Title 24 Compliant

Title 24 Acceptance Test Technician Lab/Hands-on Task Form

Lab Work Performed (Mech Form) Mech-2A OSA Ventilation Acceptance

Student Name ______________________________________________________

Student Signature ____________________________________________________

Date of Lab Exam ____________________________________________________

Instructors Name ____________________________________________________

Instructor Signature __________________________________________________

Date Witnessed ______________________________________________

The above signed is verification of proof of lab performed testing of said Title 24 Mechanical Acceptance Form per NITC and the California State Pipe Trades Council.

Title 24 Compliant

Title 24 Acceptance Test Technician Lab/Hands-on Task Form

Lab Work Performed (Mech Form) Mech-3A Pkg. CAV, Unitary AC Control Acceptance

Student Name ______________________________________________________

Student Signature ____________________________________________________

Date of Lab Exam ____________________________________________________

Instructors Name ____________________________________________________

Instructor Signature __________________________________________________

Date Witnessed ______________________________________________

The above signed is verification of proof of lab performed testing of said Title 24 Mechanical Acceptance Form per NITC and the California State Pipe Trades Council.

Title 24 Compliant

Title 24 Acceptance Test Technician Lab/Hands-on Task Form

Lab Work Performed (Mech Form) Mech-4A Air Distribution System Acceptance

Student Name ______________________________________________________

Student Signature ____________________________________________________

Date of Lab Exam ____________________________________________________

Instructors Name ____________________________________________________

Instructor Signature __________________________________________________

Date Witnessed ______________________________________________

The above signed is verification of proof of lab performed testing of said Title 24 Mechanical Acceptance Form per NITC and the California State Pipe Trades Council.

Title 24 Compliant

Title 24 Acceptance Test Technician Lab/Hands-on Task Form

Lab Work Performed (Mech Form) Mech-5A Air Economizer Controls Acceptance

Student Name ______________________________________________________

Student Signature ____________________________________________________

Date of Lab Exam ____________________________________________________

Instructors Name ____________________________________________________

Instructor Signature __________________________________________________

Date Witnessed ______________________________________________

The above signed is verification of proof of lab performed testing of said Title 24 Mechanical Acceptance Form per NITC and the California State Pipe Trades Council.

Title 24 Compliant

Title 24 Acceptance Test Technician Lab/Hands-on Task Form

Lab Work Performed (Mech Form) Mech-6A Demand Controlled Ventilation Acceptance

Student Name ______________________________________________________

Student Signature ____________________________________________________

Date of Lab Exam ____________________________________________________

Instructors Name ____________________________________________________

Instructor Signature __________________________________________________

Date Witnessed ______________________________________________

The above signed is verification of proof of lab performed testing of said Title 24 Mechanical Acceptance Form per NITC and the California State Pipe Trades Council.

Title 24 Compliant

Title 24 Acceptance Test Technician Lab/Hands-on Task Form

Lab Work Performed (Mech Form) Mech-7A Supply Fan Variable Flow Control Acceptance

Student Name ______________________________________________________

Student Signature ____________________________________________________

Date of Lab Exam ____________________________________________________

Instructors Name ____________________________________________________

Instructor Signature __________________________________________________

Date Witnessed ______________________________________________

The above signed is verification of proof of lab performed testing of said Title 24 Mechanical Acceptance Form per NITC and the California State Pipe Trades Council.

Title 24 Compliant

Title 24 Acceptance Test Technician Lab/Hands-on Task Form

Lab Work Performed (Mech Form) Mech-8A Valve Leakage Acceptance

Student Name ______________________________________________________

Student Signature ____________________________________________________

Date of Lab Exam ____________________________________________________

Instructors Name ____________________________________________________

Instructor Signature __________________________________________________

Date Witnessed ______________________________________________

The above signed is verification of proof of lab performed testing of said Title 24 Mechanical Acceptance Form per NITC and the California State Pipe Trades Council.

Title 24 Compliant

Title 24 Acceptance Test Technician Lab/Hands-on Task Form

Lab Work Performed (Mech Form) Mech-9A Supply Water Temperature Reset Controls Acceptance

Student Name ______________________________________________________

Student Signature ____________________________________________________

Date of Lab Exam ____________________________________________________

Instructors Name ____________________________________________________

Instructor Signature __________________________________________________

Date Witnessed ______________________________________________

The above signed is verification of proof of lab performed testing of said Title 24 Mechanical Acceptance Form per NITC and the California State Pipe Trades Council.

Title 24 Compliant

Title 24 Acceptance Test Technician Lab/Hands-on Task Form

Lab Work Performed (Mech Form) Mech-10A Hydronic System Variable Flow Control Acceptance

Student Name ______________________________________________________

Student Signature ____________________________________________________

Date of Lab Exam ____________________________________________________

Instructors Name ____________________________________________________

Instructor Signature __________________________________________________

Date Witnessed ______________________________________________

The above signed is verification of proof of lab performed testing of said Title 24 Mechanical Acceptance Form per NITC and the California State Pipe Trades Council.

Title 24 Compliant

Title 24 Acceptance Test Technician Lab/Hands-on Task Form

Lab Work Performed (Mech Form) Mech-11A Automatic Demand Shed Control Acceptance

Student Name ______________________________________________________

Student Signature ____________________________________________________

Date of Lab Exam ____________________________________________________

Instructors Name ____________________________________________________

Instructor Signature __________________________________________________

Date Witnessed ______________________________________________

The above signed is verification of proof of lab performed testing of said Title 24 Mechanical Acceptance Form per NITC and the California State Pipe Trades Council.

Title 24 Compliant

Title 24 Acceptance Test Technician Lab/Hands-on Task Form

Lab Work Performed (Mech Form) Mech-12A Automatic Fault Detection Diagnostics (FDD) For Packaged Direct-Expansion (DX) Units Acceptance

Student Name ______________________________________________________

Student Signature ____________________________________________________

Date of Lab Exam ____________________________________________________

Instructors Name ____________________________________________________

Instructor Signature __________________________________________________

Date Witnessed ______________________________________________

The above signed is verification of proof of lab performed testing of said Title 24 Mechanical Acceptance Form per NITC and the California State Pipe Trades Council.

Title 24 Compliant

Title 24 Acceptance Test Technician Lab/Hands-on Task Form

Lab Work Performed (Mech Form) Mech-13A Automatic Fault Detection Diagnostics (FDD) for Air Handler Units and Zone Terminal Units Acceptance

Student Name ______________________________________________________

Student Signature ____________________________________________________

Date of Lab Exam ____________________________________________________

Instructors Name ____________________________________________________

Instructor Signature __________________________________________________

Date Witnessed ______________________________________________

The above signed is verification of proof of lab performed testing of said Title 24 Mechanical Acceptance Form per NITC and the California State Pipe Trades Council.

Title 24 Compliant

Title 24 Acceptance Test Technician Lab/Hands-on Task Form

Lab Work Performed (Mech Form) Mech-14A Distribution Energy Storage DX AC Acceptance

Student Name ______________________________________________________

Student Signature ____________________________________________________

Date of Lab Exam ____________________________________________________

Instructors Name ____________________________________________________

Instructor Signature __________________________________________________

Date Witnessed ______________________________________________

The above signed is verification of proof of lab performed testing of said Title 24 Mechanical Acceptance Form per NITC and the California State Pipe Trades Council.

Title 24 Compliant

Title 24 Acceptance Test Technician Lab/Hands-on Task Form

Lab Work Performed (Mech Form) Mech-15A Thermal Energy Storage (TES) System Acceptance

Student Name ______________________________________________________

Student Signature ____________________________________________________

Date of Lab Exam ____________________________________________________

Instructors Name ____________________________________________________

Instructor Signature __________________________________________________

Date Witnessed ______________________________________________

The above signed is verification of proof of lab performed testing of said Title 24 Mechanical Acceptance Form per NITC and the California State Pipe Trades Council.

Title 24 Compliant

Title 24 Acceptance Test Technician Lab/Hands-on Task Form

Lab Work Performed (Mech Form) Mech-16A Supply Air Temperature Reset Controls Acceptance

Student Name ______________________________________________________

Student Signature ____________________________________________________

Date of Lab Exam ____________________________________________________

Instructors Name ____________________________________________________

Instructor Signature __________________________________________________

Date Witnessed ______________________________________________

The above signed is verification of proof of lab performed testing of said Title 24 Mechanical Acceptance Form per NITC and the California State Pipe Trades Council.

Title 24 Compliant

Title 24 Acceptance Test Technician Lab/Hands-on Task Form

Lab Work Performed (Mech Form) Mech-17A Condenser Water Temperature Reset Controls Acceptance

Student Name ______________________________________________________

Student Signature ____________________________________________________

Date of Lab Exam ____________________________________________________

Instructors Name ____________________________________________________

Instructor Signature __________________________________________________

Date Witnessed ______________________________________________

The above signed is verification of proof of lab performed testing of said Title 24 Mechanical Acceptance Form per NITC and the California State Pipe Trades Council.

Title 24 Compliant

Title 24 Acceptance Test Technician Lab/Hands-on Task Form

Lab Work Performed (Mech Form) Mech-18A Energy Management Control System Acceptance

Student Name ______________________________________________________

Student Signature ____________________________________________________

Date of Lab Exam ____________________________________________________

Instructors Name ____________________________________________________

Instructor Signature __________________________________________________

Date Witnessed ______________________________________________

The above signed is verification of proof of lab performed testing of said Title 24 Mechanical Acceptance Form per NITC and the California State Pipe Trades Council.