analog/addressable fire alarm panels...oct 21, 2005  · lt-959 rev. 7 march 2019 fx-350 series. 3...

70
Installation and Operation Manual Analog/Addressable Fire Alarm Panels LT-959 Rev. 7 March 2019 FX-350 Series

Upload: others

Post on 20-Feb-2021

1 views

Category:

Documents


0 download

TRANSCRIPT

  • Installation and Operation Manual

    Analog/Addressable Fire Alarm Panels

    LT-959 Rev. 7March 2019

    FX-350 Series

  • Table of Contents

    1.0 Industry Canada and FCC Notice 8

    1.1 Notice for all FX-350 Series Built-In UDACTs Sold in Canada ...................................... 8

    2.0 Introduction 10

    2.1 Features ......................................................................................................................... 10

    3.0 Conventions 12

    3.1 Circuits .......................................................................................................................... 123.2 Zone/Group .................................................................................................................... 123.3 Display Points ............................................................................................................... 123.4 Wiring Styles ................................................................................................................. 12

    4.0 System Components 13

    4.1 Panel Models ................................................................................................................. 134.2 Output Class A converter: four circuits .......................................................................... 154.3 Polarity reversal/city tie .................................................................................................. 154.4 Remote Annunciator ...................................................................................................... 154.5 Smart Relay Module ...................................................................................................... 164.6 RAM-216 Ancillary Annunciator ..................................................................................... 164.7 Panel Components and System Accessories ................................................................ 174.8 Analog/Addressable Devices ......................................................................................... 18

    5.0 Mechanical Installation 19

    5.1 Installing the Enclosures ................................................................................................ 195.2 BBX-1024DS and BBX-1024DSR Mechanical Installation ............................................ 22

    6.0 Installing Adder Modules 23

    6.1 Cable and Jumper Connections for Main Board and Adder Modules ........................... 246.2 Connectors and Jumpers on the Main Fire Alarm Board ............................................... 266.3 OCAC-304 Output Class A Converter Adder Module ................................................... 266.4 Polarity Reversal and City Tie Module (Model PR-300) ............................................... 276.5 RAX-332 Display Adder Module .................................................................................... 27

    3

  • Table of Contents

    7.0 Circuits and Devices 28

    7.1 Addressable/Analog Devices ......................................................................................... 287.2 Analog Devices .............................................................................................................. 297.3 Contact Inputs ................................................................................................................ 297.4 Contact Outputs ............................................................................................................. 29

    8.0 Field Wiring 30

    8.1 Main Fire Alarm Board Field Wiring ............................................................................... 308.2 Loop Isolators ................................................................................................................. 318.3 Loop Operation .............................................................................................................. 318.4 Indicating (Powered Output) Circuits ............................................................................. 328.5 Indicating Circuit Wiring ................................................................................................. 328.6 Dialer Wiring ................................................................................................................... 348.7 Polarity Reversal and City Tie Module (PR-300) Wiring ............................................... 368.8 Auxiliary Power Supplies ................................................................................................ 378.9 Power Supply Connections ............................................................................................ 388.10 Connecting to a 3G4010 Interface Device for Canada .................................................. 398.11 Connecting to a 3G4010CF Interface Device outside Canada ...................................... 40

    9.0 System Checkout 41

    9.1 Before turning the power “ON” ....................................................................................... 419.2 Power-up procedure ....................................................................................................... 41

    10.0 Troubleshooting 42

    11.0 Indicators, Controls and Operations 43

    11.1 Common Indicators ........................................................................................................ 4411.2 Common Controls .......................................................................................................... 4611.3 Single Stage Operation .................................................................................................. 4711.4 Two-Stage Operation ..................................................................................................... 4811.5 Positive Alarm Sequence ............................................................................................... 4911.6 Enabling or Disabling the Positive Alarm Sequence ...................................................... 5011.7 Input Types .................................................................................................................... 5011.8 Output Types .................................................................................................................. 5311.9 Evacuation Codes .......................................................................................................... 5311.10 Initial Power-up Sequence ............................................................................................. 54

    12.0 Remote Annunciator Operation 57

    12.1 Conventional Annunciators (RA-1000 Series) ............................................................... 57

    4

  • Table of Contents

    12.2 Supervision .................................................................................................................... 5712.3 Shared Display Annunciator (RAM-300LCD) ................................................................. 5712.4 Supervision .................................................................................................................... 57

    13.0 Dialer Operation 58

    13.1 Event Reporting ............................................................................................................. 5813.2 Telephone line supervision ............................................................................................ 58

    14.0 Appendix A: Compatible Receivers 59

    15.0 Appendix B: Reporting 60

    16.0 Appendix C: Specifications 62

    16.1 FX-350 Series Specifications ......................................................................................... 6216.2 FX-350 System Modules and Annunciators ................................................................... 63

    17.0 Appendix D: Power Supply and Battery Calculations 64

    18.0 Warranty and Warning Information 66

    5

  • 6

    List of Figures

    Figure 1 Wallbox Dimensions / Mounting the FX-350 – Surface .................................................. 19Figure 2 Mounting the FX-350 - Flush ......................................................................................... 20Figure 3 Flush Trim Detail ............................................................................................................ 20Figure 4 Wallbox Dimensions / Mounting the FX-351/FX-353 – Surface /Flush ......................... 21Figure 5 BBX-1024DS and BBX-1024DSR Installation Instructions and Dimensions ................. 22Figure 6 Installation of Adder Modules ........................................................................................ 23Figure 7 Main Fire Alarm Board Cable Connectors and Jumper Locations ................................. 24Figure 8 Main Board (3 loop model) Cable Connectors and Jumper Locations ........................... 25Figure 9 OCAC-304 Output Class A Converter Adder Modules .................................................. 26Figure 10 Polarity Reversal and City Tie Module .......................................................................... 27Figure 11 Addressable Loop Wiring - Class B or Style 4 ............................................................... 30Figure 12 Addressable Loop Wiring - Class A or Style 6 ............................................................... 31Figure 13 Indicating Circuit – Class B or Style Y Wiring ................................................................ 34Figure 14 Indicating Circuit –Class A or Style Z Wiring .................................................................. 34Figure 15 Dialer Wiring ................................................................................................................... 35Figure 16 Polarity Reversal and City Tie Module Terminal Connection ........................................ 36Figure 17 Supervision Of Auxiliary Supplies .................................................................................. 37Figure 18 Main Power Supply Connections ................................................................................... 38Figure 19 Connecting an FX-350 FACP to a 3G4010 Interface Device ......................................... 39Figure 20 Connecting an FACP to a 3G4010CF Interface Device outside Canada ....................... 40Figure 21 LCD Display, LED indicators and control buttons ......................................................... 43Figure 22 Evacuation and Alert Codes ........................................................................................... 54

  • 7

    List of Tables

    Table 1 FX-350 Series Comparison Chart .................................................................................. 14Table 2 Settings permitted in CAN/ULCS527 ............................................................................. 30Table 3 Loop Wiring Table .......................................................................................................... 31Table 4 Maximum Wiring Distances ........................................................................................... 32Table 5 Input Types .................................................................................................................... 50Table 6 Output Types ................................................................................................................. 53Table 7 Ademco Contact-ID - FX-350 Series Event Codes ........................................................ 60Table 8 Security Industries Association SIA-DCS - FX-350 Series Event Codes ....................... 61Table 9 FX-350 Series Specifications ......................................................................................... 62Table 10 FX-350 System Modules and Annunciators ................................................................... 63Table 11 FX-350 Batteries ............................................................................................................ 65

  • 1.0 Industry Canada and FCC Notice1.1 Notice for all FX-350 Series Built-In UDACTs Sold in Canada

    Mircom's FX-350 SERIES BUILT-IN UDACT Communicator described in this manual is listedby Underwriters Laboratories Canada (ULC) for use in slave application in conjunction with aListed Fire Alarm Control Panel under Standard ULC-S527-11 (Standard for Control Units forFire Alarm Systems) and CAN/ULC-S561-13 (Standard for Installation and Services for FireSignal Receiving Centres and Systems). These Communicators should be installed inaccordance with this manual; the Canadian / Provincial / Local Electrical Code; and/or thelocal Authority Having Jurisdiction (AHJ).

    1.1.1 Industry Canada NoticeRepairs to certified equipment should be made by an authorized Canadian maintenancefacility designated by the supplier. Any repairs or alteration made by the user to thisequipment, or equipment malfunctions, may give the telecommunications company cause torequest the user to disconnect the equipment. Users should ensure for their own protectionthat the Earth Ground connections of the power utility, telephone lines and internal metallicwater pipe system, if present, are connected together. This is necessary both for properoperation and for protection.

    1.1.2 Notice for all FX-350 Series Built-in UDACTs Sold in the U.S.A.

    Mircom's FX-350 SERIES BUILT-IN UDACT Digital Communicator described in this manualis listed by Underwriters Laboratories Inc. (ULI) for use in slave application in conjunction witha Listed Fire Alarm Control Panel under Standard 864 (Control Units for Fire ProtectiveSignalling Systems). These Communicators comply with the National Fire ProtectionAssociation (NFPA) performance requirements for UDACTs and should be installed inaccordance with NFPA 72 Chapter 4 (Supervising Station Fire Alarm System). TheseCommunicators should be installed in accordance with this manual; the National ElectricalCode (NFPA 70); and/or the local Authority Having Jurisdiction (AHJ).

    1.1.3 FCC NoticeThis equipment complies with Part 68 of the FCC rules and the requirements adopted by theACTA. On the telco transformer of this equipment is a label that contains, among otherinformation, a product identifier in the format US:1M8AL02BFX350. If requested, this number

    Attention: Users should not attempt to make such connections themselves, butshould contact the appropriate electric inspection authority, orelectrician, as appropriate

    Notes: The Ringer Equivalence Number (REN) assigned to each terminal deviceprovides an indication of the maximum number of terminals allowed to beconnected to a telephone interface. The termination on an interface may consistof any combination of devices subject only to the requirement that the sum of theRinger Equivalence Numbers of all the devices does not exceed 5.

    The Label Identification Number for this product is US:1M8AL02BFX350. The02B represents the REN without a decimal point (e.g., 02B is a REN of 0.2B). Forearlier products, the REN is separately shown on the label.

    !

    i

    8

  • Industry Canada and FCC Notice

    must be provided to the telephone company. This equipment is capable of seizing the line.This capability is provided in the hardware.

    Type of Service: The Communicator is designed to be used on standard device telephonelines. It connects to the telephone line by means of a standard jack called the USOC RJ-11C(or USOC FJ45S). Connection to telephone company provided coin service (central officeimplemented systems) is prohibited. Connection to party lines service is subject to state tariffs.

    Telephone Company Procedures: The goal of the telephone company is to provide you withthe best service it can. In order to do this, it may occasionally be necessary for them to makechanges in their equipment, operations or procedures. If these changes might affect yourservice or the operation of your equipment, the telephone company will give you notice, inwriting, to allow you to make any changes necessary to maintain uninterrupted service.

    In certain circumstances, it may be necessary for the telephone company to requestinformation from you concerning the equipment which you have connected to your telephoneline. Upon request of the telephone company, provide the FCC registration number and theringer equivalence number (REN); both of these items are listed on the equipment label. Thesum of all of the REN’s on your telephone lines should be less than five in order to assureproper service from the telephone company. In some cases, a sum of five may not be usableon a given line.

    If Problems Arise: If any of your telephone equipment is not operating properly, you shouldimmediately remove it from your telephone line, as it may cause harm to the telephonenetwork. If the telephone company notes a problem, they may temporarily discontinue service.When practical, they will notify you in advance of this disconnection. If advance notice is notfeasible, you will be notified as soon as possible. When you are notified, you will be given theopportunity to correct the problem and informed of your right to file a complaint with the FCC.Contact your telephone company if you have any questions about your phone line. In theevent repairs are ever needed on the Communicator, they should be performed by MircomTechnologies Ltd. or an authorized representative of Mircom Technologies Ltd. For informationcontact Mircom Technologies Ltd. at the address and phone numbers shown on the back pageof this document.

    9

  • 2.0 IntroductionMircom’s FX-350 Series Analog/Addressable Fire Alarm Control Panel provides a loop for60,126 or three loops for 378 input and output devices, four supervised Class B or A (Style Yor Z) indicating circuits, a full range of auxiliary power supplies, and extensive common controlfeatures via its integrated LCD display and push button console. Many of its features are fullyconfigurable utilizing the built-in configuration capability via the front panel display andswitches. The panels are available with or without an optional, integrated dialer/modem(except the FX-353 version which always includes the dialer/modem), and is available (FX-351 and FX-353 - in a larger enclosure) with an internal LED display for up to 64 points (32standard). Optional modules include Polarity Reversal and City Tie, RAX-332 LED DisplayAdder, and Class A Converter for indicating circuits. Semi-flush or surface mountableenclosures can be used for retrofits and on new installations. This manual covers the followingpanels:

    2.1 Features

    • The FX-350 panels support a loop of 60 or 126 analog devices and up to 3 loops of 378 analog devices, including thermal, ion, photo detectors, and contact input and output devices. Drift compensation and Auto Test features are provided for analog devices.

    • Four Power Limited Class B (Style Y) indicating circuits. Each indicating circuit may be configured as Class A (Style Z) using an output Class A converter adder module. Each indicating circuit may be configured as silenceable signal, non-silenceable signal, silenceable strobes, non-silenceable strobes, or relay output. The audible signal may be Steady, Temporal Code, California Code, or March Time. The system provides the necessary protocols to sync strobes from major manufacturers.

    • Two-stage, alarm verification, and waterflow retard operations available.• Configurable Signal Silence Inhibit, Auto Signal Silence, Two-Stage Operation, and

    One-Man Walk Test. For UL installations, disable Auto Signal Silence.• Subsequent Alarm, Supervisory, and Trouble operation.• provides a regulated, supervised 21.1VDC auxiliary power supply @ 500mA max.;

    unfiltered, unsupervised 24V FWR power supply @ 1.7 A max and a resettable auxiliary power supply @ 300mA max.

    Note: Installation of the FX-350 Series Fire Alarm Control panel should be in accordance with Canadian Electrical Code Part 1, ULC-S524 installation of Fire Alarm System, National Electrical Code NFPA 70 and NFPA 72. Final acceptance subject to the Local Authority Having Jurisdiction (AHJ).

    FX-350-60-DR 60 pt addressable FACP (w/ dialer)FX-351-LW 126 pt addressable FACP (w/ one 32 point LED display)FX-351-LDW 126 pt addressable FACP (w/ dialer and one 32 point LED display)FX-351-LDR 126 pt addressable FACP (w/ dialer)FX-353-LW 378 pt addressable FACP without LED strip (w/ dual loop adder and one

    32 point LED display)

    FX-353-LDR 378 pt addressable FACP without LED strip (w/ dialer and dual loop adder)FX-350-60D 60 pt addressable FACP (w/ dialer)FX-351-LD 126 pt addressable FACP (w/ dialer)

    i

    10

  • Introduction

    • Relay Contacts for Common Alarm, Common Supervisory and Common Trouble all non-disconnectable and Auxiliary Alarm Relay (disconnectable).

    • Output for remote trouble indicator and Buzzer (RTI).• RS-485 Interface for RAM-300LCD Annunciators, RA-1000 Series Remote

    Annunciators and SRM-312 Smart Relay Modules (max total of 7 remote annunciators). • Optional Module for City Tie and Polarity Reversal Signaling. • Extensive transient protection • With or without built-in UDACT (Digital Alarm Communicator Transmitter) • Extensive and easy configuration of the panel via the integrated LCD display and

    keypad• Remote dial up (with built-in UDACT version) for event log checking and/or configuration

    changing

    11

  • 3.0 Conventions 3.1 Circuits

    Refers to a physical electrical interface for the analog loop, indicating signals or relays, andcommon alarm, supervisory, and trouble relay outputs.

    3.2 Zone/Group

    Is a logical concept for a Fire Alarm Protected Area, and will consist of at least one Circuit.Groups are used extensively in the FX-350 to facilitate annunciation of multiple input andoutput points on the 32 (up to 64) LED display and to facilitate bypassing of inputs andoutputs.

    3.3 Display Points

    The FX-350 provides an LCD display to annunciate the status of the system and connecteddevices. The FX-351 and FX-353 also provides up to 64 LED display points on the panel frontin addition to the LCD display. Display points may be assigned to LEDs during configuration togroups of inputs or outputs. There are two LEDs for every display point: one single color(amber) and one dual color (red/amber).

    3.4 Wiring Styles

    The analog loop can be connected in Class B (Style Y) or Class A (Style D) configurations.Changing the indicating circuits to Class A requires an OCAC-304 adder board which willconvert four indicating zones from Class B (Style Y) circuits to Class A (Style Z). This is donewithout reducing the number of circuits.

    Note: The Model FX-350-60-R and FX-350-60DR panels DO NOT recognize any devices with addresses higher than 60.i

    12

  • 4.0 System Components 4.1 Panel Models

    All FX-350 Series Panels have the following features:

    • Multi-zone fire alarm control panel with 2 x 20 LCD display.• Style Y or Style D analog loop(s).• Four Power Limited Class B (Style Y) indicating circuits (max 1.7 Amps each - 5 Amps

    total).• Dedicated common alarm, supervisory, trouble, and auxiliary alarm relays.• Additional RAX-332 Display Adders can be added to provide 64 annunciation points per

    added.• An optional OCAC-304 Class A converter module may be used to convert the indicating

    circuits to Class A (Style Z).• Additional outputs include connections for a RTI remote trouble indicator, PR-300

    Reverse Polarity Module, an RS-485 bus for connection of up to seven RAM-300LCDs,SRM-312s and RA-1000 Series annunciators.

    • Auxiliary power is available in the form of 24V FWR unfiltered and unsupervised, 24VDCfiltered and regulated, and resettable auxiliary power supply.

    FX-350-60-DRUL/

    ULC only if configured as one input zone

    FX-351-LDRFX-353-LDR

    UL/ULC

    FX-351-LWFX-351-LDWFX-353-LW

    UL/ULC

    FX-350-60DFX-351-LD

    UL/ULC

    13

  • System Components

    al p er

    n)

    See Table 1 for the specifics of each panel.

    Some models may not be available in all markets. Verify with your local distributor.

    Table 1 FX-350 Series Comparison Chart

    Model # of devices # of analog loops

    2 line UDACT Digital

    Communicator(y/n)

    Door

    Color

    # of 32 point LED Displays

    Max # of LED

    Displays

    DuLooAdd(y/

    FX-350-60-DR 60 1 y red n/a n/a n

    FX-351-LW 126 1 n white 1 2 n

    FX-351-LDW 126 1 y white 1 2 n

    FX-351-LDR 126 1 y red 0 2 n

    FX-353-LW 378 3 n white 1 2 y

    FX-353-LDR 378 3 y red 0 2 y

    FX-350-60D 60 1 y purchased separatelypurchased separately 2 n

    FX-351-LD 126 1 y purchased separatelypurchased separately 2 n

    14

  • System Components

    4.2 Output Class A converter: four circuits

    4.3 Polarity reversal/city tie

    4.4 Remote Annunciator

    Model Description

    OCAC-304 Output Class A converter module (fourcircuits)

    Model Description

    PR-300 Polarity Reversal and/or City Tie Module

    Model Description

    RAM-300LCDR Remote Annunciator module, LCD display,white painted box

    RAM-300LCDR Remote Annunciator Module, LCD display,red painted box

    - SI

    G1

    OU

    T+-

    SIG

    2 O

    UT+

    - SI

    G1

    RET

    +-

    SIG

    2 R

    ET+

    BLK

    RED

    BLK

    RED

    - SI

    G3

    OU

    T+-

    SIG

    4 O

    UT+

    - SI

    G3

    RET

    +-

    SIG

    4 R

    ET+

    BLK

    RED

    BLK

    RED

    POLAR

    ITYREVER

    SALALAR

    M

    POLAR

    ITYREVER

    SALSU

    PV

    CITYTIE

    + | -+ | -

    + | -

    JW4

    P1 P2

    Mounting hole for#6-32 screws

    Mounting hole for#6-32 screws

    FA-300 SERIESRemote Annunciator

    SYSTEMRESET

    SIGNALSILENCE

    FIREDRILL

    LAMPTEST

    1

    4

    7

    *

    2

    5

    8

    0

    3

    6

    9

    #

    ENTER

    MENU

    CANCEL

    INFO

    ABC DEF

    GHI JKL MNO

    PRS TUV WXY

    QZ

    A.C. ON ALARM SUPV TRBL CPU FAIL

    �� ��� ��� ��� �� �

    � ��� ��� ��� ��� ��� ���

    Advanced Life Safety Solutions

    BUZZERSILENCE

    15

  • System Components

    4.5 Smart Relay Module

    4.6 RAM-216 Ancillary Annunciator

    Model Description

    SRM-312W Smart Relay Module (12 relays) with whiteenclosure

    SRM-312R Smart Relay Module (12 relays) with redenclosure

    Model Description

    RAM-216 16 Zone ancillary annunciator

    REMOTE RELAY

    Advanced Life Safety Solutions

    FA-300 SERIES

    A.C.ON

    COMMONTROUBLE

    SIGNALSILEBCE

    BUZZERSILENCE

    SIGNALSILENCE

    LAMPTEST

    SYSTEMRESET

    SWITCHENABLE

    FIRE ALARMANNUNCIATOR

    16

  • System Components

    4.7 Panel Components and System Accessories

    MODEL NO. DESCRIPTIONS

    ALC-252 252 Point Dual Loop Addressable Adder

    RAX-332 32 Zone Internal Display Adder (for FX-351 and FX-353 only)

    RAM-208/R 8 LED Remote Annunciator

    RAM-1016/TZ Remote Annunciator with 16 bi-colored (red and yellow) LEDs. TZ version has 32 yellow LEDs for trouble indication.

    RAM-1032/TZ Remote Annunciator with 32 bi-colored (red and yellow) LEDs. TZ version has 32 yellow LEDs for trouble indication.

    RAX-1048/TZ Remote Annunciator with 48 bi-colored (red and yellow) LEDs. TZ version has 48 yellow LEDs for trouble indication.

    MGD-32 Graphic Annunciator

    AGD-048 Graphic Annunciator Adder Driver Board

    RTI-1 Remote Trouble Indicator, Buzzer and LED

    FA-300-TRB Trim Ring For Small Enclosure (Black)

    FA-UNIV-TRB Universal Trim Ring For Big Enclosure (Black)

    BB-1001(R) Enclosure for one annunciator, white. R version is red.

    BB-1002(R) Enclosure for two annunciators, white. R version is red.

    BB-1003(R) Enclosure for three annunciators, white. R version is red.

    BB-1008(R) Enclosure for eight annunciators, white. R version is red.

    BB-1012(R) Enclosure for twelve annunciators, white. R version is red.

    MP-300 End-of-line resistor plate, 3.9K ohm

    BC-160 External Battery Cabinet

    17

  • System Components

    18

    4.8 Analog/Addressable DevicesDescription Mircom Model

    Ionization Smoke Detector (U.S. Model Only) MIX-3000

    Photoelectric Smoke Detector MIX-3100

    * Multi-sensor (photoelectric with supplemental rate-of-rise heat sensor) MIX-3200Heat Detector MIX-3300

    Bases Mircom Model

    4 inch Standard Base MIX-2000

    6 inch E-Z Fit Base MIX-2001

    6 inch Base with Relay MIX-2001R

    6 inch Base with Sounder MIX-2001H

    6 inch Base with Temporal Tone Sounder MIX-2001HT

    Ancillary Modules Mircom Model

    Priority Monitor Module MIX-100P

    Mini Priority Monitor Module MIX-101P

    Single Relay Output Module (1 Form C Contacts, 2 Gang Mount) 55000-820

    Supervised Control Module MIX-100S

    Isolator c/w Mounting Base

    MIX-100X (Kit)

    100XH (Isolator)

    100XB (Base)

    Addressable Duct Detectors Mircom Model

    Ionization Duct Smoke Detector (UL Listed) MIX-DH3000

    Photoelectric Duct Smoke Detector (UL Listed) MIX-DH3100

    Ionization Duct Smoke Detector with relay (UL Listed) MIX-DH3000R

    Photoelectric Duct Smoke Detector with relay (UL Listed) MIX-DH-3100R

    Addressable Pull Stations Mircom Model

    Addressable Single Stage Pull Station MS-401ID(U)

    Addressable Two Stage Pull Station (Canadian Model Only) MS-402ID

    Addressable Single Stage Single Action Pull Station MS-701ID(U)

    Addressable Two Stage Single Action Pull Station MS-702ID(U)

    Addressable Single Stage Dual Action Pull Station MS-710ID(U)

    * Unit employs an integral heat sensor; however it must not be used as a regular heat detector. Refer to the product data sheet for detailed functionality, operation and application.Manual configuration for the MIX-3200 is NOT PERMITTED. This device must be configured via the AUTO CONFIG.

  • 5.0 Mechanical Installation5.1 Installing the Enclosures

    Install the FX-350 Series Fire Alarm Panel enclosure as shown below. Mount the enclosureusing the four mounting holes and the screws provided.

    Figure 1 Wallbox Dimensions / Mounting the FX-350 – Surface

    11"

    14.5"

    1.5"

    14.5"

    4"

    4.5"

    20"

    Mounting Hole

    Mounting Hole

    Mounting Hole

    Mounting Hole

    19

  • Mechanical Installation

    m depthunting

    ring

    Figure 2 Mounting the FX-350 - Flush

    Figure 3 below shows a cross-section of the semi-flush mounted backbox and the trim ring.Make sure to allow a minimum depth of 1” above the wall surface for proper door opening.

    Figure 3 Flush Trim Detail

    17"

    22.5"

    PLACE FA-300TRB TRIM RING OVER BACKBOX

    14.5"

    3.5"

    1"

    4.5"

    11"

    20.0"

    1.5"

    4"

    14.5"

    3.5" is the maximufor semi-flush mousing the flush trim

    1" is the minimum depthabove the wall requiredfor semi-flush mountingusing the flush trim ring

    4 MountingHoles forSurface

    Mounting

    Adhere trim ring towall surface aroundFX-350 backbox

    TRIM RING

    MIN 1”WALL

    WOOD ORMETAL STUD

    BACKBOX

    20

  • Mechanical Installation

    Figure 4 Wallbox Dimensions / Mounting the FX-351/FX-353 – Surface /Flush

    Note: See Figure 3 for mounting the trim ring.i

    21

  • Mechanical Installation

    5.2 BBX-1024DS and BBX-1024DSR Mechanical Installation

    The BBX-1024DS and BBX-1024DSR are suitable for flush or surface mounting, and have abuilt-in trim ring.

    Figure 5 BBX-1024DS and BBX-1024DSR Installation Instructions and Dimensions

    Dimensions of Enclosure (minus built in trim ring) 14.5” x 4.2” x 26”Distance between horizontal mounting screws 12”Distance between vertical mounting screws 23.5”Complete Dimensions of Enclosures 16.3” x 5.5” x 27.5”

    26.0 "

    14.5 "

    4.2 "

    External Dimensions

    12.0 "

    23.5 "

    Mounting Dimensions

    1.3 " 1.7 "

    2.0 "

    Top View

    2.1 "

    1.3 "6.0 "

    9.5 "

    Side View

    22

  • ertercating304

    r

    rminal

    6.0 Installing Adder ModulesThe FX-350 Series Fire Alarm panels come pre-assembled with all components and boardsexcept for Adder Modules. Module installation locations are shown below. Refer to Figure 6and Figure 7 for Jumper or DIP Switch settings and see Chapter 8.0 Field Wiring on page 30for wiring specifications.

    Figure 6 Installation of Adder Modules

    CLASS- A convboard for indicircuits OCAC-(4 circuits)

    Reverse polarity and citytie module PR -300.Mounted on hex spacerwith two screws provided

    Transforme

    AC wiring te

    -SI

    G 1O

    UT+

    -SI

    G2

    OUT

    +

    -SI

    G1

    RET+

    -SI

    G2

    RET

    +

    BLK

    RED

    BLK

    RED

    -SI

    G3

    OUT

    +-

    SIG

    4O

    UT+

    -SI

    G3

    RET+

    -SIG

    4R

    ET+

    BLK

    RED

    BLK

    RED

    P3

    BATTERY

    P4

    + -

    P1 P2

    SEC TX

    POW

    ERS

    UPPLY

    Power supplyboard

    BATTERY

    + -

    BATTERY

    + -

    S-

    +NC

    NO

    CNC

    NOC

    NC

    NOC

    NCN

    OC

    RT

    RT

    RT

    RT

    RES

    CORE

    SC

    O

    LINE

    1LI

    NE2

    JW7

    -+

    +-

    +-

    -+

    -+

    -+

    SIG

    1SI

    G2

    SIG

    3SI

    G4

    TO PR-300 MODULE

    RS-4

    85AU

    X.R

    ELAY

    ALAR

    MRE

    LAY

    SUPE

    RVIS

    ORY

    REL

    AYTR

    OUBL

    ERE

    LAY

    AUX

    SUPP

    LY4-

    WIR

    ESU

    PPLY

    COM+COM-TRLTRB

    UNFILTEREDFWR24VDC

    RTIPORT

    SYSTEM NORMAL

    OCT 21 , 2005 02:41AM

    Loop A

    +-

    +-

    B

    JW9

    JW1

    JW3

    JW4

    SYSTEMRESET

    F IREDRILL

    AUTOMATIC ALARM SIGNAL CANCEL

    GENERALALARM

    SIGNALSILENCE

    ALM/SUP/TBL/BLDG AUDIBLE SIL

    LAMPTEST

    SPARE

    AC ON 1 2ABC

    3

    5 6

    7 8 9

    * 0 #

    4

    X

    M

    ?

    D EF

    GH I JKL MN O

    PR S TU V WXY

    QZ

    COMMON ALARM

    COMMON SUPV

    COMMON TROUBLE

    CPU FAULT

    GROUND FAULT

    PR- 300 is mountedhere for FX-351

    JW2

    JW6

    JW5

    For PC programming use UIMAInterface module not UL-864 orULC-527 listed. Please refer toDocument LT-929 for details

    RS-232C PORT

    TO RAX-332

    P12

    P3 P24P8P

    ALM/SUP/TBL/BLDG AUDIBLE S IL

    23

  • Installing Adder Modules

    Tel

    Tel

    RS-ann

    Au

    Ala

    Sup

    Tre

    e

    6.1 Cable and Jumper Connections for Main Board and Adder Modules

    Figure 7 Main Fire Alarm Board Cable Connectors and Jumper Locations

    ephone line #1

    ephone line #2

    485 for unciators

    xiliary Relay

    rm Relay

    ervisory Relay

    ouble Relay

    Auxiliary Supply

    ResettablAuxiliary Supply

    Unfiltered24V supply

    Connect to PR-300

    Connect to Remote trouble indicator

    Connect to RAX-332

    AddressablLoop

    BL

    K

    RE

    D

    BLK

    RED

    BLK

    RE

    D

    BL

    K

    RE

    D

    PO

    WE

    R

    SU

    PP

    LY

    S-

    +N

    CN

    OC

    NC

    NO

    CN

    CN

    OC

    NC

    NO

    CR

    TR

    TR

    TR

    T

    RE

    SC

    OR

    ES

    CO

    LIN

    E1LI

    NE

    2

    JW7

    -+

    -+

    -+

    -+

    -+

    -+

    SIG

    1SI

    G2

    SIG

    3SI

    G4

    RS-

    48

    5A

    UX

    .R

    ELA

    YA

    LA

    RM

    RE

    LAY

    SU

    PER

    VIS

    OR

    Y

    RE

    LAY

    TR

    OU

    BLE

    RE

    LAY

    AU

    X

    SU

    PP

    LY

    4-W

    IRE

    SU

    PP

    LY

    COM +COM -TRLTRB

    UNFILTERED

    FWR 24 VDC

    RTI

    PORT

    SYSTEM NORMAL

    OCT 21 , 2005 02 : 41 AM

    Lo

    op A

    +-

    +-

    B

    JW9

    JW1

    JW3

    JW4

    SYSTEM

    RESET

    F IREDRILL

    AUTOMATIC ALARM SIGNAL CANCEL

    GENERALALARM

    SIGNAL

    SILENCE

    ALM/SUP/TBL/BLDG AUDIBLE SIL

    LAMP

    TEST

    SPARE

    AC ON

    1 2ABC

    3

    5 6

    7 8 9

    * 0 #

    4

    X

    M

    ?

    D EF

    GH I JKL MN O

    PR S TU V WXY

    QZ

    COMMON ALARM

    COMMON SUPV

    COMMON TROUBLE

    CPU FAULT

    GROUND FAULT

    JW2

    JW6

    JW5

    For PC programming use UIMAInterface module not UL-864 orULC-527 listed. Please refer to Document LT-929 for details

    RS-232C PORTFor PC programming

    P12

    P3 P2P8 P4

    24

  • Installing Adder Modules

    iliaryply

    ettableiliaryply

    ble

    Figure 8 below shows the main board for the 3 loop addressable model. It is the same as thesingle loop model with two additional addressable loops.

    Figure 8 Main Board (3 loop model) Cable Connectors and Jumper Locations

    Telephone line #1

    Telephone line #2

    RS-485 forannunciators

    Auxiliary Relay

    Alarm Relay

    Supervisory Relay

    Trouble Relay

    AuxSup

    ResAuxSup

    Unfiltered24V supply

    Connect to PR-300

    Connect toRemote troubleindicator

    Connect to RAX-332

    Addressa

    1 3 2Loops

    BLK

    RED

    BLK

    RED

    BLK

    RED

    BLK

    RED

    PO

    WER

    SUP

    PLY

    S-

    +N

    CN

    OC

    NC

    NO

    CN

    CN

    OC

    NC

    NO

    CR

    TR

    TR

    TR

    T

    RE

    SC

    OR

    ES

    CO

    LIN

    E1LI

    NE

    2

    JW7

    -+

    -+

    -+

    -+

    -+

    -+

    SIG

    1SI

    G2

    SIG

    3SI

    G4

    RS-

    48

    5A

    UX

    .R

    ELA

    YA

    LA

    RM

    RE

    L AY

    SU

    PER

    VIS

    OR

    Y

    RE

    LAY

    TR

    OU

    BLE

    RE

    LAY

    AU

    X

    SU

    PP

    LY

    4-W

    IRE

    SU

    PP

    LY

    COM +COM -TRLTRB

    UNFILTERED

    FWR 24 VDC

    RTI

    PORT

    SYSTEM NORMAL

    OCT 21 , 2005 02 : 41 AM

    Lo

    op A

    +-

    +-

    B

    JW9

    JW1

    JW3

    JW4

    SYSTEM

    RESET

    F IREDRIL L

    AUTOMATIC ALARM SIGNAL CANCEL

    GENERALAL ARM

    SIGNAL

    SIL ENCE

    L AMP

    T EST

    SPARE

    AC ON

    1 2ABC

    3

    5 6

    7 8 9

    * 0 #

    4

    X

    M

    ?

    DEF

    GHI JKL MNO

    PRS TUV WXY

    QZ

    COMMON ALARM

    COMMON SUPV

    COMMON TROUBLE

    CPU FAULT

    GROUND FAULT

    JW2

    JW6

    JW5

    For PC programming use U IM AInterface module not UL-864 orULC-527 lis ted. Pleas e refer toD ocument LT-929 for details

    R S -232C PORTFor PC programming

    P12

    P3 P2P8 P4

    ALM/SUP/TBL/BLDG AUDIBLE SIL

    25

  • Installing Adder Modules

    6.2 Connectors and Jumpers on the Main Fire Alarm Board

    6.3 OCAC-304 Output Class A Converter Adder Module

    Figure 9 OCAC-304 Output Class A Converter Adder Modules

    Indicating circuits must be wired from the OCAC-304 to the main Fire Alarm board. Forexample indicating circuit 1 positive (red wire) and negative (black wire) is wired from theClass A Converter Module to the positive and negative terminals of Indicating circuit 1 on theMain Fire Alarm board.

    P8 Cable from P1 of the PR-300 Polarity Reversal and City Tie Module connects here.Otherwise not used.

    P4 Cable from connector P1 of the RAX-332 Display Adder Module connects here.Otherwise not used.

    JW1 On the Main Fire Alarm Module, this jumper is not used, open.JW2 Remove this jumper if a remote annunciator is used.JW3 Not used, open.JW4 Not used, open.JW5 Normally open. Place jumper here and power down (AC and batteries) and power back

    to restore Master Passcode. After reset, remove jumper and leave normally open.

    JW6 Normally open to BLOCK remote configuration via modem. Place jumper here toALLOW for remote configuration.

    JW7 On the Main Fire Alarm Module, this jumper must be removed if a PR-300 PolarityReversal and City Tie Module is installed.

    JW8 Not used, open.JW9 Not used, open.JW10 Not used, open.JW11 Not used, open.JW12 Not used, open.

    -SIG

    1 O

    UT+

    -SIG

    2 O

    UT+

    -SI

    G1

    RET

    +-

    SIG

    2 R

    ET+

    BLK

    RED

    BLK

    RED

    -SI

    G3 O

    UT+

    -SI

    G4 O

    UT+

    -SIG

    3 R

    ET+

    -SIG

    4 R

    ET+

    BLK

    RED

    BLK

    RED

    OCAC-304

    Mounting hole for #6-32 screw

    Mounting hole for #6-32 screw

    Wire to Main Board

    26

  • Installing Adder Modules

    The actual indicating zone is wired from the SIGNAL OUT positive and negative to thesignaling devices and then wired back to the SIGNAL RET positive and negative.

    6.4 Polarity Reversal and City Tie Module (Model PR-300)

    Mount the PR-300 on the left side panel of the backbox with the two screws provided, refer toFigure 10.

    Figure 10 Polarity Reversal and City Tie Module

    6.4.1 PR-300 Cable and Jumper Settings The following hardware configuration must be performed before installing the PR-300.

    The Alarm Transmit signal to the PR-300 can be programmed to turn OFF when signal silenceis active. This allows the City Tie Box to be manually reset. On subsequent alarms thesilenceable signals will resound and the City Tie Box will be retriggered.

    The Trouble Transmit signal to the PR-300 can be programmed to delay AC power fail 0, 1, 2,or 3 hours if this is the only system trouble.

    6.5 RAX-332 Display Adder Module

    The RAX-332 Display Adder Module is used only with the FX-351 and FX-353 Fire AlarmPanels. No jumpers or other physical configuration steps are required to install this secondRAX-332 Display Adder Module. Remove the blank cover plate from the front door and installthe RAX-332 with the clear cover in the opening with the hardware provided. Disconnect mainand standby power and connect the cable of the second RAX-332 into the open, remainingheader of the existing RAX-332. The additional LEDs will be available for configuration asLEDs 33 to 64, when the system power is restored.

    P1 Cable connects to P8 (bottom left-hand corner) on the Main Fire AlarmBoard.

    JW4 Not used. Keep jumper intact.

    POLAR

    ITYREVER

    SALALAR

    M

    POLAR

    ITYREVER

    SALSU

    PV

    CITYTIE

    + | -+ | -

    + | -

    JW4

    P1 P2

    Mounting hole for#6-32 screws

    Mounting hole for#6-32 screws

    27

  • 7.0 Circuits and Devices7.1 Addressable/Analog Devices

    The FX-350 supports up to 3 loops of addressable/analog devices. The device loop can beused to connect up to 60, 126 or 378 analog devices and addressable input or output moduleson an unshielded twisted pair (UTP). The devices must be compatible with the Mircom deviceprotocol.

    The loop interface software continuously supervises the devices on its loop against thosefound during configuration for the following conditions:

    • device missing• unconfigured device responding• two or more devices responding to the same address• wrong device type

    A communication or addressing error on a device is reported as a trouble on the associatedzone LED if configured.

    The addressable loop can be configured for class A or B operation. "T-tapping" is allowed(Refer to device installation documentation for details).

    Devices on the loop have an optional LED which normally flashes when the device is polledand goes ON steady when the device is active (alarm for an input device or active for anoutput device). The flashing of the LED on polling for sensors can be suppressed duringconfiguration. For input or output modules, the LED always flashes when polling. The softwarelimits the maximum number of the devices which can have their LED turned ON when active tofifteen (15).

    Certain devices are designed to support an optional external LED, which operates when theLED on the device is activated. Remote/external LEDs must NOT be used on this system. Thepanel can provide up to 350mA of current to the devices on the loop. A maximum line loss of 5volts is permitted, so the loop distance, wire size, and maximum number of devices are limitedby this constraint.

    The devices should be installed using unshielded twisted pair (UTP). The total line drop on theloop must not exceed 5 volts at the last device. The calculations required to determine themaximum permissible loop wiring distance with various combinations of devices is relativelycomplicated, and when isolators are used, includes a consideration of device inrush currentswhich must not exceed 20mA for a single isolator. In no case should more that twenty devicesbe connected to a single isolator. To simplify the calculation process, please utilize the loopcalculator program located on the Mircom website at http:/www.mircom.com in order todetermine maximum loop lengths, number of devices, and wire sizes etc.

    It is also important to note that the device LEDs present a significant extra load on the loopwhich must be considered in calculating permissible loop lengths, battery capacities, etc.Please refer to the device Installation Instructions and other documentation provided with theaddressable devices, bases, and isolators for further information. The system willautomatically limit the maximum number of device LEDs which can be illuminated to15.

    28

    http://www.apollo-fire.co.uk/prod-serv/loopcalc.htm

  • Circuits and Devices

    uts

    7.2 Analog Devices

    The system supports Mircom MIX-3000 Series photo, ion, multi-sensor and thermal (heat)type analog detectors, as well as contact input and output devices. The detectors may beconfigured as non-verified or verified alarm inputs. To determine an alarm condition, thesystem polls the analog device and compares the analog value against stored thresholds forpre-alarm and alarm conditions.

    A range of thresholds is provided for each type of analog device (except for contact devices),corresponding to the agency approved range of threshold for a particular device type. Eachdevice can be individually configured to a value in the range of threshold for “day time” andone for the “night time” or after hours operation; i.e. a device may be configured to a lowsensitivity for “day time” and high sensitivity at “night time”. The day time threshold will be usedunless the after hours operation is active.

    7.2.1 Drift CompensationThe FX-350 will automatically adjust for gradually increasing affects of dust and otheraccumulations of dirt in the detectors. It will adjust the thresholds to compensate for a detectorgoing dirty according to the gradual change in the normal clean air value received. When it canno longer compensate for an increasingly dirty detector, a dirty detector trouble is indicated forthat device.

    7.2.2 Auto TestPeriodically each detector is commanded to return an alarm value to test its ability to alarm. Ifit fails the test, a trouble is indicated on that device.

    7.3 Contact InputsContact input modules on the addressable/analog device loop may be configured as any ofthe following input types:

    7.4 Contact Outputs

    Contact output modules on the addressable/analog device loop may be configured as any ofthe following output types:

    • signals• strobes• relay outputs

    Analog devices may be installed with relay or sounder bases. The outputs of these bases areactivated when the device active LED turns ON steady in response to an alarm. The commandto activate the output is separate from the command that activates the LED and they are notsubject to the same restrictions as the LED. Output modules configured as signals are notstroked by software at the current signal rate. When the system commands them to be eitherin alert or in evacuation, the panel will simply activate them continuously. It is possible toprovide stroked operation by connecting the signal power to a conventional signal outputwhich is stroking at the correct rate when the device is active. Depending on the device, thesystem can detect open and short troubles and report it as an output circuit trouble.

    • non-verified alarm inputs • latching supervisory inputs • trouble only inputs• waterflow inputs • monitor inputs • remote switch inp• non-latching supervisory inputs

    29

  • 8.0 Field Wiring

    8.1 Main Fire Alarm Board Field Wiring

    Wire devices to the addressable loop as shown in Figure 11 for Class B (Style 4) or Figure 12for Class A (Style 6). Refer to Table 3 for loop wire gauges. Wire devices to addressableloops 2 and 3, if available, in the same manner.

    Figure 11 Addressable Loop Wiring - Class B or Style 4

    Table 2 Settings permitted in CAN/ULCS527

    NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION, AND OTHER INVOLVED PARTIES

    This product incorporates field-programmable software. In order for the product to comply with the requirements in CAN/ULCS527, Standard for Control Units for Fire Alarm Systems, certain programming features or options must be limited to specific values or not used at all as indicated below.

    Program feature or option

    Permitted in CAN/ULCS527? (Y/N) Possible settings\methods

    Settings permitted in CAN/ULCS527

    FX-350-60-DR Y Sequential Display

    Fire Alarm panel configured as one zone (common input tag designation).

    System Reset and Signal Silence on RAM-208/216

    N

    JW4 (Orange Wire) Intact = Buzzer silence & Lamp Test local function only. System Reset & Signal Silence are disabled.

    Cut Jumper (Orange Wire) to have all remote functions operate.

    Leave JW4 intact on RAM-208/216

    CLASS BWIRING

    ION SMOKE DETECTOR

    PHOTO SMOKE DETECTOR

    HEAT DETECTOR PULL STATION

    Loop A

    +-

    +-

    B

    OUTPUT MODULE

    30

  • Field Wiring

    AG

    Table 3 Loop Wiring Table

    8.2 Loop Isolators

    To limit the number of addressable devices compromised by a short on the addressable loop,isolators (MIX-100X, 100XH, or 100XB) may be used to isolate the affect of the short circuit. Ifthe impact of a short circuit must be limited to only one device, an isolating base must be usedfor each detector. A maximum of twenty devices can be connected between isolators, orbetween the panel and the first isolator, as long as the maximum in-rush current for thedevices on one segment of the loop does not exceed 20 mA. Refer to the installationinstructions for addressable devices for additional details.

    Figure 12 Addressable Loop Wiring - Class A or Style 6

    8.3 Loop Operation

    When there is a short circuit on the Class A loop with isolators installed, the isolators isolatethe shorted fault, the panel detects it as an open loop and generates an open loop trouble.

    UNSHIELDED TWISTED PAIR WIRE GAUGE

    LOOP TOTAL (OUT AND IN) WIRE RUN

    AWG FEET METRES

    12 20,000 6098

    14 15,942 4859

    16 9960 3036

    18 6265 1910

    CLASS WIRIN

    ION SMOKE DETECTOR

    PHOTO SMOKE DETECTOR

    HEAT DETECTOR INPUT MODULE

    Loop A

    +-

    +-

    B

    OUTPUT MODULE

    This Loop Wiring Table is for reference only and shouldnot be used without a detailed loop calculation.

    Maximum Loop Current: 350 mA

    Maximum Loop Resistance: 35 subtract 0.2 Ohms perisolator.

    Maximum Loop Capacitance: 0.5 μF

    Maximum Number of Isolators is 40.

    31

  • Field Wiring

    When a Class A loop is opened there may be a few missing devices reported by the panelwhich will be restored once the panel has established the Class A connection.

    8.4 Indicating (Powered Output) Circuits

    Powered output circuits can be configured as signal, strobe or relay outputs. Powered outputcircuits are supervised while they are not active for both open circuits and shorts. The circuitwill not actually be activated if there is a short trouble on the circuit. It will be activated if anopen trouble is indicated. Since open circuit supervision does not operate while the circuit is inalarm, if the circuit was in trouble before it was activated, it will still indicate trouble whileactive. The trouble condition will be re-evaluated when supervision resumes.

    Output circuits configured as strobes can have sync protocol for synchronization if configured.Certain strobe and strobe/horns models of the following manufacturers are supported.

    • All normal non-sychronized horns• Faraday• System Sensor• Wheelock• Gentex• Mircom

    When configured as normal, the output circuit is ON continuously when activated and does notuse any sync protocol. When configured as non-silenceable strobes, the strobes cannot besilenced, but the horn can be silenced by pressing the 'signal silence' button

    If the strobe is configured as silenceable strobe both the horn and the strobe are silenced(stopped) by pressing the 'signal silence' button

    8.5 Indicating Circuit Wiring

    The FX-350 Series Addressable Fire Alarm Panel supports Class B (Style Y) and Class A(Style Z) wiring for its indicating circuits. Each circuit is supervised by a 3.9K End-of-Lineresistor. Each indicating circuit provides up to 1.7 Amperes, total 5 Amperes of currentmaximum if no auxiliary power is used. Wire indicating circuits as in Figure 11 for Class B(Style Y) or as in Figure 12 for Class A (Style Z).

    Note: When there is an "Open loop trouble" look for both open and shorts on the loop. As a guide line the isolators which are activated in response to a short will have their LED ON; look for the short between the two isolators with their LEDs ON.

    Table 4 Maximum Wiring Distances

    TOTALSIGNALLOAD

    MAXIMUM WIRING RUN TO LAST DEVICE (ELR) MAX. LOOPRESISTANCE

    18AWG 16AWG 14AWG 12AWG

    Amperes ft m ft m ft m ft m Ohms

    0.06 2350 716 3750 1143 6000 1829 9500 2895 30

    0.12 1180 360 1850 567 3000 915 4720 1438 15

    0.30 470 143 750 229 1200 366 1900 579 6

    i

    32

  • Field Wiring

    YG

    YG

    ATING IT - 1

    ATING IT - 2

    0.60 235 71 375 114 600 183 950 289 3

    0.90 156 47 250 76 400 122 630 192 2

    1.20 118 36 185 56 300 91 470 143 1.5

    1.50 94 29 150 46 240 73 380 115 1.2

    1.70 78 24 125 38 200 61 315 96 1.0

    Notes: For Class A wiring the resistance in ohms is multiplied by two.

    Maximum voltage drop should not exceed 1.8 volts.

    Table 4 Maximum Wiring Distances

    TOTALSIGNALLOAD

    MAXIMUM WIRING RUN TO LAST DEVICE (ELR) MAX. LOOPRESISTANCE

    18AWG 16AWG 14AWG 12AWG

    i-

    SIG

    1 +

    STYLEWIRIN

    STYLEWIRIN

    INDICCIRCU

    INDICCIRCU

    RLE TTAW 2/1 K9.3EBORTSLLEB

    INDICATINGCIRCUIT #1

    INDICATINGCIRCUIT #2

    HORN

    FIRE PANEL MAIN BOARD

    - S

    IG 2

    +

    NOTE: WIRE INDICATING CIRCUITS # 3 AND #4 IN THE SAME WAY AS#1 AND #2

    33

  • Field Wiring

    Z

    Z

    TING T 1

    TING T 2

    AY

    Figure 13 Indicating Circuit – Class B or Style Y Wiring

    Figure 14 Indicating Circuit –Class A or Style Z Wiring

    8.6 Dialer Wiring

    If you have Fire Alarm Panel model FX-350-60-DR, FX-350-126-DR, FX-350-378-LDR, FX-351-LDW or FX-353-DR, there is a dialer on board and terminals marked Line 1 and Line 2must be wired as shown in Figure 15 below. Terminals are located in the top left hand corner of

    BELL

    STROBE

    HORN

    +

    -

    STYLE WIRING

    STYLE WIRING

    INDICATINGCIRCUIT #1

    INDICATINGCIRCUIT #2

    INDICACIRCUI

    INDICACIRCUI

    2 MORE INDICATING CIRCUITS NOT SHOWN

    OCAC-304 CLASS A CONVERTER MODULE

    FIRE PANEL MAIN BOARD

    BLK

    RED

    BLK

    RED

    -SIG

    1 O

    UT+

    -SI

    G2

    OU

    T+

    -SI

    G1

    RET

    +-

    SIG

    2 R

    ET+

    +

    -

    SIG

    1S

    IG 2

    NOTE: WIRE INDICATING CIRCUITS # 3 AND #4 IN THE SAME WAS #1 AND #2

    34

  • Field Wiring

    the main fire alarm board, from the top down. Refer to Figure 6 and Figure 7 for terminallocations.

    Figure 15 Dialer Wiring

    Refer to Chapter 13.0 Dialer Operation on page 58 and Chapter 15.0 Appendix B:Reporting on page 60 for more information regarding the built-in dialer.

    TT

    RR

    premise telephoneIF permitted

    TT

    RR

    LINE-1

    LINE-2

    1

    2 3

    4

    8 5

    7 6

    Public switchTelephone company

    wiring

    TIP

    RING

    TIP

    RING

    RJ31X

    GREY

    BROWN

    RED

    GREENC

    OC

    OR

    ESR

    ES Line 2 is Wired as shown for Line 1

    FIRE ALARM MAIN BOARD

    35

  • Field Wiring

    8.7 Polarity Reversal and City Tie Module (PR-300) Wiring

    Wire the PR-300 Polarity Reversal and City Tie Module (if used) as shown in Figure 16 below.Power Limited cable type FPL, FPLR or FPLP must be used. For USA installation, the installermust use Atlantic Scientific (Tel: 407-725-8000), Model #24544 Protective Device, orsimilar UL-Listed QVRG secondary protector, as shown. For use in Canada, the ProtectiveDevice is not required but still recommended.

    Figure 16 Polarity Reversal and City Tie Module Terminal Connection

    1

    1

    2

    2

    S

    S

    CITY TIE LOCAL ENERGYRATED - 24VDC FILTEREDTRIP COIL - 14 Ohms, 210mA, 5mV RIPPLE

    POLARITY REVERSAL ALARM24VDC OPEN12VDC AT 3.5mA8mA MAX. SHORT

    POLARITY REVERSAL SUPV .24VDC OPEN12VDC AT 3.5mA8mA MAX. SHORT

    PROTECTOR1

    1

    2

    2

    S

    S

    1

    1

    2

    2

    S

    S

    PROTECTOR1

    1

    2

    2

    S

    S

    USE A SHORTING WIRE WHEN THE CITY TIE IS NOT USED

    +

    +

    +

    -

    -

    -

    +

    +

    +

    -

    -

    -

    CONFORMS TO NEMA STANDARD SB3-1969 INTENDED FOR CONNECTION TO POLARITY REVERSAL CIRCUIT OF A REMOTE STATION RECEIVING UNIT HAVING COMPATIBLE RATINGSDIN RAIL CONNECTION

    TO EARTH GROUND

    DIN RAIL CONNECTION TO EARTH GROUND

    NOT POWER LIMITED

    POWER LIMITED

    POWER LIMITED

    PR-300

    PRO

    TECT

    EDPR

    OTE

    CTED

    UN

    PRO

    TECT

    EDUN

    PRO

    TECT

    ED

    NOTES:1. Plug PR-300 ribbon cable P1 into connector P8 of the Main Fire Alarm board.2. Cut Jumper JW1 on the PR-300 Polarity Reversal and City Tie Module in order to transmit a trouble condition from the Polarity Reversal Alarm terminals to the monitoring station.3. Cut Jumper JW2 on the PR-300 Polarity Reversal and City Tie Module in order to transmit a trouble condition from the Polarity Reversal Supervisory terminals to the monitoring station.4. Remove jumper plug from JW7 on the Main Fire Alarm board.5. For USA installation, the installer must use an Atlantic Scientific (Tel. 407-725-8000), Model #24544 Protective Device or similar UL-Listed QVRG secondary protector.6. The Polarity Reversal interface is Power Limited and must use power limited cable type FPL, FPLR or FPLP from the PR-300 to the Protectors.

    EITHER THE CITY TIE or POLARITY REVERSAL INTERFACE MAY BE USED, NOT BOTH.

    36

  • Field Wiring

    8.8 Auxiliary Power Supplies

    8.8.1 Aux 2 Resettable Auxiliary Power (supervised, regulated)The AUX 2 resettable auxiliary power supply is supervised for shorts, therefore a short willdisconnect the power until the “RESET” button is pressed. A trouble signal will be generated ifthere is a short. The circuit must be supervised for opens utilizing the End of Line Relay ModelPAM-3 as shown in Figure 17. This supply is rated at 21.1 VDC regulated / 300 mA max / 1 Vvoltage drop maximum.

    8.8.2 Auxiliary Supply (supervised, regulated) Supervised auxiliary power is used to power the remote annunciators and smart relaymodules. This filtered circuit is supervised for shorts, therefore a short will disconnect thepower until the “RESET” button is pressed. A trouble signal will be generated if there is ashort. The circuit must be supervised for opens utilizing the End of Line Relay Model PAM-3 asshown in Figure 17. This supply is rated at 21.1 VDC regulated / 500 mA max / 1 V voltagedrop maximum.

    8.8.3 Unfiltered Supply (unsupervised, unregulated) This unregulated supply is not supervised. When required, it is recommended that the circuitbe supervised for opens utilizing the (UL listed - S3403) End of Line Relay Model PAM-3 asshown in Figure 17. This supply is rated at 24 VDC / 1.7 A max. If there is a short on thiscircuit, the auxiliary power does not recover automatically when the short is removed. Themain power and the battery must be disconnected, then reconnected and the panel reset tore-establish the auxiliary power supply.

    Figure 17 Supervision Of Auxiliary Supplies

    14

    23

    56DETECTOR POWER SUPPLY22VDC, 200mAMAX. CURRENT - 300mAMAX. RIPPLE VOL. 5mV(POWER LIMITED)

    END OF LINE RELAY

    +

    -RESETTABLE AUXILIARY POWER OR AUXILIARY SUPPLY ORUNFILTERED SUPPLY

    FIRE ALARM MAIN BOARD

    E.O.L.47K Ohms

    ION SMOKE DETECTOR

    PHOTO SMOKE DETECTOR

    HEAT DETECTOR

    +-

    +-

    B

    LEGEND

    Class B (Style B) WIRING

    Loop

    A

    MIX-101PViolet

    White

    Red

    RedBlack

    Black

    Supervision for Auxiliary Supplies

    MINI MONITOR MODULE

    AUX 2

    Connect auxiliary devices here*

    * Use this supervision set-up only if auxiliary devices are used

    37

  • Field Wiring

    8.9 Power Supply Connections

    The power supply is located directly behind and below the main board. The ratings are:

    Figure 18 Main Power Supply Connections

    Electrical Input rating 120 VAC, 60Hz, 1.73A / 240VAC, 50Hz, 0.864ABattery fuse on Main module 10A, slow blow micro fuse (not replaceable)

    Caution: The main AC branch circuit connection for the Fire Alarm Control Unit mustprovide a dedicated continuous power without any disconnect devices. Use#12 AWG wire with 600-volt insulation and proper over-current circuitprotection that complies with the local codes. Refer to 16.0 Appendix C:Specifications on page 62 for specifications.

    Note: Ensure that the AC supply is disconnected before wiring the power to the panel. Wire the AC power to the AC wiring terminals as shown in Figure 18 using the proper wire gauge. Fire alarm systems must be installed in compliance with local codes and standards and with the Authority Having Jurisdiction (AHJ)

    Note: The FX-350 panel is capable of being wired for 120 VAC or 240 VAC 50/60 Hz as shown above. A good ground connection to the “Ground" terminal is essential to electrical safety, ensure proper operation, and specified noise immunity.

    !

    iP

    3

    BATTERY

    P4

    + -

    P1 P2

    SEC TX

    P6P5

    POW

    ER

    SU

    PP

    LYTRANSFORMER

    AC WIRING TERMINALS

    POWER SUPPLY BOARD

    BATTERY

    + -

    JW7

    TO PR-300 MODULECOM+COM-TRLTRB

    UNFILTEREDFWR 24VDC

    RTI PORT

    BATTERY

    + -

    Yellow

    Red

    Black

    Green

    240VAC 50Hz

    120VAC 60Hz

    N

    Ground

    P3 P2

    RIBBON CABLE

    POWER CONNECTOR

    BLACKRED

    RED

    i

    38

  • Field Wiring

    8.10 Connecting to a 3G4010 Interface Device for Canada

    A typical connection is shown in Figure 19. The PCS-100 Passive Communications Interface Board (sold separately) is required.

    For information on Compatible DACR Receivers see 14.0 Appendix A: Compatible Receivers on page 59.

    Figure 19 Connecting an FX-350 FACP to a 3G4010 Interface Device

    Note: The DSC interface device 3G4010 is required if the installation requires ULC S559 certification. The DSC interface device 3G4010CF is required if the installation requires UL864 9th edition certification.

    ALARM RELAY

    SPV RELAY

    TRBL RELAY

    TelephoneLine A

    Connection

    DC IN

    EOL

    To GSM/GPRS

    Typical Installation in Canada

    Line 2Line 1

    PCS-100

    POW

    ER24V

    G

    ND P GM

    4 GN

    D 1 4V

    NC

    CO

    M N

    O

    TBL RELA

    Y

    JW1

    PGM4

    AUX SUPPLY +

    -

    Internet

    Computer

    Printer SUR-GARD SYSTEM IV

    Internal IP: X.X.X.XExternal IP: X.X.X.X

    SG-SystemsConsole 2.1

    Default Gateway: X.X.X.XSub-Net Mask:X.X.X.XPort #: YYYY (UDP)

    NOC

    NOC

    NOC

    COM

    Z3

    Z2

    Z1 T1

    R1

    (-)

    (+)

    FX-350

    3G4010 TRBL

    Addressable module configured as 3G4010 radio trouble

    3G4010

    C.O. C.O.

    FX-350 - 3G4010 Connection - Typical Diagram

    Router

    - All units must be installed in the same room- All extended wiring must be in metallic conduit- Wiring between FACP and 3G4010:18 m max.

    Contact DSC to reprogram the zone inputs to match the FACP as shown in this diagram

    -

    i

    39

  • Field Wiring

    8.11 Connecting to a 3G4010CF Interface Device outside Canada

    For information on Compatible DACR Receivers see 14.0 Appendix A: Compatible Receivers on page 59.

    A typical connection is shown in Figure 20. The 3G4010CF is powered separately from the PCS-100 and requires 2 DSC RM-2 relays (sold separately). The PCS-100 Passive Communications Interface Board (sold separately) is also required.

    Figure 20 Connecting an FACP to a 3G4010CF Interface Device outside Canada

    Note: The DSC interface device 3G4010 is required if the installation requires ULC S559 certification. The DSC interface device 3G4010CF is required if the installation requires UL864 9th edition certification.

    TelephoneLine A

    Connection

    EOL

    Line 2C.O.

    Line 1 C.O.

    PCS-100

    POW

    ER24V

    G

    ND P GM

    4 GN

    D 1 4V

    NC

    CO

    M N

    O

    TBL RELA

    Y

    JW1AUX SUPPLY +

    -

    To GSM/GPRS

    Internet

    Computer

    Printer SUR-GARD SYSTEM IV

    Internal IP: X.X.X.XExternal IP: X.X.X.X

    SG-SystemsConsole 2.1

    Default Gateway: X.X.X.XSub-Net Mask:X.X.X.XPort #: YYYY (UDP)

    Router

    FX-350

    3G4010CF TRBL

    ALARM RELAY

    SPV RELAY

    TRBL RELAY

    NOC

    NOC

    NOC

    FX-350 - 3G4010CF Connection - Typical Diagram

    Typical Installation outside Canada

    - All units must be installed in the same room- All extended wiring must be in metallic conduit- Wiring between FACP and 3G4010CF: 20 feet max.- Contact DSC to reprogram the zone inputs to match the FACP as shown in this diagram- Use 2 DSC RM-2 Relays (sold separately) to supervise both AC failure trouble and low battery trouble- Install the DSC RM-2 Relays inside the 3G4010CF enclosure above the PS4086

    3G4010CF TRBL

    PGM4

    COM

    Z3

    Z2

    Z1

    T1 R1

    NC COM NO

    DSC RM-2 Relay

    EOL

    -

    PS4086

    Transformer Battery

    DC IN

    +12V COMAC IN

    +

    ACT LBT

    NC COM NO

    DSC RM-2 Relay

    EOL

    -+

    BAT+ BAT-

    3G4010CF

    3G4010CF TRBL

    +-

    Addressable module configured as AC failure trouble

    Addressable module configured as low

    battery trouble

    Addressable module configured as 3G4010CF radio trouble

    i

    40

  • 9.0 System Checkout9.1 Before turning the power “ON”

    To prevent sparking, do not connect the batteries. Connect the batteries after powering thesystem from the main AC supply.

    1. Check that all adder modules are installed in the proper location with the proper connections.

    2. Check all field (external) wiring for opens, shorts, and ground.

    3. Check that all interconnection cables are secure, and that all connectors are plugged in properly.

    4. Check all jumpers and switches for proper setting.

    5. Check the AC power wiring for proper connection.

    6. Check that the chassis is connected to earth ground (cold water pipe).

    7. Make sure to close the front cover plate before powering the system from main AC supply.

    The best way to set up a panel for the first time is to avoid connecting any field wiring at first.To begin set up, power up the panel with end of line resistors connected where appropriate,then connect the battery. The panel will show “System Restart Active”. Press System Resetbutton to reset the panel. If the panel is free of trouble, connect one circuit at a time, checkingfor troubles each time. If a trouble occurs at any point during the set-up, correct the fault, thencontinue connecting the field wiring.

    9.2 Power-up procedure

    After completing the system checkout procedures outlined above,

    1. Power up the panel. The "AC-ON" green LED and the “Common Trouble” LED should illuminate, and the buzzer should sound. Press the “System Reset” button. Since the batteries are not connected, the trouble buzzer should sound intermittently and the common trouble LED should flash.

    2. Connect the batteries while observing correct polarity: the red wire is positive (+) and black wire is negative(-). All indicators should be OFF except for normal power "AC ON" green LED.

    3. Configure the Fire Alarm Control Panel as described in the System Configuration section.

    41

  • asen oral

    or

    nal

    illas

    ing

    10.0 Troubleshooting Symptoms Possible Cause

    Circuit Trouble Normally when a circuit trouble occurs, its designated trouble indicator will be illuminated,well as the common trouble indicator and trouble buzzer. To correct the fault, check for opwiring on that particular circuit loop or that the Circuit Disconnect Switch is in the ONCLOSED position. Note: Disconnecting a Circuit will cause a system trouble (off-normposition).

    Remote Trouble Remote Trouble will be indicated on the main panel display for any failure reported by,failure to communicate with a remote annunciator or other remote device.

    Ground Fault This panel has a common ground fault detector. To correct the fault, check for any exterwiring touching the chassis or other Earth Ground connection.

    Battery Trouble Check for the presence of batteries and their conditions. Low voltage (below 20.4V) wcause a battery trouble. If battery trouble condition persists, replace batteries as soon possible.

    Walk Test Mode If the Walk Test LED is illuminated steadily, the system is in Walk Test Mode.

    Common Trouble If only a common trouble is indicated on the main panel and none of the above confirmtrouble indicators are ON, check the following for possible fault:

    • Check for any missing interconnection wiring.

    • Check for any Module missing that was part of the Configuration.

    • Check for improperly secured cabling.

    42

  • 11.0 Indicators, Controls and Operations Figure 21 below shows the common display panel for both the FX-350, FX-351 and the FX-353 Fire Alarm Control Panels.

    Figure 21 LCD Display, LED indicators and control buttons

    The display panel on the FX-350/FX-351/353 main fire alarm control board consists of:

    • a two line by twenty character LCD display• a sixteen button keypad• common LED Indicators• common control buttons

    FX-351 and FX-353 models are equipped with one RAX-332 LED display adder (32 zoneannunciation), with provision for a second optional adder (see section 4.1 Panel Models onpage 13 for further explanation) for another 32 zone annunciation for a total of 64 zoneannunciation. Each LED zone has a red/amber alarm/supervisory LED and an amber troubleLED.

    LED Indicators may be amber, red, or green, and may illuminate continuously, or at one offollowing Flash Rates:

    • Steady (Alarm) - ON continuously.• Fast Flash (Supervisory) - 120 flashes per minute, 50% duty cycle.• Trouble Flash (Trouble) - 20 flashes per minute, 50% duty cycle.

    Red indicators are used for Alarm, amber indicators for Trouble or Supervisory and green forpower ON.

    Note: Each RAX-332 display is supplied with blank paper labels (#NP-681) for sliding into the plastic label template on the display.

    COMMON ALARM

    COMMON SUPV

    TROUBLE

    CPU FAULT

    GROUNDFAULT

    SYSTEMRESET

    FIREDRI LL

    AUTOMATIC ALARM SIGNAL CANCEL

    GENERALALARM

    SIGNAL

    ALM/SUP/TBL/BLDG AUDIBLE SIL

    LAMPTEST

    BATTERY/CHARGER

    AC ON1 2

    ABC3

    DEF

    5JKL

    6MNO

    7 8TUV

    9WXY

    * 0QZ

    #

    4GHI

    PRS

    X

    M

    ?

    SYSTEM NORMAL

    DEC 03, 2009 02:41AM

    COMMON

    SILENCE

    TROUBLE

    i

    43

  • Indicators, Controls and Operations

    11.1 Common Indicators

    11.1.1 BuzzerThe Buzzer is activated by any of the following:

    • Fire Alarm: Steady • Supervisory Alarm: Fast flash rate• Trouble: trouble flash rate• Property and Building Safety: Configurable to sound at trouble flash rate

    11.1.2 AC On LEDThe AC On LED illuminates steady green whilethe main AC power is within acceptable levels. Itturns off when the power level falls below thepower-fail threshold and the panel switches tostandby (battery) power.

    11.1.3 Common Alarm LEDThe Common Alarm LED illuminates steady redwhenever the panel is in alarm. An alarm resultsfrom any alarm on any point or input programmedas alarm or activation of the manual GeneralAlarm button. Since all alarms are latched until thealarm conditions are cleared and the panel isreset, the LED will remain ON until then.

    11.1.4 Common Supervisory LEDThe Common Supervisory LED flashes amber at the Supervisory or Fast Flash rate whenthere is a supervisory alarm in the panel resulting from any un-bypassed latching or non-latching supervisory circuit. The LED turns OFF if all non-latching Supervisory Circuits arerestored and there are no active latching supervisory circuits. Latching supervisory alarmsremain active until the panel is reset.

    11.1.5 Common Trouble LEDThe Common Trouble LED flashes amber at the Trouble Flash rate when the panel detectsany trouble condition in the system. The LED turns OFF once all troubles are cleared.

    11.1.6 CPU Fault LEDThe CPU Fault LED flashes amber at the Trouble Flash rate when the panel detects a fault onthe CPU. It is turned OFF when the CPU fault is corrected.

    11.1.7 Ground Fault LEDThe Ground Fault LED flashes amber at the trouble flash rate when the Ground Fault Detectordetects a ground fault on any field wiring. It turns off immediately after the ground fault iscleared.

    11.1.8 System Reset LEDThe amber System Reset LED will illuminate steadily after the system reset button has beenpressed and the system is resetting.

    COMMON ALARM

    COMMON SUPV

    COMMON TROUBLE

    CPU FAULT

    GROUNDFAULT

    SYSTEMRESET

    AC ON

    44

  • Indicators, Controls and Operations

    11.1.9 Signal Silence LEDThe Signal Silence LED flashesamber at the Trouble Flash rateafter indicating circuits are silencedeither by the Signal Silence button,or by the Auto Signal Silence Timer.It turns OFF after the signals are re-sounded by a subsequent alarm.For UL installations, disable Auto Signal Silence.

    11.1.10Fire Drill LEDThe Fire Drill LED turns ON steady amber while Fire Drill is active.

    11.1.11ALM/SUP/TBL/BLDG AUDIBLE SIL LED (Buzzer Silence)The ALM/SUP/TBL/BLDG AUDIBLE SIL LED flashes amber at the Trouble Flash rate whenthe ALM/SUP/TBL/BLDG AUDIBLE SIL button is pressed. Any new alarm, supervisory ortrouble events will resound the buzzer and will cause the ALM/SUP/TBL/BLDG AUDIBLE SILLED to turn off.

    11.1.12AUTOMATIC ALARM SIGNAL CANCEL LED (Acknowledge)If the panel is configured as a two stage system, the AUTOMATIC ALARM SIGNAL CANCELLED turns ON steady amber after the Auto General Alarm Timer is cancelled by the activationof the AUTOMATIC ALARM SIGNAL CANCEL or Signal Silence buttons. If the Auto GeneralAlarm Timer times out and puts the panel into General Alarm, the AUTOMATIC ALARMSIGNAL CANCEL LED turns OFF. If the panel is configured as Positive Alarm Sequence(PAS), the AUTOMATIC ALARM SIGNAL CANCEL LED flashes amber at the Fast Flash ratewhile a timer counts down 15 seconds to common alarm.

    11.1.13General Alarm LEDThe red General Alarm LED illuminates steadily after the General Alarm button is pressed, ageneral alarm initiating circuit is activated, or the Auto General Alarm timer times out. Oncethe General Alarm LED turns on, it will stay active until the panel is reset.

    11.1.14Lamp Test LEDThe amber Lamp Test LED will illuminate steadily after the Lamp Test button is pressed andwhile system is in Lamp Test mode.

    11.1.15Battery/Charger Trouble LEDIn a ULI application the amber Battery/Charger Trouble LED flashes at the Trouble Flash ratewhen any Battery/Charger Trouble occurs.

    In a ULC application the amber Battery/Charger Trouble LED illuminates steady when anyBattery/Charger Trouble occurs.

    11.1.16LEDs 1 to 32 for FX-351 and FX-353 Series OnlyPoints labelled 1 to 32 are available for alarm, supervisory, and property and building safetyannunciation (bi-coloured red/amber LEDs) and trouble annunciation (amber LEDs).

    11.1.17RAX-332 LEDs 33 to 64 for FX-351 and FX-353 Series OnlyPoints labelled 33 to 64 are available for alarm, supervisory, and property and building safetyannunciation (bi-coloured red/amber LEDs) and trouble annunciation (amber LEDs).

    SYSTEMRESET

    FIREDRI LL

    AUTOMATIC ALARM SIGNAL CANCEL

    GENERALALARM

    SIGNAL

    ALM/SUP/TBL/BLDG AUDIBLE SIL

    LAMPTEST

    BATTERY/CHARGER

    S ILENCE

    TROUBLE

    45

  • Indicators, Controls and Operations

    11.2 Common Controls

    11.2.1 LCD DisplayThe display is a two line, 20 character back-lit alphanumeric LCD. It displays informationregarding the panel, its circuits, and devices. An on-screen cursor is controlled by the cursorbuttons (located to the right of the display) for menu selection and control. Report informationprovided by the LCD display includes Alarm, Event Log, Current Levels, Verification, andMaintenance reports.

    11.2.2 Cursor ButtonsLocated at key number 2, 8, 6 and 4. The cursorbuttons Up (next), Down (previous), Right, and Leftallow you to select items on the LCD display. The Upand Down buttons scroll through lists in a continuousloop.

    11.2.3 Enter Button

    Use this button to select a displayed item on the LCDdisplay.

    11.2.4 Cancel Button

    Use this button to cancel an operation or exit a menu.

    11.2.5 Menu Button

    Use this button to view the Command Menu.

    11.2.6 Info Button

    Push and hold this button to get detailed information about any displayed item.

    11.2.7 Signal Silence ButtonPressing the Signal Silence button after the panel is in alarm turns ON the Signal Silence LEDand de-activates any silenceable indicating circuits. Non-silenceable circuits are unaffected.Signals will re-sound upon any subsequent alarm. This button does not function during anyconfigured Signal Silence Inhibit Timer period. It also does not function if indicating circuits areactive as the result of a Fire Drill. In a two-stage system, the Signal Silence button silences thestage 1 and stage 2 alarms.

    11.2.8 Fire Drill ButtonThe Fire Drill button activates all programmed and non-disconnected indicating circuits, butdoes not transmit any Alarms via the city tie or common alarm relay. The Fire Drill is cancelledby pressing the button again (toggle switch), or if the panel goes into a true alarm.

    11.2.9 General Alarm ButtonPressing the General Alarm button immediately sends the panel into General Alarm. It will alsore-activate the signals if they have been silenced during General Alarm initiated through an

    1 2ABC

    3DEF

    5JKL

    6MNO

    7 8TUV

    9WXY

    * 0QZ

    #

    4GHI

    PRS

    X

    M

    ?

    X

    M

    ?

    46

  • Indicators, Controls and Operations

    addressable device configured as General Alarm. The General Alarm condition remains activeuntil the panel is reset.

    11.2.10System Reset ButtonThe System Reset button resets the panel and all circuits:

    11.2.11AUTOMATIC ALARM SIGNAL CANCEL Button (Two Stage or PAS only)If the panel is configured for two stage operation, activation of the AUTOMATIC ALARMSIGNAL CANCEL button while the Auto General Alarm Timer is timing (e.g. there is an alarmin the panel but it is still in the first stage) cancels the timer and turns the AUTOMATIC ALARMSIGNAL CANCEL LED ON steady amber. If the panel is configured for Positive AlarmSequence (PAS), activation of the AUTOMATIC ALARM SIGNAL CANCEL button within 15seconds of a PAS alarm will delay a common alarm activation for 60 seconds.

    11.2.12Lamp Test ButtonPressing and holding the Lamp Test button causes all front panel indicators to illuminate andsounds the buzzer steadily. Bi-coloured LEDs will illuminate twice to show both colors. If lamptest is active for more than ten seconds, the Common Trouble LED activates.

    11.3 Single Stage Operation

    In a single stage system, all alarm inputs are treated in a similar manner. Alarm inputs includeany of the following: non-verified alarm, verified alarm, waterflow alarm, and general alarmcircuits. Any of these alarm inputs occurring when the panel is not already in alarm cause thefollowing:

    • The buzzer sounds steadily• If fire drill is active, it is cancelled• The Common Alarm LED turns ON• The Common Alarm relay activates if Aux disconnect is not active• The Auto Signal Silence timer, if configured, starts. For UL installations, disable Auto

    Signal Silence.• The Signal Silence Inhibit timer, if configured, starts• All non-disconnected indicating programmed to the input are activated provided that Aux

    disconnect is not active

    • Resets Aux Resettable Power Supply • Turns off all Indicating Circuits• Turns OFF Signal Silence, Ack & GA LEDs • Turns off Fire Drill• Stops and resets all Timers • Processes inputs as new events

    • Aux Disconnect is not affected• Reset cannot be activated until the

    Signal Silence Inhibit timer has expired

    • Pressing Reset button after a PAS Acknowledge will reset the system and clear the alarm event.

    Attention: After power-up, press the System Reset button to bring the system tonormal and restore the “system power up” trouble.!

    47

  • Indicators, Controls and Operations

    • Non-disconnected strobes associated with the input are activated• Non-disconnected signals associated with the input are activated at the evacuation rate

    Pressing the General Alarm button on the panel also initiates a general alarm.

    Subsequent alarms when the panel is already in alarm, cause the following:

    • The alert buzzer sounds steadily • If Signals have been silenced, they are resounded, the Signal Silence LED turns OFF,

    and the Auto Signal Silence timer, if configured, is restarted. For UL installations, disable Auto Signal Silence.

    • Any additional non-disconnected strobes associated with the input are activated continuously

    • Any additional non-disconnected signals associated with the new input are activated at the evacuation rate

    11.4 Two-Stage Operation

    In a Two-Stage system, alarm inputs are either First Stage (alert) inputs or Second Stage(general alarm) inputs. First stage inputs include inputs from the following types of circuits:non-verified alarm, verified alarm, and waterflow alarm. Second stage inputs include alarmson the general alarm circuits, activation of the General Alarm button, or expiration of the AutoGeneral Alarm timer. Any of these alarm inputs occurring when the panel is not already inalarm cause the following:

    • The buzzer sounds steadily.• If fire drill is active, it is cancelled.• The Common Alarm LED turns ON• The Common Alarm relay activates if Aux disconnect is not active.• The Auto Signal Silence timer, if configured, starts. For UL installations, disable Auto

    Signal Silence.• The Signal Silence Inhibit timer, if configured, starts.• All non-disconnected outputs programmed to the input are activated provided that Aux

    disconnect is not active.

    If the alarm is a Second Stage alarm,

    • All non-disconnected strobe circuits are activated continuously, if correlated to an alarm input.

    • All non-disconnected signal circuits are activated at the evacuation rate, if correlated to an alarm input.

    • The General Alarm LED turns ON.

    If the alarm is a First Stage alarm,

    • Non-disconnected strobe circuits programmed to that circuit are activated continuously.• Non-disconnected signal circuits programmed to that circuit are activated with the alert

    code (see section 11.8 Output Types on page 53).• The Auto General Alarm timer, if configured, starts.

    Subsequent First Stage alarms when the panel is already in alarm, cause the following:

    • The buzzer sounds steadily.• If signals have been silenced as a result of the silence button or the Auto signal silence

    timer, signals are resounded as they were before signal silence, the Signal Silence LED

    48

  • Indicators, Controls and Operations

    turns OFF, and the Auto Signal Silence timer, if configured, is restarted. For UL installations, disable Auto Signal Silence.

    • If the panel is not already in General Alarm, additional non-disconnected signals programmed to the new input are activated with the Alert Code (see section 11.8 Output Types on page 53).

    • If the panel is not already in General Alarm and if the AUTOMATIC ALARM SIGNAL CANCEL LED is ON steady indicating that the Auto General Alarm timer has been acknowledged the timer is restarted and the AUTOMATIC ALARM SIGNAL CANCEL LED is extinguished.

    A second stage alarm (general alarm) when the panel is already in alarm causes the following:

    • The buzzer sounds steadily.• All non-disconnected signals are activated at the evacuation rate.• If the Signal Silence LED is ON, it turns OFF and the Auto Signal Silence timer, if

    configured, is restarted. For UL installations, disable Auto Signal Silence.• The AUTOMATIC ALARM SIGNAL CANCEL LED if ON, turns OFF.

    Alarm inputs are latching, they remain active until system reset.

    11.5 Positive Alarm Sequence

    In a Positive Alarm Sequence (PAS) system, only smoke detectors can be dedicated as PASinputs. PAS Inputs can only be from the following types of circuits: non-verified alarm andverified alarm. Any of these alarm inputs occurring when the panel is not already in alarmcause the following:

    • The buzzer sounds steadily.• If fire drill is active, it is cancelled.• The Common Alarm LED turns ON• The individual zone LED (if programmed) turns ON.• The Common Alarm relay does not activate.• The PAS timer starts for 15 seconds.• All outputs programmed to the input are not activated.

    When the PAS alarm has been ack