TeSys motor startersup to 65 A
Increase automationDirect Control Quickfit pre-wired control technology
■ Control and save
Control TeSys low consumption contactor from your PLC outputs.
■ Pre-wire and communicate
The TeSys Quickfit pre-wired solution allows communication with PLCs via Advantys STB interface or a splitter box.
Save space
45 and 55 mm widths Compact DC contactor S-shape and multiple tap-off busbar systems
■ SmallerWith a width of 45 mm up to 38 A and 55 mm up to 65 A, TeSys motor starters fit more easily into electrical enclosures.
■ Install without wiring
Special busbar systems allow fast pre-wiring of power connections. Assemble a motor starteron a single rail with the “S” shape busbar system.
Increase reliability and safety
Auxiliary safety contacts Spring terminals and Type 2 tested motor starters
Save timeSpring terminals andReverser kitCommon accessories range
■ Combine without wiring
Simple manual unclipping of a terminal block allows you to combine the circuit-breaker with the contactor. Assembling a reverser becomes child’s play. Using standard contactors, you can build your reversing starter in less than 2 minutes on the clock, without any risk of wiring errors. Flexibility using add-on blocks and accessories, that are common throughout the 9 to 65A motorstarters range.
■ Increase safety
Mechanically linked auxiliary and mirror contactsensure reliable return of information and allow you to include TeSys contactors in your safety applications.
■ Increase reliability
Spring terminals and Schneider Electric’s new,patented terminal block technologyensure permanent tightening quality by compensating for cable creep.
■ Guarantee performance
Continuity of service is guaranteed by using tested combinations with high breaking capacity.Type 2 coordination allows operation to be resumed more quickly after a short-circuit fault.
TeSys motor starters selection guide
GV2 + LC1D Circuit breaker + contactor TeSysHigh breaking capacity / Icu/400v 130KA 130KA 130KA 130KA 130KA 130KA 130KA
Setting range of thermal trips 0.16…0.25 A 0.25…0.40 A 0.40…0.63 A 0.63…1 A 1…1.6 A 1.6…2.5 A 2.5...4 A
Thermal-magnetic circuit-breaker GV2P02 GV2P03 GV2P04 GV2P05 GV2P06 GV2P07 GV2P08
Standard breaking capacity / Icu/400v 130KA 130KA 130KA 130KA 130KA 130KA 130KA
Setting range of thermal trips 0.16…0.25 A 0.25…0.40 A 0.40…0.63 A 0.63…1 A 1…1.6 A 1.6…2.5 A 2.5...4 A
Thermal-magnetic circuit-breaker GV2ME02 GV2ME03 GV2ME04 GV2ME05 GV2ME06 GV2ME07 GV2ME08
Ie AC-3 (A) 0.2 0.3 0.44...0.6 0.85 1.1...1.5 1.9 2.7...3.6
Ie AC1 (T<60°C) (A) 25 25 25 25 25 25 25
Contactor LC1D09 LC1D09 LC1D09 LC1D09 LC1D09 LC1D09 LC1D09
GV2 + LC1D + LRD Circuit breaker + contactor + thermal relayTeSysHigh breaking capacity / Icu/400v 130KA 130KA 130KA 130KA 130KA 130KA 130KA
Magnetic circuit-breaker GV2L02 GV2L03 GV2L04 GV2L05 GV2L06 GV2L07 GV2L08
Standard breaking capacity / Icu/400v 130KA 130KA 130KA 130KA 130KA 130KA 130KA
Magnetic circuit-breaker GV2LE02 GV2LE03 GV2LE04 GV2LE05 GV2LE06 GV2LE07 GV2LE08
Ie AC3 (A) 0.2 0.3 0.44...0.6 0.85 1.1...1.5 1.9 2.7...3.6
Ie AC1 (T<60°C) (A) 25 25 25 25 25 25 25
Contactor LC1D09 LC1D09 LC1D09 LC1D09 LC1D09 LC1D09 LC1D09
Setting range 0.16…0.25 A 0.25…0.40 A 0.40…0.63 A 0.63…1 A 1…1.7 A 1.6…2.5 A 2.5...4 A
Thermal overload relay cl10A LRD02 LRD03 LRD04 LRD05 LRD06 LRD07 LRD08
Setting range - - - - - - -
Thermal overload relay cl10A - - - - - - -
Setting range - - - - - - 2.5...4 A
Thermal overload relay cl20 - - - - - - LRD1508
Setting range - - - - - - -
Thermal overload relay cl20 - - - - - - -
Standard power ratings of 3-phase motors 50-60 Hz
in category AC3/400V (kw)0.06 0.09 0.12...0.18 0.25 0.37...0.55 0.75 1.1...1.5
Connection : GV2P, GV2ME, LC1D up to 32 A : by screw clamp terminal (for power and control spring terminal, add 3 at the end of
Connection : GV2L, GV2LE, LC1D & LRD up to 32 A : by screw clamp terminal (for power and control spring terminal, add 3 at the end of the reference
TeSys GV3 + LC1D
Coil voltage
Contactor AC Standard LowDC consumption
DC *
50/60 HZ 5,4 W < 2,4 W24 V B7 BD BL48 V E7 ED EL72 V - SD SL110 V F7 FD120 V G7 -220 V M7 MD230 V P7240 V U7380 V Q7400 V V7415 V N7440 V R7
* Only for LC1D40 to D65, please order LAD4DBL accessory for direct control from a PLC.
130KA 130KA 130KA 130KA 100KA 100KA 100KA 100KA 50KA 50KA 50KA
4...6.3 A 6...10 A 6...10 A 9...14 A 12...18 A 12...18 A 17...25 A 23...32 A 30...40 A 37...50 A 48...65 A
GV2P10 GV2P14 GV2P14 GV2P16 GV3P18 GV3P25 GV3P25 GV3P32 GV3P40 GV3P50 GV3P65
130KA 130KA 130KA 15KA 15KA 15KA 15KA 15KA 50KA 50KA 50KA
4...6.3 A 6...10 A 6...10 A 9...14 A 13...18 A 17...23 A 20...25 A 24...32 A 30...40 A 37...50 A 48...65 A
GV2ME10 GV2ME14 GV2ME14 GV2ME16 GV2ME20 GV2ME21 GV2ME22 GV2ME32 GV3P40 GV3P50 GV3P65
4.9 6.5 8.5 11.5 15.5 18.1 22 29 35 41 55
25 25 25 25 32 40 40 50 60 80 80
LC1D09 LC1D09 LC1D09 LC1D12 LC1D18 LC1D25 LC1D25 LC1D32 LC1D40A LC1D50A LC1D65A
130KA 130KA 130KA 50KA 50KA 50KA 100KA 100KA 50KA 50KA 50KA
GV2L10 GV2L14 GV2L14 GV2L16 GV2L20 GV2L22 GV3L25 GV3L32 GV3L40 GV3L50 GV3L65
130KA 130KA 130KA 15KA 15KA 15KA 15KA 15KA 50KA 50KA 50KA
GV2LE10 GV2LE14 GV2LE14 GV2LE16 GV2LE20 GV2LE22 GV2LE22 GV2LE32 GV3L40 GV3L50 GV3L65
4.9 6.5 8.5 11.5 15.5 18.1 22 29 35 41 55
25 25 25 25 32 40 40 50 60 80 80
LC1D09 LC1D09 LC1D09 LC1D12 LC1D18 LC1D25 LC1D25 LC1D32 LC1D40A LC1D50A LC1D65A
4...6 A 5.5...8 A 7...10 A 9...13 A 12...18 A 16...24 A 16...24 A 23...32 A - - -
LRD10 LRD12 LRD14 LRD16 LRD21 LRD22 LRD22 LRD32 - - -
- - - - - - 17...25 A 23..32 A 30...40 A 37...50 A 48...65 A
- - - - - - LRD325 LRD332 LRD340 LRD350 LRD365
4...6 A 5.5...8 A 7...10 A 9...13 A 12...18 A 17...25 A 17...25 A 25...32 A - - -
LRD1510 LRD1512 LRD1514 LRD1516 LRD1521 LRD1522 LRD1522 LRD1532 - - -
- - - - - - 17...25 A 23...32 A 30...40 A 37...50 A 48...65 A
- - - - - - LRD325L LRD332L LRD340L LRD350L LRD365L
TeSys GV3 + LC1D + LRD3
2.2 3 4 5.5 7.5 9 11 15 18.5 22 30
the reference selected). GV3P, LC1D40 to D65 : by EverLink terminal (for control spring terminal, add 3 at the end of the reference selected). Connection by lugs add the digit 6 at the end of the reference selected
selected). GV3L, LC1D & LRD3 : by EverLink terminal (for control spring terminal, add 3 at the end of the reference selected). Connection by lugs add the digit 6 at the end of the reference selected
LC1DAdd-on blocks for TeSys LC1D contactors
Accessories for TeSys GV2-GV3 circuit-breakers
Add-on blocks common to TeSys GV2-GV3 circuit-breakers
SETS OF 3-POLE 63 A BUSBARS
Number of combined GV2 circuit-breakers 2 3 4 5
Bar pitch (1) 45 mm GV2G245 GV2G345 GV2G445 -
54 mm GV2G254 GV2G354 GV2G454 GV2G554
72 mm GV2G272 - GV2G472 -
(1) Protective end cover for unused busbar outlets, reference: GV1G10
SETS OF 3-POLE 115 A BUSBARS
Number of combined GV3 circuit-breakers 2 3
Bar pitch 64 mm GV3G264 GV3G364
TERMINAL BLOCKS
For supply to one or more busbar sets GV2ME/P/L GV3P/L
Connection from the top GV1G09 -
"Large spacing" terminal block UL508 GV2P..H7 GV3P
GV2GH7 GV3G66
PADLOCKING DEVICE
For 4 padlocks Shank diameter 6 mm max., padlocks not supplied
GV2ME/P/L-GV3P/L GV2V03
PADLOCKABLE EXTERNAL OPERATOR
Colour of operator Black handle/blue legend plate Red handle/yellow legend plate
GV2P/L Padlocking In ON and OFF positions GV2AP01 In OFF position GV2AP02
GV2LE Padlocking In ON and OFF positions GV2AP03
GV3P/L Padlocking In ON and OFF positions GV3AP01 In OFF position GV3AP02
CONTACT BLOCK
Instantaneous auxiliary contacts 1”F” 1”0” 1”F” + 1”0” 2”F” 2”0” 2”F” + 2”0” 1”F” + 3”0” 3”F” + 1”0”
Mounting position Front LADN10 LADN01 LADN11 LADN20 LADN02 LADN22 LADN13 LADN31
Side - - LAD8N11 LAD8N20 LAD8N02 - - -
Time delay auxiliary contacts 0.1...3 s 0.1...30 s 10...180 s
Mounting position Front On-delay LADT0 LADT2 LADT4
Off-delay LADR0 LADR2 LADR4
CONTACT BLOCK
Instantaneous auxiliary contacts "F" or "O" "F" and "O" "F" + "F"
Mounting position Left-hand side - GVAN11 (1) GVAN20 (1)
Front GVAE1 GVAE11 (1) GVAE20 (1)
(1) For spring terminal version, add 3 to the end of the reference, example: GVAN11 becomes GVAN113
Fault contact + instantaneous auxiliary contact "F" (fault) + "O" "F" (fault) + "F" "O" (fault) + "O" "O" (fault) + "F"
Mounting position Left-hand side GVAD1001 GVAD1010 GVAD0101 GVAD0110
Front GV3 only GVAED011 (2) GVAED101 (2)
(2) For spring terminal version, add 3 to the end of the reference, example: GVAED011 becomes GVAED0113 (GV3 only)
Short-circuit signalling contact "OF" with common point
Mounting position Left-hand side GVAM11
TeSys motor starter mounting accessories COMBINATION MOUNTING
< 38 A (with GV2 range) < 65 A (with GV3 range)
GV2AF3 (on mounting rail) Without accessory (1)
GV2AF4 (on mounting plate LAD311)
(1) GV3P/L can be ordered without outgoing terminal block. Ex : GV3P651
SIDE-BY-SIDE MOUNTING – S-SHAPE BUSBAR SYSTEM
< 38 A (with GV2 range) < 65 A (with GV3 range)
- GV3S (2)
(2) Can be associated with a combination reverser assembly
COMBINATION REVERSER ASSEMBLY – REVERSER KIT (3)
< 38 A from 40 to 65 A
LAD9R1V LAD9R3
(3) Can be associated with a side-by-side assembly
SEPARATE RELAY MOUNTING – TERMINAL BLOCK
< 38 A (for LRD) < 65 A (for LRD3)
LAD7B106 LAD96560
MOUNTING WITH PRE-WIRED CONTROL TECHNOLOGY – TESYS QUICKFIT MOUNTING KIT (for LC1D..3 contactor with spring terminals)
Motor connection module - Direct 1
Without relay Electronic relay (for DC coil control)
LAD9AP3D1 LAD9AP31
Motor connection module - Reverser 2
Without relay Electronic relay (for DC coil control)
LAD9AP3D2 LAD9AP32
Parallel wiring module
Advantys STB 3 Splitter block 4
4xRJ45 2xHE10 / 8xRJ45
STBEPI2145 LU9G02
1
4
2
3
www.schneider-electric.com
ART. 831641
Schneider Electric Industries S.A.S.
Head office
89 boulevard Franklin Roosevelt
92504 Rueil-Malmaison Cedex
France
http://www.schneider-electric.com
Owing to changes in standards and equipment,
the characteristics given in the text and images
in this document are not binding until they have been confirmed by us.
Design/Production: JAPA
Printed by:
Photos: Schneider Electric
DIA
1ED
1070
901E
N
01/2008