veris flow measurement group · 2017. 8. 1. · purpose regular spring -lock retractable hot taps...
Post on 09-Dec-2020
1 Views
Preview:
TRANSCRIPT
1
VERIS FLOW MEASUREMENT GROUP
2
Flow Meter Considerations
1. Pipe Size
2. Media Being Measured
3. Flow Rates
4. Pressure
5. Temperature
6. Outputs?
3
Flowmeter Sizing
4
Application Data Sheets
5
How Verabar Works
Verabar's superior performance is due
to its shape, surface roughness, and
low pressure port location
Verabar senses and averages the natural
pressures created by the velocity profile
High Pressure
VorticesLow Pressure
Flow
Flo
w
Low
Pressure
Hi
Pressure+ -
Average
Velocity
DP
6
Location of Average Velocity
±10%
±1%
Actual
Profiles
Verabar
Other
Textbook
Profile
Verabar Outperforms Other Insert Meters
• Velocity profiles vary with upstream pipe configuration and disturbances.
• The Verabar averages the profile.
• Other insert meters only sense a single point.
7
Bullet Shape Sensor Generates
Accurate & Trouble-Free Performance– No clogging
– Stable signal
– Low drag and increased structural strength
– Solid one-piece
construction
Pressure ports are
forward
of separation point to
eliminate clogging and
produce stable signal
Vortices
Frontal surface roughness
lowers drag and extends
accuracy range
8
Verabar's Non-Clog Design
•Low-pressure ports located on sensor sides
•virtually eliminate clogging and produce an
•extremely stable signal
9
Advantages of
Frontal Surface Roughness
•Turbulent Boundary Layer:
–Lowers drag and vortex- shedding forces by 50%
–Predictable, constant drag coefficient
•Dormant/Laminar Boundary Layer:
– Increases drag and vortex-shedding forces
– Unpredictable drag coefficient
Verabar's Roughened Surface
Verabar's
relative low-
pressure sensing
port location
Wake
Separation
point
Relative low -
pressure port
locations
Wake
Variable
separation point
Competitors’ Smooth Surface
10
Verabar's No-Leak Construction
•Verabar Flow Sensor– Solid, one-piece
construction
– No leaks between chambers
•Competitors' Construction– Tubes within a tube can leak
due to vibration or changes in pressure or temperature
Verabar Round, Diamond and T Shapes
L L
L
L
HH H
11
Exclusive Benefits of
Verabar Flow Sensor– Improved accuracy and turndown
– Eliminates clogging of sensor ports
– Superior signal stability
– Lowers drag, flow-induced vibration
– 5-year performance warranty
– Up to 2500 LB ANSI, 6000 PSI and 1000 Deg F
– Square and Rectangular Ducts, Large Stacks
– 1.5” – 22 feet in length
12
22 FOOT VERABAR (V510)
13
The Verabar DP Advantage
– DP is one of the most reliable, dependable flow measurement systems
– Plant personnel can verify calibration and service transmitters in the field
– Measures gas, liquid and steam
– Insertion and retraction under pressure, remote mount
– Low permanent pressure loss
– Minimum pipe penetrations
– Lower installation cost
14
Verabar Models
General Purpose
Regular Spring-Lock
Retractable Hot TapsRegular Flanged
Flanged
Regular Spring-
Lock
V100 V150
V110
V200 V400
V500
V550
V510
15
Verabar Retractable (Hot Tap) Models
• Insert and Retract Under Full Pipe PressureFlanged Models
Threaded Models Synchro-Drive
Fast Insertion Of Dual-Rod Drive Systems
Drive Nut
Drive Chain Protective Chain Shroud
16
Straight-Run Requirements
24D
18D
9D
7D
D
2D
3D
EccentricReducers &Expanders
Two Or MoreElbows In
Different Planes
One Or More Tees,Y’s Or Crosses, Single Inlet,
Multiple Outlets(Same Or Different Plane)
< 5D < 5D
ConcentricReducers & Expanders
> 5D
All Valves
Two Or MoreElbows In
Same Plane
One Or More Tees,Y’s Or Crosses, Single Inlet,
Multiple Outlets(Same Plane)
Open Gate, BallOr Plug Valve
Elbow Mount For Minimum Straight Run
(Accuracy ±3.0% & RequiresAn Adjusted K Factor)
Sensors Must Be Located In Plane
With The Center LineOf The Elbow
17
Installation and Orientation
– Simple, fast installation
– Accomplished by plant personnel
Vertical PipesHorizontal Pipes
Liquid
or Steam
Remote Mount
160°
160°
Gas Direct Mount
Liquid
or
Steam
Gas
360°
18
Exotic Materials
Some of exotic materials we’ve used:
• Hastelloy C
• Haynes 25 (2100 Deg. F, cobalt-nickel-chromium-tungsten alloy)
• Tantelum Infused (Hydrogen Bromine, Sulf. Acid)
• Monel
• Duplex SS (2x stronger than regular SS)
• Inconel
• Kynar (PVDF - Polyvinylidene fluoride)
• Nickel Aluminum Bronze (sea water)
• 310 SS
• 316 H (High Temp SS rated for over 1000 Deg.)
19
Verabar Summary – Features & Benefits
• Gas, Liquid, Steam• DP is a well known technology• ±1% of rate accuracy• Excellent Repeatability (± 0.05%)• Stable signal & no clogging• Solid Steel Construction-No Leaking• Hot tap installation• Low permanent pressure loss• 5 Year Warranty• Maintenance Free
Bullet Shape
Wake
Roughened Surface
Separation Point
20
Veris Accelabar
21
ACCELABAR DESIGN
The INLET is a
patented
torroidal radius
that accelerates
and conditions
the flow to
produce a
linear velocity
profile
The STRAIGHTENING & SETTLING
ZONE stabilizes & linearizes the
velocity profile
The DIFFUSER is
a gradual increase
in the diameter
to reduce the
permanent
pressure loss
22
ACCELABAR ADVANTAGES
23
ACCELABAR ADVANTAGES
24
ACCELABAR ADVANTAGES
25
Integral Expanders and Reducers
Saves on Installation Cost
12” x 10” Reducers8” x 12” Expanders
26
Single Source Responsibility5 year guarantee from date of invoice
D/P or MV TRANSMITTER
RTD / J BOX THERMO-WELL SST
3 VALVE MANIFOLD
ACCELABAR KEP ES749 Flow Computer
27
28
University Steam Piping
29
No straight run
Natural gas to LNG heaters
80 psig @ 70°F
2 stacked transmitters
0-302.8”H20
0-1.6:” H20
Replaced a turbine meter that was unable to cover the turndown and handle the short straight run
Natural Gas Installation60 ,000 to 1 ,000SCFH (Turndown 60 :1)
30
Installation below ground in vault flanged
between butterfly and gate valve
31
NASA high pressure (6000PSIG) nitrogen flow
Accelabar for fire suppression
32
Accelabar Applications
• Mayo Industries – Loveland, CO
• Two 3” Accelabarswith IMV25
transmitters measuring and blending land fill gas and natural gas
• Skid mounted
• Space requirement was at a minimum
33
2” X 1” Hastelloy C Accelabars U.S. ARMY CHEMICAL
WEAPONS DESTRUCTION
34
API 22.2 test at CEESI
35
Accelabar Summary
FEATURES
• 1) No Straight Run required
• 2) Five Year Performance warranty from date of invoice.
• 3) No pipe reduction required.
• 4) Single source responsibility.
• 5) High Flow turndown (Up to 65:1)
• 6) No field calibration required
• 7) 0.5% of Rate accuracy.
• 8) Pre configured, install, start up, walk away.
• 9) Pulse, Analog, Modbus/Bacnet options.
36
Armstrong Vortex Meter
37
Armstrong Vortex Meter
A Little History Lesson:• Vortices were first observed by Leonardo De Vinci in the
early 1500’s• About 400 years later Theodore von Kármán observed the
repeating pattern of swirling vortices caused by the unsteady separation of flow of a fluid around blunt bodies, named the von Kármán vortex street
38
Armstrong Vortex Meter
39
Armstrong Vortex Meter
40
Armstrong Vortex Meter
41
Armstrong Vortex Meter
• Steam, water, gas measurement• Sizes ½” to 12”• Temps -330°F to 750°F• Up to ANSI Class 600• Multivariable options: Velocity, Temp, Pressure, Temp & Pressure, BTU• Velocity, temperature, pressure measurements integral to meter body• Outputs: Loop powered 4-20 mA, Relays, Pulse output, HART, MODBUS, BACnet• 1.5% of rate accuracy or better • Turndown up to 100:1 (application dependent)• Push button digital display • Remote electronics available • FM, FMC, ATEX, IECEx – Approvals In Process
42
Armstrong Vortex Meter
43
Armstrong Vortex Meter
44
VERIS Verabar
1991
VERIS Accelabar
2004
Venturi Tube Flow Nozzle Orifice Plate2017Wedge Meter
Armstrong
Vortex Meter
Complete Flow Offering
45
6315 Monarch Park PlaceNiwot, Colorado 80503 USA
Phone: (303) 652-8550Cell: 720-491-9926
E-Mail: jzoppa@armstronginternational.comWebsite: armstronginternational.com/veris
Contact: Jon Zoppa