ap06 - mobile visibility and control key to w/ww predictive maintenance and operator efficacy

54
Copyright © 2015 Rockwell Automation, Inc. All Rights Reserved. Rockwell Automation TechED 2015 @ROKTechED #ROKTechED PUBLIC INFORMATION AP06 - Mobile Visibility and Control Key to W/WW Predictive Maintenance and Operator Efficiency 1

Upload: rockwell-automation

Post on 26-Jul-2015

425 views

Category:

Technology


0 download

TRANSCRIPT

Page 1: AP06 - Mobile Visibility and Control Key to W/WW Predictive Maintenance and Operator Efficacy

Copyright © 2015 Rockwell Automation, Inc. All Rights Reserved. Rockwell Automation TechED 2015 @ROKTechED #ROKTechED

PUBLIC INFORMATION

AP06 - Mobile Visibility and Control Key to W/WW Predictive Maintenance and Operator Efficiency

1

Page 2: AP06 - Mobile Visibility and Control Key to W/WW Predictive Maintenance and Operator Efficacy

D. John Costello 2015

Page 3: AP06 - Mobile Visibility and Control Key to W/WW Predictive Maintenance and Operator Efficacy

D. John Costello

• Over 41 years of Control System Design and Integration Experience

• With CH2M (Hill) for over 22 years

• CH2M Water Market West Regional Technology Leader – Automation Systems

• Rockwell Automation PlantPAx® System Integrator

• Certified Profibus DP & PA Network Engineer

[email protected]

3

Presenter Introduction

Page 4: AP06 - Mobile Visibility and Control Key to W/WW Predictive Maintenance and Operator Efficacy

CH2M Hill

26,000 employees on six continents

Provides water industry planning, engineering, construction, and operations services

Provides Intelligent Water Solutions Services

Facility Automation

Smart Grid

Water Information Management

Integrated Security and Emergency Preparedness

Rockwell Automation® Recognized Control System Integrator

Rockwell Automation Recognized Process System Integrator

Rockwell Automation Recognized Information System Integrator

4

Company Introduction

Page 5: AP06 - Mobile Visibility and Control Key to W/WW Predictive Maintenance and Operator Efficacy

Safety Moment

5

Exit Plan? Fall Restraint?

Picture from www.BrainJet.com

Page 6: AP06 - Mobile Visibility and Control Key to W/WW Predictive Maintenance and Operator Efficacy

Project Overview

Client: Metro Wastewater Reclamation District

Project: Northern Treatment Plant – Brighton, CO

• 28.8 MGD Wastewater Treatment Plant

• Future Expansion to 75 MGD

• 1.0 Mile Long by 0.25 Mile Wide

Design-Build Contractor: CH2M HILL / Garney Construction

Cost: $250 Million

Delivery Method - Fast Track Progressive Design-Build

6

Page 7: AP06 - Mobile Visibility and Control Key to W/WW Predictive Maintenance and Operator Efficacy

Site Overview

7

Page 8: AP06 - Mobile Visibility and Control Key to W/WW Predictive Maintenance and Operator Efficacy

PlantPAx Integrated Architecture

FIELD DEVICE LEVEL • Profibus, DeviceNet, BACNet, DNP3

PROCESS CONTROL LEVEL • CompactLogix™ Hardware Platform

OPERATIONS LEVEL • FactoryTalk® View SE / ME HMI software

• Site Edition (SE): Uses FactoryTalk® Alarms and Events for alarming • Machine Edition (ME): Designed for use on PanelView™

• SUPERVISORY / MAINTENANCE CONTROL LEVEL • FactoryTalk® Historian / FactoryTalk® VantagePoint® Vantage Point Software

• Microsoft Excel reporting from FactoryTalk Historian and FactoryTalk Alarms and Events • FactoryTalk® AssetCentre Software

• Document Control / Disaster Recovery • Process device configuration • Calibration management

8

Page 9: AP06 - Mobile Visibility and Control Key to W/WW Predictive Maintenance and Operator Efficacy

Northern Treatment Plant - Special Features

• Rockwell Automation PlantPAx based

• HMI graphics developed to support ISA Standard 18.2 and a modified grey scale

• State-of-the-art video wall in the plant control room

• Wireless mobility using iPads

• Virtualized control system using high availability redundant SAN

• Virtual environment with zero clients

• Replica process simulation software

• Redundant Network(s)

9

Page 10: AP06 - Mobile Visibility and Control Key to W/WW Predictive Maintenance and Operator Efficacy

Control Room Video Wall

10

Page 11: AP06 - Mobile Visibility and Control Key to W/WW Predictive Maintenance and Operator Efficacy

Video Wall

11

Page 12: AP06 - Mobile Visibility and Control Key to W/WW Predictive Maintenance and Operator Efficacy

PASS Virtualized Servers

Process Network:

DMZ:

• Domain Controller – Primary

• Domain Controller – Secondary

• FactoryTalk Historian (5000 Tags)

• FactoryTalk VantagePoint

• Operator Workstations (Six Total + Video Wall)

Total of 18 Virtual Servers

• FactoryTalk® Directory

• FactoryTalk View SE [Unlimited Graphics] Primary Server

• FactoryTalk View SE [Unlimited Graphics] Secondary Server

• Engineering Server

• Engineering Workstation

• WIN911

• Windows Update Server

Page 13: AP06 - Mobile Visibility and Control Key to W/WW Predictive Maintenance and Operator Efficacy

PASS Overview

13

Page 14: AP06 - Mobile Visibility and Control Key to W/WW Predictive Maintenance and Operator Efficacy

PASS Sizing

14

Controller Verification

Page 15: AP06 - Mobile Visibility and Control Key to W/WW Predictive Maintenance and Operator Efficacy

Control System Overview

Six Redundant Controllers & Four Non-Redundant Controllers

• 41 Hard-wired Analog Inputs

• 13 Hard-wired Analog Outputs

• 390 Hard-wired Digital Inputs

• 129 Hard-wired Digital Outputs

• 561 Profibus DP Devices

• 425 Profibus PA Devices

• 375 DeviceNet Devices

Thirteen Vendor supplied Controllers – Redundant & Non-Redundant Configurations

(ControlLogix® & CompactLogix™ + 1 non-Rockwell Automation solution)

15

Page 16: AP06 - Mobile Visibility and Control Key to W/WW Predictive Maintenance and Operator Efficacy

PASS Architecture

16

Page 17: AP06 - Mobile Visibility and Control Key to W/WW Predictive Maintenance and Operator Efficacy

Network / Processor Redundancy

17

Simplified Diagram

Page 18: AP06 - Mobile Visibility and Control Key to W/WW Predictive Maintenance and Operator Efficacy

Fieldbus Implementation

18

Plant Control System (PCS) I/O Communicate via Fieldbus

Field Instruments Communicate via Profibus DP/PA

• Prosoft DP Module

• DP – Control Valves, Metering Pumps, Flowmeters and Analytical Instruments

• PA – Level, Pressure, Temperature, Weight

MCCs Communicate via DeviceNet

• MCC Bucket Control

• VFD Control

Most Packaged Systems Communicate via EtherNet/IP

Page 19: AP06 - Mobile Visibility and Control Key to W/WW Predictive Maintenance and Operator Efficacy

Rockwell Automation’s AssetCentre Software

19

Provides Automatic Program Version Control.

Provides ability to configure and troubleshoot field instrumentation over HART or

Profibus communications technology.

Provides ability to schedule, manage, track, and report on field instrumentation

calibration activities.

Page 20: AP06 - Mobile Visibility and Control Key to W/WW Predictive Maintenance and Operator Efficacy

AssetCentre

20

File Organization / Archiving

Page 21: AP06 - Mobile Visibility and Control Key to W/WW Predictive Maintenance and Operator Efficacy

AssetCentre Process Device Configuration

21

Via Profibus

Page 22: AP06 - Mobile Visibility and Control Key to W/WW Predictive Maintenance and Operator Efficacy

AssetCentre Process Device Configuration

22

Online Values

Page 23: AP06 - Mobile Visibility and Control Key to W/WW Predictive Maintenance and Operator Efficacy

REPLICA SIMULATION SOFTWARE

23

Page 24: AP06 - Mobile Visibility and Control Key to W/WW Predictive Maintenance and Operator Efficacy

Use of Replica Process Simulation Software

24

Influent Pump Station and the Tertiary Pump Station

modeled using Replica

Replica software blocks replicated in RSLogix™ 5000

(LogixDesigner) software.

Pump block resides in an Add-On-Instruction (AOI)

Incorporates pump curves to find most efficient

operating point.

Page 25: AP06 - Mobile Visibility and Control Key to W/WW Predictive Maintenance and Operator Efficacy

Modified Gray Scale Technology

25

Page 26: AP06 - Mobile Visibility and Control Key to W/WW Predictive Maintenance and Operator Efficacy

Gray Scale Technology

26

Page 27: AP06 - Mobile Visibility and Control Key to W/WW Predictive Maintenance and Operator Efficacy

Gray Scale Technology

27

Situational Awareness

Page 28: AP06 - Mobile Visibility and Control Key to W/WW Predictive Maintenance and Operator Efficacy

Gray Scale Technology

28

Situational Awareness

Page 29: AP06 - Mobile Visibility and Control Key to W/WW Predictive Maintenance and Operator Efficacy

Liquids Flow Model

29

Page 30: AP06 - Mobile Visibility and Control Key to W/WW Predictive Maintenance and Operator Efficacy

Solids Flow Model

30

Page 31: AP06 - Mobile Visibility and Control Key to W/WW Predictive Maintenance and Operator Efficacy

ISA Standard 18.2 - Workflow

31

Construction Phase

Operations Phase

Programming Phase

Page 32: AP06 - Mobile Visibility and Control Key to W/WW Predictive Maintenance and Operator Efficacy

ISA Standard 18.2 - Philosophy

32

Alarm definition

Roles and requirements

Rationalization requirements

Alarm class definitions, design, requirements

Alarm priorities, definitions, etc.

Alarm shelving / suppression rules

Alarm system monitoring requirements

Management of change

Training

Requires a committee of stakeholders

• Senior Management • Operators • Maintenance • SCADA Design Team

Draft, review, edit, repeat as necessary

Once approved, review the alarm philosophy periodically for any necessary changes

• Document should contain the minimum review period.

Page 33: AP06 - Mobile Visibility and Control Key to W/WW Predictive Maintenance and Operator Efficacy

ISA 18.2 – Quick Drill Down

33

Drilling Down to Problems

Page 34: AP06 - Mobile Visibility and Control Key to W/WW Predictive Maintenance and Operator Efficacy

ISA 18.2 Alarm Features

34

Ability to Shelve Alarms

Page 35: AP06 - Mobile Visibility and Control Key to W/WW Predictive Maintenance and Operator Efficacy

ISA 18.2 Alarm Features

35

Breadcrumbs – Alarm Priorities

Page 36: AP06 - Mobile Visibility and Control Key to W/WW Predictive Maintenance and Operator Efficacy

ISA 18.2 Alarm Features

36

Page 37: AP06 - Mobile Visibility and Control Key to W/WW Predictive Maintenance and Operator Efficacy

ISA 18.2 Alarm Management

37

Single Alarm – Multiple Causes

Page 38: AP06 - Mobile Visibility and Control Key to W/WW Predictive Maintenance and Operator Efficacy

ISA 18.2 - Monitoring

38

Alarms per Day: ~150/Day Target ~300/Day Maximum

Alarms per Hour: ~6 Average ~12 Maximum

Alarms per 10 Min: ~1 Average ~2 Average

Hours containing >30 Alarms: ~<1%

Priority Distribution:

•P1 (Urgent) ~5%

• P2 (High) ~15%

• P3 (Medium) ~80%

• P4 (Low / Maintenance Required) Event

Page 39: AP06 - Mobile Visibility and Control Key to W/WW Predictive Maintenance and Operator Efficacy

ISA 18.2 Monitoring

FactoryTalk VantagePoint reporting installed to provide Alarming Key Performance Indicator Monitoring

39

Page 40: AP06 - Mobile Visibility and Control Key to W/WW Predictive Maintenance and Operator Efficacy

ISA 18.2 Alarming KPI Reports

40

Alarms Grouped by Class

Page 41: AP06 - Mobile Visibility and Control Key to W/WW Predictive Maintenance and Operator Efficacy

ISA 18.2 Alarming KPI Reports

41

Top Alarms – Time to Acknowledge

Page 42: AP06 - Mobile Visibility and Control Key to W/WW Predictive Maintenance and Operator Efficacy

ISA 18.2 Alarming KPIs

42

Alarms – Hourly Alarm Counts

24 Alarms/Hour

Page 43: AP06 - Mobile Visibility and Control Key to W/WW Predictive Maintenance and Operator Efficacy

ISA 18.2 Alarming KPI Reports

43

Drill Down into 24 Alarms/Hour

Page 44: AP06 - Mobile Visibility and Control Key to W/WW Predictive Maintenance and Operator Efficacy

Tools to Help Improve Integration Effort

44

“Smart” P&IDs

Page 45: AP06 - Mobile Visibility and Control Key to W/WW Predictive Maintenance and Operator Efficacy

Tools to Help Improve Integration Effort

45

P&IDs Linked to Database

Page 46: AP06 - Mobile Visibility and Control Key to W/WW Predictive Maintenance and Operator Efficacy

Tools to Help Improve Integration Effort

46

Database creates CSV Tag file for RSLogix5000

Page 47: AP06 - Mobile Visibility and Control Key to W/WW Predictive Maintenance and Operator Efficacy

Tools to Help Improve Integration Effort

47

Same information used for HMI

Page 48: AP06 - Mobile Visibility and Control Key to W/WW Predictive Maintenance and Operator Efficacy

Tools to Help Improve Integration Effort

48

PlantPAx_OnlineConfigTool_xxx.XLS

Page 49: AP06 - Mobile Visibility and Control Key to W/WW Predictive Maintenance and Operator Efficacy

Tools to Help Improve Integration Effort

49

PAX_AlarmsBuilder_Vxxxx

Page 50: AP06 - Mobile Visibility and Control Key to W/WW Predictive Maintenance and Operator Efficacy

Tools to Help Improve Integration Effort

50

PAX_AlarmsBuilder_Vxxxx

Page 51: AP06 - Mobile Visibility and Control Key to W/WW Predictive Maintenance and Operator Efficacy

Tools to Help Improve Integration Effort

51

PAX_AlarmsBuilder_Vxxxx

Page 52: AP06 - Mobile Visibility and Control Key to W/WW Predictive Maintenance and Operator Efficacy

Tools to Help Improve Integration Effort

52

PAX_AlarmsBuilder_Vxxxx

Page 53: AP06 - Mobile Visibility and Control Key to W/WW Predictive Maintenance and Operator Efficacy

Summary

Modeled the Process Using Replica

Used Fieldbus Technology

Used existing AOI (P_Alarm), knowing it would be upgraded at a later time to support S18.2

Alarm Management.

• This allowed development to start before the desired functionality was actually available without impacting

the project schedule.

Linked Directly to the AOIs

• Eliminated the HMI Tag Database

– Reduced Development Time.

– Reduces Processor Memory Usage roughly 50% over using UDTs

Implemented Rockwell Devices

• Rockwell Automation PowerMonitor™

– Imported the Add-On Profile and Configured the Device – Reduced Development Time.

Implemented FactoryTalk AssetCentre PDC

• Configure and Verify Instrument Operation – Reduce Start-Up Time

53

Page 54: AP06 - Mobile Visibility and Control Key to W/WW Predictive Maintenance and Operator Efficacy

www.rockwellautomationteched.com

Copyright © 2015 Rockwell Automation, Inc. All Rights Reserved.

PUBLIC INFORMATION

Rockwell Automation TechED 2015 @ROKTechED #ROKTechED

Thank you!