“the manufacture of 600 volt underground secondary cables,” · 2016. 11. 13. · microsoft...

31
“The Manufacture of 600 Volt Underground Secondary Cables,” Nick Ware Technical Director Presented at the Insulated Conductors Committee April 20, 2005 Educational Session

Upload: others

Post on 19-Apr-2021

1 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: “The Manufacture of 600 Volt Underground Secondary Cables,” · 2016. 11. 13. · Microsoft PowerPoint - 1 Ware ICC4-20-05Mfg of 600V Cables.ppt Author: kwbrown Created Date: 4/29/2005

“The Manufacture of 600 Volt Underground Secondary

Cables,”Nick Ware

Technical Director

Presented at the Insulated Conductors CommitteeApril 20, 2005

Educational Session

Page 2: “The Manufacture of 600 Volt Underground Secondary Cables,” · 2016. 11. 13. · Microsoft PowerPoint - 1 Ware ICC4-20-05Mfg of 600V Cables.ppt Author: kwbrown Created Date: 4/29/2005

Power Delivery System

POWERGENERATIONSTATION

POWER TRANSMISSION LINES

SUBSTATION

600 Volt Underground Residential Distribution Cable

Page 3: “The Manufacture of 600 Volt Underground Secondary Cables,” · 2016. 11. 13. · Microsoft PowerPoint - 1 Ware ICC4-20-05Mfg of 600V Cables.ppt Author: kwbrown Created Date: 4/29/2005

The Product

600V, 75ºC or 90ºC Cable, Suitable for Direct Burial

Page 4: “The Manufacture of 600 Volt Underground Secondary Cables,” · 2016. 11. 13. · Microsoft PowerPoint - 1 Ware ICC4-20-05Mfg of 600V Cables.ppt Author: kwbrown Created Date: 4/29/2005

Outline

• Processes – the basics!• Design – as it affects processes• Future Cables

Page 5: “The Manufacture of 600 Volt Underground Secondary Cables,” · 2016. 11. 13. · Microsoft PowerPoint - 1 Ware ICC4-20-05Mfg of 600V Cables.ppt Author: kwbrown Created Date: 4/29/2005

Conductors and Insulators“The metals are very good conductors of electricity, silver and copper being the best; and being nearly equally as good, copper is, of course, preferred for economy, and it is this property of copper which has so increased the demand for the metal during the last half-century.”

“Glass, india-rubber, cotton, and silk, are all such poor conductors that they have been termed non-conductors or insulators. Between the metals and these come some materials which are neither good conductors nor good insulators; and it must be borne in mind that these terms are merely comparative, for a substance might be a conductor for one purpose and an insulator for another.”

The Romance of Modern Electricity, Charles R. Gibson, London, 1906.

Page 6: “The Manufacture of 600 Volt Underground Secondary Cables,” · 2016. 11. 13. · Microsoft PowerPoint - 1 Ware ICC4-20-05Mfg of 600V Cables.ppt Author: kwbrown Created Date: 4/29/2005

Let’s Not Start at the Beginning

• Fast forward from 1906 to today– Conductors are predominately aluminum 1350 (EC) with a

small market for 8000 series aluminum alloy or copper– Insulation is typically low density thermoplastic

polyethylene (PE) or crosslinked polyethylene (XLP) of low, medium or high density, or a combination thereof

– For the most part, 600V UG products are considered a commodity item

• drives process changes and improvements!

Page 7: “The Manufacture of 600 Volt Underground Secondary Cables,” · 2016. 11. 13. · Microsoft PowerPoint - 1 Ware ICC4-20-05Mfg of 600V Cables.ppt Author: kwbrown Created Date: 4/29/2005

First We Need a Wire!

• Aluminum rod 3/8” diameter is “drawn” (pulled through progressively smaller dies) to size

• Size depends on what end product is desired

Now we need to strand the wire into a conductor…

Page 8: “The Manufacture of 600 Volt Underground Secondary Cables,” · 2016. 11. 13. · Microsoft PowerPoint - 1 Ware ICC4-20-05Mfg of 600V Cables.ppt Author: kwbrown Created Date: 4/29/2005

The Conductor

• Concentric round, produced on a strander, either rigid head or tubular

• May be reversed layers• “Lumpy” outer surface

– increases covering usage

Page 9: “The Manufacture of 600 Volt Underground Secondary Cables,” · 2016. 11. 13. · Microsoft PowerPoint - 1 Ware ICC4-20-05Mfg of 600V Cables.ppt Author: kwbrown Created Date: 4/29/2005

The Conductor• 3% Compression

– Provides a smooth outer surface– Reduces covering usage– Same equipment – die compressed

• Not compacted…compressed!

Page 10: “The Manufacture of 600 Volt Underground Secondary Cables,” · 2016. 11. 13. · Microsoft PowerPoint - 1 Ware ICC4-20-05Mfg of 600V Cables.ppt Author: kwbrown Created Date: 4/29/2005

The Conductor

Rigid head strander

Tubular strander

Page 11: “The Manufacture of 600 Volt Underground Secondary Cables,” · 2016. 11. 13. · Microsoft PowerPoint - 1 Ware ICC4-20-05Mfg of 600V Cables.ppt Author: kwbrown Created Date: 4/29/2005

The Conductor• Compacted – very popular in building wires

– 8-9% reduction in diameter– Same equipment, smaller dies– Further reduces covering usage

Page 12: “The Manufacture of 600 Volt Underground Secondary Cables,” · 2016. 11. 13. · Microsoft PowerPoint - 1 Ware ICC4-20-05Mfg of 600V Cables.ppt Author: kwbrown Created Date: 4/29/2005

The Conductor

• 19W and 37W Bunchers– Can twist all layers simultaneously– Can shape wires while twisting

Page 13: “The Manufacture of 600 Volt Underground Secondary Cables,” · 2016. 11. 13. · Microsoft PowerPoint - 1 Ware ICC4-20-05Mfg of 600V Cables.ppt Author: kwbrown Created Date: 4/29/2005

The Conductor

• Unidirectional concentric stranding• Produced on a buncher• What’s wrong with this picture?

Page 14: “The Manufacture of 600 Volt Underground Secondary Cables,” · 2016. 11. 13. · Microsoft PowerPoint - 1 Ware ICC4-20-05Mfg of 600V Cables.ppt Author: kwbrown Created Date: 4/29/2005

The Conductor

• Must do something to change the hex shape– Combination Unilay– Compressed Unilay

Page 15: “The Manufacture of 600 Volt Underground Secondary Cables,” · 2016. 11. 13. · Microsoft PowerPoint - 1 Ware ICC4-20-05Mfg of 600V Cables.ppt Author: kwbrown Created Date: 4/29/2005

The Conductor• SIW Compressed

– Uses similar input wires to make multiple conductor sizes

#2 AWG (1+6)

1- 0.101”

6- 0.101”

#1 AWG (2+7)

2- 0.101”

7- 0.101”

1/0 AWG (2+7)

2- 0.115”

7- 0.115”

2/0AWG (3+8)

3- 0.115”

8- 0.115”

3/0 AWG (1+5+11)

1- 0.115”

5- 0.115”

11- 0.101”

4/0 AWG (1+6+11)

1- 0.115”

6- 0.115”

11- 0.115”

250 MCM (4+9+13)

4- 0.106”

9- 0.106”

13- 0.106”

350 MCM

(3+7+11+16)

3- 0.106”, 7- 0.106”

11- 0.106”, 16- 0.106”

Page 16: “The Manufacture of 600 Volt Underground Secondary Cables,” · 2016. 11. 13. · Microsoft PowerPoint - 1 Ware ICC4-20-05Mfg of 600V Cables.ppt Author: kwbrown Created Date: 4/29/2005

The Extrusion Process

• The basics– Drop pelletized plastic into a heated barrel and

screw– Rotate screw to feed and blend materials– Push plastic through a “crosshead” to apply to

wire• The details…

Page 17: “The Manufacture of 600 Volt Underground Secondary Cables,” · 2016. 11. 13. · Microsoft PowerPoint - 1 Ware ICC4-20-05Mfg of 600V Cables.ppt Author: kwbrown Created Date: 4/29/2005

The Extrusion Process

Thermoplastic line – apply plastic, cool it off

Polyethylene Insulation 75ºC

Page 18: “The Manufacture of 600 Volt Underground Secondary Cables,” · 2016. 11. 13. · Microsoft PowerPoint - 1 Ware ICC4-20-05Mfg of 600V Cables.ppt Author: kwbrown Created Date: 4/29/2005

The Extrusion Process

• Plastic lines– Relatively inexpensive line– Easy to run and maintain

Page 19: “The Manufacture of 600 Volt Underground Secondary Cables,” · 2016. 11. 13. · Microsoft PowerPoint - 1 Ware ICC4-20-05Mfg of 600V Cables.ppt Author: kwbrown Created Date: 4/29/2005

The Extrusion ProcessCrosslinked Polyethylene Insulation 90ºC

Thermosetting (CV) line – apply insulation, vulcanize (or cure) with heat and pressure, cool it off

Page 20: “The Manufacture of 600 Volt Underground Secondary Cables,” · 2016. 11. 13. · Microsoft PowerPoint - 1 Ware ICC4-20-05Mfg of 600V Cables.ppt Author: kwbrown Created Date: 4/29/2005

The Extrusion Process

• CV lines– Expensive, complex line– Difficult to maintain

Page 21: “The Manufacture of 600 Volt Underground Secondary Cables,” · 2016. 11. 13. · Microsoft PowerPoint - 1 Ware ICC4-20-05Mfg of 600V Cables.ppt Author: kwbrown Created Date: 4/29/2005

The Extrusion Process

• Crosslinking without heat?– Possible with newer water curable insulations– Allows use of thermoplastic lines, or CV lines

to make XLP cables – Lowers cost of new installations– Curing step transfers to a heated high humidity

room after cable is on the reel

Crosslinkable Cable!

Page 22: “The Manufacture of 600 Volt Underground Secondary Cables,” · 2016. 11. 13. · Microsoft PowerPoint - 1 Ware ICC4-20-05Mfg of 600V Cables.ppt Author: kwbrown Created Date: 4/29/2005

The Extrusion Process

• Crosshead design – pressure set-up– Used on CV or thermoplastic lines– Centering & tolerances are critical– Fills interstices

Compound Flow

DieTip

Page 23: “The Manufacture of 600 Volt Underground Secondary Cables,” · 2016. 11. 13. · Microsoft PowerPoint - 1 Ware ICC4-20-05Mfg of 600V Cables.ppt Author: kwbrown Created Date: 4/29/2005

The Extrusion Process

• Crosshead design – tubing set-up– Most often used on thermoplastic lines– “Tube” dimensions are independent of conductor– Lays over interstices

Compound Flow

Tip moves forward to align

with Die

Wall thickness is independent of conductor

Page 24: “The Manufacture of 600 Volt Underground Secondary Cables,” · 2016. 11. 13. · Microsoft PowerPoint - 1 Ware ICC4-20-05Mfg of 600V Cables.ppt Author: kwbrown Created Date: 4/29/2005

The Extrusion Process

• Crosshead design – tubing set-up– Most often used on thermoplastic lines– “Tube” dimensions are independent of conductor– Lays over interstices

Compound Flow

Tip moves forward to align

with Die

Tube draws down on conductor

Apply vacuum

Page 25: “The Manufacture of 600 Volt Underground Secondary Cables,” · 2016. 11. 13. · Microsoft PowerPoint - 1 Ware ICC4-20-05Mfg of 600V Cables.ppt Author: kwbrown Created Date: 4/29/2005

The Final Steps

• Plexing of singles into 2, 3, or 4 cable assemblies

• Final electrical testing• Shipout

Page 26: “The Manufacture of 600 Volt Underground Secondary Cables,” · 2016. 11. 13. · Microsoft PowerPoint - 1 Ware ICC4-20-05Mfg of 600V Cables.ppt Author: kwbrown Created Date: 4/29/2005

Future Cables

• Biggest problem with 600V UG cable is aluminum corrosion !

• Causes usually related to mechanical damage

• Solutions are here

Page 27: “The Manufacture of 600 Volt Underground Secondary Cables,” · 2016. 11. 13. · Microsoft PowerPoint - 1 Ware ICC4-20-05Mfg of 600V Cables.ppt Author: kwbrown Created Date: 4/29/2005

Future Cables

• Sealant incorporated in discrete channels• Bleeds when cut• Viscoelastic sealant material seals cable and

then stops bleeding

Page 28: “The Manufacture of 600 Volt Underground Secondary Cables,” · 2016. 11. 13. · Microsoft PowerPoint - 1 Ware ICC4-20-05Mfg of 600V Cables.ppt Author: kwbrown Created Date: 4/29/2005

Future CablesLeakage Current Testing

BAD!

GOOD!

Leak

age,

mA

Time

Leak

age,

mA

Time

Salt Water Beaker Testing

Dirt Box Testing

Page 29: “The Manufacture of 600 Volt Underground Secondary Cables,” · 2016. 11. 13. · Microsoft PowerPoint - 1 Ware ICC4-20-05Mfg of 600V Cables.ppt Author: kwbrown Created Date: 4/29/2005

Future Cables

• AC Breakdown– 30kV initial ACBD– 4kV ACBD after 30

minutes– Withstood 1 week

at 1kV – 8kV ACBD after 1

week at 1kV volts

Page 30: “The Manufacture of 600 Volt Underground Secondary Cables,” · 2016. 11. 13. · Microsoft PowerPoint - 1 Ware ICC4-20-05Mfg of 600V Cables.ppt Author: kwbrown Created Date: 4/29/2005

Future Cables

• Similar self-healing cables are commercially available from multiple manufacturers

• Several years of successful experience• Offers alternatives to high failure rates and

repair budgets

Page 31: “The Manufacture of 600 Volt Underground Secondary Cables,” · 2016. 11. 13. · Microsoft PowerPoint - 1 Ware ICC4-20-05Mfg of 600V Cables.ppt Author: kwbrown Created Date: 4/29/2005

Conclusion

• Cable making machines are big!• You can’t see it all in a slide show• If you haven’t been, go visit a

manufacturer!