6000 Uptown Blvd. NE, Suite 200 Albuquerque, NM 87110 tel: 505 243-3200 fax: 505 243-2700 PW_XM1\Documents\36207\105673\04 Design Services NM_100%\15 Bidding Services\04 Addenda Well 8A and 19 Addendum No.2.doc Camino Real Regional Utility Authority Doña Ana County, New Mexico CDM Smith Project No. 36207-105673 ADDENDUM NO. 2 October 27, 2016 ADDENDUM NO. 1: TO CONSTRUCTION PLANS AND CONTRACT DOCUMENTS PROJECT: WELL 19 REPLACEMENT AND WELL 8A CONTROL BUILDING BID NO. 17-0014 OWNER: CAMINO REAL REGIONAL UTILITY AUTHORITY NOTICE TO BIDDERS: The following information is provided to all Contractors: 1. The Bid Opening will be held in the Doña Ana County Building room 2-143. The following items shall be modified to the Contract Documents: 1. SECTION 02676 Paragraph 1.02G – Following the first sentence insert the following text: “Drilling fluid may be disposed of by pumping to the land surface at the approved location where water will be discharged during development and test pumping.” 2. SHEET E-04 WELL 19 ELECTRICAL FLOOR PLAN Replace the sheet in its entirety with the revised version attached to this addendum. 3. SHEET E-06 WELL 19 CONTROL SCHEMATICS Replace the sheet in its entirety with the revised version attached to this addendum. 4. SHEET E-09 WELL 19 ELECTRICAL SCHEDULES Replace the sheet in its entirety with the revised version attached to this addendum. 5. SHEET E-14 WELL 8A CONTROL SCHEDULES Replace the sheet in its entirety with the revised version attached to this addendum.

Upload: others

Post on 23-Apr-2020

4 views

Category:

Documents


0 download

TRANSCRIPT

6000 Uptown Blvd. NE, Suite 200

Albuquerque, NM 87110

tel: 505 243-3200

fax: 505 243-2700

PW_XM1\Documents\36207\105673\04 Design Services NM_100%\15 Bidding Services\04 Addenda Well 8A and 19 Addendum No.2.doc

Camino Real Regional Utility Authority

Doña Ana County, New Mexico

CDM Smith Project No. 36207-105673

ADDENDUM NO. 2

October 27, 2016

ADDENDUM NO. 1: TO CONSTRUCTION PLANS AND CONTRACT DOCUMENTS PROJECT: WELL 19 REPLACEMENT AND WELL 8A CONTROL BUILDING

BID NO. 17-0014 OWNER: CAMINO REAL REGIONAL UTILITY AUTHORITY NOTICE TO BIDDERS: The following information is provided to all Contractors:

1. The Bid Opening will be held in the Doña Ana County Building room 2-143. The following items shall be modified to the Contract Documents:

1. SECTION 02676 Paragraph 1.02G – Following the first sentence insert the following text:

“Drilling fluid may be disposed of by pumping to the land surface at the approved location where water will be discharged during development and test pumping.”

2. SHEET E-04 WELL 19 ELECTRICAL FLOOR PLAN

Replace the sheet in its entirety with the revised version attached to this addendum.

3. SHEET E-06 WELL 19 CONTROL SCHEMATICS

Replace the sheet in its entirety with the revised version attached to this addendum.

4. SHEET E-09 WELL 19 ELECTRICAL SCHEDULES

Replace the sheet in its entirety with the revised version attached to this addendum.

5. SHEET E-14 WELL 8A CONTROL SCHEDULES

Replace the sheet in its entirety with the revised version attached to this addendum.

Addendum No. 2

PW_XM1\Documents\36207\105673\04 Design Services NM_100%\15 Bidding Services\04 Addenda Well 8A and 19 Addendum No.2.doc

6. SHEET E-17 WELL 8A ELECTRICAL SCHEDULES

Replace the sheet in its entirety with the revised version attached to this addendum.

7. SHEET E-18 ELECTRICAL DETAILS 1

Replace the sheet in its entirety with the revised version attached to this addendum.

8. Section 15072

Paragraph 2.01B.3 – Insert “or hex” after “square” in the first sentence of text. ATTACHMENTS: The following attachments are included with this Addendum No. 1:

• Contractor Question and Answer Summary (6 pages)

• Drawings (6 pages): o E-04/Well 19 Electrical Floor Plan o E-06/Well 19 Control Schematics o E-09/Well 19 Electrical Schedules o E-14/Well 8A Control Schematics o E-17/Well 8A Electrical Schedules o E-18/Electrical Details 1

• Current Plan Holders List (2 pages) All other provisions of the Contract Documents shall remain unchanged. This addendum is hereby made a part of the Contract Documents to the same extent as those provisions contained in the original documents and all itemized listings thereof. Each bidder shall acknowledge receipt of this Addendum No. 2 as required by Section 00201, page 2 and Section 00300, page 3. _______________________________ Robert A. Fowlie P.E., BCEE Senior Project Manager CDM Smith

Addendum No. 2

PW_XM1\Documents\36207\105673\04 Design Services NM_100%\15 Bidding Services\04 Addenda Well 8A and 19 Addendum No.2.doc

Contractor Question and Answer Summary

Addendum 1 Question 1: The room finish schedule for the above job lists "sealer" for the floors in the Equipment

Room and the Chlorination Room. There is no sealer in the specifications, only the following:

Chemical Resistant Coatings on Concrete 1 prime coat Series 120 2 coats Series 120 Please clarify.

Response 1: Service Condition J: To be applied on concrete floors not finished with tile. 1. Surface preparation: Same as Service Condition H. 2. Prime Coat: Tnemec Series 201 Epoxoprime at 10.0-12.0 dry mils 3. Intermediate Coat: Tnemec Series 282 Tnemec-Glaze at 8.0-10.0 dry mils 4. Finish Coat: Tnemec Series 290 CRU at 2.0-3.0 dry mils The following is to be applied for the coating in the chlorine room. A. Provide concrete of the following characteristics: 1. Minimum compressive strength (f c) at 28 days: 5,000 psi. 2. Maximum slump: 4 inches. 3. Maximum water/cement ratio: 0.45. 4. Maximum aggregate size: 1 inch. 5. Air entrainment: 4.5 percent plus or minus 1.5 percent. B. Provide chemical corrosion (Sulfate and Chloride) protection admixture: 1. Xypex C-500 Admixture 2. 3% by weight of cement

3. The crystalline waterproofing admixture shall be added to the concrete during the mixing cycle and shall conform to the manufacturer specifications.

4. The Contractor shall submit materials conformance documents with concrete mix design submittals for approval prior to construction.

5. Manufacturers of equivalent products submitted and approved by Engineer. Question 2: Specification 11214, Part 2, Paragraph 2.02 (Conditions of Operation A) calls for model

J11HC 13 Stage to meet 800 GPM @ 590’ TDH.

Please review model J11HC 9 Stage for the design point. Will this pump model be acceptable?

Response 2: Pump model J11HC 9 Stage is acceptable. Paragraph 2.02A of Specification Section 11214 has been revised by removing the number of stages required for the National Pump Company Model J11HC.

Addendum No. 2

PW_XM1\Documents\36207\105673\04 Design Services NM_100%\15 Bidding Services\04 Addenda Well 8A and 19 Addendum No.2.doc

Question 3: There is a discrepancy between the figure on Sheet MD-01 and the technical specs. The figure indicates that the upper blank is HSLA 0.3125” wall.

The specs and measurement and payment indicate it is ASTM A53 Grade B, 0.375” wall. Please clarify.

Response 3: Per Specification Section 02676, the upper blank casing shall conform to ASTM A53 Grade B, and shall have a 0.375-in wall thickness. Sheet MD-01 has been modified to include this change.

Question 4: Specification Section 11244, Part 2, Paragraph 2.06C calls for a chlorine emergency shut off

system. Sheet M-02 does not have any notes indicating requirements for a chlorine emergency shut off system.

Please clarify if the chlorine emergency shut off system is required as specified in Specification Section 11244.

Response 4: A chlorine emergency shut off system as described in Specification Section 11244, Part 2, Paragraph 2.06C is required.

Question 5: Do you know what slot size required for the SS well screen? Also are you looking for weld rings, and will you be requiring a bottom cap on the screen?

Response 5: Per Specification Section 02676, Paragraph 2.06.F.1, slot size is tentative of 0.05-in. and

subject to change after sieve analysis. Per Specification Section 02676, Paragraph 2.06.B, weld collars are required. A bottom cap is required and must be stainless steel. Casing and screen can’t be ordered until the sieve analysis is reviewed.

Question 6: Specification Section 02676, Paragraph 2.06 E.1. States the 16" mild steel casing from ground level to the dissimilar metal connector shall have 0.375" wall thickness (Bid Form Item 2F says same thing) but the well diagram (DWG MD-01) indicates the 16" casing will be HSLA with 0.3125" wall thickness. Which wall thickness and material composition is correct?

Response 6: Per Specification Section 02676 Paragraph 2.06.E.1, the upper 16-in blank casing shall

conform to ASTM A-53 Grade B and have a wall thickness of 0.375-in.

Question 7: MD-01 shows the conductor casing to be 26" and the reamed borehole to be 24" but the bid form (Item 2B) indicates the conductor casing will be 24". I believe the 26" is the correct diameter. Please confirm.

Response 7: Correct. Item 2B in the bid form and measurement and payment should read 26-inch

Conductor Casing.

Addendum No. 2

PW_XM1\Documents\36207\105673\04 Design Services NM_100%\15 Bidding Services\04 Addenda Well 8A and 19 Addendum No.2.doc

Question 8: The specifications refer to the nominal dimension of the 16" well casing, but the only casing manufacturer that provides HSLA casing (Roscoe Moss) provides oversized casing in 16.625" OD vs the more standard 16" OD. Please clarify the specified outside diameter of the 16" casing.

Response 8: As in item 1 above, the upper 16-in blank casing shall conform to ASTM A-53 Grade B and

have a wall thickness of 0.375-in.

Question 9: The specifications refer to air release valves “of the special type for use with non-clean water”. Please clarify what is meant by non-clean water.

Response 9: For this project, the air release valves specified in Specification Section 15100, Paragraph

2.02.R.4, shall be used for municipal well water supply. For the Well Service ARVs shown on drawings M-02, -03, -04, and -05, please refer to Paragraph 2.02.T in Specification Section 15100.

Addendum 2

Question 10: Spec section 01172, GENERAL EQUIPMENT REQUIREMENTS 2.10 Lifting Lugs: requires Lifting Lugs or Eye Bolts provided for all equipment or any component weighing 50 pounds or more. Will this requirement include pipe and fittings? Please clarify what Items will require a Lifting Lug.

Response 10: This requirement does not apply to pipe and fittings. Pipe and fittings will not require

lifting lugs or eye bolts.

Question 11: Spec section 02622, 2.01, B calls for Ductile Iron Fittings per AWWA C110, similarly Spec section 15072, 2.01, C also calls for Ductile Iron Fittings per AWWA C110. As neither section makes any reference to fittings per AWWA C153, shall it be inferred that fittings per AWWA C153 will NOT be acceptable?

Response 11: Ductile Iron Fittings per AWWA C110 and AWWA C153 will be acceptable.

Question 12: Spec section 02622, 2.01, B calls makes reference to “GRIT SLURRY LINES”, where fittings

require glass lining. No such lines are specifically called out as “GRIT SLURRY LINES”, please confirm that NONE of the Lines on this project are considered “GRIT SLURRY LINES”, and therefore do not require Glass Lining?

Response 12: None of the lines on this project are considered “GRIT SLURRY LINES”, therefore none of the lines on this project require glass lining.

Addendum No. 2

PW_XM1\Documents\36207\105673\04 Design Services NM_100%\15 Bidding Services\04 Addenda Well 8A and 19 Addendum No.2.doc

Question 13: Plan Sheet CD-01, Detail D shows Trace Wire, will Trace Wire be required for ALL buried Piping? Including the Drain Lines?

Please clarify.

Response 13: Trace wire shall be provided for all buried pressure piping (well discharge and well collector lines). Marking tape shall be provided for all buried piping including both pressure and gravity flow pipe. Marking tape used for buried pressure piping (well discharge and well collector lines) shall be blue. Marking tape used for buried gravity flow pipe (drain lines) shall be green.

Question 14: Plan Sheet M-04 and Sheet I-03: M-04 shows 1-1/2-PW-GS while I-03 shows 1-1/4-PW-

GS. Please clarify the size of this line and appurtenances.

Response 14: The size of this line shall be 1-1/4” as indicated on Sheet I-03 and M-02 for Well 19. Similarly, the size of this line shall be 1-1/4” as indicated on Sheet I-04 and M-03 for Well 8A. Associated appurtenances on this line shall be 1-1/4” (globe valves, reduced pressure backflow preventer, pressure reducing valve and pressure relief valve).

Question 15: Plan Sheet M-04 and Sheet I-03: M-04, 1-1/2-PW-GS shows a Pressure Reducing Valve before the Reduced Pressure Backflow Preventer, while I-03 Does not show a Pressure Reducing Valve before the Reduced Pressure Backflow Preventer. Will a Pressure Reducing Valve be required on this line before the Reduced Pressure Backflow Preventer?

Response 15: The line size is incorrect as noted in the response to Question 5 of this addendum. This line

shall be 1-1/4”. As indicated on I-03 and I-04 for Well 19 and 8A, respectively the 1-1/4” line shall include a reduced pressure backflow preventer, followed by a pressure reducing valve and pressure relief valve. A pressure reducing valve is not required upstream of the reduced pressure backflow preventer

Question 16: Spec 13340, 2.05 PRESSURE GAUGE makes reference to an INSTRUMENT DEVICE SCHEDULE, from which we may find required Ranges and whether or not the gauges are Liquid Filled. Where may this INSTRUMENT DEVICE SCHEDULE be located?

Response 16: Refer to Appendix of Section 13300 for the Instrumentation Index which lists the required

ranges of instruments. Question 17: Spec 15072.2.01.B.3 calls for “square headed carbon steel machine bolts”. Square headed

bolts cost three to four times as much as hex headed bolts. Please confirm that square headed bolts will be required.

Response 17: Bolts may be either square or hex headed. Section 15072 has been revised in Addendum 2

to include this change.

Addendum No. 2

PW_XM1\Documents\36207\105673\04 Design Services NM_100%\15 Bidding Services\04 Addenda Well 8A and 19 Addendum No.2.doc

Question 18: Spec 15072, 2.01, B.3 calls for “square headed carbon steel machine bolts”. Please confirm that square headed bolts will be required. There is a significant cost difference between Square Head Bolts and Standard Hex Head Bolts.

Response 18: Bolts may be either square or hex headed. Section 15072 has been revised in Addendum 2

to include this change. Question 19: On the well that is to be pulled and treated, if the existing pumping equipment is bad and

has to be replaced and this increases cost above the $75,000 allowance, how would we handle this? Change order?

For new well testing and development, we will provide hose to get water 300’ from the

well. Can the water then run out on the ground? Once the existing well is treated, can the debris on the bottom of the well be cleaned out

with a bailing bucket instead of airlifting the debris out? Can drill cuttings and drill fluids be disposed of onsite?

Response 19: If the Well 8A pump is to be replaced, a change order will be required. Drilling fluid may be disposed of by pumping to the land surface at the approved location

where water will be discharged during development and test pumping. Specification Section 02676 has been modified to include this statement.

Per specification section 02676, paragraph 1.05C.5, removal of debris from the bottom of

the well shall be carried out by reverse air-lift pumping or sand pumping.

Question 20: A. In Section 11244, Part 1.06.D.1, the equipment description quantity includes one gas

chlorine manifold and chlorine solution diffusers. Is the manifold referring to flex tubing? Otherwise Regal Model 216 does not have a manifold. What page and item # is the diffuser? Please clarify.

B. Regarding Section 11244, Part 1.07.A.2, there is no chemical required in the Regal gas

detector as manufactured by Chlorinators Inc., as mentioned in Part 2.03.A of this Section. Also there is no chlorine analyzer mentioned in the technical specifications or this Section. Please clarify.

C. Regarding Section 11244, Part 2.01.C, the Regal VAC1000 has an “out of gas alarm

switch” but it is not called out in these specifications. No other items in the specifications has this switch. Will the Regal VAC1000 be accepted? Please clarify.

D. Part 2.04.B of Section 11244 indicates the chlorine gas leak detector shall contain an

electro-chemical cell utilizing platinum electrodes and a glycerin base electrolyte requiring replacement only once yearly under normal operating conditions. Additionally, it indicates the unit shall be provided with a self-contained sample air pump, a sample flowrate meter and a sample flow rate control valve.

Addendum No. 2

PW_XM1\Documents\36207\105673\04 Design Services NM_100%\15 Bidding Services\04 Addenda Well 8A and 19 Addendum No.2.doc

E. Part 2.05.A of Section 11244 indicates that the automatic changeover system be suitable

for wall mounting. The Regal 216 automatic changeover vacuum regulators are not designed for wall mounting. Please clarify.

Response 20: A. The gas chlorine manifold is referring to the pressure relief valve and associated

manifold where vacuum and vent tubing intersect. There is no chlorine solution diffuser included in this project.

B. The specified chlorine gas detector does not require chemicals for operation, therefore

additional supply of chemicals for operation of the chlorine gas detector is not required for this project. A chlorine analyzer is not included in this project.

C. Loss of vacuum and out of gas alarm switches are not required for the chlorinators as

part of this project. The Regal VAC1000 is not required for this project.

D. The chlorine leak detector shall be Regal Series 3001 as indicated on the Drawings. For this project chlorine leak detector will not be an electro-chemical cell utilizing platinum electrodes and a glycerin base electrolyte requiring replacement only once yearly under normal operating conditions. Additionally, this project will not require the leak detector to be provided with a self-contained sample air pump, a sample flowrate meter or a sample flow rate control valve.

E. The vacuum regulators shall be cylinder mounted as indicated on the drawings and not wall mounted.

E-04

WELL 19

ELECTRICAL FLOOR PLAN

PLAN 1

N

6000 Uptown Blvd N.E., Suite 200

Albuquerque, NM 87110

Tel: (505) 243-3200

©

CAMINO REAL REGIONAL UTILITY AUTHORITY

DOÑA ANA COUNTY, NEW MEXICO

WELL 19 REPLACEMENT AND

WELL 8A CONTROL BUILDING

www.bhinc.com

800.877.5332

AutoCAD SHX Text
CHLORINATION ROOM 200
AutoCAD SHX Text
PUMP ROOM 100
AutoCAD SHX Text
WP
AutoCAD SHX Text
WP
AutoCAD SHX Text
M
AutoCAD SHX Text
WP
AutoCAD SHX Text
WP
AutoCAD SHX Text
WP
AutoCAD SHX Text
EM
AutoCAD SHX Text
WP
AutoCAD SHX Text
WP
AutoCAD SHX Text
M
AutoCAD SHX Text
UH-3110
AutoCAD SHX Text
M
AutoCAD SHX Text
MCC1
AutoCAD SHX Text
TYP.
AutoCAD SHX Text
13
AutoCAD SHX Text
3
AutoCAD SHX Text
14
AutoCAD SHX Text
NEMA 12
AutoCAD SHX Text
12
AutoCAD SHX Text
NEMA 3R WET
AutoCAD SHX Text
5
AutoCAD SHX Text
LPA-6
AutoCAD SHX Text
4
AutoCAD SHX Text
LPA-5
AutoCAD SHX Text
WP
AutoCAD SHX Text
15
AutoCAD SHX Text
11
AutoCAD SHX Text
M
AutoCAD SHX Text
15
AutoCAD SHX Text
SEE ELECTRICAL SITE PLAN SHEET E-03 FOR CONTINUATION
AutoCAD SHX Text
LPA-8
AutoCAD SHX Text
LPA-10
AutoCAD SHX Text
LPA-8
AutoCAD SHX Text
LPA-6
AutoCAD SHX Text
LPA-11
AutoCAD SHX Text
LPA-6
AutoCAD SHX Text
T
AutoCAD SHX Text
LPA-10
AutoCAD SHX Text
LPA-5
AutoCAD SHX Text
T
AutoCAD SHX Text
M
AutoCAD SHX Text
J
AutoCAD SHX Text
DAMP
AutoCAD SHX Text
NEMA 4X
AutoCAD SHX Text
CORROSIVE
AutoCAD SHX Text
LPA-7
AutoCAD SHX Text
P117
AutoCAD SHX Text
P109
AutoCAD SHX Text
P103
AutoCAD SHX Text
WP
AutoCAD SHX Text
P102
AutoCAD SHX Text
P102
AutoCAD SHX Text
J
AutoCAD SHX Text
P111
AutoCAD SHX Text
P112
AutoCAD SHX Text
P114
AutoCAD SHX Text
WP
AutoCAD SHX Text
WP
AutoCAD SHX Text
P113
AutoCAD SHX Text
P104
AutoCAD SHX Text
P125
AutoCAD SHX Text
P106
AutoCAD SHX Text
P107
AutoCAD SHX Text
P116
AutoCAD SHX Text
P101
AutoCAD SHX Text
P120
AutoCAD SHX Text
P115
AutoCAD SHX Text
P103
AutoCAD SHX Text
SSSS
AutoCAD SHX Text
P108
AutoCAD SHX Text
16
AutoCAD SHX Text
J
AutoCAD SHX Text
P122
AutoCAD SHX Text
P110
AutoCAD SHX Text
E-18
AutoCAD SHX Text
8
AutoCAD SHX Text
E-19
AutoCAD SHX Text
3
AutoCAD SHX Text
E-19
AutoCAD SHX Text
5
AutoCAD SHX Text
E-18
AutoCAD SHX Text
5
AutoCAD SHX Text
E-18
AutoCAD SHX Text
11
AutoCAD SHX Text
P123123
AutoCAD SHX Text
WP
AutoCAD SHX Text
P124
AutoCAD SHX Text
S
AutoCAD SHX Text
T
AutoCAD SHX Text
P123
AutoCAD SHX Text
7
AutoCAD SHX Text
S
AutoCAD SHX Text
S
AutoCAD SHX Text
S
AutoCAD SHX Text
S
AutoCAD SHX Text
J
AutoCAD SHX Text
J
AutoCAD SHX Text
E-07
AutoCAD SHX Text
1
AutoCAD SHX Text
2
AutoCAD SHX Text
E-08
AutoCAD SHX Text
A
AutoCAD SHX Text
EM
AutoCAD SHX Text
S
AutoCAD SHX Text
S
AutoCAD SHX Text
B
AutoCAD SHX Text
B
AutoCAD SHX Text
EM
AutoCAD SHX Text
A
AutoCAD SHX Text
A
AutoCAD SHX Text
A
AutoCAD SHX Text
A
AutoCAD SHX Text
P121
AutoCAD SHX Text
P118
AutoCAD SHX Text
P121
AutoCAD SHX Text
A
AutoCAD SHX Text
17
AutoCAD SHX Text
17
AutoCAD SHX Text
A
AutoCAD SHX Text
18
AutoCAD SHX Text
TYPICAL
AutoCAD SHX Text
GND
AutoCAD SHX Text
GND
AutoCAD SHX Text
GND
AutoCAD SHX Text
GND
AutoCAD SHX Text
GND
AutoCAD SHX Text
GND
AutoCAD SHX Text
GND
AutoCAD SHX Text
GND
AutoCAD SHX Text
GND
AutoCAD SHX Text
GND
AutoCAD SHX Text
1
AutoCAD SHX Text
2
AutoCAD SHX Text
(TYP.)
AutoCAD SHX Text
10
AutoCAD SHX Text
6
AutoCAD SHX Text
GROUND TO FENCE
AutoCAD SHX Text
E-18
AutoCAD SHX Text
7
AutoCAD SHX Text
8
AutoCAD SHX Text
9
AutoCAD SHX Text
6" PRESSURE SURGE ANTICIPATOR VALVE CLA-VAL 52-03
AutoCAD SHX Text
6" PUMP CONTROL VALVE CLA-VAL 61-02
AutoCAD SHX Text
WELL PUMP BASE
AutoCAD SHX Text
10" WELL DISCHARGE LINE
AutoCAD SHX Text
CL WATER BOOSTER PUMP
AutoCAD SHX Text
VERTICAL TURBINE PUMP AND MOTOR
AutoCAD SHX Text
SCBA CABINET
AutoCAD SHX Text
WASH WATER DISCHARGE VAULT
AutoCAD SHX Text
SURGE PROTECTION DISCHARGE VAULT
AutoCAD SHX Text
E-18
AutoCAD SHX Text
GND
AutoCAD SHX Text
GND
AutoCAD SHX Text
T
AutoCAD SHX Text
6
AutoCAD SHX Text
T
AutoCAD SHX Text
S
AutoCAD SHX Text
P105
AutoCAD SHX Text
EX-3116
AutoCAD SHX Text
EX-3117
AutoCAD SHX Text
EX-3118
AutoCAD SHX Text
WP
AutoCAD SHX Text
WP
AutoCAD SHX Text
LPA-6
AutoCAD SHX Text
LPA-10
AutoCAD SHX Text
WIND SOCK
AutoCAD SHX Text
P119
AutoCAD SHX Text
FE/FIT-3119
AutoCAD SHX Text
UH-3111
AutoCAD SHX Text
UH-3112
AutoCAD SHX Text
EMERGENCY EYE WASH
AutoCAD SHX Text
TERMINAL BOARD CABINET AND RTU (RTB)
AutoCAD SHX Text
E-19
AutoCAD SHX Text
9
AutoCAD SHX Text
P-3115
AutoCAD SHX Text
P-3119
AutoCAD SHX Text
E-04
AutoCAD SHX Text
E. FLEISCHER
AutoCAD SHX Text
L. MILLER
AutoCAD SHX Text
E. FLEISHER
AutoCAD SHX Text
M. THOMPSON
AutoCAD SHX Text
2
AutoCAD SHX Text
10/16
AutoCAD SHX Text
LLM
AutoCAD SHX Text
ETF
AutoCAD SHX Text
CHANGES TO ELECTRICAL SERVICE RACK
AutoCAD SHX Text
M. THOMPSON
AutoCAD SHX Text
ELECTRICAL POWER
AutoCAD SHX Text
1/2" = 1'-0"
AutoCAD SHX Text
E-03
AutoCAD SHX Text
KEYED CONSTRUCTION NOTES:
AutoCAD SHX Text
#
AutoCAD SHX Text
1.INSTALL 3/4"x10' COPPER CLAD STEEL GROUND RODS 6" BFG. REFER TO INSTALL 3/4"x10' COPPER CLAD STEEL GROUND RODS 6" BFG. REFER TO GROUNDING DETAILS AND DWG E-18 AND GOUNDING DIAGRAM DWG E-19. 2.INSTALL 4/0 AWG BARE STRANDED COPPER CONDUCTOR FOR BUILDING INSTALL 4/0 AWG BARE STRANDED COPPER CONDUCTOR FOR BUILDING COUNTERPOISE. CONNECT CONDUCTOR TO GROUND RODS BY EXOTHERMIC WELD ONLY. BURY CONDUCTOR 30" BELOW FINISHED GRADE. MAINTAIN A MINIMUM HORIZONTAL DISTANCE OF 4' FROM EDGE OF BUILDING FOUNDATION TO COUNTERPOISE. 3.INSTALL UL LISTED LIGHTNING PROTECTION SYSTEM FOR CMU PARAPET INSTALL UL LISTED LIGHTNING PROTECTION SYSTEM FOR CMU PARAPET ROOF. EXTEND ALL VERTICAL CONDUCTORS, RISERS OR HORIZONTAL RUNS CONCEALED IN SCH. 40 PVC CONDUIT IN CMU WALL, KEEP WIRE FREE FROM SHARP BENDS, KINKS, OR SPLICES. LIGHTNING ROD SECURED TO TOP OF PARAPET, SEE AERIAL TERMINAL DETAIL, AND PAINTED DESERT TAN. 4.EXOTHERMIC WELD BOND GROUNDING CONDUCTOR TO BUILDING FOUNDATION EXOTHERMIC WELD BOND GROUNDING CONDUCTOR TO BUILDING FOUNDATION REBAR, AND SERVICE RACK METAL FRAME WITH EXOTHERMIC WELD. 5.INSTALL 3/4" x 10' COPPER CLAD STEEL GROUND ROD AT SERVICE INSTALL 3/4" x 10' COPPER CLAD STEEL GROUND ROD AT SERVICE ENTRANCE, A MINIMUM OF 10' FROM THE NEAREST GROUND ROD. EXTEND 2 AWG GROUNDING CONDUCTOR IN 1/2" CONDUIT FROM DISCONNECT TO FINISHED GRADE AND CONTINUE CONDUCTOR 18" BELOW GRADE TO GROUND ROD. EXTEND 4/0 AWG BARE STRANDED COPPER CONDUCTOR FROM GROUND ROD TO COUNTERPOISE. EXOTHERMIC WELD BOND ALL CONDUCTOR TO ELECTRODE CONNECTIONS. 6.ALL BURIED GROUNDING CONDUCTOR BONDING TO BE BY ALL BURIED GROUNDING CONDUCTOR BONDING TO BE BY EXOTHERMIC WELD ONLY. 7.EXTEND COUNTERPOISE AND BOND TO STEEL/ BI METALLIC PIPE WITH EXTEND COUNTERPOISE AND BOND TO STEEL/ BI METALLIC PIPE WITH EXOTHERMIC WELD. 8.INSTALL GROUND SYSTEM TEST WELL. INSTALL GROUND SYSTEM TEST WELL. 9.GROUND TO FENCE PER DETAILS 1 AND 2 DWG E-19. GROUND TO FENCE PER DETAILS 1 AND 2 DWG E-19. 10.BOND TO WELL HEAD CASING FLANGE WITH 6 AWG GROUNDING BOND TO WELL HEAD CASING FLANGE WITH 6 AWG GROUNDING CONDUCTOR. 11.INSTALL EPEC APPROVED CT CABINET, METER CAN AND 600 AMP, 3-POLE INSTALL EPEC APPROVED CT CABINET, METER CAN AND 600 AMP, 3-POLE SOLID NEUTRAL DISCONNECT MOUNTED TO STEEL RACK PER DETAIL. 12.INSTALL 4" CONCRETE HOUSEKEEPING SLAB OF ADEQUATE WIDTH AND INSTALL 4" CONCRETE HOUSEKEEPING SLAB OF ADEQUATE WIDTH AND LENGTH TO MOUNT MCC PLUS 4". ANCHOR MCC ENCLOSURE TO SLAB PER MANUFACTURER RECOMMENDATIONS. 13.INSTALL CONDUIT FROM WELL MOTOR STARTER MCC SECTION TO EXTERIOR INSTALL CONDUIT FROM WELL MOTOR STARTER MCC SECTION TO EXTERIOR JUNCTION BOX. 14.EXTEND LFMC FROM JUNCTION BOX TO MOTOR ENTRANCE EXTEND LFMC FROM JUNCTION BOX TO MOTOR ENTRANCE 15.INSTALL INDIVIDUAL UNIT HEATER DISCONNECTS FOR EACH DEVICE, TYPICAL INSTALL INDIVIDUAL UNIT HEATER DISCONNECTS FOR EACH DEVICE, TYPICAL OF TWO. HEATERS TO HAVE INTEGRAL THERMOSTATS. 16.INSTALL ALL RIGID PVC CONDUITS BELOW CONCRETE AND TRANSITION TO INSTALL ALL RIGID PVC CONDUITS BELOW CONCRETE AND TRANSITION TO RIGID GALVANIZED METALLIC PRIOR TO EXITING CONCRETE SLAB. 17. CONNECT ALL EMERGENCY LIGHTS TO ROOM LIGHTING CIRCUIT UNSWITCHED HOT LEG AND NEUTRAL. 18.SEE LIGHT FIXTURE SCHEDULE DETAIL 1 SHEET E-09. SEE LIGHT FIXTURE SCHEDULE DETAIL 1 SHEET E-09.
AutoCAD SHX Text
0
AutoCAD SHX Text
1'
AutoCAD SHX Text
2'
AutoCAD SHX Text
4'
AutoCAD SHX Text
1/2"=1'-0"
AutoCAD SHX Text
A
AutoCAD SHX Text
B
AutoCAD SHX Text
C
AutoCAD SHX Text
D
AutoCAD SHX Text
E
AutoCAD SHX Text
F
AutoCAD SHX Text
G
AutoCAD SHX Text
H
AutoCAD SHX Text
1
AutoCAD SHX Text
2
AutoCAD SHX Text
3
AutoCAD SHX Text
4
AutoCAD SHX Text
REV.
AutoCAD SHX Text
NO.
AutoCAD SHX Text
DATE
AutoCAD SHX Text
DRWN
AutoCAD SHX Text
CHKD
AutoCAD SHX Text
REMARKS
AutoCAD SHX Text
DESIGNED BY:
AutoCAD SHX Text
DRAWN BY:
AutoCAD SHX Text
CROSS CHK'D BY:
AutoCAD SHX Text
APPROVED BY:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
SHEET CHK'D BY:
AutoCAD SHX Text
SHEET NO.
AutoCAD SHX Text
PROJECT NO.
AutoCAD SHX Text
FILE NAME:
AutoCAD SHX Text
0
AutoCAD SHX Text
1"
AutoCAD SHX Text
BAR IS ONE INCH ON
AutoCAD SHX Text
ORIGINAL DRAWING
AutoCAD SHX Text
IF NOT ONE INCH ON
AutoCAD SHX Text
THIS SHEET, ADJUST
AutoCAD SHX Text
SCALES ACCORDINGLY.
AutoCAD SHX Text
OCTOBER 2016
AutoCAD SHX Text
36207-105673
AutoCAD SHX Text
CDM SMITH ALL RIGHTS RESERVED.      REUSE OF DOCUMENTS:  THESE DOCUMENTS AND DESIGNS PROVIDED BY PROFESSIONAL SERVICE, INCORPORATED HEREIN, ARE THE PROPERTY OF CDM SMITH AND ARE NOT TO BE USED, IN WHOLE OR PART, FOR ANY OTHER PROJECT WITHOUT THE WRITTEN AUTHORIZATION OF CDM SMITH. 
AutoCAD SHX Text
NEW MEXICO EXTENDED PAYMENT PROVISION: THIS CONTRACT ALLOWS FOR OWNER TO MAKE PAYMENT WITHIN 45 DAYS AFTER SUBMISSION OF AN UNDISPUTED REQUEST FOR PAYMENT.
AutoCAD SHX Text
2
AutoCAD SHX Text
2

6000 Uptown Blvd N.E., Suite 200

Albuquerque, NM 87110

Tel: (505) 243-3200

©

CAMINO REAL REGIONAL UTILITY AUTHORITY

DOÑA ANA COUNTY, NEW MEXICO

WELL 19 REPLACEMENT AND

WELL 8A CONTROL BUILDING

www.bhinc.com

800.877.5332

SCHEMATIC 1

LAYOUT 2

E-06

WELL 19

CONTROL SCHEMATICS

AutoCAD SHX Text
N/O PUSH BUTTON
AutoCAD SHX Text
SCHEMATIC LEGEND
AutoCAD SHX Text
SOLENOID
AutoCAD SHX Text
M
AutoCAD SHX Text
FIELD DEVICE TERMINAL POINT
AutoCAD SHX Text
N/O CONTACT
AutoCAD SHX Text
N/C CONTACT
AutoCAD SHX Text
N/C PUSH BUTTON
AutoCAD SHX Text
H - HAND
AutoCAD SHX Text
N/O LIMIT SWITCH
AutoCAD SHX Text
N/C LIMIT SWITCH
AutoCAD SHX Text
O - OFF
AutoCAD SHX Text
A - AUTO
AutoCAD SHX Text
SELECTOR SWITCH
AutoCAD SHX Text
A
AutoCAD SHX Text
O
AutoCAD SHX Text
H
AutoCAD SHX Text
TEMPERATURE SWITCH. CLOSE ON RISING TEMPERATURE
AutoCAD SHX Text
PRESSURE SWITCH. N/C OPEN ON RISING PRESSURE
AutoCAD SHX Text
PRESSURE SWITCH. N/O CLOSE ON RISING PRESSURE
AutoCAD SHX Text
TIME DELAY RELAY (TDR) NORMALLY OPEN TIME DELAY CLOSED ON ENERGIZE
AutoCAD SHX Text
COIL: M= MOTOR; CR=CONTROL RELAY; PR = POWER RELAY
AutoCAD SHX Text
TDR NOTCE
AutoCAD SHX Text
NORMALLY CLOSED TIME DELAY OPEN ON ENERGIZE
AutoCAD SHX Text
TDR NCTOE
AutoCAD SHX Text
NORMALLY CLOSED TIME DELAY CLOSE ON ENERGIZE (OPENS IMMEDIATELY ON ENERGIZE, CLOSES AFTER DE-ENERGIZATION)
AutoCAD SHX Text
TDR NCTCE
AutoCAD SHX Text
INDICATOR LIGHT IN CONTROL PANEL (ALL TO BE PUSH TO TEST TYPE)
AutoCAD SHX Text
TIME DELAY RELAY (TDR) NORMALLY OPEN TIME DELAY OPEN ON DE-ENERGIZE (CLOSE IMMEDIATELY ON ENERGIZE)
AutoCAD SHX Text
TDR NOTOD
AutoCAD SHX Text
EMERGENCY STOP
AutoCAD SHX Text
HAND-OFF-AUTO
AutoCAD SHX Text
START
AutoCAD SHX Text
STOP
AutoCAD SHX Text
CONTROL POWER
AutoCAD SHX Text
W
AutoCAD SHX Text
WELL PUMP STARTER
AutoCAD SHX Text
R
AutoCAD SHX Text
PUMP ON
AutoCAD SHX Text
G
AutoCAD SHX Text
PUMP OFF
AutoCAD SHX Text
CONTROL VALVE OPEN
AutoCAD SHX Text
R
AutoCAD SHX Text
CONTROL VALVE CLOSED
AutoCAD SHX Text
G
AutoCAD SHX Text
H
AutoCAD SHX Text
A
AutoCAD SHX Text
O
AutoCAD SHX Text
MOTOR PROTECTION
AutoCAD SHX Text
SYSTEM FAULT
AutoCAD SHX Text
A
AutoCAD SHX Text
HIGH PRESSURE
AutoCAD SHX Text
A
AutoCAD SHX Text
ACKNOWLEDGE
AutoCAD SHX Text
ACKNOWLEDGE
AutoCAD SHX Text
PUMP RUN TIME
AutoCAD SHX Text
ETM
AutoCAD SHX Text
Y
AutoCAD SHX Text
LUBRICATION ON
AutoCAD SHX Text
MMR
AutoCAD SHX Text
SOFT START INTERFACE
AutoCAD SHX Text
SS
AutoCAD SHX Text
CAUTION: MOTOR STARTS AUTOMATICALLY UPON COMPLETION OF PRE-START LUBRICATION PERIOD
AutoCAD SHX Text
EMERG. STOP
AutoCAD SHX Text
H
AutoCAD SHX Text
0
AutoCAD SHX Text
A
AutoCAD SHX Text
XOO
AutoCAD SHX Text
OOX
AutoCAD SHX Text
A
AutoCAD SHX Text
PUMP RUNNING PILOT LIGHT
AutoCAD SHX Text
CONTROL VALVE CLOSED
AutoCAD SHX Text
CONTROL VALVE OPEN
AutoCAD SHX Text
PUMP OFF PILOT LIGHT
AutoCAD SHX Text
1
AutoCAD SHX Text
L
AutoCAD SHX Text
N
AutoCAD SHX Text
L1
AutoCAD SHX Text
480/120V CONTROL TRANSFORMER
AutoCAD SHX Text
SOLID STATE OL
AutoCAD SHX Text
X1
AutoCAD SHX Text
X2
AutoCAD SHX Text
H1
AutoCAD SHX Text
H4
AutoCAD SHX Text
L2
AutoCAD SHX Text
L3
AutoCAD SHX Text
POWER POLE
AutoCAD SHX Text
WELL PUMP MOTOR
AutoCAD SHX Text
STOP
AutoCAD SHX Text
CONTROL VALVE OPEN
AutoCAD SHX Text
SS RUN/ STOP INPUT
AutoCAD SHX Text
PUMP RUN PERMISSION RELAY
AutoCAD SHX Text
CONTROL VALVE SOLENOID DELAY
AutoCAD SHX Text
CONTROL VALVE CLOSED LIMIT SWITCH
AutoCAD SHX Text
PUMP RUN COMMAND
AutoCAD SHX Text
POWER FACTOR CORRECTION CAPACITORS
AutoCAD SHX Text
LIMIT SWITCH OPENS ON VALVE FULL OPEN
AutoCAD SHX Text
MOTOR MANAGEMENT RELAY (MMR)
AutoCAD SHX Text
TO RTDs (TYP. OF 4.)
AutoCAD SHX Text
GROUND FAULT CT
AutoCAD SHX Text
PHASE CT
AutoCAD SHX Text
PR
AutoCAD SHX Text
SOFT START SHORTING CONTACTOR
AutoCAD SHX Text
SHORTING CONTACTOR ACTIVATE
AutoCAD SHX Text
L
AutoCAD SHX Text
N
AutoCAD SHX Text
L
AutoCAD SHX Text
N
AutoCAD SHX Text
TDR
AutoCAD SHX Text
CR7
AutoCAD SHX Text
SYSTEM HIGH PRESSURE PILOT LIGHT
AutoCAD SHX Text
SYSTEM FAULT CONTROL RELAY
AutoCAD SHX Text
SYSTEM FAULT PILOT LIGHT
AutoCAD SHX Text
SYSTEM HIGH PRESSURE CONTROL RELAY
AutoCAD SHX Text
PUSH TO ACKNOWLEDGE
AutoCAD SHX Text
HIGH PRESSURE
AutoCAD SHX Text
TDR4
AutoCAD SHX Text
SYSTEM FAULT
AutoCAD SHX Text
PUSH TO ACKNOWLEDGE
AutoCAD SHX Text
A
AutoCAD SHX Text
SOLID STATE SOFT START (SS)
AutoCAD SHX Text
(SS) FAULT
AutoCAD SHX Text
FR
AutoCAD SHX Text
HIGH DISCHARGE PRESSURE SWITCH
AutoCAD SHX Text
CR
AutoCAD SHX Text
SYSTEM HIGH PRESSURE TIME DELAY RELAY
AutoCAD SHX Text
CR1
AutoCAD SHX Text
START
AutoCAD SHX Text
RC
AutoCAD SHX Text
CR1
AutoCAD SHX Text
MSR
AutoCAD SHX Text
CR4
AutoCAD SHX Text
MSR
AutoCAD SHX Text
CR2
AutoCAD SHX Text
SCA
AutoCAD SHX Text
SC
AutoCAD SHX Text
CR2
AutoCAD SHX Text
CR4
AutoCAD SHX Text
CR5
AutoCAD SHX Text
MSR
AutoCAD SHX Text
CR3
AutoCAD SHX Text
MMR FAULT
AutoCAD SHX Text
SCA
AutoCAD SHX Text
END OF RAMP
AutoCAD SHX Text
MOTOR START RELAY
AutoCAD SHX Text
TDR3 NOTCE
AutoCAD SHX Text
TDR3
AutoCAD SHX Text
CONTROL VALVE SOLENOID
AutoCAD SHX Text
CR4
AutoCAD SHX Text
STOP
AutoCAD SHX Text
+24V
AutoCAD SHX Text
RUN
AutoCAD SHX Text
120 VAC
AutoCAD SHX Text
PFC
AutoCAD SHX Text
RTU
AutoCAD SHX Text
MSR
AutoCAD SHX Text
(REMOTE TERMINAL UNIT OUTPUT)
AutoCAD SHX Text
CR7
AutoCAD SHX Text
TDR4 NOTCE
AutoCAD SHX Text
FR
AutoCAD SHX Text
PFC
AutoCAD SHX Text
PFC
AutoCAD SHX Text
MMR
AutoCAD SHX Text
(0-30 SEC)
AutoCAD SHX Text
CR
AutoCAD SHX Text
A
AutoCAD SHX Text
CR
AutoCAD SHX Text
FR
AutoCAD SHX Text
CR7
AutoCAD SHX Text
CR
AutoCAD SHX Text
R
AutoCAD SHX Text
CR
AutoCAD SHX Text
TDR1
AutoCAD SHX Text
CR
AutoCAD SHX Text
ETM
AutoCAD SHX Text
PUMP RUN TIME TOTALIZER (MOUNT IN FRONT PANEL)
AutoCAD SHX Text
PR
AutoCAD SHX Text
POWER FACTOR CORRECTION CONTACTOR
AutoCAD SHX Text
PFC
AutoCAD SHX Text
SCA
AutoCAD SHX Text
TDR
AutoCAD SHX Text
(0-30 MIN)
AutoCAD SHX Text
CR
AutoCAD SHX Text
R
AutoCAD SHX Text
G
AutoCAD SHX Text
CR
AutoCAD SHX Text
G
AutoCAD SHX Text
CR6
AutoCAD SHX Text
CR
AutoCAD SHX Text
MOTOR START TIME DELAY
AutoCAD SHX Text
CR1
AutoCAD SHX Text
TDR1 NOTCE
AutoCAD SHX Text
PUMP LUBRICATION SOLENOID VALVE
AutoCAD SHX Text
SV1
AutoCAD SHX Text
TDR
AutoCAD SHX Text
(0-30 MIN)
AutoCAD SHX Text
CR1
AutoCAD SHX Text
CR1
AutoCAD SHX Text
PERMISSION RELAY FORWARD
AutoCAD SHX Text
CR3
AutoCAD SHX Text
CR
AutoCAD SHX Text
CR2
AutoCAD SHX Text
CR3
AutoCAD SHX Text
MSR
AutoCAD SHX Text
CR
AutoCAD SHX Text
CR8
AutoCAD SHX Text
CHLORINE PUMP START
AutoCAD SHX Text
250 HP P-3119
AutoCAD SHX Text
CONTROL POWER
AutoCAD SHX Text
W
AutoCAD SHX Text
REMOTE RUN REQUEST
AutoCAD SHX Text
R
AutoCAD SHX Text
REMOTE RUN REQUEST INDICATOR
AutoCAD SHX Text
RC
AutoCAD SHX Text
CR
AutoCAD SHX Text
LUBRICATION ON PILOT LIGHT
AutoCAD SHX Text
Y
AutoCAD SHX Text
PHASE PT
AutoCAD SHX Text
CL2
AutoCAD SHX Text
L
AutoCAD SHX Text
N
AutoCAD SHX Text
TO DC POWER SUPPLY
AutoCAD SHX Text
CIRCUIT BREAKER
AutoCAD SHX Text
SHORTING CONTACTOR
AutoCAD SHX Text
120 VAC SUPPLY TO MMR
AutoCAD SHX Text
SV2
AutoCAD SHX Text
ISOLATION CONTACTOR
AutoCAD SHX Text
ISOLATION CONTACTOR
AutoCAD SHX Text
IC
AutoCAD SHX Text
FR
AutoCAD SHX Text
PR
AutoCAD SHX Text
CR7
AutoCAD SHX Text
TDR2
AutoCAD SHX Text
ISOLATION CONTACTOR ACTIVATE
AutoCAD SHX Text
TDR2 NOTOD
AutoCAD SHX Text
TDR
AutoCAD SHX Text
2
AutoCAD SHX Text
MSR
AutoCAD SHX Text
A
AutoCAD SHX Text
A
AutoCAD SHX Text
(0-5 MIN)
AutoCAD SHX Text
3
AutoCAD SHX Text
A
AutoCAD SHX Text
A
AutoCAD SHX Text
CL1
AutoCAD SHX Text
L1
AutoCAD SHX Text
L2
AutoCAD SHX Text
L3
AutoCAD SHX Text
T1
AutoCAD SHX Text
T2
AutoCAD SHX Text
T3
AutoCAD SHX Text
A2
AutoCAD SHX Text
B2
AutoCAD SHX Text
C2
AutoCAD SHX Text
CR6
AutoCAD SHX Text
KEYED NOTES: 1. TEMPORARY INSTALLATION OF A N/O MOMENTARY PUSHBUTTON SWITCH ACROSS THESE FIELD TERMINALS WILL ALLOW THE PUMP MOTOR TO BE "BUMPED" TO CHECK DIRECTION OF ROTATION. 2. FOR THE SAKE OF CLARITY ALL PILOT LIGHT PUSH-TO-TEST CIRCUITS ARE NOT SHOWN. ALL PILOT LIGHTS TO HAVE PUSH-TO-TEST FEATURE. 3.SET TIME DELAY ON DE-ENERGIZE TIME TO BE SLIGHTLY LONGER THAN SET TIME DELAY ON DE-ENERGIZE TIME TO BE SLIGHTLY LONGER THAN EXPECTED DECELERATION TIME FROM RATED SPEED TO ZERO SPEED.
AutoCAD SHX Text
PUMP ON
AutoCAD SHX Text
DO
AutoCAD SHX Text
MSR
AutoCAD SHX Text
PUMP OFF
AutoCAD SHX Text
DO
AutoCAD SHX Text
MSR
AutoCAD SHX Text
SYSTEM FAULT
AutoCAD SHX Text
DO
AutoCAD SHX Text
FR
AutoCAD SHX Text
SYSTEM HIGH PRESSURE
AutoCAD SHX Text
DO
AutoCAD SHX Text
CR7
AutoCAD SHX Text
CHORINE PUMP START/STOP
AutoCAD SHX Text
MS
AutoCAD SHX Text
CR8
AutoCAD SHX Text
DI
AutoCAD SHX Text
RC
AutoCAD SHX Text
DO
AutoCAD SHX Text
AUTO
AutoCAD SHX Text
PUMP IN AUTO
AutoCAD SHX Text
REMOTE RUN REQUEST
AutoCAD SHX Text
A
AutoCAD SHX Text
B
AutoCAD SHX Text
C
AutoCAD SHX Text
D
AutoCAD SHX Text
E
AutoCAD SHX Text
F
AutoCAD SHX Text
G
AutoCAD SHX Text
H
AutoCAD SHX Text
1
AutoCAD SHX Text
2
AutoCAD SHX Text
3
AutoCAD SHX Text
4
AutoCAD SHX Text
REV.
AutoCAD SHX Text
NO.
AutoCAD SHX Text
DATE
AutoCAD SHX Text
DRWN
AutoCAD SHX Text
CHKD
AutoCAD SHX Text
REMARKS
AutoCAD SHX Text
DESIGNED BY:
AutoCAD SHX Text
DRAWN BY:
AutoCAD SHX Text
CROSS CHK'D BY:
AutoCAD SHX Text
APPROVED BY:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
SHEET CHK'D BY:
AutoCAD SHX Text
SHEET NO.
AutoCAD SHX Text
PROJECT NO.
AutoCAD SHX Text
FILE NAME:
AutoCAD SHX Text
OCTOBER 2016
AutoCAD SHX Text
36207-105673
AutoCAD SHX Text
CDM SMITH ALL RIGHTS RESERVED.      REUSE OF DOCUMENTS:  THESE DOCUMENTS AND DESIGNS PROVIDED BY PROFESSIONAL SERVICE, INCORPORATED HEREIN, ARE THE PROPERTY OF CDM SMITH AND ARE NOT TO BE USED, IN WHOLE OR PART, FOR ANY OTHER PROJECT WITHOUT THE WRITTEN AUTHORIZATION OF CDM SMITH. 
AutoCAD SHX Text
NEW MEXICO EXTENDED PAYMENT PROVISION: THIS CONTRACT ALLOWS FOR OWNER TO MAKE PAYMENT WITHIN 45 DAYS AFTER SUBMISSION OF AN UNDISPUTED REQUEST FOR PAYMENT.
AutoCAD SHX Text
--
AutoCAD SHX Text
WELL PUMP CONTROL
AutoCAD SHX Text
NO SCALE
AutoCAD SHX Text
--
AutoCAD SHX Text
WELL PUMP MCC FRONT STARTER SECTION
AutoCAD SHX Text
NO SCALE
AutoCAD SHX Text
2
AutoCAD SHX Text
E-14
AutoCAD SHX Text
E. FLEISCHER
AutoCAD SHX Text
L. MILLER
AutoCAD SHX Text
M. THOMPSON
AutoCAD SHX Text
M. THOMPSON
AutoCAD SHX Text
2
AutoCAD SHX Text
10/16
AutoCAD SHX Text
LLM
AutoCAD SHX Text
ETF
AutoCAD SHX Text
CHANGES TO CONTROL DIAGRAM
AutoCAD SHX Text
M. THOMPSON

E-09

WELL 19

ELECTRICAL SCHEDULES6000 Uptown Blvd N.E., Suite 200

Albuquerque, NM 87110

Tel: (505) 243-3200

©

CAMINO REAL REGIONAL UTILITY AUTHORITY

DOÑA ANA COUNTY, NEW MEXICO

WELL 19 REPLACEMENT AND

WELL 8A CONTROL BUILDING

www.bhinc.com

800.877.5332

SCHEDULE 2

SCHEDULE 3

SCHEDULE 4

SCHEDULE 1

AutoCAD SHX Text
E-09
AutoCAD SHX Text
E. FLEISCHER
AutoCAD SHX Text
L. MILLER
AutoCAD SHX Text
M. THOMPSON
AutoCAD SHX Text
M. THOMPSON
AutoCAD SHX Text
2
AutoCAD SHX Text
10/16
AutoCAD SHX Text
LLM
AutoCAD SHX Text
ETF
AutoCAD SHX Text
CHANGES TO POWER AND INSTRUMENTATION CONDUIT SCHEDULES
AutoCAD SHX Text
M. THOMPSON
AutoCAD SHX Text
A
AutoCAD SHX Text
B
AutoCAD SHX Text
C
AutoCAD SHX Text
D
AutoCAD SHX Text
E
AutoCAD SHX Text
F
AutoCAD SHX Text
G
AutoCAD SHX Text
H
AutoCAD SHX Text
1
AutoCAD SHX Text
2
AutoCAD SHX Text
3
AutoCAD SHX Text
4
AutoCAD SHX Text
REV.
AutoCAD SHX Text
NO.
AutoCAD SHX Text
DATE
AutoCAD SHX Text
DRWN
AutoCAD SHX Text
CHKD
AutoCAD SHX Text
REMARKS
AutoCAD SHX Text
DESIGNED BY:
AutoCAD SHX Text
DRAWN BY:
AutoCAD SHX Text
CROSS CHK'D BY:
AutoCAD SHX Text
APPROVED BY:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
SHEET CHK'D BY:
AutoCAD SHX Text
SHEET NO.
AutoCAD SHX Text
PROJECT NO.
AutoCAD SHX Text
FILE NAME:
AutoCAD SHX Text
OCTOBER 2016
AutoCAD SHX Text
36207-105673
AutoCAD SHX Text
CDM SMITH ALL RIGHTS RESERVED.      REUSE OF DOCUMENTS:  THESE DOCUMENTS AND DESIGNS PROVIDED BY PROFESSIONAL SERVICE, INCORPORATED HEREIN, ARE THE PROPERTY OF CDM SMITH AND ARE NOT TO BE USED, IN WHOLE OR PART, FOR ANY OTHER PROJECT WITHOUT THE WRITTEN AUTHORIZATION OF CDM SMITH. 
AutoCAD SHX Text
NEW MEXICO EXTENDED PAYMENT PROVISION: THIS CONTRACT ALLOWS FOR OWNER TO MAKE PAYMENT WITHIN 45 DAYS AFTER SUBMISSION OF AN UNDISPUTED REQUEST FOR PAYMENT.
AutoCAD SHX Text
PANEL LPA
AutoCAD SHX Text
NOT TO SCALE
AutoCAD SHX Text
-
AutoCAD SHX Text
POWER CONDUIT
AutoCAD SHX Text
NOT TO SCALE
AutoCAD SHX Text
-
AutoCAD SHX Text
INSTRUMENTATION CONDUIT
AutoCAD SHX Text
NOT TO SCALE
AutoCAD SHX Text
-
AutoCAD SHX Text
LIGHT FIXTURE
AutoCAD SHX Text
NOT TO SCALE
AutoCAD SHX Text
E-04
AutoCAD SHX Text
2
AutoCAD SHX Text
2
AutoCAD SHX Text
2

E-14

WELL 8A

CONTROL SCHEMATICS6000 Uptown Blvd N.E., Suite 200

Albuquerque, NM 87110

Tel: (505) 243-3200

©

CAMINO REAL REGIONAL UTILITY AUTHORITY

DOÑA ANA COUNTY, NEW MEXICO

WELL 19 REPLACEMENT AND

WELL 8A CONTROL BUILDING

www.bhinc.com

800.877.5332

SCHEMATIC 1

LAYOUT 2

AutoCAD SHX Text
N/O PUSH BUTTON
AutoCAD SHX Text
SCHEMATIC LEGEND
AutoCAD SHX Text
SOLENOID
AutoCAD SHX Text
M
AutoCAD SHX Text
FIELD DEVICE TERMINAL POINT
AutoCAD SHX Text
N/O CONTACT
AutoCAD SHX Text
N/C CONTACT
AutoCAD SHX Text
N/C PUSH BUTTON
AutoCAD SHX Text
H - HAND
AutoCAD SHX Text
N/O LIMIT SWITCH
AutoCAD SHX Text
N/C LIMIT SWITCH
AutoCAD SHX Text
O - OFF
AutoCAD SHX Text
A - AUTO
AutoCAD SHX Text
SELECTOR SWITCH
AutoCAD SHX Text
A
AutoCAD SHX Text
O
AutoCAD SHX Text
H
AutoCAD SHX Text
TEMPERATURE SWITCH. CLOSE ON RISING TEMPERATURE
AutoCAD SHX Text
PRESSURE SWITCH. N/C OPEN ON RISING PRESSURE
AutoCAD SHX Text
PRESSURE SWITCH. N/O CLOSE ON RISING PRESSURE
AutoCAD SHX Text
TIME DELAY RELAY (TDR) NORMALLY OPEN TIME DELAY CLOSED ON ENERGIZE
AutoCAD SHX Text
COIL: M= MOTOR; CR=CONTROL RELAY; PR = POWER RELAY
AutoCAD SHX Text
TDR NOTCE
AutoCAD SHX Text
NORMALLY CLOSED TIME DELAY OPEN ON ENERGIZE
AutoCAD SHX Text
TDR NCTOE
AutoCAD SHX Text
NORMALLY CLOSED TIME DELAY CLOSE ON ENERGIZE (OPENS IMMEDIATELY ON ENERGIZE, CLOSES AFTER DE-ENERGIZATION)
AutoCAD SHX Text
TDR NCTCE
AutoCAD SHX Text
INDICATOR LIGHT IN CONTROL PANEL (ALL TO BE PUSH TO TEST TYPE)
AutoCAD SHX Text
TIME DELAY RELAY (TDR) NORMALLY OPEN TIME DELAY OPEN ON DE-ENERGIZE (CLOSE IMMEDIATELY ON ENERGIZE)
AutoCAD SHX Text
TDR NOTOD
AutoCAD SHX Text
EMERGENCY STOP
AutoCAD SHX Text
HAND-OFF-AUTO
AutoCAD SHX Text
START
AutoCAD SHX Text
STOP
AutoCAD SHX Text
CONTROL POWER
AutoCAD SHX Text
W
AutoCAD SHX Text
WELL PUMP STARTER
AutoCAD SHX Text
R
AutoCAD SHX Text
PUMP ON
AutoCAD SHX Text
G
AutoCAD SHX Text
PUMP OFF
AutoCAD SHX Text
CONTROL VALVE OPEN
AutoCAD SHX Text
R
AutoCAD SHX Text
CONTROL VALVE CLOSED
AutoCAD SHX Text
G
AutoCAD SHX Text
H
AutoCAD SHX Text
A
AutoCAD SHX Text
O
AutoCAD SHX Text
MOTOR PROTECTION
AutoCAD SHX Text
SYSTEM FAULT
AutoCAD SHX Text
A
AutoCAD SHX Text
HIGH PRESSURE
AutoCAD SHX Text
A
AutoCAD SHX Text
ACKNOWLEDGE
AutoCAD SHX Text
ACKNOWLEDGE
AutoCAD SHX Text
PUMP RUN TIME
AutoCAD SHX Text
ETM
AutoCAD SHX Text
Y
AutoCAD SHX Text
LUBRICATION ON
AutoCAD SHX Text
MMR
AutoCAD SHX Text
SOFT START INTERFACE
AutoCAD SHX Text
SS
AutoCAD SHX Text
CAUTION: MOTOR STARTS AUTOMATICALLY UPON COMPLETION OF PRE-START LUBRICATION PERIOD
AutoCAD SHX Text
EMERG. STOP
AutoCAD SHX Text
H
AutoCAD SHX Text
0
AutoCAD SHX Text
A
AutoCAD SHX Text
XOO
AutoCAD SHX Text
OOX
AutoCAD SHX Text
A
AutoCAD SHX Text
PUMP RUNNING PILOT LIGHT
AutoCAD SHX Text
CONTROL VALVE CLOSED
AutoCAD SHX Text
CONTROL VALVE OPEN
AutoCAD SHX Text
PUMP OFF PILOT LIGHT
AutoCAD SHX Text
1
AutoCAD SHX Text
L
AutoCAD SHX Text
N
AutoCAD SHX Text
L1
AutoCAD SHX Text
480/120V CONTROL TRANSFORMER
AutoCAD SHX Text
SOLID STATE OL
AutoCAD SHX Text
X1
AutoCAD SHX Text
X2
AutoCAD SHX Text
H1
AutoCAD SHX Text
H4
AutoCAD SHX Text
L2
AutoCAD SHX Text
L3
AutoCAD SHX Text
POWER POLE
AutoCAD SHX Text
WELL PUMP MOTOR
AutoCAD SHX Text
STOP
AutoCAD SHX Text
CONTROL VALVE OPEN
AutoCAD SHX Text
SS RUN/ STOP INPUT
AutoCAD SHX Text
PUMP RUN PERMISSION RELAY
AutoCAD SHX Text
CONTROL VALVE SOLENOID DELAY
AutoCAD SHX Text
CONTROL VALVE CLOSED LIMIT SWITCH
AutoCAD SHX Text
PUMP RUN COMMAND
AutoCAD SHX Text
POWER FACTOR CORRECTION CAPACITORS
AutoCAD SHX Text
LIMIT SWITCH OPENS ON VALVE FULL OPEN
AutoCAD SHX Text
MOTOR MANAGEMENT RELAY (MMR)
AutoCAD SHX Text
TO RTDs (TYP. OF 4.)
AutoCAD SHX Text
GROUND FAULT CT
AutoCAD SHX Text
PHASE CT
AutoCAD SHX Text
PR
AutoCAD SHX Text
SOFT START SHORTING CONTACTOR
AutoCAD SHX Text
SHORTING CONTACTOR ACTIVATE
AutoCAD SHX Text
L
AutoCAD SHX Text
N
AutoCAD SHX Text
L
AutoCAD SHX Text
N
AutoCAD SHX Text
TDR
AutoCAD SHX Text
CR7
AutoCAD SHX Text
SYSTEM HIGH PRESSURE PILOT LIGHT
AutoCAD SHX Text
SYSTEM FAULT CONTROL RELAY
AutoCAD SHX Text
SYSTEM FAULT PILOT LIGHT
AutoCAD SHX Text
SYSTEM HIGH PRESSURE CONTROL RELAY
AutoCAD SHX Text
PUSH TO ACKNOWLEDGE
AutoCAD SHX Text
HIGH PRESSURE
AutoCAD SHX Text
TDR4
AutoCAD SHX Text
SYSTEM FAULT
AutoCAD SHX Text
PUSH TO ACKNOWLEDGE
AutoCAD SHX Text
A
AutoCAD SHX Text
SOLID STATE SOFT START (SS)
AutoCAD SHX Text
(SS) FAULT
AutoCAD SHX Text
FR
AutoCAD SHX Text
HIGH DISCHARGE PRESSURE SWITCH
AutoCAD SHX Text
CR
AutoCAD SHX Text
SYSTEM HIGH PRESSURE TIME DELAY RELAY
AutoCAD SHX Text
CR1
AutoCAD SHX Text
START
AutoCAD SHX Text
RC
AutoCAD SHX Text
CR1
AutoCAD SHX Text
MSR
AutoCAD SHX Text
CR4
AutoCAD SHX Text
MSR
AutoCAD SHX Text
CR2
AutoCAD SHX Text
SCA
AutoCAD SHX Text
SC
AutoCAD SHX Text
CR2
AutoCAD SHX Text
CR4
AutoCAD SHX Text
CR5
AutoCAD SHX Text
MSR
AutoCAD SHX Text
CR3
AutoCAD SHX Text
MMR FAULT
AutoCAD SHX Text
SCA
AutoCAD SHX Text
END OF RAMP
AutoCAD SHX Text
MOTOR START RELAY
AutoCAD SHX Text
TDR3 NOTCE
AutoCAD SHX Text
TDR3
AutoCAD SHX Text
CONTROL VALVE SOLENOID
AutoCAD SHX Text
CR4
AutoCAD SHX Text
STOP
AutoCAD SHX Text
+24V
AutoCAD SHX Text
RUN
AutoCAD SHX Text
120 VAC
AutoCAD SHX Text
PFC
AutoCAD SHX Text
RTU
AutoCAD SHX Text
MSR
AutoCAD SHX Text
(REMOTE TERMINAL UNIT OUTPUT)
AutoCAD SHX Text
CR7
AutoCAD SHX Text
TDR4 NOTCE
AutoCAD SHX Text
FR
AutoCAD SHX Text
PFC
AutoCAD SHX Text
PFC
AutoCAD SHX Text
MMR
AutoCAD SHX Text
(0-30 SEC)
AutoCAD SHX Text
CR
AutoCAD SHX Text
A
AutoCAD SHX Text
CR
AutoCAD SHX Text
FR
AutoCAD SHX Text
CR7
AutoCAD SHX Text
CR
AutoCAD SHX Text
R
AutoCAD SHX Text
CR
AutoCAD SHX Text
TDR1
AutoCAD SHX Text
CR
AutoCAD SHX Text
ETM
AutoCAD SHX Text
PUMP RUN TIME TOTALIZER (MOUNT IN FRONT PANEL)
AutoCAD SHX Text
PR
AutoCAD SHX Text
POWER FACTOR CORRECTION CONTACTOR
AutoCAD SHX Text
PFC
AutoCAD SHX Text
SCA
AutoCAD SHX Text
TDR
AutoCAD SHX Text
(0-30 MIN)
AutoCAD SHX Text
CR
AutoCAD SHX Text
R
AutoCAD SHX Text
G
AutoCAD SHX Text
CR
AutoCAD SHX Text
G
AutoCAD SHX Text
CR6
AutoCAD SHX Text
CR
AutoCAD SHX Text
MOTOR START TIME DELAY
AutoCAD SHX Text
CR1
AutoCAD SHX Text
TDR1 NOTCE
AutoCAD SHX Text
PUMP LUBRICATION SOLENOID VALVE
AutoCAD SHX Text
SV1
AutoCAD SHX Text
TDR
AutoCAD SHX Text
(0-30 MIN)
AutoCAD SHX Text
CR1
AutoCAD SHX Text
CR1
AutoCAD SHX Text
PERMISSION RELAY FORWARD
AutoCAD SHX Text
CR3
AutoCAD SHX Text
CR
AutoCAD SHX Text
CR2
AutoCAD SHX Text
CR3
AutoCAD SHX Text
MSR
AutoCAD SHX Text
CR
AutoCAD SHX Text
CR8
AutoCAD SHX Text
CHLORINE PUMP START
AutoCAD SHX Text
CONTROL POWER
AutoCAD SHX Text
W
AutoCAD SHX Text
REMOTE RUN REQUEST
AutoCAD SHX Text
R
AutoCAD SHX Text
REMOTE RUN REQUEST INDICATOR
AutoCAD SHX Text
RC
AutoCAD SHX Text
CR
AutoCAD SHX Text
LUBRICATION ON PILOT LIGHT
AutoCAD SHX Text
Y
AutoCAD SHX Text
PHASE PT
AutoCAD SHX Text
CL2
AutoCAD SHX Text
L
AutoCAD SHX Text
N
AutoCAD SHX Text
TO DC POWER SUPPLY
AutoCAD SHX Text
CIRCUIT BREAKER
AutoCAD SHX Text
SHORTING CONTACTOR
AutoCAD SHX Text
120 VAC SUPPLY TO MMR
AutoCAD SHX Text
SV2
AutoCAD SHX Text
ISOLATION CONTACTOR
AutoCAD SHX Text
ISOLATION CONTACTOR
AutoCAD SHX Text
IC
AutoCAD SHX Text
FR
AutoCAD SHX Text
PR
AutoCAD SHX Text
CR7
AutoCAD SHX Text
TDR2
AutoCAD SHX Text
ISOLATION CONTACTOR ACTIVATE
AutoCAD SHX Text
TDR2 NOTOD
AutoCAD SHX Text
TDR
AutoCAD SHX Text
2
AutoCAD SHX Text
MSR
AutoCAD SHX Text
A
AutoCAD SHX Text
A
AutoCAD SHX Text
(0-5 MIN)
AutoCAD SHX Text
3
AutoCAD SHX Text
A
AutoCAD SHX Text
A
AutoCAD SHX Text
CL1
AutoCAD SHX Text
L1
AutoCAD SHX Text
L2
AutoCAD SHX Text
L3
AutoCAD SHX Text
T1
AutoCAD SHX Text
T2
AutoCAD SHX Text
T3
AutoCAD SHX Text
A2
AutoCAD SHX Text
B2
AutoCAD SHX Text
C2
AutoCAD SHX Text
CR6
AutoCAD SHX Text
125 HP P-3108
AutoCAD SHX Text
KEYED NOTES: 1. TEMPORARY INSTALLATION OF A N/O MOMENTARY PUSHBUTTON SWITCH ACROSS THESE FIELD TERMINALS WILL ALLOW THE PUMP MOTOR TO BE "BUMPED" TO CHECK DIRECTION OF ROTATION. 2. FOR THE SAKE OF CLARITY ALL PILOT LIGHT PUSH-TO-TEST CIRCUITS ARE NOT SHOWN. ALL PILOT LIGHTS TO HAVE PUSH-TO-TEST FEATURE. 3.SET TIME DELAY ON DE-ENERGIZE TIME TO BE SLIGHTLY LONGER THAN SET TIME DELAY ON DE-ENERGIZE TIME TO BE SLIGHTLY LONGER THAN EXPECTED DECELERATION TIME FROM RATED SPEED TO ZERO SPEED.
AutoCAD SHX Text
PUMP ON
AutoCAD SHX Text
DO
AutoCAD SHX Text
MSR
AutoCAD SHX Text
PUMP OFF
AutoCAD SHX Text
DO
AutoCAD SHX Text
MSR
AutoCAD SHX Text
SYSTEM FAULT
AutoCAD SHX Text
DO
AutoCAD SHX Text
FR
AutoCAD SHX Text
SYSTEM HIGH PRESSURE
AutoCAD SHX Text
DO
AutoCAD SHX Text
CR7
AutoCAD SHX Text
CHORINE PUMP START/STOP
AutoCAD SHX Text
MS
AutoCAD SHX Text
CR8
AutoCAD SHX Text
DI
AutoCAD SHX Text
RC
AutoCAD SHX Text
DO
AutoCAD SHX Text
AUTO
AutoCAD SHX Text
PUMP IN AUTO
AutoCAD SHX Text
REMOTE RUN REQUEST
AutoCAD SHX Text
E-14
AutoCAD SHX Text
E. FLEISCHER
AutoCAD SHX Text
L. MILLER
AutoCAD SHX Text
M. THOMPSON
AutoCAD SHX Text
M. THOMPSON
AutoCAD SHX Text
2
AutoCAD SHX Text
10/16
AutoCAD SHX Text
LLM
AutoCAD SHX Text
ETF
AutoCAD SHX Text
CHANGES TO CONTROL DIAGRAM
AutoCAD SHX Text
M. THOMPSON
AutoCAD SHX Text
A
AutoCAD SHX Text
B
AutoCAD SHX Text
C
AutoCAD SHX Text
D
AutoCAD SHX Text
E
AutoCAD SHX Text
F
AutoCAD SHX Text
G
AutoCAD SHX Text
H
AutoCAD SHX Text
1
AutoCAD SHX Text
2
AutoCAD SHX Text
3
AutoCAD SHX Text
4
AutoCAD SHX Text
REV.
AutoCAD SHX Text
NO.
AutoCAD SHX Text
DATE
AutoCAD SHX Text
DRWN
AutoCAD SHX Text
CHKD
AutoCAD SHX Text
REMARKS
AutoCAD SHX Text
DESIGNED BY:
AutoCAD SHX Text
DRAWN BY:
AutoCAD SHX Text
CROSS CHK'D BY:
AutoCAD SHX Text
APPROVED BY:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
SHEET CHK'D BY:
AutoCAD SHX Text
SHEET NO.
AutoCAD SHX Text
PROJECT NO.
AutoCAD SHX Text
FILE NAME:
AutoCAD SHX Text
OCTOBER 2016
AutoCAD SHX Text
CDM SMITH ALL RIGHTS RESERVED.      REUSE OF DOCUMENTS:  THESE DOCUMENTS AND DESIGNS PROVIDED BY PROFESSIONAL SERVICE, INCORPORATED HEREIN, ARE THE PROPERTY OF CDM SMITH AND ARE NOT TO BE USED, IN WHOLE OR PART, FOR ANY OTHER PROJECT WITHOUT THE WRITTEN AUTHORIZATION OF CDM SMITH. 
AutoCAD SHX Text
NEW MEXICO EXTENDED PAYMENT PROVISION: THIS CONTRACT ALLOWS FOR OWNER TO MAKE PAYMENT WITHIN 45 DAYS AFTER SUBMISSION OF AN UNDISPUTED REQUEST FOR PAYMENT.
AutoCAD SHX Text
36207-106147
AutoCAD SHX Text
--
AutoCAD SHX Text
WELL PUMP CONTROL
AutoCAD SHX Text
NO SCALE
AutoCAD SHX Text
--
AutoCAD SHX Text
WELL PUMP MCC FRONT STARTER SECTION
AutoCAD SHX Text
NO SCALE
AutoCAD SHX Text
2

6000 Uptown Blvd N.E., Suite 200

Albuquerque, NM 87110

Tel: (505) 243-3200

©

CAMINO REAL REGIONAL UTILITY AUTHORITY

DOÑA ANA COUNTY, NEW MEXICO

WELL 19 REPLACEMENT AND

WELL 8A CONTROL BUILDING

www.bhinc.com

800.877.5332

SCHEDULE 2

SCHEDULE 4

5

SCHEDULE 1

SCHEDULE

SCHEDULE 3

SCHEDULE 6

E-17

WELL 8A

ELECTRICAL SCHEDULES

AutoCAD SHX Text
A
AutoCAD SHX Text
B
AutoCAD SHX Text
C
AutoCAD SHX Text
D
AutoCAD SHX Text
E
AutoCAD SHX Text
F
AutoCAD SHX Text
G
AutoCAD SHX Text
H
AutoCAD SHX Text
1
AutoCAD SHX Text
2
AutoCAD SHX Text
3
AutoCAD SHX Text
4
AutoCAD SHX Text
REV.
AutoCAD SHX Text
NO.
AutoCAD SHX Text
DATE
AutoCAD SHX Text
DRWN
AutoCAD SHX Text
CHKD
AutoCAD SHX Text
REMARKS
AutoCAD SHX Text
DESIGNED BY:
AutoCAD SHX Text
DRAWN BY:
AutoCAD SHX Text
CROSS CHK'D BY:
AutoCAD SHX Text
APPROVED BY:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
SHEET CHK'D BY:
AutoCAD SHX Text
SHEET NO.
AutoCAD SHX Text
PROJECT NO.
AutoCAD SHX Text
FILE NAME:
AutoCAD SHX Text
OCTOBER 2016
AutoCAD SHX Text
CDM SMITH ALL RIGHTS RESERVED.      REUSE OF DOCUMENTS:  THESE DOCUMENTS AND DESIGNS PROVIDED BY PROFESSIONAL SERVICE, INCORPORATED HEREIN, ARE THE PROPERTY OF CDM SMITH AND ARE NOT TO BE USED, IN WHOLE OR PART, FOR ANY OTHER PROJECT WITHOUT THE WRITTEN AUTHORIZATION OF CDM SMITH. 
AutoCAD SHX Text
NEW MEXICO EXTENDED PAYMENT PROVISION: THIS CONTRACT ALLOWS FOR OWNER TO MAKE PAYMENT WITHIN 45 DAYS AFTER SUBMISSION OF AN UNDISPUTED REQUEST FOR PAYMENT.
AutoCAD SHX Text
36207-106147
AutoCAD SHX Text
PANEL L1
AutoCAD SHX Text
NOT TO SCALE
AutoCAD SHX Text
-
AutoCAD SHX Text
POWER CONDUIT
AutoCAD SHX Text
NOT TO SCALE
AutoCAD SHX Text
-
AutoCAD SHX Text
INSTRUMENTATION CONDUIT
AutoCAD SHX Text
-
AutoCAD SHX Text
LIGHT FIXTURE
AutoCAD SHX Text
NOT TO SCALE
AutoCAD SHX Text
E-04
AutoCAD SHX Text
PANEL HB
AutoCAD SHX Text
NOT TO SCALE
AutoCAD SHX Text
-
AutoCAD SHX Text
PANEL HA
AutoCAD SHX Text
NOT TO SCALE
AutoCAD SHX Text
-
AutoCAD SHX Text
2
AutoCAD SHX Text
E-14
AutoCAD SHX Text
E. FLEISCHER
AutoCAD SHX Text
L. MILLER
AutoCAD SHX Text
M. THOMPSON
AutoCAD SHX Text
M. THOMPSON
AutoCAD SHX Text
2
AutoCAD SHX Text
10/16
AutoCAD SHX Text
LLM
AutoCAD SHX Text
ETF
AutoCAD SHX Text
CHANGES TO INSTRUMENTATION CONDUIT SCHEDULE
AutoCAD SHX Text
M. THOMPSON
AutoCAD SHX Text
2

E-18

ELECTRICAL DETAILS 1

6000 Uptown Blvd N.E., Suite 200

Albuquerque, NM 87110

Tel: (505) 243-3200

©

CAMINO REAL REGIONAL UTILITY AUTHORITY

DOÑA ANA COUNTY, NEW MEXICO

WELL 19 REPLACEMENT AND

WELL 8A CONTROL BUILDING

www.bhinc.com

800.877.5332

DETAIL

DETAIL 1

DETAIL 2

DETAIL

DETAIL 3

DETAIL 4

DETAIL 9

DETAIL

DETAIL

DETAIL 11

5

6

8

DETAIL 10

7

AutoCAD SHX Text
1/4" BI-METAL BRASS/ALUMINUM BONDING PLATE
AutoCAD SHX Text
BOLT
AutoCAD SHX Text
COMPRESSION RING LUG
AutoCAD SHX Text
GROUND CONDUCTOR
AutoCAD SHX Text
BUSHING
AutoCAD SHX Text
CONDUIT
AutoCAD SHX Text
PIPE FLANGE WITH UNCOATED FACE ON BOND PLATE
AutoCAD SHX Text
CONDUIT
AutoCAD SHX Text
REFERENCE STRUCTURAL DRAWINGS FOR CONNECTION TO BUILDING (TYP.)
AutoCAD SHX Text
MSS TYPE 1 PIPE HANGER AT 12'-0" SPACING (TYP.)
AutoCAD SHX Text
JAM NUT AND PLATE PLATE FITTING, TYP.
AutoCAD SHX Text
CHANNEL UNISTRUT P1000 OR EQUAL
AutoCAD SHX Text
PIPE SLEEVE OVER BOLT
AutoCAD SHX Text
CONDUIT
AutoCAD SHX Text
TYPE 316SS CONCRETE INSERT
AutoCAD SHX Text
CHANNEL UNISTRUT P1000 OR EQUAL, LENGTH AS REQ'D
AutoCAD SHX Text
CONDUIT
AutoCAD SHX Text
CONDUIT CLAMP, NUMBER AND SIZE AS REQ'D
AutoCAD SHX Text
4/O
AutoCAD SHX Text
3/4" x 10' COPPER WELD GROUND ROD
AutoCAD SHX Text
3/4" x 10' COPPER WELD GROUND ROD
AutoCAD SHX Text
4/O
AutoCAD SHX Text
FINISH GRADE
AutoCAD SHX Text
END VIEW
AutoCAD SHX Text
SIDE VIEW
AutoCAD SHX Text
INDIVIDUAL CONDUIT SUPPORT
AutoCAD SHX Text
END VIEW
AutoCAD SHX Text
MULTIPLE TRAPEZE CONDUIT SUPPORT
AutoCAD SHX Text
"A"
AutoCAD SHX Text
"A"
AutoCAD SHX Text
SECTION "A" - "A"
AutoCAD SHX Text
NOTE: LEAVE REBARS INTACT WHEN BREAKING OUT EXISTING WALLS.
AutoCAD SHX Text
FORM OPENING SQUARE FOR NEW WORK. SAW CUT EXISTING STRUCTURES 2" INTO SURFACE BOTH SIDES AND BREAK OUT OPENING.
AutoCAD SHX Text
CONDUIT
AutoCAD SHX Text
FILL OPENING WITH FIRE RETARDANT SEALING COMPOUND, INDOORS OR NON-SHRINK CEMENTITOUS GROUT OUTDOORS.
AutoCAD SHX Text
STAINLESS STEEL WALL COLLAR
AutoCAD SHX Text
GROUT SLEEVE IN A NEAT AND WORKMANSHIP LIKE MANNER WITH SMOOTH SURFACES.
AutoCAD SHX Text
OPENING IN BRICK OR CMU SHALL HAVE EDGES AS SMOOTH AND STRAIGHT AS POSSIBLE
AutoCAD SHX Text
WATERTIGHT SEAL AS SPECIFIED
AutoCAD SHX Text
H.D. GALVANIZED STEEL SLEEVE W/ WATER STOP. SLEEVE DIAMETER AS REQUIRED BY SEAL MANUF.
AutoCAD SHX Text
CONDUIT
AutoCAD SHX Text
EXTERIOR
AutoCAD SHX Text
INTERIOR
AutoCAD SHX Text
TYPE 316SS ADHESIVE CAPSULE ANCHOR
AutoCAD SHX Text
CONCRETE
AutoCAD SHX Text
MCC
AutoCAD SHX Text
INSULATED BUSHING W/ GROUND LUG (TYP.)
AutoCAD SHX Text
4" CONCRETE PAD W/ 3/4" CHAMFER ALL AROUND
AutoCAD SHX Text
1/2" ANCHOR BOLTS AT 24" O.C. W/ LEVELING NUTS (TYP.)
AutoCAD SHX Text
BOND ALL CONDUITS TO EQUIPMENT BUS WITH BONDING JUMPER
AutoCAD SHX Text
REMOVE NUT. CUT BOLT FLUSH AND PLUG WELD TO STEEL PRIOR TO SETTING EQUIPMENT (TYP.)
AutoCAD SHX Text
FULL LENGTH 4" GALVANIZED STEEL CHANNELS LAID LEVEL ALONG ENTIRE LENGTH AND WITH EACH OTHER. DRILL AND TAP FOR EQUIPMENT ANCHORS.
AutoCAD SHX Text
EQUIPMENT CHANNEL
AutoCAD SHX Text
PVC COATED CONDUIT AND COUPLING
AutoCAD SHX Text
PVC COATED GALVANIZED RIGID STEEL SWEEP ELBOW
AutoCAD SHX Text
CONCRETE DUCTBANK AS INDICATED ON PLANS
AutoCAD SHX Text
PRECAST CONCRETE TRAFFIC RATED GROUND WELL WITH CAST IRON HINGED LID MARKED "GROUND".
AutoCAD SHX Text
FINISH GRADE
AutoCAD SHX Text
CONTINUOUS BARE COPPER GROUND CABLE, SIZE AS INDICATED ON PLANS.
AutoCAD SHX Text
GRAVEL FILL
AutoCAD SHX Text
1'-0"
AutoCAD SHX Text
6"
AutoCAD SHX Text
1'-0"
AutoCAD SHX Text
6"x6" CONCRETE COLLAR
AutoCAD SHX Text
GROUND ROD
AutoCAD SHX Text
EXOTHERMIC WELD BOND
AutoCAD SHX Text
P-1000 STAINLESS STEEL UNISTRUT HORIZONTAL MEMBERS
AutoCAD SHX Text
P-1001 STAINLESS STEEL DUAL BACK-TO-BACK UNISTRUT
AutoCAD SHX Text
INSTALL NEMA 4X 316SST JUNCTION BOX
AutoCAD SHX Text
INSTALL LOWER P-1000 SST UNISTRUT FOR CONDUIT ANCHORING
AutoCAD SHX Text
FLOOR MOUNTING PLATES AND CHEMICAL SET SST ANCHOR, 3" EMBEDMENT MIN.
AutoCAD SHX Text
1" GROUT PACK
AutoCAD SHX Text
CONDUITS AS SHOWN ON DRAWING
AutoCAD SHX Text
P5501 GALVANIZED DUAL UNISTRUT POST FRAME WITH FRAME SUPPORTS
AutoCAD SHX Text
3'-0" 12" CONCRETE
AutoCAD SHX Text
TO COUNTERPOISE
AutoCAD SHX Text
GROUND CONDUCTOR IN CONDUIT, BONDED TO DISCONNECT, FRAME, AND GROUND ROD, TYP.
AutoCAD SHX Text
INSTALL EPEC APPROVED METER SOCKET
AutoCAD SHX Text
INSTALL EPEC APPROVED 600 AMP CT CABINET
AutoCAD SHX Text
INSTALL 600 AMP FUSED SAFETY DISCONNECT SWITCH
AutoCAD SHX Text
TO COUNTERPOISE
AutoCAD SHX Text
ALL VERTICAL SUPPORTS 3" PAINTED STEEL SQUARE TUBING SET IN CONCRETE TYPICAL OF 3
AutoCAD SHX Text
GROUND CONDUCTOR IN CONDUIT, BONDED TO DISCONNECT, FRAME, AND GROUND ROD
AutoCAD SHX Text
3'-0" 18" CONCRETE
AutoCAD SHX Text
HA
AutoCAD SHX Text
INSTALL 400 AMP SERVICE ENTRANCE PANELBOARD
AutoCAD SHX Text
SSSS ENCLOSURE
AutoCAD SHX Text
ALL HORIZONTAL SUPPORTS 1-5/8" GALV. FRAMING CHANNEL BOLTED TO VERTICAL CUPPORTS, ZINC SPRAY ALL CUTS
AutoCAD SHX Text
4" SERVICE CONDUITS TO UTILITY POINT OF SERVICE
AutoCAD SHX Text
4" CONDUITS TO MCC
AutoCAD SHX Text
E-18
AutoCAD SHX Text
E. FLEISCHER
AutoCAD SHX Text
L. MILLER
AutoCAD SHX Text
E. FLEISCHER
AutoCAD SHX Text
M. THOMPSON
AutoCAD SHX Text
2
AutoCAD SHX Text
10/16
AutoCAD SHX Text
LLM
AutoCAD SHX Text
ETF
AutoCAD SHX Text
CHANGES TO ELECTRCIAL SERVICE RACK
AutoCAD SHX Text
M. THOMPSON
AutoCAD SHX Text
A
AutoCAD SHX Text
B
AutoCAD SHX Text
C
AutoCAD SHX Text
D
AutoCAD SHX Text
E
AutoCAD SHX Text
F
AutoCAD SHX Text
G
AutoCAD SHX Text
H
AutoCAD SHX Text
1
AutoCAD SHX Text
2
AutoCAD SHX Text
3
AutoCAD SHX Text
4
AutoCAD SHX Text
REV.
AutoCAD SHX Text
NO.
AutoCAD SHX Text
DATE
AutoCAD SHX Text
DRWN
AutoCAD SHX Text
CHKD
AutoCAD SHX Text
REMARKS
AutoCAD SHX Text
DESIGNED BY:
AutoCAD SHX Text
DRAWN BY:
AutoCAD SHX Text
CROSS CHK'D BY:
AutoCAD SHX Text
APPROVED BY:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
SHEET CHK'D BY:
AutoCAD SHX Text
SHEET NO.
AutoCAD SHX Text
PROJECT NO.
AutoCAD SHX Text
FILE NAME:
AutoCAD SHX Text
OCTOBER 2016
AutoCAD SHX Text
CDM SMITH ALL RIGHTS RESERVED.      REUSE OF DOCUMENTS:  THESE DOCUMENTS AND DESIGNS PROVIDED BY PROFESSIONAL SERVICE, INCORPORATED HEREIN, ARE THE PROPERTY OF CDM SMITH AND ARE NOT TO BE USED, IN WHOLE OR PART, FOR ANY OTHER PROJECT WITHOUT THE WRITTEN AUTHORIZATION OF CDM SMITH. 
AutoCAD SHX Text
NEW MEXICO EXTENDED PAYMENT PROVISION: THIS CONTRACT ALLOWS FOR OWNER TO MAKE PAYMENT WITHIN 45 DAYS AFTER SUBMISSION OF AN UNDISPUTED REQUEST FOR PAYMENT.
AutoCAD SHX Text
36207-106147
AutoCAD SHX Text
CEILING MOUNTED CONDUIT RACK
AutoCAD SHX Text
NTS
AutoCAD SHX Text
-
AutoCAD SHX Text
WALL MOUNTED CONDUIT RACK
AutoCAD SHX Text
NTS
AutoCAD SHX Text
-
AutoCAD SHX Text
BLOCK OR CONCRETE WALL
AutoCAD SHX Text
-
AutoCAD SHX Text
CONCEALED CONDUIT INSTALLATION
AutoCAD SHX Text
EXTERIOR BLOCK OR BRICK WALL
AutoCAD SHX Text
-
AutoCAD SHX Text
BUILDING CONDUIT ENTRANCE TO EQUIPMENT PAD
AutoCAD SHX Text
NTS
AutoCAD SHX Text
E-04
AutoCAD SHX Text
ELECTRICAL EQUIPMENT MOUNTING WELL 19
AutoCAD SHX Text
NTS
AutoCAD SHX Text
E-04
AutoCAD SHX Text
GROUND BUS CONNECTION TO GROUND ROD
AutoCAD SHX Text
NTS
AutoCAD SHX Text
E-04, E-12
AutoCAD SHX Text
PIPE GROUNDING
AutoCAD SHX Text
NTS
AutoCAD SHX Text
E-04, E-11
AutoCAD SHX Text
JUNCTION BOX MOUNTING
AutoCAD SHX Text
NTS
AutoCAD SHX Text
E-04, E-11
AutoCAD SHX Text
ELECTRICAL EQUIPMENT MOUNTING WELL 8A
AutoCAD SHX Text
NTS
AutoCAD SHX Text
E-11
AutoCAD SHX Text
COUNTERPOISE GROUND TEST WELL
AutoCAD SHX Text
NTS
AutoCAD SHX Text
E-04, E-11
AutoCAD SHX Text
2

Planholder Address City State Zip Phone #

1 John Fermiza-ConstructConnect 30 Technology Pwy S Norcross GA 30092 323-602-5079

2 RMCI Construction 6211 Chappell NW Albuquerque NM 87107 505-345-0008

3 Highland Enterprises P.O. Box 2409 Las Cruces NM 88004 545-524-3551

4 LWV GLC (Dale Yeo Voter Services) P.O. Box 8322 Las Cruces NM 88006 575-405-7530

5 Stewart Brothers Drilling Company 306 Airport Rd. Milan NM 87021 505-287-2986

6 Contract Opportunities Center

7 Golder Associates Inc. 5200 Pasadena Ave # C Albuquerque NM 87113

8 VENCOR Engineering, LLC 665 E University Ave Suite C Las Cruces NM 88011

9 Jobe Materials 1150 Southview Dr El Paso TX 79928 915-298-9900

10 Smithco Construction 1010 King Canyon Loop Caballo NM 87931 575-740-0473

11 crdotcom

12 Morrow Enterprises P.O. Box 1747 Las Cruces NM 88004 575-526-1178

13 Onvia

14 Deltek

15 IMS

16 Builders News 3435 Princeton NE Albuquerque NM 87102 505-243-9793

17 Contractors Register Inc.

18 Blue Book Network

20 CSW Contractors, Inc.

21 Layne Christensen Company 17800 E. 22nd Ave. Aurora CO 80011 303-755-1281

22 Caliper Construction 2000 S Valley Dr Las Cruces NM 88005

Planholders List

Well 19 Replacement and Well 8A Control Building

Bid No. 17-0014

23 Dodge Data & Analytics 3315 Central Ave. Hot Springs AR 71913 501-321-2956

24 Huitt-Zollars, Inc. 6501 Americas Pkwy NE Suite 550 Albuquerque NM 87110

25 Maddox Plumbing 409 N Archuleta Rd Las Cruces NM 88005

26 Online Data Services

27 El Paso A.R.C. Electric, Inc. 8010 North Loop Dr. Suite 200 El Paso TX 79915

28 Construction Bid Source

29 Smith & Aguirre Const. Co, Inc. 2475 Lakeside Dr Las Cruces NM 88007 575-527-2500

30 File Construction 119 Industrial Ave NE Albuquerque NM 87109 505-554-1780

31 Construction Reporter 1609 2nd St. NW Albuquerque NM 87102 505-243-9793

32 The PlanIt Room 1155 Westmorland Suite 109 El Paso TX 79925 915-781-2900

33 Yellow Jacket Drilling Services 1515 Wynkoop Street, Suite 360 Denver CO 80202 303-921-0616

34 Jensen Drilling Company

33 White Cloud Pipeline Corp P.O. Box 2184 Roswell NM 88202 575-622-5995

33 R.M. Wright Const 285 Rio West El Paso TX 79932 915-584-1691

34 Maez Water Sources and Drilling

35 Visual

36 Bohanan Huston

37 Envirobidnet

38 Southeast Electric

39 L-E Electric, Inc.

40 Russells Sand and Gravel

41 PureOps