analysis of industrial steel portal frames under fire conditions · 2014. 11. 27. · analysis of...

217
The University of Sheffield Department of Civil and Structural Engineering Analysis of Industrial Steel Portal Frames under Fire Conditions by: Yuanyuan Song A thesis submitted in partial fulfilment of the requirements for the degree of Doctor of Philosophy November 2008

Upload: others

Post on 11-Feb-2021

0 views

Category:

Documents


0 download

TRANSCRIPT

  • The University of Sheffield

    Department of Civil and Structural Engineering

    Analysis of Industrial Steel Portal

    Frames under Fire Conditions

    by:

    Yuanyuan Song

    A thesis submitted in partial fulfilment of the requirements for the degree of

    Doctor of Philosophy

    November 2008

  • ABSTRACT

    A new quasi-static solver has been developed and incorporated in to Vulcan for

    dealing with temporary instabilities, such as the snap-through of the pitched roof of a

    portal frame, which occurs in static analysis at elevated temperatures. A new

    dynamic model is designed to work following a quasi-static solution procedure, so

    that divergence of the numerical analysis is avoided in situations where the stiffness

    matrix becomes singular, when part of the structure loses stability in fire, and the

    structural behaviour after that can be traced. The capabilities and accuracy of this

    new solver have been validated, using several benchmark problems, against the

    results of reduced-scale fire tests and numerical analysis performed using

    commercial software.

    Using this new solver, the final failure mechanism of single-span pitched-roof portal

    frames, at much higher deflections than that at which the frame initially loses stability

    due to snap-through, is shown in the numerical modelling. Factors which may affect

    the failure mechanisms of industrial portal frames in fire have been investigated by a

    series of parametric studies. The effects of semi-rigid column bases, load ratio,

    haunch length, rafter section and different heating profiles have been tested using

    two-dimensional models. The restraint provided by secondary members has also

    been investigated using three-dimensional models. Two distinct phases of failure,

    one of which involves a mechanism which is different from that assumed in the

    widely used UK design guide, have been shown from both the fire tests and the

    numerical studies.

    A new design method based on these two phases of failure has been developed to

    determine the final failure mechanisms and critical temperatures of portal frames in

    fire. This new method has been compared with the predictions of the current design

    guide and numerical tests.

  • Acknowledgments

    This work would not have been possible without the help of my supervisors,

    Professor Ian Burgess, Dr Zhaohui Huang and Professor Roger Plank. They have

    provided assistance in numerous ways, including encouragement and heuristic

    discussion during the whole process of this research, and the sound advice and

    patience in reviewing this thesis. The financial support provided by The University of

    Sheffield and Vulcan Solutions is also greatly appreciated.

    I would like to express my deep and sincere gratitude to my family, their love gave

    me strength to accomplish this work. Also thanks to colleagues in the Fire

    Research group who provided helpful discussions on my research topic and also

    great opportunities to acquire knowledge in different fields.

    Special thanks goes to SAFE Ltd for their support during writing this thesis.

  • Declaration

    Except where specific reference has been made to the work of others, this thesis is

    the result of my own work. No part of it has been submitted to any organization for a

    degree or qualification.

    Yuanyuan Song

  • i

    CONTENTS

    List of Figures iv

    List of Tables xiv

    Notation xv

    1. INTRODUCTION 1

    1.1. Design of Portal Frame at Ambient Temperature ................................. 1

    1.2. Fire Concept ........................................................................................ 3

    1.3. Steel Properties at Elevated Temperatures ......................................... 5

    1.4. Current Design Method for Portal Frames In Fire ...............................12

    1.5. Behaviour of Portal Frames In Fire .....................................................14

    1.5.1. Fire Test ......................................................................................15

    1.5.2. Behaviour of Single-Storey Portal Frames in Fire ........................18

    1.5.3. Overall Behaviour of Industrial Frames in Fire .............................24

    1.6. Numerical Modelling ...........................................................................32

    1.6.1. Vulcan .........................................................................................32

    1.7. Scopes of The Research and Layout of The Thesis ...........................33

    2. NEW QUASI-STATIC PROCEDURE 35

    2.1. Introduction .........................................................................................35

    2.2. Dynamic Methods ...............................................................................41

    2.2.1. Direct Integration Method ............................................................42

    2.2.2. Mode Base Method .....................................................................45

    2.3. Developed Dynamic Model .................................................................47

    2.3.1. Predictor ......................................................................................47

    2.3.2. Corrector .....................................................................................48

    2.3.3. Lumped Mass Assumption ..........................................................50

    2.3.4. Damping Matrix ...........................................................................54

  • ii

    2.3.5. Transfer Matrix for Three-Noded Beam Elements .......................58

    2.4. Quasi-Static Solution Procedure .........................................................63

    2.5. Conclusion..........................................................................................64

    3. VALIDATIONS 67

    3.1. Validation of the Dynamic Model ........................................................67

    3.1.1. Hinge Supported Beam ...............................................................67

    3.1.2. Half Roof Frame ..........................................................................71

    3.1.3. Pitched Portal Frame ...................................................................74

    3.2. Validation of the Quasi-Static Solution Procedure ...............................76

    3.2.1. Twin-Bay Single-Storey Steel Portal Frame .................................77

    3.3. Validation Using Fire Tests .................................................................81

    3.3.1. Wong’s Test ................................................................................81

    3.3.2. Numerical Model .........................................................................85

    3.4. Comparisons Against Static Analysis ..................................................91

    3.5. Conclusion..........................................................................................95

    4. BEHAVIOUR OF PITCHED PORTAL FRAMES IN FIRE 96

    4.1. Introduction .........................................................................................96

    4.2. Behaviour of Portal Frames with Semi-Rigid Bases ............................97

    4.2.1. Frames without Fire Protection ....................................................98

    4.2.2. Frames with Columns Protected ................................................ 101

    4.3. Parametric Studies ........................................................................... 103

    4.3.1. Numerical Model ....................................................................... 104

    4.3.2. The Effect of Base Capacity ...................................................... 111

    4.3.3. The Effect of Base Stiffness ...................................................... 117

    4.3.4. The Effect of Loading Ratio ....................................................... 121

    4.3.5. The Effect of Haunch Length ..................................................... 124

    4.3.6. The Effect of the Rafter Section ................................................. 127

    4.3.7. The Effect of Column Heating .................................................... 129

  • iii

    4.3.8. The Effect of Asymmetrical Localised Fire ................................. 134

    4.3.9. The Effect of Purlins .................................................................. 140

    4.4. Conclusion........................................................................................ 148

    5. A NEW DESIGN METHOD FOR INDUSTRIAL FRAMES IN FIRE 151

    5.1. Discussion on Current Design Method .............................................. 152

    5.1.1. Current Design Model ................................................................ 152

    5.1.2. Comparison with Numerical Results .......................................... 156

    5.2. Development of the Simple Design Method ...................................... 161

    5.2.1. First Phase Failure Mechanism ................................................. 161

    5.2.2. Second Phase Failure Mechanism ............................................ 165

    5.3. Calibration of the New Design Method .............................................. 172

    5.3.1. Cases with Different Base Strength ........................................... 172

    5.3.2. Cases with Different Haunches ................................................. 175

    5.3.3. Cases with Different Rafters ...................................................... 176

    5.3.4. Cases with Different Loading Ratio ............................................ 177

    5.4. Conclusions ...................................................................................... 180

    6. CONCLUSION 182

    6.1. New Dynamic Model and Quasi-Static Procedure ............................ 182

    6.2. Paramatric Studies ........................................................................... 183

    6.3. New Simple Design Method ............................................................. 186

    6.4. Recommendations for Further Work ................................................. 188

    APPENDIX 190

    REFERENCES 193

  • iv

    List of Figures

    Figure Page

    1.1 Cross section showing the portal frame and its restraints 1

    1.2 A typical nominally pinned base 2

    1.3 Development of a natural fire 4

    1.4 Heat release rate for a fire in an industrial building 5

    1.5 Stress-strain curves for steel tested at 550°C 6

    1.6 Stress-strain curves of steel tested at the medium strain-rate 7

    1.7 The comparison of the stress-strain curves between the

    Ramberg-Osgood and Eurocode model up to 2% strain 9

    1.8 The comparison of the stress-strain curves between the

    Ramberg-Osgood and Eurocode models up to 20% strain 9

    1.9 Strength reduction factors from the stress-strain relationships

    of steel at elevated temperatures according to the Eurocode

    and British Standard 10

    1.10 Thermal elongation of carbon steel as a function of the

    temperature 11

    1.11 Failure mechanism used in current design method 13

    1.12 Frame dimensions used in calculation of overturing moment 13

    1.13 The first test: heating of the whole rafte 16

    1.14 The second test: edge fire 16

    1.15 The deformed portal frame after the third fire test 17

    1.16 Variation of overturning moment with the deformation of the

    portal frame in fire 19

    1.17 Heating situation considered in O’Meagher et al.’s model 20

    1.18 Failure temperatures of portal frames 21

  • v

    1.19 Comparison of failure temperatures with pinned and

    semi-rigid bases 22

    1.20 Variation of deflected shape showing the out-of-plane

    collapse of frames heated by the ISO834 fire 23

    1.21 Overall building behaviour 25

    1.22 Deflected shape for the model with purlins at the moment of

    failure, with an amplification factor of 10 25

    1.23 Deflected shape at 660°C of the entire roof heated case 26

    1.24 Vertical displacement at apex -2D vs 3D analysis 26

    1.25 Vertical displacements at apex of the central frame 27

    1.26 The analytical model in Bong’s study 28

    1.27 Deflected shapes immediately before and after the rapid

    sagging of roof of the pinned-base case with purlin axial

    restraint 28

    1.28 Sidesway collapse of the pinned-base case without purlin

    axial restraint 28

    1.29 Inward collapse of the fixed-base case without purlin axial

    restraint 29

    1.30 Finally deflected shape of the pinned-base case without

    purlin axial restraint and with full concrete encasement of

    columns 29

    1.31 Lateral displacements at the tops of columns in Phase 1 31

    1.32 Lateral displacements at the tops of columns in Phase 2 31

    2.1 Illustration of Newton-Raphson iterative procedure 36

    2.2 Illustration of the ill-conditioning of stiffness matrix in static

    analysis 36

    2.3 Illustration of the mechanism of snap-through for portal frame

    37

  • vi

    2.4 Load-deflection relationships for the pitched roof frame 39

    2.5 Effect of damping in the snap-through process 40

    2.6 Calculation of mass based on the segments of the beam

    sections 51

    2.7 Illustration of lumped mass assumption for a three-noded

    beam element 52

    2.8 The relationship between damping ratio and frequency 55

    2.9 Calculation of direction cosines of beam element 60

    2.10 Illustration of the quasi-static solution procedure 64

    3.1 Illustration of the loading on the pinned connected beam 68

    3.2 Comparison of the mid-span deflections of the elastic beam

    with geometrically linear dynamic modelling by VULCAN and

    ABAQUS 68

    3.3 Comparison of the mid-span deflections of the elastic beam

    with geometrically linear dynamic modelling by VULCAN and

    ABAQUS (from t = 4 to t = 6 second) 69

    3.4 Predicted mid-span displacements of the elastic beam with

    geometrically non-linear behaviour using different time steps 70

    3.5 Predicted mid-span displacements of the elastic beam with

    geometrically non-linear behaviour using different time steps

    (from 4.7 to 5.4 second) 70

    3.6 Single element model to e snap-through behaviour 71

    3.7 Deflection curves at the moving end of the element (ξ =1.0) 72

    3.8 Detailed deflection curves at the moving end of the element

    (ξ =1.0) 72

    3.9 Effect of damping during snap-through of the frame 74

    3.10 Single pitched roof frame with loading P on apex 74

    3.11 Deflections of the apex of the pitched frame 75

  • vii

    3.12 Deflections of the mid-point of the left rafter of the pitched

    frame 75

    3.13 Deflections of the mid-point of the right rafter of the pitched

    frame 76

    3.14 Initial configuration and loading arrangement of Franssen’s

    frame 77

    3.15 Vertical displacement at node A 78

    3.16 Horizontal displacement at node A 78

    3.17 Vertical displacement at node B 79

    3.18 Horizontal displacement at node B 79

    3.19 Vertical displacement at node C 80

    3.20 Horizontal displacement at node C 80

    3.21 Horizontal displacement at node D 81

    3.22 Deflected shape of the twin-bay steel portal frame 81

    3.23 General layout of the structure in the fire test 82

    3.24 The loading system for the portal frame 82

    3.25 Lateral support system 83

    3.26 Dimensions of base connection 83

    3.27 Recorded displacements from the third test 84

    3.28 The deformation of the rafter and purlins after the fire test 84

    3.29 The details of the base connection in the third test 85

    3.30 Comparison between numerical modelling and test results 86

    3.31 Deflected shape predicted by Vulcan in two dimensional view

    with pinned-base assumption 87

    3.32 Vertical displacements of the apex from different numerical

    models performed by Vulcan quasi-static analysis 88

    3.33 Z-Purlin section modelled by the equivalent I section 88

  • viii

    3.34 Deflected shape predicted by Vulcan in three-dimensional

    view 90

    3.35 Comparison between the test result and the two dimensional

    numerical models with nominally pinned bases 91

    3.36 Initial configuration of the pitched portal frame for the

    comparison between static and quasi-static analysis 92

    3.37 Vertical apex displacements of the frames with different

    columns 92

    3.38 Horizontal displacements of the left eaves with different

    columns 93

    3.39 Horizontal displacements of the right eaves of the frames

    with different columns 93

    3.40 Failure modes of the pitched portal frames with different

    column sections 94

    4.1 Vertical displacement of the apex of the frame 98

    4.2 Horizontal displacement of the left eaves of the frame 99

    4.3 Horizontal displacement of the right eaves of the frame 99

    4.4 Failure progress of portal frame with nominally rigid bases

    when only rafters are heated 100

    4.5 Vertical deflection of the apex 102

    4.6 Horizontal deflection of the left eaves 102

    4.7 Horizontal deflection of the right eaves 103

    4.8 Failure progress of portal frame with nominally rigid bases

    with only rafters heated case 103

    4.9 Layout of the pitched portal frame for parametrical studies 105

    4.10 Details of haunch models 106

    4.11 Vertical displacements at the apex for different haunch

    models 107

  • ix

    4.12 Horizontal displacements at the eaves for different haunch

    models 107

    4.13 The comparison between the simple assumption and test

    data for the initial stiffness of the steel column bases 109

    4.14 The comparison of the ultimate resistance of the bases

    obtained in different tests 109

    4.15 Illustration of the column base model 110

    4.16 Effect of base capacity: vertical displacements at apex 113

    4.17 Effect of base capacity: horizontal displacements at left

    eaves 113

    4.18 Effect of base capacity: horizontal displacements at right

    eaves 114

    4.19 Effect of base capacity: failure progress of the frame with

    pinned base 115

    4.20 Effect of base capacity: failure progress of the frame with

    semi-rigid base (a=0.5, k=0.1) 115

    4.21 Effect of base capacity: failure progress of the frame with

    semi-rigid base (a=0.5, k=0.2) 116

    4.22 Effect of base capacity: failure progress of the frame with

    semi-rigid base (a=0.5, k=0.5) 117

    4.23 Effect of base stiffness: vertical displacements at apex 119

    4.24 Effect of base stiffness: horizontal displacements at left

    eaves 119

    4.25 Effect of base stiffness: horizontal displacements at right

    eaves 120

    4.26 Effect of base capacity: failure sequence of the frame with a

    semi-rigid base ( a =4.0, k =0.5) 120

    4.27 Effect of load ratio: vertical displacement at apex 122

  • x

    4.28 Effect of load ratio: horizontal displacement at left eaves 123

    4.29 Effect of load ratio: horizontal displacement at right eaves 123

    4.30 Effect of haunch length: vertical displacement at apex 125

    4.31 Effect of haunch length: horizontal displacement at left eaves

    126

    4.32 Effect of haunch length: horizontal displacement at right

    eaves 127

    4.33 Effect of rafter section: vertical displacement at apex 128

    4.34 Effect of rafter section: horizontal displacement at left eaves 128

    4.35 Effect of rafter section: horizontal displacement at right eaves

    129

    4.36 Effect of column heating: vertical displacement at apex 131

    4.37 Effect of column heating: horizontal displacement at left

    eaves .. 131

    4.38 Effect of column heating: horizontal displacement at right

    eaves 132

    4.39 Effect of column heating: failure sequence of the frame 133

    4.40 Effect of column heating: failure sequence of the frame 133

    4.41 Heating profiles of the frame modelled 134

    4.42 Effect of different localised fire: vertical displacements at

    apex (part 1) 136

    4.43 Effect of different localised fires: failure sequence of frame

    under heating Profiles 1 and 7 137

    4.44 Effect of different localised fires: failure sequence of frame

    under heating Profiles 2 and 8 138

    4.45 Effect of different localised fires: vertical displacements at

    apex(part 2) 139

  • xi

    4.46 Effects of different localised fire: failure progress of frame

    under heating Profile 3 139

    4.47 Comparison of the bending moment diagrams given by

    heating Profiles 5 and 6 140

    4.48 Effects of purlins: a part of the portal frame in a

    three-dimensional view 141

    4.49 Effects of purlins: the model of the half frame 142

    4.50 Heating profiles assumed for the three dimensional model 143

    4.51 Comparison of vertical displacements of the apex of the

    central frame 144

    4.52 Vertical displacement of the apex of the internal frame 145

    4.53 Vertical displacement of the apex of the external frame 145

    4.54 Deflected shape of the frames at 1015°C in Test 1 146

    4.55 Deflected shape of the frame at 1015°C in Test 2 146

    4.56 Deflected shape of the frames in Test 3 147

    4.57 Deflected shape of the frames in Test 4 147

    5.1 Forces and moments acting on the frame 152

    5.2 Base overturning moment of the column changed with

    column inclination and rafter temperatures 155

    5.3 Vertical displacements of the apex of the frame with different

    column’s base strength 156

    5.4 Comparisons: current design model against the numerical

    model 157

    5.5 Vertical displacements of the apex of the frame with different

    column’s base strength 158

    5.6 Comparisons: the current design method against the

    numerical test results 159

    5.7 The boundary wall of the portal frame after fire 160

  • xii

    5.8 The model of Wong’s simple design method 163

    5.9 The haunch included model of Wong’s method 164

    5.10 Illustration of the second phase failure mechanism 166

    5.11 The iterative procedure for estimating the critical temperature

    of the second phase failure mechanism of the frame 167

    5.12 Model for the calculation of the re-stabilised position of the

    frame 168

    5.13 Haunch included model for the calculation of the re-stabilised

    position of the frame 170

    5.14 Haunch included model for the second phase failure

    mechanism of the frame 172

    5.15 Comparison of predicted critical temperatures between new

    design method and numerical analysis results for the frames

    without haunch 174

    5.16 Comparison of predicted critical temperatures between new

    design method and numerical analysis results for the frames

    with haunch 175

    5.17 Comparison of predicted critical temperatures for the first

    phase mechanism between new design method and

    numerical analysis 176

    5.18 Comparison of predicted critical temperatures for the first

    phase mechanism between new design method and

    numerical analysis 177

    5.19 Comparison of predicted critical temperatures for the first

    phase mechanism between new design method and

    numerical analysis, together with current design method 178

  • xiii

    5.20 Comparison of predicted critical temperatures for the second

    phase mechanism between new design method and

    numerical analysis 179

  • xiv

    LIST OF TABLES

    Table Page

    1 Mass-proportional damping factor and referential damping

    ratio values for single element model 71

    2 Load combinations 97

    3 List of the numerical studies conducted 143

    4 Recommended horizontal deflection limits at eaves level and

    the corresponding lean limit of columns in a pitched portal

    frame 154

  • xv

    NOTATION

    x,y,z global axis

    r,s,t elemental axis

    t time increment

    F internal force vector

    U displacement vector

    U velocity vector

    U acceleration vector

    K stiffness matrix

    M mass matrix

    R external load vector

    C damping matrix

    zyx FFF ,, force in direction x, y, z

    zyx MMM ,, moment about axis x, y, z

    wvu ,, translational displacement in directions x, y, z

    zyx ,, rotational displacement about axis x, y, z

    density of an element.

    L length of an element

    J rotational inertia

  • Chapter 1 Introduction

    1

    1. INTRODUCTION

    1.1. DESIGN OF PORTAL FRAME AT AMBIENT TEMPERATURE

    Over half of the usage of the steel in UK is on the primary framework of the industrial

    portal frames. For its significant advantages in simple assemblage and cost

    efficiency, the portal frame has become the most common construction form for

    single-storey industrial buildings in the UK. A typical single-span symmetrical portal

    frame, as shown in Figure 1.1 could have a span up to 50m, eaves height up to 10m

    and a roof pitch between 5° and 10°. Because the bending resistance of the

    connections at the eavess and apex determines the capacity of the frame, rigid

    connections between each column and the deep rafter section are required. In the

    most common situation, haunches are adopted at the eavess and apex to reduce the

    depth of the rafters. For ultimate limit state design at ambient temperature, such

    frames are usually designed on the assumption that the column bases act as

    frictionless hinges for convenience in foundation construction.

    Figure 1.1 Cross-section showing a portal frame and its restraints. (Salter et al.,

    2004)

    A dado masonry wall up to a height of 2.5m is normally provided along the edges of

    the building. It is required to be designed in compliance with the deflection criteria

    which are specified for masonry construction. In order to provide stability for the

  • Chapter 1 Introduction

    2

    building, both during erection and in the completed building under full loading, the

    resistance of the frames to wind load in the longitudinal direction is needed.

    Therefore, an adequate anchorage is required for the purlins and sheeting rails to

    ensure their function of restraining the rafters and columns. Also, bracing is required

    both in the plane of the rafters and vertically in the side walls. Purlins and side rails,

    to support the roof and side wall sheeting, are designed to be continuous over the

    rafters and also provide restraint to the rafters or columns. (Salter et al., 2004)

    Nominally pinned bases are normally chosen for the columns due to the difficulty and

    expense of providing moment-resisting bases. These nominally pinned bases are

    normally designed to provide resistance to the vertical loading on the roof and to

    horizontal loading caused by the wind. It is formed by a base plate, holding down

    bolts and a concrete foundation block as shown in Figure 1.2. If a moment-resisting

    base is required, a bigger lever arm for bolts, a stiffer base plate and additional

    gusset plates should be designed, as well as a much larger concrete foundation.

    Holding down bolts

    Base

    plate

    Bedding

    space

    Anchor

    plates

    Location

    tube

    Top of

    concrete

    foundation

    Holding down bolts

    Base

    plate

    Bedding

    space

    Anchor

    plates

    Location

    tube

    Top of

    concrete

    foundation

    Figure 1.2 A typical nominally pinned base.

  • Chapter 1 Introduction

    3

    1.2. FIRE CONCEPT

    The development of a natural fire is described by Purkiss (1996) as consisting of

    three periods: pre-flashover, post-flashover and decay, as shown in Figure 1.3.

    During the pre-flashover stage, the fire is still localized within the compartment, so

    the rise in the overall temperature is small. The highly non-uniform temperature

    distribution within the compartment, the hazard posed by the toxic gases, and the

    “back-draught” caused by sudden ventilation are also stressed by Wong (2002). At

    this stage, the enclosure is filled by hot air and smoke, with combustible products

    near the ceiling and cool air at the floor. When the temperature of the hot layer is high

    enough it can ignite all the rest of the unburned combustible materials within the

    room, and the fire develops to the flashover stage. Purkiss (1996) defined flashover

    as the moment when the local fire spreads to all the combustible material within the

    compartment, so the temperature in the compartment increases dramatically after

    flashover, because all the available fuel is burning at this stage. The fire reaches its

    highest temperature at this stage, and the duration of the post-flashover period

    largely depends on the exposed surface of the fuel and the ventilation conditions of

    the fire compartment. When the amount of combustible material begins to reduce

    after a period of steady burning, the heating rate decreases and the compartment

    begins to cool. Normally, it takes a longer time to achieve flashover in a large

    enclosure.

  • Chapter 1 Introduction

    4

    Figure 1.3 Development of a natural fire.

    For fires in large compartments, the concept of progressive burning is discribed by

    Buchanan (2001), on the basis of fire tests and numerical modelling. It is claimed that

    the development of the fire at different positions within the compartment largely

    depends on the distance from the fire source. The maximum temperature is

    developed progressively at different positions due to the delayed burning of the fuel

    at more remote positions.

    The industrial portal frame is a special case in fire. When a fire is ignited in a

    single-storey industrial frame, cool air is drawn into the space, and hot air and smoke

    rise to the roof due to the buoyancy caused by the fire plume. The hot gas layer can

    then spread across the ceiling and either escape at the edge of the ceiling or decend

    towards the floor, provided that the ceiling is closed. However, in most portal frames,

    the hot air can escape either through skylights in the roof, or through openings

    caused by the burning out of flammable cladding, so that flashover is unlikely to

    happen in portal frames. The developing fire concept was introduced by O’Meagher

    (1992) into numerical modeling to investigate the behaviour of industrial steel frames

    at the pre-flashover stage. A possible heat release rate senario for industrial portal

    frame is presented by Buchanan (2001) as the sequence shown in Figure 1.4.

    Time

    Temperature

    Flashover

    Pre-flashover Post-

    flashover Decay

  • Chapter 1 Introduction

    5

    Figure 1.4 Heat release rate for a fire in an industrial building (Buchanan, 2001).

    To assess the performance of building materials and structural elements, a standard

    heating curve is defined for full-scale fire tests. This is the so-called “Standard

    Fire”(Buchanan, 2001). In the UK, the widely-used Standard Fire temperature-time

    ( tT ) curve is defined in ISO834 (ISO, 1975) which is defined by Equation (1.1) as

    0100 8log345 TtTT (1.1)

    where T (0C ) is the furnace temperature at time t, 0T (0C ) is the initial furnace

    temperature , and t is the time in minutes. This is also adopted as the design fire in

    Eurocode 1 Part 1.2 (CEN, 2002) for wood-based, or cellulosic, fires.

    1.3. STEEL PROPERTIES AT ELEVATED TEMPERATURES

    For steel at ambient temperature, plastic yield can be observed as a sudden change

    in the stress-strain curve. However, the change of steel strain at elevated

    temperatures is determined as a combination of thermal strain, creep strain and

    stress-related strain, so the mechanical properties of steel at elevated temperatures

    Heat release rate

    Ventilation

    Control

    Fuel Control

    Time

    Growth

    Period

    Skylights melt

    Roof collapse

    Decay period

  • Chapter 1 Introduction

    6

    are quite different from those at ambient temperature. Some typical stress-strain

    curves for steel at elevated temperatures presented by Harmathy (1993) show that

    the elastic tangent modulus decreases gradually before the steel reaches plastic

    yield at elevated temperatures, and that the ultimate strength of steel is higher than

    that of cold steel when it is heated to a temperature range between 200°C and

    320°C.

    In 1988, a series of tensile capacity tests on hot-rolled steel was performed by Kirby

    and Preston (1988). Strength reduction factors, which are the ratios of the steel

    strength at elevated temperature to its strength at ambient temperature, was

    obtained from these tests. The definitions of the stress-strain curves for steel at

    elevated temperatures in BS5950 Part 8 (BSI, 2003), Eurocode 3 Part 1.2 (CEN,

    2005a) and Eurocode 4 Part 1.2 (CEN, 2005c) are based on this test data.

    0

    50

    100

    150

    200

    250

    300

    350

    400

    450

    500

    0 0.1 0.2 0.3 0.4 0.5 0.6

    Fast speed (0.7mm/min)

    Middle speed (3.1mm/min)

    Slow speed (6mm/min)

    EC-Curve

    Stress (N/mm2)

    Strain

    0

    50

    100

    150

    200

    250

    300

    350

    400

    450

    500

    0 0.1 0.2 0.3 0.4 0.5 0.60

    50

    100

    150

    200

    250

    300

    350

    400

    450

    500

    0 0.1 0.2 0.3 0.4 0.5 0.6

    Fast speed (0.7mm/min)

    Middle speed (3.1mm/min)

    Slow speed (6mm/min)

    EC-Curve

    Fast speed (0.7mm/min)

    Middle speed (3.1mm/min)

    Slow speed (6mm/min)

    EC-Curve

    Stress (N/mm2)

    Strain

    Figure 1.5 Stress-strain curves for steel tested at 550°C (Renner, 2005).

  • Chapter 1 Introduction

    7

    A group of tensile tests on S275 steel aimed to study the effect of strain-rate was

    performed by Renner (2005) at Sheffield University. The tests were focused on the

    steel properties between 400°C and 700°C, and three displacement speeds:

    0.7mm/min, 3.1mm/min and 6mm/min were applied. The results presented in Figure

    1.5 prove that the ultimate strength of the heated steel changes with the loading

    speed, as a result of the re-arrangement of microstructure during the deformation. It

    is also observed that the true stress at 15% strain is higher than the assumption

    made in Eurocode 3 (CEN, 2005a). Results shown in Figure 1.6 are an example

    taken from these tests.

    0

    50

    100

    150

    200

    250

    300

    350

    400

    450

    500

    0 0.1 0.2 0.3 0.4 0.5 0.6

    Strain

    Stress (N/mm2)

    ambient°C Test

    ambient°C EC

    400°C Test

    400°C EC

    450°C Test

    450°C EC

    500°C Test

    500°C EC

    550°C Test

    550°C EC

    600°C Test

    600°C EC

    700°C Test

    700°C EC

    0

    50

    100

    150

    200

    250

    300

    350

    400

    450

    500

    0 0.1 0.2 0.3 0.4 0.5 0.6

    Strain

    0

    50

    100

    150

    200

    250

    300

    350

    400

    450

    500

    0 0.1 0.2 0.3 0.4 0.5 0.6

    Strain

    Stress (N/mm2)

    ambient°C Test

    ambient°C EC

    400°C Test

    400°C EC

    450°C Test

    450°C EC

    500°C Test

    500°C EC

    550°C Test

    550°C EC

    600°C Test

    600°C EC

    700°C Test

    700°C EC

    ambient°C Test

    ambient°C EC

    400°C Test

    400°C EC

    450°C Test

    450°C EC

    500°C Test

    500°C EC

    550°C Test

    550°C EC

    600°C Test

    600°C EC

    700°C Test

    700°C EC

    Figure 1.6 Stress-strain curves of steel tested at the medium strain-rate (Renner,

    2005).

    The stress-strain curves at elevated temperatures have been defined by a

    Ramberg-Osgood (Ramberg & Osgood,1943) type of equation:

  • Chapter 1 Introduction

    8

    TN

    T

    T

    T

    TT

    bBaA

    01.0 (1.2)

    where the value of TA , TB and TN are temperature-dependent.. The terms T

    and T are the strain and stress at the temperature T , respectively.

    In Eurocode 3 Part 1.2 (CEN, 2005a), the stress-strain curves at elevated

    temperature are represented by one elliptical and three linear equations. In the first

    stage, the stress increases with strain following the slope ,aE until the stress

    exceeds the proportional limit ,pf and a perfect plastic stress plateau is defined

    from 2% strain to 15% strain at a constant stress which equals the effective yield

    stress ,yf . An elliptical curve is used to connect the linear elastic and plastic

    curves. The stress decays to zero linearly from 15% to 20% strain. The detailed

    formulation of the curve is given in Figure 3.1 of Eurocode 3 Part 1.2 and values of

    ,aE , ,pf and ,yf at elevated temperatures are givien in Table 3.1 of Eurocode 3

    Part 1.2.

    The stress-strain curves for S275 steel calculated using the Ramberg-Osgood

    (Ramberg & Osgood, 1943) model (BSI, 1985) and the Eurocode model are

    presented in Figures 1.7 and 1.8. It is shown that Ramberg-Osgood is very close to

    the Eurocode model when the strain is less than 2%. After this, the Eurocode model

    gives much lower effective stress than the Ramberg-Osgood model.

  • Chapter 1 Introduction

    9

    0

    50

    100

    150

    200

    250

    300

    0 0.005 0.01 0.015 0.02

    Strain

    20°C

    100°C

    200°C

    300°C

    400°C

    500°C

    600°C

    700°C

    800°C

    Stress (N/mm2)

    0

    50

    100

    150

    200

    250

    300

    0 0.005 0.01 0.015 0.02

    Strain

    20°C

    100°C

    200°C

    300°C

    400°C

    500°C

    600°C

    700°C

    800°C

    Stress (N/mm2)

    Figure 1.7 The comparison of the stress-strain curves between the

    Ramberg-Osgood (dashed line) and Eurocode model (solid line) up to 2% strain.

    0

    50

    100

    150

    200

    250

    300

    350

    400

    450

    500

    0 0.05 0.1 0.15 0.2

    Strain

    20°C

    100°C

    200°C

    300°C

    400°C

    500°C

    600°C

    700°C

    800°C

    Stress (N/mm2)

    0

    50

    100

    150

    200

    250

    300

    350

    400

    450

    500

    0 0.05 0.1 0.15 0.2

    Strain

    20°C

    100°C

    200°C

    300°C

    400°C

    500°C

    600°C

    700°C

    800°C

    Stress (N/mm2)

    Figure 1.8 The comparison of the stress-strain curves between the

    Ramberg-Osgood (dashed line) and Eurocode models (solid line) up to 20% strain.

  • Chapter 1 Introduction

    10

    Figure 1.9 Strength reduction factors from the stress-strain relationships of steel at

    elevated temperatures according to the Eurocode and British Standard.

    For design proposes, the strength retention factors for steel strains of 0.5%, 1.5%

    and 2% are given in BS5950 Part 8 (BSI, 2003). The strain limit required for a

    composite member is 2% and for a non-composite member is 1.5%. 0.5% strain is

    required for all other members. In Eurocode 3 Part 1.2 (CEN, 2005a), 2% strain is

    used in almost all calculations. Figure 1.9 shows that the strength reduction factors

    obtained from BS5950 and Eurocode are similar; this is not surprising since they are

    all based on the result from the same test programme (Kirby & Preston,1988).

    Thermal elongation of steel is critical to structural behaviour at elevated

    temperatures. It can lead to the thermal bowing due to temperature gradients, or

    buckling when the beam or slab is restrained at the boundary and an extra internal

    compression is generated on the cross-section. Because the internal forces through

    out the structure are affected by the thermal strains in the structural members, the

    load distribution within the structure become complex under high temperatures. Also,

    0

    0.2

    0.4

    0.6

    0.8

    1

    0 200 400 600 800 1000

    0.5% strain BS5950 Part 8 0.5% strain Eurocode 3&4

    1.5% strain BS5950 Part 8 1.5% strain Eurocode 3&4

    2% strain BS5950 Part 8 2% strain Eurocode 3&4

    Strength reduction factor

    Temperature (°C)

  • Chapter 1 Introduction

    11

    for a long span structure, such as the single-span pitched portal frame, the

    elongation of the members can be significant and can not be ignored in design.

    0

    4

    8

    12

    16

    20

    0 200 400 600 800 1000 1200

    Elongation 310/ ll

    Temperature (°C)

    0

    4

    8

    12

    16

    20

    0 200 400 600 800 1000 1200

    Elongation 310/ llElongation 310/ ll

    Temperature (°C)

    Figure 1.10 Thermal elongation of carbon steel as a function of the temperature

    (CEN, 2005a)

    The thermal elongation of steel is defined as a function of temperature in BS5950

    Part 8 (BSI, 2003) and Eurocode 3 Part 1.2 (CEN, 2005a). As shown in Figure 1.10,

    the steel elongates quite linearly with increasing temperature until 750°C, and then

    stops from 750°C to 860°C due to a phase-change of the microstructure of steel. The

    steel then continues to expand linearly when the temperature is beyond 860°C.

    The basic steel properties at 20°C, assumed for the numerical studies, are listed as

    follows:

    Mass density: 3/7850 mkg ;

    Young’ modulus: MPaE 210000 ;

    Yield strength for S275 Steel: MPaf y 275 .

    The thermal properties of steel adopted in this study are basically those according to

    Eurocode 3 Part 1.2 (CEN, 2005a). Considering that the decay of stress beyond 15%

  • Chapter 1 Introduction

    12

    strain could be much slower than the assumption in Eurocode, in this study the steel

    stress remains constant as the ultimate stress when the strain exceeds 15%.

    1.4. CURRENT DESIGN METHOD FOR PORTAL FRAMES IN FIRE

    In UK, the fire safety of the buildings has to comply with the Building Regulations

    2000, Approved Document B (DETR, 2006). To prevent the collapse of buildings in

    fire, a degree of fire protection of the structural elements is required for multi-storey

    buildings, but the main concern for single-storey buildings is stopping fire spread

    between buildings. In order to meet this requirement, when a single-storey building is

    designed to satisfy fire safety requirements, the distance from its external wall to the

    site boundary must be at least 15m, or fire protection of the external wall is

    necessary. Moreover, all structural elements which are used to support the external

    wall must have the same fire resistance as the boundary wall itself. A portal frame is

    considered as a single structural element, due to the rigid connection between rafters

    and columns, so if any part of it needs to be protected against fire, the whole frame

    has to be protected. As a result, the whole portal frame has to be fully protected

    against fire to guarantee the longitudinal stability of the boundary wall when the

    frame is in a fire boundary condition. Fire protection to the whole portal frame is very

    expensive compared with the cost of the portal frame itself. To avoid this, a simple

    design method (Simms & Newman, 2002), which allows no fire protection for portal

    frames, was published by the Steel Construction Institute. This method is widely

    used in the UK.

    In order to guarantee the longitudinal stability of the boundary wall, the inclination of

    the columns in the boundary frame should be limited if they are not protected against

    fire. When the roof collapses below the eavess level, due to the mechanism shown in

    Figure 1.11, the catenary force generated on the rafters becomes dominant in pulling

    the columns inward, and causes an overturning moment (OTM ) at the column

  • Chapter 1 Introduction

    13

    bases. The idea of Newman’s method is to specify a very strong base connection to

    resist the OTM generated at the column bases.

    Figure 1.11 Failure mechanism used in current design method (Newman, 1990).

    Referring to Figure 1.12, the vertical reaction RV , the horizontal reaction RH and

    OTM at the column bases can be calculated by Equations (1.3) to (1.5).

    wallofweightdeadSLWV fR 2

    1 (1.3)

    Y

    M

    G

    CMSGAWKH C

    p

    fR10

    (1.4)

    10065.0 Cpf

    M

    G

    CYM

    Y

    BASGAWKOTM (1.5)

    G

    L

    Y

    RV

    RHOTM

    G

    L

    Y

    RV

    RHOTM

    Figure 1.12 Frame dimensions used in calculation of overturing moment

    (Newman, 1990).

    Fire hinges

  • Chapter 1 Introduction

    14

    where

    G

    GLB

    8

    22 (1.6)

    and

    fW = load at time of collapse;

    S = distance between frame centers;

    G = distance between ends of haunches;

    Y = vertical height of end of haunch;

    L = span;

    pM = plastic moment of resistance of rafter

    cM = plastic moment of resistance of column

    K = 1 for single bay frames or is taken from Table 2 of SCI Publication 087

    (Newman, 1990);

    A and C are taken from Table 1 of SCI Publication 087 (Newman, 1990).

    In the latest design guide, SCI Publication P313 (Simms&Newman, 2002), for single

    storey steel frame buildings in fire boundary conditions, this simple method is still

    recommended for the design of single- or multi-span symmetrical pitched portal

    frames, either with or without haunches. Instead of using the single value of A for

    frames with various span-to-height ratios, the new design guide gives modified

    values of A for frames with low span-to-height ratio. In addition, the derivation of

    the simple calculation method for symmetrically pitched portal frames is given based

    on the same assumptions used in the old design guide (Newman, 1990).

    1.5. BEHAVIOUR OF PORTAL FRAMES IN FIRE

    Many studies(De Souza Jonior et al., 2002, Bong, 2005, Vassart, et al., 2005, Moss

    et al., 2006) have been carried out on the thermal and structural performance of

  • Chapter 1 Introduction

    15

    single-storey industrial buildings. Only a limited number of fire tests (Wong, 1999,

    2001) have been carried out on the portal frames in the past 20 years. Thanks to the

    development of advanced finite element software, the behaviour of industrial steel

    frames at elevated temperatures can now be modelled in two- and three-dimensions.

    The basic failure mechanism of industrial steel frames and the effect of the

    secondary elements under different heating scenarios have been investigated using

    such models. Although the fire safety regulations differ in different countries, with

    different design goals, the resistance of fire-walls is a common concern for industrial

    buildings under fire conditions. Column bases may remain at a relatively low

    temperature, but the effect of their strength and flexibility can be significant on the

    global behaviour when the rafters are very hot and the catenary forces on the column

    tops are significant. Previous works related to the behaviour of industrial portal

    frames under fire conditions are briefly summarised in the next section.

    1.5.1. FIRE TESTS

    In order to investigate the behaviour of industrial frames in fire, three fire tests on a

    scaled pitched-roof portal frame were performed by Wong (Wong et al., 1999) at the

    University of Sheffield. In the first experiment (see Figure 1.13), the rafter of one

    frame was heated by a line fire under sufficient ventilation. The fire was produced by

    liquid heptane contained by a metal tray hanging below the frame, supported by a

    separate frame, and lasted for about 10 minutes; some parts of the steel were heated

    to just over 900°C. A certain amount of deflection was recorded, but the frame did not

    totally collapse. The second experiment (See Figure 1.14) was carried out on

    another internal bay of the same frame. In order to obtain a longer-lasting fire, the

    liquid fuel was replaced by timber cribs. This test lasted for well over 40 minutes,

    before the fire was manually extinguished. The compartment temperature achieved a

    state of equilibrium after about 10 minutes, and this continued for at least 30 minutes.

  • Chapter 1 Introduction

    16

    The maximum steel temperature recorded in the test was only about 800°C, and no

    collapse mechanism of the portal frame was observed during the test.

    Figure 1.13 The first test: heating of the whole rafter (Wong, 2001).

    Figure 1.14 The second test: edge fire (Wong, 2001).

    In order to produce a structural collapse, the overall rafter-heated test was repeated

    on the rebuilt internal bay, with some improvements to the test arrangement.

    Insulation was applied to the roof so that the temperature of the rafter could be

    maintained for longer, and the entire rafter section could be heated evenly by the fire.

    It had been shown in the first test that the use of liquid heptane as fuel was efficient in

    heating, but that the heating time was limited by the amount of fuel, so a controllable

    fuel supply system, which could provide sufficient fuel for burning until the collapse of

    the frame, was devised. For convenience in the numerical modelling, the uncertainty

  • Chapter 1 Introduction

    17

    of the base rotational stiffness was minimized by artificially creating pinned bases for

    the columns.

    In the test the fire lasted for approximately 500 seconds, and the average gas

    temperature was around 900°C. The column sections were not exposed to much

    radiation, and remained relatively cool. According to the test data, the apex was seen

    to start to deflect downward after about 280 seconds, and then underwent a vertical

    dive as both raters were seen to collapse rapidly. This phenomenon is believed to be

    a snap-through failure of the rafters. Both eavess were initially deflected outward due

    to the thermal expansion of the rafters, until the snap-through took place, and they

    were then pulled inward by the catenary force generated in the rafters which was in

    highly curvature. The different horizontal displacements at the eavess indicated that

    the runaway deflection of the portal frame was not induced by a ‘beam mechanism’

    but more likely by a ‘combined mechanism’. The post-test inspection showed that

    three plastic hinges (marked in Figure 1.15), generated near each eaves and to the

    right of the apex could have led to the snap-though collapse observed in the test.

    Figure 1.15 The deformed portal frame after the third fire test

    Plastic Hinges

  • Chapter 1 Introduction

    18

    1.5.2. BEHAVIOUR OF SINGLE-STOREY PORTAL FRAMES IN FIRE

    In industrial warehouses, the fire-wall is normally made of masonry or concrete, and

    can either be built embedded between the flanges of the steel column, or stand as a

    cantilever wall. If the fire-wall is supported laterally by the steel columns of the portal

    frames, its stability would mainly be based on the amount of lateral movement of the

    column in fire.

    As early as 1980, the behaviour of steel portal frames in accidental fires was

    described as the result of a study (CONSTRADO, 1979) of fires in a number of portal

    frames in the UK. At the early stage of a fire, the frame begins to heat up and

    expand, so the apex deforms upward while the eavess deform outward.

    Subsequently, due to the moments caused by the increasing thermal expansion of

    the rafters, plastic hinges tend to form at the maximum moment positions on the

    rafters, which are at the ends of the haunches and near to the apex. Because these

    hinges are generated due to the degradation of steel at elevated temperature, they

    are described as “fire hinges”. The formation of two or three fire hinges completes the

    mechanism in the rafter which leads to the collapse of the pitched roof. When the

    rafters collapse to near eavess level and the pitched roof deforms to a roughly level

    shape, as shown in Figure 1.16, the rafter is still laterally restrained by the purlins,

    and is capable of supporting itself, and the columns are still upright. When the rafter

    falls below eavess level, most of its stiffness is lost and it tends to deform to a

    catenary, and the pull-in of the tops of the columns becomes significant. It is found

    that columns with fixed bases stand when the rafters are collapsing, while in other

    cases they can be pulled inward by the collapse of the rafters when the bases are

    pinned or partially fixed. Therefore, the design of the bases becomes important when

    the rafters collapse below eavess level.

    A typical variation of the overturning moment at the column base with time, after a

    fire is ignited in a pitched portal frame is described by CONSTRADO (1980) as

  • Chapter 1 Introduction

    19

    shown in Figure 1.16. At an early stage, the thermal expansion of the heated roof

    pushes the columns outward, so that the base rotates outwards. The moment at the

    base then reduces to zero when the rafter deforms to roughly eavess level, with the

    columns standing upright. When the rafter collapses below eavess level, the

    catenary force developed in the rafters becomes dominant which pulls the columns

    inwards, so that the bases tend to rotate in the opposite direction and the moment at

    the base increases again. It is believed that the stability of portal frames in fire is

    mainly determined by the resistance provided the column base connections. In other

    words, inclination of the column should be stopped provided that the moment

    resistance at the column base is bigger than the maximum overturning moment

    generated during the collapse of the rafters.

    OTM

    Time

    Maximum

    outward

    inclination

    No

    inclination

    Inward

    inclination

    OTM

    Time

    OTM

    Time

    Maximum

    outward

    inclination

    Maximum

    outward

    inclination

    No

    inclination

    No

    inclination

    Inward

    inclination

    Inward

    inclination

    Figure 1.16 Variation of overturning moment with the deformation of the portal frame

    in fire.

    In order to compare the behaviour of single-storey industrial frames against the

    Building Code of Australia (BCA, 1990), two-dimensional numerical modelling of

  • Chapter 1 Introduction

    20

    portal frames under seven critical heating profiles (see Figure 1.17) in a developing

    fire situation was performed by O’Meagher et al. (1992) using ABAQUS. Pitched

    portal frames with and without haunches were modelled two-dimensionally, and

    nominal rotational stiffness was applied at the column bases. The effects of column

    fire protection, different heated regions of the rafters, and the lateral restraint

    provided by adjacent cooler parts of the roof were considered. The results showed

    that single-span pitched portal frames, tested with nominal moment resistance at the

    column bases, always collapsed inward so that they would not injure people outside

    the building, or damage adjacent buildings, as required by the Building Code of

    Australia.

    L

    L/4

    L

    L/2

    Situation A Situation B

    L

    L/4

    L

    L/4

    L

    L/2

    Situation A Situation B

    L

    L/4

    L

    L/2

    Situation C Situation D

    L

    L/4

    L

    L/2

    Situation C Situation D

    L

    3L/4

    L

    Situation E Situation F

    L

    3L/4

    L

    Situation E Situation F

    L

    Situation G

    Temperature = T

    Temperature = 3T/4

    CoolL

    Situation G

    Temperature = T

    Temperature = 3T/4

    Cool

    Temperature = TTemperature = T

    Temperature = 3T/4Temperature = 3T/4

    Cool

    Figure 1.17 Heating situation considered in O’Meagher et al. (1992)’s model.

  • Chapter 1 Introduction

    21

    The effects of the load ratio, span and column height, heating profiles, horizontal load

    and rotational stiffness at the bases were investigated by Wong (2001) using Vulcan

    (Huang, et al. 2003a, 2003b & 2004). Portal frames with different spans, column

    heights and different loadings were modelled two-dimensionally. The results

    presented in Figure 1.18 show that the load ratio has the greatest effect on the failure

    temperature of the frame. Frames heated by different heating profiles, including both

    symmetrical and localised fire scenarios, initially collapsed in a combined

    mechanism, and the heated column showed no significant influence on the limiting

    temperatures. The semi-rigid base represented by a rotational spring element, which

    gives a certain amount of rotational stiffness, showed a beneficial effect on the

    collapse temperature of the rafters compared with the pinned base as shown in

    Figure 1.19.

    400

    450

    500

    550

    600

    650

    700

    750

    0 2 4 6 8 10 12

    Span/Height Ratio

    Failure Temperature (°C)

    Load Ratio =0.2

    Load Ratio =0.4

    Load Ratio =0.7

    Load Ratio =0.5

    0.2 span 300.2 ht 70.2 ht 40.2 span 500.4 ht 40.4 span 500.5 span 300.5 ht 70.5 ht 40.5 span 500.7 span 300.7 ht 70.7 ht 40.7 span 50

    Load Ratio Dim (m)

    400

    450

    500

    550

    600

    650

    700

    750

    0 2 4 6 8 10 12

    Span/Height Ratio

    Failure Temperature (°C)

    Load Ratio =0.2

    Load Ratio =0.4

    Load Ratio =0.7

    Load Ratio =0.5

    0.2 span 300.2 ht 70.2 ht 40.2 span 500.4 ht 40.4 span 500.5 span 300.5 ht 70.5 ht 40.5 span 500.7 span 300.7 ht 70.7 ht 40.7 span 50

    Load Ratio Dim (m)

    Figure 1.18 Failure temperatures of portal frames (Wong, 2001) (ht – height of

    column in metres).

  • Chapter 1 Introduction

    22

    0

    200

    400

    600

    800

    1000

    1200

    0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9

    Load Ratio

    Temperature (°C)

    0

    5

    10

    15

    20

    25Percentage %

    Failure Temp for pinned bases (°C)

    Failure Temp for Semi-Rigid Bases (°C)Actual Difference in °C

    Difference in %

    0

    200

    400

    600

    800

    1000

    1200

    0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9

    Load Ratio

    Temperature (°C)

    0

    5

    10

    15

    20

    25Percentage %

    Failure Temp for pinned bases (°C)

    Failure Temp for Semi-Rigid Bases (°C)Actual Difference in °C

    Difference in %

    Figure 1.19 Comparison of failure temperatures with pinned and semi-rigid bases

    (Wong, 2001)

    The comparisons between two- and three-dimensional analyses on a laterally

    unrestrained single-span portal frame performed by de Souza Junior et al.(2002)

    using SAFIR (2003) shows that the simulation of the structural behaviour of a

    single-storey industrial portal frame by two-dimensional modelling in which lateral

    instability of the members is not taken into account is not realistic. The collapse

    progress of a single portal frame in fire due to out-of-plane deformation was also

    observed in three-dimensional analysis by Bong (2005). Because no lateral restraint

    was applied, in three-dimensional analysis the fames collapsed at almost the same

    load level regardless of whether the column bases were pinned or fixed, as shown in

    Figure 1.20.

  • Chapter 1 Introduction

    23

    Pinned Support Frame Fixed Support Frame

    Time = 16 second

    Time = 19 second

    Time = 17 second

    Time = 20 second

    Time = 18 second

    Time = 21 second

    Figure 1.20 Variation of deflected shape showing the out-of-plane collapse of frames

    heated by the ISO834 fire (UDL=1.269kN/m) (Bong, 2005).

    Another solution to provide stability to the boundary fire-wall is to build it seperate

    from the boundary frame. A clearance between the frames and the fire-wall is

    essential in this case, to prevent the damage caused by excessive deformation of the

    steel frames in fire. It is observed from a series of numerical simulations on

    single-storey steel frames in the USA (Hosam et al., 2004) that the later deformation

    of the frame could be caused either by the expansion of the steel roof, or by outward

    buckling of the columns if a localized fire was ignited close to the column nearest to

    the fire wall. If the fire is assumed to occupy both spans in a double-span frame, the

    collapse of the frame is likely to be caused by inward collapse of the heated column

  • Chapter 1 Introduction

    24

    which is pulled in by the catenary force generated in the beam. The minimum

    clearance between frames and fire-walls is mainly determined by the spatial extent of

    the fire, and it can be reduced if stiffer or shorter columns, which provide more

    restraint to the frame, are adopted. The simulations also found that higher loads on

    the roof could reduce both the time to collapse and the maximum lateral expansion of

    the frames, which means that the response of the frame in fire will depend on the

    load remaining on the roof.

    1.5.3. OVERALL BEHAVIOUR OF INDUSTRIAL FRAMES IN FIRE

    Industrial sheds are normally formed by several parallel frames. They are connected

    in the out-of-plane direction by secondary members such as purlins, and the sheeting

    anchored on the purlin finishes, the roof and part of the external wall. The purlins are

    relatively slender, so they are heated quickly and fail earlier in a real fire. As

    mentioned in Section 1.2, fires rarely occupy the whole industrial building

    immediately, so the frames near to the fire source can be very hot while the rest of

    the frames remain relatively cold. The collapse of hot frames could be suppressed by

    the restraint from secondary members connected to the relatively cold frames, and

    therefore the overall behaviour of whole industrial buildings may be different from

    that of individual frames.

    It is postulated by O’Meagher et al. (1992) that the collapsed frame could act as

    “anchors” to the rest of the building as shown in Figure 1.21, provided that the force

    developed in the purlins is very small and that they have sufficient capacity at high

    temperatures. Therefore, the nearby frames will deform in a similar mode as the

    collapsed frame, so the whole building will collapse in an inward mode which is

    acceptable under the Building Code of Australia (AUBRCC, 1990).

  • Chapter 1 Introduction

    25

    Figure 1.21 Overall building behaviour (O’Meagher et al., 1992).

    It is observed in the three-dimensional modelling by de Souza Junior et al. (2002)

    that, although the stability of the portal frame was not endangered by the buckling of

    the purlins, after this failure the purlins tend to deform in a catenary shape which may

    contribute to the lateral stability of the portal frame at a later stage, as shown in

    Figure 1.22.

    Figure 1.22 Deflected shape for the model with purlins at the moment of failure,

    with an amplification factor of 10 ( de Souza Junior et al., 2002).

    Wong (2001) recognized that the analysis performed by the preliminary static Vulcan

    model including portal frames and purlins, could not easily be extended to high

    temperatures because of the buckling failure of purlins at an early stage. This

    problem was overcome by adding imaginary members (see Figure 1.23) that connect

    the purlins together to simulate the effect of the restraint from the roof cladding.

    These imaginary members were not heated in the analysis, which implies that the

  • Chapter 1 Introduction

    26

    cladding is infinitely strong and will not detach in the fire condition. This assumption

    makes the roof stronger than in reality. It was found from the analysis that the purlins

    lose stability very quickly in comparison with the portal frame when the entire roof

    was heated, so the two- and three-dimensional analyses show very similar results

    when different load ratios were tested (Figure 1.24).

    Portal frames

    Purlins

    Imaginary membersHeated members

    Unheated members

    Portal frames

    Purlins

    Imaginary membersHeated members

    Unheated members

    Figure 1.23 Deflected shape of the entire-roof-heated case at 660°C steel

    temperature. (Wong, 2001).

    -1400

    -1200

    -1000

    -800

    -600

    -400

    -200

    0

    200

    0 100 200 300 400 500 600 700 800

    Temperature (°C)

    Vertical Displacement (mm)

    Load Ratio 0.2 - 2D Analysis

    Load Ratio 0.2 - 3D Analysis

    Load Ratio 0.5 - 2D Analysis

    Load Ratio 0.5 - 3D Analysis

    -1400

    -1200

    -1000

    -800

    -600

    -400

    -200

    0

    200

    0 100 200 300 400 500 600 700 800

    Temperature (°C)

    Vertical Displacement (mm)

    Load Ratio 0.2 - 2D Analysis

    Load Ratio 0.2 - 3D Analysis

    Load Ratio 0.5 - 2D Analysis

    Load Ratio 0.5 - 3D Analysis

    Load Ratio 0.2 - 2D Analysis

    Load Ratio 0.2 - 3D Analysis

    Load Ratio 0.5 - 2D Analysis

    Load Ratio 0.5 - 3D Analysis

    Figure 1.24 Vertical displacement at apex. 2D vs 3D analysis (Wong, 2001).

  • Chapter 1 Introduction

    27

    The effect of the different fire senarios shown in Figure 1.25 as a three-dimensional

    model was tested by Wong (2001). The tests showed that the major deformation

    always occurs to the rafters, especially with low load ratios and long-span portal

    frames. The comparison of vertical deflections at the apex for frames under different

    fire senarios shows that the heating of columns has little effect on the overall

    behaviour of the portal frame, whether the purlins are heated fully or partially.

    Vertical Displacement (mm)

    Steel Temperature (°C)

    (a)

    (b)

    (c)

    (d)

    Entire roof

    heated

    Vertical Displacement (mm)

    Steel Temperature (°C)

    (a)

    (b)

    (c)

    (d)

    Entire roof

    heated

    Figure 1.25 Vertical displacements at apex of the central frame (Wong, 2001)

    A comprehensive study (Bong, 2005) on the overall behaviour of a full-sized

    industrial frame shown in Figure 1.26, was carried out at the University of Canterbury

    in 2005. In this study, a three-dimensional numerical model was set up using the

    advanced finite element analysis software SAFIR (2003). The effects of different

    support conditions at the column bases, the out-of-plane restraint to columns and the

    axial restraint of purlins were investigated. Three heating profiles which simulate fully

    developed and localized fires near the centre or the end of the building were tested

    on frames with two extreme base support conditions: fixed and pinned. A recovery of

    the frame’s stability could be observed if the axial restraint from the purlins was

  • Chapter 1 Introduction

    28

    applied when the frame was heated by the ISO standard fire (ISO, 1975) up to 1

    hour. This was also observed in pin-supported frames with restraint from purlins

    heated by the External Fire curve (BSI, 1999), in which a well-ventilated fire is

    simulated and the maximum temperature is taken as 660°C. It was concluded from

    an inspection of the deformed shape that the degree of the axial restraint from purlins

    is much less important to the failure mode than the flexural fixity of the bases of the

    columns.

    Figure 1.26 The analytical model in Bong’s study (Bong, 2005).

    Time=14.14 minutes Time=19.6 minutes

    Figure 1.27 Deflected shapes

    immediately before and after the rapid

    sagging of roof of the pinned-base case

    with purlin axial restraint (Peter et al.,

    2006)

    Figure 1.28 Sidesway collapse of the

    pinned-base case without purlin axial

    restraint (Peter et al., 2006)

  • Chapter 1 Introduction

    29

    Time =14.92 minutes

    Figure 1.29 Inward collapse of the

    fixed-base case without purlin axial

    restraint (Peter et al., 2006)

    Time =15.9 minute

    Figure 1.30 Finally deflected shape of the

    pinned-base case without purlin axial

    restraint and with full concrete

    encasement of columns (Peter et al.,

    2006)

    The passive fire protection achieved by concrete encasement of either the full height

    or two-thirds of the height of the column was also simulated by Bong (2002). Frames

    with partially fixed bases, which were simulated by halving the stiffness and strength

    of the elements adjacent to the fixed bases, were also tested when passive fire

    protection to columns was considered. Protection of columns with pinned bases

    shows no improvement in structural performance. For frames with partially rigid and

    rigid bases, because the strength and stiffness of the concrete-encased parts of the

    steel columns are largely unaffected, protected columns remain relatively straight

    during the fire.

    The structural fire performance of steel portal frame buildings was also studied by

    Peter et al. (2006) on the basis of Bong’s work. Four modes of deformation:

    Catenary, Sway, Inward and Upright were observed in Bong’s tests on frames in a

    fully developed ISO fire (ISO, 1975). When rigid bases and purlin restraint were

    assumed for a frame, its deformation tended to be a Catenary mode, which means

    that the frame deformed almost symmetrically and the roof structure deformed into a

    catenary shape, as shown in Figure 1.27. For a frame with pinned bases, the roof

    lost its stiffness due to the thermal degradation of the steel and sagged relatively

    quickly, so that the frame could lose stability in a Sway mechanism, as shown in

  • Chapter 1 Introduction

    30

    Figure 1.28. When the restraint from the purlins was released, the heated frame

    could collapse into the building in an Inward mode of failure as described in Figure

    1.29. When columns with pinned bases were protected in fire, they did not collapse

    inwards together with the collapse of the rafters, and stood upright after the fire, as

    shown in Figure 1.30. It is suggested by Peter et al. (2006) that, in practical design,

    some level of rotational restraint should be provided to the frame base connections to

    prevent sidesway of frames and outward collapse of walls. Passive fire protection to

    the column legs was also recommended, to ensure the stability of the columns and

    walls in fire.

    The simple assumption for partial fixed bases made by Bong (2002) can produce

    stiffness and strength between the fully rigid and pinned conditions for the base

    connections. However it could introduce extra horizontal movement to the column

    when the column element adjacent to the base begins to plastically yield, which is

    different from the real behaviour of the frame. It could also influence the overall

    behaviour of the frame if the artificial base element is not short enough. The required

    design capacity of the column base can not be indicated by the model with this

    simple assumption. Although the cooling phase of the fire was considered in this

    study, a fully developed fire was assumed, which means that all the frames in the

    building begin to cool down at the same time. It is very possible in a real fire that,

    when the temperature of some frames begins to decrease the other frames are still

    hot. The interaction between the cool and hot frames can be extreme, and so some

    localized fire including cooling phase, should be considered in a three-dimensional

    analysis of industrial portal frames.

    The structural behaviour of multi-span portal frames was analysed by Vassart et al.

    (2005). The collapse of a frame was divided into two successive phases, according

    to the inclination of columns. In the first phase, the lateral displacements at the tops

    of columns increases progressively due to the thermal expansion of heated

    members, so that the cold frames are pushed outwards, as shown in Figure 3.30.

  • Chapter 1 Introduction

    31

    The second phase is defined by collapse of the heated roof. Tensile forces then

    become dominant in the heated members, so the unheated frames are pulled inward

    in this stage. A simple method was developed for frames with more than one span, to

    estimate the outward deflection at the tops of columns in the expansion phase.

    Figure 1.31 Lateral displacements at the tops of columns in Phase 1 (Vassart et al.

    2005).

    Figure 1.32 Lateral displacements at the tops of columns in Phase 2. (Vassart et al.

    2005).

    A dynamic analysis, performed by ABAQUS (2004), was adopted to model the failure

    progression of the multi-span portal frame. Semi-rigid bases were simulated by

    spring elements defined using a bi-linear M - curve. Because this study concerns

    the French fire safety requirements for industrial buildings, which specify no

    progressive collapse between different fire compartments and no collapse outwards,

    an inward collapse of the frame was not important. Inward collapse normally leads to

    a much higher inclination of the columns comparing to the outward inclination in the

    initial expansion stage, which may be more harmful to the stability of a boundary wall,

    and so the results from this study are not very helpful for portal frames designed in

    the UK.

  • Chapter 1 Introduction

    32

    1.6. NUMERICAL MODELLING

    Structural behaviour in fire involves highly geometric and material nonlinearity which

    can not be represented by a closed form solution in most cases. In order to solve this

    problem the finite element method and advanced solution procedures have been

    applied to simulate the behaviour of structures in fire. Compared to laboratory tests,

    numerical analysis has a significant advantage in cost efficiency, and is capable of

    providing results with acceptable accuracy.

    1.6.1. VULCAN

    Many finite element analysis programs, such as ABAQUS (2004), ANSYS (1992),

    have been developed for the numerical modelling of structural behaviours under

    different circumstances. They are normally designed to provide a comprehensive tool

    for modelling of structures at ambient temperature. It may sometimes be difficult to

    use them for structural analysis under fire conditions. In recent years a specialised

    finite element analysis software Vulcan has been developed at the University of

    Sheffield for three-dimensional modelling of steel, composite and reinforced concrete

    buildings under fire conditions. In this program buildings are modelled as an

    assembly of a finite beam-column, slab and connection elements, and both material

    and geometric non-linearities are considered. Currently, a Newton-Raphson iterative

    method is adopted to solve for the incremental displacements at each node, on the

    basis of static force equilibrium. This program has been well validated against fire

    tests (Huang et al. 2003b). The academic version of Vulcan, coded in FORTRAN,

    has mainly been developed for research purposes, which allows incorporation of new

    developments, such as new elements or solvers, into the original program.

  • Chapter 1 Introduction

    33

    1.7. SCOPE OF THE RESEARCH AND LAYOUT OF THE THESIS

    As mentioned above, in the last decade several studies have been carried out to

    investigate the response of steel portal frames to fire conditions. However, for

    numerical modelling, most of them are based on static analysis. Hence, the

    behaviour of the pitched-roof portal frame is not represented fully, especially when

    temporary instability is encountered during the collapse of the frame. Of course a

    fully dynamic procedure can be employed to deal with the instability encountered in

    the analysis, but the computational efficiency is very low under such conditions

    because the analysis is mainly of stable equilibrium, apart from the period of the

    dynamic snap-through.

    A fundamental feature of the collapse of pitched-roof portal frames in fire is the loss

    of stability at the point where the snap-through mechanism happens, which may

    re-stabilise when the roof is inverted. Hence, one of the main objectives of this

    research is to investagate the behaviour of the portal frame after re-stabilisation, and

    to identify the eventual failure point. Hence, the first step of the research is to develop

    a robust quasi-static procedure to effectively model the snap-through mechanism

    of portal frames under fire conditions. The new procedure is validated using both test

    data and fully dynamic application of other software, such as ABAQUS (2004) and

    ANSYS (1992).

    In previous researches numerical modelling based on the fully dynamic procedure

    has been used to trace the behaviour of portal frames in fire up to very big

    deformations. However, the failure mechanisms of portal frames under different

    conditions have not been fully investigated. The current design guide used in the UK

    is based on several arbitrary assumptions, and it is still doubtful whether designs are

    reasonable and conservative. Hence, the newly developed procedure in Stage 1 is

    used to conduct a series of numerical studies on typical industrial frames under

  • Chapter 1 Introduction

    34

    different conditions. The research has revealed the common failure mechanism of

    the steel portal frames at elevated temperatures.

    As required by the current design method, specification of a strong moment-resisting

    column base is the only way to guarantee the fire safety of a portal frame in a fire

    boundary condition. However, this solution is complex and expensive from the

    practical point of view. Therefore, based on the data generated at Stage 2 of the

    research, a new simplified design method is proposed for fire safety design of portal

    frames in boundary conditions.

    An overview of the remaining chapters of this thesis is given below:

    Chapter 2: The detailed theory and formulation of the robust quasi-static procedure

    are presented.

    Chapter 3: A detailed validation of the newly-developed procedure is provided.

    Chapter 4: A series of numerical studies on typical industrial portal frames are

    conducted.

    Chapter 5: The current design method is validated by the results from the

    numerical tests. A new design method is developed.

    Chapter 6: The main findings of this research are reiterated and the scope for

    possible future work on this topic is discussed.

  • Chapter 2 New Quasi-static Procedure

    35

    2. NEW QUASI-STATIC PROCEDURE

    2.1. INTRODUCTION

    At present, most numerical analysis codes developed for modelling the behaviour of

    structures subject to fire are based on static formulations, which assume that the

    variation of loading and temperature does not introduce inertial effects to the

    structure and that the loading process is infinitely slow. The current static procedures

    with the geometrical and material nonlinearity have been able to capture the major

    aspects of the behaviour of steel and composite structures under fire conditions,

    such as catenary action of beams and membrane action of composite slabs.

    In static analysis the external forces at nodes are balanced by the internal forces to

    achieve equilibrium, which can be expressed as

    tt ExtInt FF (2.1)

    where tIntF is the internal nodal force vector, and tExtF is the external nodal

    force vector. In geometrically and materially nonlinear problems, the stiffness of the

    structure is not constant but changes with the variation of the strain in the elements,

    so Newton-Raphson iterative solvers are commonly used. This procedure can be

    represented mathmatically as Equation (2.2) for a load-controlled analysis.

    1,,1

    ,

    ,1,

    nktt

    Int

    kttk

    Int

    nttInt

    ktt

    Int

    ktt UKFUU

    FFF (2.2)

    where Int

    ktt ,F is the unbalanced force at the k th iteration of step tt . Equilibrium

    between external and internal forces at time tt is achieved when the unbalance

    force ktt ,g has a very small value, say StaticTOL , after the k th iteration. That is,

    Static

    Int

    ktt

    Ext

    ttktt TOL ,, FFg (2.3)

  • Chapter 2 New Quasi-static Procedure

    36

    The incremental displacement U from time t to time tt can be calculated

    by summing the incremental displacements from each iteration, as shown in Figure

    2.1. That is,

    kUUUUU 321 (2.4)

    Figure 2.1 Illustration of Newton-Raphson iterative procedure.

    Figure 2.2 Illustration of the ill-conditioning of stiffness matrix in static analysis

    δU1 δU2

    tU ttU

    Load

    Displacement

    Ext

    ttF

    Int

    t

    Ext

    t FF

    Ext

    tt 0,g

    δU3

    Divergence

    Negative stiffness

    Limiting point

    δU1 δU2

    tU ttU

    Load

    Displacement

    Int

    ttF 2,

    Ext

    ttF

    Int

    ttF 1,

    Int

    t

    Ext

    t FF

    Ext

    tt 0,g

    Ext

    tt 1,g

    Ext

    tt 2,g

    δU3 δU4 … δUn

  • Chapter 2 New Quasi-static Procedure

    37

    This iterative solver only converges for incremental displacements on a continuously

    ascending part of the load-displacement curve, as shown in Figure 2.1. However,

    when the stiffness of the structure becomes negative, as shown in Figure 2.2,

    equilibrium cannot be achieved in the opposite direction, so the analysis becomes

    divergent after the limit point.

    In previous studies on industrial frames under fire conditions, the numerical failure

    caused by ill-conditioning of the stiffness matrix has been observed by O’Meagher et

    al (1992), Wong (2001) and De Souza Junior (2002). Unless special solution

    processes, such as displacement control, are used the analysis cannot be continued

    beyond any point in the fire at which the structural stiffness matrix is not

    positive-definite. The appearance of negative stiffness in a static analysis may be

    caused by either true structural failure, or numerical failure. This can easily happen to

    pitched portal frames in fire, because of the snap-through behaviour of the frame due

    to load on the roof and the degradation of steel at elevated temperatures.

    P

    a

    b

    c

    yh

    S

    PP

    a

    b

    c

    yh

    S

    Figure 2.3 Illustration of the mechanism of snap-through for portal frame.

    The mechanism of snap-through which happens to a pitched portal frame roof can be

    idealised by the two-strut model shown in Figure 2.3. The theory has been explained

    by Crisfield (1991) using a bar and spring model. When a downward force acts on

    the apex and pinned bases are assumed, the deformation of the struts follows the

    sequence from shape a to shape b, and then from shape b to shape c. The internal

  • Chapter 2 New Quasi-static Procedure

    38

    force in the vertical direction, VN , at the apex can be simply calculated by Equation

    (2.5) if the shallow roof pitch assumption is adopted, so that the change of the length

    of the truss can be ignored in the calculations.

    L

    yhNNNV sin (2.5)

    where is the modified pitch as shown in Figure 2.3, and N is the axial force

    developed in the truss element which can be calculated using Equation (2.6)

    EAN (2.6)

    The strain can be estimated by Equation (2.7).

    2

    222

    3

    2

    3

    222

    3

    2

    1

    S

    y

    S

    hy

    hS

    SyhhS (2.7)

    where 3S is the strut length when the both struts deform to the horizontal positions,

    and for the shallow roof assumption 3S can be represented by the original strut

    length S , h represents the apex height, and y is the displacement of the apex

    from the original position as shown in Figure 2.3. The relationship between the

    vertical reaction VN and the apex deflection y can be obtained by subs