andambike project 11 book final.doc
TRANSCRIPT
-
8/10/2019 Andambike PROJECT 11 BOOK FINAL.doc
1/46
DECLARATION
I, Timothy Andambike, declare that to the best of my knowledge the project presented here
as part of the fulfillment for the award of Bachelor degree in electrical engineering is a work
of my origin. All references used from books, articles, reports, papers etc in preparation ofthis project have their sources acknowledged in the reference list.
Signature
Timothy Andambike
!ay "#$%
Supervised by
Signature....
!r. &dimba
!ay "#$%
i
-
8/10/2019 Andambike PROJECT 11 BOOK FINAL.doc
2/46
-
8/10/2019 Andambike PROJECT 11 BOOK FINAL.doc
3/46
ACKNOWLEDGEMENT
/irst of all I would like to thank our creator the Almighty 0od for giving me these chances
to pursue the Bachelor degree in engineering programmed and preparation of this project
report.
I would like to e+tend my thanks to my project supervisor !r. &dimba .T for his valuable
advice and guidance during the planning as well as implementation of this work.
I am also deeply indebted to the project coordinator -r. A. 1ilimo for the help and
directives he e+tended to me while preparing this project.
!y thanks and appreciation should also go to all academic staff of electrical engineering
department for the tireless advices, assistances supports and encouragement towards making
this project successful.
!y appreciation are also due to my employer for trusting and granting me the opportunity
for pursuing studies at -IT. I also e+tend my thanks to my fellow workers who supported me
in one way or another in fulfillment of this task.
Also special thanks to my family members for their encouragement and support throughoutthe preparation of this work.
As it is not possible to thank everyone, I would like to thank all people who have helped
and inspired me during my project.
iii
-
8/10/2019 Andambike PROJECT 11 BOOK FINAL.doc
4/46
TABLE OF CONTENTS
-()2A3ATI*&........................................................................................................................I
ABST3A)T..............................................................................................................................II
A)1&*42(-0(!(&T.......................................................................................................III
TAB2( */ )*&T(&TS.........................................................................................................I5
2IST */ S6!B*2S...............................................................................................................5I
2IST */ TAB2(S.....................................................................................................................5
2IST */ /I073(S8................................................................................................................5I
2IST */ ABB3(5IATI*&S.................................................................................................5II
)A9T(3 *&(.......................................................................................................................5$.$ I&T3*-7)TI*&8..........................................................................................................5
$.". 93*B2(! STAT(!(&T.............................................................................................."
$.:. 93*;()T *B;()TI5(S..............................................................................................."
$.:.$. !AI& *B;()TI5(8................................................................................................:
$.:.". S9()I/I) *B;()TI5(S8.......................................................................................:
$.%. !(T*-*2*06..........................................................................................................:
$.7(&)( */ T( 93*;()T................................................:
)A9T(3 T4*........................................................................................................................ B"#$% &i'gr'( #) *+ -ig" "i 8#0r -/-*( $#$*& *# *+ "ig+*ig
'rr-*r.
".%.% A33(ST(3S S(2()TI*& A&- A992I)ATI*&S
The primary objective in arrester application is to select the lowest rated surge arrester
that will provide ade'uate protection of the e'uipment insulation and be rated such that it will
have a satisfactory service life when connected to the power system. An arrester of the
minimum rating is preferred because it provides the highest margin of protection for the
e'uipment insulation system. There is a fine line between protection and service life of a
surge arrester. igher arrester ratings will increase the capability of the arrester to survive on
a specific power system but reduce the margin of protection provided for the insulation level
of the e'uipment it is protecting. Therefore, one should consider both issues of arrester
survival and e'uipment protection when selecting surge arresters.The best location for installation of a surge arrester is as close as possible to the e'uipment
it is protecting, preferably at the terminals where the line is connected to the e'uipment. This
is based on the mathematics of wave theory addressing incident and reflected waves at a
junction Dor protected e'uipment terminalE. 2ead length for the connection of the surge
arrester to the e'uipment terminals and to ground should be minimied and installed as
straight, minimiing bends in the leads, as possible. This will ensure that the surge energies
are shunted to ground by the most direct path.
++ii
-
8/10/2019 Andambike PROJECT 11 BOOK FINAL.doc
25/46
Increases in the lead length will reduce the protection capabilities of the surge arrester, due
to the additional increase of impedance in the lead.
The rating of the arrester is defined as the 3!S voltage at which the arrester passes the duty
cycle test as defined by the referenced standard.
There are some basic considerations when selecting the appropriate surge arrester for a
particular application, these are8
$. )ontinuous system voltages
". Temporary over voltages
:. Switching surges Dmore often considered for transmission voltages of $:"k5 and higher,
capacitor banks, and cable applicationsE
%. 2ightning surges
-
8/10/2019 Andambike PROJECT 11 BOOK FINAL.doc
26/46
normal voltage continuously applied to the arrester will be the full phase?to?phase voltage,
even though the arresters are connected line to ground.
2.3.3.2. TEMPORARY OVER VOLTAGES
Temporary over voltages DT*5E can be caused by a number of system events, such as
switching surges, line?to?ground faults, load rejection and ferro resonance. The system
configuration and operating practices should be evaluated to identify the most probable forms
and causes of temporary over voltages. If detailed transient system studies or calculations are
not available, it is acceptable, as a minimum, to consider the over voltages due to single line?
to?ground faults. The configuration and details of the system grounding will determine the
over voltages associated with single line?to?ground faults. The arrester application standards,
gives the guidance in determining the magnitude of over voltages associated with single line?
to?ground faults. The primary effect of temporary overvoltageD T*5E on metal?o+ide
arresters is the increased current and power dissipation, and a rising arrester temperature.
These conditions affect the protection and survivability characteristics of the arrester.
The arresters T*5 capability must meet or e+ceed the e+pected temporary over voltages of
the system. Temporary overvoltage capabilities have been defined independent of system
impedance and are valid for the voltages applied at the arrester location.
2.3.3.. SWITCHING SURGES
The arresters ability to dissipate switching surges can be 'uantified to a large degree in
terms of energy. The unit used in 'uantifying the energy capability of metal?o+ide arresters is
kilo;oulesFkilo5olt Dk;F k5E.
The ma+imum amount of energy that may be dissipated are defined assuming multiple
discharges distributed over a one?minute period. In applications where the discharges are
distributed over a longer period of time, arresters will have considerably more capability. As
noted previously, arresters applied correctly can repeat these capabilitiesK therefore, after a
one?minute rest period the above discharges may be repeated. The one?minute rest period
allows the diskDsE temperature distribution to reach e'uilibrium and become uniform. These
energy ratings assume that the switching surges occur in a system having surge impedances
of several hundred ohms, which would be typical for overhead transmission lines. In low
impedance circuits having cables or shunt capacitors as elements, the energy capability metal?
o+ide arresters may be reduced because currents can e+ceed the values noted.
++iv
-
8/10/2019 Andambike PROJECT 11 BOOK FINAL.doc
27/46
2.3.3.3 SYSTEM CONFIGURATION
1nowing the system configuration, wyeFdelta, grounded or ungrounded, is a key factor in
selecting an arrester rating. The arrester nominal ratings for various utiliation system
voltages Dline?to?lineE are based on the systems grounding configuration.
If the system is solidly grounded, then a lower?rated arrester can be chosen. If the system is
ungrounded, impedance grounded or temporarily ungrounded, then a higher arrester rating
must be chosen to compensate for the potential of a higher continuous voltage, or !)*5,
being impressed on the arrester for an e+tended period of time. *ther than a solidly grounded
system, any other system configuration is considered to be effectively ungrounded and a
higher arrester rating should be chosen. 1nowing the system configuration and choosing the
correct arrester rating is critical in averting an application where the arrester can potentially
have a failure and cause violent end of life.
2.3.3.4 ARRESTER FAILURE AND PRESSURE RELIEF
If the capability of an arrester is e+ceeded, the metal?o+ide diskDsE may crack or puncture.
Such damage will reduce the arrester internal electrical resistance.
This condition will limit the arresters ability to survive future system conditionsK it does not
jeopardie the insulation protection provided by the arrester.
In the unlikely case of complete failure of an arrester, a line?ground arc will develop and
pressure will build up inside the housing. This pressure will be safely vented to the outside
and an e+ternal arc will be established provided the fault current is within the pressure relief
fault current capability of the arrester. This low?voltage arc maintains e'uipment protection.
*nce an arrester has safely vented, it no longer possesses its pressure reliefFfault current
capability and should be replaced immediately. /or a given application, the arrester selected
should have a pressureFfault current capability greater than ma+imum short?circuit currentavailable at the intended arrester location. This rating of arrester capability should include
appropriate allowances for future growth in the system.
2.3.3.5 FAILURE MODES OF SURGE ARRESTERS
An arrester failure may appear in different ways8
1. An arrester with porcelain housing may in worst case e+plode and cause severe
damages to the surroundings.
++v
-
8/10/2019 Andambike PROJECT 11 BOOK FINAL.doc
28/46
Such a failed arrester is shown in /igure ".. In case of arresters with polymer
housing, the housing may burst open, but the risk for objects being scattered is more
limited.
2. The arrester can be causing an earth fault due to internal flashovers etc. Such
arresters can be difficult to locate.
3. Aged or overloaded arresters may show reduced protection against overvoltage, i.e.
during severe transient overvoltage, for instance due to multiple lightning stroke or
high?energy temporary overvoltage, the arrester can fail before it actually has
suppressed the overvoltage.
Thus, the apparatus that the arrester is set to protect may be subject to overvoltage that can
cause damage to it.
Figur.2.?: M*'" O,i& Surg Arr-*r@ MOSA 0i*+ 8#r$"'i +#u-ig *+'* )'i"&
$'*'-*r#8+i$'""/ i -r;i$.
2.3.3.< ARRESTERS SELECTION AND APPLICATIONS SUMMARY
The arrester selection and application process should include a review of all system
stresses, service conditions e+pected, and system?grounding configuration Dgrounded or
effectively ungroundedE at the arrester installation location. System stresses shall include
continuous operating voltage, temporary over voltages, and switching surges. If arresters
of different ratings are re'uired to meet these individual criteria, then the highest resulting
arrester rating should be chosen.
++vi
-
8/10/2019 Andambike PROJECT 11 BOOK FINAL.doc
29/46
/igure below shows various sies of porcelain housed lightning arresters used in the system.
Figur.2.19.P#r$"'i +#u-& "ig+*ig 'rr-*r- #) ;'ri#u- -i- '& r'*ig.
++vii
-
8/10/2019 Andambike PROJECT 11 BOOK FINAL.doc
30/46
-
8/10/2019 Andambike PROJECT 11 BOOK FINAL.doc
31/46
9A3A!(T(3S
A&&7A2 T(!9(3AT73( "
-
8/10/2019 Andambike PROJECT 11 BOOK FINAL.doc
32/46
The resistivity depends on the amount of salts dissolved in its moisture .
.2..2 M'-ur(* #) 'r*+ r-i-*'$-.
(arth resistance measurements at different distribution transformers was done using a digital
(arth and 3esistivity Tester as outlined below. (arth resistance measurement with the : polemethod .
Figur .2: C+'u;i Ar#u, E'r*+ '& R-i-*i;i*/ T-*r. Nu(!r C.A 53
-
8/10/2019 Andambike PROJECT 11 BOOK FINAL.doc
33/46
Figur . : E'r*+ %i*:)#r ('-urig ,i-*ig 'r*+ r-i-*'$-
Pr#$&ur- )#r ('-ur(*
$. Turn off the installation power supply and disconnect it from the (arth by opening the
ground terminal bar.
". Short?circuit the terminals ( and (S using the corresponding terminal bar and connect
them to the earth point to be measured.
:. 9ush rod as deep as possible into the ground at a distance HA from the earth to be
measured.
It is advisable to have the distance HA greater than "
-
8/10/2019 Andambike PROJECT 11 BOOK FINAL.doc
34/46
-
8/10/2019 Andambike PROJECT 11 BOOK FINAL.doc
35/46
1A!4(&( "=
!I4A&0A&I $"
111T 3(2I&I %
!I(!B(&I