  • AnswerbyLittlewats

    Thiscanbedone,butisusuallynotdonebecauseameteringCTismadetobeveryaccurateatexpectedloadcurrentlevels.AprotectionCTismadetobeaccurateatfaultcurrentlevels(whichisoftensignificantlyaboveloadcurrent).IftheCTistoosmall,andhastoosmallofaratio,theCTwilllikelysaturate,whichwillskewtheresultstheprotectivedeviceexpectstoget.

    Anexample:ameteringCTmayhavearatioof100:5(madefor100Aloadcurrent,whichwillproduce5ampssecondarycurrent).Faultcurrentlevelsmaybe~10,000A.You'dexpectthesecondaryoutputofaperfectlylinearCTtobe500A.OnewayresistanceofthecableconnectingtheprotectivedevicetotheCTmaybeontheorderof.52ohms.IgnoringtheresistanceoftheCTandconnecteddevices,secondaryvoltageswouldreach2501,000voltsforaphasefault,and5002,000voltsforagroundfault.ThebiggestCTsmayberatedfor800voltsoutputbelowthekneepoint,sothis100:5CTwouldclearlysaturate.Therealoutputcurrentwouldlikelybeontheorderof150Aatthemost.

    ...AndtheaboveisignoringanyDCoffset,whichwouldcausetheCTtosaturateatunpredictableACcurrentlevels.EDIT