vitodens300 wb3a 49 66kw service
Post on 02-Jun-2018
216 Views
Preview:
TRANSCRIPT
-
8/10/2019 Vitodens300 WB3A 49 66kW Service
1/132
VIESMANN Service instructionsfor heating engineers
Vitodens 300Type WB3A , 49 and 66 kWGas fired wall mounted condensing boiler natural gas and LPG version
See applicability on the last page
VITODENS 300
5692 550 GB 5/2004 Please keep safe
-
8/10/2019 Vitodens300 WB3A 49 66kW Service
2/132
Please follow these safety instructions closely to prevent accidents andmaterial losses.
Safety instructions explained
Danger This symbol warns against therisk of injury.
! Important informationThis symbol warns against therisk of material losses andenvironmental pollution.
NoteDetails identified by the words "Note" contain additional information.
Warranty
All war ranty rights are void if theseservice instructions are not observed.
Target group
These service instructions are exclu-sively designed for qualified person-nel.Work on gas equipment must only becarried out by a registered gas fitter.Only approved contractors may mod-ify this equipment for countries other than those designated on the typeplate. That contractor will thenarrange for the relevant approval inthat country.Electrical work must only be carriedout by a qualified electrician.The system must be commissioned bythe system installer or a qualified per-son authorised by the installer.
Regulations
Observe the following during servicework:& all legal instructions regarding the
prevention of accidents,& the TRGI, TRF and special regula-
tions, e.g. those of the BDH,& all legal instructions regarding
environmental protection,& the Code of Practice by relevant
trade associations and all local reg-ulations.
If you notice a smell of gas
Danger Escaping gas can cause explo-sions which may lead to ser-ious injury.& Do not smoke. Prevent
naked flames and sparks.Never switch electrical lightsor equipment.
& Open windows and doors.& Close the gas shut-off valve.& Remove all personnel from
the danger zone.& Observe the safety regula-
tions of your local gas sup-plier which can be found onthe gas meter.
& Notify your heating contrac-tor from outside the building.
Safety instructions
2
Safety instructions
5 6 9 2 5 5 0 G B
-
8/10/2019 Vitodens300 WB3A 49 66kW Service
3/132
If you smell flue gas
Danger Flue gas may lead to life-threa-tening poisoning.& Shut down the heating sys-
tem.& Ventilate the boiler room.& Close all doors leading to the
living space.
Repair work
It is not permitted to carry out repairson parts that fulfil a safety function.Use only original Viessmann spareparts, or equivalent parts that havebeen approved by Viessmann.
Service work on the heating system
& Isolate the system from mains sup-ply, e.g. by removing a separatefuse or by means of a mains electri-cal isolator, and check that it is nolonger 'live'.
& Safeguard the system againstunauthorised reconnection.
& When using gas as fuel, also closethe main gas shut-off valve and
safeguard against unauthorisedreopening.
Ancillary components, spare andwearing parts
! Important informationComponents which are nottested with the heating system,the installation of non-approved spare parts andunauthorised conversion maylead to damage to the heatingsystem, which may affect their function and limit our warranty.For conversions or replace-ments, use only original partsfrom Viessmann or those whichare approved by Viessmann.
Safety instructions (cont.)
3
Safety instructions
5 6 9 2 5 5 0 G B
-
8/10/2019 Vitodens300 WB3A 49 66kW Service
4/132
Initial start-up, inspection, maintenanceSteps - initial start-up, inspection and maintenance ..................................... 5Further details regarding the individual steps .............................................. 7
CodingCode 1........................................................................................................ 38Code 2........................................................................................................ 42Resetting the coding to the delivered condition ........................................... 62
Service scansService level summary ................................................................................ 63
Temperatures, boiler coding card and brief scans ....................................... 64Checking outputs (relay test) ...................................................................... 68Scanning operating conditions and sensors ................................................ 70
TroubleshootingCalling up fault code history ........................................................................ 73Call up current fault codes .......................................................................... 73Checking and acknowledging faults ............................................................ 75Repairs ...................................................................................................... 85
Function descriptionConstant temperature control units ............................................................. 95Weather-compensated control units ............................................................ 96Extensions for external connections (accessory) ......................................... 98Control functions ........................................................................................ 102
DesignsConnection and wiring diagrams internal connections .............................. 107Connection and wiring diagrams external connections.............................. 109
Parts lists .................................................................................................. 111
Commissioning/service reports ............................................................... 118
Specification ............................................................................................. 124
CertificatesDeclaration of conformity ............................................................................ 125Manufacturer's certificate according to the 1st BImSchV [Germany]............. 126
Keyword index .......................................................................................... 127
Index
4
Index
5 6 9 2 5 5 0 G B
-
8/10/2019 Vitodens300 WB3A 49 66kW Service
5/132
For further instructions on individual steps, see pages indicated
Commissioning steps
Inspection steps
Maintenance steps Page
! ! ! 1. Filling the heating system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 2. Venting the boiler . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
3. Venting the heating system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 4. Filling the siphon with water . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 5. Checking the electrical mains connection 6. Language selection (if required) - only for the
weather-compensated control units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 7. Setting the time and date (if required) - only for
weather-compensated control units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 8. Checking the gas type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 9. Changing the gas type (see separate installation
instructions) 10. Function sequence and possible faults . . . . . . . . . . . . . . . . . . . . . . . 10 11. Checking static and supply pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 12. Checking the CO 2 settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 13. Setting the max. output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 14. Checking all connections on the primary and DHW
side for leaks 15. Checking the burner (recording values on
page 118 of commissioning report) 16. Checking the balanced flue system for soundness
(annular gap check) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 17. Removing the burner and checking the burner
gasket (replace gasket every two years) . . . . . . . . . . . . . . . . . . . . . . 18 18. Checking the burner gauze assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 19. Checking and adjusting the ignition and ionisation
electrodes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Steps - initial start-up, inspection and maintenance
5
Initial start-up, inspection, maintenance
5 6 9 2 5 5 0 G B
-
8/10/2019 Vitodens300 WB3A 49 66kW Service
6/132
Commissioning stepsInspection steps
Maintenance steps Page
! ! ! 20. Cleaning the combustion chamber/heating
surfaces and installing the burner . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 21. Checking the condensate drain and cleaning the
siphon . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22 22. Checking the neutralising system (if installed)
23. Checking the diaphragm expansion vessel andsystem pressure
24. Checking the function of all safety valves 25. Checking tightness of electrical connections 26. Checking all gas equipment for soundness at
operating pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22 27. Checking the ionisation current . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23 28. Checking the external LPG safety valve (if
installed) 29. Matching the control unit to the heating system . . . . . . . 24 30. Connecting the control unit to the LON system
(only for weather-compensated control units) . . . . . . . . . . 31 31. Implementing a user check (in conjunction with
the LON system) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32 32. Adjusting heating curves (only for weather-
compensated control units) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33 33. Instructing the system user . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
34. Scanning and resetting the "Maintenance" display 37
Steps - initial start-up, inspection and maintenanc . . . (cont.)
6
Initial start-up, inspection, maintenance
5 6 9 2 5 5 0 G B
-
8/10/2019 Vitodens300 WB3A 49 66kW Service
7/132
Filling the heating system1. Check the charge pressure of the
diaphragm expansion vessel.
2. Close the gas shut-off valve.
3. ! Important informationUnsuitable fill water increases the level of depos-its and corrosion and may
lead to boiler damage.& Thoroughly flush the entire
heating system prior to fill-ing with water.
& Only use fill water of pota-ble quality.
& Soften fill water harder than 20 dH (3.58 mmol/l).For suitable means of water softening, see theVitotec pricelist.
& An ant i-freeze additive sui-table for heating systemscan be mixed with the fillwater.
Fill the heating system via the boi-ler fill & drain valve A (minimumsystem pressure > 0.8 bar).
4. Close the boiler fill & drainvalve A .
Further details regarding the individual steps
7
Initial start-up, inspection, maintenance
5 6 9 2 5 5 0 G B
-
8/10/2019 Vitodens300 WB3A 49 66kW Service
8/132
Venting the boiler 1. Close the shut-off valves on the
heating water side.
2. Connect the drain hose to the boiler fill & drain valve B .
3. Open valves A and B , and ventat mains pressure, until no sound of escaping air can be heard.
4. Close valves A and B , and openthe primary shut-off valves.
Venting the heating system
1. Close the gas shut-off valve andstart the control unit.
2. Activate the venting program viacoding address 2F:1.
NoteTo call up code 1 and for setting thecoding address, see page 38.For function and sequence of theventing program, see page 103.
3. Check the system pressure.
Further details regarding the individual steps (cont.)
8
Initial start-up, inspection, maintenance
5 6 9 2 5 5 0 G B
-
8/10/2019 Vitodens300 WB3A 49 66kW Service
9/132
Filling the siphon with water 1. Remove the retaining clip and
siphon A .
2. Fill the siphon with water.
3. Fit siphon A and secure with theretaining clip.
Language selection (if required) - only for the weather-com-pensated control units
1. Press c .
2. Select the required languagewith b .
3. Confirm with d .
Setting the time and date (if required) - only for weather-com-pensated control units
NoteDuring commissioning, or after prolonged time out of use, it may be necessary to set the time and date.
1. Press D .
2. Set the correct time with a / b .
3. Confirm with d ; Date will then bedisplayed.
4. Set the current date with a / b .
5. Confirm with d .
Further details regarding the individual steps (cont.)
9
Initial start-up, inspection, maintenance
5 6 9 2 5 5 0 G B
-
8/10/2019 Vitodens300 WB3A 49 66kW Service
10/132
Checking the gas type
! Important informationThe natural gas version cannot beconverted to LPG.
1. Enquire about the gas type andWobbe index (Wo) from your localmains gas or LPG supplier.
Note
In the delivered condition, Vito- dens 300 is set up for natural gas E or LPG P.Natural gas E version:The boiler can be operated in theWobbe index range 12.0 to16.1 kWh/m 3 (43.2 to 58.0 MJ/m 3 ).LPG P version:The boiler can be operated in theWobbe index range 21.4 to22.5 kWh/m 3 (76.9 to 81.0 MJ/m 3 ).
2. Compare the gas category (gastype) and gas group with the detailson the label on the gas train andthe cap plate.
3. If these details do not match thefuel provided, the burner must beconverted according to the detailsprovided by the mains gas or theLPG supplier.
See separate conversion kitinstallation instructions.
After conversion from& Natural gas E or LPG P to nat-
ural gas LLThe boiler can be operated in theWobbe index range 10.0 to13.1 kWh/m 3 (36.0 to 47.2 MJ/ m 3 ).
& LPG P to natural gas EThe boiler can be operated in theWobbe index range 12.0 to16.1 kWh/m 3 (43.2 to 58.0 MJ/ m 3 ).
4. Set the gas type via codingaddress 1E at the control unit.
NoteTo call up code 1 and for setting thecoding address, see page 38.
5. Record the gas type in the servicereport on page 118.
Function sequence and possible faults
For further details regarding faults, see page 75.
Further details regarding the individual steps (cont.)
10
Initial start-up, inspection, maintenance
5 6 9 2 5 5 0 G B
-
8/10/2019 Vitodens300 WB3A 49 66kW Service
11/132
Display screen RemedyControl unitissues heatdemand
No Set value
Yes
Fan startsNo
After approx .51 seconds
Check cables andplug-in connec-tionsFault
F9
Yes
Differential pres-sure sensor enables start(0.75 V acrossterminals X8.5and X8.6)
No After approx .51 seconds
Check fan cablesand fan plug-inconnections,check fan
FaultE6
YesIgnition No Fault Check the ignition
module (controlvoltage 230 Vacross plugs X2.1and X2.2)
F4
Yes
Gas combination
valve opens
No Fault Check the gas
train (control vol-tage 230 V) andgas supply pres-sure
F4
Yes
Further details regarding the individual steps (cont.)
11
Initial start-up, inspection, maintenance
5 6 9 2 5 5 0 G B
-
8/10/2019 Vitodens300 WB3A 49 66kW Service
12/132
Ionisation cur-rent builds(higher than5 A) No
Fault Check electrodeadjustment andgas pipe for air-locks
Symbol A F4
Yes
Operational bur-ner
Stops below setboiler tempera-ture and restarts
Check flue gassystem for sound-ness (flue gas
recirculation),check gas flowpressure
Checking static and supply pressure
Danger Higher CO emissions can lead to poisoning.Measure the CO value before and after any work on gas equipment toprevent any health hazards and to ensure the perfect operational condi-tion of the system.
Operation with LPG Flush the LPG tank twice during commissioning/replacement. Thoroughly vent the tank and gas lines after flushing.
Further details regarding the individual steps (cont.)
12
Initial start-up, inspection, maintenance
5 6 9 2 5 5 0 G B
-
8/10/2019 Vitodens300 WB3A 49 66kW Service
13/132
1. Close the gas shut-off valve.
2. Release the screw inside test nip-ple PE A on the gas combinationvalve , but do not remove, and con-nect the pressure gauge.
3. Open the gas shut-off valve.
4. Check the static pressure; it shouldbe a max. of 57.5 mbar. Record the
actual value in the service report.
5. Start up boiler.
NoteDuring commissioning, the boiler can enter a fault state because of airlocks in the gas pipe. After approx. 5 seconds, press E toreset the burner.
6. Check the supply (flow) pressure; itshould be& 20 mbar for natural gas,& 50 mbar for LPG.
NoteUse suitable test equipment with aresolution of at least 0.1 mbar tomeasure the supply pressure.
Record the actual value in the ser-vice report.Take the action shown in the table.
Further details regarding the individual steps (cont.)
13
Initial start-up, inspection, maintenance
5 6 9 2 5 5 0 G B
-
8/10/2019 Vitodens300 WB3A 49 66kW Service
14/132
Supply (flow)pressure for nat-ural gas
Supply (flow)pressure for LPG
Remedy
Below 17.4 mbar Below 42.5 mbar Do not start up. Notify your mains gas or LPG supplier.
17.4 to 57.5 mbar 42.5 to57.5 mbar
Start up boiler.
Above 57.5 mbar Above 57.5 mbar Install a separate gas governor down-stream of the system and regulate thepressure to 20 mbar for natural gas or 50 mbar for LPG.Notify your mains gas
or LPG supplier.
7. Shut down the boiler, close the gasshut-off valve, remove the pressuregauge, and close test nipple Awith the screw.
8. Open the gas shut-off valve andstart the boiler.
Danger Gas escaping from the testnipple leads to a risk of explosion.Check test nipple A for soundness.
Checking the CO 2 settings
Vitodens 300 is factory-set for natural gas E or LPG P. The natural gas E versioncan be converted to natural gas LL using a conversion kit. The LPG P versioncan be converted to natural gas E or LL using a conversion kit.During commissioning or maintenance, check the CO 2 level at the boiler adap-tor.
NoteThe MatriX burner for Vitodens 300 is preset for the entire gas group. Therefore,the burner requires no further setting or adjustment.
Subject to the Wobbe index, the CO 2 content fluctuates between
Further details regarding the individual steps (cont.)
14
Initial start-up, inspection, maintenance
5 6 9 2 5 5 0 G B
-
8/10/2019 Vitodens300 WB3A 49 66kW Service
15/132
& 6.6 to 10.0 % for natural gas E& 7.0 to 10.0 % for natural gas LL and& approx. 10.0 % for LPG P.
Compare the actual CO 2 value with the above CO 2 value ranges for the indivi-dual gas groups (check the gas group with your mains gas or LPG supplier).If the actual CO 2 value deviates by more than 1 % for natural gas or 0.5 % for LPG, proceed as follows:& Check whether the correct gas restrictor has been installed.& Check the balanced flue system for soundness, see page 17.
1. Connect a flue gas analyser at theflue gas aperture A on the boiler adaptor.
2. Open the gas shut-off valve, com-mission the boiler and create a heatdemand.
3. Select the lower rated output.
Constant temperature control units:& Press both keys 9 and d simul-
taneously, until the display shows1.
Weather-compensated controlunits:& Press both keys 9 and d simul-
taneously until the display shows"Relay test".
& With a / b in the display, select"Basic load".
4. Check the CO 2 content. Should theactual value deviate by more than1 % from the above range, imple-ment steps from page 15 (possiblyreplace the burner).
5. Enter actual values into the serv icereport.
Further details regarding the individual steps (cont.)
15
Initial start-up, inspection, maintenance
5 6 9 2 5 5 0 G B
-
8/10/2019 Vitodens300 WB3A 49 66kW Service
16/132
6. Set the upper rated output.
Constant temperature control units:& With a / b in the display, select
2.
Weather-compensated controlunits:& With a / b in the display, select
"Full load".
7. Check the CO 2 content. Should theactual value deviate by more than1 % from the above range, imple-ment steps from page 15 (possiblyreplace the burner).
8. After testing, press d .
9. Enter actual values into the servicereport.
Setting the max. output
NoteThe max. output can be limited for heating operation . You can limit the output via the modulation range.
1. Start up boiler.
2. Press both K and F simulta-neously until 100 flashes on thedisplay, (equals 100 % of the ratedoutput) and A appears. Onweather-compensated controlunits, the display additionallyshows "Max. output".
3. With a / b select the requiredvalue in % of rated output as max.output.
4. Confirm the set value with d .
5. Record the settings for max. outputon the additional type plateincluded with the technical docu-mentation. Affix the type plate nextto the original type plate on top of the boiler.
NoteThe output can also be limited for DHW loading. For this, change coding address 6F in code 2.
Further details regarding the individual steps (cont.)
16
Initial start-up, inspection, maintenance
5 6 9 2 5 5 0 G B
-
8/10/2019 Vitodens300 WB3A 49 66kW Service
17/132
Checking the balanced flue system for soundness (annular gap check)
A Combustion air aperture
For balanced flue systems testedtogether with the gas fired wallmounted boiler, some Federal States(e.g. Northrhein-Westphalia) waivethe requirement for a soundness test(overpressure test) during commis-sioning by the flue gas inspector.For such cases we recommend that
your heating contractor carries out asimple soundness test during theinitial start-up of your system. For this, it would be sufficient to check theCO 2 concentration in the combustionair at the annular gap in the balancedflue pipe.The flue pipe is deemed to be sound,if the CO 2 concentration of the com-bustion air is no higher than 0.2 % or the O 2 concentration is at least20.6 %.If actual CO 2 values are higher or O 2values are lower, carry out a pressuretest on the flue pipe at a static pres-sure of 200 Pa.
Further details regarding the individual steps (cont.)
17
Initial start-up, inspection, maintenance
5 6 9 2 5 5 0 G B
-
8/10/2019 Vitodens300 WB3A 49 66kW Service
18/132
Removing the burner and checking the burner gasket(replace gasket every two years)
1. Switch OFF the control unit ON/ OFF switch and the mains electricalsupply.
2. Close the gas shut-off valve andsafeguard against reopening.
3. Pull electrical cables from fan
motor A , differential pressure sen-sor B , gas valve C , ionisationelectrode D , ignition electrodesE and earth F .
4. Release gas connection pipe Gfixing screws and fittings.
5. Release six nuts H and removethe burner.
! Important informationPrevent damage to the wiremesh.Never rest the burner on thegauze assembly.
6. Check the burner gasket (see partslist) for damage.Generally, replace the burner gas-ket every two years .
Further details regarding the individual steps (cont.)
18
Initial start-up, inspection, maintenance
5 6 9 2 5 5 0 G B
-
8/10/2019 Vitodens300 WB3A 49 66kW Service
19/132
Checking the burner gauze assemblyReplace the burner gauze assembly if the wire mesh is damaged.
1. Remove electrodes A .
2. Turn thermal insulation ring Bclockwise and remove.
3. Release the eight Torx screws Cand remove the burner gauze
assembly D .
4. Remove the old gauze assemblygasket E .
5. Insert a new burner gauze assem-bly with a new gasket, and securewith eight Torx screws.
NoteTorque: 4.5 Nm
6. Refit the thermal insulation ring B .
Checking and adjusting the ignition and ionisation electro-des
A Ionisation electrode B Ignition electrodes
Further details regarding the individual steps (cont.)
19
Initial start-up, inspection, maintenance
5 6 9 2 5 5 0 G B
-
8/10/2019 Vitodens300 WB3A 49 66kW Service
20/132
1. Check the electrodes for wear andcontamination.
2. Clean the electrodes with a smallbrush (not with a wire brush) or emery paper.
! Important informationWire meshdo not damage.
3. Check all clearances. If the gapsare not as specified or the electro-des are damaged, replace andalign the electrodes together withnew gaskets. Tighten the electrodefixing screws with 2 Nm.
Further details regarding the individual steps (cont.)
20
Initial start-up, inspection, maintenance
5 6 9 2 5 5 0 G B
-
8/10/2019 Vitodens300 WB3A 49 66kW Service
21/132
Cleaning the combustion chamber/heating surfaces andinstalling the burner
1. If required, clean combustionchamber A and heatingsurfaces B with a brush or flushwith water.
! Important informationScratches on parts whichare in contact with flue
gases can lead to corrosion.Only use plastic brushes andNOT wire brushes.
Apply a solvent-/potassium-freecleaning agent if residues remain:& Remove soot deposits with alka-
line cleaning agents with addi-tional surfactants (e.g. Fauch600).
& Remove coatings and surfacediscolouration (yellow-brown)with slightly acidic, chloride-freecleaning agents based on phos-phoric acid (e.g. Antox 75 E).
& Thoroughly flush with water.
NoteFauch 600 and Antox 75 E are sup- plied by:Hebro Chemie GmbH Rostocker Strae 40 D 41199 Mnchengladbachc : Intec Bassersdorf AGGrindelstrasse 12 PostfachCH-8303 Bassersdorf
2. Install the burner and torque nutsdiagonally with 4.5 Nm.
Further details regarding the individual steps (cont.)
21
Initial start-up, inspection, maintenance
5 6 9 2 5 5 0 G B
-
8/10/2019 Vitodens300 WB3A 49 66kW Service
22/132
3. Secure the gas supply pipe with anew gasket.
4. Check the gas connections for soundness.
Danger Escaping gas leads to a riskof explosion.Check all fittings for sound-ness.
5. Connect the electrical cables/leadsto each corresponding component.
Checking the condensate drain and cleaning the siphon
1. Check at the siphon, that the con-densate can freely drain.
2. Remove the retaining clip and thesiphon.
3. Clean the siphon.
4. Fit the siphon and secure with theretaining clip.
Checking all gas equipment for soundness at operating pres-
sureDanger Escaping gas leads to a risk of explosion.Check gas equipment for soundness.
Further details regarding the individual steps (cont.)
22
Initial start-up, inspection, maintenance
5 6 9 2 5 5 0 G B
-
8/10/2019 Vitodens300 WB3A 49 66kW Service
23/132
Checking the ionisation current
A Adaptor line (available as acces-sory)
B Control unit cable
1. Remove the cable and connect thetest equipment.
2. Set the upper rated output.
Constant temperature control units:& Press K and d simultaneously
for at least 2 seconds.& With a / b in the display, select
2.
Weather-compensated controlunits:& Press K and d simultaneously
for at least 2 seconds.& With a / b in the display, select
"Full load".
NoteThe minimum ionisation current should be at least 5 A as soon asthe flame is established (approx. 2 - 3 seconds after opening the gastrain).
3. If the ionisation current is < 5 A\;& Check the electrode gap, see
page 19.& Check the control unit power sup-
ply.
4. After testing, press d .
5. Record the actual value in the ser-vice report.
Further details regarding the individual steps (cont.)
23
Initial start-up, inspection, maintenance
5 6 9 2 5 5 0 G B
-
8/10/2019 Vitodens300 WB3A 49 66kW Service
24/132
Matching the control unit to the heating systemNoteThe control unit must be matched to the system equipment. Various systemcomponents are automatically recognised by the control unit, and codes areautomatically set.& For selection of an appropriate design, see the following diagrams.& For coding steps, see page 38.
System design 1
With/without DHW heating with 1 heating circuit without mixer
! Outside temperature sensor (onlyfor weather-compensated controlunits)or
lH Vitotrol 100 (only for constanttemperature control units)
% Cylinder temperature sensor s Heating circuit pump
sA Cylinder loading pump (connec-tion via external extension H1)
sK Cylinder loading pump (connec-tion via internal extension H1 or H2)
A Internal extension H1 or H2or External extension H1
Further details regarding the individual steps (cont.)
24
Initial start-up, inspection, maintenance
5 6 9 2 5 5 0 G B
-
8/10/2019 Vitodens300 WB3A 49 66kW Service
25/132
Required coding AddressFunction relay of the internal extension: Cylinder loadingpump
53:3
System design 2
With/without DHW heating with 1 heating circuit with mixer and systemseparation
! Outside temperature sensor ? Flow temperature sensor % Cylinder temperature sensor s Heating circuit pumpsA Cylinder loading pump (connec-
tion via external extension H1)sK Cylinder loading pump (connec-
tion via internal extension H1 or H2)
lH Power supplyaVG KM BUS
A Internal extension H1 or H2or External extension H1
B Extension kit for 1 heating circuitwith mixer
C Maximum temperature controller (underfloor heating)
D Heating circuit pump (sec-ondary)
E Heating circuit pump (primary)F Heat exchanger for system
separationG Expansion vessel
Further details regarding the individual steps (cont.)
25
Initial start-up, inspection, maintenance
5 6 9 2 5 5 0 G B
-
8/10/2019 Vitodens300 WB3A 49 66kW Service
26/132
Required coding Address1 heating circuit with mixer & with DHW cylinder 00:4& without DHW cylinder 00:3Function relay of the internal extension: Cylinder loadingpump
53:3
System design 3
With/without DHW heating with low loss header, 1 heating circuit withoutmixer and 1 heating circuit with mixer
! Outside temperature sensor ? Flow temperature sensor % Cylinder temperature sensor s Heating circuit pump or boiler
circuit pumpsA Cylinder loading pump (connec-
tion via external extension H1)lH Power supplyaVG KM BUS
A External extension H1B Low loss header C Extension kit for 1 heating circuit
with mixer D Maximum temperature controller
(underfloor heating)
Further details regarding the individual steps (cont.)
26
Initial start-up, inspection, maintenance
5 6 9 2 5 5 0 G B
-
8/10/2019 Vitodens300 WB3A 49 66kW Service
27/132
E Heating circuit pump heating cir-cuit with mixer F Heating circuit pump heating cir-
cuit without mixer (connectionvia external extension H1)
Required coding Address
Further details regarding the individual steps (cont.)
27
Initial start-up, inspection, maintenance
5 6 9 2 5 5 0 G B
-
8/10/2019 Vitodens300 WB3A 49 66kW Service
28/132
System design 4
With/without DHW heating with 3 or more heating circuits with mixer andlow loss header
! Outside temperature sensor ? Flow temperature sensor % Cylinder temperature sensor s Heating circuit pump or boiler cir-
cuit pumpsA Cylinder loading pump (connec-
tion via external extension H1)
sK Cylinder loading pump (connec-tion via internal extension H1 or H2)
f Power supplygS Mixer motor A Internal extension H1 or H2
or External extension H1
B Low loss header
Further details regarding the individual steps (cont.)
28
Initial start-up, inspection, maintenance
5 6 9 2 5 5 0 G B
-
8/10/2019 Vitodens300 WB3A 49 66kW Service
29/132
C Vitotronic 050D Maximum temperature controller (underfloor heating)
E Heating circuit pumpF Mixer motor
Required coding AddressFunction relay of the internal extension: Cylinder loadingpump
53:3
Further details regarding the individual steps (cont.)
29
Initial start-up, inspection, maintenance
5 6 9 2 5 5 0 G B
-
8/10/2019 Vitodens300 WB3A 49 66kW Service
30/132
System design 5
Multi-boiler system with/without DHW heating with several heating circuitswith mixer and low loss header
! Outside temperature sensor ? Flow temperature sensor heat-
ing circuits? / Flow temperature sensor / low
loss header % Cylinder temperature sensor s Heating circuit pump or boiler
circuit pumpsA Cylinder loading pump
f Power supplygS Mixer motor aVG KM BUSA Low loss header B Vitotronic 333C Maximum temperature control-
ler (underfloor heating system)D Heating circuit pumpE Mixer motor
Further details regarding the individual steps (cont.)
30
Initial start-up, inspection, maintenance
5 6 9 2 5 5 0 G B
-
8/10/2019 Vitodens300 WB3A 49 66kW Service
31/132
Required coding AddressMulti-boiler system with Vitotronic 333 01:2
NoteCodes for multi-boiler system, seeVitotronic 333 installation and operat- ing instructions.
Connecting the control unit to the LON system (only for weather-compensated control units)
The LON communication module (accessory) must be plugged in.
Installation instructionsLON communication module
NoteData transfer via the LON system can take 2 to 3 minutes.
Setting up LON user numbers
Adjust the user number via codingaddress 77 (see below).
In a LON system, the same number cannot be allocated twice.
Updating the LON user list
Only possible, if all users are connected, and the control unit is encoded as faultmanager (code 79:1).
1. Press L and d simultaneouslyfor approx. 2 seconds. User checkinitiated (see page 32).
2. Press e . The user list is updatedafter approx. 2 minutes. User check completed.
Single boiler system with Vitotronic 050 and Vitocom 300
Further details regarding the individual steps (cont.)
31
Initial start-up, inspection, maintenance
5 6 9 2 5 5 0 G B
-
8/10/2019 Vitodens300 WB3A 49 66kW Service
32/132
Boiler controlunit Vitotronic 050 Vitotronic 050 Vitocom
User no. 1Code 77:1
User no. 10Code 77:10
User no. 11Set code 77:11
User no. 99
Control unit isfault manager *1Code 79:1
Control unit is notfault manager *1Code 79:0
Control unit is notfault manager *1Code 79:0
Control unit isfault manager
Sent time via LONCode 7b:1
Time received viaLONSet code 81:3
Time received viaLONSet code 81:3
Time receivedvia LON
Transmit outsidetemperature viaLONSet code 97:2
Outside tempera-ture is received viaLONSet code 97:1
Outside tempera-ture is received viaLONSet code 97:1
Fault monitoringLON user code9C:20
Fault monitoringLON user code9C:20
Fault monitoringLON user code9C:20
Implementing a user check (in conjunction with the LON sys-tem)
Communication with the system devices connected to the fault manager istested with a user check.Preconditions:& The control unit must be encoded as fault manager (code 79:1).& The LON user number must be encoded in all control units (see page 31).& The fault manager user list must be up to date (see page 31).
Further details regarding the individual steps (cont.)
32
Initial start-up, inspection, maintenance
5 6 9 2 5 5 0 G B
*1In each heating system, only one Vitotronic may be encoded as fault manager.
-
8/10/2019 Vitodens300 WB3A 49 66kW Service
33/132
A Consecutive list number B User number
1. Press L and d simultaneouslyfor approx. 2 seconds. User checkinitiated.
2. Select the required user with aand b .
3. Activate checking with d ."Check " flashes until its comple-tion. The display and all key illumi-nations of the selected user flash
for approx. 60 seconds.& "Check OK " flashes during com-
munication between bothdevices.
& "Check not OK " flashes if thereis no communication betweenboth devices. Check LON con-nection.
4. For checking further users, proceedas for items 2 and 3.
5. Press L and d simultaneouslyfor approx. 1 second. User checkcompleted.
Adjusting heating curves (only for weather-compensatedcontrol units)
The heating curves illustrate the rela-tionship between the outside tem-perature and the boiler water or theflow temperature. To put it simply: thelower the outside temperature, thehigher the boiler water or flow tem-perature. The room temperature,again, depends on the boiler water or the flow temperature.
Settings in the delivered condition:& Slope = 1.4& Level = 0
Generally, the slope of the heatingcurve lies& in the range of A for underfloor
heating systems,& in the range of B for low tempera-
ture heating systems (according tothe Energy Savings Order [Ger-many]).
Further details regarding the individual steps (cont.)
33
Initial start-up, inspection, maintenance
5 6 9 2 5 5 0 G B
-
8/10/2019 Vitodens300 WB3A 49 66kW Service
34/132
Changing slope and level
A Changing the slopeB Changing the level
1. Modify the slope in code 1 with cod-ing address d3 (see page 38).Value adjustable from 0.2 to 3.5.
2. Modify the slope in code 1 with cod-ing address d4 (see page 38).Value adjustable from 13 to +40 K.
Further details regarding the individual steps (cont.)
34
Initial start-up, inspection, maintenance
5 6 9 2 5 5 0 G B
-
8/10/2019 Vitodens300 WB3A 49 66kW Service
35/132
Adjusting the set room temperature
Standard room temperature:
1. Select a heating circuit:& Press a .
1 r flashes on the display.& Select heating circuit A1 (heating
circuit without mixer):Press d .
& Select heating circuit M2 (heating
circuit with mixer): Press a . 2 r flashes on the display. Press d .
Example 1: Modifying the standardroom temperature from 20 C to 26 C
A Boiler water or flow temperaturein C
B Outside temperature in CC Set room temperature in CD Heating circuit pump OFFE Heating circuit pump ON
2. Adjust the set day temperature withrotary selector ts .The value will be automaticallyadopted after approx. 2 seconds. Accordingly, the heating curve isadjusted along the set room tem-perature axis, which results in mod-ified start/shutdown characteristicsof the heating circuit pumps, if theheating circuit pump logic is acti-vated.
Further details regarding the individual steps (cont.)
35
Initial start-up, inspection, maintenance
5 6 9 2 5 5 0 G B
-
8/10/2019 Vitodens300 WB3A 49 66kW Service
36/132
Reduced room temperature:
1. Select a heating circuit:& Press a .
1 r flashes on the display.& Select heating circuit A1 (heating
circuit without mixer):Press d .
& Select heating circuit M2 (heatingcircuit with mixer): Press a . 2 r flashes on the display. Press d .
Example 2: Modifying the reducedroom temperature from 5 C to 14 C.
A Boiler water or flow temperaturein C
B Outside temperature in CC Set room temperature in CD Heating circuit pump OFFE Heating circuit pump ON
2. Call up the set night temperaturewith E .
3. Change this value with a and b .
4. Confirm the set value with d .
Instructing the system user
The system installer must hand the operating instructions to the system user and instruct them in the operation of the system.
Further details regarding the individual steps (cont.)
36
Initial start-up, inspection, maintenance
5 6 9 2 5 5 0 G B
-
8/10/2019 Vitodens300 WB3A 49 66kW Service
37/132
Scanning and resetting the "Maintenance" displayThe red fault indicator flashes when the limits set via coding address 21 and 23have been reached. As regards the operating interface display:& For constant temperature control units, the hours run (subject to setting) or
the given time interval and the clock symbol flashes.& For weather-compensated control units "Maintenance" flashes.
NoteSet code 24:1 and then code 24:0, if maintenance is implemented before main- tenance is displayed; the set maintenance parameters for hours run and interval
are then reset to 0.
1. Press c .Maintenance scan is activated.
2. Scan maintenance messageswith a or b .
3. Press d , for weather-compen-sated control units also confirm thedisplay "Acknowledge: Yes"with d ."Maintenance" is cancelled fromthe display and the red fault indica-tor continues to flash.
Note An acknowledged maintenancemessage can be redisplayed by pressing d (approx. 3 seconds).
After maintenance has been carriedout
1. Reset code 24:1 to 24:0.The red fault indicator is extin-guished.
NoteIf coding address 24 is not reset, anew "Maintenance" message will be displayed on Monday at 07:00 h.
2. If required:& Press c .& Reset burner hours run, burner
starts and consumption (seepage 70).
& Press c .
Further details regarding the individual steps (cont.)
37
Initial start-up, inspection, maintenance
5 6 9 2 5 5 0 G B
-
8/10/2019 Vitodens300 WB3A 49 66kW Service
38/132
Call up code 11. Press K and L simultaneously
for approx. 2 seconds.
2. Select the required coding addresswith a or b ; the address flashes.Confirm with d ; the value flashes.
NoteCodes are displayed in plain text
on weather-compensated control units. Codes, which are not rele- vant because of the equipment level of your heating system or because of settings of other codes,will not be displayed.
3. Change this value with a and b ;confirm with d . The display brieflyshows "adopted", then the addressflashes again. Select additionaladdresses (if required) with aor b .
4. Press K and L simultaneouslyfor approx. 1 second.
Code 1
38
Coding
5 6 9 2 5 5 0 G B
-
8/10/2019 Vitodens300 WB3A 49 66kW Service
39/132
SummaryCodes
Coding inthe asdeliveredconditionAddress:value
Function mode CodingchangeAddress:value
Possible change
System design00:1 System version 1:
1 heating circuit withoutmixer A1, without DHWheating
00:2 System version 1:1 heating circuit withoutmixer A1, with DHW heat-ing
00:3 System version 2, 4, 5:1 mixer circuit M2, with-out DHW heating
00:4 System version 2, 4, 5:1 mixer circuit M2, withDHW heating
00:5 System version 3:1 heating circuit withoutmixer A1 and 1 mixer cir-cuit M2, without DHWheating
00:6 System version 3:1 heating circuit withoutmixer A1, 1 mixer circuitM2 with DHW heating
Single and multi-boiler system01:1 *1Single boiler system 01:2 Mult i-boiler system with
Vitotronic 333Max. boiler temp.06:... Maximum limit of the
boiler water tempera-ture, defaulted by theboiler coding card
06:20to06:127
Maximum limit of the boi-ler water temperaturewithin the rangesdefaulted by the boiler
Code 1 (cont.)
39
Coding
5 6 9 2 5 5 0 G B
*1Only for constant temperature control units.
-
8/10/2019 Vitodens300 WB3A 49 66kW Service
40/132
Coding inthe asdeliveredconditionAddress:value
Function mode CodingchangeAddress:value
Possible change
Gas type1E:0 Natural gas operation,
defaulted by the boiler coding card
1E:1 LPG operation, defaultedby the boiler coding card
Venting/filling
2F:0 Venting program dis-abled
2F:1 Venting program enabled2F:2 Filling program enabled
User no.77:1 LON user number 77:2
to77:99
LON user number, adjus-table from 1 to 99:1 - 4 = boiler 5 = cascade10 - ... = Vitotronic 05099 = Vitocom
Note Allocate each number only once.
DHW priority A1 A2:2 DHW cylinder prior ity
applicable to heatingcircuit pump and mixer
A2:0 Without cylinder prior ityfor heating circuit pump
DHW priority M2 A2:2 DHW cylinder prior ity
applicable to heating
circuit pump and mixer
A2:0 Without DHW cylinder priority applicable to
heating circuit pump andmixer A2:1 DHW cylinder prior ity
only applicable to mixer A2:3to A2:15
Modulating DHW cylinder priority
Summer econ. A1 A5:5 *1With heating circuit
pump logic function A5:0 Without heating circuit
pump logic function
Code 1 (cont.)
40
Coding
5 6 9 2 5 5 0 G B
*1Only for weather-compensated control units.
-
8/10/2019 Vitodens300 WB3A 49 66kW Service
41/132
Coding inthe asdeliveredconditionAddress:value
Function mode CodingchangeAddress:value
Possible change
Summer econ. M2 A5:5 *1With heating circuit
pump logic function A5:0 Without heating circuit
pump logic functionMin. flow temp. A1C5:20 Electronic limit of the
minimum flow tempera-ture: 20 C
C5:1
toC5:127
Minimum limit adjustable
from 1 to 127 C
Min. flow temp. M2C5:20 Electronic limit of the
minimum flow tempera-ture: 20 C
C5:1toC5:127
Minimum limit adjustablefrom 1 to 127 C
Max. flow temp. A1C6:75 *1Electronic maximum
flow temperature limit at75 C
C6:1toC6:127
Maximum limit adjustablefrom 1 to 127 C
Max. flow. temp. M2C6:75 *1Electronic maximum
flow temperature limit at75 C
C6:1toC6:127
Maximum limit adjustablefrom 1 to 127 C
Slope A1d3:14 *1Heating curve slope =
1.4d3:2tod3:35
Heating curve slopeadjustable from 0.2 to 3.5(see page 33)
Slope M2d3:14 *1Heating curve slope =
1.4d3:2to
d3:35
Heating curve slopeadjustable from 0.2 to 3.3
(see page 33)Level A1d4:0 *1Heating curve level =
0d4: 13tod4:40
Heating curve leveladjustable from 13 to 40(see page 33)
Level M2d4:0 *1Heating curve level =
0d4: 13tod4:40
Heating curve leveladjustable from 13 to 40(see page 33)
Code 1 (cont.)
41
Coding
5 6 9 2 5 5 0 G B
*1Only for weather-compensated control units.
-
8/10/2019 Vitodens300 WB3A 49 66kW Service
42/132
Calling up code 21. Press L and G simultaneously
for approx. 2 seconds; confirmwith d .
2. Select the required coding addresswith a or b ; the address flashes.Confirm with d ; the value flashes.
3. Change this value with a and b ;confirm with d . The display brieflyshows "adopted", then the addressflashes again. Select additionaladdresses (if required) with aor b .
4. Press L and G simultaneouslyfor approx. 1 second.
Overall summary
The coding addresses are grouped in accordance with the following functionranges . The respective function range is displayed.Scroll through the ranges in the following sequence with a or b .
Function range Coding addressesSystem design 00 and 01Boiler/burner 06 to 54DHW 56 to 73General 76 to 9FBoiler circuit (heating circuit A1 withoutmixer)
A0 to F7
Mixer circuit (heating circuit M2 with mixer) A0 to F7
NoteCodes, which are not relevant because of the equipment level of your heating system or because of settings of other codes, will not be displayed.For heating systems with 1 heating circuit without mixer and 1 heating circuit with mixer, initially the possible coding addresses A0 to F7 are scrolled for theheating circuit without mixer A1, then those for the heating circuit with mixer M2.
Code 2
42
Coding
5 6 9 2 5 5 0 G B
-
8/10/2019 Vitodens300 WB3A 49 66kW Service
43/132
Codes
Coding inthe asdeliveredconditionAddress:value
Function mode CodingchangeAddress:value
Possible change
System design00:1 System design 1:
1 heating circuit withoutmixer A1, without DHWheating
00:2 System design 1:1 heating circuit withoutmixer A1, with DHW heat-ing
00:3 System design 2, 4, 5:1 mixer circuit M2, with-out DHW heating
00:4 System design 2, 4, 5:1 mixer circuit M2, withDHW heating
00:5 System design 3:1 heating circuit without
mixer A1 and 1 mixer cir-cuit M2, without DHWheating
00:6 System design 3:1 heating circuit withoutmixer A1, 1 mixer circuitM2 with DHW heating
01:1 *1Single boiler system 01:2 Mult i-boiler system withVitotronic 333
Boiler/burner 06:... Maximum limit of the
boiler water tempera-ture, defaulted by theboiler coding card
06:20to06:127
Maximum limit of the boi-ler water temperaturewithin the rangesdefaulted by the boiler
07:1 *1Boiler number inmulti-boiler systems
07:2to07:4
Boiler number 2 to 4 inmulti-boiler systems
1E:0 Natural gas operation,defaulted by the boiler coding card
1E:1 LPG operation, defaultedby the boiler coding card
Code 2 (cont.)
43
Coding
5 6 9 2 5 5 0 G B
*1Only for constant temperature control units.
-
8/10/2019 Vitodens300 WB3A 49 66kW Service
44/132
Coding inthe asdeliveredconditionAddress:value
Function mode CodingchangeAddress:value
Possible change
21:0 No maintenance indica-tionBurner
21:1to21:100
The number of hours runbefore the burner shouldbe serviced is adjustablefrom 100 to 10000 hours(each step represents
100 hours)23:0 No time interval for bur-
ner maintenance23:1to23:24
Time interval adjustablefrom 1 to 24 months
24:0 No "Maintenance" dis-play
24:1 "Maintenance" display(the address is automati-cally set and must bemanually reset after maintenance has beencompleted)
25:0 *1No recognition of out-side temperature sen-sor or remotemonitoring
25:1 Recognition of outsidetemperature sensor andfault monitoring
28:0 No burner interval igni-tion
28:1 The burner is forced ONonce every 24 hours
2E:0 Without external exten-sion
2E:1 Inc luding ex ternal exten-sion (automatical adjust-ment on connection)
2F:0 Venting program dis-abled
2F:1 Venting program enabled2F:2 Filling program enabled
30:1 Internal variable speedcirculation pump (auto-matic adjustment)
30:0 Internal circulation pumpwithout variable speed(e.g. temporarily for ser-vice)
31:65 Set speed of the inter-nal circulation pumpwhen operated as boiler circuit pump 65 %,defaulted by the boiler coding card
31:0to31:100
Set speed adjustablefrom 0 to 100 %
Code 2 (cont.)
44
Coding
5 6 9 2 5 5 0 G B
*1Only for constant temperature control units.
-
8/10/2019 Vitodens300 WB3A 49 66kW Service
45/132
Coding inthe asdeliveredconditionAddress:value
Function mode CodingchangeAddress:value
Possible change
32:0 Signal "External lock-out" on circulationpumps: All pumps arecontrolled
32:1to32:15
Signal "External lockout"on circulation pumps:See the following table
Coding Internalcircula-tion pump
Heating cir-cuit pumpHeating cir-cuit withoutmixer
Heating circuitpumpHeating circuitwith mixer
Cylinder loadingpump
0 Controlfunct.
Control funct. Control funct. Control funct.
1 Controlfunct.
Control funct . Control funct. OFF
2 Controlfunct.
Control funct. OFF Control funct.
3 Controlfunct.
Control funct. OFF OFF
4 Controlfunct.
OFF Control funct. Control funct.
5 Controlfunct.
OFF Control funct. OFF
6 Controlfunct.
OFF OFF Control funct.
7 Control
funct.
OFF OFF OFF
8 OFF Control funct. Control funct. Control funct.9 OFF Control funct. Control funct. OFF10 OFF Control funct. OFF Control funct.11 OFF Control funct. OFF OFF12 OFF OFF Control funct. Control funct.13 OFF OFF Control funct. OFF14 OFF OFF OFF Control funct.15 OFF OFF OFF OFF
Code 2 (cont.)
45
Coding
5 6 9 2 5 5 0 G B
-
8/10/2019 Vitodens300 WB3A 49 66kW Service
46/132
Coding inthe asdeliveredconditionAddress:value
Function mode CodingchangeAddress:value
Possible change
Boiler/burner 34:0 Signal "External
demand" on circulationpumps: All pumps arecontrolled
34:1to34:23
Signal "External demand"on circulation pumps:See the following table
Coding Internalcirculationpump
Heating cir-cuit pumpHeating cir-cuit withoutmixer
Heating cir-cuit pumpHeating cir-cuit withmixer
Cylinder loading pump
0 Controlfunct.
Controlfunct.
Control funct. Control funct.
1 Controlfunct.
Controlfunct.
Control funct. OFF
2 Controlfunct.
Controlfunct.
OFF Control funct.
3 Controlfunct.
Controlfunct.
OFF OFF
4 Controlfunct.
OFF Control funct. Control funct.
5 Controlfunct.
OFF Control funct. OFF
6 Controlfunct.
OFF OFF Control funct.
7 Controlfunct. OFF OFF OFF
8 OFF Controlfunct.
Control funct. Control funct.
9 OFF Controlfunct.
Control funct. OFF
10 OFF Controlfunct.
OFF Control funct.
11 OFF Controlfunct.
OFF OFF
12 OFF OFF Control funct. Control funct.
Code 2 (cont.)
46
Coding
5 6 9 2 5 5 0 G B
-
8/10/2019 Vitodens300 WB3A 49 66kW Service
47/132
Coding Internalcirculationpump
Heating cir-cuit pumpHeating cir-cuit withoutmixer
Heating cir-cuit pumpHeating cir-cuit withmixer
Cylinder loading pump
13 OFF OFF Control funct. OFF14 OFF OFF OFF Control funct.15 OFF OFF OFF OFF16 ON Control
funct.Control funct. Control funct.
17 ON Controlfunct.
Control funct. OFF
18 ON Controlfunct.
OFF Control funct.
19 ON Controlfunct.
OFF OFF
20 ON OFF Control funct. Control funct.21 ON OFF Control funct. OFF22 ON OFF OFF Control funct.23 ON OFF OFF OFF
Coding inthe asdeliveredconditionAddress:value
Function mode CodingchangeAddress:value
Possible change
Boiler/burner 50:0 Alternative control
(automatic adjustmentupon recognition of the
operating interface)
50:1 Constant temperaturecontrol units
50:3 Weather-compensated
control units52:0 Without flow tempera-ture sensor for low lossheader
52:1 With flow temperaturesensor for low lossheader (automatic adjust-ment upon recognition)
Code 2 (cont.)
47
Coding
5 6 9 2 5 5 0 G B
-
8/10/2019 Vitodens300 WB3A 49 66kW Service
48/132
Coding inthe asdeliveredconditionAddress:value
Function mode CodingchangeAddress:value
Possible change
53:1 Function relay 2 of theinternal extension:DHW circulation pump
53:0 Function relay 2: Centralfault
53:2 Function relay 2: Externalheating circuit pump(heating circuit without
mixer)53:3 Function relay 2: External
cylinder loading pump54:0 Without solar control
unit54:1 With Vitosolic 10054:2 With Vitosolic 200 (auto-
matic adjustment onrecognition)
Domestic hot water 56:0 DHW temperature
adjustable from 10 to60 C
56:1 DHW temperature adjus-table from 10 to 95 C(only for gas fired boilers)Observe the max. per-missible DHW tempera-ture
58:0 Without auxiliary func-tion for DHW loading
58:1to58:95
Input of set DHW value 2;adjustable from 1 to95 C (observe codingaddress 56)
59:0 DHW cylinder loading:Starting point -2.5 KStopping point +2.5 K
59:1to59:10
Starting point adjustablefrom 1 to 10 K below theset value
5b:0 DHW cylinder directlyconnected to the boiler 5b:1 DHW cylinder connecteddownstream of the lowloss header
60:10 *1During DHW loading,the boiler water tem-perature is up to 20 Khigher than the setDHW temperature
60:5to60:25
The difference betweenthe boiler water tempera-ture and the set DHWtemperature is adjustablefrom 10 to 50 K
Code 2 (cont.)
48
Coding
5 6 9 2 5 5 0 G B
*1Only for weather-compensated control units.
-
8/10/2019 Vitodens300 WB3A 49 66kW Service
49/132
Coding inthe asdeliveredconditionAddress:value
Function mode CodingchangeAddress:value
Possible change
62:2 Circulation pump with 2minutes run-on time
62:0 Circulation pump withoutrun-on
62:1to62:15
Run-on time adjustablefrom 1 to 15 minutes
63:0 *1Without auxiliaryfunction for DHW load-ing
63:1 Additional function: 1 xdaily
63:2to63:14
Every 2 to every 14 days
63:15 2 x daily65:... Information regarding
the type of diverter valve (not adjustable)
65:0 Without diverter valve65:1 Diverter valve by Viess-
mann65:2 Diverter valve by Wilo65:3 Diverter valve by Grund-
fos67:40 In conjunc tion with Vito-
solic solar control unit:Set DHW value 3
67:0to67:60
DHW set value adjusta-ble from 0 to 60 C
6C:100 Set speed internal DHWloading pump 100 %
6C:0to6C:100
Set speed adjustablefrom 0 to 100 %
6F:100 Max. output duringDHW loading 100 %,defaulted by the boiler
coding card
6F:0to6F:100
Max. output during DHWloading adjustable from 0to 100 %
71:0 *2DHW circulationpump: On according toDHW time program
71:1 OFF during DHW loadingto set value 1
71:2 ON during DHW loadingto set value 1
72:0 *2DHW circulationpump: ON according totime program
72:1 OFF during DHW loadingto set value 2
72:2 ON during DHW loadingto set value 2
Code 2 (cont.)
49
Coding
5 6 9 2 5 5 0 G B
*1Only for constant temperature control units.*2 Only for weather-compensated control units.
-
8/10/2019 Vitodens300 WB3A 49 66kW Service
50/132
-
8/10/2019 Vitodens300 WB3A 49 66kW Service
51/132
Coding inthe asdeliveredconditionAddress:value
Function mode CodingchangeAddress:value
Possible change
80:1 With 5 seconds' timedelay for fault message;message will be issued,if a fault persists for atleast 5 seconds
80:0 Without time delay80:2to80:199
Time delay adjustablefrom 10 to 995; 1 step =5 s
81:1 Automatic summer/win-ter changeover
81:0 Manual summer/winter changeover
81:2 The application of theradio clock module will berecognised automatically
81:3 Accept time via LON88 :0 Temperature display in
Celsius88 :1 Temperature display in
Fahrenheit90:128 Time constant for calcu-
lating the adjusted out-side temperature21.3 hours
90:0to90:199
Fast (low values) or slow(high values) matching of flow temperature subjectto set value if the outsidetemperature changes;1 step = 10 min
91:0 *1No external operatingmode changeover viaexternal extension
91:1 External heating programchangeover applies toheating circuit withoutmixer
91:2 External heating programchangeover applies toheating circuit with mixer
91:3 External heating programchangeover applies toheating circuit withoutmixer and heating circuitwith mixer
95:0 Without Vitocom 100communication inter-face
95:1 With Vitocom 100 com-munication interface;automatic recognition
Code 2 (cont.)
51
Coding
5 6 9 2 5 5 0 G B
*1Only for weather-compensated control units.
-
8/10/2019 Vitodens300 WB3A 49 66kW Service
52/132
Coding inthe asdeliveredconditionAddress:value
Function mode CodingchangeAddress:value
Possible change
97:0 *1The outside tempera-ture of the sensor con-nected to the controlunit is utilised internally
97:1 Outside temperature isadopted by the LON BUS
97:2 The outside temperatureof the sensor connectedto the control unit will be
utilised internally andtransmitted via LON BUSto any connected Vitotro-nic 050.
98:1 Viessmann systemnumbers (in conjunctionwith monitoring of sev-eral systems via Vito-com 300)
98:1to98:5
System number adjusta-ble from 1 to 5
9b:70 Minimum set boiler water temperature incase of externaldemand
9b:1to9b:127
Set temperature adjusta-ble from 1 to 127 C
9C:20 *1Monitoring LON usersWhen there is noresponse from a user,values defaulted insidethe control unit continueto be used for a further 20 minutes. Only thenwill a fault message betriggered.
9C:0 No monitoring9C:5to9C:60
Time adjustable from 5 to60 minutes
9F:8 *1Differential tempera-ture 8 K; only in con- junction with a mixer circuit
9F:0to9F:40
Differential temperatureadjustable from 0 to 40 K
Boiler circuit, mixer circuit A0:0 *1Without remote con-
trol A0:1 With Vitotrol 200 (auto-
matic recognition) A0:2 With Vitotrol 300 (auto-
matic recognition)
Code 2 (cont.)
52
Coding
5 6 9 2 5 5 0 G B
*1Only for weather-compensated control units.
-
8/10/2019 Vitodens300 WB3A 49 66kW Service
53/132
-
8/10/2019 Vitodens300 WB3A 49 66kW Service
54/132
Parameters Heating circuit pumpAddress A3:... ON at OFF at-9 -10 C -8 C-8 -9 C -7 C-7 -8 C -6 C-6 -7 C -5 C-5 -6 C -4 C-4 -5 C -3 C-3 -4 C -2 C-2 -3 C -1 C-1 -2 C 0 C0 -1 C 1 C1 0 C 2 C2to15
1 Cto14 C
3 C
16 C
Coding inthe asdeliveredconditionAddress:value
Function mode CodingchangeAddress:value
Possible change
Boiler circuit, mixer circuit A4:0 *1With frost protection A4:1 No fros t protection,
adjustment only possibleif code A3:-9 is selected.
NoteWhen selecting a valuebelow 1 C there will be a
risk of pipes outside thethermal insulation envel- ope of the house freez- ing-up. The standby mode, in particular,should be observed, e.g.during holidays.
Code 2 (cont.)
54
Coding
5 6 9 2 5 5 0 G B
*1Only for weather-compensated control units.
-
8/10/2019 Vitodens300 WB3A 49 66kW Service
55/132
Coding inthe asdeliveredconditionAddress:value
Function mode CodingchangeAddress:value
Possible change
A5:5 *1With heating circuitpump logic function(economy circuit): Heat-ing circuit pump OFF, if the outside temperature
(AT) is 1 K higher thanthe set room tempera-ture (RT Set ) AT > RT Set +1 K
A5:0 Without heating circuitpump logic function
A5:1to A5:15
With heating circuit pumplogic function: Heatingcircuit pump OFF, if (see
the following table)
Parameter addressA5:...
With heating circuit pump logic function: Heatingcircuit pump OFF, if
1 AT > RTSet +5 K2 AT > RTSet +4 K3 AT > RTSet +3 K4 AT > RTSet +2 K5 AT > RTSet +1 K6 AT > RTSet7to
AT > RT Set -1 K
15 AT > RT Set - 9 K
Code 2 (cont.)
55
Coding
5 6 9 2 5 5 0 G B
*1Only for weather-compensated control units.
-
8/10/2019 Vitodens300 WB3A 49 66kW Service
56/132
Coding inthe asdeliveredconditionAddress:value
Function mode CodingchangeAddress:value
Possible change
Boiler circuit, mixer circuit A6:36 *1Extended economy
circuit inactive A6:5to A6:35
Extended economy cir-cuit enabled, i.e. the bur-ner and heating circuitpump will be switched
OFF, and the mixer willbe closed at a variablevalue, which is adjustablebetween 5 and 35 C plus1 C. This value is basedon the adjusted outsidetemperature, comprisingthe actual outside tem-perature and a time con-stant, which takes thecooling down of an aver-age building into consid-eration.
A7:0 *1Without mixer econ-omy function
A7:1 With mixer economyfunction (extended heat-ing circuit pump logic):Heating circuit pump alsoOFF, if the mixer wasclosed for longer than20 minutes. Heatingpump ON,& if the mixer changes to
control modeor
& after cylinder loading(for 20 min.)or
& if there is a risk of frost.
Code 2 (cont.)
56
Coding
5 6 9 2 5 5 0 G B
*1Only for weather-compensated control units.
-
8/10/2019 Vitodens300 WB3A 49 66kW Service
57/132
Coding inthe asdeliveredconditionAddress:value
Function mode CodingchangeAddress:value
Possible change
A8:1 *1Heating circuit M2(mixer circuit) creates ademand for the internalcirculation pump
A8:0 Heating circuit M2 (mixer circuit) creates nodemand for the internalcirculation pump
A9:7 *1With pump idle per-iod: Heating circuitpump OFF in case of set value modification(by changing the oper-ating mode or changingthe set room tempera-ture)
A9:0 *1Without pump idle per-iod
A9:1to A9:15
With pump idle time,adjustable from 1 to 15
b0:0 *1With remote control:Heating mode/reducedmode: Weather-com-pensated *2
b0:1 Heating mode: Weather-compensatedReduced mode: Withroom temperature hook-up
b0:2 Heating mode: With roomtemperature hook-upReduced mode: Weather-compensated
b0:3 Heating mode/reducedmode: With room tem-perature hook-up
b2:8 With remote control unitand for the heating cir-
cuit, heating with roomtemperature hook-upmust be encoded:Room influence factor 8*2
b2:0 Without room influenceb2:1
tob2:64
Room influence factor
adjustable from 1 to 64
Code 2 (cont.)
57
Coding
5 6 9 2 5 5 0 G B
*1Only for weather-compensated control units.*2 Change the coding for the heating circuit without mixer A1 or for mixer circuit M2, if the
remote control unit affects that heating circuit.
-
8/10/2019 Vitodens300 WB3A 49 66kW Service
58/132
Coding inthe asdeliveredconditionAddress:value
Function mode CodingchangeAddress:value
Possible change
b5:0 *1With remote control:Without room tempera-ture-dependent heatingcircuit pump logic func-tion *2
b5:1tob5:8
Heating circuit pumplogic function - see thefollowing table
Parameter address b5:...
With heating circuit pump logic function: Heating cir-cuit pump OFF, if
1: active RT Actual > RT Set + 5 K; passive RT Actual < RT Set + 4 K2: active RT Actual > RT Set + 4 K; passive RT Actual < RT Set + 3 K3: active RT Actual > RT Set + 3 K; passive RT Actual < RT Set + 2 K4: active RT Actual > RT Set + 2 K; passive RT Actual < RT Set + 1 K5: active RT Actual > RT Set + 1 K; passive RT Actual < RT Set6: active RT Actual > RT Set ; passive RT Actual < RT Set - 1 K7: active RT Actual > RT Set - 1 K; passive RT Actual < RT Set - 2 K8: active RT Actual > RT Set - 2 K; passive RT Actual < RT Set - 3 K
Coding inthe asdeliveredconditionAddress:value
Function mode CodingchangeAddress:value
Possible change
Boiler circuit, mixer circuit
C5:20 *1
Electronic limit of theminimum flow tempera-ture: 20 C
C5:1toC5:127
Minimum limit adjustablefrom 1 to 127 C
C6:74 *1Electronic limit of themaximum flow tempera-ture: 74 C
C6:0toC6:127
Maximum limit adjustablefrom 1 to 127 C
d3:14 *1Heating curve slope =1.4
d3:2to
Heating curve slopeadjustable from 0.2 to 3.5
Code 2 (cont.)
58
Coding
5 6 9 2 5 5 0 G B
*1Only for weather-compensated control units.*2 Change the coding for the heating circuit without mixer A1 or for mixer circuit M2, if the
remote control unit affects that heating circuit.
-
8/10/2019 Vitodens300 WB3A 49 66kW Service
59/132
Coding inthe asdeliveredconditionAddress:value
Function mode CodingchangeAddress:value
Possible change
d3:35 (see page 33)d4:0 *3Heating curve level =
0d4: 13tod4:40
Heating curve leveladjustable from 13 to 40(see page 33)
d5:0 *3The external operat-ing mode changeover changes the heatingprogram to "Constantoperation with reducedroom temperature"
d5:1 The external operating
mode changeover changes the heating pro-gram to "Constant opera-tion with standard roomtemperature"
E1:1 *3With remote control:Set day value is adjus-table at the remote con-trol unit from 10 to30 C
E1:0 Set day value adjustablefrom 3 to 23 C
E1:2 Set day value adjustablefrom 17 to 37 C
E2:50 *3With remote controlunit and for the heatingcircuit, heating withroom temperature hook-up must be encoded:No display correction of the actual room tem-perature
E2:0toE2:49
Display correction 5 Kor Display correction 0.1 K
E2:51toE2:99
Display correction +0.1 Kor Display correction +4.9 K
E5:0 *3Without variablespeed circuit pump
E5:1 With variable speed cir-cuit pump; automaticrecognition
E6:65 *3Max. speed of thevariable speed pump =
65 % of max. speed instandard mode
E6:0toE6:100
Maximum speed adjusta-ble from 0 to 100 % of max. speed
E7:30 *3Min. speed of the vari-able speed pump =30 % of max. speed
E7:0toE7:100
Minimum speed adjusta-ble from 0 to 100 % of max. speed
E8:1 *3Min. speed subject tothe setting in codingaddress E9
E8:0 Speed subject to the set-ting in coding address E7
Code 2 (cont.)
59
Coding
5 6 9 2 5 5 0 G B
*3 Only for weather-compensated control units.
-
8/10/2019 Vitodens300 WB3A 49 66kW Service
60/132
Coding inthe asdeliveredconditionAddress:value
Function mode CodingchangeAddress:value
Possible change
E9:45 *1Speed of the variablespeed pump = 45 % of max. speed in reducedmode
E9:0toE9:100
Speed adjustable from 0to 100 % of max. speed
Mixer circuit
F1:0 Screed drying functiondisabled*1
F1:1toF1:5
Screed drying functionadjustable in accordancewith 5 optional tempera-ture time profiles (seepage 104)
NoteObserve the screed dry- ing supplier's instruc- tions.
Observe DIN 4725-2 or local regulations. Thereport to be provided bythe heating contractor must contain the follow-ing heat-up details:& Heat-up data with
respective flow tem-peratures
& Max. flow temperatureachieved
& Operating conditionand outside tempera-ture during handover.
The function continuesafter power failure or after the control unit hasbeen switched OFF. Theheating program rwwill be started, after the
Code 2 (cont.)
60
Coding
5 6 9 2 5 5 0 G B
*1Only for weather-compensated control units.
-
8/10/2019 Vitodens300 WB3A 49 66kW Service
61/132
Coding inthe asdeliveredconditionAddress:value
Function mode CodingchangeAddress:value
Possible change
screed-drying functionhas been completed or if the address is manuallyset to 0.
F1:6
toF1:15
Constant flow tempera-
ture 20 C
F2:8 *2Time limit for partyoperation 8 hours or external operatingmode changeover viapush button *3
F2:0 No time limit for partymode
F2:1toF2:12
Time limit adjustable from1 to 12 hours *3*3
F5:12 Run-on time of the inter-nal circulation pump inheating mode
F5:0 No run-on time of theinternal circulation pump
F5:1toF5:20
Run-on time of the inter-nal circulation pumpadjustable from 1 to20 minutes
F6:0 *4In "DHW only" operat-ing mode, the internalcirculation pump is per-manently OFF
F6:1toF6:24
In "DHW only" operatingmode, the internal circu-lation pump will bestarted 1 to 24 times per day for 10 minutesrespectively
F6:25 In "DHW only" operatingmode, the internal circu-
lation pump is perma-nently ONF7:0 *4In "Standby mode",
the internal circulationpump is permanentlyOFF
F7:0 In "Standby mode", theinternal circulation pumpis permanently OFF
F7:1to
In "Standby mode", theinternal circulation pump
Code 2 (cont.)
61
Coding
5 6 9 2 5 5 0 G B *2 Only for weather-compensated control units.
*3 In heating program rw , the party mode ends automatically when changing over tooperation with standard room temperature.
*4Only for constant temperature control units.
-
8/10/2019 Vitodens300 WB3A 49 66kW Service
62/132
Coding inthe asdeliveredconditionAddress:value
Function mode CodingchangeAddress:value
Possible change
F7:24 will be started 1 to 24times per day for 10 minutes respectively
F7:25 *5In "Standby mode", theinternal circulation pump
is permanently ON
Resetting the coding to the delivered condition
1. Press L and G simultaneouslyfor approx. 2 seconds.
2. Press e .Confirm "Basic setting? Yes"with d .With a or b , you can select"Basic setting? Yes" or "Basic set-ting? No".
Code 2 (cont.)
62
Coding
5 6 9 2 5 5 0 G B
*5 Only for constant temperature control units.
-
8/10/2019 Vitodens300 WB3A 49 66kW Service
63/132
Function Key combination Exit PageTemperatures, boiler cod-ing card and brief scans
Press K and G simulta-neously for approx.2 seconds
Press d 64
Relay test Press K and d simulta-neously for approx.2 seconds
Press d 68
Max. output (heatingmode)
Press K and F simulta-neously for approx.2 seconds
Press d 16
Operating condition Press c Press c 70Maintenance scan c (if "Maintenance"
flashes)Press d
Adjusting the display con-trast
Press d and b simulta-neously; display darkens
Press d and a simulta-neously; display becomeslighter
Fault history Press G and d simulta-neously for approx.2 seconds
User check (in conjunc-tion with LON system)
Press L and d simulta-neously for approx.2 seconds
Emissions test functionS
Press F and E simulta-neously for approx.2 seconds
Press Fand Esimulta-neously
Coding level 1Plain text display
Press K and L simulta-neously for approx.2 seconds
Press Kand Lsimulta-neously
38
Coding level 2Numerical display
Press L and G simulta-neously for approx.2 seconds
Press Land Gsimulta-neously
42
Max. output in heatingmode
Press K and F simulta-neously for approx.2 seconds
Press Kand Fsimulta-neously
16
Service level summary
63
Service scans
5 6 9 2 5 5 0 G B
-
8/10/2019 Vitodens300 WB3A 49 66kW Service
64/132
Weather-compensated control units1. For two heating circuits select
heating circuit:& Press a .
1 r flashes on the display.& Select heating circuit A1 (heating
circuit without mixer):Press d .
& Select heating circuit M2 (heatingcircuit with mixer):
Press a . 2 r flashes on the display. Press d .
2. Press K and G simultaneouslyfor approx. 2 seconds.
3. Select the required scan with aand b .
4. Press d .
The following values can be scanned, subject to the actual equipment level:
& Slope A1 Level A1& Slope M2 Level M2& Adj . outside temp.& Outside temp., actual
The adjusted outside temperature can be reset
to the current outside temperature with e .& Boiler temp., set& Boiler temp., actual& DHW temp., set& DHW temp., actual& DHW outlet temp., actual& DHW outlet temp., set& Flow temperature, set& Flow temperature, actual
Heating circuit with mixer Heating circuit with mixer
& Mixed flow temp., set& Mixed flow temp., actual
Low loss header Low loss header
& Boiler coding card& Brief scan 1
toBrief scan 8
Temperatures, boiler coding card and brief scans
64
Service scans
5 6 9 2 5 5 0 G B
-
8/10/2019 Vitodens300 WB3A 49 66kW Service
65/132
Display screenBrief scan
Boiler codingcard
N/A N/A X X X X
1 Software versionControl unit
VersionBoiler (EEPROM)
VersionBurner control unit(EEPROM)
2 System design 1 to
6indication in accor-dance with the rele-vant design
Display
KM BUSusers
Max. demand temperature
3 N/A SoftwareversionPro-gram-ming unit
SoftwareversionMixer exten-sion kit
SoftwareversionSolar controlunit
SoftwareversionLONsystem
SoftwareversionExt. exten-sion
4 Software versionBurner control unit
TypeBurner control unit
Boiler type
5 0: No ext.demandor oper-atingmodechange-over 1: Ext.demandor oper-atingmodechange-over pre-sent
0: Noext.blocking1: Ext.blockingpresent
N/A External hook-up 0 to 10 V,displayed in %
6 Number of LONusers
SoftwareversionThirdpartycontrol-ler
Max. output,displayed in %
Temperatures, boiler coding card and brief scans (cont.)
65
Service scans
5 6 9 2 5 5 0 G B
-
8/10/2019 Vitodens300 WB3A 49 66kW Service
66/132
Display screenBrief scan
Heating circuit 1(boiler circuit A1)
Heating circuit 2(mixer circuit M2)
7 N/A N/A Remotecontrol0: excl.1: Vito-
trol
2002: Vito-trol300
SoftwareversionRemotecontrol
Remotecontrol0: excl.1: Vito-
trol
2002: Vito-trol300
SoftwareversionRemotecontrol
Internal circulationpump
Heating circuit pumpboiler circuit A1
Heating circuit pumpmixer circuit M2
8 Variablespeedpump0: excl.1: Wilo
2: Grun-dfos
SoftwareversionVariablespeedpump
Variablespeedpump0: excl.1: Wilo
2: Grun-dfos
SoftwareversionVariablespeedpump
Variablespeedpump0: excl.1: Wilo
2: Grun-dfos
SoftwareversionVariablespeedpump
Constant temperature control units
1. Press K and G simultaneouslyfor approx. 2 seconds.Scanning enabled.
2. Select the required scan with aand b .
3. Press d .Scanning is completed.
Temperatures, boiler coding card and brief scans (cont.)
66
Service scans
5 6 9 2 5 5 0 G B
-
8/10/2019 Vitodens300 WB3A 49 66kW Service
67/132
Display screenBrief scan
0 Systemdesign,indicationin accor-dance withthe design
Software versionControl unit
SoftwareversionUser inter-face
1 Software
versionSolar panel
Software version
Burner control unit
Software
versionExt. exten-sion
Software
versionCascademodule
E 0: No ext.demand or operatingmodechange-over 1: Ext.demand or
operatingmodechange-over pre-sent
0: No ext.blocking1: Ext.blockingpresent
External hook-up 0 to 10 V,displayed in %
3 Set boiler temperature at the boiler temperature sensor
A Highest demand temperature4 Burner control unit type Boiler type5 Set cylinder temperature at the cylin-
der temperature sensor (currentvalue)
b Max. heating output in %C Boiler coding card (hexa-decimal)c Version
Equipment (EEPROM)VersionBurner control unit(EEPROM)
Temperatures, boiler coding card and brief scans (cont.)
67
Service scans
5 6 9 2 5 5 0 G B
-
8/10/2019 Vitodens300 WB3A 49 66kW Service
68/132
Display screenBrief scan
d Variablespeedpump0: excl.1: Wilo2: Grund-
fos
SoftwareversionVariablespeed pump
Checking outputs (relay test)
Weather-compensated control units
1. Press K and d simultaneouslyfor approx. 2 seconds.Relay test enabled.
2. Select the relay outputs with aand b .
3. Press d .Relay test is completed.
Subject to the actual equipment level, the following relay outputs can be con-trolled:
Display DescriptionBasic load Burner modulation lower outputFull load Burner modulation upper outputHeating valve Diverter valve set to heating modeValve central pos. Changeover valve in central position (fill)DHW valve Diverter valve set to DHW modeInt. pump ON Int. pump/output 20 ONClose mixer Mixer extensionOpen mixer Mixer extensionHeating circ. pump M2 ON Mixer extensionOutput int. Internal extensionHeating circ. pump A1 ON Ext. extensionCylinder loading pump ON Ext. extensionDHW circ. pump ON Ext. extensionCentral fault display ON Ext. extension
Temperatures, boiler coding card and brief scans (cont.)
68
Service scans
5 6 9 2 5 5 0 G B
-
8/10/2019 Vitodens300 WB3A 49 66kW Service
69/132
Display DescriptionSolar pump ON Vitosolic
Constant temperature control units
1. Press K and d simultaneouslyfor approx. 2 seconds.Relay test enabled.
2. Select the relay outputs with aand b .
3. Press d .Relay test enabled.
Subject to the actual equipment level, the following relay outputs can be con-trolled:
Display Description1 Burner modulation lower output2 Burner modulation upper output3 Diverter valve set to heating mode4 Valve in central position5 Valve set to DHW mode6 Internal pump/output 20 ON10 Output sK internal extension11 Heating circuit pump A1 external extension12 Cylinder loading pump external extension13 DHW circulation pump external extension14 Central fault external extension
Checking outputs (relay test) (cont.)
69
Service scans
5 6 9 2 5 5 0 G B
-
8/10/2019 Vitodens300 WB3A 49 66kW Service
70/132
Weather-compensated control units1. Select a heating circuit:
& Press a .1 r flashes on the display.
& Select heating circuit A1 (heatingcircuit without mixer):Press d .
& Select heating circuit M2 (heatingcircuit with mixer): Press a . 2 r flashes on the display. Press d .
2. Press c .
3. Select the required operating con-dition scan with a or b .
4. Press c .
Heating circuits A1 and M2Operating condition display(subject to system equip-ment level)
Description
User no. Encoded user no. in the LON systemHoliday program Displayed only if a holiday program has been
set upDate of departure DateDate of return DateOutside temperature, ... C Actual valueBoiler temperature, ... C Actual valueFlow temperature, ... C Actual value (only for heating circuit M2)Standardroom temperature, ... C
Set value
Room temperature, . .. C Actual valueExt. set room temp., ... C If external hook-upDHW temperature, ... C Actual DHW temperature
Solar DHW temp. , . .. C Actual valueCollector temperature, ... C Actual valueMixed flow temp., ... C Actual value, only with low loss header Burner, ...h *1 Hours runBurner starts, ... *1*1 Actual valueSolar energy Displayed in kW/hTimeDate
Scanning operating conditions and sensors
70
Service scans
5 6 9 2 5 5 0 G B
*1Reset hours run and burner starts after maintenance has been completed. You can reset the hours run to 0 by pressing e .
-
8/10/2019 Vitodens300 WB3A 49 66kW Service
71/132
Operating condition display(subject to system equip-ment level)
Description
Burner OFF or ONInt. pump OFF or ON Output 20Int. output OFF or ON Internal extens ionHeating pump OFF or ON Ext
top related