-18-0 . WIRE, ELECTRICAL, BLACK ......... AR 9 81349 M5086/2-18-6 . WIRE, ELECTRICAL, BLUE............ AR

10 81349 M5086/2-18-0 . WIRE, ELECTRICAL, BLACK ......... AR 11 06383 PN10-10R . TERMINAL, LUG, BARREL.............

#10 RING AR

12 06383 DNFR18-250FIB . TERMINAL, LUG WIRE NO. ........... 22-18, RED, FLAG PUSH-ON (fits spade terminal)

AR

13 06383 DNF18-250FIB . SPADE, QUICK DISCONNECT, FEMALE, INSULATED

AR

14 0V5R4 LCAC-CMB006 . CONNECTOR, J3............................ 1 END OF FIGURE

Labels From To

Wire Size

AWG Wire Color

Type of End to End Connection

Length Of

Wire

Remarks

J3-0 B1-T1 10 BLACK STRIPPED END FLAG DNFR14-

250B

18 J3

J3-P B1-T2 10 RED STRIPPED END FLAG DNFR14-

250B

18

J3-R B1-T3 10 BLUE STRIPPED END FLAG DNFR14-

250B

18

J3-U TB-1 14 BLACK STRIPPED END #10 RING PN10-10R

32

J3-Y TB-2 14 RED STRIPPED END #10 RING PN10-10R

32

J3-X TB-3 14 BLUE STRIPPED END #10 RING PN10-10R

32

J3-N TB-4 14 BLACK STRIPPED END #10 RING PN10-10R

33

J3-W TB-5 14 RED STRIPPED END #10 RING PN10-10R

33

J3-V TB-6 14 BLUE STRIPPED END #10 RING PN10-10R

33

J3-I HR1 14 BLACK STRIPPED END FLAG DNFR14-

250B

44

TM 21614-LCAC 0077 00

0077 00-28

Labels From To

Wire Size

AWG Wire Color

Type of End to End Connection

Length Of

Wire

Remarks

J3-H S6 14 RED STRIPPED END #10 RING PN10-10R

35

J3-L S6 14 BLUE STRIPPED END #10 RING PN10-10R

34

J3-T HR3 14 BLACK STRIPPED END FLAG DNFR14-

250B

33

J3-A CH 20 BLUE STRIPPED END STRIPPED END

20

J3-B CH 20 BLACK STRIPPED END STRIPPED END

20

J3-C TB-7 20 BLACK STRIPPED END #10 RING PN10-10R

35

J3-F TB-8 20 BLUE STRIPPED END #10 RING PN10-10R

35

J3-G TB-9 20 BLACK STRIPPED END #10 RING PN10-10R

35

J3-S E3 (GRD) 12 GREEN STRIPPED END #10 RING PN10-10R

22

TM 21614-LCAC 0077 00

0077 00-29

Figure 14. LCAC Unit Wiring

TM 21614-LCAC 0077 00

0077 00-30

Table 1. Unit Wiring

Labels From To

Wire Size

AWG Wire Color

Type of End to End Connection

Length Of

Wire

Remarks

J3-0 B1-T1 10 BLACK STRIPPED END FLAG DNFR14-

250B

18 J3

J3-P B1-T2 10 RED STRIPPED END FLAG DNFR14-

250B

18

J3-R B1-T3 10 BLUE STRIPPED END FLAG DNFR14-

250B

18

J3-U TB-1 14 BLACK STRIPPED END #10 RING PN10-10R

32

J3-Y TB-2 14 RED STRIPPED END #10 RING PN10-10R

32

J3-X TB-3 14 BLUE STRIPPED END #10 RING PN10-10R

32

J3-N TB-4 14 BLACK STRIPPED END #10 RING PN10-10R

33

J3-W TB-5 14 RED STRIPPED END #10 RING PN10-10R

33

J3-V TB-6 14 BLUE STRIPPED END #10 RING PN10-10R

33

J3-I HR1 14 BLACK STRIPPED END FLAG DNFR14-

250B

44

J3-H S6 14 RED STRIPPED END #10 RING PN10-10R

35

J3-L S6 14 BLUE STRIPPED END #10 RING PN10-10R

34

J3-T HR3 14 BLACK STRIPPED END FLAG DNFR14-

250B

33

S6 HR2 14 RED #10 RING

PN10-10R FLAG

DNFR14-250B

17 HR

S6 HR3 14 BLUE #10 RING PN10-10R

FLAG DNFR14-

250B

11

HR1 HR2 14 RED #10 RING PN10-10R

FLAG DNFR14-

250B

4

HR2 HR3 14 BLUE #10 RING PN10-10R

FLAG DNFR14-

250B

4

J3-A CH 20 BLUE STRIPPED END STRIPPED

END 20 J3

J3-B CH 20 BLACK STRIPPED END STRIPPED END

20

TM 21614-LCAC 0077 00

0077 00-31

Labels From To

Wire Size

AWG Wire Color

Type of End to End Connection

Length Of

Wire

Remarks

J3-C TB-7 20 BLACK STRIPPED END #10 RING PN10-10R

35

J3-F TB-8 20 BLUE STRIPPED END #10 RING PN10-10R

35

J3-G TB-9 20 BLACK STRIPPED END #10 RING PN10-10R

35

TB-9 S2-D 20 BLACK #10 RING

PN10-10R FLAG

DNFR14-250B

35

S2 S4 20 BLACK FLAG DNFR14-250B

#10 RING PN10-10R

4.5

J3-S E3 (GRD) 12 GREEN STRIPPED END #10 RING PN10-10R

22

J1-A CB1-LINE 10 BLACK STRIPPED END #10 RING PN10-10R

12

J1-B CB1-LINE 10 RED STRIPPED END #10 RING PN10-10R

12

J1-C CB1-LINE 10 BLUE STRIPPED END #10 RING PN10-10R

12

J1-E E1 (GRD) 10 GREEN STRIPPED END #10 RING PN10-10R

10

CB-1 LINE CB2-LINE 12 BLACK #10 RING PN10-10R

#10 RING PN10-10R

5

CB-1 LINE CB2-LINE 12 RED #10 RING PN10-10R

#10 RING PN10-10R

5

CB-1 LINE CB2-LINE 12 BLUE #10 RING PN10-10R

#10 RING PN10-10R

5

CB-2 LINE CB3-LINE 12 BLACK #10 RING PN10-10R

#10 RING PN10-10R

5

CB-2 LINE CB3-LINE 12 RED #10 RING PN10-10R

#10 RING PN10-10R

5

CB-2 LINE CB3-LINE 12 BLUE #10 RING PN10-10R

#10 RING PN10-10R

5

CB-3 LINE CB4-LINE 12 BLACK #10 RING PN10-10R

#10 RING PN10-10R

5

CB-3 LINE CB4-LINE 12 RED #10 RING PN10-10R

#10 RING PN10-10R

5

CB-3 LINE CB4-LINE 12 BLUE #10 RING PN10-10R

#10 RING PN10-10R

5

CB-1 LOAD K1-5 12 BLACK #10 RING PN10-10R

STRIPPED END

6

CB-1 LOAD K1-3 12 RED #10 RING PN10-10R

STRIPPED END

6

CB-1 LOAD K1-1 12 BLUE #10 RING PN10-10R

STRIPPED END

6

CB-2 LOAD K2-5 12 BLACK #10 RING PN10-10R

STRIPPED END

6

CB-2 LOAD K2-3 12 BLACK #10 RING PN10-10R

STRIPPED END

6

CB-2 LOAD K2-1 12 BLUE #10 RING PN10-10R

STRIPPED END

6

TM 21614-LCAC 0077 00

0077 00-32

Labels From To

Wire Size

AWG Wire Color

Type of End to End Connection

Length Of

Wire

Remarks

CB-3 LOAD K3-5 12 BLACK #10 RING PN10-10R

STRIPPED END

6

CB-3 LOAD K3-3 12 RED #10 RING PN10-10R

STRIPPED END

6

CB-3 LOAD K3-1 12 BLUE #10 RING PN10-10R

STRIPPED END

6

CB-4 LOAD K4-5 12 BLACK #10 RING PN10-10R

STRIPPED END

6

CB-4 LOAD K4-3 12 RED #10 RING PN10-10R

STRIPPED END

6

CB-4 LOAD K5-1 12 BLUE #10 RING PN10-10R

STRIPPED END

6

K4-5 K5-5 12 BLACK STRIPPED END STRIPPED END

3.5

K1-6 J2-0 10 BLACK STRIPPED END STRIPPED END

7

K1-4 J2-P 10 RED STRIPPED END STRIPPED END

7

K1-2 J2-R 10 BLUE STRIPPED END STRIPPED END

7

K2-6 J2-U 14 BLACK STRIPPED END STRIPPED END

8

K2-4 J2-Y 14 RED STRIPPED END STRIPPED END

8

K2-2 J2-X 14 BLUE STRIPPED END STRIPPED END

8

K3-6 J2-N 14 BLACK STRIPPED END STRIPPED END

9

K3-4 J2-W 14 RED STRIPPED END STRIPPED END

9

K3-2 J2-V 14 BLUE STRIPPED END STRIPPED END

9

K4-6 J2-I 14 BLACK STRIPPED END STRIPPED END

10

K4-4 J2-H 14 RED STRIPPED END STRIPPED END

10

K5-2 J2-L 14 BLUE STRIPPED END STRIPPED END

11

K5-6 J2-T 14 BLACK STRIPPED END STRIPPED END

11

J8-A SS+ 20 RED STRIPPED END SPADE DNF18-250F1B

17

J8-B SS-Y 20 YELLOW STRIPPED END #10 RING PN10-10R

19

J8-C SS-FAN 20 BLUE STRIPPED END SPADE DNF18-250F1B

20

J8-D K4-+A1 20 RED STRIPPED END STRIPPED END

14

J8-E K5-+A1 20 BLACK STRIPPED END STRIPPED END

15

TM 21614-LCAC 0077 00

0077 00-33

Labels From To

Wire Size

AWG Wire Color

Type of End to End Connection

Length Of

Wire

Remarks

J8-G E1(GRD) 20 GREEN STRIPPED END #10 RING PN10-10R

11

J2-C RR- 20 BLACK STRIPPED END SPADE DNF18-250F1B

6

J2-F K4-14 20 BLUE STRIPPED END STRIPPED END

11

J2-G K3-14 20 BLACK STRIPPED END STRIPPED END

8

J2-B CB5 LOAD 20 BLACK STRIPPED END #10 RING PN10-10R

20

J2-A FM-5 20 BLUE STRIPPED END SPADE DNF18-250F1B

22

K1-14 K3-14 20 BLACK STRIPPED END STRIPPED END

8

K5-14 K2-14 20 BLUE STRIPPED END STRIPPED END

10

K2-14 K4-14 20 BLUE STRIPPED END STRIPPED END

8

SS-Y-OUT K1-+A1 20 YELLOW PIGGY DNFR18-250B

STRIPPED END

18.5

SS-Y-FAN K2-+A1 20 BLUE SPADE DNF18-250F1B

STRIPPED END

17

SS-Y-OUT TD-3 20 YELLOW SPADE DNF18-250F1B

SPADE DNF18-250F1B

6.5

TD-1 K3-+A1 20 RED SPADE DNF18-250F1B

STRIPPED END

18

SS-+ PM-5 20 RED PIGGY DNFR18-250B

STRIPPED END

6

SS-+ K3-14 20 BLACK SPADE DNF18-250F1B

STRIPPED END

9

FM-1 CB5 LINE 20 BLAC SPADE DNF18-250F1B

STRIPPED END

2.5

CB5 LOAD TR-5 20 BLACK RING PN18-10R

STRIPPED END

18

PM-4 RR-+ 20 RED STRIPPED END SPADE DNF18-250F1B

13

CB6 LINE TR-7 20 BLUE RING PN18-10R

STRIPPED END

20

CB6 LOAD RR 20 BLUE RING PN18-10R

SPADE DNF18-250F1B

20

TM 21614-LCAC 0077 00

0077 00-34

Labels From To

Wire Size

AWG Wire Color

Type of End to End Connection

Length Of

Wire

Remarks

TR-8 RR 20 BLUE STRIPPED END SPADE DNF18-250F1B

7.5

FM-5 CB4 LINE 20 BLUE SPADE DNF18-250F1B

RING PN18-10R

5

FM-2 CB4 LINE 20 BLACK SPADE DNF18-250F1B

RING PN18-10R

5

PM-L3 CB2 LINE 20 BLUE STRIPPED END STRIPPED END

13

PM-L2 CB2 LINE 20 RED STRIPPED END STRIPPED END

13

PM-L1 CB2 LINE 20 BLACK STRIPPED END STRIPPED END

13

J2-S E1 (GND) 12 GREEN STRIPPED END

RING PN18-10R

11

TR-2 CB4 LINE 20 RED STRIPPED END

RING PN18-10R

13

TR-3 TR-5 20 BLACK STRIPPED END

STRIPPED END

2

(1) ITEM NO.

(2) NSN

(3) CAGEC

(4) PART NUMBER

(5) DESCRIPTION AND USABLE ON CODE (UOC)

(6) QTY

14 UNIT WIRING AND BULK

MATERIALS REF

1 81349 ZZ-T-831 . TUBE, PLASTIC, 0.500 I.D............ X 0.750 O.D., CLEAR, TYPE VIII, CLASS 8, CUT TO LENGTH

AR

2 81327 6-1-5853-11 . TUBE, METALLIC.......................... .250 OD, CUT TO LENGTH

AR

3 39428 5174K5 . TUBE, METALLIC.......................... .375 OD, CUT TO LENGTH

AR

4 39428 5174K6 . TUBE, METALLIC.......................... .500 OD, CUT TO LENGTH

AR

5 39428 5174K12 . TUBE, METALLIC.......................... .875 OD, CUT TO LENGTH

AR

6 81349 M5086/2-10-0 . WIRE, ELECTRICAL, BLACK ....... AR 7 81349 M5086/2-10-2 . WIRE, ELECTRICAL, RED............ AR 8 81349 M5086/2-10-6 . WIRE, ELECTRICAL, BLUE.......... AR 9 81349 M5086/2-10-5 . WIRE, ELECTRICAL, GREEN ...... AR

10 81349 M5086/2-10-3 . WIRE, ELECTRICAL, ORANGE.... AR 11 81349 M5086/2-10-9 . WIRE, ELECTRICAL, WHITE........ AR 12 81349 M5086/2-12-0 . WIRE, ELECTRICAL, BLACK ....... AR 13 81349 M5086/2-12-2 . WIRE, ELECTRICAL, RED............ AR 14 81349 M5086/2-12-6 . WIRE, ELECTRICAL, BLUE.......... AR 15 81349 M5086/2-12-5 . WIRE, ELECTRICAL, GREEN ...... AR

TM 21614-LCAC 0077 00

0077 00-35

(1) ITEM NO.

(2) NSN

(3) CAGEC

(4) PART NUMBER

(5) DESCRIPTION AND USABLE ON CODE (UOC)

(6) QTY

16 81349 M5086/2-12-3 . WIRE, ELECTRICAL, ORANGE .... AR 17 81349 M5086/2-12-9 . WIRE, ELECTRICAL, WHITE ........ AR 18 81349 M5086/2-14-0 . WIRE, ELECTRICAL, BLACK........ AR 19 81349 M5086/2-14-2 . WIRE, ELECTRICAL, RED ............ AR 20 81349 M5086/2-14-6 . WIRE, ELECTRICAL, BLUE .......... AR 21 81349 M5086/2-14-5 . WIRE, ELECTRICAL, GREEN....... AR 22 81349 M5086/2-14-3 . WIRE, ELECTRICAL, ORANGE .... AR 23 81349 M5086/2-20-0 . WIRE, ELECTRICAL, BLACK........ AR 24 81349 M5086/2-20-2 . WIRE, ELECTRICAL, RED ............ AR 25 81349 M5086/2-20-6 . WIRE, ELECTRICAL, BLUE .......... AR 26 81349 M5086/2-20-4 . WIRE, ELECTRICAL,YELLOW...... AR 27 81349 M5086/2-20-5 . WIRE, ELECTRICAL, GREEN....... AR 28 81349 M5086/2-20-3 . WIRE, ELECTRICAL, ORANGE .... AR 29 81349 M5086/2-20-9 . WIRE, ELECTRICAL, WHITE ........ AR 30 81349 M5086/2-12-9 . WIRE, ELECTRICAL, WHITE ........ AR 31 81343 MS25036-112 . TERMINAL, LUG, BARREL ...........

NON-INSULATED, #10 RING

AR

32 81343 MS25036-103 . TERMINAL, LUG, BARREL ........... NON-INSULATED, RING

AR

33 06383 DNF10-250FIB . SPADE, QUICK DISCONNECT, FEMALE, INSULATED

AR

34 06383 DV18-250P .TERMINAL, LUG, PIGGY, ............. QUICK DISCONNECT,

AR

35 06383 DNFR18-250FIB . TERMINAL, LUG WIRE NO........... 22-18, RED, FLAG PUSH-ON (fits spade terminal)

AR

END OF FIGURE

TM 21614-LCAC 0077 00

0077 00-36

Figure 15. Junction Box Assembly

TM 21614-LCAC 0077 00

0077 00-37

(1) ITEM NO.

(2) NSN

(3) CAGEC

(4) PART NUMBER

(5) DESCRIPTION AND USABLE ON CODE (UOC)

(6) QTY

15 0V5R4 S9160-JBA-3 . JUNCTION BOX ...............................

ASSEMBLY (SEE FIGURE 1 FOR NHA)

REF

1 0V5R4 LCAC-JA3S-NS-0030-02E

. CIRCUIT BREAKER, CB1, ............... COMPRESSOR, 3 POLE, 400HZ, 30

AMPS, EATON HEINEMANN JA3S-NS-0030-02E

1

2 0V5R4 LCAC-JA3S-NS-0030-02E

. CIRCUIT BREAKER, CB2 ................ EVAPORATOR MOTOR, 3 POLE,

400HZ, 30 AMPS, EATON HEINEMANN JA3S-NS-0030-02E

1

3 0V5R4 LCAC-JA3S-N3-0015-02E

. CIRCUIT BREAKER, CB3 ................. CONDENSER MOTOR, 3 POLE, 400

HZ, 15 AMPS, EATON HEINEMANN JA3S-N3-0015-02E

1

4 0V5R4 LCAC-JA3S-N3-0015-02E

. CIRCUIT BREAKER, CB4, ELECTRIC........................................

HEATER, 3 POLE, 400HZ, 20 AMPS, EATON HEINEMANN JA3S-N3-0020-02E

1

5 0V5R4 LCAC-W31-X2M1G-2 . CIRCUIT BREAKER,CB5, CONTROL CIRCUIT, PRIMARY, 2 AMPS,

POTTER & BRUMFIELD W31-X2M1G-2

1

6 0V5R4 LCAC-W31-X2M1G-4 . CIRCUIT BREAKER,CB6,CONTROL CIRCUIT, SECONDARY, 4 AMPS,

POTTER & BRUMFIELD W31-X2M1G-4

1

7 0V5R4 LCAC-38-T067-F4583 . FREQUENCY MONITOR RELAY, FM (START RELAY) PRODUCTS

UNLIMITED 38-T067-F4583

1

8 0V5R4 LCAC-J1-01A . J1 WIRING ASSEMBLY (SEE .......... FIGURE 17 FOR DETAILS)

1

9 0V5R4 LCAC-J2-01A . J2 WIRING ASSEMBLY (SEE .......... FIGURE 18 FOR DETAILS)

1

10 0V5R4 LCAC-J8-01A . J8 WIRING ASSEMBLY (SEE .......... FIGURE 16 FOR DETAILS)

1

11 0V5R4 LCAC-LC1D32BD . RELAY, K1,COMPRESSOR MOTOR, SCHNEIDER ELECTRIC LC1D32BD

1

12 0V5R4 LCAC-LC1D32BD . RELAY, K2, EVAPORATOR MOTOR, SCHNEIDER ELECTRIC LC1D32BD

1

13 0V5R4 LCAC-LC1D32BD . RELAY, K3, CONDENSER MOTOR,. SCHNEIDER ELECTRIC LC1D32BD

1

14 0V5R4 LCAC-LC1D32BD . RELAY, K4, ELECTRIC HEATER, LOW,............

SCHNEIDER ELECTRIC LC1D32BD

1

15 0V5R4 LCAC-LC1D32BD . RELAY, K5, ELECTRIC HEATER, HIGH,...........

SCHNEIDER ELECTRIC LC1D32BD

1

16 0V5R4 LCAC-460-400Hz . PHASE MONITOR , PM, 3 PHASE – 208V, 400HZ POWER, SYMCOM

460-400HZ

1

17 0V5R4 LCAC-RR-01A . RECTIFIER ASSEMBLY (SEE ......... FIGURE 20 FOR DETAILS)

1

18 0V5R4 LCAC-0388-004TD . SEQUENCER,SS, EVAPORATOR.... AND COMPRESSOR MOTOR

START, 1CM-AM1712

1

TM 21614-LCAC 0077 00

0077 00-38

THIS PAGE INTENTIONALLY LEFT BLANK

TM 21614-LCAC 0077 00

0077 00-39

(1) ITEM NO.

(2) NSN

(3) CAGEC

(4) PART NUMBER

(5) DESCRIPTION AND USABLE ON CODE (UOC)

(6) QTY

19 0V5R4 LCAC-1CM-1CM103 . TIME DELAY RELAY, TD,– .............. CONDENSER MOTOR START,

1CM-1CM103

1

20 0V5R4 LCAC-TR-01A . TRANSFORMER ASSEMBLY (SEE . FIGURE 19 FOR DETAILS)

1

21 0V5R4 LCAC-W31-X2M1G-5 . CIRCUIT BREAKER, (SPARE) 5 AMPS, ...........................................

POTTER & BRUMFIELD W31-X2M1G-5

1

22 0V5R4 LCAC-SK33K-30 . CONTROL BOX................................. 1 23 0V5R4 LCAC-SK33K-31 . COVER, CONTROL BOX .................. 1 24 0V5R4 LCAC-SK33K-4 . WIRING SCHEMATIC........................ 1 25 0V5R4 LCAC-SK33K-RCP ID

PLATE . IDENTIFICATION PLATE .................. 1

26 0V5R4 LCAC-13218E6961 . CAPACITOR, (C1).056uf @ 400V, .... ARMY 13218E6961 (97403)

1

27 0V5R4 LCAC-95C1369 . CAPACITOR, (C2) 100uf @ 63v, MFG. #2222-138-38101, NEWARK-IN-ONE 95C1369

1

28 0V5R4 LCAC-02F2574 . RESISTOR, (R) 15 OHM, 3 WATT, ... NEWARK-IN-ONE 02F2574

5

END OF FIGURE

TM 21614-LCAC 0077 00

0077 00-40

Figure 16. J8 Wiring Assembly

PART NO. LCAC-MS34 TO L16-85

SPADE 17” (J8-A TO SS +)

SPADE 19” (J8-B TO SS-Y)

SPADE 20” (J8-C TO SS-FAN)

STRIP + SOLDER 14” (J8-D TO K4- +A1)

STRIP + SOLDER 15” (J8-E TO K5- +A1)

#10 EYE 11” (J8-G TO 1 (GND)

TM 21614-LCAC 0077 00

0077 00-41

Labels From To

Wire Size

AWG Wire Color

Type of End to End Connection

Length Of

Wire

Remarks

J8-A SS+ 20 RED STRIPPED END SPADE DNF18-250F1B

17

J8-B SS-Y 20 YELLOW STRIPPED END #10 RING PN10-10R

19

J8-C SS-FAN 20 BLUE STRIPPED END SPADE DNF18-250F1B

20

J8-D K4-+A1 20 RED STRIPPED END STRIPPED END

14

J8-E K5-+A1 20 BLACK STRIPPED END STRIPPED END

15

J8-G E1(GRD) 20 GREEN STRIPPED END #10 RING PN10-10R

11

(1) FIG/

ITEM NO.

(2) NSN

(3) CAGEC

(4) PART NUMBER

(5) DESCRIPTION

(7) QTY

16 0V5R4 LCAC-J8-01A J8 WIRING ASSEMBLY (SEE

FIGURE 15 FOR NHA) REF

1 81349 M5086/2-20-5 . WIRE, ELECTRICAL, GREEN ........ AR 2 81349 M5086/2-20-0 . WIRE, ELECTRICAL, BLACK ......... AR 3 81349 M5086/2-20-2 . WIRE, ELECTRICAL,RED............... AR 4 81349 M5086/2-20-6 . WIRE, ELECTRICAL, BLUE............ AR 5 81349 M5086/2-20-4 . WIRE, ELECTRICAL, YELLOW ...... AR 6 81349 M5086/2-16-4 . WIRE, ELECTRICAL, YELLOW ...... AR 7 06383 PN10-10R . TERMINAL, LUG, BARREL.............

#10 RING AR

8 0V5R4 LCAC-MS3470L16-8S . CONNECTOR, J8............................ 1 END OF FIGURE

TM 21614-LCAC 0077 00

0077 00-42

Figure 17. J1 Wiring Assembly

E

#10 EYE 12” (J1-A TO CB1-LINE)

#10 EYE 12” (J1-B TO CB1 LINE)

#10 EYE 12” (J1-C TO CB1 LINE)

#10 EYE 12” (J1-E TO E1 GND)

PART NO. LCAC-75-19002A-75P

TM 21614-LCAC 0077 00

0077 00-43

(1)

FIG/ ITEM

NO.

(2) NSN

(3) CAGEC

(4) PART NUMBER

(5) DESCRIPTION

(7) QTY

17 0V5R4 LCAC-J1-01A J1 WIRING ASSEMBLY (SEE

FIGURE 15 FOR NHA) REF

1 81349 M5086/2-10-5 . WIRE, ELECTRICAL, GREEN ........ AR 2 81349 M5086/2-10-0 . WIRE, ELECTRICAL, BLACK ......... AR 3 81349 M5086/2-10-2 . WIRE, ELECTRICAL,RED............... AR 4 81349 M5086/2-10-6 . WIRE, ELECTRICAL, BLUE............ AR 5 06383 PN10-10R . TERMINAL, LUG, BARREL.............

#10 RING AR

6 0V5R4 LCAC-75-19002A-75P . CONNECTOR, J1............................ 1 END OF FIGURE

TM 21614-LCAC 0077 00

0077 00-44

Figure 18. J2 Wiring Assembly

Labels From To

Wire Size

AWG Wire Color

Type of End to End Connection

Length Of

Wire

Remarks

J2-C RR- 20 BLACK STRIPPED END SPADE DNF18-

6

TM 21614-LCAC 0077 00

0077 00-45

Labels From To

Wire Size

AWG Wire Color

Type of End to End Connection

Length Of

Wire

Remarks

250F1B J2-F K4-14 20 BLUE STRIPPED END STRIPPED

END

11

J2-G K3-14 20 BLACK STRIPPED END STRIPPED END

8

J2-B CB5 LOAD 20 BLACK STRIPPED END #10 RING PN10-10R

20

J2-A FM-5 20 BLUE STRIPPED END SPADE DNF18-250F1B

22

K1-6 J2-0 10 BLACK STRIPPED END STRIPPED END

7

K1-4 J2-P 10 RED STRIPPED END STRIPPED END

7

K1-2 J2-R 10 BLUE STRIPPED END STRIPPED END

7

K2-6 J2-U 14 BLACK STRIPPED END STRIPPED END

8

K2-4 J2-Y 14 RED STRIPPED END STRIPPED END

8

K2-2 J2-X 14 BLUE STRIPPED END STRIPPED END

8

K3-6 J2-N 14 BLACK STRIPPED END STRIPPED END

9

K3-4 J2-W 14 RED STRIPPED END STRIPPED END

9

K3-2 J2-V 14 BLUE STRIPPED END STRIPPED END

9

K4-6 J2-I 14 BLACK STRIPPED END STRIPPED END

10

K4-4 J2-H 14 RED STRIPPED END STRIPPED END

10

K5-2 J2-L 14 BLUE STRIPPED END STRIPPED END

11

K5-6 J2-T 14 BLACK STRIPPED END STRIPPED END

11

(1) FIG/

ITEM NO.

(2) NSN

(3) CAGEC

(4) PART NUMBER

(5) DESCRIPTION

(7) QTY

18 0V5R4 LCAC-J2-01A J2 WIRING ASSEMBLY (SEE

FIGURE 15 FOR NHA) REF

1 81349 M5086/2-12-5 . WIRE, ELECTRICAL, GREEN ........ AR 2 81349 M5086/2-10-0 . WIRE, ELECTRICAL, BLACK ......... AR 3 81349 M5086/2-10-2 . WIRE, ELECTRICAL,RED............... AR 4 81349 M5086/2-10-6 . WIRE, ELECTRICAL, BLUE............ AR 5 81349 M5086/2-14-0 . WIRE, ELECTRICAL, BLACK ......... AR 6 81349 M5086/2-14-2 . WIRE, ELECTRICAL,RED............... AR

TM 21614-LCAC 0077 00

0077 00-46

(1) FIG/

ITEM NO.

(2) NSN

(3) CAGEC

(4) PART NUMBER

(5) DESCRIPTION

(7) QTY

7 81349 M5086/2-14-6 . WIRE, ELECTRICAL, BLUE ........... AR 8 81349 M5086/2-20-0 . WIRE, ELECTRICAL, BLACK......... AR 9 81349 M5086/2-20-6 . WIRE, ELECTRICAL, BLUE ........... AR

10 81349 M5086/2-16-0 . WIRE, ELECTRICAL, BLACK......... AR 11 06383 PN10-10R . TERMINAL, LUG, BARREL ............

#10 RING AR

12 06383 DNF18-250FIB . SPADE, QUICK DISCONNECT, FEMALE, INSULATED

AR

13 0V5R4 LCAC-CMB007 . CONNECTOR, J2 ........................... 1 END OF FIGURE

Figure 19. Transformer Assembly

Labels From To

Wire Size

AWG Wire Color

Type of End to End Connection

Length Of

Wire

Remarks

CB5 LOAD TR-5 20 BLACK RING PN18-10R

STRIPPED END

18

TM 21614-LCAC 0077 00

0077 00-47

Labels From To

Wire Size

AWG Wire Color

Type of End to End Connection

Length Of

Wire

Remarks

CB6 LINE TR-7 20 BLUE RING PN18-10R

STRIPPED END

20

TR-8 RR 20 BLUE STRIPPED END SPADE DNF18-250F1B

7.5

TR-2 CB4 LINE 20 RED STRIPPED END

RING PN18-10R

13

TR-3 TR-5 20 BLACK STRIPPED END

STRIPPED END

2

(1) FIG/

ITEM NO.

(2) NSN

(3) CAGEC

(4) PART NUMBER

(5) DESCRIPTION

(7) QTY

19 0V5R4 LCAC-TR-01A TRANSFORMER ASSEMBLY (SEE

FIGURE 15 FOR NHA) REF

TR 0V5R4 LCAC-13221E9117 . TRANSFORMER (TR) 208V – 400HZ PRI TO 30V- 400HZ SEC

1

BE-20 81349 M5086/2-20-6 . WIRE, ELECTRICAL,BLUE ............. 20” BE-7.5 81349 M5086/2-20-6 . WIRE, ELECTRICAL,BLUE ............. 7.5” RD-13 81349 M5086/2-20-2 . WIRE, ELECTRICAL, RED.............. 13” BK-18 81349 M5086/2-20-0 . WIRE, ELECTRICAL,BLACK........... 18”

BK-2 81349 M5086/2-20-0 . WIRE, ELECTRICAL,BLACK (JUMPER) ..................................

2”

1 06383 DNF18-250FIB . SPADE, QUICK DISCONNECT, FEMALE, INSULATED

1

2 06383 PN10-10R . TERMINAL, LUG, BARREL ............. #10 RING

3

END OF FIGURE

TM 21614-LCAC 0077 00

0077 00-48

Figure 20. Rectifier Assembly

(1) FIG/

ITEM NO.

(2) NSN

(3) CAGEC

(4) PART NUMBER

(5) DESCRIPTION

(7) QTY

20 0V5R4 LCAC-RR-01A RECTIFIER ASSEMBLY,28VDC

(SEE FIGURE 15 FOR NHA) REF

RR 0V5R4 LCAC-13216E6223 . RECTIFIER (RR), 28VDC 1 C1 0V5R4 LCAC-13218E6961 . CAPACITOR, C1 1 C2 0V5R4 LCAC-95C1369 . CAPACITOR, C2 1

END OF FIGURE

TM 21614-LCAC 0078 00

PART NUMBER INDEX

0078 00-1

PART NUMBER FIG. ITEM AS21919WDG34 1 10 ASTM-C534TP2 12 10 DNF10-250FIB 14 33 DNF18-250FIB 13 13 DNF18-250FIB 18 12 DNF18-250FIB 19 1 DNF18-250FIB 9 10 DNFR18-250FIB 13 12 DNFR18-250FIB 14 35 DV18-250P 14 34 LCAC-02F2574 15 28 LCAC-0388-004TD 15 18 LCAC-105025200 1 5 LCAC-105025200 4 2 LCAC-105025800 1 2 LCAC-105025800 3 3 LCAC-13216E6223 20 RR LCAC-13218E6961 15 26 LCAC-13218E6961 20 C1 LCAC-13221E9117 19 TR LCAC-13225E8453 2 5 LCAC-1CM-1CM103 15 19 LCAC-2010 WAR 9 1 LCAC-2201 9 3 LCAC-304-0428-000 10 10 LCAC-304-0430-000 10 7 LCAC-304-0437-000 11 10 LCAC-33KH-1 1 LCAC-38-T067-F4583 15 7 LCAC-460-400Hz 15 16 LCAC-5120T1-2M-650 7 1 LCAC-75-19002A-75P 17 6 LCAC-95C1369 15 27 LCAC-95C1369 20 C2 LCAC-97038676 1 28 LCAC-97039332 1 27 LCAC-ADRSE-2-0/80 8 1 LCAC-C-053-S 5 1 LCAC-CB-01A 1 47 LCAC-CB-01A 11 LCAC-CD-01A 4 LCAC-CD3604 WITH CD3688 1 25 LCAC-CD3604 WITH CD3688 1 26 LCAC-CI-030486 10 9 LCAC-CI-030487 11 9 LCAC-CMB006 13 14 LCAC-CMB007 18 13 LCAC-CMB007 9 11 LCAC-COPPER STRAP-LPS 1 40 LCAC-DRAIN CLAMP 1 18

PART NUMBER FIG. ITEM LCAC-DRAIN HOSE 1 17 LCAC-EB-01A 1 46 LCAC-EB-01A 10 LCAC-EP-01A 3 LCAC-FD-01A 1 9 LCAC-FD-01A 5 LCAC-HG-01A 1 21 LCAC-HG-01A 8 LCAC-HI-ITT3 6 1 LCAC-HR-01A 1 30 LCAC-HR-01A 9 LCAC-ILPS-424-010E025E 1 39 LCAC-J1-01A 15 8 LCAC-J1-01A 17 LCAC-J2-01A 15 9 LCAC-J2-01A 18 LCAC-J3-01A 1 49 LCAC-J3-01A 13 LCAC-J8-01A 15 10 LCAC-J8-01A 16 LCAC-JA3S-N3-0015-02E 15 3 LCAC-JA3S-N3-0015-02E 15 4 LCAC-JA3S-NS-0030-02E 15 1 LCAC-JA3S-NS-0030-02E 15 2 LCAC-LC1D32BD 15 11 LCAC-LC1D32BD 15 12 LCAC-LC1D32BD 15 13 LCAC-LC1D32BD 15 14 LCAC-LC1D32BD 15 15 LCAC-MIL-Z-40-VAC-420 1 1 LCAC-MIL-Z-40-VAC-420 2 1 LCAC-MIL-Z-40-VAC-420 2 7 LCAC-MS27183-14 2 3 LCAC-MS3470L16-8S 16 8 LCAC-P20EB-2 1 38 LCAC-P20EB-2 8 5 LCAC-PR-01A 1 20 LCAC-PR-01A 7 LCAC-RIVE-3-GA-RPB 1 8 LCAC-RIVE-3-GA-RPB 3 2 LCAC-RR-01A 15 17 LCAC-RR-01A 20 LCAC-S2049062212 9 6 LCAC-S9500-3/8-16LK 2 2 LCAC-S9500-3543 10 6 LCAC-S9500-3543 11 8 LCAC-S9500-8165-2 2 6 LCAC-S9500-8165-3 2 4 LCAC-S9500-E9949 1 22 LCAC-SG-01A 1 13

TM 21614-LCAC 0078 00

0078 00-2

PART NUMBER FIG. ITEM LCAC-SG-01A 6 LCAC-SK33K-101 1 43 LCAC-SK33K-16 10 2 LCAC-SK33K-21 10 4 LCAC-SK33K-22 11 6 LCAC-SK33K-23 1 16 LCAC-SK33K-24 1 34 LCAC-SK33K-30 15 22 LCAC-SK33K-31 15 23 LCAC-SK33K-4 15 24 LCAC-SK33K-7 11 2 LCAC-SK33K-72 1 19 LCAC-SK33K-8 11 4 LCAC-SK33K-80 1 29 LCAC-SK33K-RCP ID PLATE 15 25 LCAC-TR-01A 15 20 LCAC-TR-01A 19 LCAC-W01206 7 5 LCAC-W02312 4 4 LCAC-W02312 6 2 LCAC-W02716 4 1 LCAC-W31-X2M1G-2 15 5 LCAC-W31-X2M1G-4 15 6 LCAC-W31-X2M1G-5 15 21 LCAC-W40324 6 4 LCAC-W40350 7 3 M5086/2-10-0 13 2 M5086/2-10-0 14 6 M5086/2-10-0 17 2 M5086/2-10-0 18 2 M5086/2-10-2 13 3 M5086/2-10-2 14 7 M5086/2-10-2 17 3 M5086/2-10-2 18 3 M5086/2-10-3 14 10 M5086/2-10-5 14 9 M5086/2-10-5 17 1 M5086/2-10-6 13 4 M5086/2-10-6 14 8 M5086/2-10-6 17 4 M5086/2-10-6 18 4 M5086/2-10-9 14 11 M5086/2-12-0 14 12 M5086/2-12-2 14 13 M5086/2-12-3 14 16 M5086/2-12-5 13 1 M5086/2-12-5 14 15 M5086/2-12-5 18 1 M5086/2-12-6 14 14 M5086/2-12-9 14 17 M5086/2-12-9 14 30 M5086/2-14-0 13 5 M5086/2-14-0 14 18

PART NUMBER FIG. ITEM M5086/2-14-0 18 5 M5086/2-14-2 13 6 M5086/2-14-2 14 19 M5086/2-14-2 18 6 M5086/2-14-2 9 7 M5086/2-14-3 14 22 M5086/2-14-5 14 21 M5086/2-14-6 13 7 M5086/2-14-6 14 20 M5086/2-14-6 18 7 M5086/2-14-6 9 8 M5086/2-16-0 18 10 M5086/2-16-4 16 6 M5086/2-18-0 13 10 M5086/2-18-0 13 8 M5086/2-18-6 13 9 M5086/2-20-0 14 23 M5086/2-20-0 16 2 M5086/2-20-0 18 8 M5086/2-20-0 19 BK-18 M5086/2-20-0 19 BK-2 M5086/2-20-2 14 24 M5086/2-20-2 16 3 M5086/2-20-2 19 RD-13 M5086/2-20-3 14 28 M5086/2-20-4 14 26 M5086/2-20-4 16 5 M5086/2-20-5 14 27 M5086/2-20-5 16 1 M5086/2-20-6 14 25 M5086/2-20-6 16 4 M5086/2-20-6 18 9 M5086/2-20-6 19 BE-20 M5086/2-20-6 19 BE-7.5 M5086/2-20-9 14 29 MS18065-20 10 11 MS18065-20 10 8 MS18065-20 11 11 MS24693C298 11 12 MS24693C51 1 32 MS24693C51 1 36 MS24693C51 1 45 MS24693C51 12 3 MS24693C51 12 5 MS24693C51 12 7 MS24693C54 1 11 MS24693C54 1 14 MS24693C54 1 41 MS25036-103 14 32 MS25036-112 14 31 MS35308-306 11 3 MS35308-306 11 5 MS35308-334 10 12

TM 21614-LCAC 0078 00

0078 00-3

PART NUMBER FIG. ITEM MS35308-334 11 13 MS35338-137 1 15 MS35338-137 1 33 MS35338-137 1 37 MS35338-137 1 4 MS35338-137 1 7 MS35338-137 12 9 MS51957-46 1 3 MS51957-46 1 31 MS51957-46 1 35 MS51957-46 1 44 MS51957-46 1 6 MS51957-46 10 3 MS51957-46 10 5 MS51957-46 11 1 MS51957-46 11 7 MS51957-46 12 8 MS51958-70 1 23 MS51958-83 10 1 PN10-10R 13 11 PN10-10R 16 7 PN10-10R 17 5 PN10-10R 18 11 PN10-10R 19 2 PN10-10R 9 9 S9160-JBA-3 1 52 S9160-JBA-3 15 SK33K-1 12 1 SK33K-11 12 6 SK33K-47 9 2 SK33K-49 9 5 SK33K-5 12 2 SK33K-6 11 16 SK33K-70 12 4 SK33K-98 9 4 SK33K-TB-001 3 1 SK33K-TB-003 7 2 SK33K-TB-004 7 4 SK33K-TB-005 8 3 SK33K-TB-006 8 2 SK33K-TB-007 8 4 SK33K-TB-008 5 2 SK33K-TB-009 5 3 SK33K-TE-3020 3 4 SK33K-TS-3022 6 5 SK33K-TS-3056 6 3 SK33K-TS-3146 4 3 ZZ-T-831 14 1 5174K12 14 5 5174K5 14 3 5174K6 14 4 6-1-5853-11 14 2 8-32 1 12

PART NUMBER FIG. ITEM 8-32 1 42 #10 1 24 #10-32 1 51 #5/16 10 13 #5/16 11 14 #5/16 x 24 10 14 #5/16 x 24 11 15

TM 21614 LCAC 0079 00

AIR CONDITIONER, HORIZONTAL COMPACT, 33,000 BTU/HR

208 VOLT, 3 PHASE, 400 HERTZ, ENVIRONMENTAL SYSTEMS LCAC-33KH-1

NSN 4120-01-512-2399 REFERENCE DESIGNATOR INDEX

0079 00-1

REFERENCE FIG. ITEM DESIGNATOR CB1 15 1 CB2 15 2 CB3 15 3 CB4 15 4 CB5 15 5 CB6 15 6 C1 15 26 C2 15 27 FM 15 7 J1 22 6 J2 20 13 J3 21 14 J8 23 8 HR 18 1 K1 15 11 K2 15 12 K3 15 13 K4 15 14 K5 15 15 PM 15 16 R 15 28 RR 15 17 SS 15 18 S4 1 39 S5 1 38 S5 8 5 S6 9 6 TD 15 19 TR 15 21 TR 19 TR

REFERENCE FIG. ITEM DESIGNATOR

TM 21614-LCAC

CHAPTER 10

SCHEMATIC AND

WIRING

TM 21614-LCAC

0080-00

TM 21614-LCAC

0081-00-1

UNIT WIRING LIST 0081-00 TERMINAL TYPE CODE “A” Flag Insul. “B” Spade Insul. “C” Compr. Flag “D” Piggyback Spade “E” #10 Ring “F” Stripped End COMPONENTS WITH INTEGRAL LEAD WIRES B2, B3, S4, S1, S3

TERMINATIONS

WIRE SIZE

COLOR

LENGTH

TERMINAL TYPE COLOR

J3-0 TO B1-T1 10 GA. BK 18 IN. F-C J3-P TO B1-T2 10 GA. RD 18 IN. F-C J3-R TO B1-T3 10 GA. BE 18IN. F-C J3-U TO TB-1 14 GA. BK 32 IN. F-E J3-Y TO TB-2 14 GA. RD 32 IN. F-E J3-X TO TB-3 14 GA. BE 32 IN. F-E J3-N TO TB-4 14 GA. BK 33 IN. F-E J3-W TO TB-5 14 GA. RD 33 IN. F-E J3-V TO TB-6 14 GA. BE 33 IN. F-E J3-I TO HR1 14 GA. BK 44 IN. F-A J3-H TO S6 14 GA. RD 35 IN. F-E J3-L TO S6 14 GA. BE 34 IN. F-E J3-T TO HR3 14 GA. BK 33 IN. F-A S6 TO HR2 14 GA. RD 17 IN. E-A S6 TO HR3 14 GA. BE 11 IN. E-A HR1 TO HR2 14 GA. RD 4 IN. E-A HR2 TO HR3 14 GA. BE 4 IN. E-A J3-A TO CH 20 GA. BE 20 IN. F-F J3-B TO CH 20 GA. BK 20 IN. F-F J3-C TO TB-7 20 GA. BK 35 IN. F-E J3-F TO TB-8 20 GA. BE 35 IN. F-E J3-G TO TB-9 20 GA. BK 35 IN. F-E TB-9 TO S2-D 20 GA. BK 35 IN. E-C S2 TO S4 20 GA. BK 4.5 IN. C-F J3-S TO E2 (GND) 20 GA. GN 22 IN. F-E J1-A TO CB1-LINE 12 GA. BK 12 IN. F-E J1-B TO CB1-LINE 10 GA. RD 12 IN. F-E J1-C TO CB1-LINE 10 GA. BE 12 IN. F-E J1-E TO E1 (GND) 10 GA. GN 10 IN. F-E CB1-LINE TO CB2-LINE 12 GA. BK 5 IN. E-E CB1-LINE TO CB2-LINE 12 GA. RD 5 IN. E-E CB1-LINE TO CB2-LINE 12 GA. BE 5 IN. E-E CB2-LINE TO CB3-LINE 12 GA. BK 5 IN. E-E CB2-LINE TO CB3-LINE 12 GA. RD 5 IN. E-E CB2-LINE TO CB3-LINE 12 GA. BE 5 IN. E-E CB3-LINE TO CB4-LINE 12 GA. BK 5 IN. E-E

TM 21614-LCAC

0081-00-2

UNIT WIRING LIST - Continued 0081-00

TERMINATIONS

WIRE SIZE

COLOR

LENGTH

TERMINAL TYPE COLOR

FM-1 TO CB5 LINE 20 GA. BK 2.5 IN. B-E CB5 LOAD TO TR-5 20 GA. BK 18 IN. E-F PM-4 TO RR-+ 20 GA. RD 13 IN. F-B CB6 LINE TO TR-7 20 GA. BE 20 IN. E-F CB6 LOAD TO RR 20 GA. BE 20 IN. E-B TR-8 TO RR 20 GA. BE 7.5 IN. F-B FM-5 TO CB4 LINE 20 GA. BE 5 IN. B-E FM-2 TO CB4 LINE 20 GA. BK 5 IN. B-E PM-L3 TO CB2 LINE 20 GA. BE 13 IN. F-F PM-L2 TO CB2 LINE 20 GA. RD 13 IN. F-F PM-L1 TO CB2 LINE 20 GA. BK 13 IN. F-F J2-S TO E1 (GND) 12 GA. GN 11 IN. F-E TR-2 TO CB4 LINE 20 GA. RD 13 IN. F-E TR-3 TO TR-4 20 GA. BK 2 IN. F-F

TM 21614-LCAC

CHAPTER 12

DRAWILNGS AND

PARTS INFORMATION

FOR

AIR CONDITONER, HORIZONAL, COMPACT,

33,000 BTU/HR 208 VOLT,

THREE PHASE, 400 HERTZ

PART NO. LCAC-33KH-1 NSN 4120-01-512-2399

ENVIRONMENTAL SYSTEMS, INC.

TM 21614 - LCAC 0085 00

0085 00-1

Table 1. Tools and Test Equipment for Air Conditioner

(1) TOOLS OR

TEST EQUIPMENT

REF CODE

(2)

MAINTENANCE LEVEL

(3)

NOMENCLATURE

(4)

NATIONAL STOCK NUMBER

(5)

TOOL NUMBER

NOTE

Standard tools and test equipment in the following kits are adequate to accomplish the maintenance functions listed in Table 1.

1

O,F,H Tool Kit, General Mechanics 5180-00-699-5273 SC5180-90-CL-N05

2 O,F,H Tool Kit, Service, Refrigeration Unit

5180-00-596-1474 SC5180-90-CL-N18

3

F Pump, Vacuum 4310-00-289-5967

4

F Nitrogen Regulator 6680-00-503-1327

5

F Recovery and Recycle Unit, Refrigerant

4130-01-338-2707

6

O Heat Gun 4940-01-042-4855

7

O, F Rivet Gun 5120-00-508-1588

8

F,H Welding Shop, Trailer Mounted

3431-01-090-1231 SC-3431-95-CL-A04

9

O, F Solder Gun Kit 3439-00-930-1638

10

F Thermometer Set 6685-00-874-5834

11

O, F Strengthener Fin 5120-00-157-2180

12

F Screwdriver, Cross Tip 5120-01-412-3430

13 F Key, Socket Head Screw

5120-00-076-1787

END OF WORK PACKAGE

TM 21614-LCAC 0086 00 EXPENDABLE AND DURABLE ITEMS LIST

0086 00-1

INTRODUCTION Scope This work package lists expendable and durable items that you will need to operate and maintain the air conditioner. This list is for information only and is not authority to requisition the listed items. Explanation of Columns in the Expendable/Durable Items list Column (1) - Item Number. This number is assigned to the entry in the list and is referenced in the narrative instructions to identify the item (e.g., “Use lubricating oil (Item 25, WP 5230-00)”). Column (2) - Level. This column identifies the lowest level of maintenance that requires the item (C = Operator/Crew). Column (3) - National Stock Number. This is the NSN assigned to the item which you can use to requisition it. Column (4) - Item Name, Description, Commercial and Government Entity Code (CAGE), and Part Number. This column provides the other information you need to identify the item. Column (5) - Unit of Issue (U/M). This code indicates the physical measurement or count of the item , such as per gallon, dozen, gross, etc.

Table 1. Expendable and Durable Items List (1)

ITEM NUMBER

(2)

LEVEL

(3) NATIONAL STOCK

NUMBER

(4) ITEM NAME, DESCRIPTION, CAGEC, PART

NUMBER

(5)

U/I 1 O Silicone Adhesive Sealant, RTV, General, Mil-A-

46106, Type I

2 O Solder, Lead-Tin, QQ-S-571, Type SN60WRP2

3 F 3040-00-664-0439 Adhesive, General Purpose, 1 pint container

ea

4 F 6830-00-292-0732 Nitrogen

cy

5 F Brazing Alloy, Silver, QQ-B-654, Grade O, I, or II

6 F Brazing Alloy, Silver, QQ-B-654, Grade III

7 F 3439-00-640-3713 Flux, Brazing, O-F-499, Type B

8 F 5350-00-192-5047 Abrasive Cloth

pg

9 C,O,F 7920-00-205-1711 Rags

10 F 6850-00-837-9927 Monochlorodifluoromethane, Technical: w/cylinder 22 lbs. (Refrigerant-22), BB-F-1421, Type 22 (81348)

cy

11 O,F Tape PPP-T-60, Type IV, Class I

roll

12 F 6830-00-872-5120 Trichloromonofluoromethane, Technical: w/cylinder 50 lbs. (Refrigerant-11), BB-F-1421, Type II (81348)

TM 21614-LCAC 0086 00

0086 00-2

Table 1. Expendable and Durable Items List - Continued (1)

ITEM NUMBER

(2)

LEVEL

(3) NATIONAL STOCK

NUMBER

(4) ITEM NAME, DESCRIPTION, CAGEC, PART

NUMBER

(5)

U/I 13 F 8030-00-889-3534 Tape, Antiseize, Polytetgrafluorethylene, MIL-T-

22730, Size I

roll

14 O,F Lubricating Oil, VV-L-825, Type IV

qt

15 O,F 3439-01-045-7940 Flux, Soldering, Liquid Rosin Base, MIL-F-14256

qt

16 O,F 6850-01-331-3349 Dry Cleaning Solvent, P-D-680 Type III (81348)

5 gal.

17 O Coater, Air Filter, MIL-L-2104 (81348)

18 O,H Adhesive, MMM-A-121

qt

19 H Cellular Rubber Strips, MIL-R-6130, Tyhpe I, Grade A

ft

20 H Flexible Elestomeric Thermal Insulation (ASTM C 534, Type 2, Sheet)

shts

21 O,F Solder, Silver, QQ-S-561, Type 3, 4 or 6A

22 H Acetone

pt

23 O,F Insulation, Sheet, Cellular, MIL-I-14511

24 O,F Plastic Foam, Unicellular, Sheet Form, MIL-P-15280

25 O,F Adhesive, MMM-A-132, Type I, Class I

26 F Industrial Sealant 800

27 O,F Acid Swab Brush

28 F 9150-00-985-7316 Grease, General Purpose

29 O,F,H 4240-01-152-3555 Mask, Air Filtering pkg

END OF WORK PACKAGE

PL1

REMOTE CONTROL PANEL Part No. LCAC-33KH-1 (RCP)

CAGE 0V5R4

PL1

CONDENSER BLOWER ASSEMBLY – PART NO. LCAC-CB-01A

PL2

PL2

EVAPORATOR BLOWER ASSEMBLY – PART NO. LCAC-EB-01A

PL3

EVAPORATOR BLOWER ASSEMBLY

PL3