ultra-flexible robust design - trinetics.com recloser... · ultrasmart recloser • 15kv & 27kv...
Post on 04-Feb-2018
236 Views
Preview:
TRANSCRIPT
UltraSmart Recloser
Ultra-flexible robust design
UltraSmart Recloser• 15kV&27kV3phgangedoperation•630A&800A;12.5kA•Compatiblewithmultiplecontrols•Vacuuminsoliddielectric•3or6voltagesensors
NOTE:Fordetailedspecificationsregardingratingsandoperatingcharacteristics,pleaseseetheinstallationinstructionsfortheUltraSmartRecloserandtheappropriatecontrol.
URCIIFalcon
UltraSmart RecloserReclosersprotectdistributionfeedersandequipmentfromdamagingfaultsandovercurrentsthatcanoccurduringabnormalsystemconditions.Whenafaultoccurs,theUltraSmartRecloser,togetherwiththecompatiblecontrol,detectsandinterruptsthefaultaccordingtoyourpreselectedsettingsandtheactualfaultconditions.
Featureslikeembeddedvoltageandcurrentsensors,alongwithcontroldependentfeatureslikedirectionalfaultprotection,loadmonitoring,profiles,eventlogsandoscillography,arejustafewofthestandardtoolsthatareavailableforsystemanalysisandcontrol.Withratingsfrom15kVthrough27kVand630Athrough800A,selecttheUltraSmartRecloserandcontroltomeetyourprotectionrequirements.
© 2012 Trinetics, a division of Maysteel, LLC. All Rights Reserved. SS_02_012_E_0512
Trinetics,adivisionofMaysteel,LLC,POBox1240,MenomoneeFalls,WI53052-1240Trinetics.com
Dimensions
Q u a l i t y C E Rt i F i E DISO 9001:2008
RecloSeR
Rated maximum voltage (kV, RMS) 15.5kV 27kV
Power frequency insulation level withstand test1 minute dry10 seconds wet
50kV45kV
60kV50kV
Creepage between upper & horizontal conductor (in/mm) 47/1195 47/1195
Creepage between horizontal conductor & ground (in/mm) 36/914 36/914
Weight (lbs/kg) 248.6/113 270.6/123
Rated lightning impulse withstand voltage (kV BIL) 110 125
Rated power frequency (Hz) 50/60
Rated continuous current (A rms) 630/800
Rated short-time withstand current 1 second (kA rms) 12.5/(16)kA1
Rated peak withstand current (kA) 32.5/(41.6)kA1
Rated symmetrical interrupting current (kA rms) 12.5/(16)kA1
Rated asymmetrical making current (kA peak) 32.5kA
Rated operating sequence O-0.25s-CO-2.0s-CO-2.0s-CO
Rated line charging interrupting current (A rms) 5A
Rated cable charging interrupting current (A rms) 25A
Mechanical operating sequences (CO) 10,000
Operating temperature range (˚C) –40˚C to 55˚C
Relative humidity (%) 0–100%
Maximum altitude above sea level (masl) 3000
Manufacture standards ANSI IEEE C37.60, IEC 62271-111
Current transformer ratio 600/1, 800/1–600/5, 800/52
Voltage transformer ratio 6.5V sensor or 120V PT2
Trip and close speed Time to close 60msTime to open 40ms
Duty cycle: 20% of interrupting rating with 12.0kA 50% of interrupting rating with 12.0kA 100% of interrupting rating with 12.0kA
44 operations56 operations16 operations
Auxiliary supply options 125–230Vac-Vdc
The UltraSmart Recloser is compatible with the following controls:• SEL-351R Falcon control• ICMI URC II control
1Thevaluesbetween()arevalidupto24kV2Selectpreferredoptionattimeoforder.
40.5”
25.5”
15”
15.1” 15” 15”
17.6”
2.5”
39”
top related