VARIABLE SPEED PUMPING SYSTEMSINSTRUCTION MANUAL
VARIABLE SPEED PUMP CONTROLLER ANDINTEGRATED AJUSTABLE FREQUENCY DRIVE
INSTALLER: PLEASE LEAVE THIS MANUAL FOR THE OWNER’S USE.
HV 2.1-3.11
DESCRIPTION: Microprocessor based pumpcontroller and adjustable speed drive for variablevolume pumping systems. The controller consistsof the following components: microprocessor,operator interface with alphanumeric display, andmembrane keypad.
OPERATIONAL LIMITS: See the control panelnameplate for operating voltage, current draw, aswell as information on the equipment to beconnected to the control panel.
SAFETY INSTRUCTION
This safety alert symbol will be used in thismanual to draw attention to safety relatedinstructions. When used, the safety alertsymbol means ATTENTION!BECOME ALERT! YOUR SAFETY IS INVOLVED!FAILURE TO FOLLOW THE INSTRUCTION MAYRESULT IN A SAFETY HAZARD!
WARNING LABEL #S11550INSTALLED IN THIS LOCATION.IF MISSING IT MUST BEREPLACED.
INSTRUCTION MANUAL
210 980-2HV 120-1-ENBG26.03.2003
HV3.15-3.22
Operating Instruction
2
Index
1 Important safety instructions ........................................................................5
2 System Design................................................................................................7
3 Pressure tank ................................................................................................8
4 Technical Data - Frequency Inverter And General Data .................................9
5 Dimensions and Weights .............................................................................11
6 Mounting the Technovar..............................................................................12
6.1Mounting the Technovar on the pump.................................................126.1.1 Components included............................................................................................ 126.1.2 Mounting .............................................................................................................. 136.1.3 Mounting the thermistor ....................................................................................... 23
6.2 Electric installation and wiring.............................................................246.2.1 Means of protection .............................................................................................. 246.2.2 Wiring the Technovar to the motor ....................................................................... 24
6.3 Main Voltage Terminals .......................................................................25
6.4 Control Terminals .................................................................................266.4.1 Control terminals ................................................................................................... 276.4.2 Dip-Switch on the controller board........................................................................ 286.4.3 Main parts from the control card........................................................................... 28
6.5 Front plate............................................................................................29
7 Language Selection......................................................................................30
8 Typical applications .....................................................................................31
8.1 Control .................................................................................................31
8.2 The Main Menu Setting........................................................................31
8.3 Single Pump – Pump Protection...........................................................348.3.1 To set run out protection....................................................................................... 34
8.4 Single Pump – System Curve Compensation........................................368.4.1 Entering the compensation values ......................................................................... 37
8.5 Multiple Pump - Constant Pressure and System Curve Compensation 38
9 Parameters of the main menu .....................................................................43
10 Settings at Secondary Menu .......................................................................46
10.1 JOG-MODE..........................................................................................46
10.2 Window - %........................................................................................47
10.3 Ramp Hysteresis .................................................................................47
10.4 Ramp 1: Fast running up time:...........................................................47
10.5 Ramp 2: Fast running down time:......................................................47
10.6 Ramp 3: Slow running up time: .........................................................48
10.7 Ramp 4: Slow running down time: ....................................................48
Operating Instruction
3
Ramp – Window .........................................................................................48
10.8 Maximum Frequency..........................................................................48
10.9 Minimum Frequency ..........................................................................49
10.10 Operation at the minimum frequency .............................................49
10.11 Delay time for shut off at minimum frequency ...............................49
10.12 Boost ................................................................................................49
10.13 Sensor – Adjust.................................................................................50
10.14 Sensor - Curve ..................................................................................50
10.15 Setting of the measuring range .......................................................50
10.16 Operation Mode ...............................................................................50
10.17 Control Response .............................................................................51
10.18 Start Value........................................................................................52
10.19 2nd Required Value............................................................................52
10.20 Configuration of 1st relay .................................................................53
10.21 Submenu Offset ...............................................................................5310.21.1 Source of the Offset input ................................................................................. 5310.21.2 1st Offset level .................................................................................................... 5310.21.3 2nd Offset level ................................................................................................... 5410.21.4 INTENSITY 1 ....................................................................................................... 5410.21.5 INTENSITY 2 ....................................................................................................... 54
10.22 Submenu Sequence control .............................................................5410.22.1 Lift Value ........................................................................................................... 5510.22.2 Fall Value ........................................................................................................... 5510.22.3 Release frequency of the following controller.................................................... 5610.22.4 Switch Interval ................................................................................................... 5610.22.5 Source of required value.................................................................................... 5710.22.6 Synchronous Control ......................................................................................... 5710.22.7 Pump status indication ...................................................................................... 5810.22.8 Error Signals for Data Bus Interruptions............................................................. 58
10.23 Submenu - RS 485 Interface .............................................................5910.23.1 Pump Address.................................................................................................... 5910.23.2 ADC Reference................................................................................................... 59
10.24 Compensation Frequency.................................................................59
10.25 Lift-Intensity .....................................................................................60
10.26 Analog - Output ...............................................................................60
10.27 Unit...................................................................................................61
10.28 Automatic test run ...........................................................................61
10.29 Submenu for manual test run ..........................................................6110.29.1 Activate manual test run.................................................................................... 6110.29.2 Test Frequency................................................................................................... 6110.29.3 Boost ................................................................................................................. 61
10.30 Submenu - Error ...............................................................................6210.30.1 Conveyor Limit................................................................................................... 6210.30.2 Delay Time ......................................................................................................... 62
Operating Instruction
4
10.30.3 Automatic Error reset......................................................................................... 6210.30.4 Erase Error memory ........................................................................................... 63
10.31 Operating Hours...............................................................................63
10.32 Display - Contrast .............................................................................63
10.33 Set Password ....................................................................................63
10.34 Operating Lock .................................................................................63
10.35 Internal Heater .................................................................................63
10.36 Setting Default Values......................................................................6410.36.1 Default Values Europe ....................................................................................... 6410.36.2 Default Values USA............................................................................................ 64
10.37 Saving...............................................................................................64
11 Error Signals................................................................................................65
11.1 Low Water ..........................................................................................65
11.2 Conveyor Control ...............................................................................65
11.3 Overheating – Motor ..........................................................................65
11.4 Overheating – Inverter .......................................................................65
11.5 Over voltage.......................................................................................65
11.6 Under voltage.....................................................................................66
11.7 Limit ...................................................................................................66
11.8 Short Circuit .......................................................................................66
11.9 Overload.............................................................................................66
11.10 Pressure Sensor Error I < 4 mA ......................................................66
11.11 Additional Error signals:...................................................................67
12 RS 485 - Interface........................................................................................67
13 Auxiliary Texts.............................................................................................68
14 Maintenance ...............................................................................................73
14.1 Notes ..................................................................................................73
Follow the Pump Operating and Maintenance InstructionsWe reserve the right to alter specifications
Operating Instruction
5
1 Important safety instructions
In addition to the instructions contained in these operating instructions please payattention to universal safety and accident prevention regulations.
The TECHNOVAR drive head must be disconnected from the power supply before any workcan be carried out in the electrical or mechanical part of the system.Installation, maintenance and repair work may only be carried out by trained, skilled andqualified personnel.Unauthorized modifications or changes to the system make all guarantees null and void.When in operation, the motor can be stopped by remote control, whereby the drive head andthe motor remain under voltage. For safety reasons, the unit has to be disconnected from thepower supply when carrying out work on the machinery as locking out the equipment byswitching off the release mechanism or set value cannot prevent accidental starting of themotor.
When the drive head is connected to power supply, the components of thepower unit as well as certain components of the master control unit are alsoconnected to the power supply.
Touching these components seriously endangers life !
Before removing the frequency inverter cover the system must bedisconnected from the power supply. After switching off the power supplywait at least 5 minutes before starting work on or in the TECHNOVAR drivehead (the capacitors in the intermediate circuit have to be discharged by theinstalled discharge resistors first).
Voltages of up to 800 volts are possible (if there are faults it can be higher)
All work, carried out when the frequency inverter is open, may only beperformed by qualified authorized staff.
Furthermore, care must be taken not to short circuit the neighbouringcomponents when connecting the external control wires and that opencable ends which are not in use are isolated.
Operating Instruction
6
The TECHNOVAR drive head contains electronic safety devices whichswitch off the control element in the event of faults, whereby themotor has zero current but remains energized and comes to a halt. Themotor can also be halted by mechanical blocking. If it is switched offelectronically the motor is disconnected from the mains voltagethrough the electronics of the frequency converter but is not potential-free in the circuit.In addition voltage fluctuations, especially power failures can cause thesystem to switch off itself.
The system may only be put into operation when it has been earthened. In addition,equipotential bonding of all pipes must be ensured.
Warns that failure to observe the precautions may cause electrical shock.Failure to follow these instructions could result in serious personal injury or death.
Warns that failure to follow these instructions could result in serious personalinjury or death as well as property damage.
Repair of faults can cause the motor to start up again!
Operating Instruction
7
2 System Design
The following diagrams show typical single pump and multi-pump systems using theTechnovar control unit. Connection can be made directly to a water supply or water can bedrawn from a break tank or well. In the case of break tanks and wells, level switches, shouldbe used to shut down the pumps when water is low. In the direct connection, a pressureswitch on the suction side should be used.
Single Pump Layout
Multiple Pump Layout
(1) pump with drive head
(2) diaphragm tank
(3) distribution panel
(4) gate valve
(5) non return valve
(8) incoming pressure control
(9) pressure gauge
(14) pressure transmitter
3
Operating Instruction
8
3 Pressure tank
A diaphragm pressure tank is used on the discharge side of the pump or pumps to maintainpressure in the line when there is no demand. This will keep the pumps from continuing torun. With the Technovar control unit, it is not necessary to have a large tank for supplypurposes.In selecting a tank, make sure it is permit and suitable for systems pressure. The tank shouldhave a capacity of more than 10% of the maximum system flow rate g/min of one pump (alsoin a multiple pump system!).
Pre charge the tank to the following:
Required pressure
Note: De-pressurize the tank prior to charging to ensure accuracy of thepre-charged pressure.
Pre charge pressure (psi)
Operating Instruction
9
4 Technical Data - Frequency Inverter And General Data
TECHNOVAR Technovaroutput tothe Motor
Supply Voltage
ModelNo.
nominalHorsepower
Max. Current
HV 2.1 2 7 A *1x220...240VAC ±15%
HV 2.2 3 10 A *1x220...240VAC ±15%
HV 3.2 3 5,7 A 3x380...460VAC ±15%
HV 3.3 4 7,3 A 3x380...460VAC ±15%
HV 3.4 5 9 A 3x380...460VAC ±15%
HV 3.5 7.5 13,5 A 3x380...460VAC ±15%
HV 3.7 10 17 A 3x380...460VAC ±15%
HV 3.11 15 23 A 3x380...460VAC ±15%
HV 3.15 20 30 A 3x380...460VAC ±15%
HV 3.18 25 37 A 3x380...460VAC ±15%
HV 3.22 30 43 A 3x380...460VAC ±15%
Note: Consult local authorities in your jurisdiction for fuse sizing.* Output voltage is 3 phase and requires a motor suitable for 220-240V/3/60 input power
Mains frequency: 48....62 Hz
Max. frequency: See chapter 10.8Min. frequency: 0 – f-max see chapter 10.9Electrical efficiency: > 95%
PleaseNote!
If the motor and control unit are assembled separately keep themotor cable as short as possible in order to avoid electromagneticemissions and capacitive currents. The length may not exceed 66 m.and a shielded cable has to be used.
Protection against: Short circuit, under- and over voltage, overheating of the electronics(overload) and additional external protective functions via PTC (motor temperature) andlow water switch.A mains filter is fitted to ensure interference immunity.
Operating Instruction
10
The HV-series frequency converter complies with the general EMV provisions and has beentested according to the following standards:
� Radio Interference Suppression EN 50082 Part 2EN 55011
� High Frequency Field Interference ENV 50204� Electrostatic Discharge EN 61000-4
Ambient temperature: +5° C ... +40°CStorage temperature: -25° C ... +55° C (+70°C during max. 24 hours.)Humidity: RH max. 50% at 40°C, Unlimited
RH max. 90% at 20°C, max. 30 days per year75% average per year (Class F, DIN 40 040)Condensation is not permitted !
Air pollution: The air may contain dry dust as found in workshops where there isno excessive quantity of dust due to machines. Excessive amountsof dust, acids, corrosive gases, salts etc. are not permitted
Altitude:: max. 3280 ft. above sea level At higher altitudes the max. availablepower has to be reduced. Please ask the manufacturer for furtherdetails.
Class of protection : IP 54 3.15-3.22Nema 4 bis 3.11
Operating Instruction
11
5 Dimensions and Weights
HV2.1/2.2/3.2/3.3/3.4 HV 3.5/3.7/3.11
all measurements in inches
Motorfancover max. 7.9 Ø Type: Weight: Type: Weight:
[lbs] [lbs]HV 2.1 13 HV 3.4 13HV 2.2 13 HV 3.5 22HV 3.2 13 HV 3.7 22HV 3.3 13 HV 3.11 22
Type Weight[lbs]
HV3.15 64HV3.18 64HV3.22 64
Motorfancover max. 15.2 Ø
HV 3.15/ 3.18/ 3.22
Operating Instruction
12
6 Mounting the Technovar
6.1 Mounting the Technovar on the pump
6.1.1 Components included
Thermal resistorScrew M5x90
Mounting clampcable gland
Operating Instruction
13
6.1.2 Mounting
HV2.1-3.11
Fix the display with the 4 Screws.
Mounting:
� Remove the 3 screws from the Technovar cover.� Place the Technovar fan cover on the motor .� Hang the 4 clamps by the Motor fan cover and mounted with the 4 screws.� Mounted the cover with the 3 screws.
Displaychangeableto 180°
Thermistor
4 Mountingclamps
4 ScrewsM5x90
Don’t forget the gaskets for the 3 screws .Ensure that there is no water on the unit before you open the cover.
Operating Instruction
14
If you use a motor with bis HV2,2kW, you have to use amounting ring.
Mounting ring
Operating Instruction
15
Wall mounting kit HV2.1-3.11
Included components for wallmounted kit HV2.1-3.11
1 mounting plate with fan Picture 1 A4 M3x 8mm screws (self threading) for kit HV2.1-3.4 Picture 2 B or M4x15mm screws (self threading) for kit HV3.5-3.11 Picture 2 B1 Molex connector Mod. 6471-021 Picture 2 C1 Cable gland M12x1,5 Picture 2 D1 counter nut M12x1,5 Picture 2 E
not included: Dowels and mounting screws for mounting the kit on the wall.Recommended diameter for this screws: � 5-6mm for kit HV2.1-3.4
� 6-8mm for kit HV3.5-3.11
Picture 1 Picture 2
A
B C D E
Operating Instruction
16
Picture 3 Picture 4
Picture 5
Picture 6 Picture 7
Picture 8 Picture 9
Open
Screw M3x8mm or M4x15mm(self threading)
+ plus pole
Molex connector
cable gland forfan cable
red
black
plus pole/ red Black / minus
Operating Instruction
17
Free space for wallmounting
MOUNTING INSTRUCTIONS
BEFORE REMOVING THE FREQUENCY INVERTER COVER THE SYSTEM MUST BE DIS-CONNECTEDFROM THE POWER SUPPLY. AFTER SWITCHING OFF THE POWER SUPPLY WAIT AT LEAST 5MINUTES BEFORE STARTING WORK ON OR IN THE TECHNOVAR DRIVE HEAD.
Mounting the mounting plate on the HV 2.1-3.11Place the heat sink of the Technovar on the mounting plate and fix them together by using the 4 selfthreading M3x8mm respective M4x15mm screws (Picture 3).
Connecting the fan-cableRemove the 3 screws holding the top cover of the Technovar and lift it carefully (picture 4).NOTE: Take care with the connection cable to the display and the Ground-cable!Left the cover aside.Mount the included cable gland (Picture 2D/2E) on the cover plate and put the cable through the cablegland. (Picture 7).Connect the fan cable with the Molex connector (Picture 5) and then plug it into the right connectionon the control card (Picture 6).NOTE: Take care of at the correct polarity: Red cable – plus pole
Black cable – minus pole
Fix the length of the cable inside the Technovar and tighten the cable gland to have ensure the IP55class of protection.
Note: You have to leave a free space in front of the Technovar forconfiguration and for dismounting the cover.
free space required for cooling and mounting
Operating Instruction
18
Afterwards replace the top cover and be careful with the connection cable to the display and theEarth-cable. At last fix the 3 screws of the top cover.
In Pictures 8 and 9 you can see the Technovar with the mounted wallmounting-kit.
Mark the 4 holes according to the dimension drawing (see next page) on the wall and drill it with adrilling machine. Mount the whole Technovar unit on the wall by using suitable screws.
Dimension drawing (HV2.1-3.4) (inches)
Dimension drawing (HV3.5-3.11)
Operating Instruction
19
Wall mounting – kit 15/22kW
Picture 1 Picture 2E
Included Components for wallmounted kit4 long screw M6x25 Picture 1 A4 washer Picture 1 B4 short screw M6x12 Picture 1 C4 washer Picture 1 D1 AC-fan incl. connection cable Picture 21 fan board incl. 3 fuses T 1A/500V Picture 3 and 3 G2 cable connector Picture 71 2 wire cable with connector Picture 7 and 81 cable gland for fan-cable Picture 121 wallmounted component Picture 13
A
B D
F
F
C
Operating Instruction
20
Picture 3 Picture 4
Picture 5 Picture 6
Picture 7 Picture 8
Picture 9 Picture 10
G
L1
L2
L3
U2
V2
W2
L3
L2
L1
Operating Instruction
21
Picture 11 Picture 12
12
Picture 13 Picture 14
Mounting the wallmounted kit on the Technovar
BEFORE REMOVING THE FREQUENCY INVERTER COVER THE SYSTEM MUST BE DIS-CONNECTEDFROM THE POWER SUPPLY. AFTER SWITCHING OFF THE POWER SUPPLY WAIT AT LEAST 5MINUTES BEFORE STARTING WORK ON OR IN THE TECHNOVAR DRIVE HEAD.
Mounting the fan-boardLoosen the 4 main screws from the Technovar cover and also the 8 screws holding thecontrol-card.Then remove the Technovar cover carefully. (Take care with the control-card and the GND-Cable.)Picture 3 shows you the fan-board (incl. the 3 fuses 1A/500V- picture 3/G) that you can fixwith the 3 plastic-distances in the 3 holes which are made for. (Picture 4)The power supply for the fan-board comes from the connections L1, L2, L3 on the primary-side from the rectifier-board.Please fasten the connection screw as well and connect the right cable with the rightconnectionCompare the cable number and the connection number. (Picture 5).
Connecting the control-cable
Operating Instruction
22
Connect the included 2-wire.black cable with the fan-board (Picture 6) an take it upside tothe internal fan. Then place the cable beside the internal fan and fix it with the two cable-connectors which are shown in Picture 7.Next put the cable through the hole at the front of the Technovar and pull it below thecontrol card at the bottom (Picture 8).On the frontside of the control-card is an connector for plug in the control cable what you seein Picture 9.
Mounting the fan on the Technovar
Place the Technovar at the AC-fan that you can see the LCD-Display at the front and thepieces for the wallmounted component are on the side (Picture 11).Then put the fan-cable through the hole and fix it with the included cable gland from picture12. Look that the cable goes between the heat sink and isn´t fixed from it (Picture 12).
Connect the fan-cable at the connection clamps U2, V2, W2 on the fan board and screw theGND-cable with the GND screw (Picture 10).Next take the four long screws M6x25mm and the lock washers (see picture 1/A and B) and fixthe Technovar on the AC-fan with the nuts you can see in picture 2/E.At least put the wall mounted component (Picture 13) behind the Technovar and fix this 2components with the four short screws M6x12mm and the lock washers (see Picture 1/C andD) what you see in picture 14.
!! PLEASE NOTE: The fan is only running with the TECHNOVAR (Run Signal).Connect the fan cable so that the fan can blow from the carrier-sheed through the heat sink.
Dimension drawing
Operating Instruction
23
6.1.3 Mounting the thermistorVariant A:
Variant B:
1. Open the cover of the conduit box and remove also the terminal block inside.2. Fix the thermistor (Variant A or B)3. Electrical connection of the motor cables see chapter 6.2.4. Electrical connection to the Technovar see chapter 6.2
motor
thermistor
terminal block
rubber gasket
cover of theconduit box
Thermistor
Operating Instruction
24
6.2 Electric installation and wiring
6.2.1 Means of protection
Ask your power supply company which means of protection are required.
Applicable: AC and DC current-operated circuit breaker (FI), TN systems, protectivecircuits.
When using a FI protection switch, make sure that it also releases in the event ofa DC fault, use for each Technovar a separate FI-switch!
6.2.2 Wiring the Technovar to the motor
Remove the 3 screws holding the top cover of the Technovar. Lift off the top carefully, takeoff the connection cable to the display carefully remove the ground screw and left aside.On the next page you can see:
(1) control card with all terminals for the control signals and the RS485 interface(2) main card with all power components and terminals for power supply and motor
connections
Operating Instruction
25
6.3 Main Voltage Terminals
supply cableThe main power cable is connected to the terminals labeled L1, N for the 1x230 VAC, singlephase unit or L1, L2, L3 for the 3x400VAC, three phase unit.
Power supply1x230 VAC Motor connection
Control terminals
RS485 interface
Power supply3x400 VAC
Motor connection
RS485 interface
Control terminals
HV2.1 / HV2.2 HV 3.2 – 3.11
RS485 interface
Motor connection
Controlterminals
Power supply3x400 VAC
HV 3.15/ 3.18/ 3.22
Operating Instruction
26
6.4 Control Terminals
All externally used cables have to be shielded. Do not connect the ground of the electroniccomponents to other potentials (all electronic ground and GND of the RS 485-interface areconnected together internally).
For external off/on switches, contacts suitable for switching <10 VDC are necessary.
If unshielded control cables are used, signal interference may occur and interfere withthe function of the inverter.
Terminal: X1/ 1 GND2 Actual value input 4...20mA, 50 Ohm load resistance3 Power supply for external control 15VDC, max. 100mA4 GND5 External on/off (release) Ri=10kOhm, 5 Volt DC
(gold plated contact necessary!)6 GND7 Low water; Ri=10kOhm, 5 Volt DC
(e.g. incoming pressure switch or water level switch)8 Thermo switch or PTC (in motor terminal box) Ri=10k, 5 VDC9 Thermo switch or PTC10 GND11 Analog output 0...10 V, max. 2mA12 Current signal input 4...20mA13 Voltage signal input 0....10V or 2......10V14 Digital input
Terminal: X2/ 1 Fault signal relay NC max. 250VAC 1A free of inductivity(for dry 2 Fault signal relay CC max. 250VAC 1A free of inductivityContacts) 3 Fault signal relay NO max. 250VAC 1A free of inductivity
4 Pump operationsignal relay
NC max. 250VAC 1A free of inductivity
5 Pump operationsignal relay
CC max. 250VAC 1A free of inductivity
6 Pump operationsignal relay
NO max. 250VAC 1A free of inductivity
!! Fault relay (X2/2 - X2/3) is closed, when there is no error!!
Terminal: X5-6/ 1 RS 485 SIO - LOW2 RS 485 SIO + HIGH3 RS 485 GND4 RS 485 + 5 VDC max. 20mA out
For supply of external interfaceconverter
Operating Instruction
27
6.4.1 Control terminals
When connecting the variable speed pumps (max. 4 pumps) via the interface RS 485, theterminals X5/1/2/3 or X6/1/2/3 of each Technovar are to be connected together by means of ashielded cable and programmed accordingly (� Programming Sequential Operations).
Operating Instruction
28
6.4.2 Dip-Switch on the controller board
SW4: DIP-Switch to select the switching frequency
!!Attention!!Before switching, disconnect the power supply, otherwise theTechnovar could be destroyed.
SW4 Switching frequency1 2
OFF OFF 8kHz (standard)ON OFF 5kHzOFF ON 4kHzON ON 2.5kHz
6.4.3 Main parts from the control card
RS-4
85 t
erm
inal
s
Control terminalblocks
24V output(max. 800mA)
for external fan
40 pin connection(to power board) Dip-switch
Main supply3x400 V
Motor connection
Pin connection(to Display)
Operating Instruction
29
HV 3.15/ 3.18/ 3.22
6.5 Front plateHV3.15/ 3.18/ 3.22
LCDPush buttons RS-485
terminals
40 pin connection(to power board)
24V output(max. 1A) forexternal fan
Dip-switch
Con
trol
ter
min
al b
lock
s
Operating Instruction
30
HV 2.1-3.11
7 Language Selection
The information on the display can be called up in German, English, Italian, French, Spanish,Portuguese or Dutch.To select the desired language proceed as follows:Briefly press + simultaneously (in 1st display); � the actual language will now appearin the second line and the desired language can be selected with the button or . Afterthe language has been selected, press button briefly and the first menu window of themain window will appear again. If only the language is changed it is not necessary to SAVE.
ON
OFF
Select
Power Run Fault
Operating Instruction
31
8 Typical applications
8.1 ControlBy means of the built-in Technovar controller acc. to constant pressure by pressuretransmitter and/or acc. to constant flow by flow-meter or orifice plate with differentialpressure transmitter and differential pressure transmitter or - if required - acc. to externalmanual control by reference 4 - 20 mA DC (only for special applications).
8.2 The Main Menu SettingThere are ten display screens in the main menu which will allow you set the required systempressure, save it, and turn the system on. Several of these display screens were already usedduring the test run. After power has been turned on, the “Power on” light should illuminateand the display should show “No Autostart – disable inverter”.
Instructions:
Check the green POWER light NO Autostartdisable inverter
Press the button to advance the display to INVERTER STOPON -> START
Press to advance the display to REQUIRED VALUEX.XX psi
REQUIRED VALUESet the desired set pressure with either or . If several pumps are connected via the RS-485 interface, one pump must be ready for operation when the set pressure is changed,otherwise the set value will not be accepted by the follow-up pumps. Afterwards the newrequired pressure has to be saved in all pumps.
Press to confirm and the display changes to AUTO – STARTOFF
AUTO – STARTSelect (ON) with the button or (OFF) with . Auto-start ON starts the pump automaticallyagain after an interruption of the power supply (power failure).At the Auto-start setting OFF, the pump must be restarted manually by pressing the buttons
(OFF) and then (ON) after power failure.
Press and the display changes to: ERROR 1...................
Last error
Note: All errors are only readable
Press the button to change toError before last error:
ERROR 2...................
Operating Instruction
32
Press the button to change toerror before error 2:
ERROR 3...................
Press the button to change toerror before error 3:
ERROR 4...................
Press the button to change toerror before error 4:
ERROR 5...................
Press the to advance the display to: TOTAL RUN TIME0000:00
Press the button and the display will change to SAVE ??? +
Simultaneously press buttons and until...SAVE ???SAVED
appears and the display jumps back to Window 1“INVERTER STOP” after few seconds.
Warning: After each change of a setting, this has to be saved (newvalues are stored in an EEPROM).Otherwise the changes will be lost in case of a power supplyfailure!
Operating Instruction
33
ITT
IND
UST
RIES
x.xx
psi
Requ
ired
Valu
e 1
126
,9 p
siA
uto
- S
tart
ON
Erro
r 1
Erro
r 2
Erro
r 3
Erro
r 4
Erro
r 5
Tota
l Run
Tim
e00
00 :
00Sa
ve ?
?+
��
Pass
wor
d00
00JO
G -
Mod
e0
.0 H
z 3
19,5
psi
Win
dow
5 %
Ram
p H
yste
resi
s80
%Ra
mp
14.
0 Se
cRa
mp
24.
0 Se
cRa
mp
370
Sec
Ram
p 4
70 S
ecM
ax. F
req
uenc
y60
.0 H
zM
in. F
requ
ency
0.0
Hz
Con
fig. F
min
F ->
0St
op -
Del
ay F
min
0 Se
kBo
ost
5.0
%Se
nsor
Adj
ust
?ou
t of
ran
geSe
nso
r -
Curv
eLi
near
Sens
or R
ange
20 m
A =
362
,6 p
siM
ode
Cont
rolle
rRe
gula
tion
Mod
eN
orm
alSt
art
Valu
ed
isab
led
Con
fig. R
eq. V
al. 2
OFF
Rela
y C
onfig
.Ru
n M
otor
SUBM
ENU
Off
set
Off
set
- In
put
OFF
Leve
l 10.
0 %
Leve
l 20.
0 %
Inte
nsity
1+
0.0
%
Inte
nsity
2+
0.0
%
SUBM
ENU
Seq
. Con
trol
Act
u. V
alu
e In
c.5
psi
Act
u. V
alue
Dec
.2,
1psi
Enab
le S
eq. C
TL.
58.
0 H
z
Swit
ch In
terv
al1
2 ho
urs
Sour
ce R
eq. V
alu
eO
FF
SUBM
ENU
Syn
ch. C
ontr
olSy
nchr
on. L
imit
0.0
Hz
Sync
hron
- W
indo
w2.
0 H
zPu
mp
- Se
que
nce
Adr
1
f
ault
Busa
rbit
- D
iag.
0
SUBM
ENU
RS4
85 -
Inte
rfac
e
Pum
p - A
ddre
ssO
FF
AD
C Re
fere
nce
Loca
l
Lift
- A
mou
nt0.
0 %
Ana
log
- O
utA
ctua
l Val
ueD
imen
sion
Uni
tps
iTe
st R
un
afte
r 10
0 h.
SUBM
ENU
Test
Run
Test
Run
man
.�
�+
Test
- F
req
uenc
y3
0.0
Hz
Boos
t Te
st -
Run
10.0
%
SUBM
ENU
Erro
rs
Conv
eyo
r -
Lim
itdi
sab
led
Del
ay T
ime
2 Se
c
Erro
r -
Rese
tdi
sab
led
Cle
ar E
rror
s00
00
Ope
rati
ng H
ours
0000
h.
Dis
p. -
Con
tras
t50
%Se
t Pa
ssw
ord
0066
Hea
ting
ON
Def
ault
Eu
rope
+�
�
Def
ault
USA
+�
�
SUBM
ENU
Def
ault
Valu
esSa
ve ?
?+
��
Lock
Fun
ctio
nO
FF
Star
t
Freq
u. -
Lift
ing
37.0
Hz
Operating Instruction
34
8.3 Single Pump – Pump Protection
The Technovar has the ability to protect the pump by shutting off in low/no suction or run outconditions.
Note: Low/no suction protection depends on the installation of a suction linepressure switch, or float switch for a tank. This switch is connected tothe Technovar. The cut out setting for a suction pressure switch shouldbe greater than the minimum incoming pressure, required by the pump.
Note: Run out protection is available for one pump systems and multiple pumpsystems with a common suction pipe. (described at chapter ”ConveyorLimit” 11.30.1 In multiple pump systems with separate suction pipes,you can not avoid dry running by measuring the system pressure,because the pressure is produced from another pump in the system.
8.3.1 To set run out protection
Hold the button for 3 seconds and the display changes to PASSWORD0000
Password:The password protection prevents untrained personal from accidentally changing of the basesettings:
Set ‘Password 0066’ by pressing or PASSWORD0066
You will now be able to access all of the alternate menus for all Technovar optional controls.
After entering the password you have to confirm by pressingthe button to advance the display to the next window
JOG – MODE0.0 Hz X.XX psi
JOG-MODEActual outgoing frequency and actual analog input are shown. By pressing or in thismenu, the internal controller of the Technovar will be shut off and the inverter changes tomanual mode. With the buttons and you can set any constant speed. Setting of 0,0 Hzstops the inverter. If the JOG-MODE is left at a frequency higher than 0,0 Hz the inverter willcontinue its normal automatic operation.
Press the button repeatedly until you reach SUBMENUERRORS
Hold the button down for 3 seconds to enter thesubmenu, until the display changes to
CONVEYOR-LIMITdisabled
Operating Instruction
35
CONVEYOR-LIMITDisabled or adjustable between disabled...NORMALIZE. To disable the conveyor limit, press
till “disabled” is shown on the display. An adjusted value >0 has to be reached till theprogrammed. “DELAY TIME”.
If this value is not reached, the failure “CONVEYOR CONTROL ERROR” will be indicated andthe pump will stop.
Press once the button and change to DELAY TIME2 Sec.
DELAY TIMEThe delay time is adjustable between 0 and 100 Sec. for switch-off of the Technovar in case of lowwater, (Terminal X1/6-X1/7) and conveyor limit.
Press to advance the display to ERROR-RESETdisabled
ERROR-RESETif you want to have an automatic error reset for 5 times (not for errors in the control-port),you have to set a delay time for the automatic reset (range: 0-250 sec.).That means after a non fatal error, the Technovar will be restarted after the set delay time.After five consecutive errors the converter switches off.To disable this function press until “disabled” appears. (The internal counter of the automatic resets will be reduced by one each operating hour).
Note: “Fatal” errors will always shut down the system at the first time.
Hold down the key for 3 sec. to leave the submenu andthe display changes to
SUBMENUERRORS
Press the button repeatedly until you reach SAVE ??? +
Press both buttons until the display changes to SAVE ???SAVED
After a moment, the screen will automatically return to the 1st window.
ITT INDUSTRIESX.XX psi
Operating Instruction
36
8.4 Single Pump – System Curve Compensation
The Technovar can automatically compensate for system friction losses due to increased flow.Tables are available in most pump catalogs, indicating the amount of friction losses that canbe expected in various sizes of pipes at different flow rates. Use these tables to determine thefriction losses for the pipe size you are using at maximum flow rate.This Diagram shows a typical system curve. The system pressure set point is shown at shutoffand pressure increase is shown for increasing flow.Calculate the pressure required to overcome friction losses at maximum flow.
Operating Instruction
37
8.4.1 Entering the compensation values
Hold the button for 3 seconds and the display changes to PASSWORD0000
Password:The password protection prevents untrained personal from accidentally changing of the basesettings:
Set ‘Password 0066’ by pressing or . PASSWORD0066
You will now be able to access all of the alternate menus for all Technovar optional controls.
Press the button repeatedly until you reach FREQU.-LIFTING37.0 Hz
FREQUENCY-LIFTINGAdjustable between 6 Hz and the set MAXIMUM FREQUENCY, this setting states at whichoutput frequency the set pressure should be increased. That is the speed at which the pumpworks at the set pressure and at delivery rate 0(can be read in the JOG MODE).
Press the button to change to LIFT-INTENS.0.0 %
LIFT-ITENS.Increasing value, when the reaches its maximum speed (maximum volume).
Enter settings as follows:1. Setting the set pressure (see: Inverter main menu).
2. Enter frequency at zero demand and actual pressure = set pressure � FREQU. LIFTING
3. Set desired lifting at maximum speed (in %) of set pressure.
Increasing values up to 200% are allowed. If your friction losses are above 200% of your setpressure, bigger pipes should be used.
Press the button repeatedly until you reach SAVE ??? +
Press both buttons until the display changes to SAVE ???SAVED
All new settings are stored.After a moment, the screen will automatically return to the 1st display.
ITT INDUSTRIESX.XX psi
Operating Instruction
38
8.5 Multiple Pump - Constant Pressure and System Curve Compensation
When two, three or four Technovar controlled pumps are connected in a system, they can beprogrammed to work together to maintain system pressure up to the maximum flow rate ofall pumps combined. As the first pump reaches its maximum speed and flow, the second willautomatically turn on (and so on). In addition, the sequence of the pump that will run first(lead pump) can be automatically varied to reduce premature wear of any pump in thesystem.
Hold the button for 3 seconds and the display changes to PASSWORD0000
Password:The password protection prevents untrained personal from accidentally changing of the basesettings:
Set ‘Password 0066’ by pressing or . PASSWORD0066
You will now be able to access all of the alternate menus for all Technovar optional controls.
Press the button repeatedly until you reach MODE:Controller
Use and to change the setting to: MODE:Multicontroller
MODE:Controller:If only one TECHNOVAR pump is in operation set the Controller for a stand alone controllerfunction. If more than one pump are working together, connected via the RS485 interface(follow-up pump control), the Multicontroller must be set with the buttons or .Synch. Controller:The Synchronous Controller mode is working in the same way like the Multicontroller. Theonly difference is, that all pumps in the multi pump system are running at the samefrequency.Actuator:The Actuator application is only used if you have an external controller and the Technovar isused as a standard frequency converter. In the Actuator-Mode, the internal controller is shutoff, and the output frequency is proportional to the input signal (X1/2) � 4-20 mA = 0 -fmax. The frequency changes with the programmed ramps 1 and 2. The functions of lowwater, thermal protection and external ON/OFF are still working.
Operating Instruction
39
...... = fmax
If Manual control is selected, the parameter REQUIRED VALUE will change to Manualcontrol LOCAL, where the actual frequency and the actual value is displayed (according tothe JOG-MODE in the submenu).Now the frequency can be changed with the and buttons, and the speed of the pumpwill change with the fasten ramps1 and 2. After selecting the right frequency, it can besaved with the standard SAVE-parameter.After a supply failure, the pump will then run with this selected frequency (depending onthe parameter AUTO-START).
In the first window, the actual frequency is displayed. The frequency can be changedbetween the set minimum and maximum frequency. (CONFIG. FMIN is not active in thismode!).
Attention Driving the pump in a not allowed speed range can damage the motor or theTechnovar-head!
Press the button five times and you reach SUBMENUSeq. Control
Hold down the button for 3 seconds until the displaychanges to
ACTU. VALUE INC.5 psi
ACTUAL PRESSURE INCREASE (=LIFT VALUE):This value, together with the fall value (ACTUAL VALUE DECREASE) determines theincrease of the required value after starting of the following pumps (see example)
Operating Instruction
40
Generally a slight pressure drop is allowed on the first pump before the next is started.This allows for brief systems fluctuations without pump cycling. Once the next pumpstarts, however, you will want the system to resume its normal set pressure.
To do this, enter the amount of pressure drop you willallow before the next pump starts (= value ofparameter ACTUAL VALUE DECREASE). The diagramshows the pressure drop and increase.
To increase the pressure even more to compensate forsystem loss at higher flows, enter the total of thesystem drop allowed before next pump starts and theincreased pressure (ACTUAL VALUE INCREASE) desired.
Application example:1) Pump 1 reaches the speed of ENABLE SEQ: CONTROL or more2) Pressure falls and reaches the start-value of the 2nd pump
(= REQUIRED VALUE – ACTUAL VALUE DECREASE)3) Pump 2 is switched on automatically4) The required value is calculated new, after the start of the 2nd pump in the following
way!
New required value = REQUIRED VALUE – ACTUAL VALUE DECREASE + ACTUAL VALUE INCREASE
Generally:k ... Number of active pumpsP = Pset + (k-1)*[lift value – fall value]
� Lift value = Fall value � Pressure constant when pumps switch on� Lift value > Fall value � Pressure rises when lag-pump switches on� Lift value < Fall value � Pressure falls when lag-pump switches on
Enter the required value by pressing the and button ACTU. VALUE INC.7,1 psi
Press the button to confirm and change to ACTU. VALUE DEC.2,1 psi
ACTUAL PRESSURE DECREASE (= Fall value):This value determines amount of pressure drop you willallow before the next pump starts.
Operating Instruction
41
Enter the required value by pressing the and button ACTU. VALUE DEC.5 psi
Press the button to change to ENABLE SEQ. CTL58.0 Hz
ENABLE SEQUENCE CONTROL: (Release frequenz)The follow-up pump only starts, when the start-value (SET VALUE – ACTUAL VALUEDECREASE) is reached and the lead pump has reached the programmed release-frequency.(Adjustable from 0.0 Hz to 70 Hz).Normally this start frequency is set 1 to 2 Hz lower than the MAX. FREQUENCY If you don’twant to start a following pump this value has to be set higher than the MAX. FREQUENCY.
Enter the required value by pressing the and button ENABLE SEQ. CONTROL59.0 Hz
Note: In the standard multicontroller mode, the next pump will not start until both thesystem pressure drop and release frequency first pump speed have been reached.In the synchronous control mode, the first pump only has to reach the releasefrequency, then the next pump will start.
Press button briefly to advance to SWITCH INTERVAL12 hours
SWITCH INTERVAL:For changeover of the master pump and follow-up pumps, in order to achieve evenoperating hours. Adjustable between 1 hour and 100 operating hours of the Technovar. Ifan interval of more than 100 is selected, the automatic changeover is deactivated.Manual changeover of the master pump in the 1st display by pressing the -button.
Enter the required value by pressing or button SWITCH INTERVAL24 hours
After pressing the button for 3 seconds, you leave the submenu and the display changes to
SUBMENUSeq. Control
Operating Instruction
42
Press the button again briefly to advance to SUBMENURS485-Interface
Hold the again for 3 seconds to enter the submenu andthe display changes to
PUMP-ADDRESSOFF
PUMP-ADDRESS:If only one pump is used, the setting remains OFF. If several pumps are connected via the RS-485 interface (max. 4) each pump must be allocated its own address number (1-4)(each number may only be allocated once!).
Use the and button to select a “PUMP-ADDRESS” PUMP-ADDRESS1
Hold the button for 3 seconds to return to SUBMENURS485-Interface
Press the button repeatedly until you reach SAVE ??? +
Press both buttons until the display changes to SAVE ???SAVED
All settings are stored.
After a moment, the screen will automatically return to the 1st display.
ADR X (X) P XX.XX psi
Note: Repeat this steps for each pump in the system. Use a differentaddress number for each pump!
Operating Instruction
43
9 Parameters of the main menu
After connection of the Technovar unit to the power supply the following possibledisplays become visible.
SW-Ver: VOG 120Date: xxxx
The current software version with the date ofprogramming is displayed for about three seconds.
The following two displays are depending on the selected mode:
a) Active MODE = Controller:
1. ITT INDUSTRIESXX.X psi
This window is mentioned several times in theOperating Instructions as 1st display at Mode Controller
Continue by pressing the -button
2. REQUIRED VALUE 1X.XX psi
Set the desired set pressure with either or and then briefly press the -button.
If several pumps are connected via the RS-485 interface, one pump must be ready foroperation when the set pressure is changed, otherwise the set value will not be accepted bythe follow-up pumps. Afterwards the new required pressure has to be saved in all pumps.
If you want to change to Required Value 2 you have to close the external contact,connected to X1/10-X1/14.
After closing this contact, the display changes from Required value 1 to
2.1 REQUIRED VALUE 2ADC-X XX.X psi
In this window, there is shown the condition ofthe second Required value.
ADC-X: This parameter shows you the source of the external or internal valueXX.X Bar: shows the actual value of the Required Value 2.
Continue by pressing the -button
b) Active MODE = Actuator:
1. ITT INDUSTRIESFrequency XX.X Hz
This window is mentioned several times in theOperating Instructions as 1st display at the Mode
Actuator.Continue by pressing the -button
2. REQUIRED VALUE 1X.XX psi
Set the desired set pressure with either or and then briefly press the -button.
If several pumps are connected via the RS-485 interface, you have to set this parameter oneach pump!
Operating Instruction
44
c) Active MODE = Synch. Controller or Multicontroller:
1. ADR (X) P XXX.X psi
This window is mentioned several times in theOperating Instructions
as 1st display at the Synch. Controller or Multicontroller mode.
Continue by pressing the -button
2. REQUIRED VALUE 1X.XX psi
Set the desired set pressure with either or andthen briefly press the -button.
If several pumps are connected via the RS-485 interface, one pump must be ready foroperation when the set pressure is changed, otherwise the set value will not be accepted bythe follow-up pumps. Afterwards the new required pressure has to be saved in all pumps.
If you want to change to Required Value 2 you have to close theexternal contact, connected to X1/10-X1/14.
After closing this contact, the display changes from Required value 1 to
2.1 REQUIRED VALUE 2ADC-X XX.X psi
In this window, there is shown the condition ofthe second Required value.
ADC-X: This parameter shows you the source of the external or internal valueXX.X Bar: shows the actual value of the Required Value 2.
Continue by pressing the -button
d) Active MODE = Actuator local:
1. ITT INDUSTRIESFrequency XX.X Hz
This window is mentioned several times in theOperating Instructions as 1st display at the Mode
Actuator local.Continue by pressing the -button
2. ACTUATOR LOCAL X.X Hz X.XX psi
Set the desired set pressure with either or andthen briefly press the -button. If several pumps are
connected via the RS-485 interface, you have to set this parameter on each pump!
Press the button on the Technovar to change to
!! The following displays of the main menu are valid for all selected Modes !!
3. AUTO - STARTON
Select (ON) with the button or (OFF) with .
AUTO-START ON starts the pump automatically again after a failure of the power supply.If AUTO-START is OFF, the Technovar has to be restarted by pressing the buttons (OFF)and then (ON) after a power supply failure.
Operating Instruction
45
If the AUTO-START is OFF, the unit will not start again in cases of a failure or disconnection.After restarting is following message is shown:
3.1 NO AUTOSTARTdisable inverter
To restart the unit, press at first the and than to start the button.
Press and the display changes to
Note: All errors are only readable
4. E R R O R 1.........................
Here, the last error is shown
Press the button to change to
5. E R R O R 2.........................
Shows the error before the last error
Press the button to change to
6. E R R O R 3.........................
Shows the error before error 2
Press the button to change to
7. E R R O R 4.........................
Shows the error before error 3
Press the button to change to
8. E R R O R 5.........................
Shows the error before error 4
Press the button to change to
9. TOTAL RUN TIME0000:00
Runtime of the motor.This time is reset together with the
operating hours.
Press the button to change to
Please Note : All changes have to be saved, that they will not be lost in case of shut off of the power supply !!
10. SAVE ??? +
Simultaneously press buttons and until...:
Operating Instruction
46
11. SAVE ???SAVED
appears on the display. After fiveseconds the display jumps back to the1st display.
These parameters can also be set during operation; To do so, briefly press thebutton and repeat steps 1 – 10.
Please Note: often shown display
12. INVERTER LOCKEDenable inverter
This message appears when the connection ofterminal X1/4-X1/5 is open (external release contact).
10 Settings at Secondary Menu
Important: Before entering the secondary menu these instructions mustbe read carefully to prevent incorrect settings which will causemalfunction.
Secondary Menu:
Stop motor by pressing OFFINVERTER STOP
ON -> START
Press for 3 seconds to change toPASSWORD
0000
Set ‘Password 0066’ by pressing PASSWORD
0066
Confirm by pressing and the firstwindow of the sub menu is shown
J O G – MODE0.0Hz X.XX psi
In the following paragraphs all possible settings are listed (in the display, there isshown the European default setting).
10.1 JOG-MODEDisplay and Manual Operation Mode
J O G – MODE0.0Hz X.XX psi
Actual outgoing frequency and actual analog input areshown. By pressing or in this menu, the
Note: The password must be entered at each entry
Operating Instruction
47
internal controller of the Technovar will be shut off and the inverter changes to manualmode. With the buttons and you can set any constant speed.Setting of 0,0 Hz stops the inverter. If the JOG-MODE is left at a frequency higher than 0,0Hz the inverter will continue its normal automatic operation.
Press on the Technovar to change to
10.2 Window - %
WINDOW5%
This value indicates the max. variation of the outgoingpressure (see diagram “Ramp window”).
Possible setting: between 0% - 100% of required pressure.
Press on the Technovar to change to
10.3 Ramp Hysteresis
RAMP HYSTERESIS80%
Level, where the fast ramp changes to the slowramp (see diagram “Ramp window” )Possible setting: between 0%..100% of the window
Press on the Technovar to change to
10.4 Ramp 1: Fast running up time:Time setting at Ramp 1, 2, 3, or 4 will influence the control of the pump andMUST NOT BE CHANGED at normal operation. Possible setting of each ramp 0,05 - 1000sec.
RAMP 14.0 Sec
Excessively fast running up time may overload theinverter in the starting moment.
Excessively slow running up time may cause a break down of the outgoing pressure duringoperation.
Press on the Technovar to change to
10.5 Ramp 2: Fast running down time:
RAMP 24.0 Sec
Excessively fast running down time tends to causeoscillation or hunting or can cause an error
(OVERVOLTAGE) during ramp down of the pump.Excessively slow running down time tends to generate over pressure.
Press on the Technovar to change to
Operating Instruction
48
10.6 Ramp 3: Slow running up time:The following ramps 3 and 4 determine the speed of the internal Technovar controllerand depend on the system, which should be controlled.
RAMP 370 Sec
A too slow running up time can cause a break of theoutgoing pressure during variation of the demand.
A too fast running up time may lead to oscillation and/or overload of the inverter.
Press on the Technovar to change to
10.7 Ramp 4: Slow running down time:
RAMP 470 Sec
A too fastA too slow
setting leads to oscillationsetting delays the switching off too much
Ramp – Window
Press on the Technovar to change to
10.8 Maximum Frequency
MAX. FREQUENCY60.0 Hz
Possible setting between 40 and 70 Hz.Attention: Settings higher than 60 Hz may overload themotor!
Settings of 10% above nominal frequency cause 33% more power consumption!
Press on the Technovar to change to
Operating Instruction
49
10.9 Minimum Frequency
MIN. FREQUENCY0.0 Hz
Here you can set the minimum frequency between 0,0and Max.frequency.
Attention!: If there is set f>fmin in the parameter CONFIG. FMIN the pump will not stop inthe normal mode. It will keep running with the set minimum frequency.!! Possibility of overheating of the pump !!
Press on the Technovar to change to
10.10 Operation at the minimum frequency
CONFIG FMINf => fmin
If you have selected „f->0“ the frequency will godown to the selected minimum frequency.
Then the inverter will keep running for the selected time and after this time the Technovarwill stop automatically.
If the selection is „f->fmin“ you can not run the pump below the set minimum frequency. Inthe controller, actuator and multi controller mode the pump will never run below the setminimum frequency (the pump will only stop with an external on/off-(terminals X1/4 andX1/5) or in case of a failure.
Press on the Technovar to change to
10.11 Delay time for shut off at minimum frequency
STOP-DELAY FMIN5 s
After running the pump for this selected time atminimum frequency, the pump will stop, if parameter
CONFIG. FMIN it set to f � 0 Adjustable between 0 and 100s.
Press on the Technovar to change to
10.12 Boost
BOOST5.0 %
The stated value determines the course of theU/f-curve.
Setting of the motor starting voltage in % of rated voltage.Settings of 0...25% of maximum output voltage are possible. However, care should be takenthat settings are kept as low as possible so that the motor does not become thermallyoverloaded at lower frequencies.
Press on the Technovar to change to
Operating Instruction
50
10.13 Sensor – Adjust
SENSOR_ADJUST?Out of range
Zero point adjustment of the transmitterDepressurise the system and press buttons +
simultaneously. After adjustment "adjusted" appears on the display. If “out of range” is shownon the display, no adjustment is possible
Press on the Technovar to change to
10.14 Sensor - Curve
SENSOR-CURVELinear
Function of the input signal (4...20mA) of theTechnovar to the actual measured value.
Application:linear:Pressure control, differential pressure control, level, temperature and flow control(inductive or mechanical).quadratic: Flow control with an orifice plate together with a differential pressure transmitter.
Press on the Technovar to change to
10.15 Setting of the measuring range
SENSOR RANGE20mA = 362,6 psi
Setting the end value of the measuring transmitter,e.g. 362 psi = 20mA of the pressure transmitter
Adjustable range: 20 mA = 100%; corresponds to the possible adjustable ranges:PSI: 2.9 to 1450; GAL/MIN: 9 to 10560FT: max 3345 ft. 0 to100 %; without unit: max 1000;
Press on the Technovar to change to
10.16 Operation Mode
MODE:Controller
Select with the and buttons
If only one TECHNOVAR pump is in operation set the Controller. If more than one pump worktogether via the RS485 interface (follow-up pump control), the Multicontroller must be setwith the buttons or .
Synch. Controller:The Synchronous Controller mode is working in the same way like the Multicontroller. Theonly difference is, that all pumps in the multipump system are running at the same frequency.Actuator:
Operating Instruction
51
The Actuator application is only used if you have an external controller and the Technovar isused as a standard frequency converter. In the Actuator-Mode, the internal controller is shutoff, and the output frequency is proportional to the input signal (X1/2) � 4-20 mA = 0 - fmax.The frequency changes with the programmed ramps 1 and 2. The functions of low water,thermal protection and external ON/OFF are still working.
If MANUAL CONTROL is selected, the parameter REQUIRED VALUE will change to MANUALCONTROL in the main menu, where the actual frequency and the actual value is displayed(according to the JOG-MODE in the submenu).Now the frequency can be changed with the and . buttons, and the speed of the pumpwill change with the fasten ramps. After selecting the right frequency, it can be saved withthe standard SAVE.After a supply failure, the pump will then run with this selected frequency (depending on theparameter AUTO-START).The frequency can be changed between the set minimum and maximum frequency.
In the 1st display, there is shown the actual frequency.
NOTE: CONFIG. FMIN will not work in this mode.
Attention Driving the pump in a not allowed speed range can damage the motor or theTechnovar-head!
Press on the Technovar to change to
10.17 Control Response
REGULATION MODENormal
Normal: Speed is increased with falling actual valuesignals. (e.g.: Control at constant output pressure).
Inverse: Speed is reduced with falling actual value signal, (e.g.: Control at constantsuction pressure or at constant level).
Press on the Technovar to change to
Operating Instruction
52
10.18 Start Value
START VALUEdisabled
This parameter gives you the start value after pumpstop in percentage of the required value (adjustable
between disabled and sensor range).e.g.required value: 72 PSIstart value: 36 PSIIf the pump system reaches the required pressure of 72 PSI and there is nomore consumption, the Technovar shuts off the pump. When the consumption increasesand the pressure goes down to or below the start value, 36 PSI, the pump will start.
Press on the Technovar to change to
10.19 2nd Required Value
CONFIG. REQ. VAL.2OFF
With this parameter CONFIG. REQ. VAL.2 you canselect an independent 2nd required value. The change
Between 1st and the 2nd required value can be done over the digital input, terminal X1/14on the control card. If this input is connected to Ground, 2nd required value active.
Possible selections:
OFF : actual value 2 is not active (no change after closing the input X1/14)INT : internal required value 2, function and setting according to
existing required value.EXT ADC-I : the required value 2 is made from the value of the current signal
(4-20mA) at the terminals X1/12, X1/10. 20mA is equal to the programmed SENSOR RANGE. If the incoming current signal is below 4mA, there will be shown an error message on the display, but no failure is indicated (failure relay is not closed). In this case the required value 2 will be 0.
EXT ADC-U 0-10V or the required value 2 is made from the value of the voltage signalEXT ADC-U 2-10V (0-10V or 2-10V) at the terminals X1/13, X1/10 (Ground).
10 V is equal to the programmed SENSOR RANGE.
Setting the required value2:The active required value is shown in the actual display of the parameter required value.Is the 2nd required value active (digital input, terminal X1/14, closed), in the first line, there isshown Required value 2. The second line will show the source of the 2nD value, which isselected in the parameter CONFIG. REQ VAL:2(INT or EXT-ADC-I or EXT-ADC-U) and also the actual value of this input.INT : you can select your value with the up- and down buttonsEXT: only display of the value of the 2nd analog input signal.In case of saving, every time both required values are saved.
Press on the Technovar to change to
Operating Instruction
53
10.20 Configuration of 1st relay
RELAY CONFIG.Run Motor
Possible selections with buttons and .Simple Multicontr. � allows to start / stop a
constant speed pump
Run Motor � motor run indication (over the relay)
If you have selected Simple Multicontr. two parameters get new functions. The start level of theslave pump you enter at the parameter Enable Seg. Ctl. and the stop value in the parameterSynchron. Limit.e.g. if the speed controlled pump reaches the start level, the relay will be switched on, and will beswitched off, when the output frequency falls below the stop level.Press on the Technovar to change to
10.21 Submenu Offset
S U B M E N UOffset
Press for about 3 seconds to enter thesubmenu and the display changes to
10.21.1 Source of the Offset input
OFFSET INPUTOff
The second additional input can be used as requiredvalue 2 and also for an Offset ofthe 1st required value.
There are three possibilities for the source of the OFFSET INPUT:
OFF : Offset deactivatedEXT ADC-I : Offset will be calculated according to the current input (4-20mA) at the
terminals X1/12 (X1/10=Ground).
Note: If the incoming current signal is below 4mA, there will be an error message onthe display, but no failure is shown (failure relay is not closed). In this case theOFFSET INPUT works like external signal=0.
EXT ADC-U 0-10V: Offset will be calculated according to the voltage input (0-10V or 2-EXT ADC-U 2-10V 10V) at terminals X1/13 (X1/10=Ground)
Press on the Technovar to change to
10.21.2 1st Offset level
Operating Instruction
54
LEVEL 1XX.X %
The level 1 is the start level of the 1st Offset.(adjustable between 0 and 100% of the additionalanalog input).
Press on the Technovar to change to
10.21.3 2nd Offset level
LEVEL 2XX.X %
The level 2 is the start level of the 2nd Offset.(adjustable between 0 and 100% of the additionalanalog input).
Press on the Technovar to change to
10.21.4 INTENSITY 1
INTENSITY 1+XX.X %
This is the intensity of the 1st Offset of the requiredvalue at the zero point of the second analog inputSetting range: -200% up to +200% of the sensor range.
Press on the Technovar to change to
10.21.5 INTENSITY 2
INTENSITY 2+XX.X %
This is the intensity of the 2nd Offset of the requiredvalue at the maximum point of the second analog
Input. Setting range: -200% up to +200% of the sensor range.
To leave the submenu press the longer than 3 sec. to change to
S U B M E N UOffset
Press on the Technovar to change to
10.22 Submenu Sequence control
S U B M E N USeq. Control
Programming Sequential Operations
Up to four pumps can be connected using the integrated RS-485 interface (Connection of theterminals /1, /2 and /3 of the terminal blocks X5 or X6 of each pump together). However, thefollowing additional programming must be carried out in the submenu:
Operating Instruction
55
Press for about 3 seconds to enter the submenu and the display changes to
10.22.1 Lift Value
ACTU. VALUE INC.5 psi
Adjustable between 0.0 to the pre-selectedSensor range
Application Example:1) Pump 1 reaches fmax (maximum speed)2) Pressure falls and reaches the start-value of the 2nd pump
(= REQUIRED VALUE – ACTU. VALUE DEC.)3) Pump 2 is switched on automatically4) The required value is calculated new, after the start of the 2nd pump in the following
way!
New required value = REQUIRED VALUE – ACTU. VALUE DEC. + ACU. VALUE INC.
Generally:k ... Number of active pumps (k >1)p = pset + (k-1)*[lift value – fall value]
� Lift value = Fall value � Pressure constant when pumps switch on� Lift value > Fall value � Pressure rises when lag-pump switches on� Lift value < Fall value � Pressure falls when lag-pump switches on
Press on the Technovar to change to
10.22.2 Fall Value
For calculation of the set pressure after start of pumps 2 to 4
ACTU. VALUE DEC.2.1 psi
Adjustable from 0,0 to pre-selected Sensor rangedetermines the start-value of the 2nd pump and the
Operating Instruction
56
other following pumps. (Start-Value = REQUIRED VALUE –ACT. VALUE DEC.)
Press on the Technovar to change to
10.22.3 Release frequency of the following controller
ENABLE SEQ. CTL.58.0 Hz
Release of the follow-up pump only when the start-value is reached and the lead pump
has reached the programmed frequency. (Adjustable from 0.0 Hz to 70 Hz).If you do not want to start a following pump this value has to be set higher than themaximum frequency.This parameter is also used to start a constant speed pump, when Simple Multicontr. isset). When this frequency level is reached, the potential free contact of the relay X2/5 –X2/6 will be closed.
Press on the Technovar to change to
10.22.4 Switch Interval
SWITCH INTERVAL12 hours
for changing the master pump and follow-up pump inorder to achieve even operating hours of the pumps
Adjustable between 1 hour and 100 hours. If it is set higher than 100 hours, the automaticchangeover is deactivated).Manual change of master pump in the 1st display with the -button.
Press on the Technovar to change to
Operating Instruction
57
10.22.5 Source of required value
SOURCE REQ. VALUEOFF
for selecting the address of the source of therequired value. Five adjustments are possible:
OFF, ADR1,ADR2, ADR3 and ADR4. If an additional (INT or EXT-ADC-I or EXT-ADC-U) inputis active, you must enter here the address where this input is connected.At active Multicontroller or Synch. Controller there is shown the active value in a bracket inthe middle of the display. If the sign “#” is shown in the second line of the display, the pumpwill work with a required value from a other pump in the multipump system. On the pump,which is the source of the required value, there is no “#” shown.
Press on the Technovar to change to
10.22.6 Synchronous Control
If the synchronous control is active the activated pumps try to regulate the set pressuretogether (all pumps run at the same frequency). The 2nd pump starts, when the 1st pumpreaches the release frequency (ENABLE SEQ: CONTR) The pumps will now attempt tomaintain pressure by running synchronously. The follow-up pump will than be stopped,when both pump together run below the set SYNCHRON. LIMIT. This creates the hysteresiseffect.
S U B M E N USynch. Control
Press for about 3 seconds to enter thesubmenu and the display changes to
10.22.6.1 Synchronous Limit
SYNCHRON. LIMIT0,0 Hz
Frequency threshold adjustable between 0,0 Hz andthe set maximum frequency.
Switch off threshold of the first follow-up pump. The switch off thresholds of the otherpumps are each higher by the SYNCHRON-WINDOW.This parameter is also used for the stop value for the external constant speed pump atactivated Simple Multicontroller in the parameter configuration relay.
Press on the Technovar to change to
10.22.6.2 Synchronous Window
SYNCHRON-WINDOW2.0 Hz
Frequency offsetAdjustable between 0...10 Hz
Threshold lift for switching off the next follow-up pump.
Setting the Synchronous Threshold:1. Set the desired set value and close the outgoing valves for no flow.2. Start the first pump in JOG Mode (1st Window in the submenu), increase the
frequency, till you reach the required value. Read the frequency ( = f0 )
Operating Instruction
58
3. Set the synchronous threshold (f0 + 2-3 Hz)4. Set the synchronous offset to 1-2 Hz
(depending on the pump curve and operating point).
To leave the submenu press the longer than 3 sec. to change to
S U B M E N USynch. Control
Press on the Technovar to change to
10.22.7 Pump status indication
PUMP – SEQUENCEAdr1 disabled
Shows the status of the individual drives- for follow-up pump switching- (adjustable from addresses 1 to 4, address 5 is
reserved for an external control device)- for master function / take over of master function if
there is any malfunction of the master drive.- Information concerning the actual sequential status
of each pump.
The following diagnosis parameters can be also be read in this display window:
hold Px Pump is stopped (control released)run Px Pump is running (control released)
stop Px Pump is stopped, because f< start frequency of the previouspump
Disabled Converter not ready to start (no release)Error Converter errorFault Polling failure (RS-485)
(interface connection wrong or not connected)Detected Polling successful (RS-485)
AdrX * “*” -> Address of the pump that is being read
Press on the Technovar to change to
10.22.8 Error Signals for Data Bus Interruptions
BUSARBIT-DIAG.0
Counts the number of synchronising attempts overthe RS-485 interface.
To leave the submenu press the longer than 3 sec. to change to
S U B M E N USeq. Control
Operating Instruction
59
Press on the Technovar to change to
10.23 Submenu - RS 485 Interface
S U B M E N URS 485-Interface
Press for about 3 seconds to enter thesubmenu and the display changes to
10.23.1 Pump Address
PUMP-ADDRESSOFF
If only one pump is used, the setting remains OFF. Ifseveral pumps are connected via the RS-485
interface (max. 4) each pump must be allocated its own address number.
Each address may only be used once!
Press on the Technovar to change to
10.23.2 ADC Reference
ADC REFERENCELocal
Reference for the local ADC (Analog/Digital-Converter)or SIO (RS485 interface).
LOCAL: Actual value from transmitter (Terminal X1/ 1-2)REMOTE: Actual value via RS-485 (Terminal X2/ 1-2-3)
To leave the submenu press the longer than 3 sec. to change to
S U B M E N URS 485-Interface
Press on the Technovar to change to
10.24 Compensation Frequency
Control according to a unit curve (increase of the set pressure, depending upon thedelivery rate or speed).
FREQU. – LIFTING37.0 Hz
Adjustable between 6 Hz and the set MAXIMUMFREQUENCY, this setting states at which frequency the
set pressure should be increased. That is the speed at which the pump works at the setpressure and at flow rate=0 (can be read in the JOG MODE).Press on the Technovar to change to
Operating Instruction
60
10.25 Lift-Intensity
LIFT – AMOUNT0.0 %
Adjustable from 0% to 99,9%; this value states howmuch the set value should be continually
increased, till the maximum speed (maximum volume) is reached.1. Setting the set pressure (see: Inverter main menu)2. Enter frequency for demand = 0 and set pressure = Actual Value
(see: Jog Mode ) � FREQU. LIFTING3. Set desired lift at maximum speed, in % of set pressure.
Figure: Lift-Intensity
Press on the Technovar to change to
10.26 Analog - Output
ANALOG - OUTActual value
Analog output 0 - 10V = 0 - 100% (max. 2 mA)Possible settings:� Actual value (signal at terminal X1/3)� Output frequency (0 - fmax)
Press on the Technovar to change to
Operating Instruction
61
10.27 Unit
DIMENSION UNITpsi
Adjustable units: psi, bar, m3/h, g/min, ft, mH2O,% or without unit can be changed with or .
Press on the Technovar to change to
10.28 Automatic test run
TEST RUNafter 100 h.
Adjustable between 10...100 operating hours. Thetest run starts the pump at the set time after the
last stop for 20 seconds to a speed of 30 Hz.Deactivating test run: Set 100 hours, keep button depressed, briefly press the button in addition, -> deactivated then appears in the display.Reactivate the test run: Select test run and set the desired hours using the button .
The test run is only active, when the pump is stopped!
Press on the Technovar to change to
10.29 Submenu for manual test run
S U B M E N UTEST RUN man.
Press for about 3 seconds to enter thesubmenu and the display changes to
10.29.1 Activate manual test run
TEST RUN man. +
By simultaneously pressing + a test run willbe released.
The Technovar speeds up to the test frequency with ramp1 and then decreases the speed tillstop with ramp2.Press on the Technovar to change to
10.29.2 Test Frequency
TEST-FREQUENCY30.0 Hz
Frequency for manual test run.Can be set from 6.0 Hz up to 70,0 Hz
Press on the Technovar to change to
10.29.3 Boost
BOOST TEST-RUN10.0 %.
Start voltage in % of rated voltage in order toensure that the motor starts safely.Adjustable between 0% and 25%
Operating Instruction
62
To leave the submenu press the longer than 3 sec. to change to
S U B M E N UTEST RUN man.
Press on the Technovar to change to
10.30 Submenu - Error
S U B ME N UERRORS
Press for about 3 seconds to enter thesubmenu and the display changes to
10.30.1 Conveyor Limit
CONVEYOR-LIMITdisabled
Disabled or adjustable between 0.00...SENSORRANGE. To disable the conveyor limit, press till
“disabled” or “0 bar” is shown on the display.An adjusted value >0 has to be reached till the programmed “DELAY TIME”.If this value is not reached; the failure “VAL. RANGE CONTR.” will be indicated and thepump will stop.
Press on the Technovar to change to
10.30.2 Delay Time
DELAY TIME2 Sec
Adjustable between 0...100 Sec.Delayed switch-off of the Technovar in case of low
water, (terminals X1/6-X1/7 opened) and also for the conveyor limit.
Press on the Technovar to change to
10.30.3 Automatic Error reset
ERROR – RESETOFF
The parameter can be set OFF (no automatic reset)or, if you want to have an automatic error reset for
5 times, a delay time of the automatic reset (0-250 sec.).e.g. ERROR-RESET = 5 secondsThe Inverter will reset the failure 5 times with a 5 second interval. After the 5th restart, the Technovar will shut down and an error message will appear on the screen.
The last five error signals are always stored in the memory Error 1 to 5 (main menu)
Press on the Technovar to change to
Operating Instruction
63
10.30.4 Erase Error memory
CLEAR ERRORS0000
The error memory can be deleted by entering apassword. If you want to know that, please contactyour distributor!
To leave the submenu press the longer than 3 sec. to change to
S U B ME N UERRORS
Press on the Technovar to change to
10.31 Operating Hours
OPPERATING HOURS0000 h.
operating time of the control unit (Technovar-supply O.K.) Reset by simultaneously pressing the
buttons + until TIMER – RESET appears.
Press on the Technovar to change to
10.32 Display - Contrast
DISP. CONTRAST50 %
Can be adjusted between 10...100%. For improvedclarity of the display, depending on the installationposition.
Press on the Technovar to change to
10.33 Set Password
SET PASSWORD0066
The pre-set password can be changed if necessary.
Press on the Technovar to change to
10.34 Operating Lock
LOCK FUNCTIONOFF
When activated [ON], it is not able to make anychanges in the main menu. Only ON/OFF (start and
stop) with buttons and are possible.In order to change the desired set value, the lock function must be switched off [OFF], thatthe set pressure can be changed in the main menu.
Press on the Technovar to change to
10.35 Internal Heater
HEATINGON
Standstill heating in TECHNOVAR head!In order to prevent condensation in the control unit
Operating Instruction
64
(depending on ambient conditions), a heating resistance (approx. 10 watt) is switched on,when the motor is at a standstill provided that HEATING ON was selected and the supply ofthe Technovar is O.K.
Press on the Technovar to change to
10.36 Setting Default Values
S U B M E N UDEFAULT VALUES
Press for about 3 seconds to enter thesubmenu and the display changes to
10.36.1 Default Values Europe
DEFAULT EUROPE +
Load the DEFAULT – PARAMETERS for Europe(e.g.: maximum frequency 50 Hz, display unit = bar)
Loading Parameter : Press buttons + for approx. 5 seconds.
Press on the Technovar to change to
10.36.2 Default Values USA
DEFAULT USA +
Load the DEFAULT – PARAMETER for the USA(e.g.: max. frequency 60 Hz, display unit = psi)
Loading Parameter : Press buttons + for approx. 5 seconds.
Attention After reloading the default settings the display is flashing, to deactivate theflashing press the until you reach the parameter “SAVE” (see next chapter)
To leave the submenu press the longer than 3 sec. and change to
S U B M E N UDEFAULT VALUES
Press on the Technovar to change to
10.37 Saving
SAVE ??? +
All values must be saved (stored in an EEPROM) afterchanging. If they are not saved, all changes will be
lost in case of a power failure! Saving: Press + till the message “SAVED” is shown on the display.
After saving, the display changes automatically to the 1st display after a few seconds.
Operating Instruction
65
11 Error Signals
11.1 Low Water
LACK OF WATER :E R R O R
Remedy:Check suction pressure or tank level!
If suction pressure or tank level is normal the unit restarts itself. If there is no suctionpressure switch (e.g. circulating systems), bridge terminals X1/6 and X1/7.
11.2 Conveyor Control
VAL.RANGE CONTR.E R R O R
The set minimum pressure threshold formonitoring pump delivery (delivery
threshold) was not achieved within the set delay time.At error reset ON the system is only shut down after 5 attempts of starting. If the deliverythreshold is set at <0, this function is deactivated.After the cause has been remedied, the malfunction can be reset by cutting off the powersupply for >30 seconds or pressing all three buttons ( , and. ) together for about 5seconds.
11.3 Overheating – Motor
MOTOR OVERHEATE R R O R
Possible causes: insufficient coolingAmbient temperature is too high, motor
overloaded. After the cause has been remedied, the malfunction can be reset by cutting offthe power supply for >30 seconds or pressing all three buttons ( , and ) together forabout 5 seconds.
11.4 Overheating – Inverter
INVERT. OVERHEADE R R O R
Possible causes: dirty dissipater or lack ofcooling air.
After the cause of the overheating has been remedied, the malfunction can be reset bycutting off the power supply for >30 seconds or pressing all three buttons ( , and )together for about 5 seconds.
11.5 Over voltage
OVERVOLTAGEE R R O R
Possible cause: Check mains supply, supplyvoltage too high, peak voltage owing to
switching heavy loads on the network, or RAMP 2 is to fast! Find the cause and takecountermeasures (e.g. network filter, RC-elements).After the cause has been remedied, the malfunction can be reset by cutting off the powersupply for >30 seconds or pressing all three buttons ( , and ) together for about 5seconds.
Operating Instruction
66
11.6 Under voltage
ITT INDUSTRIESUNDERVOLTAGE
Possible cause: Check mains supply, faultyfuse or phase unsymmetry.
After the cause has been remedied, the malfunction can be reset by cutting off the powersupply for >30 seconds or pressing all three buttons ( , and. ) together for about 5seconds.
11.7 Limit
ITT INDUSTRIESOverloaded
Possible causes: false data settings or thepump is working at a capacity significantly in
excess of its performance data. If the limit signal remains, OVERLOADED will appear after afew seconds and the frequency converter will stop.After the cause has been remedied, the malfunction can be reset by cutting off the powersupply for >30 seconds or pressing all three buttons ( , and. ) together for about 5seconds.
11.8 Short Circuit
OUTPUT SHORTE R R O R
This error means a too fast current peak atthe unit-output.
Possible reasons for this error!Connection cable between the control unit and the motor is damaged or the motor isdefective.Disconnect the system from the power supply and remedy the fault.After the cause has been remedied, the malfunction can be reset by cutting off the powersupply for >30 seconds or pressing all three buttons ( , and. ) together for about 5seconds.
11.9 Overload
OVERLOADEDE R R O R
Possible cause: Pump is jammed!Foreign body in the pumps, mechanical seal
defective (stiff) or the pump was idle for a long period of time.Ramp 1 too fast:Maximum frequency too high:Boost too low:Defective non-return valve – Pump runs in reverse when switched off (OFF).De-energise and get the pump running again or if necessary call customer service.After the cause has been remedied, the malfunction can be reset by cutting off the powersupply for >30 seconds or pressing all three buttons ( , and. ) together for about 5seconds.
11.10 Pressure Sensor Error I < 4 mA
ACT. VALUE SENSORE R R O R
Possible cause: Defective pressuretransmitter or broken cable (damaged cable)
Operating Instruction
67
Check the pressure transmitter!After the cause has been remedied, the malfunction can be reset by cutting off thepower supply for >30 seconds or pressing all three buttons ( , and. ) together forabout 5 seconds.
All error signals are given at terminal X2/1, X”/2 and X2/3 (changeover contact).If no Error is active, the relay switches on and terminals X2/2 and X2/3 are closed.
Attention If "AUTO - START ON" and "ERROR-RESET – ON" are programmed, the unitcan start again automatically after a power failure.
11.11 Additional Error signals:
ERROR 1 : EEPROM-ERROR (corresponding data block malfunction)
ERROR 2 : Security error / Software protection error
ERROR 4 : Buttonboard error (e.g.: jammed key)
ERROR 5 : EPROM-error
ERROR 6 : Program error: Watchdog error
ERROR 7 : Program error: Processor pulse error
ERROR 8 : Program error: invalid processor command
These ERROR signals can be reset by cutting off the power supply for >30 seconds orpressing all three buttons ( , and. ) together for about 5 seconds.If the error signal should appear again, contact customer service and provide a detaileddescription of the error.
12 RS 485 - Interface
Standardized Bus-Interface for communication between the inverters (Technovar Drive heads)and/or an overruling external control system.
The data protocol complies with ISO 1745 for RS 485 interfaces and contains the followingconfigurations:
Data rate : 9600 Baud (1 Startbit, 8 Data, 1 Stopbit)
An interface inverter RS 232/RS 485 is necessary in case communication with a V24 interface ofa PC or another external control system is wanted.
All parameters can be approached via the standard interface. The inline structure of theTechnovar Drive head can be obtained upon request.
1A fist1E Status word:
Operating Instruction
68
BIT0...BIT7 Inverter faultBIT8 FreeBIT9 fist<than set starting pressureBIT10 Pump Stop/StartBIT11 Pump runsBIT12 lead/lag operation active (activ=1)
1F Control Word:
0000 Inverter stop0001 Inverter start0002 Parameter – Save
0100 Master overrules0200 Requirement reset0300 Master overrules and requirement reset
For further information see:
serial data transmission – RS485TECHNOVAR – Protocol 120
13 Auxiliary Texts
All auxiliary texts that are available in texts in the display window are listed here. To call themup press the buttons + ; each auxiliary text then appears as "running text" in the secondline of the window.
Window Text: Auxiliary Text:
ITT INDUSTRIESx.xx psi
No auxiliary text available! Pressing buttons and provides LANGUAGE SELECTION
REQUIRED VALUEx.xx psi
Input or displayed of the desired value
REQUIRED VALUE 2x.xx psi
Input or displayed of the desired value 2
AUTO – STARTOFF
ON -> Autostart enabled; OFF -> Autostart disabled
Operating Instruction
69
ERROR 1..............
Last error
ERROR 2..............
4th recorded ERROR
ERROR 3..............
3rd recorded ERROR
ERROR 4..............
2nd recorded ERROR
ERROR 5..............
1st recorded ERROR
TOTAL RUN TIME0000:00
Total motor run time hh:mm
SAVE ??? +
Press [ + ] to save parameter values
PASSWORD0000
Enter Password
JOG - MODE0.0Hz xx.xx psi
JOG MODE: Frequency controlled by [ ] or [ ];(no control)
W I N D O W5%
Desired window width around the desired value(in % from the desired value)
RAMP HYSTERESIS80%
% of half desired window width related to hysteresis
RAMP 14.0 Sec
Ramp 1: acceleration time(actual value outside operating window)
RAMP 24.0 Sec
Ramp 2: deceleration time(actual value outside operating window)
RAMP 370 Sec
Ramp 3: acceleration time(actual value within window)
RAMP 470 Sec
Ramp 4: deceleration time(actual value within window)
Operating Instruction
70
MAX. FREQUENCY60.0 Hz
Maximum output frequency(Range: 40...70Hz)
MIN. FREQUENCY0.0 Hz
Minimum output frequency(Range: 0... MAX. FREQUENCY)
CONFIG FMINf -> 0
Configuration behaviour at minimum frequency
STOP-DELAY-FMIN0 Sec
Delay for pump stop, when f -> 0 is chosen
BOOST5.0 %
Extra power at pump start
SENSOR_ADJUST?Out of range
Sensor zero adjustment press [ + ]
SENSOR-CURVELinear
Sensor characteristic curve
SENSOR RANGE20mA = 362,6 psi
Normalise to max. SENSOR VALUE
MODE::Controller
CONTROLLER -> Standard control;ACTUATOR -> Frequency set point as ADC – VALUE;
MULTICONTROLLER -> control of up to 4 pumpsSYNCH. CONTROLLER -> synchronous regulationMANUAL CONTROL -> frequency set point using keyboard
REGULATION MODENormal
Pumping regulation mode:NORMAL -> Regulation normal;INVERS -> Regulation inverse
START VALUEdisabled
Start value
CONFIG. 2nd REQ. VALUEOFF
Configuration of a second value
RELAY CONFIGURATIONRun Motor
Relay configuration
S U B M E N UOffset
SUBMENU Offset; to entry push [SELECT] for at least 1sec.
Operating Instruction
71
OFFSET INPUTOFF
Selection of offset input
LEVEL 1XX.X %
Start level for offset 1
LEVEL 2XX.X %
Start level for offset 2
INTENSITY 1XX.X %
Intensity of offset 1
INTENSITY 2XX.X %
Intensity of offset 2
S U B M E N USeq. Control
SUBMENU Seq. Control; to entry push [ ] for at least1 sec.
ACTU. VALUE INC.5 psi
Actual value increase at switching of additional pump
ACTU. VALUE DEC.2,1 psi
Actual value decrease for consecutive pumps
ENABLE SEQ. CTL.58.0 Hz
Freq. Limit enable sequence control
SWITCH INTERVAL12 hours
Lead lay sequence changeover time
SOURCE REQ. VALUEOFF
Source of required value at active multicontroller
S U B M E N USynch. Control
SUBMENU Synchronous regulation; to entry push [ ]at least 1 sec..
SYNCHRON. LIMIT0,0 Hz
Frequency limit to enable the synchronous regulation
SYNCHRON-WINDOW2.0 Hz
Frequency window for the frequency limit whichactivates the synchronous regulation
PUMP – SEQUENCYAdr1 fault
Diagnostics: Pump sequence and status
Operating Instruction
72
BUSARBIT-DIAG.0
Diagnostics: Bus arbitation (this pump)
S U B M E N URS 485-Interface
SUBMENU Serial Interface; to entry push [ ] at least 1 sec..
PUMP-ADDRESSOFF
SIO-Address of the pump
ADC REFERENCELocal
Actual value or frequency reference enabled by thelocal ADC or by SIO
FREQU. – LIFTING37 Hz
Frequency limit for desired value lift
LIFT – AMOUNT0.0 %
Lift amount in % of desired value point(at maximum frequency)
ANALOG – OUTActual value
Meter output: ACTUAL FREQUENCY(corresp. to max. output frequency);ACTUAL VALUE (corresp. to max. desired pressure)
DIMENSION UNITpsi
Displayed dimension unit
TEST RUNafter 100 h.
Time interval for test run(10...100h...deactivated [ + ])
S U B M E N UTEST RUN man.
SUBMENU Pump test run manual; to entry push [ ]at least 1 sec..
TEST RUN man +
Start test – run with [ + ]
TEST-FREQUENCY30.0 Hz
Test – run frequency
BOOST TEST-RUN10 %
Test – run boost
S U B ME N UERRORS
SUBMENU Errors: to entry push [ ] at least 1 sec.
CONVEYOR-LIMITDisabled
Conveyor limit: In case fall short of turn off
Operating Instruction
73
DELAY TIME2 Sec
Delay for the error registration when the water islacking end for the conveyor control
ERROR – RESETOFF
Automatic Error Reset
CLEAR ERRORS0000
Clear error history
OPERATING HOURSxxxx h.
Total inverter operating time(Reset counters: press [ + ])
DISP. CONTRAST50 %
Display contrast
SET PASSWORD0066
Modify Password
LOCK FUNCTION OFF
ON -> Keypad locked;OFF -> changes are allowed
HEATINGOFF
Anti condensation heater
S U B M E N UDEFAULT VALUES
SUBMENU Load DEFAULT PARAMETERS; to entry push[ ] at least 1 sec.
DEFAULT EUROPE +
Load EUROPEAN DEFAULT PARAMETERS with [ + ]
DEFAULT USA +
Load USA DEFAULT PARAMETERS with [ + ]
SAVE ??? +
Press [ + ] to save parameter values
14 Maintenance
The TECHNOVAR control unit does not require special maintenance.However, the cooling fan and the vents should be free of dust occasionally.
14.1 NotesWhen replacing the control card in a plant with more than one pump ensure, that thesame control card version (V/STK/X) is used in all Technovar units.For further information, please ask your distributor!
Operating Instruction
74
ITT
IND
UST
RIES
x.xx
psi
Requ
ired
Val
ue 1
126,
9 ps
iA
uto
- Sta
rtO
NEr
ror
1Er
ror
2Er
ror
3Er
ror
4Er
ror
5To
tal R
un T
ime
0000
: 00
Save
??
+�
�
Pass
wo
rd0
000
JOG
- M
ode
0.0
Hz
319
,5 p
siW
indo
w5
%Ra
mp
Hys
tere
sis
80 %
Ram
p 1
4.0
Sec
Ram
p 2
4.0
Sec
Ram
p 3
70 S
ecRa
mp
470
Sec
Max
. Fre
quen
cy60
.0 H
zM
in. F
requ
ency
0.0
Hz
Conf
ig. F
min
F ->
0St
op
- D
elay
Fm
in0
Sek
Boos
t5.
0 %
Sens
or A
djus
t ?
out
of
rang
eSe
nso
r -
Cur
veLi
near
Sens
or R
ange
20 m
A =
362
,6 p
siM
ode
Cont
rolle
rRe
gula
tion
Mod
eN
orm
alSt
art
Valu
ed
isab
led
Con
fig. R
eq. V
al. 2
OFF
Rela
y C
onfi
g.Ru
n M
oto
rSU
BMEN
UO
ffse
t
Off
set
- In
put
OFF
Leve
l 10.
0 %
Leve
l 20.
0 %
Inte
nsity
1+
0.0
%
Inte
nsity
2+
0.0
%
SUBM
ENU
Seq
. Con
tro
l
Act
u. V
alue
Inc.
5 ps
i
Act
u. V
alue
Dec
.2,
1psi
Enab
le S
eq.
CTL.
58.
0 H
z
Switc
h In
terv
al12
hou
rs
Sour
ce R
eq. V
alu
eO
FF
SUBM
ENU
Sync
h. C
ontr
olSy
nch
ron.
Lim
it0.
0 H
z
Sync
hron
- W
indo
w2
.0 H
zPu
mp
- Seq
uen
ceA
dr
1
f
ault
Busa
rbit
- D
iag.
0
SUBM
ENU
RS4
85 -
Inte
rfac
e
Pum
p - A
ddre
ssO
FF
AD
C R
efer
ence
Loca
l
Lift
- A
mou
nt0
.0 %
Ana
log
- O
ut
Act
ual V
alue
Dim
ensi
on
Uni
tps
iTe
st R
un
afte
r 10
0 h
.
SUBM
ENU
Test
Run
Test
Run
man
.�
�+
Test
- F
req
uenc
y30
.0 H
z
Boos
t Te
st -
Run
10.0
%
SUBM
ENU
Erro
rs
Conv
eyor
- Li
mit
disa
bled
Del
ay T
ime
2 Se
c
Erro
r -
Rese
tdi
sabl
ed
Cle
ar E
rro
rs00
00
Ope
rati
ng H
our
s00
00 h
.D
isp.
- C
ontr
ast
50 %
Set
Pass
wo
rd00
66
Hea
ting
ON
Def
ault
Eu
rope
+�
�
Def
ault
USA
+�
�
SUB
MEN
UD
efau
lt Va
lues
Save
??
+�
�
Lock
Fun
ctio
nO
FF
Star
t
Freq
u. -
Lift
ing
37.0
Hz
Operating Instruction
75
ALABAMAMangham & Associates, Inc.Irondale (Birmingham)Phone: 205/956-2362FAX: 205/956-2477ALASKAColumbia Hydronics Co.Seattle, WAPhone: 206/988-6993FAX: 206/988-3938ARIZONAJ & B Sales CompanyPhoenixPhone: 602/258-1545FAX: 602/258-9719ARKANSASJohnson & Scott, Inc.Little RockPhone: 501/803-9520FAX: 501/803-9521Hydronic Technology Inc.Shreveport, LAPhone: 318/797-1500FAX: 318/797-1509Boone & Boone Sales Co., Inc.Tulsa, OKPhone: 918/664-9756FAX: 918/664-1675CALIFORNIACalifornia Hydronics Corp.Hayward (San Francisco)Phone: 510/293-1993FAX: 510/293-3080Rocklin (Sacramento)Phone: 510/293-1993FAX: 916/632-4765San JosePhone: 408/295-5874FAX: 408/297-8596Dawson Co.Altadena (Los Angeles)Phone: 626/797-9710FAX: 626/798-4659San DiegoPhone: 858/541-7867FAX: 858/541-0333COLORADOMcNevin CompanyDenverPhone: 303/322-0165FAX: 303/322-0374CONNECTICUTThe Bernard M. Packtor Co.Hamden (New Haven)Phone: 203/288-5241FAX: 203/287-1798
DELAWARER. D. Bitzer Co., Inc.Bensalem, PAPhone: 215/604-6600FAX: 215/604-6601Cummins-Wagner Co., Inc.Annapolis Junction, MDPhone: 800/966-1277301/490-9007FAX: 301/490-7156FLORIDAGeorge A. Israel Jr., Inc.JacksonvillePhone: 904/355-7867FAX: 904/355-0077MiamiPhone: 305/592-5343FAX: 305/591-4356OrlandoPhone: 407/423-5078FAX: 407/423-0918TallahasseePhone: 850/656-2055FAX: 850/656-1475TampaPhone: 813/839-2161FAX: 813/832-3182GEORGIAClary & Associates, Inc.AtlantaPhone: 404/873-1861FAX: 404/873-1867
George A. Israel Jr., Inc.Jacksonville, FLPhone: 904/355-7867FAX: 904/355-0077Tallahassee, FLPhone: 850/656-2055FAX: 850/656-1475HAWAIIDawson Co.Altadena (Los Angeles) CAPhone: 626/797-9710FAX: 626/798-4659IDAHOGritton & Associates, Inc.Salt Lake City, UTPhone: 801/486-0767FAX: 801/485-6364Columbia Hydronics Co.Vancouver, WAPhone:360/883-2600FAX: 360/883-2607
ILLINOISBornquist, Inc.ChicagoPhone: 773/774-2800FAX: 773/763-6534Blackmore & Glunt, Inc.Maryland Hghts. (St. Louis) MOPhone: 314/878-4313FAX: 314/878-6029Sandberg Co., Inc.East MolinePhone: 309/796-2371FAX: 309/796-2330Hydronic & Steam Equip. Co., Inc.Indianapolis, INPhone: 800/669-4926317/577-8326FAX: 317/577-7109INDIANAHydronic & Steam Equip. Co., Inc.IndianapolisPhone: 800/669-4926Phone: 317/577-8326FAX: 317/577-7109EvansvillePhone: 800/473-2753Phone: 812/473-0330FAX: 812/479-7650Ft. WaynePhone: 260/489-5785FAX: 260/489-4369South BendPhone: 800/932-6490Phone: 574/234-6005FAX: 574/234-6611Sandberg Co., Inc.East Moline, ILPhone: 309/796-2371FAX: 309/796-2330Blackmore & Glunt, Inc.Cincinnati, OHPhone: 513/489-5225FAX: 513/489-8755IOWAProducts, Inc.Des MoinesPhone: 515/288-5738FAX: 515/288-2574Sandberg Co., Inc.East Moline, ILPhone: 309/796-2371FAX: 309/796-2330Verne Simmonds Co.Omaha, NEPhone: 402/592-3131FAX: 402/592-0853
Operating Instruction
76
KANSASBlackmore & Glunt, Inc.Lenexa (Kansas City)Phone: 913/469-5715FAX: 913/469-1085KENTUCKYBlackmore & Glunt, Inc.Cincinnati, OHPhone: 513/489-5225FAX: 513/489-8755
Hydronic & Steam Equip. Co.,Inc.Evansville, INPhone: 800/473-2753812/473-0330FAX: 812/479-7650Johnson & Scott, Inc.Nashville, TNPhone: 615/254-5454FAX: 615/242-9243LOUISIANAHydronic Technology Inc.New OrleansPhone: 800/365-6746Phone: 504/827-1163FAX: 504/827-1167ShreveportPhone: 800/673-5737Phone: 318/797-1500FAX: 318/797-1509MAINEF.I.A., Inc.Woburn (Boston) MAPhone: 781/938-8900FAX: 781/933-3965MARYLANDCummins-Wagner Co., Inc.Annapolis JunctionPhone: 800/966-1277Phone: 301/490-9007FAX: 301/490-7156Thermoflo Equipment Co., Inc.Pittsburgh, PAPhone: 412/366-2012FAX: 412/367-0842MASSACHUSETTSF.I.A., Inc.Woburn (Boston)Phone: 781/938-8900FAX: 781/933-3965The Bernard M. Packtor Co.Hamden (New Haven) CTPhone: 203/288-5241FAX: 203/287-1798Albany, NYPhone: 518/459-1060FAX: 518/458-8776
MICHIGANR. L. Deppmann Co.Southfield (Detroit)Phone: 248/354-3710FAX: 248/354-3763Grand RapidsPhone: 616/656-0821FAX: 616/656-0830BridgeportPhone: 989/652-3049FAX: 989/652-3324Hydro-Flo Products, Inc.Brookfield (Milwaukee) WIPhone: 262/781-2810FAX: 262/781-2228MINNESOTABernard J. Mulcahy Co., Inc.Eagan, MNPhone: 651/686-8580FAX: 651/686-8588MISSISSIPPIHydronic Technology Inc.New Orleans, LAPhone: 800/365-6746Phone: 504/827-1163FAX: 504/827-1167Johnson & Scott, Inc.Little Rock, ARPhone: 501/803-9520FAX: 501/803-9521MISSOURIBlackmore & Glunt, Inc.Lenexa (Kansas City) KSPhone: 913/469-5715FAX: 913/469-1085Maryland Hgts. (St. Louis)Phone: 314/878-4313FAX: 314/878-6029MONTANAColumbia Hydronics Co.SpokanePhone: 509/242-1118FAX: 509/242-1120NEBRASKAVerne Simmonds Co.OmahaPhone: 402/592-3131FAX: 402/592-0853NEVADADawson Co.Las Vegas, NVPhone: 702/735-1226FAX: 702/735-1232Gritton & Associates, Inc.Salt Lake City, UTPhone: 801/486-0767FAX: 801/485-6364
NEW HAMPSHIREF.I.A., Inc.Woburn (Boston) MAPhone: 781/938-8900FAX: 781/933-3965NEW JERSEYWallace-Eannace Assoc., Inc.Franklin LakesPhone: 201/891-9550FAX: 201/891-4298R. D. Bitzer Co., Inc.Bensalem, PAPhone: 215/604-6600FAX: 215/604-6601NEW MEXICOBoyd Engineering Co., Inc.AlbuquerquePhone: 505/275-1250FAX: 505/275-1193NEW YORKWallace-Eannace Assoc., Inc.PlainviewPhone: 516/454-9300FAX: 516/454-9307Frank P. Langley Co., Inc.E. RochesterPhone: 585/248-5010FAX: 585/381-0512Amherst (Buffalo)Phone: 716/691-7575FAX: 716/691-7347Johnson CityPhone: 607/766-9950FAX: 607/766-9948The Bernard M. Packtor Co.AlbanyPhone: 518/459-1060FAX: 518/458-8776Syracuse Thermal Products,Inc.East SyracusePhone: 315/437-7321FAX: 315/437-7429NORTH CAROLINAJames M. Pleasants Co., Inc.GreensboroPhone: 800/365-9010Phone: 336/378-9911FAX: 336/378-2588CharlottePhone: 704/545-0145FAX: 704/545-2917RaleighPhone: 919/845-1960FAX: 919/845-1925WilmingtonPhone: 910/794-5447FAX: 910/794-5449
Operating Instruction
77
NORTH DAKOTABernard J. Mulcahy Co., Inc.Eagan, MNPhone: 651/686-8580FAX: 651/686-8588OHIOBlackmore & Glunt, Inc.CincinnatiPhone: 513/489-5225FAX: 513/489-8755R. L. Deppmann Co.Macedonia (Cleveland)Phone: 330/468-1102FAX: 330/468-1113Steffens-Shultz, Inc.ColumbusPhone: 614/274-5515FAX: 614/274-0126DaytonPhone: 937/278-7903FAX: 937/278-7825OHIO (Cont’d.)Thermoflo Equipment Co., Inc.Pittsburgh, PAPhone: 412/366-2012FAX: 412/367-0842OKLAHOMABoone & Boone Sales Co., Inc.Oklahoma CityPhone: 405/525-7475FAX: 405/521-1448TulsaPhone: 918/664-9756FAX: 918/664-1675OREGONColumbia Hydronics Co.Vancouver, WAPhone:360/883-2600FAX: 360/883-2607PENNSYLVANIAR. D. Bitzer Co., Inc.BensalemPhone: 215/604-6600FAX: 215/604-6601Thermoflo Equipment Co., Inc.PittsburghPhone: 412/366-2012FAX: 412/367-0842Frank P. Langley Co., Inc.Amherst (Buffalo) NYPhone: 716/691-7575FAX: 716/691-7347RHODE ISLANDF.I.A., Inc.Woburn (Boston) MAPhone: 781/938-8900FAX: 781/933-3965
SOUTH CAROLINAJames M. Pleasants Co., Inc.Greensboro, NCPhone: 800/365-9010Phone: 336/378-9911FAX: 336/378-2588ColumbiaPhone: 803/798-1405FAX: 803/798-1323GreenvillePhone: 864/232-0200FAX: 864/232-0025SOUTH DAKOTABernard J. Mulcahy Co., Inc.Eagan, MNPhone: 651/686-8580FAX: 651/686-8588Verne Simmonds Co.Omaha, NEPhone: 402/592-3131FAX: 402/592-0853TENNESSEEJohnson & Scott, Inc.NashvillePhone: 615/254-5454FAX: 615/242-9243Cordova (Memphis)Phone: 901/388-2919FAX: 901/388-0989Clary & Associates, Inc.Atlanta, GAPhone: 404/873-1861FAX: 404/873-1867James M. Pleasants Co., Inc.Greensboro, NCPhone: 800/365-9010336/378-9911FAX: 336/378-2588KnoxvillePhone: 865/584-5054FAX: 865/584-8385TEXASBoyd Engineering Co., Inc.Albuquerque, NMPhone: 505/275-1250FAX: 505/275-1193Oslin Nation CompanyDallasPhone: 214/631-5650FAX: 972/988-1446Ft. WorthPhone: 817/590-2500FAX: 817/590-2508
TEXAS (Cont’d.)Oslin Nation Company (Cont’d)HoustonPhone: 713/699-3500FAX: 713/699-8213San AntonioPhone: 800/243-7756Phone: 210/342-5544FAX: 210/342-2818UTAHGritton & Associates, Inc.Salt Lake CityPhone: 801/486-0767FAX: 801/485-6364VERMONTF.I.A., Inc.Woburn (Boston) MAPhone: 781/938-8900FAX: 781/933-3965The Bernard M. Packtor Co.Albany, NYPhone: 518/459-1060FAX: 518/458-8776VIRGINIATLA, Inc.RichmondPhone: 804/321-4444FAX: 804/321-3112Virginia BeachPhone: 757/497-3567FAX: 757/490-7362Cummins-Wagner Co., Inc.Annapolis Junction, MDPhone: 800/966-1277301/490-9007FAX: 301/490-7156WASHINGTONColumbia Hydronics Co.SeattlePhone: 206/988-6993FAX: 206/988-3938SpokanePhone: 509/242-1118FAX: 509/242-1120VancouverPhone:360/883-2600FAX: 360/883-2607WASHINGTON, DCCummins-Wagner Co., Inc.Annapolis Junction, MDPhone: 800/966-1277301/490-9007FAX: 301/490-7156
Operating Instruction
78
WEST VIRGINIABlackmore & Glunt, Inc.Cincinnati, OHPhone: 513/489-5225FAX: 513/489-8755TLA, Inc.Richmond, VAPhone: 804/321-4444FAX: 804/321-3112Thermoflo Equipment Co., Inc.Pittsburgh, PAPhone: 412/366-2012FAX: 412/367-0842WISCONSINHydro-Flo Products, Inc.Brookfield (Milwaukee)Phone: 262/781-2810FAX: 262/781-2228Bernard J. Mulcahy Co., Inc.Eagan, MNPhone: 651/686-8580FAX: 651/686-8588WYOMINGGritton & Associates, Inc.Salt Lake City, UTPhone: 801/486-0767FAX: 801/485-6364J. E. McNevin Co.Denver, COPhone: 303/322-0165FAX: 303/322-0374
top related