an-najah national university civil engineering department design of water distribution network
DESCRIPTION
An-Najah National University Civil Engineering Department Design Of Water Distribution Network For Noorshams. Submitted by : Hamza Raid Tayyah Mohammad Rasheed Ghaneem Sami Mazen Ismail Supervisor : Eng. Lubna Haj Hammad 2012. The Objective of the Project:. - PowerPoint PPT PresentationTRANSCRIPT
An-Najah National University
Civil Engineering Department
Design Of Water Distribution Network For Noorshams.
Submitted by : Hamza Raid Tayyah
Mohammad Rasheed GhaneemSami Mazen Ismail
Supervisor : Eng. Lubna Haj Hammad
2012
The Objective of the Project:
1- The main objective of this project is to design the water distribution network for Noorshams with the aid of WATERCAD.
2- Solve the problem of quality of water.
Study Area
- Noorshams is located to the east of the city of Tulkarem.
- Noorshams rises about 150 m above mean sea level.
- The area of Noorshams is about 250 dunums.
- Noorshams has a population of about 7063 inhabitants.
Questionnaire Analysis:
WaterCad
WaterCAD is a powerful yet easy to use program that helps engineers design and analyze complex, pressurized piping systems.
Advantages :
1- WaterCAD will help you to analyze multiple time-variable demands at any junction node.
2- WaterCAD provides solutions to model flow valves, pressure reducing valves, pressure sustaining valves, pressure breaking valves and throttle control valves.
Equation Used in WaterCAD
- Hazen-Williams.
Hl = 162.5(Q/C)1.852D-4.87L
- Darcy – weisbach.
Hf = F(L/D)(V2/2g)
- Manning.
Hf = F(L/D)(V2/2g)
Population :
The population of the Noorshams by the Central Statistics in year 2012 is estimated 7063.
To calculate the growth rate through the equation:--
Pf = 10095
Pp = 7063
i= 1.9%, 1.2%, 1%
n = 10, 10, 5
From these information the population in 2037 is estimated 10095.
Demand:
- The consumption in year 2012 from quastionnaire 90 (L/C.d).
- We increased the consumption in first ten years 4 (L/C.d), and 2 (L/C,d) for the second ten years, 1 (L/C,d) for the last years.
Design Criteria:
- Head pressure should be not more than 100 m, and not less than 10m.
- Maximum velocity should not be greater than 3m/sec, and minimum velocity should not be less than 0.1m/sec.
The Results:The results is acceptable the design criteria, and these result as the following:
-The Pressure:
All the pressure in the pipes is acceptable which range between (1 bar 5.5 bar).
-The velocity:
Most of the velocities are within range, but some nodes in the end of the network are low(0.01m/s), but in general the velocity is acceptable.