am_ss03_e2_p1 zxa10-msan cabinet & power module introduction(malaysia) v1.1 19p
DESCRIPTION
asdTRANSCRIPT
A10&DSL D&T GroupA10&DSL D&T Group
AM_SS03_E2_P1AM_SS03_E2_P1
ZXA10-MSAN Cabinet & Power Module Introduction
ZXA10-MSAN Cabinet & Power Module Introduction
V1.1V1.1
2
Course OutlineCourse Outline
OUT60 Rack Introduction
ZXDU45 Power Module Introduction
3
Rectifier(Height 3U)
AC&DC
Grounding box
U300 control shelf(Height 9U)
S200 shelf(Height 2U)
100AH
L0
U300 subscriber shelf(Height 9U)
L1
U300 subscriber shelf(Height 9U)
L2
Dis
tribu
tion
area
Wire routing frame(Height 1U)1# Fan tray(Height 1U) accumulator
wind outlet layer(Height 2U)
wind outlet layer(Height 1U)
wind outlet layer(Height 2U)
wind outlet layer(Height 1U)
accumulator100AH
accumulator100AH 100AH
accumulator
Wire routing frame(Height 1U) Wire routing frame(Height 1U)2# Fan tray(Height 1U)
wind outlet layer(Height 2U)
wind outlet layer(Height 2U)
Power distribution box
Overall compositionOverall composition
4
OUT60 SpecificationOUT60 SpecificationItems Description
Cabinet 620 kg
Dimensions 1600 mm × 1500 mm × 780 mm (height ×width × depth)
Operating Voltage 220 ± 30% V AC 50 Hz240 ± 30% V AC 60 Hz
Ambient Temperature –35˚C to 40˚C
Power Consumption 2000 w (without heater module)4300 w (with heater module)
Relative Humidity 10% to 100%
Grounding Resistance ≤10 ohm
Storage Battery 12 V/100 -Ah
Environment Conditions The cabinet is used outside where electromagnetism is weak
Storage Battery Four 12 V/100 Ah storage batteries
Rainproof and Dustproof MeasuresMeet IEC IP5.5 and adopt special process for major components to increase corrosion-proof capability
5
OUT60 module configurationOUT60 module configurationThe following are OUT60 module configuration:
Power supply module
Control and processing module
Test module
Subscriber module
Transmission module
Monitoring module
6
Power Supply ModulePower Supply ModuleThis power supply module provides the following functions:
It filters power and feeds 220 V AC to power rectifier and pass it to power distribution box and provides grounding to prevent equipment from lightning.
Four batteries provide -48 V DC connection. Batteries are used as a backup power.
POWER K card provides secondary power +5 V,-48 V DC and ringing current -75 V AC.
7
Control And Process ModuleControl And Process ModuleThe Control And Process Module supply module provides the
following functions:
It implements service control
It supports multiple accesses such as narrowband voices, data at various rates, DSL, and LAN
8
Test ModuleTest ModuleThe Test Module supply module provides the following functions:
Measures insulation resistance, AC/DC voltage, inter-line capacitance
Detects signal tone, tests equipment receiving pulse number, DTMF number receiving functions and tests dialing tone.
Measures ringing output voltage and frequency.
9
Subscriber ModuleSubscriber ModuleBuilt-in MDF wiring module
Internal line modules support 1152 loops.
External line modules support 1400 loops.
10
Transmission ModuleTransmission ModuleBuilt-in MSTP Products S200
ZXA10-S200 is positioned at the MAN access layer, and supports L2 Ethernet convergence between multiple NEsand small-capacity TDM service.
ZXA10-S200 is capable of access, transparent transmission and convergence of the TDM service, Ethernet service and ATM service
11
Monitoring ModuleMonitoring Module
Monitoring equipment temperature
Monitoring humidity
Smoke monitoring
Alarm indications
Flood
Secondary Power
12
IM A E H D B
RSTRST
ALM
HOOK
RUN
A LCIS T 1A IC S
RSTRST
ALM
HOOK
RUN
A LC
RSTRST
ALM
HOOK
RUN
A LC
RSTRST
ALM
HOOK
RUN
A LC
RST
U8
U5
U7
U6
U4
U3
ALM
U2
U1
RUN
D LC A
RST
U8
U5
U7
U6
U4
U3
ALM
U2
U1
RUN
D LC A IC S A D LA D L
RSTRST
ALM
HOOK
RUN
A LC
3
4
5
P E B
1
2
2
3
IE B A
1
3
IE B B
1
2
S E B IS E BE PE B
3
4
5
P E B
1
2
S E B S E B SE B S E B S E B S E B SE BSE BSE B
OUT60 Shelf LayoutOUT60 Shelf Layout
13
Subscriber cableSubscriber cable
68
34
67
33
3736
32
C
35
1
End A End B
Di rect i on C
14
Cascading cableCascading cable
C
Pos. 50 Pos. 1
Pos. 1 Pos. 50
D
End AEnd B1
End B2
Di rect i on C Di rect i on D
15
Monitoring CableMonitoring Cable
B5B6B7B8B9B10B11B12
B15B16
B25
B20B21
B23B24
B22
CB14
B17
B3
B13
B19
B18
B4
B1
B2
End A
End B
Di r ect i on C
16
ZXDU45, ZXDU75---Built-in Power System
ZXDU45, ZXDU75---Built-in Power System
17
ZXDU45---Built-in Power System
ZXDU45---Built-in Power System
ID Indicator Status Meaning
PWR On The AC input is normal.
RUN Flashing The program is running normally.
COMM On The system is communicating with the background computer.
FAU On The equipment fails.
18
ZXDU45---Built-in Power System
ZXDU45---Built-in Power System
AC input (single-phase,
3-wire)
Anti-lightning
power distribution
unit
Switched rectifier (3 at
the most)
Load I
Load II
Battery
Monitoring unit
Near-end monitoring
RS232RS232
MODEM MODEM Remote monitoring
Telephoneline
univ.zte.com.cnuniv.zte.com.cn