ASBESTOS RE-INSPECTION SURVEY REPORT
AEL Ref. S 19334.17 Rev. 11 0174
SOP10.10F7 Issue 10 Nov 17
Adams Environmental LtdUnit 6, Kimpton Link Business Park, 40 Kimpton Road, SUTTON SM3 9QP
Tel: 020 8641 6000 Fax: 020 8641 0666 Website: www.adamsenvironmental.co.uk Registered Office: Onslow Hall, Little Green, Richmond, TW9 1QH. Company Registration No. 2055824
Thorpe Coombe Hospital Forest Road, Walthamstow, E17 3HP
.
Client:
North East London NHS Foundation Trust Estates & Capital Planning Project Office Goodmayes Hospital, Ilford, Essex, IG3 8XJ For the attention of Mr Brian Stamp
Lead Surveyor: O Mmolawa
Report Authorised by:
J Passmore Date of Authorisation:
28th March 2019
CONTENTS: APPENDICES:
1 Introduction I Asbestos Register 2 Survey Findings II Materials Report 3 Recommendations III Plans IV Photographs
This Report does not constitute a Bill of Quantities and is not intended for use as a Specification of Works for asbestos remedial projects.
Page 1 of 112
Re-Inspection Survey
Part 1: Introduction
AEL Ref.
Thorpe Coombe Hospital S 19334.17 Rev. 11
SOP10.10F7 Issue 10 Nov 17
Adams Environmental LtdUnit 6, Kimpton Link Business Park, 40 Kimpton Road, SUTTON SM3 9QP
Tel: 020 8641 6000 Fax: 020 8641 0666 Website: www.adamsenvironmental.co.uk Registered Office: Onslow Hall, Little Green, Richmond, TW9 1QH. Company Registration No. 2055824
1.1 Purpose of Survey
Adams Environmental Ltd were instructed by the Client, Mr Brian Stamp, North East London NHS Foundation Trust, to carry out a survey at Thorpe Coombe Hospital, Forest Road, Walthamstow, London, E17 3HP. Buildings for inspection being Wood House, Family Consultation Block (CAMHS), Larkswood Centre, Psychotherapy Clinic and Thorpe Coombe House. The purpose of the re-inspection survey was to collate, confirm and update existing record information relating specifically to known and/or suspected ACMs.
Previous survey and reporting of ACMs has been carried out at Thorpe Coombe Hospital, by Adams Environmental Ltd, as detailed in the Survey Particulars (see 1.2 below).
This Asbestos Re-inspection Survey Report includes information on the location, extent, condition and type of asbestos material identified or suspected, together with comment and recommendations for management of identified asbestos materials, based on the requirements and occupation of the site.
This Report & Register supersedes and replaces the previous Report(s). It is recommended that all previous records are kept and appropriately archived by the Client.
Note: The Report & Register S19334.17 Rev 10 (December 2018) has been re-issued as S19334.17 Rev 11 (March 2019) and now includes Client Duty Holder generated Priority Risk Assessment rating(s) for identified ACMs; Refer to Report Section 3.1 and Appendix I Asbestos Register Glossary for details.
1.2 Survey Particulars Survey Type: Re-inspection (as defined in HSG264) Property Type: Commercial (as defined in HSG264) Original Survey: S6556.1 by Adams Environmental, carried out August 2004
Previous Re-Inspection Surveys
S9062.1 carried out March 2009 S12024.1 carried out July 2011 S13097.1 carried out October 2012 S14405.5 carried out November 2013 S15505.17 carried out October 2014 S16590.17 carried out November 2015 S17726.17 carried out December 2016 S18320.17 carried out December 2017
Lead Surveyor: Orebotse Mmolawa Survey Team: Muhaimen Siddique Date(s) that survey was undertaken: 5th December 2018 Report author: Orebotse MmolawaAdams Environmental Project Manager: Jeff Bowdery
Page 2 of 112
Re-Inspection Survey
Part 1: Introduction
AEL Ref.
Thorpe Coombe Hospital S 19334.17 Rev. 11
SOP10.10F7 Issue 10 Nov 17
Adams Environmental LtdUnit 6, Kimpton Link Business Park, 40 Kimpton Road, SUTTON SM3 9QP
Tel: 020 8641 6000 Fax: 020 8641 0666 Website: www.adamsenvironmental.co.uk Registered Office: Onslow Hall, Little Green, Richmond, TW9 1QH. Company Registration No. 2055824
1.3 Methodology
1.3.1 Site Re-Inspection The Asbestos Register details the locations of positively identified and suspected Asbestos containing
materials (ACMs) and any specific areas of ‘no access’. Within it, data is recorded for type and extent of building component, type of asbestos fibres, with comments on condition, surface treatment and recommendations.
Inspection consisted of re-visiting all specific locations where asbestos occurrences have previously been identified / suspected and recorded in the existing site Asbestos Register information. Comments on condition, surface treatment, and recommendations for remedial action or management, are updated where appropriate, including information where asbestos removal / remedial works have been carried out. The updated Register forms Appendix I of this Report.
1.3.2 Sample Analysis of ACMs Analysis results of sampled materials have been carried forward from the previous survey inspection. No
further sampling has been carried out as part of this re-inspection.
Original sample analysis results, taken as part of the original site inspection, are reproduced at Appendix II of this Report.
Details of sampling and analysis techniques are as documented in the original survey report.
1.3.3 Plans Plans with this Report form Appendix III. These are based on original supplied plans, suitably updated.
Plans are colour-highlighted and annotated to indicate asbestos occurrences.
1.3.4 Photographs Photographs providing an illustration of the asbestos occurrences present at the site are included within
Appendix IV.
1.4 Extent of Survey
Inspection has been made specifically to locations where ACMs have been previously identified as being present, as recorded in the previous survey documentation. Where materials were recorded as ‘non-asbestos’ or where locations were recorded as ‘inspected no asbestos identified’, these statements have been reproduced directly and have not been subject to any further re-inspection / sampling, etc.
The following areas of the site/building were not accessed for the reasons stated:
o Larkswood Centre Ground Floor – No key access to understairs store. o Larkswood Centre 3rd Floor – No key access to walk in cupboard within Office 3.10. o Rodway & Bryson Wards – Buildings found to be demolished at time of December 2017 re-inspection. o Thorpe Coombe House – Ground floor roofspace not accessed (hatch located over server equipment)
Page 3 of 112
Re-Inspection Survey
Part 1: Introduction
AEL Ref.
Thorpe Coombe Hospital S 19334.17 Rev. 11
SOP10.10F7 Issue 10 Nov 17
Adams Environmental LtdUnit 6, Kimpton Link Business Park, 40 Kimpton Road, SUTTON SM3 9QP
Tel: 020 8641 6000 Fax: 020 8641 0666 Website: www.adamsenvironmental.co.uk Registered Office: Onslow Hall, Little Green, Richmond, TW9 1QH. Company Registration No. 2055824
1.5 Survey Re-Inspection Parameters
Within an individual location requiring re-inspection, parts of the building structure that could be accessed due to its design were done so, i.e. via ceiling voids, service risers, ducts etc. Investigation into the sub-surface structure of the building fabric was not made, other than as described herein.
Re-inspection was not continued where damage was likely to be caused to existing building decorations (e.g. opening up of screwed wood riser cover panels that were heavily over-painted or filled to joints).
Similarly, re-inspection did not proceed where the Surveyor deemed that the opening / manoeuvring / replacing of any access cover, etc. could not be safely performed by the Surveyor.
Where previously identified / suspected asbestos materials would be, or were likely to be disturbed by re-inspection, (i.e. opening up of riser covers where unsealed asbestos materials were known to be present behind, etc.) specific re-inspection was not continued in those areas.
The opening up / dismantling of live (and suspected live) electrical equipment, etc. was not within the scope of works.
Re-inspection was curtailed where site equipment, fittings, heavy furniture or any other item prevented or restricted access. Within a location requiring re-inspection, the removal of stock, stored items or other material that prevented or restricted access was not carried out. Where the Client was able to remove such items to facilitate access at the allocated time of inspection, survey was performed.
Equipment, machinery, ducting, etc., was not moved, opened up or examined. Floor finishes (e.g. linoleum and carpets) were not taken up.
Internal building manhole covers believed to be part of the drainage system were not accessed. Other floor duct covers within the building requiring re-inspection were accessed provided that they were free to move and did not require specialist keys or lifting equipment.
Ladders were supplied in order to access heights not exceeding 3.0m for visual re-inspection. Re-inspection of building finishes, surfaces, ceiling voids etc. in excess of 3.0m above clear floor level was not carried out unless means of safe access was provided by the Client at the allocated time of site re-inspection.
NOTE: In the absence of any confirmed record of identified asbestos material to a particular location, it should
not be assumed that asbestos materials will not be encountered in or adjacent that location as part of refurbishment or building maintenance works. Such works should be carried out with caution, given the knowledge of asbestos uses that have been identified on the site.
Particular difficulties are associated with areas where ad-hoc alteration and refurbishment have previously been carried out, and where asbestos may be hidden behind cladding materials. Asbestos is also frequently concealed within the fabric of buildings within sealed voids, as shuttering etc. It is therefore possible that further asbestos containing materials may be found, particularly during electrical rewiring, heating installations and other refurbishments or demolition works.
Adams Environmental Ltd do not accept responsibility for any damage to the building fabric arising from survey inspections, or for any asbestos materials found at a later date which are not specifically detailed in the supplied Report & Register.
Page 4 of 112
Re-Inspection Survey
Part 2: Survey Findings
AEL Ref.
Thorpe Coombe Hospital S 19334.17 Rev. 11
SOP10.10F7 Issue 10 Nov 17
Adams Environmental LtdUnit 6, Kimpton Link Business Park, 40 Kimpton Road, SUTTON SM3 9QP
Tel: 020 8641 6000 Fax: 020 8641 0666 Website: www.adamsenvironmental.co.uk Registered Office: Onslow Hall, Little Green, Richmond, TW9 1QH. Company Registration No. 2055824
The following details the general asbestos occurrences that have been identified during the inspection. Where materials have not been positively identified but are suspected to be present, these are noted. Asbestos products are listed from high friable potential material type to low friable potential material type. 2.1. Lagging (Thermal Insulation)
Typical historical composition and uses
The term ‘lagging’ covers a wide range of thermal insulation materials, including sectional and composite pipe insulation, insulation to boilers and pressure vessels, slabs, blankets, quilts, asbestos paper, felts, plastered applications, together with ‘loose fill’ insulation types. Variable asbestos contents can be encountered. Examples include: 70% asbestos fibre in calcium silicate slabs, 20% in magnesium carbonate insulation, 10-15% in magnesia, calcium silicate and diatomite. Blankets, mattresses, loose fills, papers and felts can approach 100% by volume. All types of asbestos fibres have been used in lagging applications. Typical uses include insulation of boilers, pressure vessels, calorifiers and pipework associated with heating systems. ‘Loose fill’ asbestos was sometimes used as loft insulation, packing around cables between floors. Bagged ‘loose fill’ asbestos material can be found as sound proofing under floors and in walls. The likelihood of fibre release from lagging depends on its composition, friability, state of repair and surface finish. It is particularly susceptible to damage or disturbance during maintenance, or because of leaks from pipes and boilers. ‘Loose fill’ and unsealed materials may readily become airborne if disturbed. Asbestos Licensed Contractor required if any works on material required. 14 day notification to local authority or HSE prior to any major works on material. Locations and uses: CAMHS Family Consultation Block - Basement – Pipe insulation and debris to boiler room duct. Duct running off stairwell in basement area. Insulation debris to floor of duct. (Access point to duct now
sealed). Recommendation: Manage in situ.
CAMHS Family Consultation Block - Basement – Pipe insulation debris to penetration above boiler
room doorway. Pipe work now re-insulated with foil faced MMMF insulation. Recommendation: Manage in situ.
Page 5 of 112
Re-Inspection Survey
Part 2: Survey Findings
AEL Ref.
Thorpe Coombe Hospital S 19334.17 Rev. 11
SOP10.10F7 Issue 10 Nov 17
Adams Environmental LtdUnit 6, Kimpton Link Business Park, 40 Kimpton Road, SUTTON SM3 9QP
Tel: 020 8641 6000 Fax: 020 8641 0666 Website: www.adamsenvironmental.co.uk Registered Office: Onslow Hall, Little Green, Richmond, TW9 1QH. Company Registration No. 2055824
2.2. Asbestos Cement (AC) Products Typical historical composition and uses
Asbestos Cement (AC) was widely used in many building types. Uses included profiled sheets, forming roofing, wall cladding and weather-boarding. Semi and fully compressed flat sheets and partition boards, forming partitions, shuttering, decorative panels, bath panels, soffits, wall and ceiling linings, portable buildings, fire surrounds and composite panels for fire protection. Tiles and slates, used as cladding, decking, promenade tiles and roofing. Pre-formed moulded products including cisterns and tanks, drains, sewer pipes, rainwater goods, flue pipes, roofing components, cable troughs, ventilators and ducts, window boxes. AC products generally contain 10-15% of asbestos fibre bound in a matrix of Portland Cement or autoclaved calcium silicate. All types of asbestos have been used in these materials, the most common being Chrysotile (white asbestos), though Crocidolite (blue) and /or Amosite (brown) can be found. Fibres are firmly bonded and only likely to be released if the material is mechanically damaged or aged, deteriorated or decomposed. Abrasion, handsawing or use of power tools is likely to result in significant fibre release. Locations and uses: Wood House (former Children’s Centre) - External - Front entrance canopy soffit panels, cladding
panels to front & rear end elevations of ‘domed’ roof building. Wood House (former Children’s Centre) - External – Roof tiles to rear extension building. CAMHS Family Consultation Block – Basement – Shuttering and upstand within sealed duct.
Recommendation: AC materials as detailed above; manage in situ.
2.3. Textured Coatings and Paints
Typical historical composition and uses
Used as decorative applied coatings to walls and ceilings. Asbestos was used in small quantities within ‘dry mix’ textured coatings or paints such as ‘Artex’. Approximately 1% to 5% asbestos was used in these materials and fibres would have been released when the ‘dry mix’ materials were prepared. The material is not homogeneous, i.e. asbestos fibres may not be uniformly distributed within the applied coating. Use of such material was extensive through 1960’s to mid 1980’s. In-situ, fibres are well contained in the matrix but release is likely if the existing coating is sanded down or scraped off dry. Locations and uses: Wood House (former Children’s Centre) – Ground Floor – ‘Artex’ type decorative coating to
original ceilings and walls above dropped plaster ceilings. Recommendation: Manage in situ.
Page 6 of 112
Re-Inspection Survey
Part 2: Survey Findings
AEL Ref.
Thorpe Coombe Hospital S 19334.17 Rev. 11
SOP10.10F7 Issue 10 Nov 17
Adams Environmental LtdUnit 6, Kimpton Link Business Park, 40 Kimpton Road, SUTTON SM3 9QP
Tel: 020 8641 6000 Fax: 020 8641 0666 Website: www.adamsenvironmental.co.uk Registered Office: Onslow Hall, Little Green, Richmond, TW9 1QH. Company Registration No. 2055824
2.4. Compressed Asbestos Fibre (CAF) Gaskets Typical historical composition and uses
CAF materials contain asbestos fibres bonded with specially selected polymers suitable for pressures up to 2000 psi and temperatures up to 600 0C. Gaskets have asbestos fibre content approaching 100% Chrysotile (white asbestos). Such gaskets are required where two metal surfaces are joined, to allow easy future separation. CAF materials are used to seal pipework flanges, boilers and other industrial plant. The gaskets may be pre-shaped or cut from large CAF sheets. Fibres can be released when the material is cut, abraded or torn during gasket removal or gasket shaping from sheet materials. Locations and uses: Thorpe Coombe House – Basement – Gaskets to pipe flanges.
Recommendation: Manage in situ.
Page 7 of 112
Re-Inspection Survey
Part 3: Recommendations
AEL Ref.
Thorpe Coombe Hospital S 19334.17 Rev. 11
SOP10.10F7 Issue 10 Nov 17
Adams Environmental LtdUnit 6, Kimpton Link Business Park, 40 Kimpton Road, SUTTON SM3 9QP
Tel: 020 8641 6000 Fax: 020 8641 0666 Website: www.adamsenvironmental.co.uk Registered Office: Onslow Hall, Little Green, Richmond, TW9 1QH. Company Registration No. 2055824
3.1 Management of Asbestos Materials
Regulation 4 of The Control of Asbestos Regulations (2012), ‘The management of asbestos in non-domestic premises’ places a duty on those who have repair and maintenance responsibilities for premises, because of a contract or tenancy, to manage the risk of asbestos in those premises. Where there is no specific contract or tenancy the person who is deemed to be in control of building maintenance & repair is regarded as the ‘duty holder’. The ‘duty holder’ is required to:
1. Take reasonable steps to find materials in premises likely to contain asbestos and check their
condition 2. Presume that materials contain asbestos unless there is strong evidence to suppose they do not 3. Make a written record of the location and condition of asbestos and presumed asbestos-containing
materials and keep such record(s) up to date 4. Assess the risk of the likelihood of anyone being exposed to these materials 5. Prepare a plan to manage the identified risk and put it into effect to ensure that:
a) Any material known or presumed to contain asbestos is kept in a good state of repair. b) Any material that contains or is presumed to contain asbestos is, because of the risks
associated with its location or condition, repaired or if necessary removed. c) Information on the location and condition of the material is given to anyone potentially at risk. d) The condition of identified and presumed asbestos materials is monitored. e) The management plan, including the arrangements made to put it in place, is monitored and
regularly reviewed.
The information relating to identified /suspected asbestos occurrences supplied within this Survey Re-inspection Report will be of assistance to the Duty Holder in complying with the requirements of The Control of Asbestos Regulations 2012. As stipulated in HSG 264, ‘Asbestos: The Survey Guide’, the Asbestos Register contains a Materials Assessment (MA) rating for each identified asbestos occurrence. (Type of asbestos product, asbestos fibre content, condition of the material and presence of a sealant are the assessed factors). This gives initial guidance as to the potential for fibre release should the material become disturbed. Priority Assessments for each identified ACM are also provided in the Register. These have been generated from Client Duty Holder supplied information and are based on ‘human risk’ factors related to the likelihood of person(s) actually disturbing the material and include the location, extent and accessibility of the material, the use of the location and the type, frequency, volume and duration of occupancy for both normal use and maintenance activities. Consideration of these factors allows formal Priority Risk Assessments for each identified asbestos occurrence to be made. HSE document HSG227 gives comprehensive guidance for management requirements of the Duty Holder under the Asbestos Regulations and includes specific recommendations for Priority & Risk Assessments.
Page 8 of 112
Re-Inspection Survey
Part 3: Recommendations
AEL Ref.
Thorpe Coombe Hospital S 19334.17 Rev. 11
SOP10.10F7 Issue 10 Nov 17
Adams Environmental LtdUnit 6, Kimpton Link Business Park, 40 Kimpton Road, SUTTON SM3 9QP
Tel: 020 8641 6000 Fax: 020 8641 0666 Website: www.adamsenvironmental.co.uk Registered Office: Onslow Hall, Little Green, Richmond, TW9 1QH. Company Registration No. 2055824
3.2 Legislation & Approved Guidance
The key legislative documents relating to works with asbestos materials are: 'The Health and Safety at Work etc. Act' (1974) 'The Control of Asbestos Regulations' (2012) ‘The Management of Health and Safety at Work Regulations’ (1999)
The key HSE approved guidance documents relating to management of asbestos materials are:
L143 ACoP – Managing and Working with Asbestos HSG 227 – A comprehensive guide to managing asbestos in premises
Further advice is available from the HSE, the local Environmental Health Officer and Adams Environmental Ltd.
Page 9 of 112
Re-Inspection Survey
Appendix I: Asbestos Register
AEL Ref.
Thorpe Coombe Hospital S 19334.17 Rev. 11
SOP10.10F7 Issue 10 Nov 17
Adams Environmental LtdUnit 6, Kimpton Link Business Park, 40 Kimpton Road, SUTTON SM3 9QP
Tel: 020 8641 6000 Fax: 020 8641 0666 Website: www.adamsenvironmental.co.uk Registered Office: Onslow Hall, Little Green, Richmond, TW9 1QH. Company Registration No. 2055824
Register Glossary
Survey Report No / Issue Date
The Report Number issued by Adams Environmental Ltd is unique to the site. The date of authorisation records the date that the Report was authorised issued by
Adams Environmental Ltd to the Client. The Revision Issue number indicates the re-issue following any update.
Site Identification
The site name, and where appropriate, the relevant building and floor level are indicated.
Location (Area/Room)
The reference code / name of each surveyed building area as found on site or as used on any supplied plans. Where none is present a suitable reference relevant to building and floor level is given at time of site inspection to allow cross-reference between Register and plans.
Sample N° The reference given to the sample when it was taken from the parent material on site, as detailed in Appendix II: Materials Report. The suffix (A) indicates the sample has been taken from this location and analysed. The suffix (M) indicates that the result is mastered from similar analysed material.
Building Component (Product Type)
The most appropriate description of the material as a building component. This may reflect the position of the material rather than its purpose, e.g. an asbestos panel fixed to the rear of a riser access hatch may be termed ‘Door Panel’ as opposed to ‘Fire Protection’.
Asbestos Content
The type of asbestos fibre identified by sampling and analysis. Further details are given within Appendix II: Materials Report. Chrysotile, commonly known as White asbestos Amosite, commonly known as Brown asbestos Crocidolite, commonly known as Blue asbestos Where no asbestos has been detected in the sampled material, this is indicated.
Extent An approximate extent of the material is given in either square or linear metres. The symbol @ is used to denote the extent of each instance of a material where it has been used discretely and severally. These measurements are for guidance only.
Condition Good: No visible damage. Satisfactory: Asbestos is in generally sound condition with no / little exposure noted. Fair: In average condition with minor areas of damage / surface exposure. Poor: The material is in damaged or deteriorated condition and/or in debris form.
Surface Treatment
An indication of the exposure of the surface of the material, relevant to the Product Type. Sealants may be in liquid (e.g. paint encapsulant) or rigid form (e.g. overclad with board). Composite: Materials containing asbestos; reinforced plastics, resins, vinyl tiles, etc Enclosed: The asbestos material is sealed by a protection greater than paint application
alone. Sealed: The asbestos material is sealed by paint or other similar encapsulant. Partially Sealed: Sealant is present but does not completely cover the material or is
deteriorating. Unsealed: The material has not been sealed, and the surface is exposed.
Page 10 of 112
Re-Inspection Survey
Appendix I: Asbestos Register
AEL Ref.
Thorpe Coombe Hospital S 19334.17 Rev. 11
SOP10.10F7 Issue 10 Nov 17
Adams Environmental LtdUnit 6, Kimpton Link Business Park, 40 Kimpton Road, SUTTON SM3 9QP
Tel: 020 8641 6000 Fax: 020 8641 0666 Website: www.adamsenvironmental.co.uk Registered Office: Onslow Hall, Little Green, Richmond, TW9 1QH. Company Registration No. 2055824
Material Assessment
The numerical score given for each identified asbestos occurrence is derived from the application of a material assessment algorithm. The Materials Assessment (MA) is generated by scoring Type, Condition, Surface Treatment and Asbestos Fibre Type for each asbestos occurrence. Scores (0, 1, 2 or 3) are given for each parameter and then totalled to give a final score out of 12. This algorithm is based on parameters described in HSG 264 and Adams Environmental Ltd’s documented in-house procedures.
MA scores of 10 or more are regarded as having a high potential to release fibres, if disturbed. Scores of between 7 and 9 are regarded as having medium potential and between 5 and 6 a low potential. Scores of 4 or less have a very low potential to release fibres. Note: The Materials Assessment (MA) score provides guidance only and applies only to positively identified asbestos occurrences. (The use of the Materials Assessment by the Client as the basis for risk assessment is described further in Part 3 of this Report).
Accessibility Direct access: The material can be directly accessed within the location, i.e. an AIB panel fitted to the rear face of a fire door / asbestos lagging to pipework attached to a boiler.
Indirect access: The material cannot be directly accessed within the location, i.e. an AIB firebreak panel concealed within a suspended ceiling void / an internal asbestos lining beneath a sealed metal boiler body casing.
Summary One of the following summaries will be indicated for each Register entry: ASBESTOS PRESENT ASBESTOS SUSPECTED - This will be indicated when a feature within a location,
considered by the Surveyor to fall within the scope of the inspection, could not be accessed, either for inspection, i.e. an inaccessible riser cover panel, or sampling, i.e. operational machinery).
LOCATION NOT INSPECTED; ASBESTOS SUSPECTED - Indicated when access could not be gained to a location). Where the summary ASBESTOS SUSPECTED or is given, a high or low presumption of the likelihood of asbestos materials being present is indicated, based on the Surveyor’s assessment at the time of site inspection.
MATERIAL SAMPLED NO ASBESTOS DETECTED LOCATION INSPECTED; NO ASBESTOS IDENTIFIED - This entry records that
inspection of the indicated location has been made and that, within the defined parameters and scope of re-inspection, no asbestos materials were positively identified).
ASBESTOS REMOVED. Comment An appropriate descriptive comment is provided for each record.
Recomm-endations
These are Adams Environmental Ltd’s suggested control options for identified and suspected asbestos occurrences, based on the location, type and condition of asbestos material(s) (Materials Assessment rating) as found at the time of survey inspection. The appropriate and effective asbestos management action / prioritisation of works, etc., by the Duty Holder, will need to consider additional factors. These will include; The material extent; The location use; The occupancy type, frequency and volume; The likely maintenance works by type and frequency; Other pertinent factors that will be known to the Duty Holder or can be obtained by him from those with responsibility for the building(s) use and maintenance, etc. Restrict access to the asbestos material - Given when the condition of the asbestos
material is considered to present a significant hazard within the location in which it has been identified.
Page 11 of 112
Re-Inspection Survey
Appendix I: Asbestos Register
AEL Ref.
Thorpe Coombe Hospital S 19334.17 Rev. 11
SOP10.10F7 Issue 10 Nov 17
Adams Environmental LtdUnit 6, Kimpton Link Business Park, 40 Kimpton Road, SUTTON SM3 9QP
Tel: 020 8641 6000 Fax: 020 8641 0666 Website: www.adamsenvironmental.co.uk Registered Office: Onslow Hall, Little Green, Richmond, TW9 1QH. Company Registration No. 2055824
Improvement works required - Given when an asbestos material in other than satisfactory condition is found and given its location, requires remedial works to be carried out to place it in satisfactory condition. Where asbestos materials are to remain in-situ following identification, they should be maintained in / placed into a sound, sealed condition, undamaged, not releasing dust and should not be disturbed. This may be achieved by carrying out appropriate repair, encapsulation, protection works, etc. or by placing appropriate restrictions on the access / use of the location where the material is present.
Monitor material condition - Given when an asbestos material has been identified in
satisfactory condition at the time of site inspection. Where such materials are to remain in-situ, monitoring to confirm that satisfactory conditions are being maintained is required. This would normally involve site re-inspection by a competent person and updating / recording of results, etc. The timescale of re-inspections will be determined by the likelihood of the material condition changing, given factors surrounding it. These will include the physical location of the asbestos material and the likelihood of its being disturbed.
Programme further investigation - Given when asbestos materials are suspected to be
present but, within the scope and parameters of the inspection carried out, have not been positively identified, or for locations where access could not be gained at the time of site inspection.
Photo ID Where photographs are included, this number correlates between the Asbestos Register and
Appendix IV of this Report.
Page 12 of 112
Re-Inspection Survey
Appendix I: Asbestos Register
AEL Ref.
Thorpe Coombe Hospital S 19334.17 Rev. 11
SOP10.10F7 Issue 10 Nov 17
Adams Environmental LtdUnit 6, Kimpton Link Business Park, 40 Kimpton Road, SUTTON SM3 9QP
Tel: 020 8641 6000 Fax: 020 8641 0666 Website: www.adamsenvironmental.co.uk Registered Office: Onslow Hall, Little Green, Richmond, TW9 1QH. Company Registration No. 2055824
Priority Risk Assessments Note: The following information is provided in the Register for each identified asbestos occurrence. Priority Risk Assessment Ratings are generated from documented information provided by the Client (Duty Holder) to AEL. The Client is recommended to assess each Risk Assessment & confirm that assessed factors are appropriate & correct. Where the Client considers that a priority assessment requires adjustment, then this should be recorded & actioned. Priority Risk Assessment
Further to the material assessment recorded for positively identified asbestos occurrences (as detailed above), the priority assessment algorithm is based on parameters described in HSE Guidance ‘HSG 227 – A Comprehensive Guide to Managing Asbestos in Premises (2002)’. Information fields, as described below, are collated. This requires scrutiny from the Client to confirm accurate data. Four fields are each scored out of 4 parameters (0, 1, 2, or 3), (averaged when appropriate) to derive a total score out of 12, to then be used with the material assessment score to generate a Risk Assessment.
Likelihood of Disturbance Location The size of location within which the material exists, i.e. external, internal; large room, small room,
confined space, etc. Material Accessibility
The ease with which the material, given its location, can be accessed and therefore disturbed, i.e. unlikely to be disturbed, occasionally likely to be disturbed, easily disturbed, routinely disturbed. For example: Within a ceiling void – unlikely to be disturbed. Panelling to a corridor fire door – routinely disturbed.
Material Extent
The volume of the material within the recorded location.
Normal Occupant Activity Main Type of Activity
A rating of the likelihood of the main activity that is being carried out in the location where the asbestos material is present having some incidental affect on the asbestos. For example: Asbestos present in a disused store room – rare disturbance activity. Asbestos present to a fire door in a heavily trafficked corridor – high disturbance activity.
Secondary Activities
A rating of the likelihood of secondary activities that are carried out in the location where the asbestos material is present having some incidental affect on the asbestos.
Human Exposure PotentialNumber of Occupants
The maximum number of occupants considered likely to occupy the location where the asbestos material is present at any one time.
Frequency of Use
The frequency of use of the location in which the asbestos is present, i.e. daily, weekly, monthly, etc.
Time in Area The maximum period of continuous time likely to be spent in the location by the occupants, i.e. less than 1 hour, between 1 & 6 hours, etc.
Maintenance Activity Frequency of Maintenance
The frequency of maintenance or other similar likely disturbance activities that may affect the asbestos material. For example: Unlikely to be disturbed, likely to be disturbed less than once per year, more than once per year, more than once a month.
Maintenance Activity
A rating of the likelihood of the maintenance activity that is carried out in the location where the asbestos material is present having some direct affect on the asbestos. For example: Minor disturbance likely – i.e. a possibility of contact when gaining access. Low disturbance – i.e. changing lightbulbs only to inset lighting in an asbestos panelled ceiling. High disturbance – i.e. needing to remove asbestos panels to gain access to drainage pipe rodding positions.
Risk Assessment Score
The risk assessment score is derived from the Materials Assessment & Priority Assessment ratings that have been collated and combined. Scores of 20 -24 are regarded as having a VERY HIGH risk rating. Scores of 15-19 are regarded as having HIGH risk rating. Scores of 11-14 are regarded as MEDIUM risk rating, scores 6-10 LOW risk rating and scores of 5 or less VERY LOW risk rating.
Page 13 of 112
Ground FloorWood House ASBESTOS REGISTER
S 19334.17Revision Issue N° 11
March 2019Wood House
10m²Chrysotile05 M Decorative Coating
Corridor between G08 & G09
4/12Satisfactory condition
Indirect access
'Artex' type decorative coating remains to original ceiling, present in void area above existing ceilings of refurbished Woodhouse Building. Re-inspection dates 20/03/09 (Rev 2) & 05/07/11 (Rev 3).
Sealed
Area/Room Sample No
Building Component
Asbestos Content
Extent Condition Surface Treatment
Material Assessment
Recommendations/ Summary
Accessibility Photo ID
Re-inspected 24/09/12 - No access to inspect, dropped plaster ceiling present throughout.Re-inspected 18/09/13 - No Change.Re-inspected 24/09/14 - No Change.Re-inspected 28/10/15 - No ChangeRe-inspected 09/12/16 - No ChangeRe-inspected 07/12/17 - No ChangeRe-inspected 05/12/18 - No Change
Monitor condition of material.
ASBESTOS PRESENT
< 1 hour < 1 per year
Frequency of
Maintenance
Risk Assessment
Location
Rooms up to 100m²
Material Accessiblity
Usually inaccessible
or unlikely to be disturbed
No.of Occupants
None
Main Activity in Area
Secondary Activity in Area
Rare disturbance activity
Rare disturbance activity
Material Extent
<10m² or < 10m pipe run
Frequency of Use
Daily
Time in Area
Maintenance Activity
Low disturbance
Low
50m²Chrysotile05 M Decorative Coating
G.03 - 07 – Offices 3, 4, 5, 6 & 7
3/12Good condition
Indirect access
'Artex' type decorative coating remains to original ceiling, present in void area above existing ceilings of refurbished Woodhouse Building. Re-inspection dates 20/03/09 (Rev 2) & 05/07/11 (Rev 3).
Sealed
Area/Room Sample No
Building Component
Asbestos Content
Extent Condition Surface Treatment
Material Assessment
Recommendations/ Summary
Accessibility Photo ID
Re-inspected 24/09/12 - No access to inspect, dropped plaster ceiling present throughout.Re-inspected 18/09/13 - Nkeys to roofspace provided during 2013 re-inspection. Textured coating to original ceiling (above dropped plaster) was inspected and identified in satisfactory condition.Re-inspected 24/09/14 - No Change.Re-inspected 28/10/15 - No ChangeRe-inspected 09/12/16 - No ChangeRe-inspected 07/12/17 - No ChangeRe-inspected 05/12/18 - No Change
Monitor condition of material.
ASBESTOS PRESENT
> 1 to < 6 hours
< 1 per year
Frequency of
Maintenance
Risk Assessment
Location
Rooms up to 100m²
Material Accessiblity
Usually inaccessible
or unlikely to be disturbed
No.of Occupants
4 to 10
Main Activity in Area
Secondary Activity in Area
Rare disturbance activity
Rare disturbance activity
Material Extent
> 10m² to < 50m² or > 10m to > 50m pipe run
Frequency of Use
Daily
Time in Area
Maintenance Activity
Low disturbance
Low
Prepared by Adams Environmental Ltd See survey report for scope/limitations of inspectionPage 14 of 112
Ground FloorWood House ASBESTOS REGISTER
S 19334.17Revision Issue N° 11
March 2019Wood House
20m²Chrysotile05 M Decorative Coating
G.11 – Office 3/12Good condition
Indirect access
'Artex' type decorative coating remains to original ceiling, present in void area above existing ceilings of refurbished Woodhouse Building. Re-inspection dates 20/03/09 (Rev 2) & 05/07/11 (Rev 3).
Sealed
Area/Room Sample No
Building Component
Asbestos Content
Extent Condition Surface Treatment
Material Assessment
Recommendations/ Summary
Accessibility Photo ID
Re-inspected 24/09/12 - No access to inspect, dropped plaster ceiling present throughout.Re-inspected 18/09/13 - No Change.Re-inspected 24/09/14 - No Change.Re-inspected 28/10/15 - No ChangeRe-inspected 09/12/16 - No ChangeRe-inspected 07/12/17 - No ChangeRe-inspected 05/12/18 - No Change
Monitor condition of material.
ASBESTOS PRESENT
> 1 to < 6 hours
< 1 per year
Frequency of
Maintenance
Risk Assessment
Location
Rooms up to 100m²
Material Accessiblity
Usually inaccessible
or unlikely to be disturbed
No.of Occupants
1 to 3
Main Activity in Area
Secondary Activity in Area
Rare disturbance activity
Rare disturbance activity
Material Extent
> 10m² to < 50m² or > 10m to > 50m pipe run
Frequency of Use
Weekly
Time in Area
Maintenance Activity
Low disturbance
Low
20m²Chrysotile05 M Decorative Coating
G.11 – Lobby to Area Office 11
3/12Good condition
Indirect access
'Artex' type decorative coating remains to original ceiling, present in void area above existing ceilings of refurbished Woodhouse Building. Re-inspection dates 20/03/09 (Rev 2) & 05/07/11 (Rev 3).
Sealed
Area/Room Sample No
Building Component
Asbestos Content
Extent Condition Surface Treatment
Material Assessment
Recommendations/ Summary
Accessibility Photo ID
Re-inspected 24/09/12 - No access to inspect, dropped plaster ceiling present throughout.Re-inspected 18/09/13 - No Change.Re-inspected 24/09/14 - No Change.Re-inspected 28/10/15 - No ChangeRe-inspected 09/12/16 - No ChangeRe-inspected 07/12/17 - No ChangeRe-inspected 05/12/18 - No Change
Monitor condition of material.
ASBESTOS PRESENT
< 1 hour < 1 per year
Frequency of
Maintenance
Risk Assessment
Location
Rooms up to 100m²
Material Accessiblity
Usually inaccessible
or unlikely to be disturbed
No.of Occupants
None
Main Activity in Area
Secondary Activity in Area
Rare disturbance activity
Rare disturbance activity
Material Extent
> 10m² to < 50m² or > 10m to > 50m pipe run
Frequency of Use
Daily
Time in Area
Maintenance Activity
Low disturbance
Low
Prepared by Adams Environmental Ltd See survey report for scope/limitations of inspectionPage 15 of 112
Ground FloorWood House ASBESTOS REGISTER
S 19334.17Revision Issue N° 11
March 2019Wood House
Suspect HeaterG.14 – Photocopy Room
SUSPECT
No access behind internal metal panel to metal housed perimeter heating system. Internal components may contain asbestos.
Area/Room Sample No
Building Component
Asbestos Content
Extent Condition Surface Treatment
Material Assessment
Recommendations/ Summary
Accessibility Photo ID
Re-inspected 24/09/12 - No Change.Re-inspected 18/09/13 - No Change.Re-inspected 24/09/14 - No Change.Re-inspected 28/10/15 - No ChangeRe-inspected 09/12/16 - No ChangeRe-inspected 07/12/17 - No ChangeRe-inspected 05/12/18 - No Change
Low presumption of the presence of asbestos materials.
Programme further investigation.
ASBESTOS SUSPECTED
Frequency of
Maintenance
Risk Assessment
Location Material Accessiblity
No.of Occupants
Main Activity in Area
Secondary Activity in Area
Material Extent
Frequency of Use
Time in Area
Maintenance Activity
Suspect HeaterG.15 – Office SUSPECT
No access behind internal metal panel to metal housed perimeter heating system. Internal components may contain asbestos.
Area/Room Sample No
Building Component
Asbestos Content
Extent Condition Surface Treatment
Material Assessment
Recommendations/ Summary
Accessibility Photo ID
Re-inspected 24/09/12 - No Change.Re-inspected 18/09/13 - No Change.Re-inspected 24/09/14 - No Change.Re-inspected 28/10/15 - No ChangeRe-inspected 09/12/16 - No ChangeRe-inspected 07/12/17 - No ChangeRe-inspected 05/12/18 - No Change
Low presumption of the presence of asbestos materials.
Programme further investigation.
ASBESTOS SUSPECTED
Frequency of
Maintenance
Risk Assessment
Location Material Accessiblity
No.of Occupants
Main Activity in Area
Secondary Activity in Area
Material Extent
Frequency of Use
Time in Area
Maintenance Activity
Prepared by Adams Environmental Ltd See survey report for scope/limitations of inspectionPage 16 of 112
Ground FloorWood House ASBESTOS REGISTER
S 19334.17Revision Issue N° 11
March 2019Wood House
Suspect HeaterG.16 – Office SUSPECT
No access behind internal metal panel to metal housed perimeter heating system. Internal components may contain asbestos.
Area/Room Sample No
Building Component
Asbestos Content
Extent Condition Surface Treatment
Material Assessment
Recommendations/ Summary
Accessibility Photo ID
Re-inspected 24/09/12 - No Change.Re-inspected 18/09/13 - No Change.Re-inspected 24/09/14 - No Change.Re-inspected 28/10/15 - No ChangeRe-inspected 09/12/16 - No ChangeRe-inspected 07/12/17 - No ChangeRe-inspected 05/12/18 - No Change
Low presumption of the presence of asbestos materials.
Programme further investigation.
ASBESTOS SUSPECTED
Frequency of
Maintenance
Risk Assessment
Location Material Accessiblity
No.of Occupants
Main Activity in Area
Secondary Activity in Area
Material Extent
Frequency of Use
Time in Area
Maintenance Activity
Suspect HeaterG.17 – Lobby SUSPECT
No access behind internal metal panel to metal housed perimeter heating system. Internal components may contain asbestos.
Area/Room Sample No
Building Component
Asbestos Content
Extent Condition Surface Treatment
Material Assessment
Recommendations/ Summary
Accessibility Photo ID
Re-inspected 24/09/12 - No Change.Re-inspected 18/09/13 - No Change.Re-inspected 24/09/14 - No Change.Re-inspected 28/10/15 - No ChangeRe-inspected 09/12/16 - No ChangeRe-inspected 07/12/17 - No ChangeRe-inspected 05/12/18 - No Change
Low presumption of the presence of asbestos materials.
Programme further investigation.
ASBESTOS SUSPECTED
Frequency of
Maintenance
Risk Assessment
Location Material Accessiblity
No.of Occupants
Main Activity in Area
Secondary Activity in Area
Material Extent
Frequency of Use
Time in Area
Maintenance Activity
Prepared by Adams Environmental Ltd See survey report for scope/limitations of inspectionPage 17 of 112
Ground FloorWood House ASBESTOS REGISTER
S 19334.17Revision Issue N° 11
March 2019Wood House
Suspect HeaterG.17 – Kitchen / Staff Room
SUSPECT
No access behind internal metal panel to metal housed perimeter heating system. Internal components may contain asbestos.
Area/Room Sample No
Building Component
Asbestos Content
Extent Condition Surface Treatment
Material Assessment
Recommendations/ Summary
Accessibility Photo ID
Re-inspected 24/09/12 - No Change.Re-inspected 18/09/13 - No Change.Re-inspected 24/09/14 - No Change.Re-inspected 28/10/15 - No ChangeRe-inspected 09/12/16 - No ChangeRe-inspected 07/12/17 - No ChangeRe-inspected 05/12/18 - No Change
Low presumption of the presence of asbestos materials.
Programme further investigation.
ASBESTOS SUSPECTED
Frequency of
Maintenance
Risk Assessment
Location Material Accessiblity
No.of Occupants
Main Activity in Area
Secondary Activity in Area
Material Extent
Frequency of Use
Time in Area
Maintenance Activity
Suspect HeaterG.18 – Office (east)
SUSPECT
No access behind internal metal panel to metal housed perimeter heating system. Internal components may contain asbestos.
Area/Room Sample No
Building Component
Asbestos Content
Extent Condition Surface Treatment
Material Assessment
Recommendations/ Summary
Accessibility Photo ID
Re-inspected 24/09/12 - No Change.Re-inspected 18/09/13 - No Change.Re-inspected 24/09/14 - No Change.Re-inspected 28/10/15 - No ChangeRe-inspected 09/12/16 - No ChangeRe-inspected 07/12/17 - No ChangeRe-inspected 05/12/18 - No Change
Low presumption of the presence of asbestos materials.
Programme further investigation.
ASBESTOS SUSPECTED
Frequency of
Maintenance
Risk Assessment
Location Material Accessiblity
No.of Occupants
Main Activity in Area
Secondary Activity in Area
Material Extent
Frequency of Use
Time in Area
Maintenance Activity
Prepared by Adams Environmental Ltd See survey report for scope/limitations of inspectionPage 18 of 112
Ground FloorWood House ASBESTOS REGISTER
S 19334.17Revision Issue N° 11
March 2019Wood House
Suspect HeaterG.18 – Office (west)
SUSPECT
No access behind internal metal panel to metal housed perimeter heating system. Internal components may contain asbestos.
Area/Room Sample No
Building Component
Asbestos Content
Extent Condition Surface Treatment
Material Assessment
Recommendations/ Summary
Accessibility Photo ID
Re-inspected 24/09/12 - No Change.Re-inspected 18/09/13 - No Change.Re-inspected 24/09/14 - No Change.Re-inspected 28/10/15 - No ChangeRe-inspected 09/12/16 - No ChangeRe-inspected 07/12/17 - No ChangeRe-inspected 05/12/18 - No Change
Low presumption of the presence of asbestos materials.
Programme further investigation.
ASBESTOS SUSPECTED
Frequency of
Maintenance
Risk Assessment
Location Material Accessiblity
No.of Occupants
Main Activity in Area
Secondary Activity in Area
Material Extent
Frequency of Use
Time in Area
Maintenance Activity
Suspect HeaterG.20 – Office SUSPECT
No access behind internal metal panel to metal housed perimeter heating system. Internal components may contain asbestos.
Area/Room Sample No
Building Component
Asbestos Content
Extent Condition Surface Treatment
Material Assessment
Recommendations/ Summary
Accessibility Photo ID
Re-inspected 24/09/12 - No Change.Re-inspected 18/09/13 - No Change.Re-inspected 24/09/14 - No Change.Re-inspected 28/10/15 - No ChangeRe-inspected 09/12/16 - No ChangeRe-inspected 07/12/17 - No ChangeRe-inspected 05/12/18 - No Change
Low presumption of the presence of asbestos materials.
Programme further investigation.
ASBESTOS SUSPECTED
Frequency of
Maintenance
Risk Assessment
Location Material Accessiblity
No.of Occupants
Main Activity in Area
Secondary Activity in Area
Material Extent
Frequency of Use
Time in Area
Maintenance Activity
Prepared by Adams Environmental Ltd See survey report for scope/limitations of inspectionPage 19 of 112
Ground FloorWood House ASBESTOS REGISTER
S 19334.17Revision Issue N° 11
March 2019Wood House
Suspect HeaterG.21 – Office SUSPECT
No access behind internal metal panel to metal housed perimeter heating system. Internal components may contain asbestos.
Area/Room Sample No
Building Component
Asbestos Content
Extent Condition Surface Treatment
Material Assessment
Recommendations/ Summary
Accessibility Photo ID
Re-inspected 24/09/12 - No Change.Re-inspected 18/09/13 - No Change.Re-inspected 24/09/14 - No Change.Re-inspected 28/10/15 - No ChangeRe-inspected 09/12/16 - No ChangeRe-inspected 07/12/17 - No ChangeRe-inspected 05/12/18 - No Change
Low presumption of the presence of asbestos materials.
Programme further investigation.
ASBESTOS SUSPECTED
Frequency of
Maintenance
Risk Assessment
Location Material Accessiblity
No.of Occupants
Main Activity in Area
Secondary Activity in Area
Material Extent
Frequency of Use
Time in Area
Maintenance Activity
Suspect HeaterG.22 – Office SUSPECT
No access behind internal metal panel to metal housed perimeter heating system. Internal components may contain asbestos.
Area/Room Sample No
Building Component
Asbestos Content
Extent Condition Surface Treatment
Material Assessment
Recommendations/ Summary
Accessibility Photo ID
Re-inspected 24/09/12 - No Change.Re-inspected 18/09/13 - No Change.Re-inspected 24/09/14 - No Change.Re-inspected 28/10/15 - No ChangeRe-inspected 09/12/16 - No ChangeRe-inspected 07/12/17 - No ChangeRe-inspected 05/12/18 - No Change
Low presumption of the presence of asbestos materials.
Programme further investigation.
ASBESTOS SUSPECTED
Frequency of
Maintenance
Risk Assessment
Location Material Accessiblity
No.of Occupants
Main Activity in Area
Secondary Activity in Area
Material Extent
Frequency of Use
Time in Area
Maintenance Activity
Prepared by Adams Environmental Ltd See survey report for scope/limitations of inspectionPage 20 of 112
Ground FloorWood House ASBESTOS REGISTER
S 19334.17Revision Issue N° 11
March 2019Wood House
Suspect HeaterG.23 – Cleaner's Cupboard
SUSPECT
No access behind internal metal panel to metal housed perimeter heating system. Internal components may contain asbestos.
Area/Room Sample No
Building Component
Asbestos Content
Extent Condition Surface Treatment
Material Assessment
Recommendations/ Summary
Accessibility Photo ID
Re-inspected 24/09/12 - No Change.Re-inspected 18/09/13 - No Change.Re-inspected 24/09/14 - No Change.Re-inspected 28/10/15 - No ChangeRe-inspected 09/12/16 - No ChangeRe-inspected 07/12/17 - No ChangeRe-inspected 05/12/18 - No Change
Low presumption of the presence of asbestos materials.
Programme further investigation.
ASBESTOS SUSPECTED
Frequency of
Maintenance
Risk Assessment
Location Material Accessiblity
No.of Occupants
Main Activity in Area
Secondary Activity in Area
Material Extent
Frequency of Use
Time in Area
Maintenance Activity
Suspect HeaterG.24 – Office SUSPECT
No access behind internal metal panel to metal housed perimeter heating system. Internal components may contain asbestos.
Area/Room Sample No
Building Component
Asbestos Content
Extent Condition Surface Treatment
Material Assessment
Recommendations/ Summary
Accessibility Photo ID
Re-inspected 24/09/12 - No Change.Re-inspected 18/09/13 - No Change.Re-inspected 24/09/14 - No Change.Re-inspected 28/10/15 - No ChangeRe-inspected 09/12/16 - No ChangeRe-inspected 07/12/17 - No ChangeRe-inspected 05/12/18 - No Change
Low presumption of the presence of asbestos materials.
Programme further investigation.
ASBESTOS SUSPECTED
Frequency of
Maintenance
Risk Assessment
Location Material Accessiblity
No.of Occupants
Main Activity in Area
Secondary Activity in Area
Material Extent
Frequency of Use
Time in Area
Maintenance Activity
Prepared by Adams Environmental Ltd See survey report for scope/limitations of inspectionPage 21 of 112
ExternalWood House ASBESTOS REGISTER
S 19334.17Revision Issue N° 11
March 2019Wood House
12m²Chrysotile01 M AC CladdingRear Elevation of Original Building (West)
3/12Good condition
Direct access
2 N° layers of corrugated profile asbestos cement (AC) cladding present to top section of wall above windows. Re-inspection dates 20/03/09 (Rev 2) & 05/07/11 (Rev 3).
Sealed
Area/Room Sample No
Building Component
Asbestos Content
Extent Condition Surface Treatment
Material Assessment
Recommendations/ Summary
Accessibility Photo ID
Re-inspected 24/09/12 - No Change.Re-inspected 18/09/13 - No Change.Re-inspected 24/09/14 - No Change.Re-inspected 28/10/15 - No ChangeRe-inspected 09/12/16 - No ChangeRe-inspected 07/12/17 - No ChangeRe-inspected 05/12/18 - No Change
Monitor condition of material.
ASBESTOS PRESENT
Very Low< 1 hour ACM unlikely to be
disturbed for maintenance
Frequency of
Maintenance
Risk Assessment
Location
Outdoors
Material Accessiblity
Usually inaccessible
or unlikely to be disturbed
No.of Occupants
None
Main Activity in Area
Secondary Activity in Area
Rare disturbance activity
Rare disturbance activity
Material Extent
> 10m² to < 50m² or > 10m to > 50m pipe run
Frequency of Use
Infrequent
Time in Area
Maintenance Activity
Minor disturbance
3m²Chrysotile02 M AC SoffitEntrance Canopy
3/12Good condition
Direct access
Asbestos cement (AC) soffit panel to entrance canopy at front elevation. Re-inspection dates 20/03/09 (Rev 2) & 05/07/11 (Rev 3).
Sealed 01
Area/Room Sample No
Building Component
Asbestos Content
Extent Condition Surface Treatment
Material Assessment
Recommendations/ Summary
Accessibility Photo ID
Re-inspected 24/09/12 - No Change.Re-inspected 18/09/13 - No Change.Re-inspected 24/09/14 - No Change.Re-inspected 28/10/15 - No ChangeRe-inspected 09/12/16 - No ChangeRe-inspected 07/12/17 - No ChangeRe-inspected 05/12/18 - No Change
Monitor condition of material.
ASBESTOS PRESENT
Very Low< 1 hour ACM unlikely to be
disturbed for maintenance
Frequency of
Maintenance
Risk Assessment
Location
Outdoors
Material Accessiblity
Usually inaccessible
or unlikely to be disturbed
No.of Occupants
None
Main Activity in Area
Secondary Activity in Area
Rare disturbance activity
Rare disturbance activity
Material Extent
<10m² or < 10m pipe run
Frequency of Use
Infrequent
Time in Area
Maintenance Activity
Minor disturbance
Prepared by Adams Environmental Ltd See survey report for scope/limitations of inspectionPage 22 of 112
ExternalWood House ASBESTOS REGISTER
S 19334.17Revision Issue N° 11
March 2019Wood House
12m²Chrysotile01 A AC CladdingFront Elevation (East)
3/12Good condition
Direct access
2 N° layers of corrugated profile asbestos cement (AC) cladding present to top section of wall above entrance door. Re-inspection dates 20/03/09 (Rev 2) & 05/07/11 (Rev 3).
Sealed 01
Area/Room Sample No
Building Component
Asbestos Content
Extent Condition Surface Treatment
Material Assessment
Recommendations/ Summary
Accessibility Photo ID
Re-inspected 24/09/12 - No Change.Re-inspected 18/09/13 - No Change.Re-inspected 24/09/14 - No Change.Re-inspected 28/10/15 - No ChangeRe-inspected 09/12/16 - No ChangeRe-inspected 07/12/17 - No ChangeRe-inspected 05/12/18 - No Change
Monitor condition of material.
ASBESTOS PRESENT
Very Low< 1 hour ACM unlikely to be
disturbed for maintenance
Frequency of
Maintenance
Risk Assessment
Location
Outdoors
Material Accessiblity
Usually inaccessible
or unlikely to be disturbed
No.of Occupants
None
Main Activity in Area
Secondary Activity in Area
Rare disturbance activity
Rare disturbance activity
Material Extent
> 10m² to < 50m² or > 10m to > 50m pipe run
Frequency of Use
Daily
Time in Area
Maintenance Activity
Minor disturbance
>150m²
Chrysotile10 A AC Roof TileRoof of Extension Block
3/12Good condition
Direct access
Roof tiles present to pitched roof of rear extension block. Re-inspection dates 20/03/09 (Rev 2) & 05/07/11 (Rev 3).
Composite 02
Area/Room Sample No
Building Component
Asbestos Content
Extent Condition Surface Treatment
Material Assessment
Recommendations/ Summary
Accessibility Photo ID
Re-inspected 24/09/12 - No Change.Re-inspected 24/09/14 - No Change.Re-inspected 28/10/15 - No ChangeRe-inspected 09/12/16 - No ChangeRe-inspected 07/12/17 - No ChangeRe-inspected 05/12/18 - No Change
Monitor condition of material.
ASBESTOS PRESENT
Very Low< 1 hour ACM unlikely to be
disturbed for maintenance
Frequency of
Maintenance
Risk Assessment
Location
Outdoors
Material Accessiblity
Usually inaccessible
or unlikely to be disturbed
No.of Occupants
None
Main Activity in Area
Secondary Activity in Area
Rare disturbance activity
Rare disturbance activity
Material Extent
> 50m² or > 50m pipe run
Frequency of Use
Infrequent
Time in Area
Maintenance Activity
Minor disturbance
Prepared by Adams Environmental Ltd See survey report for scope/limitations of inspectionPage 23 of 112
BasementCAMHS - Family Consultation ASBESTOS REGISTER
S 19334.17Revision Issue N° 11
March 2019CAMHS - Family Consultation
Amosite
Chrysotile
< 1m²Crocidolite15 A Thermal Insulation Debris
Stairwell Duct
12/1212/12Poor condition
Indirect access
Pipe insulation debris present to floor of duct off west side of half landing staircase leading to boiler room. Entry position to duct sealed by wood and mastic and warning signage is in place. Re-inspection dates 20/03/09 (Rev 2) & 05/07/11 (Rev 3).
Enclosed 03 04
Area/Room Sample No
Building Component
Asbestos Content
Extent Condition Surface Treatment
Material Assessment
Recommendations/ Summary
Accessibility Photo ID
Re-inspected 24/09/12 - No Change.Re-inspected 18/09/13 - Seal position in duct has been broken, recommend new timber seal is put in place with labels.Re-inspected 24/09/14 - No Change.Re-inspected 28/10/15 - No ChangeRe-inspected 09/12/16 - No Change.Re-inspected 07/12/17 - No ChangeRe-inspected 05/12/18 - No Change
Monitor condition of material.
ASBESTOS PRESENT
< 1 hour ACM unlikely to be
disturbed for maintenance
Frequency of
Maintenance
Risk Assessment
Location
Confined Spaces
Material Accessiblity
Usually inaccessible
or unlikely to be disturbed
No.of Occupants
None
Main Activity in Area
Secondary Activity in Area
Rare disturbance activity
Rare disturbance activity
Material Extent
Small amounts or items
Frequency of Use
Infrequent
Time in Area
Maintenance Activity
Minor disturbance
Medium
0.2m²Chrysotile90366 A Thermal Insulation Debris Pipe Insulation
Boiler Room 10/1210/12Poor condition
Direct access
Where MMMF insulation has come away from the pipework above the door penetration it has exposed asbestos insulation debris (sampled 24/09/14 and forming Materials Report M15505.17.Existing pipework within boiler room is covered by plastic clad MMMF pipe insulation. Insulation materials not removed for inspection. Asbestos insulation debris may be present to older pipe surfaces beneath these coverings, etc.
Composite 30
Area/Room Sample No
Building Component
Asbestos Content
Extent Condition Surface Treatment
Material Assessment
Recommendations/ Summary
Accessibility Photo ID
Re-inspected 24/09/12 - No Change.Re-inspected 18/09/13 - No Change.Re-inspected 24/09/14 - Asbestos thermal insulation debris identified where MMMF insulation to pipework above door penetration has come away.Re-inspected 28/10/15 - No ChangeRe-inspected 09/12/16 - Pipework re-lagged with foil faced MMMF insulation.Re-inspected 07/12/17 - No ChangeRe-inspected 05/12/18 - No Change
Monitor condition of material.
ASBESTOS PRESENT
< 1 hour < 1 per year
Frequency of
Maintenance
Risk Assessment
Location
Rooms up to 100m²
Material Accessiblity
Occasionally likely to be disturbed
No.of Occupants
None
Main Activity in Area
Secondary Activity in Area
Low disturbance activities
Low disturbance activity
Material Extent
Small amounts or items
Frequency of Use
Monthly
Time in Area
Maintenance Activity
Low disturbance
Medium
Prepared by Adams Environmental Ltd See survey report for scope/limitations of inspectionPage 24 of 112
BasementCAMHS - Family Consultation ASBESTOS REGISTER
S 19334.17Revision Issue N° 11
March 2019CAMHS - Family Consultation
3m²Chrysotile16 A AC ShutteringStairwell Duct
5/12Fair condition
Indirect access
Asbestos cement (AC) shuttering is present to ceiling of duct off west side of half landing staircase leading to boiler room. Entry position to duct sealed by wood and mastic and warning signage is in place.Re-inspection dates 20/03/09 (Rev 2) & 05/07/11 (Rev 3).
Enclosed 03 04
Area/Room Sample No
Building Component
Asbestos Content
Extent Condition Surface Treatment
Material Assessment
Recommendations/ Summary
Accessibility Photo ID
Re-inspected 24/09/12 - No Change.Re-inspected 18/09/13 - Seal position to duct has been broken, recommend new timber seal is put in place with labels.Re-inspected 24/09/14 - No Change.Re-inspected 28/10/15 - No ChangeRe-inspected 09/12/16 - No Change.Re-inspected 07/12/17 - No ChangeRe-inspected 05/12/18 - No Change
Monitor condition of material.
ASBESTOS PRESENT
< 1 hour < 1 per year
Frequency of
Maintenance
Risk Assessment
Location
Rooms up to 100m²
Material Accessiblity
Occasionally likely to be disturbed
No.of Occupants
None
Main Activity in Area
Secondary Activity in Area
Low disturbance activities
Low disturbance activity
Material Extent
<10m² or < 10m pipe run
Frequency of Use
Monthly
Time in Area
Maintenance Activity
Low disturbance
Low
< 0.5m²
Chrysotile17 A AC UpstandStairwell Duct
5/12Fair condition
Indirect access
Asbestos cement (AC) upstand panel is present at entrance position to duct off west side of half landing staircase leading to boiler room. Entry position to duct sealed by wood and mastic and warning signage is in place. Re-inspection dates 20/03/09 (Rev 2) & 05/07/11 (Rev 3).
Enclosed 03 04
Area/Room Sample No
Building Component
Asbestos Content
Extent Condition Surface Treatment
Material Assessment
Recommendations/ Summary
Accessibility Photo ID
Re-inspected 24/09/12 - No Change.Re-inspected 18/09/13 - No Change.Re-inspected 24/09/14 - No Change.Re-inspected 28/10/15 - No ChangeRe-inspected 09/12/16 - No Change.Re-inspected 07/12/17 - No ChangeRe-inspected 05/12/18 - No Change
Maintain restricted access to the asbestos material.
ASBESTOS PRESENT
< 1 hour < 1 per year
Frequency of
Maintenance
Risk Assessment
Location
Confined Spaces
Material Accessiblity
Occasionally likely to be disturbed
No.of Occupants
None
Main Activity in Area
Secondary Activity in Area
Low disturbance activities
Low disturbance activity
Material Extent
Small amounts or items
Frequency of Use
Monthly
Time in Area
Maintenance Activity
Low disturbance
Low
Prepared by Adams Environmental Ltd See survey report for scope/limitations of inspectionPage 25 of 112
Ground FloorCAMHS - Family Consultation ASBESTOS REGISTER
S 19334.17Revision Issue N° 11
March 2019CAMHS - Family Consultation
Suspect RiserStore Cupboard
SUSPECT
No direct access to (assumed) riser position to east wall of store cupboard. Riser connects to boiler room below, where foam seals, etc are in place at pipe penetration points .
Area/Room Sample No
Building Component
Asbestos Content
Extent Condition Surface Treatment
Material Assessment
Recommendations/ Summary
Accessibility Photo ID
Re-inspected 24/09/12 - No Change.Re-inspected 18/09/13 - No Change.Re-inspected 24/09/14 - No Change.Re-inspected 28/10/15 - No ChangeRe-inspected 09/12/16 - No Change.Re-inspected 07/12/17 - No ChangeRe-inspected 05/12/18 - No Change
High presumption of the presence of asbestos materials.
Programme further investigation.
ASBESTOS SUSPECTED
Frequency of
Maintenance
Risk Assessment
Location Material Accessiblity
No.of Occupants
Main Activity in Area
Secondary Activity in Area
Material Extent
Frequency of Use
Time in Area
Maintenance Activity
Prepared by Adams Environmental Ltd See survey report for scope/limitations of inspectionPage 26 of 112
First FloorCAMHS - Family Consultation ASBESTOS REGISTER
S 19334.17Revision Issue N° 11
March 2019CAMHS - Family Consultation
Suspect Riser1.12 – W.C. Lobby
SUSPECT
Riser to west wall of W.C. Lobby not opened up for internal inspection. Riser passes from basement boiler room, where foam seals are in place where pipework enters.
Area/Room Sample No
Building Component
Asbestos Content
Extent Condition Surface Treatment
Material Assessment
Recommendations/ Summary
Accessibility Photo ID
Re-inspected 24/09/12 - No Change.Re-inspected 18/09/13 - No Change.Re-inspected 24/09/14 - No Change.Re-inspected 28/10/15 - No ChangeRe-inspected 09/12/16 - No Change.Re-inspected 07/12/17 - No ChangeRe-inspected 05/12/18 - No Change
High presumption of the presence of asbestos materials.
Programme further investigation.
ASBESTOS SUSPECTED
Frequency of
Maintenance
Risk Assessment
Location Material Accessiblity
No.of Occupants
Main Activity in Area
Secondary Activity in Area
Material Extent
Frequency of Use
Time in Area
Maintenance Activity
Prepared by Adams Environmental Ltd See survey report for scope/limitations of inspectionPage 27 of 112
ExternalCAMHS - Family Consultation ASBESTOS REGISTER
S 19334.17Revision Issue N° 11
March 2019CAMHS - Family Consultation
Suspect DuctSub-Ground Duct
SUSPECT
Sub-ground duct running in north-south direction beneath pathway leading from boiler room not accessed. Asbestos pipe insulation identified / suspected in this duct where it exits boiler room (refer to Basement Boiler Room entry).
06 07
Area/Room Sample No
Building Component
Asbestos Content
Extent Condition Surface Treatment
Material Assessment
Recommendations/ Summary
Accessibility Photo ID
Re-inspected 24/09/12 - No Change.Re-inspected 18/09/13 - No Change.Re-inspected 24/09/14 - No Change.Re-inspected 28/10/15 - No ChangeRe-inspected 09/12/16 - No Change.Re-inspected 07/12/17 - No ChangeRe-inspected 05/12/18 - No Change
High presumption of the presence of asbestos materials.
Programme further investigation.
ASBESTOS SUSPECTED
Frequency of
Maintenance
Risk Assessment
Location Material Accessiblity
No.of Occupants
Main Activity in Area
Secondary Activity in Area
Material Extent
Frequency of Use
Time in Area
Maintenance Activity
Prepared by Adams Environmental Ltd See survey report for scope/limitations of inspectionPage 28 of 112
Ground FloorLarkswood Centre ASBESTOS REGISTER
S 19334.17Revision Issue N° 11
March 2019Larkswood Centre
Suspect Water Heater
G.17 – W.C. SUSPECT
No access within 'Santon' water heater. Internal components may contain asbestos.
Area/Room Sample No
Building Component
Asbestos Content
Extent Condition Surface Treatment
Material Assessment
Recommendations/ Summary
Accessibility Photo ID
Re-inspected 24/09/12 - No Change.Re-inspected 18/09/13 - No Change.Re-inspected 24/09/14 - No Change.Re-inspected 28/10/15 - No ChangeRe-inspected 09/12/16 - No Change.Re-inspected 07/12/17 - No ChangeRe-inspected 05/12/18 - No Change
Low presumption of the presence of asbestos materials.
Programme further investigation.
ASBESTOS SUSPECTED
Frequency of
Maintenance
Risk Assessment
Location Material Accessiblity
No.of Occupants
Main Activity in Area
Secondary Activity in Area
Material Extent
Frequency of Use
Time in Area
Maintenance Activity
Prepared by Adams Environmental Ltd See survey report for scope/limitations of inspectionPage 29 of 112
Second FloorLarkswood Centre ASBESTOS REGISTER
S 19334.17Revision Issue N° 11
March 2019Larkswood Centre
Suspect Water Heater
Cleaners Cupboard
SUSPECT
No access within 'Santon' water heater. Internal components may contain asbestos.
Area/Room Sample No
Building Component
Asbestos Content
Extent Condition Surface Treatment
Material Assessment
Recommendations/ Summary
Accessibility Photo ID
Re-inspected 24/09/12 - No Change.Re-inspected 18/09/13 - No Change.Re-inspected 24/09/14 - No Change.Re-inspected 28/10/15 - No ChangeRe-inspected 09/12/16 - No Change.Re-inspected 07/12/17 - No ChangeRe-inspected 05/12/18 - No Change
Low presumption of the presence of asbestos materials.
Programme further investigation.
ASBESTOS SUSPECTED
Frequency of
Maintenance
Risk Assessment
Location Material Accessiblity
No.of Occupants
Main Activity in Area
Secondary Activity in Area
Material Extent
Frequency of Use
Time in Area
Maintenance Activity
Suspect Void2.12 – Office SUSPECT
No access into eaves. Hatches have been sealed shut.
Area/Room Sample No
Building Component
Asbestos Content
Extent Condition Surface Treatment
Material Assessment
Recommendations/ Summary
Accessibility Photo ID
Re-inspected 24/09/12 - No Change.Re-inspected 18/09/13 - No Change.Re-inspected 24/09/14 - No Change.Re-inspected 28/10/15 - No ChangeRe-inspected 09/12/16 - No Change.Re-inspected 07/12/17 - No ChangeRe-inspected 05/12/18 - No Change
Low presumption of the presence of asbestos materials.
Programme further investigation.
ASBESTOS SUSPECTED
Frequency of
Maintenance
Risk Assessment
Location Material Accessiblity
No.of Occupants
Main Activity in Area
Secondary Activity in Area
Material Extent
Frequency of Use
Time in Area
Maintenance Activity
Prepared by Adams Environmental Ltd See survey report for scope/limitations of inspectionPage 30 of 112
Second FloorLarkswood Centre ASBESTOS REGISTER
S 19334.17Revision Issue N° 11
March 2019Larkswood Centre
Suspect Void2.13 – Office SUSPECT
No access into eaves. Hatches have been sealed shut.
Area/Room Sample No
Building Component
Asbestos Content
Extent Condition Surface Treatment
Material Assessment
Recommendations/ Summary
Accessibility Photo ID
Re-inspected 24/09/12 - No Change.Re-inspected 18/09/13 - No Change.Re-inspected 24/09/14 - No Change.Re-inspected 28/10/15 - No ChangeRe-inspected 09/12/16 - No Change.Re-inspected 07/12/17 - No ChangeRe-inspected 05/12/18 - No Change
Low presumption of the presence of asbestos materials.
Programme further investigation.
ASBESTOS SUSPECTED
Frequency of
Maintenance
Risk Assessment
Location Material Accessiblity
No.of Occupants
Main Activity in Area
Secondary Activity in Area
Material Extent
Frequency of Use
Time in Area
Maintenance Activity
Suspect Void2.14 – Office SUSPECT
No access into eaves. Hatches have been sealed shut.
Area/Room Sample No
Building Component
Asbestos Content
Extent Condition Surface Treatment
Material Assessment
Recommendations/ Summary
Accessibility Photo ID
Re-inspected 24/09/12 - No Change.Re-inspected 18/09/13 - No Change.Re-inspected 24/09/14 - No Change.Re-inspected 28/10/15 - No ChangeRe-inspected 09/12/16 - No Change.Re-inspected 07/12/17 - No ChangeRe-inspected 05/12/18 - No Change
Low presumption of the presence of asbestos materials.
Programme further investigation.
ASBESTOS SUSPECTED
Frequency of
Maintenance
Risk Assessment
Location Material Accessiblity
No.of Occupants
Main Activity in Area
Secondary Activity in Area
Material Extent
Frequency of Use
Time in Area
Maintenance Activity
Prepared by Adams Environmental Ltd See survey report for scope/limitations of inspectionPage 31 of 112
Second FloorLarkswood Centre ASBESTOS REGISTER
S 19334.17Revision Issue N° 11
March 2019Larkswood Centre
Suspect Void2.15 – Office SUSPECT
No access into eaves. Hatches have been sealed shut.
Area/Room Sample No
Building Component
Asbestos Content
Extent Condition Surface Treatment
Material Assessment
Recommendations/ Summary
Accessibility Photo ID
Re-inspected 24/09/12 - No Change.Re-inspected 18/09/13 - No Change.Re-inspected 24/09/14 - No Change.Re-inspected 28/10/15 - No ChangeRe-inspected 09/12/16 - No Change.Re-inspected 07/12/17 - No ChangeRe-inspected 05/12/18 - No Change
Low presumption of the presence of asbestos materials.
Programme further investigation.
ASBESTOS SUSPECTED
Frequency of
Maintenance
Risk Assessment
Location Material Accessiblity
No.of Occupants
Main Activity in Area
Secondary Activity in Area
Material Extent
Frequency of Use
Time in Area
Maintenance Activity
Suspect Void2.17 – Office SUSPECT
No access into eaves. Hatches have been sealed shut.
Area/Room Sample No
Building Component
Asbestos Content
Extent Condition Surface Treatment
Material Assessment
Recommendations/ Summary
Accessibility Photo ID
Re-inspected 24/09/12 - No Change.Re-inspected 18/09/13 - No Change.Re-inspected 24/09/14 - No Change.Re-inspected 28/10/15 - No ChangeRe-inspected 09/12/16 - No Change.Re-inspected 07/12/17 - No ChangeRe-inspected 05/12/18 - No Change
Low presumption of the presence of asbestos materials.
Programme further investigation.
ASBESTOS SUSPECTED
Frequency of
Maintenance
Risk Assessment
Location Material Accessiblity
No.of Occupants
Main Activity in Area
Secondary Activity in Area
Material Extent
Frequency of Use
Time in Area
Maintenance Activity
Prepared by Adams Environmental Ltd See survey report for scope/limitations of inspectionPage 32 of 112
Second FloorLarkswood Centre ASBESTOS REGISTER
S 19334.17Revision Issue N° 11
March 2019Larkswood Centre
Suspect Void2.18 – Office SUSPECT
Limited access into eaves. Eaves viewed from low level hatch beneath window. Versals and foam insulation seen to pipework.
Area/Room Sample No
Building Component
Asbestos Content
Extent Condition Surface Treatment
Material Assessment
Recommendations/ Summary
Accessibility Photo ID
Re-inspected 24/09/12 - No Change.Re-inspected 18/09/13 - No Change.Re-inspected 24/09/14 - No Change.Re-inspected 28/10/15 - No ChangeRe-inspected 09/12/16 - No Change.Re-inspected 07/12/17 - No ChangeRe-inspected 05/12/18 - No Change
Low presumption of the presence of asbestos materials.
Programme further investigation.
ASBESTOS SUSPECTED
Frequency of
Maintenance
Risk Assessment
Location Material Accessiblity
No.of Occupants
Main Activity in Area
Secondary Activity in Area
Material Extent
Frequency of Use
Time in Area
Maintenance Activity
Suspect Void2.19 – Office SUSPECT
Limited access into eaves. Eaves viewed from low level hatch beneath window. Versals and foam insulation seen to pipework.
Area/Room Sample No
Building Component
Asbestos Content
Extent Condition Surface Treatment
Material Assessment
Recommendations/ Summary
Accessibility Photo ID
Re-inspected 24/09/12 - No Change.Re-inspected 18/09/13 - No Change.Re-inspected 24/09/14 - No Change.Re-inspected 28/10/15 - No ChangeRe-inspected 09/12/16 - No Change.Re-inspected 07/12/17 - No ChangeRe-inspected 05/12/18 - No Change
Low presumption of the presence of asbestos materials.
Programme further investigation.
ASBESTOS SUSPECTED
Frequency of
Maintenance
Risk Assessment
Location Material Accessiblity
No.of Occupants
Main Activity in Area
Secondary Activity in Area
Material Extent
Frequency of Use
Time in Area
Maintenance Activity
Prepared by Adams Environmental Ltd See survey report for scope/limitations of inspectionPage 33 of 112
Second FloorLarkswood Centre ASBESTOS REGISTER
S 19334.17Revision Issue N° 11
March 2019Larkswood Centre
Suspect Void2.20 – Office SUSPECT
No access into eaves. Hatches have been sealed shut.
Area/Room Sample No
Building Component
Asbestos Content
Extent Condition Surface Treatment
Material Assessment
Recommendations/ Summary
Accessibility Photo ID
Re-inspected 24/09/12 - No Change.Re-inspected 18/09/13 - No Change.Re-inspected 24/09/14 - No Change.Re-inspected 28/10/15 - No ChangeRe-inspected 09/12/16 - No Change.Re-inspected 07/12/17 - No ChangeRe-inspected 05/12/18 - No Change
Low presumption of the presence of asbestos materials.
Programme further investigation.
ASBESTOS SUSPECTED
Frequency of
Maintenance
Risk Assessment
Location Material Accessiblity
No.of Occupants
Main Activity in Area
Secondary Activity in Area
Material Extent
Frequency of Use
Time in Area
Maintenance Activity
Suspect Void2.21 – Office SUSPECT
Limited access into eaves. Eaves viewed from low level hatch beneath window. Versals and foam insulation seen to pipework.
Area/Room Sample No
Building Component
Asbestos Content
Extent Condition Surface Treatment
Material Assessment
Recommendations/ Summary
Accessibility Photo ID
Re-inspected 24/09/12 - No Change.Re-inspected 18/09/13 - No Change.Re-inspected 24/09/14 - No Change.Re-inspected 28/10/15 - No ChangeRe-inspected 09/12/16 - No Change.Re-inspected 07/12/17 - No ChangeRe-inspected 05/12/18 - No Change
Low presumption of the presence of asbestos materials.
Programme further investigation.
ASBESTOS SUSPECTED
Frequency of
Maintenance
Risk Assessment
Location Material Accessiblity
No.of Occupants
Main Activity in Area
Secondary Activity in Area
Material Extent
Frequency of Use
Time in Area
Maintenance Activity
Prepared by Adams Environmental Ltd See survey report for scope/limitations of inspectionPage 34 of 112
Second FloorLarkswood Centre ASBESTOS REGISTER
S 19334.17Revision Issue N° 11
March 2019Larkswood Centre
Suspect Void2.22 – Office SUSPECT
Limited access into eaves. Eaves viewed from low level hatch beneath window. Versals and foam insulation seen to pipework.
Area/Room Sample No
Building Component
Asbestos Content
Extent Condition Surface Treatment
Material Assessment
Recommendations/ Summary
Accessibility Photo ID
Re-inspected 24/09/12 - No Change.Re-inspected 18/09/13 - No Change.Re-inspected 24/09/14 - No Change.Re-inspected 28/10/15 - No ChangeRe-inspected 09/12/16 - No Change.Re-inspected 07/12/17 - No ChangeRe-inspected 05/12/18 - No Change
Low presumption of the presence of asbestos materials.
Programme further investigation.
ASBESTOS SUSPECTED
Frequency of
Maintenance
Risk Assessment
Location Material Accessiblity
No.of Occupants
Main Activity in Area
Secondary Activity in Area
Material Extent
Frequency of Use
Time in Area
Maintenance Activity
Suspect Void2.23 – Office SUSPECT
Limited access into eaves. Eaves viewed from low level hatch beneath window. Versals and foam insulation seen to pipework.
Area/Room Sample No
Building Component
Asbestos Content
Extent Condition Surface Treatment
Material Assessment
Recommendations/ Summary
Accessibility Photo ID
Re-inspected 24/09/12 - No Change.Re-inspected 18/09/13 - No Change.Re-inspected 24/09/14 - No Change.Re-inspected 28/10/15 - No ChangeRe-inspected 09/12/16 - No Change.Re-inspected 07/12/17 - No ChangeRe-inspected 05/12/18 - No Change
Low presumption of the presence of asbestos materials.
Programme further investigation.
ASBESTOS SUSPECTED
Frequency of
Maintenance
Risk Assessment
Location Material Accessiblity
No.of Occupants
Main Activity in Area
Secondary Activity in Area
Material Extent
Frequency of Use
Time in Area
Maintenance Activity
Prepared by Adams Environmental Ltd See survey report for scope/limitations of inspectionPage 35 of 112
Third FloorLarkswood Centre ASBESTOS REGISTER
S 19334.17Revision Issue N° 11
March 2019Larkswood Centre
Suspect Water Heater
Store Cupboard 1
SUSPECT
No access within 'Heatrae Sadia' water heater located in store cupboard in south west corner of 3.01 open plan office. Internal components may contain asbestos.
Area/Room Sample No
Building Component
Asbestos Content
Extent Condition Surface Treatment
Material Assessment
Recommendations/ Summary
Accessibility Photo ID
Re-inspected 24/09/12 - No Change.Re-inspected 18/09/13 - No Change.Re-inspected 24/09/14 - No Change.Re-inspected 28/10/15 - No ChangeRe-inspected 09/12/16 - No Change.Re-inspected 07/12/17 - No ChangeRe-inspected 05/12/18 - No Change
Low presumption of the presence of asbestos materials.
Programme further investigation.
ASBESTOS SUSPECTED
Frequency of
Maintenance
Risk Assessment
Location Material Accessiblity
No.of Occupants
Main Activity in Area
Secondary Activity in Area
Material Extent
Frequency of Use
Time in Area
Maintenance Activity
Suspect Void3.01 – Open Plan Office
SUSPECT
No access into eaves. Hatches have been sealed shut.
Area/Room Sample No
Building Component
Asbestos Content
Extent Condition Surface Treatment
Material Assessment
Recommendations/ Summary
Accessibility Photo ID
Re-inspected 24/09/12 - No Change.Re-inspected 18/09/13 - No Change.Re-inspected 24/09/14 - No Change.Re-inspected 28/10/15 - No ChangeRe-inspected 09/12/16 - No Change.Re-inspected 07/12/17 - No ChangeRe-inspected 05/12/18 - No Change
Low presumption of the presence of asbestos materials.
Programme further investigation.
ASBESTOS SUSPECTED
Frequency of
Maintenance
Risk Assessment
Location Material Accessiblity
No.of Occupants
Main Activity in Area
Secondary Activity in Area
Material Extent
Frequency of Use
Time in Area
Maintenance Activity
Prepared by Adams Environmental Ltd See survey report for scope/limitations of inspectionPage 36 of 112
Third FloorLarkswood Centre ASBESTOS REGISTER
S 19334.17Revision Issue N° 11
March 2019Larkswood Centre
Suspect Void3.02 – Office SUSPECT
No access into eaves. Hatches have been sealed shut.
Area/Room Sample No
Building Component
Asbestos Content
Extent Condition Surface Treatment
Material Assessment
Recommendations/ Summary
Accessibility Photo ID
Re-inspected 24/09/12 - No Change.Re-inspected 18/09/13 - No Change.Re-inspected 24/09/14 - No Change.Re-inspected 28/10/15 - No ChangeRe-inspected 09/12/16 - No Change.Re-inspected 07/12/17 - No ChangeRe-inspected 05/12/18 - No Change
Low presumption of the presence of asbestos materials.
Programme further investigation.
ASBESTOS SUSPECTED
Frequency of
Maintenance
Risk Assessment
Location Material Accessiblity
No.of Occupants
Main Activity in Area
Secondary Activity in Area
Material Extent
Frequency of Use
Time in Area
Maintenance Activity
Suspect Void3.10 – Office SUSPECT
No access into eaves. Hatches have been sealed shut.
Area/Room Sample No
Building Component
Asbestos Content
Extent Condition Surface Treatment
Material Assessment
Recommendations/ Summary
Accessibility Photo ID
Re-inspected 24/09/12 - No Change.Re-inspected 18/09/13 - No Change.Re-inspected 24/09/14 - No Change.Re-inspected 28/10/15 - No ChangeRe-inspected 09/12/16 - No Change.Re-inspected 07/12/17 - No ChangeRe-inspected 05/12/18 - No Change
Low presumption of the presence of asbestos materials.
Programme further investigation.
ASBESTOS SUSPECTED
Frequency of
Maintenance
Risk Assessment
Location Material Accessiblity
No.of Occupants
Main Activity in Area
Secondary Activity in Area
Material Extent
Frequency of Use
Time in Area
Maintenance Activity
Prepared by Adams Environmental Ltd See survey report for scope/limitations of inspectionPage 37 of 112
ExternalLarkswood Centre ASBESTOS REGISTER
S 19334.17Revision Issue N° 11
March 2019Larkswood Centre
Suspect Soffit Panels
Roof Perimeter
SUSPECT
No access to high level soffits to perimeter of roof and to dorma windows of 2nd floor offices.
Area/Room Sample No
Building Component
Asbestos Content
Extent Condition Surface Treatment
Material Assessment
Recommendations/ Summary
Accessibility Photo ID
Re-inspected 24/09/12 - No Change.Re-inspected 24/09/14 - No Change.Re-inspected 28/10/15 - No ChangeRe-inspected 09/12/16 - No Change.Re-inspected 07/12/17 - No ChangeRe-inspected 05/12/18 - No Change
Low presumption of the presence of asbestos materials.
Programme further investigation.
ASBESTOS SUSPECTED
Frequency of
Maintenance
Risk Assessment
Location Material Accessiblity
No.of Occupants
Main Activity in Area
Secondary Activity in Area
Material Extent
Frequency of Use
Time in Area
Maintenance Activity
Prepared by Adams Environmental Ltd See survey report for scope/limitations of inspectionPage 38 of 112
Ground FloorPsychotherapy Clinic ASBESTOS REGISTER
S 19334.17Revision Issue N° 11
March 2019Psychotherapy Clinic
Suspect ElectricsG10 – Waiting Room Electrical Cupboard
SUSPECT
Asbestos cloth flashguards may be present to old style electrical fuses.
Area/Room Sample No
Building Component
Asbestos Content
Extent Condition Surface Treatment
Material Assessment
Recommendations/ Summary
Accessibility Photo ID
Re-inspected 24/09/12 - No Change.Re-inspected 18/09/13 - No Change.Re-inspected 24/09/14 - No Change.Re-inspected 28/10/15 - No ChangeRe-inspected 09/12/16 - No Change.Re-inspected 07/12/17 - No ChangeRe-inspected 05/12/18 - No Change
High presumption of the presence of asbestos materials.Programme further investigation.
ASBESTOS SUSPECTED
Frequency of
Maintenance
Risk Assessment
Location Material Accessiblity
No.of Occupants
Main Activity in Area
Secondary Activity in Area
Material Extent
Frequency of Use
Time in Area
Maintenance Activity
Prepared by Adams Environmental Ltd See survey report for scope/limitations of inspectionPage 39 of 112
ExternalPsychotherapy Clinic ASBESTOS REGISTER
S 19334.17Revision Issue N° 11
March 2019Psychotherapy Clinic
Suspect Soffit Panels
Roof Perimeter
SUSPECT
No access to high level sloping soffits to the sides of the building. Soffits to front and rear elevation are timber.
Area/Room Sample No
Building Component
Asbestos Content
Extent Condition Surface Treatment
Material Assessment
Recommendations/ Summary
Accessibility Photo ID
Re-inspected 18/09/13 - No high level access provided; soffits still suspected to be asbestos material.Re-inspected 24/09/14 - No Change.Re-inspected 28/10/15 - No ChangeRe-inspected 09/12/16 - No Change.Re-inspected 07/12/17 - No ChangeRe-inspected 05/12/18 - No Change
Low presumption of the presence of asbestos materials.
Programme further investigation.
ASBESTOS SUSPECTED
Frequency of
Maintenance
Risk Assessment
Location Material Accessiblity
No.of Occupants
Main Activity in Area
Secondary Activity in Area
Material Extent
Frequency of Use
Time in Area
Maintenance Activity
Prepared by Adams Environmental Ltd See survey report for scope/limitations of inspectionPage 40 of 112
BasementThorpe Coombe House ASBESTOS REGISTER
S 19334.17Revision Issue N° 11
March 2019Thorpe Coombe House
0.5m²Chrysotile35 M CAF GasketB1 – Boiler Room
4/12Good condition
Direct access
Compressed asbestos fibre (CAF) gaskets present to bolted flange joints on gas pipework.
Sealed
Area/Room Sample No
Building Component
Asbestos Content
Extent Condition Surface Treatment
Material Assessment
Recommendations/ Summary
Accessibility Photo ID
Re-inspected 28/10/15 - No key access at time of inspection.Re-inspected 09/12/16 - Area accessed for inspection, No Change.Re-inspected 07/12/17 - No ChangeRe-inspected 05/12/18 - No Change
Monitor condition of material.
ASBESTOS PRESENT
< 1 hour < 1 per year
Frequency of
Maintenance
Risk Assessment
Location
Rooms up to 100m²
Material Accessiblity
Occasionally likely to be disturbed
No.of Occupants
None
Main Activity in Area
Secondary Activity in Area
Rare disturbance activity
Rare disturbance activity
Material Extent
Small amounts or items
Frequency of Use
Monthly
Time in Area
Maintenance Activity
Low disturbance
Low
0.5m²Chrysotile35 M CAF GasketB2 – Gas Intake Room
4/12Good condition
Direct access
Compressed asbestos fibre (CAF) gaskets present to bolted flange joints on gas pipework.
Sealed
Area/Room Sample No
Building Component
Asbestos Content
Extent Condition Surface Treatment
Material Assessment
Recommendations/ Summary
Accessibility Photo ID
Re-inspected 28/10/15 - No key access at time of inspection.Re-inspected 09/12/16 - Area accessed for inspection, No Change.Re-inspected 07/12/17 - No ChangeRe-inspected 05/12/18 - No Change
Monitor condition of material.
ASBESTOS PRESENT
< 1 hour < 1 per year
Frequency of
Maintenance
Risk Assessment
Location
Rooms up to 100m²
Material Accessiblity
Occasionally likely to be disturbed
No.of Occupants
None
Main Activity in Area
Secondary Activity in Area
Rare disturbance activity
Low disturbance activity
Material Extent
Small amounts or items
Frequency of Use
Monthly
Time in Area
Maintenance Activity
Low disturbance
Low
Prepared by Adams Environmental Ltd See survey report for scope/limitations of inspectionPage 41 of 112
BasementThorpe Coombe House ASBESTOS REGISTER
S 19334.17Revision Issue N° 11
March 2019Thorpe Coombe House
0.5m²Chrysotile35 M CAF GasketB3 – Electrical Intake Room
4/12Good condition
Direct access
Compressed asbestos fibre (CAF) gaskets present to bolted flange joints on gas pipework.
Sealed
Area/Room Sample No
Building Component
Asbestos Content
Extent Condition Surface Treatment
Material Assessment
Recommendations/ Summary
Accessibility Photo ID
Re-inspected 28/10/15 - No key access at time of inspection.Re-inspected 09/12/16 - Area accessed for inspection, No Change.Re-inspected 07/12/17 - No ChangeRe-inspected 05/12/18 - No Change
Monitor condition of material.
ASBESTOS PRESENT
< 1 hour < 1 per year
Frequency of
Maintenance
Risk Assessment
Location
Rooms up to 100m²
Material Accessiblity
Occasionally likely to be disturbed
No.of Occupants
None
Main Activity in Area
Secondary Activity in Area
Rare disturbance activity
Rare disturbance activity
Material Extent
Small amounts or items
Frequency of Use
Monthly
Time in Area
Maintenance Activity
Low disturbance
Low
0.5m²Chrysotile35 M CAF GasketB4 – Old Electrical Intake Room
4/12Good condition
Direct access
Compressed asbestos fibre (CAF) gaskets present to bolted flange joints on gas pipework.
Sealed
Area/Room Sample No
Building Component
Asbestos Content
Extent Condition Surface Treatment
Material Assessment
Recommendations/ Summary
Accessibility Photo ID
Re-inspected 28/10/15 - No key access at time of inspection.Re-inspected 09/12/16 - Area accessed for inspection, No Change.Re-inspected 07/12/17 - No ChangeRe-inspected 05/12/18 - No Change
Monitor condition of material.
ASBESTOS PRESENT
< 1 hour < 1 per year
Frequency of
Maintenance
Risk Assessment
Location
Rooms up to 100m²
Material Accessiblity
Occasionally likely to be disturbed
No.of Occupants
None
Main Activity in Area
Secondary Activity in Area
Rare disturbance activity
Rare disturbance activity
Material Extent
Small amounts or items
Frequency of Use
Monthly
Time in Area
Maintenance Activity
Low disturbance
Low
Prepared by Adams Environmental Ltd See survey report for scope/limitations of inspectionPage 42 of 112
BasementThorpe Coombe House ASBESTOS REGISTER
S 19334.17Revision Issue N° 11
March 2019Thorpe Coombe House
Suspect ElectricsB4 – Old Electrical Intake Room
SUSPECT
Old style electrics present to west wall. Asbestos cloth flashguards may be present to fuses. Fibrous plasterboard ceiling panels also present, as identified in Boiler Room B1.
Area/Room Sample No
Building Component
Asbestos Content
Extent Condition Surface Treatment
Material Assessment
Recommendations/ Summary
Accessibility Photo ID
Re-inspected 24/09/12 - No Change.Re-inspected 18/09/13 - No Change.Re-inspected 24/09/14 - No Change.Re-inspected 28/10/15 - No key access at tim eof inspectionRe-inspected 09/12/16 - Area accessed for inspection, No Change.Re-inspected 07/12/17 - No ChangeRe-inspected 05/12/18 - No Change
High presumption of the presence of asbestos materials.
Programme further investigation.
ASBESTOS SUSPECTED
Frequency of
Maintenance
Risk Assessment
Location Material Accessiblity
No.of Occupants
Main Activity in Area
Secondary Activity in Area
Material Extent
Frequency of Use
Time in Area
Maintenance Activity
0.5m²Chrysotile35 M CAF GasketB5 – Store 4/12Good condition
Direct access
Compressed asbestos fibre (CAF) gaskets present to bolted flange joints on gas pipework.
Sealed
Area/Room Sample No
Building Component
Asbestos Content
Extent Condition Surface Treatment
Material Assessment
Recommendations/ Summary
Accessibility Photo ID
Re-inspected 28/10/15 - No key access at time of inspection.Re-inspected 09/12/16 - Area accessed for inspection, No Change.Re-inspected 07/12/17 - No ChangeRe-inspected 05/12/18 - No Change
Monitor condition of material.
ASBESTOS PRESENT
Very Low< 1 hour < 1 per year
Frequency of
Maintenance
Risk Assessment
Location
Confined Spaces
Material Accessiblity
Occasionally likely to be disturbed
No.of Occupants
None
Main Activity in Area
Secondary Activity in Area
Rare disturbance activity
Rare disturbance activity
Material Extent
Small amounts or items
Frequency of Use
Infrequent
Time in Area
Maintenance Activity
Minor disturbance
Prepared by Adams Environmental Ltd See survey report for scope/limitations of inspectionPage 43 of 112
BasementThorpe Coombe House ASBESTOS REGISTER
S 19334.17Revision Issue N° 11
March 2019Thorpe Coombe House
0.5m²Chrysotile35 M CAF GasketB6 – Store 4/12Good condition
Direct access
Compressed asbestos fibre (CAF) gaskets present to bolted flange joints on gas pipework.
Sealed
Area/Room Sample No
Building Component
Asbestos Content
Extent Condition Surface Treatment
Material Assessment
Recommendations/ Summary
Accessibility Photo ID
Re-inspected 28/10/15 - No key accessat time of inspection.Re-inspected 09/12/16 - Area accessed for inspection, No Change.Re-inspected 07/12/17 - No ChangeRe-inspected 05/12/18 - No Change
Monitor condition of material.
ASBESTOS PRESENT
Very Low< 1 hour < 1 per year
Frequency of
Maintenance
Risk Assessment
Location
Confined Spaces
Material Accessiblity
Occasionally likely to be disturbed
No.of Occupants
None
Main Activity in Area
Secondary Activity in Area
Rare disturbance activity
Rare disturbance activity
Material Extent
Small amounts or items
Frequency of Use
Infrequent
Time in Area
Maintenance Activity
Minor disturbance
0.5m²Chrysotile35 M CAF GasketB7 – Store 4/12Good condition
Direct access
Compressed asbestos fibre (CAF) gaskets present to bolted flange joints on gas pipework.
Sealed
Area/Room Sample No
Building Component
Asbestos Content
Extent Condition Surface Treatment
Material Assessment
Recommendations/ Summary
Accessibility Photo ID
Re-inspected 28/10/15 - No key access at tim eof inspection.Re-inspected 09/12/16 - Area accessed for inspection, No Change.Re-inspected 07/12/17 - No ChangeRe-inspected 05/12/18 - No Change
Monitor condition of material.
ASBESTOS PRESENT
Very Low< 1 hour < 1 per year
Frequency of
Maintenance
Risk Assessment
Location
Confined Spaces
Material Accessiblity
Occasionally likely to be disturbed
No.of Occupants
None
Main Activity in Area
Secondary Activity in Area
Rare disturbance activity
Rare disturbance activity
Material Extent
Small amounts or items
Frequency of Use
Infrequent
Time in Area
Maintenance Activity
Minor disturbance
Prepared by Adams Environmental Ltd See survey report for scope/limitations of inspectionPage 44 of 112
Ground FloorThorpe Coombe House ASBESTOS REGISTER
S 19334.17Revision Issue N° 11
March 2019Thorpe Coombe House
Suspect VoidG12 – Server Room
SUSPECT
No access within roofspace accessed via hatch in server room. Hatch is not accessible due to location of server equipment.
Area/Room Sample No
Building Component
Asbestos Content
Extent Condition Surface Treatment
Material Assessment
Recommendations/ Summary
Accessibility Photo ID
Re-inspected 24/09/12 - No access 2012 re-inspection.Re-inspected 18/09/13 - No Change.Re-inspected 24/09/14 - No Change.Re-inspected 28/10/15 - No ChangeRe-inspected 09/12/16 - No ChangeRe-inspected 07/12/17 - No ChangeRe-inspected 05/12/18 - No Change
Low presumption of the presence of asbestos materials.
Programme further investigation.
ASBESTOS SUSPECTED
Frequency of
Maintenance
Risk Assessment
Location Material Accessiblity
No.of Occupants
Main Activity in Area
Secondary Activity in Area
Material Extent
Frequency of Use
Time in Area
Maintenance Activity
Suspect Water Heater
G9 – Cleaners Cupboard
SUSPECT
No access within 'Heatrae Sadia Hotflo' water heater. Internal components may contain asbestos.
Area/Room Sample No
Building Component
Asbestos Content
Extent Condition Surface Treatment
Material Assessment
Recommendations/ Summary
Accessibility Photo ID
Re-inspected 24/09/12 - No Change.Re-inspected 18/09/13 - No Change.Re-inspected 24/09/14 - No Change.Re-inspected 28/10/15 - No ChangeRe-inspected 09/12/16 - No Change.Re-inspected 07/12/17 - No ChangeRe-inspected 05/12/18 - No Change
Low presumption of the presence of asbestos materials.
Programme further investigation.
ASBESTOS SUSPECTED
Frequency of
Maintenance
Risk Assessment
Location Material Accessiblity
No.of Occupants
Main Activity in Area
Secondary Activity in Area
Material Extent
Frequency of Use
Time in Area
Maintenance Activity
Prepared by Adams Environmental Ltd See survey report for scope/limitations of inspectionPage 45 of 112
First FloorThorpe Coombe House ASBESTOS REGISTER
S 19334.17Revision Issue N° 11
March 2019Thorpe Coombe House
Suspect Water Heater
F14 – Cleaners Cupboard
SUSPECT
No access within 'Heatrae Sadia Hotflo' water heater. Internal components may contain asbestos. A non-asbestos supalux lining panel is present to the rear of the cupboard door.
Area/Room Sample No
Building Component
Asbestos Content
Extent Condition Surface Treatment
Material Assessment
Recommendations/ Summary
Accessibility Photo ID
Re-inspected 24/09/12 - No Change.Re-inspected 18/09/13 - No Change.Re-inspected 24/09/14 - No Change.Re-inspected 28/10/15 - No ChangeRe-inspected 09/12/16 - No ChangeRe-inspected 07/12/17 - No ChangeRe-inspected 05/12/18 - No Change
Low presumption of the presence of asbestos materials.
Programme further investigation.
ASBESTOS SUSPECTED
Frequency of
Maintenance
Risk Assessment
Location Material Accessiblity
No.of Occupants
Main Activity in Area
Secondary Activity in Area
Material Extent
Frequency of Use
Time in Area
Maintenance Activity
Prepared by Adams Environmental Ltd See survey report for scope/limitations of inspectionPage 46 of 112
Ground Floor
Wood House ASBESTOS REGISTER RE-INSPECTION - THORPE COOMBE HOSPITAL
S 19334.17Revision Issue N° 11
Area/Room Sample No
Building Component
Asbestos Content
Extent Condition Surface Treatment
Material Assessment
Recommendations/ Summary
Accessibility
March 2019
Wood House
Photo ID
G.13 – Boiler Room
LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
@ 0.5m²
Resin Composite Toilet Cistern
G.01 a – Disabled W.C.
ASBESTOS REMOVED
2 N° original asbestos toilet cisterns removed as part of Woodhouse refurbishment. (Refer to Estates Dept for records, etc.). Re-inspection date 20/03/09.
R E M O V E D6m²
Not applicable.
Decorative Coating G.01 a – Disabled W.C.
ASBESTOS REMOVED
'Artex' type decorative coating remains to original ceiling, present in void area above existing ceilings of refurbished Woodhouse Building. Re-inspection dates 20/03/09 (Rev 2) & 05/07/11 (Rev 3).
Re-inspected 24/09/12 - No access to inspect, dropped plaster ceiling present throughout.Re-inspected 18/09/13 - Removed; no textured coating present to ceiling. Details of removal unknown to Adams Environmental.
R E M O V E D
24m²
Not applicable.
Decorative Coating G.01 a – Entrance Lobby
ASBESTOS REMOVED
'Artex' type decorative coating remains to original ceiling, present in void area above existing ceilings of refurbished Woodhouse Building. Re-inspection dates 20/03/09 (Rev 2) & 05/07/11 (Rev 3).
Re-inspected 24/09/12 - No access to inspect, dropped plaster ceiling present throughout.Re-inspected 18/09/13 - Removed; no textured coating present to ceiling. Details of removal unknown to Adams Environmental.
R E M O V E D
144m²No Asbestos Detected
Bitumen Felt Roofing Underfelt
08 AExtension Block Roofspace
MATERIAL SAMPLED; NO ASBESTOS DETECTED
Roofing underfelt beneath roof tiles.
Male / Female Toilets
LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
Prepared by Adams Environmental Ltd See survey report for scope/limitations of inspectionPage 47 of 112
Ground Floor
Wood House ASBESTOS REGISTER RE-INSPECTION - THORPE COOMBE HOSPITAL
S 19334.17Revision Issue N° 11
Area/Room Sample No
Building Component
Asbestos Content
Extent Condition Surface Treatment
Material Assessment
Recommendations/ Summary
Accessibility
March 2019
Wood House
Photo ID
G.09 – Office LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
G.08 – Office LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
N/A Suspect Electrics
G.02 – Office (former Kitchen)
ASBESTOS REMOVED
Original old style fuses to electrical fuse box removed as part of building refurbishment works.
R E M O V E D6m²No Asbestos
DetectedVinyl Floor Tile11 AG.02 – Office
(former Kitchen)
MATERIAL SAMPLED; NO ASBESTOS DETECTED
Green floor tiles. (Removed as part of building refurbishment)
6m²No Asbestos Detected
Adhesive 12 AG.02 – Office (former Kitchen)
MATERIAL SAMPLED; NO ASBESTOS DETECTED
Adhesive to green floor tiles. (Removed as part of building refurbishment).
4mNo Asbestos Detected
Thermal Insulation 07 AOriginal Building Roofspace
MATERIAL SAMPLED; NO ASBESTOS DETECTED
Hessian insulation to 1 N° pipe in south east corner of roofspace.
Prepared by Adams Environmental Ltd See survey report for scope/limitations of inspectionPage 48 of 112
Ground Floor
Wood House ASBESTOS REGISTER RE-INSPECTION - THORPE COOMBE HOSPITAL
S 19334.17Revision Issue N° 11
Area/Room Sample No
Building Component
Asbestos Content
Extent Condition Surface Treatment
Material Assessment
Recommendations/ Summary
Accessibility
March 2019
Wood House
Photo ID
Rear Extension Corridor
LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
G.01 – Reception Office
LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
48m²
Not applicable.
Decorative Coating G.01 a – WC ASBESTOS REMOVED
'Artex' type decorative coating remains to original ceiling, present in void area above existing ceilings of refurbished Woodhouse Building. Re-inspection dates 20/03/09 (Rev 2) & 05/07/11 (Rev 3).
Re-inspected 24/09/12 - No access to inspect, dropped plaster ceiling present throughout.Re-inspected 18/09/13 - Removed; no textured coating present to ceiling. Details of removal unknown to Adams Environmental.
R E M O V E D
Prepared by Adams Environmental Ltd See survey report for scope/limitations of inspectionPage 49 of 112
First Floor
Wood House ASBESTOS REGISTER RE-INSPECTION - THORPE COOMBE HOSPITAL
S 19334.17Revision Issue N° 11
Area/Room Sample No
Building Component
Asbestos Content
Extent Condition Surface Treatment
Material Assessment
Recommendations/ Summary
Accessibility
March 2019
Wood House
Photo ID
G.13 – Water Tank Room
LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
Prepared by Adams Environmental Ltd See survey report for scope/limitations of inspectionPage 50 of 112
External
Wood House ASBESTOS REGISTER RE-INSPECTION - THORPE COOMBE HOSPITAL
S 19334.17Revision Issue N° 11
Area/Room Sample No
Building Component
Asbestos Content
Extent Condition Surface Treatment
Material Assessment
Recommendations/ Summary
Accessibility
March 2019
Wood House
Photo ID
6m²No Asbestos Detected
Supalux-type Board Ceiling Panel
47 ABoiler Room MATERIAL SAMPLED; NO ASBESTOS DETECTED
Supalux panels form ceiling.
8mAC SoffitFront Elevation (East)
ASBESTOS REMOVED
Original asbestos cement (AC) soffits to domed roof to front elevation removed and replaced in non-asbestos materials. (Refer to Estates Dept for work records, etc.) Re-inspection date 20/03/09.
R E M O V E DUnkno
wnNo Asbestos
DetectedCloth Thermal
Insulation63 ANorth
Garden adjacent G13 Boiler Room
MATERIAL SAMPLED; NO ASBESTOS DETECTED
Cloth insulation to 1 N° pipe in sub-ground duct running in east-west direction.
48mNo Asbestos Detected
Supalux-type Board Soffit
09 APerimeter of Extension Block
MATERIAL SAMPLED; NO ASBESTOS DETECTED
Supalux soffits present to perimeter of roof to rear extension block. Re-inspection date 20/03/09.
60mAC GutteringPerimeter of Original Building
ASBESTOS REMOVED
Original asbestos cement (AC) guttering to perimeter of roof to original 'Nissan Hut' building replaced in plastic . (Refer to Estates Dept for work records, etc.)
R E M O V E D60mAC SoffitPerimeter of
Original Building
ASBESTOS REMOVED
Original asbestos cement (AC) soffits to perimeter of roof to original 'Nissan Hut' building removed and replaced in non-asbestos materials. (Refer to Estates Dept for work records, etc.) Re-inspection date 20/03/09.
R E M O V E D8mAC SoffitRear
Elevation of Original Building (West)
ASBESTOS REMOVED
Original asbestos cement (AC) soffits to domed roof to rear elevation removed and replaced in non-asbestos materials. (Refer to Estates Dept for work records, etc.) Re-inspection date 20/03/09.
R E M O V E DPrepared by Adams Environmental Ltd See survey report for scope/limitations of inspection
Page 51 of 112
External
Wood House ASBESTOS REGISTER RE-INSPECTION - THORPE COOMBE HOSPITAL
S 19334.17Revision Issue N° 11
Area/Room Sample No
Building Component
Asbestos Content
Extent Condition Surface Treatment
Material Assessment
Recommendations/ Summary
Accessibility
March 2019
Wood House
Photo ID
160m²No Asbestos Detected
Bitumen Felt Roofing
04 ARoof of Original Building
MATERIAL SAMPLED; NO ASBESTOS DETECTED
Bitumen felt to roof of original 'Nissan Hut' building.
Prepared by Adams Environmental Ltd See survey report for scope/limitations of inspectionPage 52 of 112
Basement
CAMHS - Family Consultation
ASBESTOS REGISTER RE-INSPECTION - THORPE COOMBE HOSPITAL
S 19334.17Revision Issue N° 11
Area/Room Sample No
Building Component
Asbestos Content
Extent Condition Surface Treatment
Material Assessment
Recommendations/ Summary
Accessibility
March 2019
CAMHS - Family Consultation
Photo ID
< 0.5m²
No Asbestos Detected
Compressed Fibre Panel
21 ABoiler Room MATERIAL SAMPLED; NO ASBESTOS DETECTED
Redundant panel present to floor adjacent west wall.
@ 0.5m²
Thermal Insulation Debris
Boiler Room ASBESTOS REMOVED
Minor insulation debris occurrences identified to west wall, removed by local environmental clean of affected area by Romford Insulations Ltd. (AEL Report A7424 refers).
R E M O V E D<
0.5m²No Asbestos
DetectedSupalux-type Board
Panel19 ABoiler Room MATERIAL
SAMPLED; NO ASBESTOS DETECTED
Supalux panel is present to pipe penetration point in south wall. It has been sealed in with expandable foam.
> 1m²Thermal Insulation Debris Dust
Boiler Room ASBESTOS REMOVED
Minor insulation debris material removed from floor of boiler room by local environmental clean of affected area by Romford Insulations Ltd. (AEL Report A7424 refers).
R E M O V E D
Prepared by Adams Environmental Ltd See survey report for scope/limitations of inspectionPage 53 of 112
Ground Floor
CAMHS - Family Consultation
ASBESTOS REGISTER RE-INSPECTION - THORPE COOMBE HOSPITAL
S 19334.17Revision Issue N° 11
Area/Room Sample No
Building Component
Asbestos Content
Extent Condition Surface Treatment
Material Assessment
Recommendations/ Summary
Accessibility
March 2019
CAMHS - Family Consultation
Photo ID
G.15 – Cleaners Store
LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
G.08 – Conference Room
LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
Corridor LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
G.01 – Entrance Lobby
LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
G.07 – Office LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
G.12 – Office LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
G.10 – Office LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
Prepared by Adams Environmental Ltd See survey report for scope/limitations of inspectionPage 54 of 112
Ground Floor
CAMHS - Family Consultation
ASBESTOS REGISTER RE-INSPECTION - THORPE COOMBE HOSPITAL
S 19334.17Revision Issue N° 11
Area/Room Sample No
Building Component
Asbestos Content
Extent Condition Surface Treatment
Material Assessment
Recommendations/ Summary
Accessibility
March 2019
CAMHS - Family Consultation
Photo ID
G.13 – Office LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
G.06 – Office LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
G.18 – Office LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
G.09 – Office LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
G.05 – Office LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
G.11 – Office LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
G.04 – Office LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
Prepared by Adams Environmental Ltd See survey report for scope/limitations of inspectionPage 55 of 112
Ground Floor
CAMHS - Family Consultation
ASBESTOS REGISTER RE-INSPECTION - THORPE COOMBE HOSPITAL
S 19334.17Revision Issue N° 11
Area/Room Sample No
Building Component
Asbestos Content
Extent Condition Surface Treatment
Material Assessment
Recommendations/ Summary
Accessibility
March 2019
CAMHS - Family Consultation
Photo ID
G.17 – Office W.C.
LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
G.03 – Reception
LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
Stairwell LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
G.16 – Visitor's W.C.
LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
G.02 – Waiting Area
LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
Prepared by Adams Environmental Ltd See survey report for scope/limitations of inspectionPage 56 of 112
First Floor
CAMHS - Family Consultation
ASBESTOS REGISTER RE-INSPECTION - THORPE COOMBE HOSPITAL
S 19334.17Revision Issue N° 11
Area/Room Sample No
Building Component
Asbestos Content
Extent Condition Surface Treatment
Material Assessment
Recommendations/ Summary
Accessibility
March 2019
CAMHS - Family Consultation
Photo ID
1.01 – Corridor
LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
1.16 – Lobby LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
1.07 – Office LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
1.11 – Office LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
1.10 – Office LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
1.08 – Office LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
1.03 – Office LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
Prepared by Adams Environmental Ltd See survey report for scope/limitations of inspectionPage 57 of 112
First Floor
CAMHS - Family Consultation
ASBESTOS REGISTER RE-INSPECTION - THORPE COOMBE HOSPITAL
S 19334.17Revision Issue N° 11
Area/Room Sample No
Building Component
Asbestos Content
Extent Condition Surface Treatment
Material Assessment
Recommendations/ Summary
Accessibility
March 2019
CAMHS - Family Consultation
Photo ID
1.02 – Office LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
1.09 – Office LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
1.15 – Office LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
1.04 – Office LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
1.05 – Office LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
1.06 – Office LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
1.14 – Staff Room
LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
Prepared by Adams Environmental Ltd See survey report for scope/limitations of inspectionPage 58 of 112
First Floor
CAMHS - Family Consultation
ASBESTOS REGISTER RE-INSPECTION - THORPE COOMBE HOSPITAL
S 19334.17Revision Issue N° 11
Area/Room Sample No
Building Component
Asbestos Content
Extent Condition Surface Treatment
Material Assessment
Recommendations/ Summary
Accessibility
March 2019
CAMHS - Family Consultation
Photo ID
Stairwell LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
1.13 – W.C. LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
1.12 – W.C. LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
Water Tank Room
LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
Water tank room accessed via hatch in ceiling of Office 1.11.
Prepared by Adams Environmental Ltd See survey report for scope/limitations of inspectionPage 59 of 112
External
CAMHS - Family Consultation
ASBESTOS REGISTER RE-INSPECTION - THORPE COOMBE HOSPITAL
S 19334.17Revision Issue N° 11
Area/Room Sample No
Building Component
Asbestos Content
Extent Condition Surface Treatment
Material Assessment
Recommendations/ Summary
Accessibility
March 2019
CAMHS - Family Consultation
Photo ID
10m²No Asbestos Detected
Bitumen Felt Roofing
13 AFlat Roof to East Elevation
MATERIAL SAMPLED; NO ASBESTOS DETECTED
Bitumen felt to flat roof adjacent 1.12 W.C.
4mAC FlueNorth Elevation adjacent Room 1.11
ASBESTOS REMOVED
Redundant asbestos cement (AC) flue & cowl removed from external wall outside room 1.11.
R E M O V E D
Prepared by Adams Environmental Ltd See survey report for scope/limitations of inspectionPage 60 of 112
Ground Floor
Larkswood Centre ASBESTOS REGISTER RE-INSPECTION - THORPE COOMBE HOSPITAL
S 19334.17Revision Issue N° 11
Area/Room Sample No
Building Component
Asbestos Content
Extent Condition Surface Treatment
Material Assessment
Recommendations/ Summary
Accessibility
March 2019
Larkswood Centre
Photo ID
G.05 – Conference Room
LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
G.05 – Conference Room
LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
Corridor LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
G.01 – Entrance Lobby
LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
G.07 – Kitchen
LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
G.05 c – Lobby
LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
G.18 – Lobby LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
Prepared by Adams Environmental Ltd See survey report for scope/limitations of inspectionPage 61 of 112
Ground Floor
Larkswood Centre ASBESTOS REGISTER RE-INSPECTION - THORPE COOMBE HOSPITAL
S 19334.17Revision Issue N° 11
Area/Room Sample No
Building Component
Asbestos Content
Extent Condition Surface Treatment
Material Assessment
Recommendations/ Summary
Accessibility
March 2019
Larkswood Centre
Photo ID
G.05c – Lobby
LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
G.02 – Office LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
G.08 – Office LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
G.11 – Office LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
G.16 – Office LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
G.19 – Office LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
G.15 – Office LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
Prepared by Adams Environmental Ltd See survey report for scope/limitations of inspectionPage 62 of 112
Ground Floor
Larkswood Centre ASBESTOS REGISTER RE-INSPECTION - THORPE COOMBE HOSPITAL
S 19334.17Revision Issue N° 11
Area/Room Sample No
Building Component
Asbestos Content
Extent Condition Surface Treatment
Material Assessment
Recommendations/ Summary
Accessibility
March 2019
Larkswood Centre
Photo ID
G.10 – Office LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
G.09 – Office LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
G.13 – Office LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
G.05 b – Office
LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
G.14 – Office LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
G.03 – Reception
LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
Store LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
Prepared by Adams Environmental Ltd See survey report for scope/limitations of inspectionPage 63 of 112
Ground Floor
Larkswood Centre ASBESTOS REGISTER RE-INSPECTION - THORPE COOMBE HOSPITAL
S 19334.17Revision Issue N° 11
Area/Room Sample No
Building Component
Asbestos Content
Extent Condition Surface Treatment
Material Assessment
Recommendations/ Summary
Accessibility
March 2019
Larkswood Centre
Photo ID
Not applicable.
N/A Suspect Water Heater
Treatment Room
ASBESTOS REMOVED
No access within 'Heatrae Sadia' water heater. Internal components may contain asbestos.
R E M O V E DUnderstairs Cupboard (East Stairwell)
LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
Non-asbestos supalux lining panels to doors of cupboard.
Low presumption of the presence of asbestos materials.
Programme further investigation.
Understairs Cupboard (West Stairwell)
LOCATION NOT INSPECTED; ASBESTOS SUSPECTED
SUSPECT
No key access at time of survey.
Re-inspected 24/09/12 - No key access provided at time of inspection.Re-inspected 18/09/13 - No key access provided at time of inspection.Re-inspected 24/09/14 - No Change.Re-inspected 28/10/15 - No ChangeRe-inspected 09/12/16 - No Change.Re-inspected 07/12/17 - No ChangeRe-inspected 05/12/18 - No Change
0.5m²Resin Composite Toilet Cistern
G.12 – W.C. ASBESTOS REMOVED
Original 'Shires Lynx' asbestos toilet cistern removed as part of toilet refurbishment works. (Refer to Estates Dept for work records, etc.)
R E M O V E DW.C. adjacent G19
LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
G.05 a – Waiting Area
LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
Prepared by Adams Environmental Ltd See survey report for scope/limitations of inspectionPage 64 of 112
Ground Floor
Larkswood Centre ASBESTOS REGISTER RE-INSPECTION - THORPE COOMBE HOSPITAL
S 19334.17Revision Issue N° 11
Area/Room Sample No
Building Component
Asbestos Content
Extent Condition Surface Treatment
Material Assessment
Recommendations/ Summary
Accessibility
March 2019
Larkswood Centre
Photo ID
G.04 – Waiting Room
LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
Prepared by Adams Environmental Ltd See survey report for scope/limitations of inspectionPage 65 of 112
First Floor
Larkswood Centre ASBESTOS REGISTER RE-INSPECTION - THORPE COOMBE HOSPITAL
S 19334.17Revision Issue N° 11
Area/Room Sample No
Building Component
Asbestos Content
Extent Condition Surface Treatment
Material Assessment
Recommendations/ Summary
Accessibility
March 2019
Larkswood Centre
Photo ID
1.03 – BT Room
LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
Non-asbestos supalux panel to rear of door.
Cleaners Cupboard
LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
Corridor LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
1.09 – Female W.C.
LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
1.08 – Kitchen
LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
1.09 a – Male W.C.
LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
Prepared by Adams Environmental Ltd See survey report for scope/limitations of inspectionPage 66 of 112
First Floor
Larkswood Centre ASBESTOS REGISTER RE-INSPECTION - THORPE COOMBE HOSPITAL
S 19334.17Revision Issue N° 11
Area/Room Sample No
Building Component
Asbestos Content
Extent Condition Surface Treatment
Material Assessment
Recommendations/ Summary
Accessibility
March 2019
Larkswood Centre
Photo ID
1.21 – Office LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
1.23 – Office LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
1.06 – Office LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
1.05 – Office LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
1.04 – Office LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
1.02 – Office LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
1.19 – Office LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
Prepared by Adams Environmental Ltd See survey report for scope/limitations of inspectionPage 67 of 112
First Floor
Larkswood Centre ASBESTOS REGISTER RE-INSPECTION - THORPE COOMBE HOSPITAL
S 19334.17Revision Issue N° 11
Area/Room Sample No
Building Component
Asbestos Content
Extent Condition Surface Treatment
Material Assessment
Recommendations/ Summary
Accessibility
March 2019
Larkswood Centre
Photo ID
1.17 – Office LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
1.15 – Office LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
1.14 – Office LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
1.18 – Office LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
1.20 – Office LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
1.16 – Office LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
1.25 – Office LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
Prepared by Adams Environmental Ltd See survey report for scope/limitations of inspectionPage 68 of 112
First Floor
Larkswood Centre ASBESTOS REGISTER RE-INSPECTION - THORPE COOMBE HOSPITAL
S 19334.17Revision Issue N° 11
Area/Room Sample No
Building Component
Asbestos Content
Extent Condition Surface Treatment
Material Assessment
Recommendations/ Summary
Accessibility
March 2019
Larkswood Centre
Photo ID
1.11 – Office LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
1.07 – Photocopy Room
LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
Prepared by Adams Environmental Ltd See survey report for scope/limitations of inspectionPage 69 of 112
Second Floor
Larkswood Centre ASBESTOS REGISTER RE-INSPECTION - THORPE COOMBE HOSPITAL
S 19334.17Revision Issue N° 11
Area/Room Sample No
Building Component
Asbestos Content
Extent Condition Surface Treatment
Material Assessment
Recommendations/ Summary
Accessibility
March 2019
Larkswood Centre
Photo ID
Cleaners Cupboard
LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
Corridor LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
2.09 – Female W.C.
LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
2.04 – Kitchen
LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
2.01 – Lobby LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
2.09 a – Male W.C.
LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
Prepared by Adams Environmental Ltd See survey report for scope/limitations of inspectionPage 70 of 112
Second Floor
Larkswood Centre ASBESTOS REGISTER RE-INSPECTION - THORPE COOMBE HOSPITAL
S 19334.17Revision Issue N° 11
Area/Room Sample No
Building Component
Asbestos Content
Extent Condition Surface Treatment
Material Assessment
Recommendations/ Summary
Accessibility
March 2019
Larkswood Centre
Photo ID
1mNo Asbestos Detected
MMMF Thermal Insulation
56 A2.16 – Office MATERIAL SAMPLED; NO ASBESTOS DETECTED
'Versals' pipe insulation to pipework within eaves, accessed via hatch in wall below window.
2.25 – Office LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
2.02 – Office LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
2.11 – Office LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
2.24 – Store LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
2.03 – Team Room
LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
Prepared by Adams Environmental Ltd See survey report for scope/limitations of inspectionPage 71 of 112
Third Floor
Larkswood Centre ASBESTOS REGISTER RE-INSPECTION - THORPE COOMBE HOSPITAL
S 19334.17Revision Issue N° 11
Area/Room Sample No
Building Component
Asbestos Content
Extent Condition Surface Treatment
Material Assessment
Recommendations/ Summary
Accessibility
March 2019
Larkswood Centre
Photo ID
3m²No Asbestos Detected
Thermal Insulation Debris
57 A3.08 – Fire Escape Lobby
MATERIAL SAMPLED; NO ASBESTOS DETECTED
Debris to floor in eaves, accessed via low level door in fire escape lobby. Hessian insulation is present to 2 N° pipes. Limited access into eaves, viewed from doorway.
3.03 – Store LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
3.04 – Store LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
3.07 – Store LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
Low presumption of the presence of asbestos materials.
Programme further investigation.
Store Cupboard 2
LOCATION NOT INSPECTED; ASBESTOS SUSPECTED
SUSPECT
No key access into store cupboard located in 3.10 office.
Re-inspected 24/09/12 - No Change.Re-inspected 24/09/14 - No Change.Re-inspected 28/10/15 - No ChangeRe-inspected 09/12/16 - No Change.Re-inspected 07/12/17 - No ChangeRe-inspected 05/12/18 - No Change
Prepared by Adams Environmental Ltd See survey report for scope/limitations of inspectionPage 72 of 112
Roof
Larkswood Centre ASBESTOS REGISTER RE-INSPECTION - THORPE COOMBE HOSPITAL
S 19334.17Revision Issue N° 11
Area/Room Sample No
Building Component
Asbestos Content
Extent Condition Surface Treatment
Material Assessment
Recommendations/ Summary
Accessibility
March 2019
Larkswood Centre
Photo ID
Water Tank Room
LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
Water tank room accessed via flat roof or high level hatch in 3rd Floor Stairwell.
Prepared by Adams Environmental Ltd See survey report for scope/limitations of inspectionPage 73 of 112
Ground Floor
Psychotherapy Clinic ASBESTOS REGISTER RE-INSPECTION - THORPE COOMBE HOSPITAL
S 19334.17Revision Issue N° 11
Area/Room Sample No
Building Component
Asbestos Content
Extent Condition Surface Treatment
Material Assessment
Recommendations/ Summary
Accessibility
March 2019
Psychotherapy Clinic
Photo ID
Cleaners Cupboard
LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
G6 – Clinic Room
LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
G7 – Clinic Room
LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
G5 – Consulting Room
LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
G9 – Consulting Room
LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
G8 – Consulting Room
LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
G1 – Corridor LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
Prepared by Adams Environmental Ltd See survey report for scope/limitations of inspectionPage 74 of 112
Ground Floor
Psychotherapy Clinic ASBESTOS REGISTER RE-INSPECTION - THORPE COOMBE HOSPITAL
S 19334.17Revision Issue N° 11
Area/Room Sample No
Building Component
Asbestos Content
Extent Condition Surface Treatment
Material Assessment
Recommendations/ Summary
Accessibility
March 2019
Psychotherapy Clinic
Photo ID
Group Room 1
LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
G11 – Kitchen LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
G1 – Lobby LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
Reception/Admin
LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
G4 – Staff Room
LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
Understairs Cupboard
LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
G2 – W.C. LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
Prepared by Adams Environmental Ltd See survey report for scope/limitations of inspectionPage 75 of 112
First Floor
Psychotherapy Clinic ASBESTOS REGISTER RE-INSPECTION - THORPE COOMBE HOSPITAL
S 19334.17Revision Issue N° 11
Area/Room Sample No
Building Component
Asbestos Content
Extent Condition Surface Treatment
Material Assessment
Recommendations/ Summary
Accessibility
March 2019
Psychotherapy Clinic
Photo ID
N/A Suspect BoilerBoiler Room ASBESTOS REMOVED
Original 'Strebel' boiler unit. May contain internal ACM components, etc.
Re-inspected 24/09/12 - No Change.Re-inspected 18/09/13 - No Change.Re-inspected 24/09/14 - No Change.Re-inspected 28/10/15 - No ChangeRe-inspected 09/12/16 - No Change.Re-inspected 07/12/17. New Vaillant boiler & associated equipment now installed. Old boiler unit no longer present.
R E M O V E D
Cleaners Cupboard
LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
1.6 – Consulting Room
LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
1.5 – Consulting Room
LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
1.4 – Consulting Room
LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
1.10 – Consulting Room
LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
Prepared by Adams Environmental Ltd See survey report for scope/limitations of inspectionPage 76 of 112
First Floor
Psychotherapy Clinic ASBESTOS REGISTER RE-INSPECTION - THORPE COOMBE HOSPITAL
S 19334.17Revision Issue N° 11
Area/Room Sample No
Building Component
Asbestos Content
Extent Condition Surface Treatment
Material Assessment
Recommendations/ Summary
Accessibility
March 2019
Psychotherapy Clinic
Photo ID
1.9 – Consulting Room
LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
1.8 – Consulting Room
LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
1.7 – Consulting Room
LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
1.1 – Corridor LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
1.2 – Female W.C.
LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
Group Room 2
LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
Group Room 3
LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
Prepared by Adams Environmental Ltd See survey report for scope/limitations of inspectionPage 77 of 112
First Floor
Psychotherapy Clinic ASBESTOS REGISTER RE-INSPECTION - THORPE COOMBE HOSPITAL
S 19334.17Revision Issue N° 11
Area/Room Sample No
Building Component
Asbestos Content
Extent Condition Surface Treatment
Material Assessment
Recommendations/ Summary
Accessibility
March 2019
Psychotherapy Clinic
Photo ID
1.3 – Male W.C.
LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
200m²No Asbestos Detected
Bitumen Felt Roofing Underfelt
43 ARoofspace MATERIAL SAMPLED; NO ASBESTOS DETECTED
Roofing underfelt present below roof tiles within roofspace.
Trainees' Office
LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
Prepared by Adams Environmental Ltd See survey report for scope/limitations of inspectionPage 78 of 112
Basement
Thorpe Coombe House ASBESTOS REGISTER RE-INSPECTION - THORPE COOMBE HOSPITAL
S 19334.17Revision Issue N° 11
Area/Room Sample No
Building Component
Asbestos Content
Extent Condition Surface Treatment
Material Assessment
Recommendations/ Summary
Accessibility
March 2019
Thorpe Coombe House
Photo ID
< 0.5m²
No Asbestos Detected
Mastic Putty55 AB1 – Boiler Room
MATERIAL SAMPLED; NO ASBESTOS DETECTED
Fire putty between sections of 'Beeston' boiler. Limited access within boiler, asbestos rope gaskets may be present.
< 0.5m²
Thermal Insulation Debris
B1 – Boiler Room
ASBESTOS REMOVED
Minor insulation debris to wall at high level removed by Romford Insulations Ltd. AEL Report A7424 refers.
R E M O V E D16m²No Asbestos
DetectedPlaster Ceiling Panel52 AB1 – Boiler
RoomMATERIAL SAMPLED; NO ASBESTOS DETECTED
Fibrous plasterboard panels form ceiling. High level non-asbestos supalux boxing also present to north east corner.
< 0.5m²
No Asbestos Detected
Slate Shuttering51 ADuct MATERIAL SAMPLED; NO ASBESTOS DETECTED
Slate shuttering and packing to ceiling at pipe penetration point in north west corner.
< 0.5m²
Thermal Insulation Debris
Duct ASBESTOS REMOVED
Minor insulation debris removed where visible from floor area of duct running adjacent to the boiler room by Romford Insulations Ltd . AEL Report A7424 refers.
R E M O V E D<
0.5m²No Asbestos
DetectedThermal Insulation
Debris 54 AB6 – Store MATERIAL
SAMPLED; NO ASBESTOS DETECTED
Insulation debris to 2 N° redundant calorifiers within store. Fibrous plasterboard ceiling panels also present, as identified in Boiler Room B1.
Prepared by Adams Environmental Ltd See survey report for scope/limitations of inspectionPage 79 of 112
Ground Floor
Thorpe Coombe House ASBESTOS REGISTER RE-INSPECTION - THORPE COOMBE HOSPITAL
S 19334.17Revision Issue N° 11
Area/Room Sample No
Building Component
Asbestos Content
Extent Condition Surface Treatment
Material Assessment
Recommendations/ Summary
Accessibility
March 2019
Thorpe Coombe House
Photo ID
1m²No Asbestos Detected
Supalux-type Board Panel
49 AG3 – Boardroom
MATERIAL SAMPLED; NO ASBESTOS DETECTED
Non-asbestos supalux infill panels to entrance door.
1m²No Asbestos Detected
Supalux-type Board Panel
48 AG3 – Boardroom
MATERIAL SAMPLED; NO ASBESTOS DETECTED
Non-asbestos supalux infill panel to redundant fireplace.
G14 – Boiler Room
LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
G13 – Corridor
LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
G8 – Corridor LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
G6 – Corridor LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
Prepared by Adams Environmental Ltd See survey report for scope/limitations of inspectionPage 80 of 112
Ground Floor
Thorpe Coombe House ASBESTOS REGISTER RE-INSPECTION - THORPE COOMBE HOSPITAL
S 19334.17Revision Issue N° 11
Area/Room Sample No
Building Component
Asbestos Content
Extent Condition Surface Treatment
Material Assessment
Recommendations/ Summary
Accessibility
March 2019
Thorpe Coombe House
Photo ID
G7 – Disabled W.C.
LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
G4 – Entrance Lobby
LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
G2 – Kitchen LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
G11 – Office LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
Non-asbestos supalux infill panel present to redundant fireplace.
G10 – Office LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
Non-asbestos supalux infill panels present to door.
G5 – Office LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
Non-asbestos supalux infill panels present to door.
Prepared by Adams Environmental Ltd See survey report for scope/limitations of inspectionPage 81 of 112
Ground Floor
Thorpe Coombe House ASBESTOS REGISTER RE-INSPECTION - THORPE COOMBE HOSPITAL
S 19334.17Revision Issue N° 11
Area/Room Sample No
Building Component
Asbestos Content
Extent Condition Surface Treatment
Material Assessment
Recommendations/ Summary
Accessibility
March 2019
Thorpe Coombe House
Photo ID
G1 – Stairwell Lobby
LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
Prepared by Adams Environmental Ltd See survey report for scope/limitations of inspectionPage 82 of 112
First Floor
Thorpe Coombe House ASBESTOS REGISTER RE-INSPECTION - THORPE COOMBE HOSPITAL
S 19334.17Revision Issue N° 11
Area/Room Sample No
Building Component
Asbestos Content
Extent Condition Surface Treatment
Material Assessment
Recommendations/ Summary
Accessibility
March 2019
Thorpe Coombe House
Photo ID
F8 – Female W.C.
LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
F9 – Kitchen LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
F1 – Landing LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
F2 – Lobby LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
F12 – Male W.C.
LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
F4 – Office LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
F3 – Office LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
Prepared by Adams Environmental Ltd See survey report for scope/limitations of inspectionPage 83 of 112
First Floor
Thorpe Coombe House ASBESTOS REGISTER RE-INSPECTION - THORPE COOMBE HOSPITAL
S 19334.17Revision Issue N° 11
Area/Room Sample No
Building Component
Asbestos Content
Extent Condition Surface Treatment
Material Assessment
Recommendations/ Summary
Accessibility
March 2019
Thorpe Coombe House
Photo ID
F13 – Office LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
Non-asbestos supalux infill panel present to redundant fireplace.
F5 – Photocopy Room
LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
Roofspace LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
Roofspace accessed via hatches in F13 Office and F10 Landing.
F6 – Secretaries Office
LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
F11 – 'Sepia' Training Room
LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
F4a – Waiting Area
LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
Prepared by Adams Environmental Ltd See survey report for scope/limitations of inspectionPage 84 of 112
Second Floor
Thorpe Coombe House ASBESTOS REGISTER RE-INSPECTION - THORPE COOMBE HOSPITAL
S 19334.17Revision Issue N° 11
Area/Room Sample No
Building Component
Asbestos Content
Extent Condition Surface Treatment
Material Assessment
Recommendations/ Summary
Accessibility
March 2019
Thorpe Coombe House
Photo ID
S1 – Landing LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
S6 – Meeting Room
LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
Non-asbestos supalux infill panels present to door.
S2 – Office LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
S4 – Office LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
S6 – Office LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
S3 – Office LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
Non-asbestos supalux infill panel present to redundant fireplace.
Prepared by Adams Environmental Ltd See survey report for scope/limitations of inspectionPage 85 of 112
Second Floor
Thorpe Coombe House ASBESTOS REGISTER RE-INSPECTION - THORPE COOMBE HOSPITAL
S 19334.17Revision Issue N° 11
Area/Room Sample No
Building Component
Asbestos Content
Extent Condition Surface Treatment
Material Assessment
Recommendations/ Summary
Accessibility
March 2019
Thorpe Coombe House
Photo ID
S5 – Office LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
Non-asbestos supalux infill panels present to door.
S4 – Office LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
Non-asbestos supalux infill panels present to door.
S5 – Office LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
Prepared by Adams Environmental Ltd See survey report for scope/limitations of inspectionPage 86 of 112
Ground Floor
Comley Bank Building ASBESTOS REGISTER RE-INSPECTION - THORPE COOMBE HOSPITAL
S 19334.17Revision Issue N° 11
Area/Room Sample No
Building Component
Asbestos Content
Extent Condition Surface Treatment
Material Assessment
Recommendations/ Summary
Accessibility
March 2019
Comley Bank Building
Photo ID
Office 01 LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
Office 02 LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
Office 03 LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
Office 04 LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
Office Cluster01-04
LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
Reception Lobby
LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
Reception Office
LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
Prepared by Adams Environmental Ltd See survey report for scope/limitations of inspectionPage 87 of 112
Ground Floor
Comley Bank Building ASBESTOS REGISTER RE-INSPECTION - THORPE COOMBE HOSPITAL
S 19334.17Revision Issue N° 11
Area/Room Sample No
Building Component
Asbestos Content
Extent Condition Surface Treatment
Material Assessment
Recommendations/ Summary
Accessibility
March 2019
Comley Bank Building
Photo ID
Storage Cupboard
LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
Storage Elec. Cupboard
LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
W.C. 01 LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
W.C. 02 LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
Prepared by Adams Environmental Ltd See survey report for scope/limitations of inspectionPage 88 of 112
External
Comley Bank Building ASBESTOS REGISTER RE-INSPECTION - THORPE COOMBE HOSPITAL
S 19334.17Revision Issue N° 11
Area/Room Sample No
Building Component
Asbestos Content
Extent Condition Surface Treatment
Material Assessment
Recommendations/ Summary
Accessibility
March 2019
Comley Bank Building
Photo ID
All Elevations LOCATION INSPECTED; NO ASBESTOS IDENTIFIED
Prepared by Adams Environmental Ltd See survey report for scope/limitations of inspectionPage 89 of 112
Re-Inspection Survey
Appendix II: Materials Report
AEL Ref.
Thorpe Coombe Hospital S 19334.17 Rev. 11
SOP10.10F7 Issue 10 Nov 17
Adams Environmental LtdUnit 6, Kimpton Link Business Park, 40 Kimpton Road, SUTTON SM3 9QP
Tel: 020 8641 6000 Fax: 020 8641 0666 Website: www.adamsenvironmental.co.uk Registered Office: Onslow Hall, Little Green, Richmond, TW9 1QH. Company Registration No. 2055824
Materials Report A reproduction of Materials Report M6556.1, August 2004, provided as part of original Survey Report is enclosed, detailing original sampling analysis results. A reproduction Materials Report M15505.17, October 2014, carried out as part of Re-inspection also enclosed. No additional sampling has been carried out as part of these re-inspections.
Page 90 of 112
MATERIALS REPORT M 6556.1
Mr Martin FreestonBarking, Havering & Redbridge HospitalNHS Trust (Estates Services & CapitalPlanning Dept), Harold Wood HospitalGubbins LaneHAROLD WOODRM3 0BE
Site Thorpe Coombe Hospital
Report Date August 2004
DirectorJeff Bowdery
DirectorNigel Hare
Opinions and interpretations marked * are outside the scope of UKAS accreditation
All works involving removal, repair or disturbance of asbestos materials should be conducted in
accordance with the Control of Asbestos at Work Regulations; further information is available from
Adams Environmental Ltd
Analysis of samples is in accordance with Adams Environmental documented in-house methods, based on stereo microscopy, polarised light, dispersion staining techniques and MDHS 77: Asbestos in bulk materials - Sampling and identification by polarised light microscopy (PLM)
Samples taken by Adams Environmental are collected according to documented in-house methods unless stated otherwise
Where the sample has been received from the Client, the analytical and Report details are given in good faith on the basis of the information received
Page 1 of 8
Adams Environmental LtdUnit 6, Kimpton Link Business Park, 40 Kimpton Road, SUTTON SM3 9QP
Tel: 020 8641 6000 Fax: 020 8641 0666 Website: www.adamsenvironmental.co.uk Registered Office: 4-5 King Street, Richmond, TW9 1ND. Company Registration Number 2055824
Page 91 of 112
MATERIALS REPORT M 6556.1Laboratory
Ref. and DetailsSiteRef.
Location Asbestos Fibre Type Identified (and Quantity*)
Material Type*
37344 taken by Tracy Milnes on 04/08/2004; analysed by John
Passmore on 09/08/200401 Childrens Centre - external
asbestos cement wall cladding to main entrance.
ACChrysotile (Significant)
37345 taken by Martin Stemp on 04/08/2004; analysed by John
Passmore on 09/08/200402 Children's Centre - external
asbestos cement soffits to perimeter of roof.
ACChrysotile (Significant)
37346 taken by Martin Stemp on 04/08/2004; analysed by John
Passmore on 09/08/200403 Childrens Centre - external -
asbestos cement guttering to perimeter of roof.
ACChrysotile (Significant)
37347 taken by Tracy Milnes on 04/08/2004; analysed by John Passmore on 09/08/2004 and checked by Peter Whetman on
11/08/2004
04 Childrens Centre - external - bitumen to roof.
Bitumen FeltNo Asbestos Detected
37348 taken by Tracy Milnes on 04/08/2004; analysed by John Passmore on 09/08/2004 and checked by Peter Whetman on
11/08/2004
05 Childrens Centre - ground floor - staff W.C. (G03) - textured coating to ceiling.
Decorative Coating
Chrysotile (Trace)
37349 taken by Tracy Milnes on 04/08/2004; analysed by John
Passmore on 09/08/200406 Ground floor - G03 - Staff W.C. -
resin composite toilet cistern.Resin
CompositeAmosite (Significant)
37350 taken by Martin Stemp on 04/08/2004; analysed by John Passmore on 09/08/2004 and checked by Peter Whetman on
11/08/2004
07 Childrens centre - roofspace over G03 - staff W.C. - insulation to pipework.
Thermal Insulation
No Asbestos Detected
37351 taken by Martin Stemp on 04/08/2004; analysed by John Passmore on 09/08/2004 and checked by Peter Whetman on
11/08/2004
08 Childrens centre - roofspace over new extension block (via G.21) - roofing underfelt.
Bitumen FeltNo Asbestos Detected
37352 taken by Martin Stemp on 04/08/2004; analysed by John
Passmore on 09/08/200409 Childrens centre - external -
extension block - supalux-type board perimeter soffits.
Supalux-type Board
No Asbestos Detected
37353 taken by Martin Stemp on 04/08/2004; analysed by John
Passmore on 09/08/200410 Childrens centre - external -
extension block - roof tiles.ACChrysotile (Significant)
37354 taken by Martin Stemp on 04/08/2004; analysed by John Passmore on 09/08/2004 and checked by Peter Whetman on
11/08/2004
11 Childrens centre - ground floor - G10 Kitchen - vinyl floor tiles.
VinylNo Asbestos Detected
Page 2 of 8
Adams Environmental LtdUnit 6, Kimpton Link Business Park, 40 Kimpton Road, SUTTON SM3 9QP
Tel: 020 8641 6000 Fax: 020 8641 0666 Website: www.adamsenvironmental.co.uk Registered Office: 4-5 King Street, Richmond, TW9 1ND. Company Registration Number 2055824
Page 92 of 112
MATERIALS REPORT M 6556.1Laboratory
Ref. and DetailsSiteRef.
Location Asbestos Fibre Type Identified (and Quantity*)
Material Type*
37355 taken by Martin Stemp on 04/08/2004; analysed by John Passmore on 09/08/2004 and checked by Peter Whetman on
11/08/2004
12 Childrens centre - ground floor - G10 Kitchen - vinyl floor tiles adhesive.
AdhesiveNo Asbestos Detected
37356 taken by Martin Stemp on 04/08/2004; analysed by Peter Whetman on 09/08/2004 and checked by Tracy Milnes on
11/08/2004
13 Family Consultation - external - flat roof to front elevation - bitumen felt.
Bitumen FeltNo Asbestos Detected
37357 taken by Martin Stemp on 05/08/2004; analysed by Peter
Whetman on 09/08/200414 Family Consultation - external flat
roof - asbestos cement flue and cowl.
ACChrysotile (Substantial)
37358 taken by Martin Stemp on 05/08/2004; analysed by Peter
Whetman on 09/08/200415 Family Consultation - basement
boiler room - pipe insulation debris - within low level duct off stairwell.
Thermal Insulation
Debris
Crocidolite (Trace)Amosite (Significant)
Chrysotile (Substantial)
37359 taken by Martin Stemp on 05/08/2004; analysed by Peter
Whetman on 10/08/200416 Family Consultation - basement
boiler room - asbestos cement shuttering to low level duct off main stairwell.
ACChrysotile (Significant)
37360 taken by Martin Stemp on 05/08/2004; analysed by Peter
Whetman on 10/08/200417 Family Consultation - basement
boiler room - asbestos cement shuttering - within low level duct off main stairwell.
ACChrysotile (Significant)
37361 taken by Martin Stemp on 05/08/2004; analysed by Peter
Whetman on 10/08/200418 Family Consultation - basement
boiler room - pipe insulation debris to wall at high level over doorway adjacent boiler.
Thermal Insulation
Debris
Amosite (Trace)Chrysotile (Significant)
37362 taken by Martin Stemp on 05/08/2004; analysed by Peter Whetman on 10/08/2004 and checked by Tracy Milnes on
11/08/2004
19 Family Consultation - basement boiler room - board at pipe penetration points to south wall - adjacent water cylinder.
Supalux-type Board
No Asbestos Detected
37363 taken by Martin Stemp on 05/08/2004; analysed by Peter
Whetman on 10/08/200420 Family Consultation - basement
boiler room - pipe insulation in duct at high level travelling north from boiler room.
Thermal Insulation
Crocidolite (Significant)Amosite (Significant)
Chrysotile (Substantial)
Page 3 of 8
Adams Environmental LtdUnit 6, Kimpton Link Business Park, 40 Kimpton Road, SUTTON SM3 9QP
Tel: 020 8641 6000 Fax: 020 8641 0666 Website: www.adamsenvironmental.co.uk Registered Office: 4-5 King Street, Richmond, TW9 1ND. Company Registration Number 2055824
Page 93 of 112
MATERIALS REPORT M 6556.1Laboratory
Ref. and DetailsSiteRef.
Location Asbestos Fibre Type Identified (and Quantity*)
Material Type*
37364 taken by Martin Stemp on 05/08/2004; analysed by Peter Whetman on 10/08/2004 and checked by Tracy Milnes on
11/08/2004
21 Family Consultation - basement boiler room - rundundant board to floor adjacent sump pit.
Compressed Fibre
No Asbestos Detected
37365 taken by Martin Stemp on 05/08/2004; analysed by Peter
Whetman on 10/08/200422 Family Consultation - basement
boiler room - dust and debris to floor around boiler.
Thermal Insulation
Debris
Chrysotile (Trace)
37366 taken by Martin Stemp on 05/08/2004; analysed by Peter
Whetman on 11/08/200423 Old Generator Room - external
south side - pipe insulation debris - within sub floor duct adjacent Family Consultation boiler room entrance and generator room.
Thermal Insulation
Debris
Amosite (Significant)
37367 taken by Martin Stemp on 05/08/2004; analysed by Peter
Whetman on 10/08/200424 Old Generator Room - external -
generator room - asbestos cement roof sheeting.
ACChrysotile (Significant)
37368 taken by Martin Stemp on 05/08/2004; analysed by Peter Whetman on 10/08/2004 and checked by Tracy Milnes on
11/08/2004
25 Rodway Ward - ground floor - room G15 - red & grey floor tiles.
VinylNo Asbestos Detected
37369 taken by Martin Stemp on 05/08/2004; analysed by Peter
Whetman on 10/08/200426 Rodway Ward - ground floor -
room G15 - red & grey floor tiles adhesive.
AdhesiveChrysotile (Trace)
37370 taken by Martin Stemp on 05/08/2004; analysed by David
Povey on 10/08/200427 Rodway Ward - ground floor - G16
patient toilets - 'Shires Lynx' toilet cistern.
Resin Composite
Amosite (Significant)
37371 taken by Martin Stemp on 05/08/2004; analysed by Peter
Whetman on 10/08/200428 Rodway Ward - ground floor -
G19 - infill panels to old door positions.
AIBAmosite (Significant)
37372 taken by Martin Stemp on 05/08/2004; analysed by Peter
Whetman on 10/08/200429 Rodway Ward - ground floor -
G19 - panel beneath external window.
ACChrysotile (Significant)
37373 taken by Martin Stemp on 05/08/2004; analysed by David
Povey on 10/08/2004 and checked by Peter Whetman on
10/08/2004
30 Rodway Ward - ground floor - lift lobby - infill panels around and over double door position.
Supalux-type Board
No Asbestos Detected
Page 4 of 8
Adams Environmental LtdUnit 6, Kimpton Link Business Park, 40 Kimpton Road, SUTTON SM3 9QP
Tel: 020 8641 6000 Fax: 020 8641 0666 Website: www.adamsenvironmental.co.uk Registered Office: 4-5 King Street, Richmond, TW9 1ND. Company Registration Number 2055824
Page 94 of 112
MATERIALS REPORT M 6556.1Laboratory
Ref. and DetailsSiteRef.
Location Asbestos Fibre Type Identified (and Quantity*)
Material Type*
37374 taken by Martin Stemp on 05/08/2004; analysed by Peter
Whetman on 10/08/200431 Rodway Ward - ground floor -
G36 - asbestos insulating board ceiling tiles to true ceiling in existing ceiling void.
AIBAmosite (Significant)
37375 taken by Martin Stemp on 05/08/2004; analysed by Peter Whetman on 10/08/2004 and checked by Tracy Milnes on
11/08/2004
32 Rodway Ward - ground floor - G36 - boiler cupboard - supalux lining panel to door.
Supalux-type Board
No Asbestos Detected
37376 taken by Martin Stemp on 05/08/2004; analysed by Peter
Whetman on 10/08/200433 Bryson Ward - 1st floor - 1.17
cleaner's cupboard - asbestos cement panel to low level ceiling.
ACChrysotile (Significant)
37377 taken by Martin Stemp on 05/08/2004; analysed by David
Povey on 10/08/2004 and checked by Peter Whetman on
10/08/2004
34 Bryson Ward - 1st floor - 1.10 kitchen - supalux-type panel to old door position.
Supalux-type Board
No Asbestos Detected
37378 taken by Martin Stemp on 05/08/2004; analysed by Peter
Whetman on 10/08/200435 Rodway & Bryson - basement -
boiler room B01 - redundant CAF gasket to floor.
CAFChrysotile (Substantial)
37379 taken by Martin Stemp on 05/08/2004; analysed by David
Povey on 10/08/200436 Rodway & Bryson - basement -
boiler room B01 - thermal insulation debris to pipework at high level to north wall.
Thermal Insulation
Debris
Crocidolite (Significant)Amosite (Significant)
Chrysotile (Substantial)
37380 taken by Martin Stemp on 05/08/2004; analysed by Peter
Whetman on 10/08/200437 Rodway & Bryson - basement
boiler room B02 - thermal insulation at old pipework penetration point at high level adjacent door to B01.
Thermal Insulation
Debris
Crocidolite (Significant)Amosite (Significant)
Chrysotile (Substantial)
37381 taken by Martin Stemp on 05/08/2004; analysed by David
Povey on 10/08/200438 Rodway & Bryson - basement
boiler room B02 - thermal insulation debris to vertical pipework midway along west wall.
Thermal Insulation
Debris
Amosite (Significant)Chrysotile (Significant)
37382 taken by Martin Stemp on 05/08/2004; analysed by Peter
Whetman on 10/08/200439 Rodway & Bryson - basement -
boiler room - asbestos rope caulking to asbestos cement flue adjacent gas boiler.
RopeChrysotile (Substantial)
Page 5 of 8
Adams Environmental LtdUnit 6, Kimpton Link Business Park, 40 Kimpton Road, SUTTON SM3 9QP
Tel: 020 8641 6000 Fax: 020 8641 0666 Website: www.adamsenvironmental.co.uk Registered Office: 4-5 King Street, Richmond, TW9 1ND. Company Registration Number 2055824
Page 95 of 112
MATERIALS REPORT M 6556.1Laboratory
Ref. and DetailsSiteRef.
Location Asbestos Fibre Type Identified (and Quantity*)
Material Type*
37383 taken by Martin Stemp on 05/08/2004; analysed by Peter
Whetman on 10/08/200440 Rodway & Bryson - basement -
boiler room B02 - asbestos cement flue to gas boiler.
ACChrysotile (Significant)
37384 taken by Martin Stemp on 05/08/2004; analysed by David
Povey on 10/08/200441 Rodway & Bryson - basement -
boiler room B01 - thermal insualtion debris at high level to east wall adjacent redundant pipe hanger.
Thermal Insulation
Debris
Crocidolite (Significant)Chrysotile (Significant)
37385 taken by Martin Stemp on 05/08/2004; analysed by Peter Whetman on 10/08/2004 and checked by Tracy Milnes on
11/08/2004
42 Rodway & Bryson - basement - boiler room B02 - dust and debris to top of calorifier 2.
Thermal Insulation
Debris
No Asbestos Detected
37386 taken by Martin Stemp on 06/08/2004; analysed by Peter Whetman on 11/08/2004 and checked by Tracy Milnes on
11/08/2004
43 Psychotherapy Clinic - roofspace - original building - roofing underfelt.
Bitumen FeltNo Asbestos Detected
37387 taken by Martin Stemp on 06/08/2004; analysed by Peter Whetman on 10/08/2004 and checked by Tracy Milnes on
11/08/2004
44 Bryson - first floor - 1.19 - lounge - grey & red floor tiles.
VinylChrysotile (Trace)
37388 taken by Martin Stemp on 06/08/2004; analysed by Peter Whetman on 10/08/2004 and checked by Tracy Milnes on
11/08/2004
45 Bryson Ward - first floor - 1.19 - lounge - grey & red floor tiles adhesive.
AdhesiveNo Asbestos Detected
37389 taken by Martin Stemp on 06/08/2004; analysed by Peter Whetman on 11/08/2004 and checked by Tracy Milnes on
11/08/2004
46 Bryson Ward - 1st floor - west stairwell - door panels within cupboard.
Supalux-type Board
No Asbestos Detected
37390 taken by Martin Stemp on 06/08/2004; analysed by Peter Whetman on 11/08/2004 and checked by Tracy Milnes on
11/08/2004
47 Childrens Centre - ground floor - boiler room - ceiling panels.
Supalux-type Board
No Asbestos Detected
37406 taken by Martin Stemp on 09/08/2004; analysed by Tracy
Milnes on 11/08/200448 Thorpe Coombe House - ground
floor - boardroom - supalux type panel - infill within fireplace to chimney stack.
Supalux-type Board
No Asbestos Detected
37407 taken by Martin Stemp on 09/08/2004; analysed by Tracy
Milnes on 11/08/200449 Thorpe Coombe House - ground
floor - boardroom - infil panels to door.
Supalux-type Board
No Asbestos Detected
Page 6 of 8
Adams Environmental LtdUnit 6, Kimpton Link Business Park, 40 Kimpton Road, SUTTON SM3 9QP
Tel: 020 8641 6000 Fax: 020 8641 0666 Website: www.adamsenvironmental.co.uk Registered Office: 4-5 King Street, Richmond, TW9 1ND. Company Registration Number 2055824
Page 96 of 112
MATERIALS REPORT M 6556.1Laboratory
Ref. and DetailsSiteRef.
Location Asbestos Fibre Type Identified (and Quantity*)
Material Type*
37408 taken by Martin Stemp on 09/08/2004; analysed by Tracy
Milnes on 11/08/200450 Thorpe Coombe House -
basement - boiler room duct debris to floor.
Thermal Insulation
Debris
Chrysotile (Trace)
37409 taken by Martin Stemp on 09/08/2004; analysed by Peter Whetman on 11/08/2004 and checked by Tracy Milnes on
11/08/2004
51 Thorpe Coombe House - basement - boiler room - duct - shuttering to slab ceiling.
SlateNo Asbestos Detected
37410 taken by Martin Stemp on 09/08/2004; analysed by Peter Whetman on 11/08/2004 and checked by Tracy Milnes on
11/08/2004
52 Thorpe Coombe House - basement - boiler room - dropped plaster ceiling.
PlasterNo Asbestos Detected
37411 taken by Martin Stemp on 09/08/2004; analysed by Peter
Whetman on 11/08/200453 Thorpe Coombe House -
basement - boiler room - room B6 - insulation debris to west wall at high level.
Thermal Insulation
Debris
Amosite (Significant)Chrysotile (Significant)
37412 taken by Martin Stemp on 09/08/2004; analysed by Peter Whetman on 11/08/2004 and checked by Tracy Milnes on
11/08/2004
54 Thorpe Coombe House - basement boiler room - room B6 - insulation debris to redundant calorifier.
Thermal Insulation
Debris
No Asbestos Detected
37413 taken by Martin Stemp on 09/08/2004; analysed by Peter Whetman on 11/08/2004 and checked by Tracy Milnes on
11/08/2004
55 Thorpe Coombe House - basement boiler room - putty to plates of gas boiler.
MasticNo Asbestos Detected
37414 taken by Martin Stemp on 09/08/2004; analysed by Peter Whetman on 11/08/2004 and checked by Tracy Milnes on
11/08/2004
56 Admin Block - Larkswood Centre - 2nd floor - room 2.16 - pipe insulation within eaves of room via access hatch.
MMMFNo Asbestos Detected
37415 taken by Martin Stemp on 09/08/2004; analysed by Peter Whetman on 11/08/2004 and checked by Tracy Milnes on
11/08/2004
57 Larkswood Centre - 3rd floor - roof access lobby 3.08 - eaves roof space - debris to floor.
Thermal Insulation
Debris
No Asbestos Detected
37416 taken by Martin Stemp on 09/08/2004; analysed by Peter
Whetman on 11/08/200458 Family Consultation - ground floor
generator room - cloth flashguard to redundant fuse.
ClothChrysotile (Substantial)
37417 taken by Martin Stemp on 10/08/2004; analysed by Tracy
Milnes on 11/08/200459 Bryson Ward - roofspace - east
end - adjacent hatch A - debris to wall at pipe penetration point.
Thermal Insulation
Debris
Crocidolite (Significant)Chrysotile (Substantial)
Page 7 of 8
Adams Environmental LtdUnit 6, Kimpton Link Business Park, 40 Kimpton Road, SUTTON SM3 9QP
Tel: 020 8641 6000 Fax: 020 8641 0666 Website: www.adamsenvironmental.co.uk Registered Office: 4-5 King Street, Richmond, TW9 1ND. Company Registration Number 2055824
Page 97 of 112
MATERIALS REPORT M 6556.1Laboratory
Ref. and DetailsSiteRef.
Location Asbestos Fibre Type Identified (and Quantity*)
Material Type*
37418 taken by Martin Stemp on 10/08/2004; analysed by Tracy
Milnes on 11/08/200460 Bryson Ward - roofspace - west
end - debris to pipework adjacent main walkway.
Thermal Insulation
Debris
Crocidolite (Significant)Chrysotile (Significant)
37419 taken by Martin Stemp on 10/08/2004; analysed by Tracy
Milnes on 11/08/200461 Bryson Ward - roofspace - west
end - adjacent hatch B - debris to wall at pipe penetration point.
Thermal Insulation
Debris
Crocidolite (Significant)Chrysotile (Substantial)
37420 taken by Martin Stemp on 10/08/2004; analysed by Peter
Whetman on 11/08/200462 Bryson Ward - roofspace - east
end - debris to conduit adjacent main walkway.
DustCrocidolite (Trace)Chrysotile (Significant)
37421 taken by Tracy Milnes on 10/08/2004; analysed by Tracy
Milnes on 11/08/2004 and checked by Peter Whetman on
11/08/2004
63 Childrens Centre - external - north garden - insulation to 1 N° pipe in duct.
ClothNo Asbestos Detected
Asbestos fibre type Commonly known as Quantity Visual assessment of sample fibre contentChrysotileAmositeCrocidolite
White asbestosBrown asbestosBlue asbestos
TraceSignificantSubstantial
less than 2%2% - 50%more than 50%
Page 8 of 8
Adams Environmental LtdUnit 6, Kimpton Link Business Park, 40 Kimpton Road, SUTTON SM3 9QP
Tel: 020 8641 6000 Fax: 020 8641 0666 Website: www.adamsenvironmental.co.uk Registered Office: 4-5 King Street, Richmond, TW9 1ND. Company Registration Number 2055824
Page 98 of 112
MATERIALS REPORT M 15505.17
Mr Daniel Rogers
NELFT
(North East London NHS Foundation Trust)
Est. & Projects Dept, Goodmayes Hospital
Barley Lane
ILFORD
IG3 8XJ
Site Thorpe Coombe Hospital
Report Date October 2014
Environmental Analyst
Sonia Campos
Director
Jeff Bowdery
Opinions and interpretations marked * are outside the scope of UKAS accreditation
All works involving removal, repair or disturbance of asbestos materials should be conducted in
accordance with the Control of Asbestos Regulations 2012; further information is available from Adams
Environmental Ltd
Analysis of samples is in accordance with Adams Environmental documented in-house methods, based on stereo microscopy, polarised light, dispersion staining techniques and HSG 248 (App.2): Asbestos in bulk materials - Sampling and identification by polarised light microscopy (PLM)
Samples taken by Adams Environmental are collected according to documented in-house methods unless stated otherwise
Where the sample has been received from the Client, the analytical and Report details are given in good faith on the basis of the information received
Page 1 of 2
0647
Adams Environmental LtdUnit 6, Kimpton Link Business Park, 40 Kimpton Road, SUTTON SM3 9QP
Tel: 020 8641 6000 Fax: 020 8641 0666 Website: www.adamsenvironmental.co.ukRegistered Office: 4-5 King Street, Richmond, TW9 1ND. Company Registration Number 2055824
Page 99 of 112
MATERIALS REPORT M 15505.17
LaboratoryRef. and Details
SiteRef.
Location Asbestos Fibre Type Identified
Material Type*
90366 taken by Alex Painter on 24/09/2014; analysed by Sonia
S.Campos on 29/09/2014
02 Family Consultation Building - Basement - Boiler Room - Debris to penetration through wall.
DebrisChrysotile
Asbestos fibre type Commonly known as
ChrysotileAmositeCrocidolite
White asbestosBrown asbestosBlue asbestos
Page 2 of 2
0647
Adams Environmental LtdUnit 6, Kimpton Link Business Park, 40 Kimpton Road, SUTTON SM3 9QP
Tel: 020 8641 6000 Fax: 020 8641 0666 Website: www.adamsenvironmental.co.uk Registered Office: 4-5 King Street, Richmond, TW9 1ND. Company Registration Number 2055824
Page 100 of 112
Re-Inspection Survey
Appendix III: Plans
AEL Ref.
Thorpe Coombe Hospital S 19334.17 Rev. 11
SOP10.10F7 Issue 10 Nov 17
Adams Environmental LtdUnit 6, Kimpton Link Business Park, 40 Kimpton Road, SUTTON SM3 9QP
Tel: 020 8641 6000 Fax: 020 8641 0666 Website: www.adamsenvironmental.co.uk Registered Office: Onslow Hall, Little Green, Richmond, TW9 1QH. Company Registration No. 2055824
Reference Location 19334.17/001 Wood House - Ground Floor
19334.17/002 CAMHS Family Consultation –
Basement, Ground & First Floors 19334.17/003 Larkswood Centre - Ground & First
Floors 19334.17/004 Larkswood Centre - Second & Third
Floors 19334.17/005 Psychotherapy Clinic - Ground & First
Floors
19334.17/006 Thorpe Coombe House - Basement 19334.17/007 Thorpe Coombe House – Ground, First &
Second Floors
19334.17/008 Comley Bank Building – Ground Floor The plans included with this report do not constitute the report, or its findings, and should not be used without thorough cross-reference to the report’s text and supporting documentation.
Page 101 of 112
Unit 6, Kimpton Link Business Park, 40 Kimpton Road, Sutton, SM3 9QP Tel: 020 8641 6000, Fax: 020 8641 0666
Email: adminsupport@adamsenvironmental.co.uk
Client: Site: Drawing Ref: Date Drawn: Survey Report Ref:
NELFT Goodmayes Hospital 157 Barley Lane Ilford IG3 8XJ
Wood House Thorpe Coombe Hospital Forest Road Walthamstow E17 3HP
19334.17/001
December 2018 S19334.17
Scale Floor:
Not to scale Wood House - Ground Floor Plans
K E Y
This drawing gives general indication of identified / suspected asbestos materials and is only to be used in conjunction
with the Asbestos Report & Register.
The drawings are colour-coded: do not use black-and-white photocopies.
Building Component
CL Cladding Panels DC Decorative CoatingSO Soffit Panel SU Suspect
Asbestos Materials Identified
No Access
Asbestos Materials Suspected
N
SO
DC
DC
DC
DC
CL CL
CL
Note: AC Roof Tiles present to external pitches of rear extension block.
Perimeter Heating System
SU
SU
SU
SU
SU
SU
Page 102 of 112
Unit 6, Kimpton Link Business Park, 40 Kimpton Road, Sutton, SM3 9QP Tel: 020 8641 6000, Fax: 020 8641 0666
Email: adminsupport@adamsenvironmental.co.uk
Client: Site: Drawing Ref: Date Drawn: Survey Report Ref: NELFT Goodmayes Hospital 157 Barley Lane Ilford IG3 8XJ
Family Consultation Block Thorpe Coombe Hospital Forest Road Walthamstow E17 3HP
19334.17/002
December 2018 S19334.17
Scale Floor:
Not to scale Family Consultation Block (CAMHS) - Basement, Ground and First Floor Plans
Duct extends beneath pathway to external
PI
UP
SH
DE
BASEMENT
N
SU
GROUND FLOOR
RISER
SU
RISER
FIRST FLOOR
K E Y
This drawing gives general indication of identified / suspected asbestos materials and is only to be used in conjunction with the Asbestos Report & Register.
The drawings are colour-coded: do not use black-and-white photocopies.
Building Component
DE Debris InsulationPI Pipe Insulation SH ShutteringUP Upstand SU SuspectSU Suspect
Asbestos Materials Identified
No Access
Asbestos Materials Suspected
SH
Boiler Room
PI DE
Duct route assumed under floor of building
DE
Page 103 of 112
Unit 6, Kimpton Link Business Park, 40 Kimpton Road, Sutton, SM3 9QP Tel: 020 8641 6000, Fax: 020 8641 0666
Email: adminsupport@adamsenvironmental.co.uk
Client: Site: Drawing Ref: Date Drawn: Survey Report Ref: NELFT Goodmayes Hospital 157 Barley Lane Ilford IG3 8XJ
Larkswood Centre Thorpe Coombe Hospital Forest Road Walthamstow E17 3HP
19334.17/003
December 2018 S19334.17
Scale Floor:
Not to scale Larkswood Centre - Ground and First Floor Plans
K E Y
This drawing gives general indication of identified / suspected asbestos materials and is only to be used in conjunction
with the Asbestos Report & Register.
The drawings are colour-coded: do not use black-and-white photocopies.
Building Component
SU Suspect
No Access
Asbestos Materials Suspected
N
GROUND FLOOR
FIRST FLOOR
G02OFFICE
TREATMENT ROOM
G05WAITING ROOM
G05 CONFERENCE ROOM
OFFICE
WAITING AREA
LOBBY
G12 WC
G13 OFFICE
G14 OFFICE
G15 OFFICE G16
OFFICE STORE
Cleaners Cupboard
SU
Page 104 of 112
Unit 6, Kimpton Link Business Park, 40 Kimpton Road, Sutton, SM3 9QP Tel: 020 8641 6000, Fax: 020 8641 0666
Email: adminsupport@adamsenvironmental.co.uk
Client: Site: Drawing Ref: Date Drawn: Survey Report Ref: NELFT Goodmayes Hospital 157 Barley Lane Ilford IG3 8XJ
Larkswood Centre Thorpe Coombe Hospital Forest Road Walthamstow E17 3HP
19334.17/004
December 2018 S19334.17
Scale Floor:
Not to scale Larkswood Centre - Second and Third Floor Plans
K E Y
This drawing gives general indication of identified / suspected asbestos materials and is only to be used in conjunction
with the Asbestos Report & Register.
The drawings are colour-coded: do not use black-and-white photocopies.
Building Component
SU Suspect
No Access
Asbestos Materials Suspected
2.02 OFFICE
2.03 TEAM ROOM
2.11 OFFICE
2.11 K
ITC
HE
N
SU
SU SU SU SU SU SU
SU SU SU SU SU SU SU SU
N
3.08 FIRE EXIT
LOBBY
3.01 OPEN PLAN
OFFICE
SU SU SU
SU
SU
SU SU SU SU
SU
SU
THIRD FLOOR
SECOND FLOOR
Page 105 of 112
Unit 6, Kimpton Link Business Park, 40 Kimpton Road, Sutton, SM3 9QP Tel: 020 8641 6000, Fax: 020 8641 0666
Email: adminsupport@adamsenvironmental.co.uk
Client: Site: Drawing Ref: Date Drawn: Survey Report Ref: NELFT Goodmayes Hospital 157 Barley Lane Ilford IG3 8XJ
Psychotherapy Clinic Thorpe Coombe Hospital Forest Road Walthamstow E17 3HP
19334.17/005
December 2018 S19334.17
Scale Floor:
Not to scale Psychotherapy Clinic - Ground and First Floor Plans
K E Y
This drawing gives general indication of identified / suspected asbestos materials and is only to be used in conjunction
with the Asbestos Report & Register.
The drawings are colour-coded: do not use black-and-white photocopies.
Building Component
SU Suspect * Codes with asterisks denote a building component
suspected or known to be present but whose exact location is unknown.
No Access
Asbestos Materials Suspected
G04 G05 G06
G07G08G09G10 G11 Kitchen
N
Group Room 1 SU
Boiler Room
FIRST FLOOR
Ground FLOOR
Page 106 of 112
Unit 6, Kimpton Link Business Park, 40 Kimpton Road, Sutton, SM3 9QP Tel: 020 8641 6000, Fax: 020 8641 0666
Email: adminsupport@adamsenvironmental.co.uk
Client: Site: Drawing Ref: Date Drawn: Survey Report Ref: NELFT Goodmayes Hospital 157 Barley Lane Ilford IG3 8XJ
Thorpe Coombe House Thorpe Coombe Hospital Forest Road Walthamstow E17 3HP
19334.17/006
December 2018 S19334.17
Scale Floor:
Not to scale Thorpe Coombe House – Basement Floor Plan
K E Y
This drawing gives general indication of identified / suspected asbestos materials and is only to be used in conjunction
with the Asbestos Report & Register.
The drawings are colour-coded: do not use black-and-white photocopies.
Building Component
GA Gaskets SU Suspect
Asbestos Materials Present
Asbestos Materials Suspected
* Codes with asterisks denote a building componentsuspected or known to be present but whose exact location is unknown.
SU
N
GA* GA* GA*
GA* GA* GA* GA*
Page 107 of 112
Unit 6, Kimpton Link Business Park, 40 Kimpton Road, Sutton, SM3 9QP Tel: 020 8641 6000, Fax: 020 8641 0666
Email: adminsupport@adamsenvironmental.co.uk
Client: Site: Drawing Ref: Date Drawn: Survey Report Ref: NELFT Goodmayes Hospital 157 Barley Lane Ilford IG3 8XJ
Thorpe Coombe House Thorpe Coombe Hospital Forest Road Walthamstow E17 3HP
19334.17/007
December 2018 S19334.17
Scale Floor:
Not to scale Thorpe Coombe House – Ground, First and Second Floor Plans
K E Y
This drawing gives general indication of identified / suspected asbestos materials and is only to be used in conjunction
with the Asbestos Report & Register.
The drawings are colour-coded: do not use black-and-white photocopies.
Building Component
SU Suspect
No Access
Asbestos Materials Suspected
SU
N
Loft Hatch not accessed.
SU
Page 108 of 112
Unit 6, Kimpton Link Business Park, 40 Kimpton Road, Sutton, SM3 9QP Tel: 020 8641 6000, Fax: 020 8641 0666
Email: adminsupport@adamsenvironmental.co.uk
Client: Site: Drawing Ref: Date Drawn: Survey Report Ref: NELFT Goodmayes Hospital 157 Barley Lane Ilford IG3 8XJ
Comley Bank building Thorpe Coombe Hospital Forest Road Walthamstow E17 3HP
19334.17/008
December 2018 S19334.17
Scale Floor:
Not to scale Comley Bank building – Ground Floor Plan
K E Y
This drawing is for information only and is based on a Client supplied original and is only to be used in conjunction with the associated Asbestos Re‐Inspection Report & Register,
of which it forms Appendix III.
The drawings are colour‐coded: do not use black‐and‐white photocopies.
Page 109 of 112
Re-Inspection Survey
Appendix IV: Photographs
AEL Ref.
Thorpe Coombe Hospital S 19334.17 Rev. 11
SOP10.10F7 Issue 10 Nov 17
Adams Environmental LtdUnit 6, Kimpton Link Business Park, 40 Kimpton Road, SUTTON SM3 9QP
Tel: 020 8641 6000 Fax: 020 8641 0666 Website: www.adamsenvironmental.co.uk Registered Office: Onslow Hall, Little Green, Richmond, TW9 1QH. Company Registration No. 2055824
P01. Wood House Building – Asbestos Cement (AC) profiled wall cladding and soffit to entrance porch canopy
P02. Wood House Building – Asbestos Cement (AC) tiles to rear extension pitched roof.
Page 110 of 112
Re-Inspection Survey
Appendix IV: Photographs
AEL Ref.
Thorpe Coombe Hospital S 19334.17 Rev. 11
SOP10.10F7 Issue 10 Nov 17
Adams Environmental LtdUnit 6, Kimpton Link Business Park, 40 Kimpton Road, SUTTON SM3 9QP
Tel: 020 8641 6000 Fax: 020 8641 0666 Website: www.adamsenvironmental.co.uk Registered Office: Onslow Hall, Little Green, Richmond, TW9 1QH. Company Registration No. 2055824
P03. CAMHS Family Consultation Building – Duct running off stairwell in basement area. Insulation debris to floor of duct. (Access point to duct now sealed). Note; a seal to 1 No. duct is broken/open. Recommendation – Reseal Duct.
P04. CAMHS Family Consultation Building – Duct running off stairwell in basement area to external ground area.
P05. CAMHS Family Consultation Building – Duct running off stairwell in basement area. Access point to duct sealed.
P06. CAMHS Family Consultation Building – Duct running off stairwell in basement area to external ground area.
P07. CAMHS Family Consultation Building. – Duct running off stairwell in basement area to external ground area. Insulation debris within sub-ground duct between the Old Generator position & Family Consultation building.
Page 111 of 112
Re-Inspection Survey
Appendix IV: Photographs
AEL Ref.
Thorpe Coombe Hospital S 19334.17 Rev. 11
SOP10.10F7 Issue 10 Nov 17
Adams Environmental LtdUnit 6, Kimpton Link Business Park, 40 Kimpton Road, SUTTON SM3 9QP
Tel: 020 8641 6000 Fax: 020 8641 0666 Website: www.adamsenvironmental.co.uk Registered Office: Onslow Hall, Little Green, Richmond, TW9 1QH. Company Registration No. 2055824
P08. Psychotherapy Clinic –Ground Floor – Waiting Room electrical Cupboard. ACMs suspected as internal components within electrical switch gear.
P09. Psychotherapy Clinic –First Floor – Boiler Room. Modern installation; Boiler not suspected to contain internal ACM components
Page 112 of 112